Professional Documents
Culture Documents
Public Input No. 3-NFPA 24-2015 (New Section After 1.4)
Public Input No. 3-NFPA 24-2015 (New Section After 1.4)
A.1.4
It is the intent of the committee to recognize that future editions of this standard are a further refinement of
this edition and earlier editions. The changes in future editions will reflect the continuing input of the fire
protection community in its attempt to meet the purpose stated in this standard. Compliance with all
requirements of a future edition could be considered as providing an equivalent level of system integrity and
performance of the system.
Many AHJ's will not recognize future editions. This annex note is intended to give guidance that use of an entire
future edition of the standard could be considered an equivalency as allowed in 1.4. This language will be
proposed to other sprinkler standards and has been accepted by NFPA 14 & NFPA 25.
Committee Statement
1 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Referenced current SDO names, addresses, standard names, numbers, and editions.
Committee Statement
5 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Reference is made to the statement of problem and substantiation of Public Input No. 24-NFPA 24-2016 [ Section
No. 10.1.1.1 ].
Committee Statement
Resolution: Steel piping used for underground needs to be listed due to issues surrounding corrosion.
7 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5.1.2.1 Where a waterflow test was conducted, the volume and pressure available for use for a fire
protection system shall be determined from either 5.1.2.1.1 or 5.1.2.1.2.
5.1.2.1.1* Knowledge of the water supply and engineering judgment taking into account reasonable
daily and seasonal fluctuations not extreme conditions.
5.1.2.1.2* Use of the following formula:
P = The pressure available from the water supply to use for a fire protection system that will
be calculated for a given flow (Q)
Q = The flow that will be used to calculate the available pressure from the water supply.
P R = The residual pressure measured during the waterflow test while the flow Q R was
discharging from the water supply.
P S = The static pressure measured during the waterflow test.
Q R = The flow discharging from the water supply when P R was measured.
P L = The expected low static pressure at the location of the test results accounting for
daily and seasonal fluctuations (not extreme conditions) obtained from the water utility.
Where the water authority does not provide P L , see 24.2.2.2.1.3.
5.1.2.1.3 Where the water authority does not provide a value for P L , the value of P L shall be
calculated from the following formula:
P L = P S – 10 psi
There needs to be a reasonable adjustment to water supply data in order to accommodate changes due to daily
and seasonal fluctuations. The fact that this is currently not a requirement allows the design of fire protection
systems that are known by the designer to have an ineffective water supply almost immediately after installation.
This proposal takes care of the traditional arguments against a mandated safety margin by creating a standardized
method of calculating that safety margin; however, this standardized method is only used if there is no information
regarding the water utility. So, those situations where the fluctuations in the water delivery are known at a
particular location, then these take priority.
Spelling out the fact that NFPA 24 is not expecting unusual circumstances like water main breaks and 100 year
droughts should help alleviate liability concerns on the part of the water utility, which should lead to a more open
dialog between the fire protection professional and the water utility representative. The reality is that extreme
conditions like 100 year droughts and water main breaks are better handled by the Impairment Procedures of
NFPA 25.
One of the concerns about this proposal last cycle was that there was no way to account for the situation where
the water utility brings more pumps on line as the flow demand increases. These situations produce a water
8 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
supply curve that looks more like a saw-tooth configuration than a line. That concern has been handled with the
proposed language in the new section 5.1.2.1.1.
Another of the concerns last cycle about this proposal was the fact that the modified line was not parallel to the
original test line, and might cross the test line at a high flow. This concern has been mitigated by making the line
parallel to the test line, which is more representative of what will happen in the real world anyway.
Committee Statement
This proposal takes care of the traditional arguments against a mandated safety margin by creating a
standardized method of calculating that safety margin; however, this standardized method is only
used if there is no information regarding the water utility. So, those situations where the fluctuations in
the water delivery are known at a particular location, then these take priority.
Spelling out the fact that NFPA 24 is not expecting unusual circumstances like water main breaks and
100 year droughts should help alleviate liability concerns on the part of the water utility, which should
lead to a more open dialog between the fire protection professional and the water utility
representative. The reality is that extreme conditions like 100 year droughts and water main breaks
are better handled by the Impairment Procedures of NFPA 25.
One of the concerns about this proposal last cycle was that there was no way to account for the
situation where the water utility brings more pumps on line as the flow demand increases. These
situations produce a water supply curve that looks more like a saw-tooth configuration than a line.
