Professional Documents
Culture Documents
Eaton Vacclad W 5kv 26in Narrow Metal Clad MV Switchgear Design Guide Dg022002en
Eaton Vacclad W 5kv 26in Narrow Metal Clad MV Switchgear Design Guide Dg022002en
Contents
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-2
Usual and Unusual Service Conditions . . . . . . . . . . . . 5.2-3
Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-4
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-4
Protective Relays and Metering. . . . . . . . . . . . . . . . . . 5.2-5
Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . 5.2-5
Integral Motorized Remote Racking Option
(VC-W MR2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-10
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2-11
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
General Description 5.2-3
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-4
Circuit Breakers
Table 5.2-4. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K > 1) aabc
Identification Rated Values Related Required Capabilities
Circuit Voltage Insulation Current Rated Transient Current Values
Recovery Voltage e
Rated Continuous
K Times Rated 2.7 K 1.6 K
Current at 60 Hz
Voltage (1 min.)
Short-Circuit Times Times
Rate of Rise of
Current d Rated Rated
Short- Short-
Circuit Circuit
Rated
Current Current
50 VCP-WND 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250
a 5 and 15 kV circuit breakers are UL listed. E2
e RRRV = 1.137
b Circuit breakers shown in this table were tested in accordance with IEEE T2
standard C37.09-1979.
f Tripping may be delayed beyond the rated permissible tripping delay at
c Contact Eaton for availability of these circuit breakers.
lower values of current in accordance with the following formula:
d For three-phase and line-to-line faults, the symmetrical interrupting
capability at an operating voltage
( )
2
(KTimes Rated Short-Circuit Current)
T (seconds) =Y
Short-Circuit CurrentThrough Breaker
V
Isc = (Rated Short-Circuit Current)
Vo The aggregate tripping delay on all operations within any 30-minute period
But not to exceed KI. must not exceed the time obtained from the above formula.
Single line-to-ground fault capability at an operating voltage g For reclosing service, there is No derating necessary for Eaton’s
VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
V the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws
Isc = 1.15 (Rated Short-Circuit Current) have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Vo
Contact Eaton for special reclosing requirements.
But not to exceed KI. h Included for reference only.
The above apply on predominately inductive or resistive three-phase i Asymmetrical interrupting capability = “S” times symmetrical
circuits with normal-frequency line-to-line recovery voltage equal
interrupting capability, both at specified operating voltage.
to the operating voltage.
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-5
Ratio 20-1 35-1 40-1 60-1 70-1 90-1 100-1 120-1 130-1 150-1 175-1 200-1 225-1 300-1
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-6
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-7
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-8
A solid (non-blinking) light indicates that The remote LED lights are not included Technical Data
the breaker/auxiliary has reached and with MR2. If the customer needs to
stopped in the selected position. In case operate the MR2 with the hand-held Control Supply Ratings
normal operation fails, the appropriate pendant, the pendant becomes the ■ Nominal control voltage—120 Vac,
error code is displayed in a separate master and will override the customer’s 50 or 60 Hz, single-phase
two-character LED display window on the remote control signals.
■ Control voltage range—100 to 140 Vac,
pendant. A list of various error codes and
their descriptions along with suggested The VC-W MR2 controller is also 50 or 60 Hz
corrective actions are printed on the equipped with terminal blocks to ■ Time to travel from connect to
back side of the pendant. Examples of allow the customer to interface with disconnect, or disconnect to connect—
error states: motor overcurrent, motor the controller via their SCADA system 50 seconds maximum
overtemperature, motor timed out, using a Modbus interface. Please note
■ Current draw during the travel—
breaker position unknown, open that only one of the two options, discrete
I/O interface or Modbus interface, can be 15 A maximum for about 3 seconds
permissive, communication error and 3.6 A for about 24 seconds
and no breaker/auxiliary. used, but not both. Figure 5.2-2 shows an
illustration of a typical Modbus control ■ Optional dry output contacts when
In addition to pendant, three optional example. Additional components shown included for position indications are
I/O interfaces can be supplied as outside the MR2 controller in Figure 5.2-2 rated for 125 Vac, 2 A
follows: are not included with the MR2. System- ■ External permissive contacts, when
level controls can be optionally supplied used, must be rated for 24 Vdc, 50 mA
1. I/O interface to allow racking of by Eaton’s Engineering Services &
breaker (connect, test, disconnect) or Systems. If the customer needs to operate
auxiliary drawer (connect, disconnect) the MR2 with the hand-held pendant, Requirements for External Contacts
by external hardwired dry contacts the pendant becomes the master and and LEDs when Interfacing with MR2
and 24 Vdc output for corresponding will override the Modbus interface. Error ■ External contacts should be rated for
remote position indicating LEDs. codes are displayed on Modbus devices minimum open circuit voltage of
2. I/O board that provided dry when controlling the MR2 with Modbus 24 Vdc, and be able to close and carry
contacts for remote indication and on the pendant when controlling with 5 mA at 24 Vdc
of breaker (connect, intermediate, the pendant. ■ When remote LEDs are used, use
test, disconnect)/auxiliary drawer 24 Vdc rated LEDs, current up to 20 mA
(connect, test) position within ■ Optional dry output contacts when
its compartment. included for position indications are
3. I/O interface to allow breaker open/ rated for 125 Vac, 2 A
close functions via external hardwired ■ External permissive contacts, when
dry contacts and 24 Vdc output for used, must be rated for 24 Vdc, 50 mA
corresponding remote open/close
It is the customer’s responsibility to
status LEDs.
