Professional Documents
Culture Documents
RE - 5 - Non-Directional Earth-Fault Protection Low-Set Stage (NEF1Low) High-Set Stage (NEF1High) Instantaneous Stage (NEF1Inst)
RE - 5 - Non-Directional Earth-Fault Protection Low-Set Stage (NEF1Low) High-Set Stage (NEF1High) Instantaneous Stage (NEF1Inst)
RE - 5 - Non-Directional Earth-Fault Protection Low-Set Stage (NEF1Low) High-Set Stage (NEF1High) Instantaneous Stage (NEF1Inst)
Contents
1. Introduction .............................................................................................. 2
1.1 Features.............................................................................................. 2
1.2 Application........................................................................................... 2
1.3 Input description.................................................................................. 3
1.4 Output description ............................................................................... 3
2. Description of Operation.......................................................................... 4
2.1 Configuration....................................................................................... 4
2.2 Measuring mode ................................................................................. 4
2.3 Operation criteria................................................................................. 4
2.4 Delayed reset facility and drop-off time in DT mode ............................ 5
2.5 IDMT type operation of NEF1Low ....................................................... 6
2.5.1 Standard curve groups ............................................................... 6
2.5.2 RI curve groups.......................................................................... 8
2.5.3 RD curve groups ........................................................................ 8
2.6 Setting groups ..................................................................................... 8
2.7 Test mode ........................................................................................... 9
2.8 START, TRIP and CBFP outputs ........................................................ 9
2.9 Resetting........................................................................................... 10
3. Parameters and Events .......................................................................... 11
3.1 General ............................................................................................. 11
3.2 Setting values.................................................................................... 12
3.2.1 Actual settings.......................................................................... 12
3.2.2 Setting group 1......................................................................... 13
3.2.3 Setting group 2......................................................................... 14
3.2.4 Control settings ........................................................................ 15
3.3 Measurement values ......................................................................... 17
3.3.1 Input data ................................................................................. 17
3.3.2 Output data .............................................................................. 18
3.3.3 Recorded data.......................................................................... 18
3.3.4 Events ...................................................................................... 23
4. Technical Data ........................................................................................ 24
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
1. Introduction
1.1 Features
1.2 Application
The non-directional earth-fault protection function blocks are designed for non-
directional earth-fault protection whenever the DT characteristic or, as concerns
NEF1Low, the IDMT (Inverse Definite Minimum Time) characteristic is appropriate.
Suppression of harmonics is possible.
2
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
)LJXUH )XQFWLRQEORFNV\PEROVRI1()/RZ1()+LJKDQG1(),QVW
3
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
2.1 Configuration
The measuring devices and signal types for analogue channels are selected and
configured in a special dialogue box of the Relay Configuration Tool included in the
CAP 505 Tool Box. Digital inputs are configured in the same programming
environment (the number of selectable analogue inputs, digital inputs and digital
outputs depends on the type of the hardware used).
When the analogue channels and digital inputs have been selected and configured in
the dialogue box, the inputs and outputs of the function block can be configured on a
graphic worksheet of the configuration tool. The neutral current I0 can be connected to
the Io input of the function block. Furthermore, digital inputs are connected to the
boolean inputs of the function block and in the same way, the outputs of the function
block are connected to the output signals.
The operation of the function block is based on two alternative measuring principles:
the average value of consecutive instantaneous peak-to-peak values or the numerically
calculated fundamental frequency component of the neutral current. The measuring
mode is selected by means of an MMI parameter or a serial communication
parameter.
With both the measuring principles, the operation is insensitive to the DC component
and the operation accuracy is defined in the frequency range f/fn=0.95...1.05. In peak-
to-peak measurement, the harmonics of the neutral current are not suppressed,
whereas in fundamental frequency measurement the harmonics suppression is about
-50 dB at f = n x fn, where n = 2, 3, 4, 5,...
The function block starts if the neutral current exceeds the set start current. When the
function block starts, the START signal is set to TRUE. Should the duration of the
earth fault exceed the set definite operate time or, at the inverse-time operation, the
4
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
time determined by the level of the measured current, the function block operates. The
delay of the heavy-duty output relay is included in the total operate time. When the
function block operates, the TRIP signal is set to TRUE.