That concern has been handled with the proposed language in the new section 5.1.2.1.1.
Another of the concerns last cycle about this proposal was the fact that the modified line was not
parallel to the original test line, and might cross the test line at a high flow. This concern has been
mitigated by making the line parallel to the test line, which is more representative of what will happen
in the real world anyway.
9 of 51 11/4/2016 7:43 AM
Water Supply Adjustment Proposals Put Together
Insert new sections as follows:
5.1.2.1 Where a waterflow test was conducted, the volume and pressure available for use for a
fire protection system shall be determined from either 5.1.2.1.1 or 5.1.2.1.2.
5.1.2.1.1* Knowledge of the water supply and engineering judgment taking into account
reasonable daily and seasonal fluctuations not extreme conditions.
1.85
Q
P PR PS PL
QR
P = The pressure available from the water supply to use for a fire protection system that
will be calculated for a given flow (Q)
Q = The flow that will be used to calculate the available pressure from the water supply.
PR = The residual pressure measured during the waterflow test while the flow QR was
discharging from the water supply.
QR = The flow discharging from the water supply when PR was measured.
PL = The expected low static pressure at the location of the test results accounting for
daily and seasonal fluctuations (not extreme conditions) obtained from the water utility.
Where the water authority does not provide PL, see 24.2.2.2.1.3.
5.1.2.1.3 Where the water authority does not provide a value for PL, the value of PL shall be
calculated from the following formula:
PL = PS – 10 psi
A.5.1.2 An adjustment to the waterflow test data to account for the following should be made, as
appropriate:
(1) Daily and seasonal fluctuations
(2) Possible interruption by flood or ice conditions
(3) Large simultaneous industrial use
(4) Future demand on the water supply system
(5) Other conditions that could affect the water supply
A.5.1.2.1.1 The purpose of the adjustment is to take into account reasonable daily and seasonal
variations in the water supply, which are easily predicted and tracked by a water utility. It is not
the intent to use this section to account for unusual conditions such as 100 year droughts or water
main breaks. These unusual conditions are handled through the Impairment Procedures of
NFPA 25 and should not be considered when determining the ability of a water supply to meet
the demand of a fire protection system under more normal circumstances.
A.5.1.2.1.2 Consider the following example. A waterflow test is conducted at a location where a
city water main is going to be tapped for a new sprinkler system. During the test, the static
pressure is measured at 70 psi, the residual pressure is measured at 50 psi while 1300 gpm was
discharging from a nearby hydrant. The water utility is contacted and they indicate that a
reasonable low static pressure accounting for typical daily and seasonal fluctuations in this area
is 55 psi. The equation that describes the water supply available for a fire sprinkler system
would be:
1.85
Q
P 50 70 55
1300
There are two ways to use this formula. One would be to assume two different values for Q,
calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling
on or below the line on this graph would be acceptable in accordance with NFPA 13 to work
with this water supply. In this case, the two easiest flows to pick for Q would be 0 and 1300
gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can
be plotted on log 1.85 paper as shown in Figure A.5.1.2.1.2.
The second way to use this formula would be to calculate the fire protection system and
determine the flow necessary to make the system work. Plug this flow into the formula above
and see what the available pressure from the water supply will be at that flow. For example, if a
sprinkler system connected to this water supply had a demand of 580 gpm, the available pressure
from the water supply would be:
1.85
580
P 50 70 55
1300
P = (-20)(0.225) + 55
P = 50.5 psi
So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will
work with this water supply.
Sprinkler system demand can be
anywhere in shaded region
Figure A.5.1.2.1.2 Available Water Supply Curve for Example in Section A.5.1.2.1.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5.1.2*
The volume flow and pressure of a public water supply shall be determined from waterflow test data or
other approved method.
The flow (volume rate), typically measured or calculated in gallons/minute, is required to be determined of a public
water supply, not the volume (gallons).
Committee Statement
10 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6.1.1.4 *
A new connection to a municipal water supply shall be permitted to utilize a nonlisted, nonindicating
valve, including a T-wrench as part of a tapping assembly, shall be permitted .
6.1.1.4.1
For new installations, where more than one nonindicating underground gate valve is installed in a water
system, all underground gate valves shall be of the same opening direction.
This proposal is offered to provide better clarification to the type of valves is to be installed. Without the reference
to a new connection to a municipal water supply, the current text in the 2016 edition of the standard suggests that
a nonlisted, nonindicating valve is permitted at any time, as long as it is part of a tapping assembly.
