Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

Design Guide DG022002EN Effective February 2020

Medium-voltage power distribution and control systems > Switchgear >

VacClad-W 26" wide, metal-clad


medium-voltage drawout vacuum breakers

Contents
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-2
Usual and Unusual Service Conditions . . . . . . . . . . . . 5.2-3

Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-4
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-4
Protective Relays and Metering. . . . . . . . . . . . . . . . . . 5.2-5
Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . 5.2-5
Integral Motorized Remote Racking Option
(VC-W MR2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-10
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-11

Layouts and Dimensions . . . . . . . . . . . . . . . . . . . . . . . 5.2-14


Standard Layouts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-14

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-18


Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-18
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-18
Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-19
Heat Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-19
Typical Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-20

More about this product


Eaton.com/mva

Complete library of design guides


Eaton.com/designguides
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
General Description 5.2-2

General Description Application Description 26.00-Inch (660.4 mm) Wide


This narrow width VacClad-W MV Low Profile Model
Metal-Clad switchgear was designed In addition to the floor space saving
26.00-Inch (660.4 mm) Wide for use in instances where floor space offered by the standard 26.00-inch
5 kV 250 MVA Switchgear requirements would not allow the (660.4 mm) wide model, a further saving
industry standard 36.00-inch (914.4 mm) in the height and depth of the switchgear
wide switchgear. Typical applications is also available. Where height and
include not only new construction depths are an issue, such as an outdoor
but also replacement switchgear for powerhouse or in a mobile power
installations previously equipped with container, the standard 95.00-inch
26.00-inch (660.4 mm) wide air-break (2413.0 mm) high unit can be reduced
devices. This line of switchgear has also to an 80.00-inch high (2032.0 mm),
been used where 5 kV, 1200 A, 250 MVA 72.00-inch (1828.9 mm) deep low profile
applications are commonplace, such as model. Main bus rating available in the
generator and control applications. 80.00-inch (2032.0 mm) high x 72.00-inch
(1828.9 mm) deep low profile model is
limited to 1200 A maximum. It is not
Ratings compatible in size or location with
The 26.00-inch (660.4 mm) wide switch­ standard 26.00-inch (660.4 mm) wide or
gear line is designed for use with Eaton’s 36.00-inch (914.4 mm) wide, 95.00-inch
Type VCPW-ND “Narrow Design” vacuum (2413.0 mm) high VCP-W units.
circuit breakers rated 4.76 kV, 60 kV BIL,
The low profile model is designed to
250 MVA, 1200 A maximum, with
house breaker over auxiliary or auxiliary
rated main bus of 1200 or 2000 A. For
Fully Withdrawn Breaker over breaker, or auxiliary over auxiliary. In
installations requiring 2000 A main
order to provide maximum vertical space
breakers with 1200 A feeders, lineups
for power cable terminations, auxiliary
can be built with standard 36.00-inch
over breaker configuration should be used
(914.4 mm) wide main breaker cubicles
for customer’s top entrance cables, and
and 26.00-inch (660.4 mm) wide feeders.
breaker over auxiliary configura­tion
should be used for customer’s bottom
Configurations entrance cables. Auxiliary compartments
are designed to accom­modate one or
26.00-Inch (660.4 mm) Wide two auxiliary drawers.That is, up to four
Standard Model auxiliary drawers can be installed in an
auxiliary over auxiliary configuration. A set
The 26.00-inch (660.4 mm) wide design is
of two line-to-line or three line-to-ground
flexible. Available configurations include
connected voltage transformers, or a
breaker over breaker, one or two auxiliary
single-phase control power transformer
drawers over breaker, breaker over one
up to 15 kVA can be installed in each
or two auxiliary drawers, or up to four
auxiliary drawer. Because of the reduced
auxiliary drawers in one vertical section.
depth, control devices cannot be located
The standard height and depth are
on breaker compartment door. All
95.00-inch (2413.0 mm) and 96.25-inch
control devices should be located on
(2444.8 mm) respectively. A breaker
the auxiliary compartment doors.
Automatic Shutters over auxiliary, or auxiliary over breaker
Refer to Page 5.2-14 through
combination can be supplied in reduced
Page 5.2-18 for available configura-
depth of 86.25-inch (2190.8 mm).The depth
tions, dimen­sions and weights.
of breaker over breaker combination can
also be reduced to 86.25-inch (2190.8 mm) For all 26.00-inch (660.4 mm) wide
if power cables for top breaker enter from configurations, multifunction
the top and the cables for bottom breaker microprocessor-based relays and
enter from the bottom. meters, such as Eaton’s E-Series
relays and Power Xpert® meters are
The main bus location and connections
recommended for reduced panel space.
in the standard 95.00-inch (2413.0 mm)
high 26.00-inch (660.4 mm) wide design
are 100% compatible with standard
95.00-inch (2413.0 mm) high 36.00-inch
(914.4 mm) wide vertical sections. As
a result, additions to existing Eaton 5 kV,
250 MVA 36.00-inch (914.4 mm) wide
VCP-W installations can be simply and
rapidly performed without costly system
Fused PT Drawer modifications and transition sections.
Refer to Page 5.2-14 through
Page 5.2-18 for available configura-
tions, dimen­sions and weights.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
General Description 5.2-3

