Special Equipment Type Test Report
No. T3-311-07-014
Category of Equipment: — Passenger Lifts
Type of Equipment: Traction Passenger Lifts
Name of Product: Passenger Lifts
Model of Product: MMR
Applicant: Sigma Elevator Co., Ltd.
Manufacturer: Sigma Elevator Co,, Ltd.
Testing CenterNETEC
No.T3-311-07-014
National Elevator Inspection and Type Test Report e
Page 1 of 16
Testing Center
Name of product | Passenger lifts
Model of product | MMR
Serial No, of sample | 2006F6014E07 Production date | 2008-07-03
Main technical Rated speed 2.60mvs
parameter Rated load 1000kg
Name | Sigma Elevator Co.,Ltd,
Applicant eens No.2 Songlan Street, Economic & Technical Development Zone,
Dalian, Liaoning
Name | Sigma Elevator Co,, Ltd.
‘Manufacturer No.2 Songlan Street, Economic & Technical Development Zone,
Address,
Dalian, Liaoning
a 19 #, Xiangzhou Garden Hotel, Dalian, Liaoning
‘Test place | 19 #, Xiangzhou Garden Hotel, Dalian, Liaoning
Sample state | Normal
Testdate | 2007-03-22 Test category | Type test
Test condition | Comply with requirement Testitem | All applic:
items
Rules for Type Test of Elevators (yout)
Test basis | Rule for Type Test of Traction and Positive Drive Lifts (tryout)
GB 7588-2003, EN 81-1:1998
The type test is certificated.
Test
conclusion
Note First issued date of the Chinese versi
Reported by: (es Verified by: eh Issued wm LeipNETEC
National Elevator Inspection and Type Test Report Pea 4H
Testing Center
Test items Test results |Conctusions|
_[ Comply with requirements | Pass
| Model, markings, install posi
switches
‘Safeguard of main switches in the open
Comply with requirements | Pass
3 | 1.3. | position, to ensure no inadvertent Comply with requirements | Pass
‘operation
(in the cage of & group of lis)After the
4 | 1.4 | opening of the main switcher, parts of 1 1
circuits remain live
5 | 15 | Connection of any capacitors to correct 7 7
the power factor
‘The electric lighting supplies to the car,
the well, the machine and pulley rooms
The supply and type to socket outlets
7 | 22 | required on the car roof, in the machine 1 /
and pulley rooms and in the pit
‘A switch for lighting and socket outlets of
the lift car
Lighting switches in the machine or pulley
6 | 24 ‘Comply with requirements | Pass
‘Comply with requirements | Pass
24 Pass
yo | 25
Comply with requirements | Pass
Short circuit protection of each circult
11 | 2.6 | controlled by the switches laid down in | Comply with requirements | Pass
23~25
12 | 3.1. | Rhase break and reversal protection Comply with requirements | Pass
13 | 32 | Stopping device Comply with requirements | Pass
14 | 3. | Stopping device in the car(n the car of lis 7 :
‘3 | with docking operation)
15 | 3.4 _| Type of stopping device Comply with requirements | Pass
40 | 44 | Motor supplied and controlled directly 7 7
| 44 |fromacordc. mains .
