Professional Documents
Culture Documents
Improved Secondary and New Tertiary Voltage Control: WM Pwrs
Improved Secondary and New Tertiary Voltage Control: WM Pwrs
Improved Secondary and New Tertiary Voltage Control: WM Pwrs
voltage regulation in France is given [3, 4, 51. Prior deviations at selected nodes (pilot nodes) from their set
to proposing new solutions, critical assumptions under values. The use of pilot point measurements only, in-
which the present Secondary Voltage Control (SVC) is stead of measurements on all load buses, is referred to
implemented are reviewed [9,10, 111. in this paper as the reduced information structure at a
In section I11 of this paper, an improved control design regional level.
at the secondary level is proposed, which uses additiond To introduce these control laws, let us consider the
measurements to cancel the effects of the neighboring dynamics of each region.
regions on a regional performance criterion. This design The reactive power balance at each bus i in the region
is defined so that a regional performance criterion can can be expressed as
be met, independently from the voltage changes in the
nighboring regions as long as sufficient voltage control Qi = Z,BijVj(V, - K) + Fi (1)
reserves are available at each regional level. where Fi is the tie-line flow into bus i. (For non-
In section IV, the issue of the performance of an in- boundary buses Fi = 0).
terconnected system consisting of many electrically con- Linearizing (1)around yo= %o = 1p.u. (or any other
nected regions or utilities is studied. A tertiary level nomind operating point) one obtains
coordination scheme is proposed that optimizes this
system-wide performance criterion. The actual imple-
mentation of the proposed regional voltage coordination
Qi = E,Bij(q - vi) + F% (2)
can be decentralized (at a regional level) or centralized Using vector form to denote all load and generator
(at a tertiary level). The limits of a decentralized imple- variables in the region of interest, one obtains
mentation are addressed from the viewpoint of classes
of performance criteria that can be optimized this way. Q=[ and V =
Finally in section V, the proposed control designs are
illustrated on a large network representing two electri-
cally close regions of the French power system.
11. Survey of the EDF Secondary Voltage Equation (2) can be written as
Control
Q=DV+P ’ (5)
A. Modelling
Notice that Equation (5) is written for each region sep-
Since only the mid-term behavior of the power sys- arately, i.e. D is the sensitivity matrix of the discon-
tem is of direct interest in this paper, the transient re- nected region from the rest of the system. Equation (5)
sponse of generators and their primary controls are as- expressed in terms of variable changes at load buses
sumed stable and very fast, i.e. instantaneous relative (“states”) and generator buses (“controls”) separately
to the slow time scale of interest. Under this assump- becomes
tion, only steady state load flow equations are consid-
ered. Loads are modeled as constant power devices. To
review the basic model presently used in designing the
secondary voltage control in France, a standard real/ under the constant load modeling assumption QL = 0,
reactive power decoupling assumption is made. resulting in
The control problem under consideration in this paper
is not a conventional one since no natural dynamics are VL = -D;~(DLGVG +PL) (7)
modeled, i.e. they are assumed instantaneous. Instead,
a sequence of steady state voltages is defined. The load The control variable U is defined as the rate of change
voltages are changing in response to changes of steady of generator voltages and the state variables 5 are actual
state set points of generators. Changes are initiated by load voltages Vh. Then (7) written in a system-theoretic
a load deviation away from the nominal, or by topologi- setting takes on the form
cal changes of network parameters. In order for the load
j: = C,U -D;~FL (8)
flow equation to be satisfied for these new parameters,
one needs to compute changes in set points of genera- where
tor voltages AVG which would bring the load voltage C, = - D ; ~ D ~ ~ (9)
deviations AVL back to zero. In this context, load volt-
One should interpret (7) as a relationship at each re-
ages AV, can be thought of as system state variables,
gional level between its own load voltages and own gen-
which are regulated by changes in generator voltages
erator controls, whereas the effect of the interactions
AVG. I. Furthermore, in the present implementation
i,. France controls react only in response to load voltage 2Throughout this paper an approximate notation is used for
x = (z((i+ 1)T) - z(zT))/T,where the ith value represents the
‘In the rest of the paper for simplified notation A symbol is ith steady state solution in the sequence of solutions of interest.
omitted Here T stands for sample time of the process control computer.
1853
with the rest of the system is only seen through the sec-
ond term proportional to the reactive flow changes FL vp = CVL (14)
into the area. This is a fully decentralized, exact in-
Assume the feedback is proportional to the deviation
terpretation of small signal changes at the regional level.
measurements from their set values
The flow changes can be also interpreted in terms of
slow aggregate variables as defined in [14]. In [14] the = VG = K(Vp - V p )
U (15)
aggregate variables relevant for the inter-regional effects
are defined to be any linear combination of load voltages where VFt denotes the set (desired) values of critical
which does not change if the tie-line flows are kept con- load voltages in the region. For selection of K see
stant, under a n y form of secondary control law. Trans- [4]. With this output feedback control, the closed-loop
lating this definition into mathematical relations, one model describing pilot point load voltage changes can
obtains an intriguing relationship between the aggregate be written as
variables and the tie-line flows. This relationship is con- Vp = A(Vp - VFt> (16)
sidered to be a direct rationale for proposing a reduced
where A = C, K .
information structure for system-wide voltage coordina-
Note that the success of an incoordinated secondary
tion in terms of individual tie-line flows in addition to
control for each region briefly reviewed here strongly de-
the existing regional measurement structure.
pends on a good choice of a voltage control region. A
This leads to the dynamics of the aggregate variables
region is well defined 141 if the following three assump-
as
tions hold:
y = PC,U - PDLLFL (10)
which, in order to meet the above definition requiring e Assumption 1: When the voltage of pilot node is
that whenever FL = 0 this implies y = PC,u = 13, is maintained at a steady level, the variations of the
defined as y = Px,where matrix P satisfies other load voltages in the region remain small even
with the load variations.
