CT Sizing Calculation
CT Sizing Calculation
CT Sizing Calculation
Here In is current transformer nominal current, Is is short circuit current and
over – dimensioning factor. Most commonly KTF is used 1,2 – 2. For
example, in our case with KTF = 2, Frmin=3.
In order to select the right rating of the current transformer, we will have to
iterate for the solution by making a guess of the nominal ALF. Other
information we are going to need for this calculation: wire length 20 m,
cross section area 5 mm2, wire material is copper, Sn=5 VA, Rct=11 Ohm,
Rload = 0,5 Ohm.
First, we will try with 5P10 current transformer.
Fr is actual accuracy limiting factor. Usually actual accuracy limiting factor is
higher than nominal ALF as CT is normally under – burdened. However,
from the results we see, that F r < Frmin therefore, we should take CT with
bigger nominal ALF.
In the second iteration we will take 5P20 rating and assume that other
parameters are the same.