Date and Time Generated: EST 3 Sensitivity Report

10/03/2020 09:07:15
Node: AL-WAKRAH STADIUM

Panel: 3-CPU3_22_01

Label Description Panel Card Device Loop Device Threshold Threshold Percent Progra Commu Months Until
Type (Norm) (Alt) Dirty mmed nicates End of Life

ENERGY_L3_SD41_LE MEZZ ENERGY 22 3 41 SIGA-PS 3.5% OBSC 3.5% OBSC 20 Y Y N/A


D34 MECHANCALRM-01 (SD)
ENERGY_L3_SD43_LE MEZZ ENERGY ELECT. 22 3 43 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
D31 ROOM (SD)
ENERGY_L3_SD44_LE MEZZ. ENERGY 22 3 44 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
D32 CORRIDOR-02 (SD-CV)
ENERGY_L3_SD46_LE MEZZ ENERGY 22 3 46 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D30 MECHANCALROOM-02 (SD)
ENERGY_L3_SD47_LE MEZZ ENERGY 22 3 47 SIGA-PS 3.5% OBSC 3.5% OBSC 24 Y Y N/A
D48 STAIRECASE-02 (SD)
ENERGY_L3_SD48_LE MEZZ ENERGY 22 3 48 SIGA-PS 3.5% OBSC 3.5% OBSC 16 Y Y N/A
D48 STAIRECASE-02 (SD)
ENERGY_L3_SD49_LE ROOF ENERGY 22 3 49 SIGA-PS 3.5% OBSC 3.5% OBSC 24 Y Y N/A
D53 STAIRECASE-01 (SD)
ENERGY_L3_SD50_LE ROOF ENERGY 22 3 50 SIGA-PS 3.5% OBSC 3.5% OBSC 36 Y Y N/A
D53 STAIRECASE-01 (SD)
ENERGY_L3_SD51_LE MEZZ ENERGY MEETING 22 3 51 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D41 ROOM (SD)
ENERGY_L3_SD52_LE MEZZ ENERGY NEAR 22 3 52 SIGA-PS 3.5% OBSC 3.5% OBSC 8 Y Y N/A
D37 LIFT-LOBBY (SD)
ENERGY_L3_SD53_LE MEZZ ENERGY CORRIDOR 22 3 53 SIGA-PS 3.5% OBSC 3.5% OBSC 64 Y Y N/A
D35 -NR MECH RM (SD)
ENERGY_L3_SD54_LE MEZZ ENERGY CORRIDOR 22 3 54 SIGA-PS 3.5% OBSC 3.5% OBSC 8 Y Y N/A
D32 -NR ELE RM (SD)
ENERGY_L3_SD55_LE MEZZ ENERGY 22 3 55 SIGA-PS 3.5% OBSC 3.5% OBSC 8 Y Y N/A
D40 EQUIPMENTROOM (SD)
ENERGY_L3_SD56_LE MEZZ ENERGY MALE 22 3 56 SIGA-PS 3.5% OBSC 3.5% OBSC 16 Y Y N/A
D52 TOILET (SD)
ENERGY_L3_SD57_LE MEZZ ENERGY MALE 22 3 57 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D52 TOILET (SD-CV)
ENERGY_L3_SD58_LE MEZZ ENERGY DISABLE 22 3 58 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D52 TOILET (SD-CV)

1
Label Description Panel Card Device Loop Device Threshold Threshold Percent Progra Commu Months Until
Type (Norm) (Alt) Dirty mmed nicates End of Life

