Quality Assessment of the University Classroom


Lighting - A Case Study
Ivana Tureková 1, Danka Lukáčová 1, Gabriel Bánesz 1
1
Constantine the Philosopher University in Nitra, Faculty of Education, Department of Techniques and
Information Technologies, Dražovská 4, Post code: 949 74, Nitra, Slovakia

Abstract - The purpose of this study is to prove that children’s education, hence the strict regulations
the quality of the school environment significantly governing the natural and artificial lighting in child
influences students’ academic performance. The care and educational facilities. The majority of
factors affecting the work environment are accurate children and students spend most of the day in
lighting which plays an important role in visual tasks,
enclosed spaces where the sun penetrates in limited
resulting in either visual comfort or visual fatigue. This
study presents the results of lighting objectification of a
quantities only. Most problematic is the winter time,
selected university classroom. Specifically, it focuses on when the lack of light is most critical, although
detection of the daylight factor, which is a significant a number of buildings struggle with proper amount of
criterion for the amount of daylight in the classroom. daylight throughout the whole year. The main
Its value is a relative magnitude and depends on the struggle of educational buildings in Slovakia
correct spatial layout of the classroom. The results of nowadays is inappropriate thermal insulation,
the study indicate the insufficient values of this inadequate microclimatic conditions in the
indicator. At the end, with a software, the solution for classrooms, absence of mechanical ventilation
replacing the artificial lighting in the classroom is systems or insufficient natural daylight [3]. Besides
designed, which is a possible alternative for improving
lifestyle, genetic dispositions and healthcare quality
the visual comfort of the classroom.
level, environmental conditions are amongst the
Keywords – daylighting assessment, visual comfort, basic parameters that affect human health. The
daylight illumination coefficient, DIALux. impact of environmental factors (15 – 20 %) is the
second most important element influencing public
1. Introduction health [4]. This comes immediately after the
population lifestyle impact (50 %).
Daylight plays an essential and irreplaceable role
Daylighting is considered a resource of primary
in human life. It affects one’s productivity, comfort,
importance in schools: it’s a key factor for
mood and overall health. Its effects apply in mental,
occupants’ health and well-being, enhancing the
as well as physical terms. The controlling body of
indoor environmental quality and reducing the
humans is directly stimulated and regulated by
energy consumption for electric lighting [5]. The
daylight [1, 2]. Suitable illumination is vital in
impact of natural light on learning has physiological,
psychological and behavioural influences on school
children as well as workers [6].
DOI: 10.18421/TEM74-21
Humans are affected both physically and
https://dx.doi.org/10.18421/TEM74-21
psychologically by light [7]. As shown in Table 1.
Corresponding author: Ivana Tureková, there is a multitude of physiological and
Constantine the Philosopher University in Nitra, Faculty of psychological benefits resulting from building
Education, Nitra, Slovakia daylighting [8].
Email: iturekova@ukf.sk Table 1. Natural light and human body
Natural light and human body
Received: 21 June 2018.
Physically Psychologically
Accepted: 10 October 2018.
Improve Decrease Improve Decrease
Published: 26 November 2018.
Vitamin D Cancer Mood Depression
© 2018 Ivana Tureková, Danka Lukáčová, Possibility
Gabriel Bánesz; published by UIKTEN. This work is Visual Abnormal Mental Stress
System Bone Performance
licensed under the Creative Commons Attribution-
Formation
NonCommercial-NoDerivs 3.0 License.
Circadian Alertness Sadness
The article is published with Open Access at Rhythms
www.temjournal.com Sleep Brain Violent
Quality activity Behavior