Usual and Unusual Applications at Frequencies Power Frequency and Impulse


Less Than 60 Hz Withstand Voltage Ratings
Service Conditions No derating is required for lower
Rated Short-Circuit Current frequency.
Based on series of actual tests performed
Usual Service Conditions on Type VCP-W circuit breakers and
Usual service conditions for operation CTs, VTs, Relays and Instruments
analysis of these test data and physics
of metal-clad switchgear are as follows: of vacuum interrupters, it has been Application at frequency other than
found that the current interruption rated frequency must be verified for
■ Altitude does not exceed 3300 feet each device on an individual basis.
(1000 m) limit for Type VCP-W circuit breakers is
proportional to the square root of the Table 5.2-3. Altitude Derating Factors
■ Ambient temperature within
frequency. Table 5.2-1 provides derating
the limits of –30 °C and +40 ºC factors, which must be applied to Altitude Above Altitude Correction Factor
(–22 °F and +104 °F) Sea Level in to be Applied to:
breaker interrupting current at various Feet (m) Voltage Rated
■ The effect of solar radiation is frequencies. Continuous
not significant Current
Table 5.2-1. Derating Factors
Interrupting Current    3300 (1006)
Applications Above 3300 Feet (1006 m)      (and Below) 1.0 1.0
Derating Factors
Equipment utilizing sealed interrupting    4000 (1219) 0.98 0.995
50 Hz 25 Hz 16 Hz 12 Hz
devices (such as vacuum interrupters)    5000 (1524) 0.95 0.991
does not require derating of rated None 0.65 0.52 0.45    6000 (1829) 0.92 0.987
maximum voltage. The rated one-minute    6600 (2012) 0.91 0.985
power frequency withstand voltage,    7000 (2137) 0.89 0.98
the impulse withstand voltage and the Rated Short-Time and    8000 (2438) 0.86 0.97
continuous current rating must be Close and Latch Currents    9000 (2743) 0.83 0.965
multiplied by the appropriate correction 10,000 (3048) 0.80 0.96
factor in Table 5.2-3 to obtain modified No derating is required for short time and 12,000 (3658) 0.75 0.95
ratings that must equal or exceed the close and latch current at lower frequency. 13,200 (4023) 0.72 0.94
application requirements. 14,000 (4267) 0.70 0.935
Rated Continuous Current 16,000 (4877) 0.65 0.925
Note: Intermediate values may be obtained by 16,400 (5000) 0.64 0.92
interpolation. Because the effective resistance of circuit
18,000 (5486) 0.61 0.91
conductors is less at lower frequency, 20,000 (6096) 0.56 0.90
continuous current through the circuit can
Applications Above or Below be increased somewhat. Table 5.2-2
40 °C Ambient provides nominal current rating for
Refer to ANSI C37.20.2, Section 8.4 VCP-W breakers when operated at Unusual Service Conditions
for load current-carrying capabilities frequencies below 60 Hz. Applications of metal-clad switchgear at
under various conditions of ambient other than usual altitude or temper­ature,
Table 5.2-2. Current Ratings
temperature and load. or where solar radiation is sig­nificant,
Rated Nominal Current at
require special consideration. Other
Continuous Frequency Below 60 Hz
Current at 60 Hz unusual service conditions that may
50 Hz 25 Hz 16 Hz 12 Hz
affect design and application include:
1200 A 1243 1410 1519 1589
2000 A 2075 2374 2573 2703
■ Exposure to salt air, hot or humid
3000 A 3119 3597 3923 4139 climate, excessive dust, dripping water,
falling dirt, or other similar conditions
■ Unusual transportation or
storage conditions
■ Switchgear assemblies when used
as the service disconnecting means
■ Installations accessible to the
general public
■ Exposure to seismic shock
■ Exposure to nuclear radiation

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-4

Circuit Breakers
Table 5.2-4. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K > 1) aabc
Identification Rated Values Related Required Capabilities
Circuit Voltage Insulation Current Rated Transient Current Values

Asymmetry Factor for VCP-W Breakers


Breaker Level Recovery Voltage
Type Maximum 3-Second Closing and

Rated Permissible Tripping Delay

Maximum Voltage Divided by K


Sym. Short- Latching

Lightning Impulse Withstand


Inter- Time Capability
Nominal 3-Phase MVA Class

Power Frequency Withstand


Rated Voltage Range Factor

Rated Short-Circuit Current


rupting Current (Momentary)
Rated Maximum Voltage

(at Rated Maximum kV)

Rated Interrupting Time


Capability Carrying
Nominal Voltage Class

Rated Reclosing Time


Capability

Voltage (1.2 x 50 µs)

Rated Crest Voltage

Rated Time to Crest

Recovery Voltage e
Rated Continuous
K Times Rated 2.7 K 1.6 K

Current at 60 Hz
Voltage (1 min.)
Short-Circuit Times Times

Rate of Rise of
Current d Rated Rated
Short- Short-
Circuit Circuit

Rated
Current Current

V Id E2 V/K KI KI 2.7 KI 1.6 KI h i


kV MVA kV Kd kV kV kA kV T2 Yf g kV kA kA rms S
Class Class rms rms Crest Amp rms Crest µS kV/µS Cycles Sec. ms rms kA rms kA rms Crest asym.

50 VCP-WND   4.16   250   4.76 1.24 19 60 1200 29   8.9 50 0.2 5 2 300   3.85 36 36   97 58 1.2
250
a 5 and 15 kV circuit breakers are UL listed. E2
e RRRV = 1.137
b Circuit breakers shown in this table were tested in accordance with IEEE T2
standard C37.09-1979.
f Tripping may be delayed beyond the rated permissible tripping delay at
c Contact Eaton for availability of these circuit breakers.
lower values of current in accordance with the following formula:
d For three-phase and line-to-line faults, the symmetrical interrupting
capability at an operating voltage
( )
2
(KTimes Rated Short-Circuit Current)
T (seconds) =Y
Short-Circuit CurrentThrough Breaker
V
Isc = (Rated Short-Circuit Current)
Vo The aggregate tripping delay on all operations within any 30-minute period
But not to exceed KI. must not exceed the time obtained from the above formula.
Single line-to-ground fault capability at an operating voltage g For reclosing service, there is No derating necessary for Eaton’s
VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
V the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws
Isc = 1.15 (Rated Short-Circuit Current) have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Vo
Contact Eaton for special reclosing requirements.
But not to exceed KI. h Included for reference only.
The above apply on predominately inductive or resistive three-phase i Asymmetrical interrupting capability = “S” times symmetrical
circuits with normal-frequency line-to-line recovery voltage equal
interrupting capability, both at specified operating voltage.
to the operating voltage.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-5