Committee Statement
11 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7.1.1.1
The connection from the hydrant to the main shall not be less than 6 in on a grid system with cross
connections no greater than 600 feet . (150) (nominal). If installed on a end line the minimum size shall be
8 inch
AWWA Manual M31, "Distribution System Requirements for Fire Protection" states under a table heading "Typical
Minimum Values", for "Smallest pipes in networks" as "6 in.", and for "Smallest branching pipes (dead ends) "8
in.". This information was found on the internet
Committee Statement
Resolution: NFPA 24 limits minimum size to 6" if caluculations can be provided that support use of smaller than 8"
piping, there is no reason to mandate 8" piping.
12 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7.1.1.2
A control valve in accordance with Section 6.1 shall be installed in each hydrant connection.
7.1.1.2.1
Valves required by 7.1.1.2 shall be installed within 20 ft (6.1 m) of the hydrant.
7.1.1.2.1.1
Valves shall be clearly identified and kept free of obstructions.
7.1.1.2.2
Where valves cannot be located in accordance with 7.1.1.2.1, valve locations shall be permitted where
approved by the AHJ.
This proposal is offered to provide clarification to the type of valve is to be installed to control a hydrant. Without
the reference to Section 6.1, the current edition of the standard does not even specify that the valve be listed.
Additionally, a separate proposal has also been offered, to change the illustrations of the hydrant connection
valves Figure A.7.3.1(a) and Figure A.7.3.1(b) from the nonindicating type to the post indicator type, because as
per the charging statement Section 6.1.1, indicating type valves are called for, whereas the nonindicating type are
only allowed under 6.1.1.3 with the permission of the AHJ.
Committee Statement
Resolution:
13 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7.3.2.1
Where soil is of such a nature that the hydrants will not drain properly with the arrangement specified in
7.3.1 2 , or where groundwater stands at levels above that of the drain, the hydrant drain shall be plugged
before installation.
7.3.2.1.1 *
Hydrants with drain plugs shall be marked to indicate the need for pumping out after usage.
Editorial correction. 7.3.1 speaks on the support of hydrants, whereas it is 7.3.2 that deals with drainage
preparation.
Committee Statement
14 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
15 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.1.1.1 Listing.
16 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Steel
AWWA
Steel Water Pipe 6 in. and Larger
C200
Coal-Tar Protective Coatings and Linings for Steel Water Pipelines Enamel and Tape — Hot AWWA
Applied C203
Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. and Larger — Shop AWWA
Applied C205
AWWA
Field Welding of Steel Water Pipe
C206
AWWA
Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in.
C207
AWWA
Dimensions for Fabricated Steel Water Pipe Fittings
C208
A Guide for Steel Pipe Design and Installation AWWA M11
Concrete
AWWA
Reinforced Concrete Pressure Pipe, Steel-Cylinder Type
C300
AWWA
Prestressed Concrete Pressure Pipe, Steel-Cylinder Type
C301
AWWA
Reinforced Concrete Pressure Pipe, Non-Cylinder Type
C302
AWWA
Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned
C303
Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in., for Water Distribution AWWA
Systems C400
AWWA
Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — in Place
C602
Plastic
AWWA
Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution
C900
AWWA
Polyvinyl Chloride (PVC) Pressure Pipe, 14 in. Through 48 in., for Water Distribution
C905
17 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Brass
Specification for Seamless Red Brass Pipe ASTM B43
Copper
Specification for Seamless Copper Tube ASTM B75
Specification for Seamless Copper Water Tube ASTM B88
Requirements for Wrought Seamless Copper and Copper-Alloy Tube ASTM B251
The Resolution for the “Public Comment No. 2-NFPA 24-2014 [ Section No. 10.1.1.1 ]” says (page 25/35 of file
“24_A2015_SD_PCStatements.pdf”):
“The document has required steel piping for general underground service to be listed for the last few editions.”
The document has required steel piping for general underground service to be listed in the NFPA 13/24-2002
/7/10/13 editions.
The document has required steel piping for general underground service to not be nonlisted in the NFPA
13/24-2002/7/10/13 editions.
The document has required steel piping for other than general underground service to be listed or to be nonlisted
in the NFPA 13-2002/7/10/13 and NFPA 24-2002/10/13 editions.
The current NFPA 13/24-2016 edition requires steel piping for other than general underground service to be listed.