‘Ac. or dc, motor supplied and controlled
Boosie eee eee Comply with requirements | Pass
qo | 49 | Motor supplied and controlled using a 7 7
3 | ‘Ward-Leonard’ system
He aa poree geen ce ae acne stopping | Comply with requirements | Pass
20 | 5.1 _| Working state of the brake Comply with requirements | Pass
21 | 52_| Controling of the brake Comply with requirements | Pass
22_| 53 _| Brake without supplementary delay ‘Comply with requirements | Pass
When the motor of the lifts likely to
5.4__| function as a generator, protecting against i
23 | 54 | electric device operating the brake tobe | COmPIY with requirements | Pass
fed by the driving motor
2a | 9a | Protecting against overioads of motors 7 i
(directly connected to the mains)
Protecting against overloads of motors
25 | 6.2 | basis of increase of the temperature of the | Comply with requirements | Pass
motor windingsNETEC
National Elevator Inspection and
Testing Center
Type Test Report
No,T3-311-07-014
Page 6 of 16
Marks of some connection terminals
56 | 10.8 | remain lve after the opening of the main | Comply with requirements | Pass
switch or switches of a lift
37 | 109 | Connectors and devices of the plugin 7 7
-S | type placed in safety circuits
58 | 41.4 | Controt of lit operations Compiy with requirements | Pass
59 | 11.2 | Type test of lift control cabinets Comply with requirements | Pass
Control of leveling and re-leveling with
60 | 1? | doors open fi id
aoe Inspection speed: 0.30m/s
61 | 43.1 | Controt of inspection operation Cony wif ecuitemants |_P388
Special switches for controlling the
62 | 132 | mechanism of doors from the car roof _| Comply with requirements | _ Pass
63 | tac | Cento devi to prevent ovelondin the | Comp wth requements| Pass
“64 | 14.2 | State of the lift in the event of overioad | Comply with requirements | Pass
Priorities and signal for lifts with manual
65 | 15.1 | coon ’ 1
66 | 452 | Priorities of no-collective control 7 7
67 | 15.3 | Landing signal in the case of collective | Compy with requirements | Pass
68 | 46.1 | Controt of docking operation 7 7
Height between the landing door header
69 | 16.2 | and the floor of the ear or landing door ! 1
state in the case of docking operation
70 | 47.4_| Device for manual emergency movement _{ Comply with requirements | Pass
Mark of device for manual emergency ith reaui
71 | 172 | Movement | Comply with requirements | Pass
72 | 17.3 | Epectic safely device of he removable | Comply with requirements | Pass
Mark checking easily from the machine
73 | 17.4. |.room whether the cars in an unlocking | Comply with requirements | Pass
zone
74 | 47.5 | Control of emergency electrical operation 7 7
75 | 16.1 | Emergency alarm device in the car | Comply with requirements | Pass
76 | 18.2 | Power for emergency device Comply with requirements | Pass
77 | 48.3 | Type of emergency alarm device in the car | Comply with requirements | Pass
‘An intercom system, or similar device
78 | 18.4 | between inside the car and the machine | Comply with requirements | Pass
room if the lit travel exceeds 30m
‘Alarm device for persons working in the reer
79 | 188 | eo aing tapped Comply with requirements | Pass
80 | 49.1 | One machine of each lif own Comply with requirements | Pass
81 | 19.2 | Drive methods Traction drive Pass
This brake on ils own shall be capable of zi
stopping the machine when the caris Average retardatior
82 | 193 1.261mls' Pass
travelling downward at rated speed and | coma wath reecirements
with the rated load plus 25% ee ‘a
Average retardation
Let. 642mis
83 | 19.4 | Rated load one set braking action test Retseime? Pass
Comply with requirementsNETEC.
National Elevator Inspection and
Testing Center
Type Test Report
No.73-311-07-014
Page 7 of 16
“Tripping speed of an overspeed governor
110 26.2 | for a counterweight or balancing weight t 1
safely gear
“Tensile force inthe overspeed governor
111 | 26.3 | rope produced by the governor, when Pull force: 300~350N | Pass
tripped
‘Tensioning of overspeed governor rope or
412] 28.4 | guiding of tensioning pulley(or ts Comply with requirements | Pass
tensioning weight)
Electric safety device for breakage or
113| 26.5 | excessive rope stretch of he governor | Comply with requirements | Pass
rope
‘Seal of adjustable parts or mark of rotation i A
114 | 26.6 | Srelion on the erate fed governor Comply with requirements | Pass
Electric safety device for overspeed
115 | 26.7 jose does not automatically reset Comply with requirements | Pass
itself
116 | 26.85 Revereoen foverneriiin 7 Comply with requirements
117 | 26.9 | Overspeed governor located in the well 7
116 | 26.10 | Type test of overspeed governor ‘Comply with requirements
119 | 27.1 | Safety gear capable of operating in the car
27:
jownward di
ype of safel
Comply with requirements
Progress
‘Type of safely gears, ifthe car carries,
124 | 273 | coveral safely gears 7 i
‘Safely gear of counterweight weight or
122 | 27-4 | balance weight 7 fe
‘Control for tripping safely gear of the car,
123 | 27.5 | counterweight weight or balance weight _ | COmPY with requirements | Pass
Inclination of the car floor, when the car
124| 27.6 safety gear operates | Comply ‘with requirements: Pass
125 | 27.7_| Release of safety gear has tripped Comply with requirements | Pass _|
126 | 27.8 ee safety device of safety gear on the Comply with requirements Pass
127| 27.9 | Safely gears shall not be used as guide | Comply with requirements | Pass
128 | 27.10 | Seal of adjustable safety gear Comply with requirements | Pass.
