Alarm and shutdown values indicate deviation from designed operation and are not meant
for continuous engine service. Engine and control systems must be designed to and
operated at normal values. Disregard may result in engine damage.
Alarm and shutdown values are based on using dry natural gas of 900 BTU/cu.ft. (35.38 MJ/m3 [25,V(0;101.325)]) Saturated
Lower Heating Value (SLHV) as fuel. Refer to the “Gaseous Fuel Specification for GE Waukesha Engines” standard sheet, S-
07884-7 or latest version, and the “Lubricating Oil Recommendations for GE Waukesha Engines” standard sheet, S-01015-30 or
latest version, for typical changes to operating temperatures for jacket water and lube oil when running on landfill or digester gas
fuels.
Refer to the most recent version of the GE Waukesha’s Gas Engine Price Book to determine which shutdown devices are included
as standard equipment with any specific engine model.
For information on recommended alarms and shutdowns for other engine models, refer to the most recent version of the
RECOMMENDED ALARM AND SHUTDOWN SETPOINTS standard sheet, S-08382-2 or latest version.
Page 1 of 3
OVERSPEED:
Shutdown: Not to exceed 10% over governed speed.
Power Generation Systems:
Shutdown: 15-18% over governed speed, not to exceed 1380 RPM.
Caution: When setting engine overspeed shutdown, do not exceed the lesser of engine or driven equipment’s
speed limits. To avoid equipment damage, consult the driven equipment manufacturer for maximum
overspeed value.
FUEL PRESSURE:
Alarm: The minimum fuel pressure at the regulator (from Tech Data).
Shutdown: 85% of the alarm value.
CRANKCASE PRESSURE
Alarm: 0.22 psi (1.5 kPa)
Shutdown: 0.29 psi (2 kPa)
POST-CATALYST PRESSURE
Alarm: 0.80 psi (5.5 kPa)
Shutdown: 0.94 psi (6.5 kPa)
PRE-CATALYST PRESSURE
Alarm: 0.80 psi (5.5 kPa)
Shutdown: 0.94 psi (6.5 kPa)
Page 2 of 3
POST-CATALYST TEMPERATURE
Alarm: 1250°F (677°C)
Shutdown: 1301°F (705°C)
PRE-CATALYST TEMPERATURE
Alarm: 1250°F (677°C)
Shutdown: 1301°F (705°C)
SYSTEM VOLTAGE
High: 32 V
Low: 21 V
OVERLOAD
Alarm: 5%
Shutdown: 8%
*Indicates a trademark.