Protective Relays and Metering Instrument Transformers Current Transformers


Instrument transformers are used to The current transformer ratio is gener­ally
selected so that the maximum load
Protective Relays protect personnel and secondary devices
current will read about 70% full scale
A full scope of protective relays designed from high voltage, and permit use of
reasonable insulation levels for relays, on a standard 5 A coil ammeter. There­fore,
to meet all application requirements is the current transformer primary rating
available to provide the utmost in system meters and instruments. The secondaries
of standard instrument transformers are should be 140–150% of the maximum
and component protection. load current.
rated at 5 A and/or 120 V, 60 Hz.
Maximum system fault current can
Integrated Monitoring sometimes influence the current
Voltage Transformers transformer ratio selection because
Protection and Control
Selection of the ratio for voltage the connected secondary devices have
Communications System transformers is seldom a question since published one-second ratings.
the primary rating should be equal to
Eaton’s power management products The zero-sequence current transformer
or higher than the system line-to-line
provide hardware and software solu­tions is used for sensitive ground fault relay­ing
voltage. The number of potential
that allow customers to interface with or self-balancing primary current type
transformers per set and their connection
their switchgear at varying levels of machine differential protection. The
is determined by the type of system and
sophistication. Power Xpert and IQ zero-sequence current transformer is
the relaying and metering required.
Meters monitor common electrical available with a nominal ratio of 50/5
parameters and communicate the data When two VTs are used, they are typically or 100/5 and available opening size for
via standard industry protocols and connected L-L, and provide phase-to- power cables of 7.25 inches (184.2 mm).
optional Web interfaces. Power Xpert phase voltages, (Vab, Vbc, Vca) for Special zero-sequence transformers with
Gateways consolidate devices into a metering and relaying. larger windows are also available.
single Web browser interface and provide
Ethernet connectivity. Eaton’s Power When three VTs are used, they are The minimum number of current
Xpert Insight® and Foreseer Web-based connected line-to-ground, and provide transformers for circuit relaying
software systems display, analyze and phase-to-phase (Vab, Vbc, Vca), as well and instruments is three current
store data from multiple devices across as phase-to-ground (Va, Vb, Vc) voltages transform­ers, one for each phase
the facility to enable management of the for metering and relaying. or two-phase connected current
customer’s power system. transformers and one zero-sequence
If metering or relaying application current transformer. Separate sets of
requires phase-to-ground voltages, use current transformers are required for
three VTs, each connected L-G. If not, use differential relays.
of two VTs connected L-L is sufficient.
The minimum pickup of a ground
For ground detection, three VTs relay in the residual of three-phase
connected in Line-to-ground/broken- connected current transformers is
delta are used. primarily determined by the current
A single VT, when used, can be connected transformer ratio. The relay pickup can
line-to-line (it will provide line-to-line be reduced by adding one residual
output, for example Vab or Vbc or Vca), connected auxiliary current transformer.
or line-to-ground (it will provide line-to- This connection is very desirable on main
ground output, for example Va or Vb incoming and tie circuits of low resistance
or Vc). Generally, a single VT is used to grounded circuits.
derive voltage signal for synchronizing Standard accuracy current transform­ers
or Over Voltage/Under Voltage function. are normally more than adequate
for most standard applications of
microprocessor-based protective relays
and meters. See Table 5.2-7 for CT
accuracy information.
Table 5.2-5. Standard Voltage Transformer Ratio Information
Rating-Volts 2400 4200 4800 7200 8400 10800 12000 14400 15600 18000 21000 24000 27000 36000

Ratio 20-1 35-1 40-1 60-1 70-1 90-1 100-1 120-1 130-1 150-1 175-1 200-1 225-1 300-1

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-6

Table 5.2-6. Standard Voltage Transformer, 60 Hz Accuracy Information


Switchgear Voltage Transformer—ANSI Accuracy
kV kV Maximum Number Standard Burdens at 120 Volts Burdens at 69.3 Volts Thermal Rating Volt-Ampere
Class BIL Per Set and Connection Ratios W, X, Y Z M ZZ W, X Y M Z 55°C Connection

  5   60 2LL   20 a 0.3 1.2 — — 0.3 — — — LL   700


or 3LG   35 LG   400
  40 LG b   700
a For solidly grounded 4160 V system only or any type 2400 V system.
b For solidly grounded system only.
Note: LL = Line-to-line connection. LG = Line-to-ground connection.