TEM Journal – Volume 7 / Number 4 / 2018. 829


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

There is no doubt that people find daylight more brightness distribution throughout our vision field,
pleasant than electric lighting as their primary source exclusion of silhouette effect or glare). Illumination
of light. Foreign studies confirm [9, 10, 11, 12, 13, quality can be impaired at any state of sky, however,
14], that a high percentage of respondents surveyed mainly at direct sunlight. For instance, evenness
prefer working in daylight. Similarly, people prefer evaluation according to STN 73 0580-1/Z2 brings
to sit at tables located next to windows as opposed to inaccuracies because it is based on daylight factor
further in the room, especially when these windows values set for evenly cloudy sky [22]. Therefore, at
have access to direct sunlight [15, 16, 17, 18]. this time there is no exact evaluation method, due to
Thanks to light we are able to receive visual instable daylight.
information about the environment that we are The daylight factor D (%) is determined by the
surrounded by 75 % to 90 % of these are received daylight rate coefficient in conditions of a cloudy
through eyesight. The mental state in which the winter day according to formula [23]:
visual system fulfils its function optimally is called
visual comfort. Suitable lighting is an essential (1)
element here. Visual comfort is directly affected by
the lighting source, type and layout of the lights,
evenness, and level of luminance and brightness Where E (lx) represents illumination at the
distribution in space [14]. observed location on a levelling plain and Eh (lx)
In terms of evaluation of work conditions, the represents external illumination of the horizontal
geometrical parameters of the space and surface unshaded plain (Figure 2.).
features, including colour, matter as well as whether The daylight rate coefficient D (%) is a relative
or not there is glare [19]. Lighting should be value and therefore, unlike luminance E (lx), its
sufficient and even, without excessive brightness or value is not so much subject to changes in the
contrast. If there is proper lighting distribution, brightness of the cloudy sky [19]. Relative simplicity
objects appear to be plastic. In suitable lighting of the winter-cloudy model and its independency of
conditions one has a feeling of clear vision even after sun position or point of the compass enables us to
a longer time. The opposite of visual comfort is estimate D (%) by calculation and mathematical and
visual fatigue. This is a complex state due to graphic methods [24] as well and by using a software
shortcomings in lighting. Symptoms include burning or measurements [25].
eyes, headaches and conjunctivitis [20].
Even when it’s cloudy the lighting changes rapidly
over the course of the day. This is done to a greater
extent than we are able to realize as a result of the
adaptive ability of our vision (Figure 1.).

Figure 2. Illumination rates for a horizontal unshaded


plain with a cloudy sky in course of a day and a year

2. Method
The aim of our study was to determine the values
of illumination, the daylight illumination coefficient
Figure 1. Changes in daylight illumination throughout a
and the expression of similarity or inaccuracy of the
cloudy day and the perception of these changes results achieved with the limit values in the
representative classroom. Using the DIALux model a
The variability of daylight is an advantage to us, as new lighting system was designed [26].
in a physiologically acceptable course it forces our For our experiment we selected a small university
vision to adapt [21]. However, in terms of lighting classroom located in the building of the Faculty of
evaluation, the instability of daylight is a problem Education at Constantine the Philosopher University.
most relevant in quality assessment (evenness, The room is situated on the ground floor and lectures

830 TEM Journal – Volume 7 / Number 4 / 2018


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

take place here frequently. It holds 24 students and 1 Located 15 meters from the researched classroom,
teacher. 15 meters far from the building there is there is another building which significantly affects
another building which could have an impact on the the daylight intensity in the school.
daylight intensity in the measured classroom (Figure Particular measurement was performed by a light
3.). The foreside of the building where the classroom meter Testo 545 (Figure 4.). It was extremely
is located is heat cladded and the whole building has accurate measurement since the permissible
plastic windows. deviation defined by producer was ±2% (according
to DIN 5032, part 6).

