SUPREME

Low Voltage
PVC INSULATED Cables

NYY 0.6/1(1.2) kV
SPLN 43-1/IEC 60502-1
Copper conductor, PVC insulated and PVC sheathed cable

DIMENSIONAL & MECHANICAL DATA 2 Cores

Nominal Thickness Approximately


Nominal cross- Bending radius Standard
No of wire and conductor shape
sectional area Overall min delivery length
Insulation Outer sheath Net Weight
diameter
mm2 pcs - mm mm mm Kg/Km mm m
1.5 1 re 0.8 1.8 12 205 150 1,000
1.5 7 rm 0.8 1.8 13 213 160 1,000
2.5 1 re 0.8 1.8 13 243 160 1,000
2.5 7 rm 0.8 1.8 14 259 170 1,000
4 1 re 1.0 1.8 15 326 180 1,000
4 7 rm 1.0 1.8 16 351 200 1,000
6 1 re 1.0 1.8 16 390 200 1,000
6 7 rm 1.0 1.8 17 422 210 1,000
10 1 re 1.0 1.8 18 514 220 1,000
10 7 rm 1.0 1.8 18 557 220 1,000
16 7 rm 1.0 1.8 21 744 260 1,000
25 7 rm 1.2 1.8 24 1,066 290 1,000
35 7 rm 1.2 1.8 26 1,342 320 1,000
50 19 rm 1.4 1.8 30 1,735 360 1,000
70 19 rm 1.4 1.9 33 2,331 400 1,000
95 19 rm 1.6 2.0 39 3,159 470 1,000
120 37 rm 1.6 2.1 42 3,829 510 1,000
150 37 rm 1.8 2.2 46 4,667 560 500
185 37 rm 2.0 2.4 51 5,805 620 500
240 61 rm 2.2 2.6 58 7,482 700 500
300 61 rm 2.4 2.7 64 9,253 770 500

ELECTRICAL DATA
Resistance at 20 ºC
Current Carrying Capacity at 30 ºC
Nominal cross-sectional Short circuit current of
area conductor at 1.0 sec
DC conductor max Insulation min
In AIR In GROUND

mm 2 Ω/Km MΩ.Km A kA
1.5 12.1 50 21 27 0.19
2.5 7.41 50 29 36 0.32
4 4.61 50 38 47 0.50
6 3.08 50 48 59 0.73
10 1.83 50 66 78 1.20
16 1.15 40 90 102 1.91
25 0.727 40 120 134 2.96
35 0.524 40 150 160 4.13
50 0.387 30 180 187 5.87
70 0.268 30 230 230 8.19
95 0.193 30 275 280 11.09
120 0.153 30 320 320 13.98
150 0.124 20 375 355 17.46
185 0.0991 20 430 409 21.50
240 0.0754 20 510 472 27.86
300 0.0601 20 590 525 34.79

2
www.sucaco.com