Table 5.2-7. Current Transformers, 55 °C Ambient


CT Ratio Metering Accuracy Classification Relaying Accuracy Classification
(MR = Multi-Ratio) At 60 Hz At 60 Hz At 60 Hz Minimum Accuracy Standard Accuracy Optional High Accuracy
Standard Burden Standard Burden Standard Burden Required per IEEE Supplied in VCP-W Available in VCP-W
B 0.1 B 0.5 B 1.8 C37.20.2 Switchgear Switchgear

    50:5 1.2 — — C10 — C10


    75:5 1.2 2.4 — C10 C10 C20
  100:5 1.2 2.4 — C10 C10 C20
  150:5 0.6 2.4 — C20 C20 C50
  200:5 0.6 2.4 — C20 C20 C50
  250:5 0.6 2.4 — c C20 C50
  300:5 0.6 2.4 2.4 C20 C20 C100
  400:5 0.3 1.2 2.4 C50 C50 C100
  500:5 0.3 0.3 2.4 c C50 C100
  600:5 0.3 0.3 2.4 C50 C100 C200
  800:5 0.3 0.3 1.2 C50 C100 C200
1000:5 0.3 0.3 0.3 c C100 C200
1200:5 0.3 0.3 0.3 C100 C200 C400
1500:5 0.3 0.3 0.3 C100 C200 C400
2000:5 0.3 0.3 0.3 C100 C200 C400
2500:5 0.3 0.3 0.3 c C200 C400
3000:5 0.3 0.3 0.3 C100 C200 C400
4000:5 0.3 0.3 0.3 C100 C200 C400
  600:5 MR 0.3 0.3 2.4 c C100 C200
1200:5 MR 0.3 0.3 0.3 c C200 C400
2000:5 MR 0.3 0.3 0.3 c C200 C400
3000:5 MR 0.3 0.3 0.3 c C200 C400
    50:5 zero sequence — — — — C10 —
  100:5 zero sequence — — — — C20 —
c Not listed in C37.20.2.
Note: Maximum number of CTs—Two sets of standard accuracy or one set of high accuracy CTs can be installed in the breaker compartment on each side
of the circuit breaker.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-7

Integral Motorized Remote A microprocessor-based controller card,


located below the drive motor, interfaces
Racking Option (VC-W MR2) with an external hand-held pendant
(standard), discrete external I/O (optional)
or external Modbus communication
(optional) and controls the breaker/
auxiliary drawer move­ment via the
drive motor. The system is also designed
such that it allows manual racking of
the breaker/auxiliary using the levering
crank accessory if needed. The VC-W
MR2 controller interface is shown in
Figure 5.2-1. The crank safety switch
disables the motor whenever a breaker/
auxiliary is being manually racked in or
out. The connect, test and disconnect
limit switches provide breaker/auxiliary
Breaker Levering Pan Assembly with Test position inputs to the controller card.
Position—VC-W MR2 Integral Racking Device In addition to the standard permissive
MR2 Hand-Held Pendant switch, two terminals are provided for
connection of the customer’s external
VC-W MR2 is an optional motorized interlocking/permissive contact(s). Note
racking device accessory installed that a single-phase 120 Vac control supply
inside a circuit breaker or auxiliary is required for proper operation of the
compartment. It is available for VC-W MR2 controller and the drive motor.
application in circuit breaker compart­
ments of 5/15/27/38 kV Type VC-W arc When VC-W MR2 integral racking is
and non-arc, and 5 kV VC-W ND metal- supplied, its controller card is wired to
clad switchgear. It is also available for the CAT 6 jack installed in the associated
application in auxiliary compartments breaker/auxiliary compart­ment door,
of 5/15 kV Type VC-W arc-resistant and and each switchgear lineup is shipped
standard switchgear. This optional with one hand-held pendant with 30 feet
accessory allows a user to safely move a of CAT 6 cable (lengths up to 100 ft
Type VC-W Arc-Resistant Switchgear Auxiliary
Drawer with Type MR2 Integral Racking circuit breaker between Connected, Test available). The pendant interfaces with
and Disconnected positions and auxiliary the MR2 controller card via the CAT 6
drawer (VT, CPT, primary fuse) between cable through a CAT 6 jack located on the
Connected and Disconnected positions breaker/auxiliary compartment door. It
within their respective compartments allows the operator to move away from
from a safe distance away from the the switchgear up to 30 feet. The pendant
switchgear. The MR2 controller also includes Enable pushbutton for additional
allows a user to electri­cally open and security. It must be pressed in order to
close the circuit breaker from a safe activate the pendant functions. By
distance away from the switchgear. For pressing Enable pushbutton and an
switchgear designs/ratings not included appropriate function pushbutton together
above, contact Eaton for availability of momentarily, the operator can rack the
MR2 accessory. breaker between Connected, Test and
Disconnected positions or open or close
the breaker or rack the auxiliary drawer
between Connected and Disconnected
Type VC-W Standard Switchgear Auxiliary positions. Breaker or auxiliary drawer
Drawer with Type MR2 Integral Racking
positions (Connect, Test, Disconnect)
and breaker opened/closed status are
indicated by appropriate LED lights on
the pendant. A blinking light indicates that
the breaker/auxiliary is in motion through
the selected position.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-8