This Public Input restores the document to the requirement in the NFPA 13-2002/7/10/13 and NFPA
24-2002/10/13 editions: steel piping for other than general underground service is required to be listed (through
10.1.1.2) or to be nonlisted (through Table 10.1.1.1) .
Committee Statement
18 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Resolution: Steel piping used for underground needs to be listed due to issues surrounding corrosion.
19 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.1.4
Where piping installed in a private fire service main must be installed above grade, the piping materials
shall conform to NFPA 13.
10.1.4.1 * *
Underground piping shall be permitted to extend into the building through the slab or wall not more than
24 in
24 in . (
600 mm
600 mm ).
Chapter 10 applies to private fire service mains installed below grade. Chapter 12 applies to private fire service
mains installed above grade.
Committee Statement
20 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Editorial correction. 10.3.2 speaks to all of the various types of connections, whereas it is 10.3.4 that specifically
deals with pipe threads.
21 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Zip:
Submittal Date: Tue Jun 28 23:51:39 EDT 2016
Committee Statement
22 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Public Input No. 19-NFPA 24-2016 [ Sections 10.4.2.1.4, 10.4.2.1.5, 10.4.2.1.6, 10.4.2.1.7 ]
Private fire service mains installed in water raceways or shallow streams shall be installed so that the piping
will remain in the running water throughout the year.
10.4.2.1.6 5
Where piping is installed adjacent to a vertical face, it shall be installed from the vertical face at the same
distance as if the piping were buried.
10.4.2.1.7 6
Protection of private fire service mains from freezing using heat tracing shall be permitted when the heat
tracing is specifically listed for underground use.
10.4.2.1.7.1
Heat tracing not listed for underground use shall be permitted when piping is installed
Where an underground fire service main extends into a building in accordance with 10.1.4 , the exposed
pipe shall be protected from freezing in accordance with 12 .2.3.
Committee Statement
23 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Public Input No. 15-NFPA 24-2016 [ Section No. 10.4.2.2 [Excluding any Sub-Sections] ]
The depth of cover for private fire service mains and their appurtenances to protect against mechanical
damage shall be in accordance with 10.4.2.2.3 .
Correction of typo. The entire section of 10.4.2.2 applies to the protection of piping from mechanical damage, not
just section 10.4.2.2.3.
Committee Statement
24 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.4.2.2.6
Where private fire service mains are installed above ground, they shall be protected with bollards or other
means as approved by the AHJ when subject to mechanical damage.
Committee Statement
25 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.4.3.1.1*
Pipe joints and fittings shall not be located directly under foundation fittings footings .
Committee Statement
26 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.4.3.1.1 *
Pipe joints shall not be located directly under foundation fittings footings .
Editorial Correction.
Committee Statement
27 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.4.3.2 *
Where approved, private fire service mains supplying systems within the building shall be permitted to
extend more than 10 ft (3.0 m) under the building when all the requirements of 10.4.3.2.1 , through
10.4.3.2.4 are met.
10.4.3.2.1
Where the piping is installed under the building, all foundations or footers over the private fire service main
shall be arched to create a minimum of 24 in (600 mm) clearance.
10.4.3.2.2
It shall be acceptable to install the piping in covered trenches where the trenches are accessible from
within the building.
10.4.3.2.3
All joints shall be mechanically restrained.
10.4.3.2.4
A valve shall be installed before the piping enters under the building and within 24 in. (600 mm) of where
the piping enters the building.
During the last revision, a task group was formed to work on trench language for piping running under buildings.
During the second draft the task group proposed language to the committee and the language was accepted.
However, the first draft language was published. Attached is the language that the task group created.
Committee Statement
28 of 51 11/4/2016 7:43 AM
10.4.3.2
Private fire service mains shall not be permitted to extend more than 10 ft (3 m) under the building
except as allowed in 10.4.3.2.1.
10.4.3.2.1
Where private fire service mains extend more than 10 ft (3 m) into the building, they shall be run in a
trench.
10.4.3.2.1.1
The trench shall be accessible from within the building.
A.10.4.3.2.1.1
A grate or steel plate are common methods of accessing the trench.
10.4.3.2.1.2
The trench shall have rigid walls and a base.
10.4.3.2.1.3
The trench shall be constructed of non‐combustible materials.
10.4.3.2.1.4
Provisions for draining water shall be provided for the trench.
A.10.4.3.2.1.4
The intent of this requirement is to prevent the piping from being exposed to standing water. Draining
can be accomplished by providing a floor drain, sloping of the trench, or other approved method.