‘Matching of parameter between the safely
429 | 27.14 gear and the lift Comply with requirements | Pass
130 | 27.12 | Type test of safely gear Comply with requirements | Pass
131 | 28.1_| Position of buffers Comply with requirements | Pass
132 | 28.2 | Type of buffers Energy dissipation buffers Pass
193 | 28.3 | Stroke of reduced buffers L 7
134} 28.4 Monitoring the normal slowdown of the 1 1
4 | machine in case of reduced buffer stoke |
135) 28.5 | Matching of parameter between buffer | Comply with requirements | Pass
136 | 28.6 | Type test of buffer Comply with requirements | Pass
is 126.14 | aconaine oor oversnere Broan Comply with requirements | Pass
438) 29.2 Action place of ascending car overspeed Traction sheave Pass
protection means
hNETEC
73-311
National Elevator Inspection and Type Test Report Nove 8 of 18
Fixing of glass door panels, dimensions of
165 | 33.1 | glass, pendulum shock test of glass door i i
766 | 33.2 | Fixing of glass in doors He] 7 feet
167 | 33.3 | Type test of glass door 7 1
Request to avoid the risk of shearing
168 | 34.1 | during operation in case of automatic | Comply with requirements | Pass
power operated sliding doors
Force to prevent the door closing in case
469 | 34.2 | of automatic power operated horizontally ‘80N Pass
sliding landing doors or car door
170| 34,3 | Re-opening protective device of landing
gone aad ear dose Comply with requirements | Pass
Opening force for folding landing doors
Testing Center
474] 34.4 | and car door of automatic power operated 1 ’
horizontally sliding
| Conditions of power closing of vertically
172 345 | gliding tanding doors and car door 7 i
173:| 34.6 | Prevent of other types of doors t f ;
Reversal of closing movement of car door
17 On ee tone onertea Comply with requirements | Pass
Request of landing doors with manual
175| 40 | Reaves 1 1
176 | 34.9 | Striking stops of hinged doors o 1
Distance between any outer edge of the
177 | 94-10 | folding door and the recess 7 i
17a | 35a | Operation with landing doors open in | Unlocking zone: £0.270m | pac -
1 | normal operation or unlocking zone Comply with requirements
Safety prevention of landing doors open : |
17a} s62 | Satsly prevention ot Comply with requirements | Pass 4
Effective locking of the landing door 5
180 | 35.3 | preceding the movement of the car or Comply with requirements | Pass tee
electric safety device of proving locking
181 Engaged length of the locking elements | Engaged/ength: 10mm | pass
Comply with requirements |_
Element of the electric safety device
182 | 35.5 | proving the locked condition of the door Comply with requirements | Pass
panels or connection of locking element ce
183 | 35.6 | Locking request for hinged doors 7 1
4e4| 36,7 | Effect and maintained of the locking action
oflanding doors Comply with requirements | Pass
185 | 35.8 | Protection and inspection of lock device _ | Comply with requirements | Pass
Type request of the fixing screws for the
‘cover in the case where the lock contacts
186 | 36.9 Comply with requirements | Pass
187 | 35.10 | OPen or automatic closing of landing
idhoed iets Comply with requirements | Pass
Electrical safely device for proving the
188 | 36.17 | closed condition of the landing door
‘Comply with requirements | Pass
Devices for proving the locked condition
189 | 35.12 | and the closed condition of the landing | Comply with requirements | Pass
door coupled with car door ‘
Place of electrical safety device for
190 | 35.13 | proving the closed condition of the hinged ! 1
landing doorNETEC
No.T3-311-07-014
National Elevator inspection and Type Test Report page 11 of 18
Testing Center
Ee Width: 1000mm_ See
; : Angle: 65°
216 | 40.5 | Fitting of apron of car sil Pinecion ssa Pass
Vertical height: 760mm.
