TECHNICAL PARTICULAR AND GUARANTEE

TPG 02 : 150 kV CIRCUIT BREAKER - 3 POLE OPERATION MECHANISM

No DESCRIPTION UNIT PROPOSED AND GUARANTEE

1 Manufacturer Name ABB

2 Type Name LTB170D1/B

3 Standard IEC 62271-100 and IEC 62271-1

4 Service condition Outdoor, Tropical area

5 Type of Circuit Breaker Live Tank

6 Type of arc quenching medium SF6

7 Number of phases 3

8 Rated voltage (Ur) kV 170

9 Rated frequency (Fr) Hz 50

10 Rated normal current (Ir) A 3150

11 Rated short-time withstand current (I th) kA 40

12 Rated peak withstand current (I p) kA 2.5 x I th (100)

13 Rated duration of short circuit s 3

14 Rated Insulation level :


- Power frequency withstand voltage, dry for 1 minute
Phase to earth, between the phases and across the open breaker gap kV 325
- Impulse withstand voltage (at 1.2 / 50 µs)
Phase to earth, between the phases and across the open breaker gap kV 750

15 Minimum creepage distance mm/kV 31 (as per BoQ)

16 Operating sequence and operating duty


- Nominal sequence (Rapid auto-reclosing / dead time) O - 0.3s - CO - 180s - CO
- Out of phase O - CO

17 Rated making and breaking current to Normal / Reclose


- Making current kA 2.5 x I th (100)
- Breaking current (symmetrical) kA 40
- % DC component % 52

18 Breaking current under out of phase condition kA ≥ 25 % x I th

19 Rated capacitive switching currents N/A

20 Radio influence voltage level, measured at 1.1 Ur/√3 at 1 MHz


- Circuit closed to ground µV < 2500
- Circuit breaker open, grounded terminal µV < 2500

21 Classes
- Electrical endurance E1
- Transient recovery voltage 291 kVpeak
- Mechanical endurance M2
- Restrike performance C2

22 Temperature rise at :
- Contacts in SF6 K ≤ 65
- Connection, bolted or equivalent in SF6 K ≤ 75
- Terminal K ≤ 65
23 Number of interrupters in series per phase pcs 1

24 Number of tripping coils per phase pcs 2

25 Number of closing coils per phase pcs 1

26 Operating mechanism :
- Type Motor spring
- Number of stored energy operation 1 (one per three phase)

27 Protection level of control cubicle IP 55

28 Supply voltage :
- Control voltage VDC 110
- Tripping and closing coils VDC 110
- Motor voltage VAC 230
- Heater VAC 230

29 Tolerance range for auxiliary supply voltage


- Tripping coil % 85 - 110
- Closing coil % 85 - 110
- Motor % 85 - 110

30 Mechanical performance
1. Total break time (trip initiation to final arc extinction) ms ≤ 40
2. Opening time (trip initiation to contact separation) without current ms ≤ 22
3. Time interval between opening of interrupters of first and last phase ms ≤4
4. Time interval between opening of interrupters of one phase ms N/A
5. Closing time without current ms ≤ 40
6. Time interval between closure of interrupters of the first and last pole ms ≤ 10
7. Time interval between closure of interrupters of the one phase ms N/A
8. Time from extinction of main arc to contact make during auto-reclose ms ≤ 300

31 Number of auxiliary contacts (NO/NC) per pole pcs 8NO + 8NC

32 Discrepancy device N/A

33 Anti-pumping device Yes

34 Method of controlling voltage distribution between break unit N/A

35 Method of closing control N/A

36 Value of closing resistor Ohm N/A

37 Insertion time of closing resistor ms N/A

38 SF6 Pressure indicator per pole pcs 1

39 Counter to record number of operation per set pcs 1

40 Seismic acceleration constant consideration g 0,3

41 Leakage rate of SF6 gas per annum % ≤ 0.5

42 Contact resistance across main contacts per phase µ Ohm ≤ 40

43 Number of switch operations between two inspections for changing the


main-contacts :
- With rated continuous current 5000
- With rated breaking current 10

44 Material of insulator Porcelain

45 Minimum clearance in air :


- Between phase mm refer to dimension drawing
- Phase to earth mm refer to dimension drawing
- Live conductor to ground level mm refer to dimension drawing
- Live insulator to ground level mm refer to dimension drawing