10.4.3.2.1.5
Where the piping in the trench is installed under foundations or footers, the foundation or footer shall
be arched to create a minimum of 24 in (610 mm) clearance.
10.4.3.2.1.5.1
Where acceptable to the Authority Having Jurisdiction, pipe sleeves shall be permitted to be used.
10.4.3.2.2
Piping in the trench shall be permitted to be in accordance with 10.1.1.
10.4.3.2.2.1
Where the trench is entirely of concrete construction, aboveground piping in accordance with NFPA 13
shall be permitted to be used.
10.4.3.2.2.2
Where piping installed in the trench is in accordance with 10.1.1, all joints shall be restrained in
accordance with 10.6.2 or 10.6.3.
10.4.3.2.3
Where piping is installed in a trench as allowed by 10.4.3.2.1, a valve shall be provided where the
underground piping enters the trench.
A.10.4.3.2.3
It is the intent of this section to require a valve at each point where the pipe enters the trench when the
trench traverses the entire building. Generally if the piping terminates at a point within the building
usually a valve is provided at a riser, allowing isolation of the pipe section in the trench.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.9.3
In the absence of specific guidleines, the maximum allowable particle size for backfill within 1' of the pipe
should be 3/4". Nominal pipe sizes of 4" or smaller should not exceed 1/2" maximum particle size. Rocks
larger than 1-1/2" shall not be used for backfill.
The comment of Rocks shall not be used for backfill seems to be vague and without definition. I have proposed
language that was borrowed from Amster Howard's book Pipeline Installation 2.0. I added the 1/2" size limitation
as that is a recommendation for HDPE pipe and feel it may be appropriate for other piping materials.
Committee Statement
Resolution: PI contained unenforceable language however has technical merit. A Task Group has been formed to
further study the issue.
29 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
(1) Notifying the AHJ and the owner's representative of the time and date testing is to be performed
(2) Performing all required acceptance tests
(3) Completing and signing the contractor's material and test certificate(s) shown in Figure 10.10.1
Revise Figure 10.10. 1 to remove the use of a burlap bag while flushing.
Figure 10.10.1 Sample of Contractor's Material and Test Certificate for Underground Piping.
The figure calls out the use of a burlap bag during flushing in the sample and as such becomes a defacto
requirement. However, the use of this bag is not discussed in the body of the standard and should not be treated
as a requirement. Other methods of inspecting for debris can be used.
Committee Statement
30 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
"Have copies of appropriate instructions and care and maintenance charts been provided to the
owner or owner's representative."
Some AHJ's have been requiring that a copy NFPA 25 be left at each building of apartment
complexes.
Revise Figure 10.10.1 to remove the use of a burlap bag while flushing. (remove "in burlap bags"
from flushing section on form. The revised language will read as follows:
Flushing: Flow the required rate until water is clear as indicated by no collection of foreign material at
outlets such as hydrants and blow-offs. Flush at one of the flow rates as specified in 10.10.2.1.3.
31 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
32 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
(1) Notifying the AHJ and the owner's representative of the time and date testing is to be performed
(2) Performing all required acceptance tests
(3) Completing and signing the contractor's material and test certificate(s) shown in Figure 10.10.1
Figure 10.10.1 Sample of Contractor's Material and Test Certificate for Underground Piping.
Change the test certificate to read "Have copies of appropriate instructions and care and maintenance charts been
provided to the owner or owner's representative." Some AHJ's have been requiring that a copy NFPA 25 be left at
33 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
"Have copies of appropriate instructions and care and maintenance charts been provided to the
owner or owner's representative."
Some AHJ's have been requiring that a copy NFPA 25 be left at each building of apartment
complexes.
Revise Figure 10.10.1 to remove the use of a burlap bag while flushing. (remove "in burlap bags"
from flushing section on form. The revised language will read as follows:
Flushing: Flow the required rate until water is clear as indicated by no collection of foreign material at
outlets such as hydrants and blow-offs. Flush at one of the flow rates as specified in 10.10.2.1.3.
34 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.10.2.1.3.2
A means shall be provided to verify that the flow rate required by 10.10.2.1.3 or 10.10.2.1.3.1 was achieved
during the flushing operation.
There is currently no requirement for verification that the required flow was achieved during the flush test and
therefore, when the test is performed, it is unknown whether or not the correct flow was achieved.
Committee Statement
Resolution: Options are already provided to allow for flushing a system i.e.: opening the valve completely or
measuring flow.