ENERGY_L3_SD59_LE MEZZ ENERGY DISABLE 22 3 59 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
D52 TOILET (SD)
ENERGY_L3_SD60_LE MEZZ ENERGY FEMALE 22 3 60 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D52 TOILET (SD)
ENERGY_L3_SD61_LE MEZZ ENERGY FEMALE 22 3 61 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D52 TOILET (SD-CV)
ENERGY_L3_SD62_LE MEZZ ENERGY JANITOR 22 3 62 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
D52 ROOM (SD-CV)
ENERGY_L2_SD251_L GF ENERGY STAIRCASE1 22 2 251 SIGA-PS 3.5% OBSC 3.5% OBSC 32 Y Y N/A
ED2 DOWN AREA (SD)
ENERGY_L2_SD252_L GF ENERGY FIRE 22 2 252 SIGA-PS 3.5% OBSC 3.5% OBSC 20 Y Y N/A
ED3 COMMAND ROOM (SD)
ENERGY_L2_SD253_L GF ENERGY LOBBY 22 2 253 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
ED1 (SD-CV)
ENERGY_L2_SD254_L GF ENERGY STAIR 22 2 254 SIGA-PS 3.5% OBSC 3.5% OBSC 32 Y Y N/A
ED2 CASE-01 (SD)
ENERGY_L2_HD256_L GF ENERGY GENSET RM- 22 2 256 SIGA-HRS ROR ROR 0 Y Y N/A
ED13 (HD)
ENERGY_L2_SD257_L GF ENERGY MAIN 22 2 257 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
ED14 ENTRANCE (SD-CV)
ENERGY_L2_SD259_L GF ENERGY LIFT LOBBY- 22 2 259 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED10 (SD-CV)
ENERGY_L2_SD260_L GF ENERGY STAIR 22 2 260 SIGA-PS 3.5% OBSC 3.5% OBSC 68 Y Y N/A
ED7 CASE-02 (SD)
ENERGY_L2_SD261_L GF ENERGY STAIR 22 2 261 SIGA-PS 3.5% OBSC 3.5% OBSC 24 Y Y N/A
ED7 CASE-02 (SD)
ENERGY_L2_SD262_L GF ENERGY LOBBY NEAR 22 2 262 SIGA-PS 3.5% OBSC 3.5% OBSC 40 Y Y N/A
ED1 FACP ROOM (SD)
ENERGY_L2_SD263_L GF ENERGY WORKSHOP 22 2 263 SIGA-PS 3.5% OBSC 3.5% OBSC 8 Y Y N/A
ED5 ROOM (SD)
ENERGY_L2_SD265_L GF ENERGY MAIN 22 2 265 SIGA-PS 3.5% OBSC 3.5% OBSC 68 Y Y N/A
ED8 `ENTRANCE (SD)
ENERGY_L2_SD266_L GF ENERGY NEAR LIFT 22 2 266 SIGA-PS 3.5% OBSC 3.5% OBSC 48 Y Y N/A
ED10 LOBBY (SD)
ENERGY_L2_SD267_L GF ENERGY MVSG 22 2 267 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)
ENERGY_L2_SD268_L GF ENERGY MVSG 22 2 268 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)
ENERGY_L2_SD269_L GF ENERGY MVSG 22 2 269 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)

2
Label Description Panel Card Device Loop Device Threshold Threshold Percent Progra Commu Months Until
Type (Norm) (Alt) Dirty mmed nicates End of Life

ENERGY_L2_SD270_L GF ENERGY MVSG 22 2 270 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)
ENERGY_L2_SD271_L GF ENERGY MVSG 22 2 271 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)
ENERGY_L2_SD272_L GF ENERGY MVSG 22 2 272 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED6 TRUNCH(SD)
ENERGY_L2_SD273_L GF ENERGY 22 2 273 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED15 TRANSFORMERROOM-1
TRUNCH (SD)
ENERGY_L2_SD274_L GF ENERGY 22 2 274 SIGA-PHS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED15 TRANSFORMERROOM-1(SD
)
ENERGY_L2_MSD275_ GF ENERGY 22 2 275 SIGA-PHS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
LED15 TRANSFORMERROOM-1
(MSD)
ENERGY_L2_MSD276_ GF ENERGY 22 2 276 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
LED15 TRANSFORMERROOM-1
TRUNCH(MSD)
ENERGY_L2_SD277_L GF ENERGY 22 2 277 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED15 TRANSFORMERROOM-2
TRUNCH (SD)
ENERGY_L2_SD279_L GF ENERGY 22 2 279 SIGA-PS 3.5% OBSC 3.5% OBSC 0 Y Y N/A
ED15 TRANSFORMERROOM-2
TRUNCH (SD)
ENERGY_L2_SD280_L GF ENERGY 22 2 280 SIGA-PS 3.5% OBSC 3.5% OBSC 4 Y Y N/A
ED15 TRANSFORMERROOM-2
TRUNCH (SD)
ENERGY_L2_MSD281_ GF ENERGY 22 2 281 SIGA-PHS 3.5% OBSC 3.5% OBSC 28 Y Y N/A
LED15 TRANSFORMERROOM-2
TRUNCH (MSD)
ENERGY_L2_SD282_L GF ENERGY 22 2 282 SIGA-PS 3.5% OBSC 3.5% OBSC 16 Y Y N/A
ED15 TRANSFORMERROOM-2
(SD)
ENERGY_L2_MSD283_ GF ENERGY 22 2 283 SIGA-PHS 3.5% OBSC 3.5% OBSC 28 Y Y N/A
LED15 TRANSFORMERROOM-1
(MSD)
ENERGY_L2_SD284_L GF ENERGY (SD-CV) FIRE 22 2 284 SIGA-PS 3.5% OBSC 3.5% OBSC 16 Y Y N/A
ED3 COMMAND ROOM