Design Criteria: Project: Client: Design By: Job No.: Date: Review by
Design Criteria: Project: Client: Design By: Job No.: Date: Review by
Design Criteria: Project: Client: Design By: Job No.: Date: Review by
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Bearing Wall Design of Insulated Concrete Form (ICF) Based on ACI 318-14 & 2018 IBC
DESIGN CRITERIA
1. Insulated Concrete Form (ICF) can be waffle grid core, and screen grid core, and/or even flat wall core. This design method is
based on linear distribution of strain, which only consider the concrete strength of screen grid core conservatively.
2. Since it is difficult to design ICF wall tension-controlled (ACI 318-14 11.8.1.1) only, this software does NOT use the method of
Alternative Design of Slender Walls (ACI 318-14 11.8), so no P- D effects have to be applied (ACI 318-11 11.8.1.1).
ANALYSIS
CHECK AXIAL & FLEXURE CAPACITY
r ProvD = 0.008611 < rMAX = 0.0800 (tension face only, ACI 318-14 22.2.3.1 or 10.6.1.1)
> rMIN = 0.0015 (tension face only, ACI 318-14 9.6.1 or 11.6.1)
[Satisfactory]
60.0 f Pn f Mn
AT AXIAL LOAD ONLY 52.4 0.0
50.0
AT MAXIMUM LOAD 52.4 2.0
AT MIDDLE 30.6 3.6
40.0 AT e t = 0.002 8.8 2.7
AT BALANCED 8.4 2.7
f Pn (k) 30.0 AT e = 0.005
t 4.3 2.7
AT FLEXURE ONLY 0.0 1.9
20.0
(Note: For middle reinforcing the max fMn is at c
equal to 0.5 t / b 1, not at balanced condition.)
10.0
0.0 [Satisfactory]
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
f Mn (ft-k)
V n 2 bd '
fc = 1.48 kips / ft > Vu [Satisfactory]