Figure 4. Apparatus Testo 545 that was used for lighting


measurement
The lighting measurements were executed in
March 8.00 - 15.00 hour. This included 8
measurements of sunlight, 8 measurements of
compound lighting and 3 measurements of artificial
lighting.
The aim of objectification was to detect the current
state of a workplace. Illumination was measured
within the net of 20 selected control points [27].
Height of the datum plane was 0.85 m above the
floor, distances between measuring points were 1 m
and the outer points of the net were less than 1.5 m
from the wall.
Other control points were distributed in regular
distances so that they can adequately monitor the
whole measured place, changes in lighting and also
Figure 3. A classroom where all measurements were done places with the highest and lowest intensity of
- position of windows and the nearby building, lighting. External conditions were measured by
arrangement of furniture
anemometer (psychrometer) AN 340.
The room orientation is north-west. Table 2. shows
description data of the space. 3. Results
Table 2. Characteristics of sunlight and artificial lighting Table 3. shows the results of external conditions in
system which the measurements took place.
Description of the office place
Walls Ceiling Floor Table 3. External conditions in measurements
colour white colour white colour light
gray Temperature Humidity Wet Condensation
material plaster material plaster material PVC (°C) (%) thermometer point
state of clean state of clean state of clean temperature (°C)
surface surface surface (°C)
23.6 32.8 13.9 6.2
Description of lighting system
Natural lighting 2 windows 800 x 1100 mm
system: Average daylight values are presented in Figure 5.
4 pieces of lamps number of light At 11 o’clock the daylight amounted to a maximum
sources in lamps: 4 value measured (507,4 lx). In the morning and in the
pieces
Artificial lighting Type of light TESLA, PHILIPS
afternoon the values were considerably lower (100 –
system: sources: TL-D 200 lx).
Power input: 36 W
Position of light regular, symmetric
sources:

TEM Journal – Volume 7 / Number 4 / 2018. 831


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

902.63

835.25

476.25
790.38 312.25
466.63
1000.00 559.57
785.25 297.63 170.63
439.71
800.00 187.38
438.50 302.29
210.63
600.00 443.13 290.88
193.63
400.00 243.13
176.875
200.00

0.00
Figure 5. Average daylight values in the classroom from 8 am to 3 pm

Table 4. presents daylight values, measurement At the same time, measurement of combined light
uncertainty and illumination requirements by STN was carried out by turning on every light source in
EN 12464-1 : Light and Illumination. the classroom in the same measuring points. We have
determined the average illumination of the classroom
Table 4. Measurement results and Illumination (Ē) based on the arithmetic mean of the measured
Requirements. values of the overall scaled horizontal illumination in
Ē U Ē–U Ē+U Illumination the whole of the measured space or combined
requirements by illumination on the comparison plain (Figure 6.).
(lx) (%) (lx) (lx) STN EN 12464-1 The lowest values were on average about 1000 lx,
426.13 34.09 392.04 460.22 500 lx which meets the illumination requirements
(minimum of 500 lx) for educational spaces [28].

1557.38

1488.63 1243.50
1277.63 1046.50
1184.38
1214.25 781.50
1413.13 1172.75 933.63
1044.13
1600.00 1563.63 1147.88 905.63
1400.00 1189.38 978.25
882.38
1200.00
958.25
1000.00 831.38
800.00
600.00
400.00
200.00
0.00

Figure 6. Average combined illumination values in the course of a day in the classroom.

832 TEM Journal – Volume 7 / Number 4 / 2018


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

Table 5. presents the values of combined Table 6. summarizes the values of 20 measuring
illumination, measurement uncertainty and points of average daylight values, external
illumination requirements by STN [28]. illumination at cloudy sky in winter (there was a set
of 20 measuring points constructed, similar to the
Table 5. Combined Illumination Values. one in the classroom) and artificial lighting in the
Ē U Ē–U Ē+U Illumination classroom by using only the existing lighting sources.
(lx) (%) (lx) (lx)
requirements by The last column contains the daylight illumination
STN EN 12464-1 coefficient D (%) calculated by using the formula
1140.71 91.26 1049.45 1231.97 500 lx
(1).