A solid (non-blinking) light indicates that The remote LED lights are not included Technical Data
the breaker/auxiliary has reached and with MR2. If the customer needs to
stopped in the selected position. In case operate the MR2 with the hand-held Control Supply Ratings
normal operation fails, the appropriate pendant, the pendant becomes the ■ Nominal control voltage—120 Vac,
error code is displayed in a separate master and will override the customer’s 50 or 60 Hz, single-phase
two-character LED display window on the remote control signals.
■ Control voltage range—100 to 140 Vac,
pendant. A list of various error codes and
their descrip­tions along with suggested The VC-W MR2 controller is also 50 or 60 Hz
corrective actions are printed on the equipped with terminal blocks to ■ Time to travel from connect to
back side of the pendant. Examples of allow the customer to interface with disconnect, or disconnect to connect—
error states: motor overcurrent, motor the controller via their SCADA system 50 seconds maximum
overtemperature, motor timed out, using a Modbus interface. Please note
■ Current draw during the travel—
breaker position unknown, open that only one of the two options, discrete
I/O interface or Modbus interface, can be 15 A maximum for about 3 seconds
permissive, communication error and 3.6 A for about 24 seconds
and no breaker/auxiliary. used, but not both. Figure 5.2-2 shows an
illustration of a typical Modbus control ■ Optional dry output contacts when
In addition to pendant, three optional example. Additional compo­nents shown included for position indications are
I/O interfaces can be supplied as outside the MR2 controller in Figure 5.2-2 rated for 125 Vac, 2 A
follows: are not included with the MR2. System- ■ External permissive contacts, when
level controls can be optionally supplied used, must be rated for 24 Vdc, 50 mA
1. I/O interface to allow racking of by Eaton’s Engineering Services &
breaker (connect, test, disconnect) or Systems. If the customer needs to operate
auxiliary drawer (connect, disconnect) the MR2 with the hand-held pendant, Requirements for External Contacts
by external hardwired dry contacts the pendant becomes the master and and LEDs when Interfacing with MR2
and 24 Vdc output for corresponding will override the Modbus interface. Error ■ External contacts should be rated for
remote position indicating LEDs. codes are displayed on Modbus devices minimum open circuit voltage of
2. I/O board that provided dry when controlling the MR2 with Modbus 24 Vdc, and be able to close and carry
contacts for remote indication and on the pendant when controlling with 5 mA at 24 Vdc
of breaker (connect, intermediate, the pendant. ■ When remote LEDs are used, use
test, disconnect)/auxiliary drawer 24 Vdc rated LEDs, current up to 20 mA
(connect, test) position within ■ Optional dry output contacts when
its compartment. included for position indications are
3. I/O interface to allow breaker open/ rated for 125 Vac, 2 A
close functions via external hardwired ■ External permissive contacts, when
dry contacts and 24 Vdc output for used, must be rated for 24 Vdc, 50 mA
corresponding remote open/close
It is the customer’s responsibility to
status LEDs.
provide single-phase 120 V, 50 or 60 Hz
nominal supply for the MR2 controller.
It can be derived from within the
switchgear if an appropriate control
power transformer is available within
the switchgear.
Type VC-W MR2 motorized racking
accessory has been endurance tested
and guaranteed for 500 operations as
required by IEEE C37.20.2.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-9

Figure 5.2-1. VC-W MR2 Controller Interface for a VCB with Distinct Test Position and Open/Close Functions

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-10

Figure 5.2-2. VC-W MR2 Typical Modbus Control Example

Accessories

Ground and Test Device


The ground and test device is a drawout Standard Accessories
element that may be inserted into a ■ One test jumper
metal-clad switchgear housing in place ■ One levering crank
of a circuit breaker to provide access
to the primary circuits to permit the ■ One maintenance tool
temporary connection of grounds or ■ One lifting yoke (5–27 kV)
test­ing equipment to the high-voltage ■ One set of rails (5–27 kV)
circuits. High potential testing of cable or
phase checking of circuits are typical tests
which may be performed. The devices are Optional Accessories
insulated to suit the voltage rating of the ■ Transport dolly (5–27 kV),
switchgear and will carry required level (5–15 kV arc-resistant)
of short-circuit current. ■ Portable lifter (5–27 kV)
Before using ground and test devices, it ■ Test cabinet
is recommended that each user develop ■ Electrical levering device (5–38 kV)
detailed operating procedures consis­tent
■ Ramp for lower breaker (5–27 kV),
with safe operating practices. Only
(5–15 kV arc-resistant)
qualified personnel should be authorized
to use ground and test devices. ■ Manual or electrical ground and
test device
Manual and electrical ground and test
■ Hi-pot tester
devices are available, These devices
include six studs for connection to ■ Integral motorized remote racking
primary circuits. On the manual device, (VC-W MR2) for circuit breaker
selection and grounding is accomplished ■ Integral motorized remote racking
by cable or bus bars connection. On (VC-W MR2) for auxiliary drawer
electrical-type devices, grounding is
accomplished by an electrically operated
grounding switch.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-11

Systems Options

InsulGard Relay (PD Monitoring)

The PD sensing and monitoring system is


optional. It consists of Eaton’s InsulGard™
Relay and PD sensors specifically
developed for application in the
switchgear to work with the relay.

InsulGard Relay RFCT Sensor Partial discharges within the switch­gear


compartment are detected by installation
Partial Discharge Equipment of a small donut type radio frequency
current transformer (RFCT) sensor over
Partial Discharge Sensing and Sensing and Monitoring floating stress shields of the specially
Eaton’s Type VCP-W metal-clad switch­gear designed bus or line side primary
Monitoring for Switchgear (2.4–38 kV) is corona-free by design. bushings. Partial discharges in customer’s
Partial Discharge in Switchgear Corona emissions within the standard power cables (external discharges) are
VacClad switchgear assemblies have detected by installation of the RFCT
Partial discharge is a common name for been eliminated or reduced to very low around ground shields of the incoming
various forms of electrical discharges levels by special fabrication and assembly or outgoing power cables termination.
such as corona, surface tracking, and techniques, such as rounding and buffing
discharges internal to the insulation. It of all sharp copper edges at the joints, In 5/15 kV switchgear (refer to
partially bridges the insulation between employing star washers for bolting Figure 5.2-4), primary epoxy bushings
the conductors.These discharges are metal barriers, and using specially with stress shield and RFCT sensors
essentially small arcs occurring in or on crafted standoff insulators for primary for measurement of internal as well
the surface of the insulation system when bus supports. By making switchgear as external partial discharges are all
voltage stress exceeds a critical value. With assemblies corona-free, Eaton has made optional. InsulGard relay is also optional.
time, airborne particles, contaminants and its standard switchgear more reliable. When specified, one set of primary epoxy
humidity lead to conditions that result in However, as indicated above, with time, bushings (located on bus side) with
partial discharges. Partial discharges airborne particles, contaminants and stress shield and associ­ated RFCT
start at a low level and increase as humidity lead to conditions that cause sensor is provided at every two vertical
more insulation becomes deteriorated. partial discharges to develop in sections. An additional RFCT sensor for
Examples of partial discharge in switchgear operating at voltages 4000 V each incoming and outgoing power cable
switchgear are surface tracking across and above. Type VC-W switchgear can be circuits can be provided as required. The
bus insulation, or discharges in the air equipped with fac­tory-installed partial RFCT output signals can be connected
gap between the bus and a support, discharge sensors and partial discharge directly to InsulGard relay for continuous
such as where a bus passes through an sensing relay for continuous monitoring moni­toring of partial discharges or can
insulating window between the sections of the partial discharges under normal be used for periodic field measurements.
of the switchgear. If partial discharge operation. Timely detection of insulation
process is not detected and corrected, degrada­tion through increasing partial
it can develop into a full-scale insulation discharges can identify potential
failure followed by an electrical fault. Most problems so that corrective actions can
switchgear flashover and bus failures are be planned and implemented long before
a result of insulation degradation caused permanent deterioration develops. Partial
by various forms of partial discharges. discharge detection can be the foundation
of an effective predictive maintenance
program. Trending of partial discharge
data over time allows prediction of
failures, which can be corrected before
catastrophic failure occurs.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-12