provide single-phase 120 V, 50 or 60 Hz
nominal supply for the MR2 controller.
It can be derived from within the
switchgear if an appropriate control
power transformer is available within
the switchgear.
Type VC-W MR2 motorized racking
accessory has been endurance tested
and guaranteed for 500 operations as
required by IEEE C37.20.2.
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-9
Figure 5.2-1. VC-W MR2 Controller Interface for a VCB with Distinct Test Position and Open/Close Functions
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-10
Accessories
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-11
Systems Options
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-12
Input
Temp Sensor Terminal InsulGard
Block Relay Optional
Humidity Sensor Modem
120 Vac
Auxiliary
Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
RFCT Sensor, RTD Input, etc.) Status
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Devices 5.2-13
Radio Frequency Current Sensor (RFCT) Epoxy Bottles with Stress Shield
(5/15 kV Switchgear)
PD Sensors
PD Sensors
PD Sensors are Installed
in Switchgear Cubicle
0
Cub12
Cub13
Cub14
Cub15
Cub16
Cub11
Cub1
Cub2
Cub3
Cub4
Cub5
Cub6
Cub7
Cub8
Cub9
Figure 5.2-6. How the Process Works—Data Analysis and Report (Sample)
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-14
Standard Layouts
Available Configurations
Drawout
Auxiliary
Drawout
Auxiliary
Figure 5.2-9. 26.00-Inch (660.4 mm) Wide Typical Auxiliary/Auxiliary Figure 5.2-11. Available Configurations
Vertical Section—Dimensions in Inches (mm)
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-15
3.00 (76.2)
23.00 Rear
1
(584.2)
3 30.00 2.00 22.00 2.00
(762.0) (50.8) (558.8) (50.8)
3.00
4
(76.2)
5B 5B
23.00
2 (584.2)
28.00
(711.2)
0.88
(4) Knockouts (22.4)
5A 5A
0.88
for Top Secondary (22.4)
Conduit Entry
9.00 6
(228.6)
6.00
(152.4) 96.25
(2444.8) 44.50
7.00 (1130.3)
(177.8) 9 60.88
(1546.4)
3.00 3.00 0.56 0.56
(14.2) (14.2)
(76.2) (76.2)
Front 5A 5A 3.38
(86.0)
3.00 3.00
Figure 5.2-12. Top View of Typical Indoor 16.00 19.00
(76.2) (76.2)
0.25
7
Breaker and Auxiliary Structures— (406.4) (482.6) (6.4)
Dimensions in Inches (mm)
a Power cable entrance area. Refer to
Figure 5.2-14 for typical conduit locations. Refer 3.88
5B 5B
to shop drawings for order specific locations. 4.25 (98.6)
(108.0) 1.25
0.88 0.88
(31.8) 5.56 4
(22.4) (22.4)
(141.2)
26.00 26.00
(660.4) (660.4) 70.00 Min.
10 (1778.0)
8
Front
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-16
11.50 (292.1)
Upper
2 7 Hinged
Panel
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Layouts and Dimensions 5.2-17
80.00
(2032.0) LL
(1)
521
36.00
RTH
(914.4)
SCD
0H7
Pad
80.00
a
(2032.0)
Figure 5.2-16. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch Figure 5.2-19. Tie Breaker Bus Transition Requirements
(660.4 mm) Wide Indoor Unit, Blank/Breaker—Dimensions in Inches (mm)
a Depth can be reduced to 72.00 inches (1828.8 mm) if power cables enter
from top.
Auxiliary or
Blank
d
521 36.00 Blank 1200 Ampere 1200 Ampere
(914.4) ND Breaker ND Breaker
RTH
SCD d Auxiliary or d
0H7 Blank
d
Pad
80.00
(2032.0) Auxiliary or
1200 Ampere Blank 1200 Ampere Blank
d
ND Breaker ND Breaker
d
d
Auxiliary or
Blank
d
Figure 5.2-17. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch
(660.4 mm) Wide Indoor Unit, Breaker/Blank—Dimensions in Inches (mm)
b Depth can be reduced to 72.00 inches (1828.8 mm) if power cables enter
from below.