Table 6. Results of measuring daylight and artificial light, calculation of daylight illumination coefficient

Measuring Average Average values of Artificial Average Daylight


point daylight values combined lighting lighting values daylight values illumination
(classroom) outside coefficient
Ē (lx) Ē (lx) Ēartificial (lx) Ēoutside (lx) D (%)
1. 785.25 1563.63 840.15 12520 6.3
2. 443.13 1189.38 820.35 14310 3.1
3. 243.13 958.25 894.71 14170 1.7
4. 176.88 831.38 829.53 13880 1.3
5. 790.38 1413.13 1003.23 14210 5.6
6. 428.50 1147.88 1033.44 13250 3.2
7. 290.88 978.25 1057.53 13780 2.1
8. 193.63 882.38 999.92 14010 1.4
9. 559.57 1214.25 825.74 13360 4.2
10. 438.71 1172.75 894.58 13450 3.3
11. 302.29 1044.13 943.16 13780 2.2
12. 210.63 905.63 873.06 13970 1.5
13. 835.25 1488.63 751.22 12890 6.4
14. 466.63 1277.63 720.81 13580 3.4
15. 297.63 1184.38 852.14 13560 2.2
16. 187.38 933.63 753.26 12790 1.4
17. 902.63 1557.38 790.78 14120 6.4
18. 476.25 1243.50 767.83 13480 3.5
19. 312.25 1046.50 786.21 12780 2.4
20. 170.63 781.50 730.34 13010 1.3
Average
425.58 1040.71 858.40 13354 3.2
value

Table 7. present artificial daylight values, Table 7. Artificial daylight values and illumination
measuring uncertainty, and illumination requirements requirements
by STN EN 12464-1: Light and Illumination.
Ē U Ē–U Ē+U Illumination
Daylight illumination coefficient D (%) as one of requirements by
the criteria of daylight amount has to meet the (lx) (%) (lx) (lx) STN EN 12464-1
following requirements: 857.95 68.64 789.31 926.59 500 lx
Inside the premises or in their functionally
specialized parts where employees spend a lot of The values of average illumination we obtained by
time the minimum values of the daylight illumination the measurements and calculations were rectified by
coefficient must be: measurement uncertainties set against the
illumination requirements. Technical solutions for
a) At side illumination Dmin = 1,5 % improving lighting systems are relevant while project
b) At top and combined illumination Dmin = 1, 5 processing and reconstruction. Various modelling
% and Dm = 3 %, where: Dmin is the minimum programmes offer a range of lighting system
value of the daylight illumination coefficient solutions. Through DIAlux programme a new
on the comparison plain (%);Dm – the average lighting system was drafted using LED lights, while,
value of the daylight illumination coefficient preserving the arrangement of the existing lighting
on the comparison plain (%). system (Figures 7., 8.).

TEM Journal – Volume 7 / Number 4 / 2018. 833


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

The lights were selected from the options in the


programme - 12 pcs of PHILIPS CR200B 2xTL5-
54W HFP GT_452 (luminous flux 5852 lm; Lamp
power: 118.0 W).

Figure 9. Rendering of place by false colours

Figure 7. Modelling room arrangement. 4. Discussion

The results obtained can be summarized within the


the following conclusions:

a) The lighting in the selected classroom cannot be


sufficiently illuminated by daylight alone as
daylight cannot provide the required lighting
intensity.
b) Combined lighting values as well as artificial
lighting values meet the required minimum.
Hence, with lighting units turned on, the required
limit values are met.
c) The obtained values of artificial lighting are
sufficient, as none of the values dropped below
500 lx.
d) The amount of daylight measured by the daylight
illumination coefficient appears to be sufficient
Figure 8. 3D model of the classroom and the proposed
lighting.
because 3 of the values have fallen below 1, 5.
This means that the space is not provided with
sufficient light for mental and physiological
influences as well as for contact with the outside
environment. If, for some reason, lighting is
higher than daylight, the lighting of daylight
must be supported by artificial lighting, which is
not considered as combined lighting.
e) Optimal working temperature in the room met
the required parameters for temperature –
humidity microclimate for cooler seasons (from
18 °C to 26 °C).
f) Required relative air humidity in the classroom
in cooler seasons should amount to 30 % -70 %.
Our values are between 30,3 % to 35,9 % which
means the humidity requirements have been met
as well.