Input
Temp Sensor Terminal InsulGard
Block Relay Optional
Humidity Sensor Modem

120 Vac
Auxiliary
Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
RFCT Sensor, RTD Input, etc.) Status

Figure 5.2-3. InsulGard Relay System

RFCT #1 detects partial discharges internal to switchgear


compartment.
RFCT #2 detects partial discharges in customer’s cables up
to 100 ft from switchgear.

Figure 5.2-4. Typical Partial Discharge Sensor Connections


(5–15 kV Switchgear)
Note: Use one set of epoxy bottles with ground stress shield on bus side
(either in the top or bottom compartment) at every two vertical sections.
Use standard bottles at all other locations.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-13

Partial Discharge Sensors and Monitoring for Switchgear

Radio Frequency Current Sensor (RFCT) Epoxy Bottles with Stress Shield
(5/15 kV Switchgear)

PD Sensors

PD Sensors
PD Sensors are Installed
in Switchgear Cubicle

Figure 5.2-5. How the Process Works—Sensing and Data Collection

Pulse Repetition Rate (PPC)


5

0
Cub12

Cub13

Cub14

Cub15

Cub16
Cub11
Cub1

Cub2

Cub3

Cub4

Cub5

Cub6

Cub7

Cub8

Cub9

Relatively high Partial Discharge levels indicate problems


in older non-fluidized epoxy insulated MV bus. Problems
in cable terminations and in connected equipment can also
be revealed.

Figure 5.2-6. How the Process Works—Data Analysis and Report (Sample)

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-14

Standard Layouts

Typical Units—Indoor Tie Breaker Bus Transition Requirements

Figure 5.2-7. 26.00-Inch (660.4 mm) Wide Typical Breaker/Breaker


Vertical Section—Dimensions in Inches (mm)

Figure 5.2-10. Tie Breaker Bus Transition Requirements


a Breakers cannot be located in bus transition compartment.

Available Configurations

1200 Ampere 1200 Ampere Drawout


Breaker Breaker Auxiliary

Figure 5.2-8. 26.00-Inch (660.4 mm) Wide Typical Auxiliary/Breaker


Vertical Section—Dimensions in Inches (mm)
1200 Ampere Drawout 1200 Ampere
Breaker Auxiliary Breaker

Drawout
Auxiliary

Drawout
Auxiliary

Figure 5.2-9. 26.00-Inch (660.4 mm) Wide Typical Auxiliary/Auxiliary Figure 5.2-11. Available Configurations
Vertical Section—Dimensions in Inches (mm)

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-15

2.00 22.00 (558.8) 2.00


(50.8) (50.8)

3.00 (76.2)

23.00 Rear
1
(584.2)
3 30.00 2.00 22.00 2.00
(762.0) (50.8) (558.8) (50.8)

3.00
4
(76.2)

5B 5B
23.00
2 (584.2)
28.00
(711.2)

0.88
(4) Knockouts (22.4)
5A 5A
0.88
for Top Secondary (22.4)
Conduit Entry
9.00 6
(228.6)
6.00
(152.4) 96.25
(2444.8) 44.50
7.00 (1130.3)
(177.8) 9 60.88
(1546.4)
3.00 3.00 0.56 0.56
(14.2) (14.2)
(76.2) (76.2)

Front 5A 5A 3.38
(86.0)
3.00 3.00
Figure 5.2-12. Top View of Typical Indoor 16.00 19.00
(76.2) (76.2)
0.25
7
Breaker and Auxiliary Structures— (406.4) (482.6) (6.4)
Dimensions in Inches (mm)
a Power cable entrance area. Refer to
Figure 5.2-14 for typical conduit locations. Refer 3.88
5B 5B
to shop drawings for order specific locations. 4.25 (98.6)
(108.0) 1.25
0.88 0.88
(31.8) 5.56 4
(22.4) (22.4)
(141.2)