inthe case of a lift with a docking
217| 40.6 | operation, the height of the vertical portion I I
of apron
Dimension of an emergency trap door in
218 | 41.4 | tho car roof 7 ee
219 | 47.2 | Dimension of emergency doors in the car 7 1
Request for emergency trap doors or
220} 41.3 doors f He
221 | 42.1 | Request for glass roof ft
222 | 42.2: | Clear area for standing ef 71.60x0.60m? | ‘Pass.
223 | 42,3 | Balustrades of car roof Comply with requirements: Pass:
224 | 42.4 | Composing or height of balustrades ‘Comply with requirements | Pass
225 | 42:5 | Place of handrail and balustrades Comply with requirements | Pass.
226 | 42.6. | Protection of pulleys fixed to the car___| Comply with requirements | Pass
Gap between the car roof and the header
227 | 42.7 | oF a landing door ! !
228| 43.1 ee area of cars with imperforate Comply with requirements | Pass
229 | 43.2 | Place of ventilation apertures ‘Comply with requirements | _ Pass
; Light intensity: 60x
230 | 43.3 | Lighting and light intensity of the car Comply with requirements, Pass
231 | 43.4 | Request for the incandescent ype Daylight lamp. 7
232, | 43.5 | Condition to switch off car lighti ‘Comply with requirements [Pass
233 | 43.6 | Capacity of emergency lighting supply __| Comply with requirements | Pass
234 | 44.1 | Balancing weight 7 T
235 | 44.2 _| Fixing for filer weights ‘Comply with requirements | Pass
Protection of pulleys fixed fo the :
236 | 44.3 | Cinterveight Comply with requirements | Pass
Distance of the car and ils associated
. | components and the counterweight (or
237 | 44.4" | balancing weight) and its associated ia -
components
‘Guidance of car, counterweight or
238 | 45.1 balancing weight Comply with requirements | Pass
239 | 45.2 | Type of guide rail Machined Pass
Selection of guide rails for counterweight i
240 | 48.3 | or balancing weight without safety gear Type i
‘Adjustment of fixing of guide rails fo thelr
brackets and to the building,
241 | 45.4 | compensation of effects due to normal | Comply with requirements | Pass
setting of the building or shrinkage of
concrete
Max. calculated permissible deflections
242) 45.5 for T-profile guide rails Comply with requirements | Pass
243 | “45.6 _| Type test of guide rails ‘Comply with requirements | Pass
244 | 46.1 | Partition of lift well and around area ____| Comply with requirements | Pass.
245 | 46.2 | Exclusive use of the lift well Comply with requirements | PassNETEC
No.T3-311-07-(
National Elevator Inspection and Type Test Report page 13 of 16
Testing Center
[268 | 52.2 | Method to enter pit ~___ [Comply with requirements | Pass |
‘Space between the bottom of the pitand |
269 | 62.3 | car when the car rests on its fully Comply with requirements | Pass
compressed buffers
270 | 83 _| Intensity and lighting ofthe well 50h Pass |
Setting for lit machines, their associaled
at] 6 |S coe Comply with requirements | Pass |
Condition for inataling traction sheave in |
272| 54.2. | Condi ’ /
Headroom of the well or diverter pulleys
273 | 54.3 | be installed above the car roof id a
274 | 54.4 | Temperature of the machine room Comply with requirements | Pass
275 | 545_| Metal supporis or hooks in the mac Comply with requirements | Pass
276 | 5q/62| Temperature ofthe pulley room, measure ; Fi
for preventing frost or condensation __|
‘Access to the interior of the machine and
277 | 55st
aes Comply with requirements | Pass
278| 55.2 ae access for persons to machine and | Comply with requirements | Pass
—|~ Machine room door
279| 56.3. | Doors and trap doors of machine room ‘Width: 1,000 Pass
Height: 4,600m
280 | 56.4 | Doors and trap doors of pulley room 7
201 | 65.6" | Dimensions of holes inthe slab, machine |“ Ferrie height 8omm | Pass
