Professional Documents
Culture Documents
D.S.L.P Calculation For 100Kv Switchyard For Centur Rayon by Rolling Sphere Method, As Per IEEE-std 998-1996
D.S.L.P Calculation For 100Kv Switchyard For Centur Rayon by Rolling Sphere Method, As Per IEEE-std 998-1996
INTRODUCTION
The method employed for design of the shielding system is Electrogeometric – Rolling Sphere Method.
The Rolling Sphere method is a simple technique for applying the EGM theory for shielding of substations
The technique involves rolling an imaginary sphere of prescribed radius over the surface of the substation.
The sphere rolls up and over (and is supported by) the lightning masts, intended for lightning shielding.
A piece of equipment is protected from a direct stroke of lightning if it remains below the curved surface of the
sphere by virtue of the sphere being elevated by shield wires or other devices. Equipment that touches
the sphere or penetrates its surface is not protected from direct stroke of lightning.
DATA
ACSR Conductor Zebra
Conductor per phase (n) = 1.000 nos.
Overall Diameter of ACSR conductor (d s) = 0.02862 met
Rated Lightning Impulse withstand voltage(Vo) = 650.000 kV
Limiting corona gradient(E 0) = 1500.000 kV/met (Refer Annexure C-Page 121-IEEE-998)
height of equipment top to be protected(A) = 5.100 met.
Height of shield wire(H) = 11.000 met.
CALCULATION
Object to be protected : equipment Bus(Single "zEBRA 'ACSR Conductor )
In case of a single conductor bundle, the equivalent radius is given by R0= ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0= sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h=is the average height of the conductor in meters h= 5.100
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.092
Radius of protection by single wire mast at protected equipment height of r= √ S2 - ( S- H)2-√ S2 - ( S- A)2
5.1 met. r= 4.706 met
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 15.390 met
described in the diagrams
Radius of the curvature of the unprotected area originating a distance r1 = √ S2 - ( S- A)2
of 'd'from the midpoint of two structures, r1 = 13.648 met
Conclusion
Distance between shield wires on incoming gantry towers measured on drawing is 20 Met. which is less than maximum allowable distance 29.0
Met.Hence equipment at , 5.1 met.between two shield wires on incoming gantry towers is protected. Also, the equipment is below the curved
surface of the rolling sphere drawn at elevation of shield wire as seen in the section drg.
D.S.L.P CALCULATION FOR 100kV Switchyard FOR CENTUR RAYON
By Rolling Sphere method, as per IEEE-std 998-1996
CALCULATION
Object to be protected : Transformer
In case of a single conductor bundle, the equivalent radius is given by R0= ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0= sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h = average height of the equipment to be protected h = 5.800
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.089
R0 = 0.014 met.
h = 5.800 met.
Corona radius of the bundle conductor R'c = 0.103 met.
Equivalent radius of bundle conductor r= 0.014 met.
ZS = 337.481 ohms For ACSR conductor
The allowable stroke current is obtained by the equation(I s)
for transformer IS = 1.1X BIL/Zs ( eqn. 5.2A, IEEE 998 - 1996)
2.119 kA (divide by 2)
The allowable stike Distance is obtained by the equation S= 8 x k x Is0.65 ( eqn. 5.1A, IEEE 998 - 1996)
where S = Strike distance in m k= 1.200 for strikes to Lightning mast
S= 15.639 met For ACSR conductor
Maximum horizontal separation of MAST
S- Strike distance 15.639
H- LM height 21.000
A -Equipment height 5.800
C= √ S2 - ( S- A)2
C= 12.156 met
T= S-C _
T= 3.483 met
W= √ S2 - ( S- A)2
12.156
Y= 3.000 (ASSUMED)
Z= W-Y
Z= 9.156
Maximum Distance between two masts for protection at equipment height L= √ S2 - Z2
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 10.763 met
described in the diagrams
Radius of the curvature of the unprotected area originating a distance r1 = √ S2 - ( S- A)2
of 'd'from the midpoint of two structures, r1 = 12.156 met
age 121-IEEE-998)
2A, IEEE 998 - 1996)
CALCULATION
Object to be protected : Transformer
In case of a single conductor bundle, the equivalent radius is given by R0= ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0= sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h = average height of the equipment to be protected h = 5.800
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.089
R0 = 0.014 met.
h = 5.800 met.
Corona radius of the bundle conductor R'c = 0.103 met.
Equivalent radius of bundle conductor r= 0.014 met.
ZS = 337.479 ohms For ACSR conductor
The allowable stroke current is obtained by the equation(I s)
for transformer IS = 1.1X BIL/Zs ( eqn. 5.2A, IEEE 998 - 1996)
2.119 kA (divide by 2)
The allowable stike Distance is obtained by the equation S= 8 x k x Is0.65 ( eqn. 5.1A, IEEE 998 - 1996)
where S = Strike distance in m k= 1.000 for strikes to Lightning mast
S= 13.033 met For ACSR conductor
Maximum horizontal separation of shield wire from protected equipment(bus) at bus height
Radius of protection by single wire mast at protected equipment height of 5.8 r= √ S2 - ( S- H)2-√ S2 - ( S- A)2
met. r= 1.207 met
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 6.721 met
described in the diagrams
Radius of the curvature of the unprotected area originating a distance r1 = √ S2 - ( S- A)2
of 'd'from the midpoint of two structures, r1 = 10.841 met
Conclusion
Distance between shield wires on gantry towers measured on drawing is 20 Met. which is less than maximum allowable distance 26.0 Met.Hence equipment at , 5.8
met.between two shield wires on towers is protected. Also, the equipment is below the curved surface of the rolling sphere drawn at elevation of shield wire as seen
in the section drg.
age 121-IEEE-998)
2A, IEEE 998 - 1996)
CALCULATION
Object to be protected : Transformer
In case of a single conductor bundle, the equivalent radius is given by R0= ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0= sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h = average height of the equipment to be protected h = 5.800
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.089
R0 = 0.014 met.
h = 5.800 met.