35 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10.10.2.2.1 *
All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested
at gauge pressure of 200 psi (13.8 bar) or 50 psi (3.4 bar) in excess of the system working pressure,
whichever is greater, and shall maintain that pressure at gauge pressure of ±5 psi (0.34 bar) for 2 hours.
Aternatively, pressure testing of Polyethylene piping may be conducted in accordance with the
requirements and recommendations of ASTM F 2164(Field Leak Testing of Polyethylene Pressure Piping
Systems Using Hydrostatic Pressure).
due to the viscoelastic stress relieving nature of polyethylene pipe, the actual loss as shown by gauge pressure
may fall below the allowable listed in 10.10.2.2.1 as currently written. The proposed addition of the ASTM
standard would allow for a testing protocol that is commonly used with HDPE piping systems. This change may
be better suited as a new subparagraph to section 10.10.2.3 instead of where I proposed placement.
Committee Statement
36 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
12.2.7
Aboveground private fire service mains shall be protected with bollards or other means as approved by the
AHJ when subject to mechanical damage.
Committee Statement
37 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
38 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
A.5.1.2
An adjustment to the waterflow test data to account for the following should be made, as appropriate:
.1.1 The purpose of the adjustment is to take into account reasonable daily and seasonal variations in the
water supply, which are easily predicted and tracked by a water utility. It is not the intent to use this
section to account for unusual conditions such as 100 year droughts or water main breaks. These unusual
conditions are handled through the Impairment Procedures of NFPA 25 and should not be considered
when determining the ability of a water supply to meet the demand of a fire protection system under more
normal circumstances.
A.5.1.2.1.2 Consider the following example. A waterflow test is conducted at a location where a city water
main is going to be tapped for a new sprinkler system. During the test, the static pressure is measured at
70 psi, the residual pressure is measured at 50 psi while 1300 gpm was discharging from a nearby
hydrant. The water utility is contacted and they indicate that a reasonable low static pressure accounting
for typical daily and seasonal fluctuations in this area is 55 psi. The equation that describes the water
supply available for a fire sprinkler system would be:
There are two ways to use this formula. One would be to assume two different values for Q, calculate P
and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling on or below the line on
this graph would be acceptable in accordance with NFPA 13 to work with this water supply. In this case,
the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is simply 55 psi. When Q =
1300 gpm, P = 35 psi. These two points can be plotted on log 1.85 paper as shown in Figure A.5.1.2.1.2.
The second way to use this formula would be to calculate the fire protection system and determine the flow
necessary to make the system work. Plug this flow into the formula above and see what the available
pressure from the water supply will be at that flow. For example, if a sprinkler system connected to this
water supply had a demand of 580 gpm, the available pressure from the water supply would be:
P = (-20)(0.225) 55
P = 50.5 psi
So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will work with
this water supply.
Figure
A-24-2-2-2-1.tiff
Figure A.5.1.2.1.2 Available Water Supply Curve for Example in Section A.5.1.2.1.2
39 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
This is the annex companion to the adjustment issues proposed for the body of the standard. The examples are
helpful in explaining how to perform the calculations and use the formula.
Committee Statement
This proposal takes care of the traditional arguments against a mandated safety margin by creating a
standardized method of calculating that safety margin; however, this standardized method is only
used if there is no information regarding the water utility. So, those situations where the fluctuations in
the water delivery are known at a particular location, then these take priority.
Spelling out the fact that NFPA 24 is not expecting unusual circumstances like water main breaks and
100 year droughts should help alleviate liability concerns on the part of the water utility, which should
lead to a more open dialog between the fire protection professional and the water utility
representative. The reality is that extreme conditions like 100 year droughts and water main breaks
are better handled by the Impairment Procedures of NFPA 25.
One of the concerns about this proposal last cycle was that there was no way to account for the
situation where the water utility brings more pumps on line as the flow demand increases. These
situations produce a water supply curve that looks more like a saw-tooth configuration than a line.
That concern has been handled with the proposed language in the new section 5.1.2.1.1.
Another of the concerns last cycle about this proposal was the fact that the modified line was not
parallel to the original test line, and might cross the test line at a high flow. This concern has been
mitigated by making the line parallel to the test line, which is more representative of what will happen
in the real world anyway.
40 of 51 11/4/2016 7:43 AM
Water Supply Adjustment Proposals Put Together
Insert new sections as follows:
5.1.2.1 Where a waterflow test was conducted, the volume and pressure available for use for a
fire protection system shall be determined from either 5.1.2.1.1 or 5.1.2.1.2.