The DT or IDMT timer is allowed to run only if the blocking signal BS1 is inactive,
i.e. its value is FALSE. When the signal becomes active, i.e. its value turns to TRUE,
the timer will be stopped (frozen).
When the blocking signal BS2 is active, the TRIP signal cannot be activated. The
TRIP signal can be blocked by activating the signal BS2 until the function block
drops off.
The purpose of the delayed reset function is to enable fast clearance of intermittent
faults, e.g. self-sealing insulation faults, and severe faults which may produce high
asymmetrical fault currents that partially saturate the current transformers. It is typical
for an intermittent fault that the fault current contains so-called drop-off periods
during which the fault current is below the set start current. Without the delayed reset
function the DT timer would reset once the current drops off. In the same way, an
apparent drop-off period of the secondary current of the saturated current transformer
might reset the DT timer. The adjustable delayed reset function also enables closer
co-ordination with electromechanical induction disc relays.
When the DT timer has started, it goes on running as normally even if the current
drops off, provided the drop-off period is shorter than the set drop-off time. If the
drop-off period is longer than the set drop-off time, the DT timer will reset when the
drop-off time elapses (Figure 3).
In Figures 3 and 4 the input signal IN of the DT timer is TRUE when the current is
above the set start value and FALSE when the current is below the set start value.
1
IN
0
START
TRIP
Drop-off time
Drop-off
timer
Dropoff1.fh7
Operate time
Operate
timer
)LJXUH 7KHGURSRIISHULRGLVORQJHUWKDQWKHVHWGURSRIIWLPH
5
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
If the drop-off period is shorter than the set drop-off time and the DT timer time has
elapsed during the drop-off period, the function block will trip once the current
exceeds the set value again (Figure 4).
1
IN
0
START
TRIP
Drop-off time
Drop-off
timer
Dropoff2.fh7
Operate time
Operate
timer
)LJXUH 7KHGURSRIISHULRGLVVKRUWHUWKDQWKHVHWGURSRIIWLPH
At the inverse-time mode of NEF1Low, the operate time is a function of the current;
the higher the current, the shorter is the operate time. Six time/current curve groups
are available. Four of the groups comply with the standards BS 142 and IEC 60255,
whereas the two curve groups RI and RD (RXIDG) are special type of curve groups
corresponding to the ABB praxis. The setting “Operation mode” is used for selecting
the desired operate time characteristic.
6
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
The relationship between time and current is in accordance with the standard IEC
60255-4 and can be expressed as follows
kxβ
t[s] =
I α
( ) −1
I>
where
Inverse-time α β
characteristic
Normal inverse 0.02 0.14
Very inverse 1.0 13.5
Extremely inverse 2.0 80.0
Long-time inverse 1.0 120
According to the standard BS 142: 1966 the effective current range is defined as
2...20 times the set start current. If the time/current characteristic is normal inverse,
very inverse or extremely inverse, the function has to start at the latest when the
current exceeds the set start current by 1.3 times. For the long-time inverse
characteristic, the effective current range is specified to be 2...7 times the set start
current and the relay is to start at the latest when the current exceeds the setting value
by 1.1 times. The function block NEF1Low will start and the IDMT integration will
begin once the current exceeds the set start current.
The operate time tolerances specified by the standard BS 142 : 1966 are the following
(E denotes the accuracy in per cent):
7
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
The tolerance factors have to be smaller than those defined by the standard BS 142:
1966 for currents 2 and 5 times the setting. The NEF1Low complies with the
tolerances of class 5 (E = 5.0%) for all inverse-time curves.
For example:
k
t s =
I>
0. 339 − 0. 236 x
I
I
t[s] = 5. 8 -1. 35 x ln
k x I>
The accuracy of the RI- and RD-type characteristics is 5%. Also with the RI- and RD-
type characteristics, the function block will start and the IDMT integration will begin
once the current exceeds the set start current.
Two different groups of setting values, group 1 and group 2, are available for the
function block. Switching between the two groups can be done in the following three
ways:
The control parameter “Active group” indicates the setting group valid at a given
time.
8
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
The digital outputs of the function block can be activated with separate control
parameters for each output either locally via the MMI or externally via the serial
communication. When an output is activated with the test parameter, an event
indicating the test is generated.
The protection functions operate normally while the outputs are tested.
