4.82
D=7.288 √ LEQ∗Q1.82------1
LEQ=1.2*Lreal-----------------------2
n
Qs=Q I + QII + 1 ∑ Q 1--------3
2 i=1
Q 1.82
P1-P2=14384*LEQ* -----4
Dadop 4.82
PCS= 10.8 kw*h/m3
TRAMO O-E
LEQo-e=1.2*(5.58+602+5.50+16.10+1.30)
LEQo-e=41.62m
1
Qs=2.66+0.43+ (0.43+0.43+0.27+0.27+0.27)
2
Qs=4.43
TRAMO O-A
D=27.74 Dadop=32 1 ¼”
Lreal=1.2*6.69
L¿Lreal=6.69
14384∗6.69∗4.43 1.82
∆ P=
32 4.82
∆ P=0.08 mbar
TRAMO A-B
1
Qs=2.66+0.93+ (0.27+0.27)
2
Qs=4.43
D=26.31 Dadop=32 1 ¼”
Lreal=1.2*6.20
L¿Lreal=7.44
14384∗6.69∗3.861.82
∆ P=
324.82
∆ P=0.07 mbar
TRAMO B-C
1
Qs=2.66+0.27+ (0.27)
2
Qs=3.07
D=24.13 Dadop= 1”
Lreal=1.2*5.5
L¿Lreal=6.6
14384∗6.6∗3.071.82
∆ P=
25 4.82
∆ P=0.13 mbar
TRAMO C-D
Qs= (0.27+0.27)
Qs=0.54
14384∗19.32∗0.541.82
∆ P=
15 4.82
∆ P=0.19 mbar
TRAMO D-E
Qs=0.27
14384∗1.56∗0.271.82
∆ P=
15 4.82
∆ P=0.004 mbar
TRAMO D-F
Qs=0.27
14384∗0.12∗0.271.82
∆ P=
15 4.82
∆ P=0.0004 mbar
TRAMO C-G
Qs=2.66
14384∗6.69∗2.661.82
∆ P=
20 4.82
∆ P=0.10 mbar
TRAMO B-H
Qs=0.93
TRAMO A-I
1
Qs=0.43+0.43+ (0.27)
2
Qs=0.99
14384∗6.69∗0.991.82
∆ P=
154.82
∆ P=0.009 mbar
TRAMO I-J
Qs=0.43+0.27
Qs=0.7
14384∗7.2∗0.71.82
∆ P=
154.82
∆ P=0.11 mbar
TRAMO J-K
Qs= (0.27)
Qs=0.27
14384∗11.64∗0.271.82
∆ P=
154.82
∆ P=0.03 mbar
TRAMO J-L
Qs=0.93
Qs=0.93
14384∗1.32∗0.931.82
∆ P=
154.82
∆ P=0.009 mbar
TRAMO I-M
Qs=0.43
Qs=0.43
14384∗2.52∗0.431.82
∆ P=
154.82
∆ P=0.02 mbar
CALCULO PARA CALEFACCION DIVIDIDA
VOLUMEN CLASE
V CONFIGURACION POTENCIA Kca
AMBIENTE DE ADOPTADO MARCA
m3 DEL LOCAL KW REQ l
a b c LOCAL
DORMITORI 2, 3, 2, 23, 1 3 1 189 COPPEN
O I 4 9 5 4 ext int vit 7 2,2 2 2500 S
DORMITORI 3, 2, 2, 23, 2 2 1 180 COPPEN
O II 4 8 5 8 ext int vit 6 2,1 6 2500 S
DORMITORI 3, 2, 2, 26, 2 2 1 206 COPPEN
O III 6 9 5 1 ext int vit 6 2,4 4 2500 S
SALA 3, 5, 2, 51, 3 1 2 361 COPPEN
COMEDOR I 7 6 5 8 ext int vit 8 4,2 2 4000 S
SALA
COMERDOR 3, 5, 2, 51, 3 1 2 361 COPPEN
II 7 6 5 8 ext int vit 8 4,2 2 4000 S
CONVERTIR EN KW
1 KW
2500 Kcal* =2.91 dormitorio 1
860 Kcal
1 KW
2500 Kcal* =2.91 dormitorio 2
860 Kcal
1 KW
2500 Kcal* =2.91 dormitorio 3
860 Kcal
1 KW
4000 Kcal* =4.65 sala comedor 1
860 Kcal
1 KW
4000 Kcal* =4.65 sala comedor 2
860 Kcal