Waukesha gas engines Control Systems

VHP* SERIES FIVE


RECOMMENDED ALARM AND SHUTDOWN SETPOINTS
The following is a list of recommended “alarm” and “shutdown” setpoints for VHP Series 5 engines for various engine operating
parameters. These values can be used as a guide when designing protection or monitoring systems.
The “alarm” values shown are maximum values – they can be adjusted lower to suit a specific application or measurement device.
By utilizing controls that simultaneously shut off the fuel supply and ignition system upon reaching a “shutdown” value, the potential
for engine damage is reduced. Refer to ESM2 HMI for calibration and limits from the “PARAMETERS” > “ADV“> “Advanced
Settings” and “VISUALIZATION” > “ADV” > “Setpoints” screens respectively.

Alarm and shutdown values indicate deviation from designed operation and are not meant
for continuous engine service. Engine and control systems must be designed to and
operated at normal values. Disregard may result in engine damage.
Alarm and shutdown values are based on using dry natural gas of 900 BTU/cu.ft. (35.38 MJ/m3 [25,V(0;101.325)]) Saturated
Lower Heating Value (SLHV) as fuel. Refer to the “Gaseous Fuel Specification for GE Waukesha Engines” standard sheet, S-
07884-7 or latest version, and the “Lubricating Oil Recommendations for GE Waukesha Engines” standard sheet, S-01015-30 or
latest version, for typical changes to operating temperatures for jacket water and lube oil when running on landfill or digester gas
fuels.
Refer to the most recent version of the GE Waukesha’s Gas Engine Price Book to determine which shutdown devices are included
as standard equipment with any specific engine model.
For information on recommended alarms and shutdowns for other engine models, refer to the most recent version of the
RECOMMENDED ALARM AND SHUTDOWN SETPOINTS standard sheet, S-08382-2 or latest version.

JACKET WATER OUTLET TEMPERATURE:


Normal: 180° F (82° C) for continuous rating.
Alarm: 190° F (88° C)
Shutdown: 200° F (93° C)

LUBE OIL HEADER TEMPERATURE:


Normal: 180° F (82° C)
Alarm: 190° F (88° C)
Shutdown: 200° F (93° C)

LUBE OIL HEADER PRESSURE:


Normal: 50 – 60 psi (345 – 415 kPa)
Alarm: 35 psi (241 kPa)
Shutdown: 30 psi (207 kPa)

LUBE OIL FILTER DIFFERENTIAL PRESSURE:


Normal: 2 – 25 psi (14 – 172 kPa differential)
Alarm: 25 psi (172 kPa differential)

INTAKE MANIFOLD TEMPERATURE:


Alarm: 155° F (68.5° C)
Shutdown: 160° F (71° C)

Page 1 of 3

EN: 162283 Ref.


VHP* Series Five
S
Recommended Alarm And Shutdown Setpoints DATE: 2/19
8382-3
Waukesha gas engines Control Systems

INTAKE MANIFOLD PRESSURE:


Contact GE Waukesha’s Application Engineering.

MAIN BEARING TEMPERATURE:


Shutdown: 250° F (121° C)

OVERSPEED:
Shutdown: Not to exceed 10% over governed speed.
Power Generation Systems:
Shutdown: 15-18% over governed speed, not to exceed 1380 RPM.
Caution: When setting engine overspeed shutdown, do not exceed the lesser of engine or driven equipment’s
speed limits. To avoid equipment damage, consult the driven equipment manufacturer for maximum
overspeed value.

FUEL PRESSURE:
Alarm: The minimum fuel pressure at the regulator (from Tech Data).
Shutdown: 85% of the alarm value.

CATALYST DELTA PRESSURE


Alarm: 0.54 psi (3.75 kPa)
Shutdown: 0.73 psi (5 kPa)

CRANKCASE PRESSURE
Alarm: 0.22 psi (1.5 kPa)
Shutdown: 0.29 psi (2 kPa)

POST-CATALYST PRESSURE
Alarm: 0.80 psi (5.5 kPa)
Shutdown: 0.94 psi (6.5 kPa)

PRE-CATALYST PRESSURE
Alarm: 0.80 psi (5.5 kPa)
Shutdown: 0.94 psi (6.5 kPa)

TURBINE INLET TEMPERATURE


Alarm: 1427°F (775°C)
Shutdown: 1454°F (790°C)

EXHAUST PORT TEMPERATURE


Alarm: 1450°F (788°C)
Shutdown: 1475°F (802°C)

Page 2 of 3

EN: 162283 Ref.


VHP* Series Five
S
Recommended Alarm And Shutdown Setpoints DATE: 2/19
8382-3
Waukesha gas engines Control Systems

POST-CATALYST TEMPERATURE
Alarm: 1250°F (677°C)
Shutdown: 1301°F (705°C)

PRE-CATALYST TEMPERATURE
Alarm: 1250°F (677°C)
Shutdown: 1301°F (705°C)

CYLINDER EXHAUST TEMPERATURE LOW


Alarm: 482°F (250°C)

CYLINDER EXH TEMP DEVIATION


Alarm: 180°F (100°C)

OIL PRESSURE PREMISSIVE START


Shutdown: 1.45 psi Gauge (10 kPa Gauge)

SYSTEM VOLTAGE
High: 32 V
Low: 21 V

OVERLOAD
Alarm: 5%
Shutdown: 8%

*Indicates a trademark.

Page 3 of 3

EN: 162283 Ref.


VHP* Series Five
S
Recommended Alarm And Shutdown Setpoints DATE: 2/19