Corona radius of the bundle conductor R'c = 0.103 met.
Equivalent radius of bundle conductor r= 0.014 met.
ZS = 337.479 ohms For ACSR conductor
The allowable stroke current is obtained by the equation(I s)
for transformer IS = 1.1X BIL/Zs ( eqn. 5.2A, IEEE 998 - 1996)
2.119 kA (divide by 2)
The allowable stike Distance is obtained by the equation S= 8 x k x Is0.65 ( eqn. 5.1A, IEEE 998 - 1996)
where S = Strike distance in m k= 1.000 for strikes to Lightning mast
S= 13.033 met For ACSR conductor
Maximum horizontal separation of shield wire from protected equipment(bus) at bus height
Radius of protection by single wire mast at protected equipment height of 5.8 r= √ S2 - ( S- H)2-√ S2 - ( S- A)2
met. r= 2.032 met
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 8.107 met
described in the diagrams
Radius of the curvature of the unprotected area originating a distance r1 = √ S2 - ( S- A)2
of 'd'from the midpoint of two structures, r1 = 10.841 met
Conclusion
Distance between shield wires on gantry towers measured on drawing is 20 Met. which is less than maximum allowable distance 20.8 Met.Hence equipment at , 5.8
met.between two shield wires on towers is protected. Also, the equipment is below the curved surface of the rolling sphere drawn at elevation of shield wire as seen
in the section drg.
age 121-IEEE-998)
2A, IEEE 998 - 1996)
DATA
ACSR Conductor Zebra
Conductor per phase (n) = 1.000 nos.
Overall Diameter of ACSR conductor (d s) = 0.02862 met
Rated Lightning Impulse withstand voltage(Vo) = 650.000 kV
Limiting corona gradient(E0) = 1500.000 kV/met (Refer Annexure C-Page 121-IEEE-998)
height of equipment top be protected = 5.100 met.
Height of shield wire(H) = 18.000 met.
CALCULATION
Object to be protected : equipment Bus(Single "zEBRA 'ACSR Conductor )
In case of a single conductor bundle, the equivalent radius is given by R0 = ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0 = sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h=is the average height of the conductor in meters h= 5.100
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.092
Radius of protection by single wire mast at protected equipment height of 5.1 r= √ S2 - ( S- H)2-√ S2 - ( S- A)2
met. r= 6.973 met
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 18.034 met
described in the diagrams
Radius of the curvature of the unprotected area originating a distance r1 = √ S2 - ( S- A)2
of 'd'from the midpoint of two structures, r1 = 13.648 met
Conclusion
Distance between shield wires on gantry towers measured on drawing is 20 Met. which is less than maximum allowable distance 38.5 Met.Hence equipment at , 5.1
met.between two shield wires on towers is protected. Also, the equipment is below the curved surface of the rolling sphere drawn at elevation of shield wire as seen
in the section drg.
D.S.L.P CALCULATION FOR 100kV Switchyard FOR CENTURY RAYON(MSETCL SIDE)
By Rolling Sphere method, as per IEEE-std 998-1996
CALCULATION
Object to be protected : Transformer
In case of a single conductor bundle, the equivalent radius is given by R0= ds/2
0.014 met.
In case of a twin conductor bundle, the equivalent radius is given by R0= sqrt(r x I) ( eqn. C.5, IEEE 998 - 1996)
r = radius of subconductors in m
l = spacing between adjacent conductor in m
In case of a single conductor bundle, the equivalent radius is given by
Rc x ln {(2xh)/Rc} - (Vc/E0) = 0 ( eqn. C.1, IEEE 998 - 1996)
h = average height of the equipment to be protected h = 5.100
Vc = Rated Lightning Impulse withstand voltage Vc = BIL
650.000 kV
E0 = Limiting corona gradient Eo = 1500.000 kv/met.
By solving the equation for Rc, we have Rc = 0.089
R0 = 0.014 met.
h = 5.100 met.
Corona radius of the bundle conductor R'c = 0.103 met.
Equivalent radius of bundle conductor r= 0.014 met.
ZS = 329.641 ohms For ACSR conductor
The allowable stroke current is obtained by the equation(I s)
for transformer IS = 2.2X BIL/Zs ( eqn. 5.2A, IEEE 998 - 1996)
4.338 kA (divide by 2)
The allowable stike Distance is obtained by the equation S= 8 x k x Is0.65 ( eqn. 5.1A, IEEE 998 - 1996)
where S = Strike distance in m k= 1.200 for strikes to Lightning mast
S= 24.918 met For ACSR conductor
Maximum horizontal separation of MAST
S- Strike distance 24.918
H- LM height 21.000
A -Equipment height 5.100
C= √ S2 - ( S- A)2
C= 15.105 met
T= S-C _
T= 9.813 met
W= √ S2 - ( S- A)2
15.105
Y= 3.000 (ASSUMED)
Z= W-Y
Z= 12.105
Maximum Distance between two masts for protection at equipment height L= √ S2 - Z2
Distance from the midpoint of adjacent masts (orshield wire supports) d= √S 2 − (D/2)2 − (S −H)2)
, perpendicular to the center of the unprotected area with radius r1 as d= 22.485 met
age 121-IEEE-998)
2A, IEEE 998 - 1996)
LCLM
TRAFO 5.8 21 15.64 25.36 #NAME? 12.16
d1
15.39 EQUP
18.03 EQUP
8.11 TRAFO
10.76