VTX
(2)
80.00
(2032.0) LP
(2)
RTH
521
36.00
RTH
(914.4)
SCD
0H7
Pad
80.00 c
(2032.0)
Figure 5.2-18. 5 kV, 1200A, 250 MVA VCP-W ND Low Profile 26.00-Inch
(660.4 mm) Wide Indoor Unit, Auxiliary/Breaker—Dimensions in Inches (mm)
c Depth can be reduced to 72.00 inch (1831.7 mm) if power cables enter
from top.
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-18
Weights
Table 5.2-8. Switchgear Assembly (Less Breaker) Table 5.2-9. Circuit Breaker a
Type of Main Bus Rating, Weight Type of Current Rating, Weight Lb (kg)
Vertical Section Amperes Lb (kg) Circuit Breaker Amperes (Static)
Control Power
Table 5.2-10. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated Spring Charging Motor Close or Trip UV Trip mA Voltage Range Indicating
Control Inrush Run Average Run Amperes Maximum Close Trip Light
Voltage Amperes Amperes Time, Sec. Amperes
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-19
Operations
Table 5.2-12. Breaker Operations Information
Circuit Breaker Ratings Maximum Number of Operations a
Rated Maximum Rated Continuous Rated Short-Circuit Between No-Load Rated Continuous Inrush Current
Voltage Current Current Servicing Mechanical Current Switching Switching
kV rms Amperes kA rms, sym.
4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
a Each operation is comprised of one closing plus one opening.
Heat Loss
Table 5.2-13. Heat Loss in Watts at Full Rating, at 60 Hz
Type of Switchgear Assembly Breaker Rating 1200 A 2000 A 2500 A 3000 A 4000 A Fan Cooled
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-20
Typical Schematics
P
(+)
CS CS PR
C T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12
1 2
9A
4 7 5 6 7 8 9 10 3
3A
3
9
13
61
Y
51
53
55
57
LS1 a
bb a
Y SR
62
ST
52
56
58
54
ST 18 17 16 15 22 2
M b b 1
a
LC a
PS2 LS2 LS2
10A
PS Y
bb 1 bb aa
Not Available when Second 13
14
10
4
24 21 20 19
Trip Coil Option is Chosen
TRCO_51N
TRCS_
TCSSLT
LOCATION
Options
LOCATION
CCBSN CGL
LOCATION LOCATION
TCSSLT
TRCS_
TRCO_51N
N
(-)
1 FUSE
CAC120
LOCATION
S-MRU
S-TRU
S-CPU
CS
C
CS PR
T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
9UV
10UV
ac Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
ac (+) 12 UV
1 2
9A
4 5 9 6 7 8 10 3
10UV
7
Cap Trip Dev
3A
9
3
13
55
61
Y
51
57
53
a a
LS1 ac (–)
bb
Y SR
62
52
58
ST
54
ST 2
M 1
18 17 15 22 For ac UV
b b a
LC
a Trip Only
PS2 LS2 LS2 a
10A
bb PS Y
1 bb aa
Not Available when Second 13
14
56
10
4
2
LOCATION
CCBSN CRL
LOCATION LOCATION
TRCS_
TRSS
TRCO_51N
Options
Figure 5.2-21. Typical 5/15/27 kV VCP-W “dc” and “ac” Control Schematics
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
Application Data 5.2-21
(+)
CS CS PR
C T
11 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
Spring WL GL RL
Charged
9UV
Indicating
Light U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
UV U24
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12 OPTIONS
1 2 4 7 5 6 7 8 9 10 3
9A
13
57
3
61
3A
51
53
55
Y
LS1 a
bb a
54
62
Y
52
56
58
SR
ST
ST 18 17 16 15 22 2
b
LOCATION
M 1
b
10A
LC a
PS2 PS Y LS2 LS2 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
4
24 21 20 19
N
LOCATION
TRCS_
TCSSLT
TRCO_51N
CS
C U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
CS PR
T
11
Spring WL GL RL
Charged
9UV
U24 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
Indicating
Light
Auxiliary Switch #2 Optional
UV
10UV
ac Source
9UV
OPTIONS
TRCO_51N
TRCS_
TCSSLT
LOCATION
14
ac (+) 12 UV
1 2 4 7 5 9 6 7 8 10 3
10UV
9A
9
3A
3
61
55
51
a
53
57
Y
LS1 ac (-) a
bb
62
52
58
54
Y SR
ST
ST
1
18 17 15 22 2
For ac UV
M b a
LOCATION
b
Trip Only
10A
LC
PS2 PS Y LS2 LS2 a 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
56
4
24 21 20 16 19
2
LOCATION
TRCS_
TRSS
TRCO_51N
EATON www.eaton.com
VacClad-W 26" Wide, Metal-Clad Design Guide DG022002EN
Medium-Voltage Drawout Vacuum Breakers Effective February 2020
5.2-22
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. DG022002EN / Z23483 All other trademarks are property
February 2020 of their respective owners.