26.00 26.00
(660.4) (660.4) 70.00 Min.
10 (1778.0)
8

Front

Figure 5.2-13. Base Plan of a Typical Indoor Breaker or Auxiliary Structure


b Power cable entrance area. Refer to f Station ground connection provision.
Figure 5.2-14 for typical conduit locations. Refer g Secondary conduit space: All–maximum of
to shop drawings for order specific locations. 1.00-inch (25.4 mm) projection.
c Recommended minimum clearance to rear of h Minimum clearance to LH side of VacClad-W.
VacClad-W. Minimum clearance to RH side of the
d Floor steel, if used, must not exceed this switchgear: 6.00 inches (152.4 mm).
dimension under VacClad-W. i Finished foundation surface shall be level within
e Anchor locations: 5A and 5B for seismic 0.06-inch (1.5 mm) in 36.00 inches (914.4 mm)
applications, 5A only for non-seismic left-to-right, front-to-back, and diagonally, as
application. For indoor, use 0.5-inch (12.7 mm) measured by a laser level.
bolts or weld. j Minimum clearance to front of VacClad-W.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-16

Rear 6.00 (152.4)


6.00 (152.4)
1 2
7.00 (177.8) 


11.50 (292.1)
 Upper
2 7 Hinged
Panel

Two Conduits per Breaker 1-Large Relay


Case
3 3 4 2-Small Relay
Case
3-Instrument
6 5 4-Test Switch
 5-Switch
6-Lock-out
3 3 Relay or
4 Switch

7-Metering
6 5 Unit

One Conduit per Breaker


1
Lower
Hinged
Figure 5.2-14. Primary Conduit Locations for Stacked Breakers 7 Panel
a Changes to 8.25 (209.6 mm) if optional hinged rear doors are required.
b When cables enter from top, they connect to the breaker located in the
bottom compartment. When cables enter from bottom, they connect to
the breaker in the upper compartment. 2 2
c When cables enter from top, they connect to the breaker located in the
upper compartment. When cables enter from bottom, they connect to the
breaker in the bottom compartment.

Figure 5.2-15. Maximum Hinged Panel Equipment


Note: The figure above shows that the arrangement of components differs
between upper and lower panels. The figure may also be used to select
custom arrange­ments of hinged panel components. Also, the use of
multi-function relays such as Eaton’s E-series relays will significantly
reduce consumption of panel space.

Dimensions for estimating purposes only.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-17

80.00
(2032.0) LL
(1)

521
36.00
RTH

(914.4)
SCD
0H7
Pad

80.00
a
(2032.0)

Figure 5.2-16. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch Figure 5.2-19. Tie Breaker Bus Transition Requirements
(660.4 mm) Wide Indoor Unit, Blank/Breaker—Dimensions in Inches (mm)
a Depth can be reduced to 72.00 inches (1828.8 mm) if power cables enter
from top.

Auxiliary or
Blank
d
521 36.00 Blank 1200 Ampere 1200 Ampere
(914.4) ND Breaker ND Breaker
RTH

SCD d Auxiliary or d
0H7 Blank
d
Pad
80.00
(2032.0) Auxiliary or
1200 Ampere Blank 1200 Ampere Blank
d
ND Breaker ND Breaker
d
d
Auxiliary or
Blank
d

Figure 5.2-20. Available Configurations (Front View)


80.00 b
d Relays or control devices cannot be mounted on the circuit breaker
(2032.0)
or auxiliary compartment door.

Figure 5.2-17. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch
(660.4 mm) Wide Indoor Unit, Breaker/Blank—Dimensions in Inches (mm)
b Depth can be reduced to 72.00 inches (1828.8 mm) if power cables enter
from below.

VTX
(2)
80.00
(2032.0) LP
(2)
RTH

521
36.00
RTH

(914.4)
SCD
0H7
Pad

80.00 c

(2032.0)

Figure 5.2-18. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch
(660.4 mm) Wide Indoor Unit, Auxiliary/Breaker—Dimensions in Inches (mm)
c Depth can be reduced to 72.00 inch (1831.7 mm) if power cables enter
from top.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-18

Weights
Table 5.2-8. Switchgear Assembly (Less Breaker) Table 5.2-9. Circuit Breaker a
Type of Main Bus Rating, Weight Type of Current Rating, Weight Lb (kg)
Vertical Section Amperes Lb (kg) Circuit Breaker Amperes (Static)

B/B 1200 2000 (908) 50 VCPW-ND-250 1200 345 (157)


2000 2200 (999)
a Breaker impact weight = 1.5 x static weight.
B/A or A/B 1200 1500 (682)
1700 (772)
2000 1700 (772)
1900 (863)
A/A 1200 1400 (636)
1600 (726)
2000 1600 (726)
1800 (817)

Control Power
Table 5.2-10. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated Spring Charging Motor Close or Trip UV Trip mA Voltage Range Indicating
Control Inrush Run Average Run Amperes Maximum Close Trip Light
Voltage Amperes Amperes Time, Sec. Amperes

  48 Vdc 36.0 9 6 16 200   38–56   28–56 0.02


125 Vdc 16.0 4 6   7   80 100–140   70–140 0.02
250 Vdc   9.2 2 6   4   40 200–280 140–280 0.02
120 Vac 16.0 4 6   6 — 104–127 104–127 0.02
240 Vac   9.2 2 6   3 — 208–254 208–254 0.02

Table 5.2-11. Control Power Transformers—Single-Phase, 60 Hz b


Rated Primary Voltage, Volt Rated Secondary Voltage, Volt kVA kV
Class

  2400 240–120   5, 10, 15   5


  4160 240–120   5, 10, 15   5
  4800 240–120   5, 10, 15   5
  7200 240–120   5, 10, 15 15
  8400 240–120   5, 10, 15 15
12470 240–120   5, 10, 15 15
13200 240–120   5, 10, 15 15
13800 240–120   5, 10, 15 15
23000 240–120   5, 10, 15 27
34500 240–120 15, 25 38 c
b Line-to-line connection only available. Refer to Eaton for other voltages and kVA ratings.
c 150 kV BIL.