834 TEM Journal – Volume 7 / Number 4 / 2018


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

It is necessary to mind the ceiling lighting sources Acknowledgements


besides external daylight, considering that the values
of daylight alone without using the support of any This article was supported by the Grant Agency
artificial light did not meet the required lighting Ministry of Education SR KEGA - project no.
intensity and required value of daylight illumination 014UKF-4/2016.
coefficient. Especially in winter months, daylight
alone is not sufficient and needs to be supported by References
artificial lighting sources in order to prevent visual
fatigue and other health issues. [1]. Nevrklová, J., (2017). Světlo pro naši budoucnost.
The natural light penetration into the classroom Světlo, 6 (12).
must be ensured by regularly cleaning the covers of [2]. Kotus, M., Bujna, M., (2015). Bezpečnosť a ochrana
zdravia pri práci. Nitra: SPU, 2015. 148 p.
the lighting systems and window openings, [3]. Šolc, M., Kliment, J., Divoká, A. & Forrai, F.,
maintaining clean wall surface, ceiling and floor. (2017). Faktory ovplyvňujúce kvalitu a bezpečnosť
Designers, teachers and all people who are pracovného prostredia doktoranda pri realizovaní
involved with educational environments must experimentov. In. Doktorandské štúdium - súčasný
consider the lighting and controlling it. Physical area stav a perspektívy. Prešov : pp. 82-97.
in designing is very important and lighting is one of [4]. Lalonde, M., (1974). A new perspective on the health
the most important features in physical area in all of Canadians. Ottawa, ON: Minister of Supply and
environments especially in educational and working Services Canada. Retrieved from Public Health
environments [29]. Despite the fact that good lighting Agency of Canada website: http://www.phac-
makes workspace more efficient, the lighting system aspc.gc.ca/ph-sp/pdf/perspect-eng.pdf
[5]. Veitch, J. A., & Newsham, G. R. (1998). Lighting
is always regulated by the human factor. Modern
quality and energy-efficiency effects on task
technologies already offer lighting based on natural performance, mood, health, satisfaction, and
daylight. For example, the light is automatically comfort. Journal of the Illuminating Engineering
adjusted by the control system. The sensor inside Society, 27(1), 107-129.
measures the daylight amount and maintains the [6]. Bellia, L., Bisegna, F., & Spada, G., (2011). Lighting
lighting level for a given time, depending on daylight in indoor environments: Visual and non-visual effects
availability which guarantees energy savings. of light sources with different spectral power
Different scenarios (with varying degrees of distributions. Building and Environment, 46(10),
chromaticity and light intensity ratios) are presented 1984-1992.
in the control system [1]. [7]. Boubekri, M., (2008). Daylighting, Architecture and
Health, NY: Architectural Press, 143 p.
[8]. Shishegar, N., & Boubekri, M. (2016, April). Natural
5. Conclusions light and productivity: Analyzing the impacts of
daylighting on students’ and workers’ health and
Good lighting is a key to creating successful living, alertness. In Proceedings of the International
working and learning environment, and is necessary Conference on “Health, Biological and Life
to ensure safety, as well as, well-being, health and Science”(HBLS-16), Istanbul, Turkey (pp. 18-19).
quality of life. By objectivizing the lighting, we [9]. Wells, B. W. P. (1965). Subjective responses to the
pointed out the deficiencies in the internal lighting installation in a modern office building and
environment of the university classroom. A major their design implications. Building Science, 1(1), 57-
shortcoming in the design of the classroom is due to 68.
another building being immediately adjacent to the [10]. Manning, P., (1967). Windows, environment and
researched building. This causes shadowing and people, Interbuild/ Arena, 20-25 (Oct. 1967).
[11]. Markus, T.A., (1967). The significance of sunshine
insufficient daylight flow into the room even though
and view for office workers, in Sunlight in buildings,
the daylight coefficient met the required values. At Proc. CIE conference, Rotterdam, 59-93.
the moment, only alternative solutions can be taken, [12]. Cuttle, C. (1983, June). People and windows in
which can bring not only light comfort but also workplaces. In Proceedings of the people and
energy savings. However, other parameters such as physical environment research conference,
humidity, air flow, temperature, noise or chemical Wellington, New Zealand (pp. 203-212).
factors are very closely related to the building's [13]. Heerwagen, J. H., & Heerwagen, D. R. (1986).
suitability. Therefore, improving the lighting is Lighting and psychological comfort. Lighting Design
important, however, at the same time, maintaining and Application, 16(4), 47-51.
the classroom with both appropriate air conditioning [14]. Veitch, J. A., & Newsham, G. R. (1998). Lighting
quality and energy-efficiency effects on task
and regeneration systems is necessary, so that the
performance, mood, health, satisfaction, and
inner environment well-being, impacts the comfort. Journal of the Illuminating Engineering
performance of the student and the teacher positively, Society, 27(1), 107-129.
and does not result in discontent.