and pulley rooms floor
Clear height at working areas or clear
282| 56.1 | horizontal area for manual emergency _| Comply with requirements | Pass
operation
Clear height in machine room or width of Flaight 2:500m
283 | 56.2 | the access wa Width: 4.200m ica
‘Clear vertical distarice above the rotation i
224] 563 | Core ofthe machine Vertical distance: 1.200m | Pass
285 | 66.4 | Dimensions of pulley room 7 7
286 | 68.5 | Height or working area of pulley room 7 T
287 |_57.1- | Ventilation of machine room [Comply with requirements | Pass
288 | 67.2" | Lighting of machine room 240K Pass
289 | 57.3 _| Lighting of pulley room I 1
200 | 58.1 | ltal requests for labels, notices,
markings and operating instructions __| Comply with requirements | _ Pass
201 | 58.2 | Labels in the car Comply with requirements | Pass
292 | 68.3 | Operating directions or display in the car_| Comply with requirements | Pass
293. Permanent markings of walls or doors 1 1
3 | with glass E
294 Especial function or instructions in the car | PEELE 7
295 | 58.6 | Operating instructions on the car roof Comply with requirements | Pass
Notices ofthe main switeh(es) several RS | cormcyy wth requirements | Pass
296 | 58.7 | and light switch (es)
297| 58.8 Program or explaining about emergency
operation in the machine room
208 | 58.9 Max. permissible load on the lifting beam
= cor hooks in the machine room.
299 | 58.40 | Stopping device in the pulley room t 1
Comply with requirements | Pass
Comply with requirements || PassNETEC No.73-311-07-014
National Elevator Inspection and Type Test Report page 18 of 16
Testing Center
Appendix 1 Test data of running speed and balance coefficient
1.1 Running speed
Direction
Up |Down} Up [Down] Up Down} Up Down} Up jown! Up |Oown} Up |Down|
tems
% ° 2 100 M0
Load
kg ° 240 400 500 740 ‘1000 1100
Vottage V ¢].993 | 290 | 393] aot] as2 | 92] 392] 302] sat] 302] a0] 302] 989] 302
3|
cuenta] 03 | 272] 02 }183 } a2 |er | as | a7 [163 | 02 |s03 | o2 | 353 | o2
Motor speed
a
1 timin
Running epood
ys mis
245 | 247 | 2.47 | 2.46 | 2.48 | 2.48 | 2.47 | 2.48 | 2.48 | 2.47 | 2.47 | 2.48 | 247 | 247
1.2 Balancing coefficient
Balance coefficient: 0.49
40 : —-
36 1
30 :
26 +
Zw»
B
& -
8 9 L je
0 10 2 3 49 50 60 70 8 99 100 110
toad (%)“ MA
CNAS L0454 20080007082 (2008) 1HiAMIA# (134)
Certificate of Type Test For
Special Equipment
No. TX 3110-003-07 0014
Applicant's name and ‘Sigma Elevator Co., Ltd.
address: No.2 Songlan Street, Economic & Technical
Development Zone, Dalian, Liaoning
Manufacturer's name Sigma Elevator Co., Ltd.
and address: No.2 Songlan Street, Economic & Technical
Development Zone, Dalian, Liaoning
Name of product: Passenger lifts
Model and specifications: MMR
v=2.60m/s — Q=1000kg
Configuration of product: See annex
Type test report No.: T3-311-07-014
This certificate is valid for products of the models and specifications below
(without change of the configuration of the product):
Modol: MMR
For passenger lifts, observation lifts and hospital lifts whose rated speeds are
not more than 2.50m/s and rated loads are not more than 1600kg.
After type test, this product is accord with the Rules for Elev:
(tryout), GB 7588-2003 and EN 81-1:1998.
ee
lesuo date: Zale!
First issued date of the Chinese verdigif} ApH’ 22, 2007
Note:
1. This certiicate is to confirm the products on type and the tested sample on conformity, only valid for the
products that are in conformance with the tested sample mentioned above,
2, The holder of this certificate has responsibilies to ensure that the products conform to the requirements of the
‘codes and regulations, and to ensure that the products are consistent withthe tested sample mentioned above,