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-19

Operations
Table 5.2-12. Breaker Operations Information
Circuit Breaker Ratings Maximum Number of Operations a
Rated Maximum Rated Continuous Rated Short-Circuit Between No-Load Rated Continuous Inrush Current
Voltage Current Current Servicing Mechanical Current Switching Switching
kV rms Amperes kA rms, sym.

  4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
a Each operation is comprised of one closing plus one opening.

Heat Loss
Table 5.2-13. Heat Loss in Watts at Full Rating, at 60 Hz
Type of Switchgear Assembly Breaker Rating 1200 A 2000 A 2500 A 3000 A 4000 A Fan Cooled

VCP-W 5, 15, and 27 kV 600 W 1400 W — 2100 W 3700 W


VCP-W 38 kV 850 W 1700 W 2300 W 3800 W —
Other Components
Each CT, standard accuracy   50 W
Each CT, high accuracy 100 W
Each VT   60 W
CPT single-phase, 25 kVA 450 W
CPT single-phase, 45 kVA 892 W
Space heater—each 250 W

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-20

Typical Schematics

ANSI Standard VCP-W Breaker dc Control Schematic

P
(+)
CS CS PR
C T

11
Spring

9UV
WL GL RL
Charged
Indicating
Light
UV

10UV
dc Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

12
1 2

9A
4 7 5 6 7 8 9 10 3
3A
3

9
13

61
Y

51

53

55

57
LS1 a
bb a
Y SR

62
ST

52

56

58
54
ST 18 17 16 15 22 2
M b b 1
a
LC a
PS2 LS2 LS2

10A
PS Y
bb 1 bb aa
Not Available when Second 13
14

10
4

24 21 20 19
Trip Coil Option is Chosen
TRCO_51N
TRCS_
TCSSLT
LOCATION

Options
LOCATION
CCBSN CGL
LOCATION LOCATION
TCSSLT
TRCS_
TRCO_51N

N
(-)

ANSI Standard VCP-W Breaker ac Control Schematic

1 FUSE
CAC120
LOCATION
S-MRU
S-TRU
S-CPU

CS
C
CS PR
T
11
Spring

9UV
WL GL RL
Charged
Indicating
Light
UV

9UV
10UV
ac Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

ac (+) 12 UV
1 2
9A

4 5 9 6 7 8 10 3
10UV

7
Cap Trip Dev
3A

9
3

13

55

61

Y
51

57
53

a a
LS1 ac (–)
bb
Y SR
62
52

58

ST
54

ST 2
M 1
18 17 15 22 For ac UV
b b a
LC
a Trip Only
PS2 LS2 LS2 a
10A

bb PS Y
1 bb aa
Not Available when Second 13
14

56

10
4

24 21 20 16 19 Trip Coil Option is Chosen


TRCO_51N
TRCS_
TCSSLT
LOCATION

2
LOCATION
CCBSN CRL
LOCATION LOCATION
TRCS_
TRSS
TRCO_51N

Options

Figure 5.2-21. Typical 5/15/27 kV VCP-W “dc” and “ac” Control Schematics

Note: CS Note: LS1


C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS LS2
= Breaker Control Switch–Trip
T aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2
= Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-21

Breaker dc Control Schematic


P LOCATION
FUSE
CDC0
S-MRU
S-TRU
S-CPU

(+)
CS CS PR
C T
11 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
Spring WL GL RL
Charged

9UV
Indicating
Light U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
UV U24

Auxiliary Switch #2 Optional

10UV
dc Source

14
TRCO_51N
TRCS_
TCSSLT
LOCATION

12 OPTIONS
1 2 4 7 5 6 7 8 9 10 3

9A
13

57
3

61
3A

51

53

55
Y
LS1 a
bb a

54

62
Y

52

56

58
SR
ST
ST 18 17 16 15 22 2
b
LOCATION

M 1
b

10A
LC a
PS2 PS Y LS2 LS2 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14

10

a
4

24 21 20 19
N
LOCATION
TRCS_
TCSSLT
TRCO_51N

Customer Must Furnish


(-) This ”a“ Contact from
Auxiliary Switch When
Second Trip Coil Option
is Chosen and Make the
Appropriate Connections

Breaker ac Control Schematic


1 S-CPU
LOCATION
S-MRU
FUSE
CAC120
S-TRU

CS
C U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
CS PR
T
11
Spring WL GL RL
Charged
9UV

U24 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
Indicating
Light
Auxiliary Switch #2 Optional
UV
10UV
ac Source

9UV

OPTIONS
TRCO_51N
TRCS_
TCSSLT
LOCATION
14

ac (+) 12 UV
1 2 4 7 5 9 6 7 8 10 3
10UV
9A

CAP TRIP DEV


13

9
3A
3

61
55

51

a
53

57

Y
LS1 ac (-) a
bb
62
52

58
54

Y SR
ST
ST
1
18 17 15 22 2
For ac UV
M b a
LOCATION

b
Trip Only
10A

LC
PS2 PS Y LS2 LS2 a 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14

10

a
56
4

24 21 20 16 19
2
LOCATION
TRCS_
TRSS
TRCO_51N

Customer Must Furnish


This ”a“ Contact from
CONTACT
S-CPL
LOCATION
SACCN
SAACCN
MOTOR
CL_STD
CL_GR
CRL
TRIP
S-MRL
S-TRL
S-MRU
S-TRU
S-CPU
FUSE
CAC120

Auxiliary Switch When


Second Trip Coil Option
is Chosen and Make the
Appropriate Connections

Figure 5.2-22. Typical 38 kV VCP-W “dc” and “ac” Control Schematics

Note: CS Note: LS1


C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS LS2
= Breaker Control Switch–Trip
T aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2
= Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>

EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
5.2-22

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. DG022002EN / Z23483 All other trademarks are property
February 2020 of their respective owners.

You might also like