The output signal START is always pulse-shaped. The minimum pulse width of the
corresponding output signal is set via a separate parameter on the MMI or on serial
communication. If the start situation is longer than the set pulse width, the START
signal remains active until the start situation is over. The output signal TRIP may
have a non-latching or latching feature. When the latching mode has been selected,
the TRIP signal remains active until the output is reset even if the operation criteria
have reset.
The circuit-breaker failure protection function provides a delayed trip signal CBFP
after the TRIP signal unless the fault has disappeared during the set CBFP time delay.
The CBFP output can be used to operate a circuit breaker in front of the circuit
breaker of the feeder. The control parameter “Trip pulse” also sets the pulse width of
the CBFP output signal.
9
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
2.9 Resetting
The TRIP output signal and the registers can be reset either via the RESET input, or
over the serial bus or the local MMI.
The operation indicators, latched trip signal and recorded data can be reset as follows:
10
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
3.1 General
• Each function block has a specific channel number for serial communication
parameters and events. The channel for NEF1Low is 38, that for NEF1High 39 and
that for NEF1Inst 90.
• The data direction of the parameters defines the use of each parameter as follows:
Data direction Description
R, R/M Read only
W Write only
R/W Read and write
• The different event mask parameters (see section “Control settings”) affect the
visibility of events on the MMI or on serial communication (LON or SPA) as
follows:
Event mask 1 (FxxxV101/102) SPA / MMI (LON)
Event mask 2 (FxxxV103/104) LON
Event mask 3 (FxxxV105/106) LON
Event mask 4 (FxxxV107/108) LON
For example, if only the events E3, E4 and E5 are to be seen on the MMI of the
relay terminal, the event mask value 56 (8 + 16 + 32) is written to the “Event mask
1” parameter (FxxxV101).
In case a function block includes more than 32 events, there are two parameters
instead of e.g. the “Event mask 1” parameter: the parameter “Event mask 1A”
(FxxxV101) covers the events 0...31 and “Event mask 1B”(FxxxV102) the events
32...63.
11
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
NEF1Low
12
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
NEF1Low
13
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
NEF1Low
14
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
NEF1Low
15
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
16
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
NEF1Low
17
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
3.3.3.1 General
The information required for later fault analysis is recorded when the function block
starts or trips, or when the recording function is triggered via an external triggering
input.
The data of three last operations (operation 1...3) are recorded and the values of the
most recent operation always replace the data of the oldest operation. The registers
are updated in the following order: Operation 1, Operation 2, Operation 3, Operation
1, Operation 2,...
The recording function can be blocked via the BSREG input. For example, if an auto-
reclose sequence is initiated by the trip signal of the function block, the values most
reliable for later fault analysis are those recorded just before Shot 1. When the auto-
reclose sequence has started, no recordings are needed at the moment of tripping. The
output signal ACTIVE in AR5Func indicating AR in progress is connected to the
BSREG input to prevent useless recording.
The time stamp indicates the rising edge of the START, TRIP or TRIGG signal.
3.3.3.3 Duration
If the function block trips, the current values are updated at the moment of tripping
i.e. on the rising edge of the signal TRIP. For external triggering the current values are
18
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
updated at the moment of triggering i.e. on the rising edge of the input signal TRIGG.
If the function block starts but does not trip, the neutral current value captured one
fundamental cycle (20 ms at rated frequency 50 Hz) after the beginning of the start
situation is recorded. The value of the neutral current I0 is recorded as a multiple of
the rated current In.
The status data of the input signals BS1 and BS2 as well as the “Active group”
parameter are recorded at the moment of triggering. The “Active group” parameter
indicates the setting group valid for the recorded data.
3.3.3.6 Priority
1 Tripping
2 Starting
3 External triggering,
which means that if the function block has started, it will neglect an external
triggering request.
19
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
NEF1Low
20
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
NEF1Low
21
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
NEF1Low
22
ABB Automation NEF1Low, NEF1High, NEF1Inst RE_5_ _
3.3.4 Events
23
RE_5_ _ NEF1Low, NEF1High, NEF1Inst ABB Automation
NEF1Low:
Reset time 40...1000 ms (depends on the set minimum output pulse width)
NEF1High B -
NEF1Inst B -
24