TEM Journal – Volume 7 / Number 4 / 2018. 835


TEM Journal. Volume 7, Issue 4, Pages 829-836, ISSN 2217-8309, DOI: 10.18421/TEM74-21, November 2018.

[15]. Aldworth and Bridgers, D., (1971). Desing variety in [22]. STN 73 0580-1/Z2 .(2007). Daylighting in buildings.
lighting. Lighting research and Technology, 3, 8-23. [23]. Regulation MZ SR n. 541/2007 Z. z. about details
[16]. Collins, B., (1990). The Psychological Aspects of and requirements for lighting during work.
Lighting: A Review of the Work of CIE TC3.16. [24]. Vychytil, J., (2015). Stavební světelná technika.
Gaithersburg, MD: National Institute of Standards ČVUT Praha 2015,158 p.
and Technology. [25]. Buday, F., (2012). Požiadavky na osvetlenie pri
[17]. Ludlow, A. M. (1976). The functions of windows in práci.
buildings. Lighting Research & Technology, 8(2), http://www.aos.sk/spe/seminare/spe_2012/08_buday_
57-68. bp2012.pdf
[18]. Veicht, J. A., (1993). End user knowlage, beliefs, and [26]. DIALux v 4.6, DIAL GmbH, (2008). from
preferences for lighting. Journal of Interior design, http://urlm.co/www.dial.de
19, 15-16. [27]. STN EN 12464-1 .(2012). Light and
[19]. Tureková, I., Lukáčová, D. & Bánesz, G., (2017). lighting.Lighting of work places. Part 1:Indoor work
Monitoring of lighting in a school classroom. In: places.
WOS 2017. Proceedings from 9h International [28]. Stanko, L., (2017). Objektivizácia vnútorného
Conference on the Prevention of Accidents at Work, prostredia vo vysokoškolských učebniach.
Prague, London: Taylor&Francis, 339-344. [Bakalárska práca]. PF UKF 2017. 58 p.
[20]. Moore, T. (1998). Harvesting daylight inside [29]. Knez, I., & Kers, C. (2000). Effects of indoor
buildings. EPRI Journal, 23(4), 18-19. lighting, gender, and age on mood and cognitive
[21]. Kaňka, J. (2016) Požadavky na denní osvětlení performance. Environment and Behavior, 32(6), 817-
budov. TZB journal online: http://stavba.tzb- 831.
info.cz/denni-osvetleni-a-osluneni/15093-pozadavky-
na-denni-osvetleni-budov

836 TEM Journal – Volume 7 / Number 4 / 2018

You might also like