5.1.2.1.1* Knowledge of the water supply and engineering judgment taking into account
reasonable daily and seasonal fluctuations not extreme conditions.
1.85
Q
P PR PS PL
QR
P = The pressure available from the water supply to use for a fire protection system that
will be calculated for a given flow (Q)
Q = The flow that will be used to calculate the available pressure from the water supply.
PR = The residual pressure measured during the waterflow test while the flow QR was
discharging from the water supply.
QR = The flow discharging from the water supply when PR was measured.
PL = The expected low static pressure at the location of the test results accounting for
daily and seasonal fluctuations (not extreme conditions) obtained from the water utility.
Where the water authority does not provide PL, see 24.2.2.2.1.3.
5.1.2.1.3 Where the water authority does not provide a value for PL, the value of PL shall be
calculated from the following formula:
PL = PS – 10 psi
A.5.1.2 An adjustment to the waterflow test data to account for the following should be made, as
appropriate:
(1) Daily and seasonal fluctuations
(2) Possible interruption by flood or ice conditions
(3) Large simultaneous industrial use
(4) Future demand on the water supply system
(5) Other conditions that could affect the water supply
A.5.1.2.1.1 The purpose of the adjustment is to take into account reasonable daily and seasonal
variations in the water supply, which are easily predicted and tracked by a water utility. It is not
the intent to use this section to account for unusual conditions such as 100 year droughts or water
main breaks. These unusual conditions are handled through the Impairment Procedures of
NFPA 25 and should not be considered when determining the ability of a water supply to meet
the demand of a fire protection system under more normal circumstances.
A.5.1.2.1.2 Consider the following example. A waterflow test is conducted at a location where a
city water main is going to be tapped for a new sprinkler system. During the test, the static
pressure is measured at 70 psi, the residual pressure is measured at 50 psi while 1300 gpm was
discharging from a nearby hydrant. The water utility is contacted and they indicate that a
reasonable low static pressure accounting for typical daily and seasonal fluctuations in this area
is 55 psi. The equation that describes the water supply available for a fire sprinkler system
would be:
1.85
Q
P 50 70 55
1300
There are two ways to use this formula. One would be to assume two different values for Q,
calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling
on or below the line on this graph would be acceptable in accordance with NFPA 13 to work
with this water supply. In this case, the two easiest flows to pick for Q would be 0 and 1300
gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can
be plotted on log 1.85 paper as shown in Figure A.5.1.2.1.2.
The second way to use this formula would be to calculate the fire protection system and
determine the flow necessary to make the system work. Plug this flow into the formula above
and see what the available pressure from the water supply will be at that flow. For example, if a
sprinkler system connected to this water supply had a demand of 580 gpm, the available pressure
from the water supply would be:
1.85
580
P 50 70 55
1300
P = (-20)(0.225) + 55
P = 50.5 psi
So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will
work with this water supply.
Sprinkler system demand can be
anywhere in shaded region
Figure A.5.1.2.1.2 Available Water Supply Curve for Example in Section A.5.1.2.1.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
A.7.3.1
See Figure A.7.3.1(a) and Figure A.7.3.1(b) .
Revise Figure A.7.3.1(a) and Figure A.7.3.1(b) to change the illustrations of the hydrant
connection valves from the nonindicating type to the post indicator type.
Figure A.7.3.1(a) Typical Hydrant Connection with Minimum Height Requirement.
41 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
This proposal is offered to because as per the charging statement Section 6.1.1, indicating type valves are called
for, whereas the nonindicating type, while are currently illustrated, are only allowed under 6.1.1.3 with the
permission of the AHJ.
Currently, because non-indicating valves are shown in the two Figures and 6.1 is not referenced in either Section
7.1.1.2 or Section 7.3.1, it is not clear that the hydrant control valve should be selected in the same manner as
other water supply control valves are. With this, hydrants with nonindicating control valves are being specified
without consultation with the AHJ.
A separate proposal has also been offered, to revise 7.1.1.2 to add a clarifying reference Section 6.1. Without
such a reference the current edition of the standard does not even specify that a hydrant control valve is required
to be listed.
Committee Statement
42 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
A.10.1.1
The type and class of pipe for a particular underground installation should be determined through
consideration of the following factors:
The following pipe design manuals and standards can be used as guides:
the current reference is to AWWA standards that describe the requirements for the production of pipe and fittings.
the proposed replacement are to manuals relating to the design and installation of the referenced plastic pipes.
Committee Statement
Resolution: FR-19-NFPA 24-2016 These references are already mandated in the main body of the standard.
Statement: The current reference is to AWWA standards that describe the requirements for the production of pipe
and fittings. The proposed replacement are to manuals relating to the design and installation of the
referenced plastic pipes.
43 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
44 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
A.10.1.4.1
Where nonmetallic underground piping is provided above grade or inside a building, the following should be
considered:
Committee Statement
45 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
to assist the reader, a reference is supplied in the Annex section for a industry accepted document that can help
with the verification requirement identified in section 10.8.2.
Committee Statement
Resolution: Committee has no technical justification for this to be added to the standard. Section 10.8.2 already
addresses this topic.
46 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
A.10.10.2.2.1
A For example, consider a sprinkler system has for its water supply a connection to a public water service
main. A 100 psi (6.9 bar) rated pump is installed in the connection. With a maximum normal public water
supply of 70 psi (4.8 bar), at the low elevation point of the individual system or portion of the system being
tested and a 120 psi (8.3 bar) pump (churn) pressure, the hydrostatic test pressure is 70 psi (4.8 bar) +
120 psi (8.3 bar) + 50 psi (3.5 bar), or 240 psi (16.5 bar).
To reduce the possibility of serious water damage in case of a break, pressure can be maintained
be introduced by a small pump, the main controlling gate meanwhile being kept shut during the test.
Polybutylene pipe will undergo expansion during initial pressurization. In this case, a reduction in gauge
pressure might not necessarily indicate a leak. The pressure reduction should not exceed the
manufacturer's specifications and listing criteria.
When systems having rigid thermoplastic piping such as CPVC are pressure tested, the sprinkler system
should be filled with water. The air should be bled from the highest and farthest sprinklers. Compressed air
or compressed gas should never be used to test systems with rigid thermoplastic pipe.
A recommended test procedure is as follows: The water pressure is to be increased in 50 psi (3.5 bar)
increments until the test pressure described in 10.10.2.2.1 is attained. After each increase in pressure,
observations are to be made of the stability of the joints. These observations are to include such items as
protrusion or extrusion of the gasket, leakage, or other factors likely to affect the continued use of a pipe in
service. During the test, the pressure is not to be increased by the next increment until the joint has become
stable. This applies particularly to movement of the gasket. After the pressure has been increased to the
required maximum value and held for 1 hour, the pressure is to be decreased to 0 psi while observations
are made for leakage. The pressure is again to be slowly increased to the value specified in 10.10.2.2.1
and held for 1 more hour value it is held for 2 hours while observations are made for leakage and the
leakage measurement is made pressure readings are checked .
The revisions to the first paragraph are just editorial, to provide better clarity that the matter is just an example of
how to determine the test pressure.
The revision to the second paragraph is necessary because after the test pressure is introduced into the system,
the pump needs to be shut off, whereas the current text suggests that it can be used to “maintain” the pressure.
The revisions to the last paragraph are to provide better coordination between the Annex text and the requirement
of Section 10.10.2.2.1, which deals with a pressure variation of ±5 psi and not with leakage measurement. Also, it
makes no sense to reduce the pressure after 1 hour to check for leakage. If the pressure is reduced the test would
be skewed, because the leakage could be expected to be reduced as well.
Committee Statement
47 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Resolution: FR-20-NFPA 24-2016 There is no need to reduce the pressure to 0psi, pressure should be
maintained throughout the test.
Statement: The revisions to the first paragraph are just editorial, to provide better clarity that the matter is just an
example of how to determine the test pressure.
The revision to the second paragraph is necessary because after the test pressure is introduced into
the system, the pump needs to be shut off, whereas the current text suggests that it can be used to
“maintain” the pressure.
The revisions to the last paragraph are to provide better coordination between the Annex text and the
requirement of Section 10.10.2.2.1, which deals with a pressure variation of ±5 psi and not with
leakage measurement. Also, it makes no sense to reduce the pressure after 1 hour to check for
leakage. If the pressure is reduced the test would be skewed, because the leakage could be
expected to be reduced as well.
48 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
49 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Referenced current SDO names, addresses, standard names, numbers, and editions.
50 of 51 11/4/2016 7:43 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
City:
State:
Zip:
Submittal Date: Sun Dec 20 23:52:12 EST 2015
Committee Statement
51 of 51 11/4/2016 7:43 AM