PC, = 0 (11)
e Assumption 2: The control actions in a given
Following the same derivations as in [lo], it is straight- zone do not cause significant voltage variations in
forward to show that the other zones.
e Assumption 3: The zone has sufficient voltage
control $0 keep the pilot point voltages steady in
Relationship (12) states that the aggregate variables each region, in both normal and emergency condi-
defined as above are simply linear combinations of tie- tions.
line flows into the load buses only. These variables are
shown to be essential in forming a reduced-order model For the purposes of this paper the first assumption
for centralized TVC [14]. considering closeness of pilot and non-pilot load volt-
ages in a region of interest is not discussed further, it
B. Presently Implemented Secondary Voltage is considered to hold. The “best” pilot point nodes can
Control (SVC) be chosen for instance using the mathematical measures
introduced in [9, 12, 131. The validity of the second
In this section relations among relevant variables and and the third assumptions and ways of improving the
controls described above are simplified assuming negli- present design when they do not hold are studied in the
gible connections to the neighboring regions. Equation following sections.
(8) becomes
x = c,u (13) 111. A New Improved Secondary Voltage
Control (ISVC)
since the term FL is neglected. This model is identical
to the model used for the SVC in France at present time A. Limitations of the Present SVC
~31.
A particularly important feature of the model given The proposed Improved Secondary Voltage Control
in (13) is that it is not fully controllable since the sensi- (ISVC) design is discussed under Assumption 1 of well
tivity matrix C, whose dimension is ( nx g ) is not of full defined voltage regions.
rank for n > g, where n is the number of all loads, and It was proven in [14] that, with the present SVC [4] un-
g is the number of generators. Because the system is der certain assumptions, typically valid for wide ranges
not fully controllable, and because it is not desirable to of voltage changes, no slow persistent inter-regional volt-
measure all load voltages, a measurement (output) feed- age oscillations can take place as a result of strong effects
back z to the control signal U is introduced, instead of a of voltage changes in the neighboring regions; indeed,
feedback to all variables 2. To model this output feed- this can not occur as long as all the generators are oper-
back, suppose measurements (for example, pilot node ating within their limits and the coupling with the real
load voltages) are defined as power changes is negligible.
1854
However, because the interconnections are becoming In conclusion, the advantage of the ISVC over the
stronger, the settling time could deviate significantly SVC lies in that it ensures a guaranteed time-response
from the anticipated response under the presently im- (3 minutes in the French implementation) at the sec-
plemented SVC, which basically assumes no changes in ondary control level independently of the disturbances
the near-by voltages. Therefore, it is expected that the which occur in the neighboring regions and no matter
improvements of any type of ISVC over the presently im- how tightly the regions are connected.
plemented SVC which depend on this assumption will
only be seen in the guaranteed performance criterion de- IV. Coordinated Voltage Control of a
fined at a regional level, independently from the level of Multi-regional Electric Power System
voltage deviations in the neighboring regions. One such
new design for ISVC is described and illustrated by sim- It can be seen from the previous section that an ISVC
ulations on two regions of the Rench network in Section scheme is possible to introduce at a regional level, and
V. that the main purpose of such improvement would be to
guarantee a regional performance independently from
B. ISVC Design the voltage changes in neighboring regions. This is true
as long as the operating ranges are such that the system
The present state of secondary voltage regulators is matrix C,, in Equation (13) remains positive definite and
based only on the regional measurements, i.e. regional as long as no constraints on voltage controls are reached,
pilot point voltages. We are proposing in this section nor secondary units tripping takes place.
possible ways to improve the secondary level, by taking The situation becomes qualitatively more complex
into consideration the effect of interconnections, while when a control design is required for re-scheduling
preserving its decentralized nature. The proposed con- system-wide reserves by changing reactive power tie-line
trol laws will be such that they cancel out the effect of flows among the regions in order to manage the reactive
interactions based on additional feedback signals which power/ voltage constraints in specific regions within an
use the reactive power tie-line flow measurements. To inter-connected system. Two crucial questions could be
introduce these control laws, we start with the regional asked in this context: Is it realistic to rely on reactive
model which does include effects of flow deviations given power/ voltage support from electrically distant areas,
in Equation (10) above. An improved control law of the and if so, when is this needed? While the most economic
form real power tie-line flow scheduling is routinely done at
PG= K(Vp - VFt) GFL + (17) many systems in order to optimize a system-wide cost of
is proposed. It can be seen that this control law has an real power supply, it is not obvious that a similar concept
additional term relative to the presently implemented would be meaningful and feasible for voltage scheduling,
SVC (15) which is intended to respond to deviations in particularly because of the fundamental property of re-
line flows in such a way that their effects are canceled active power not “traveling” far [8].
out as seen at the secondary level. This will lead to the It is only when voltage constraints begin to be ap-
secondary voltage regulation according to exact specifi- proached that the effect of neighboring regions could
cations at the regional level. It was shown that if the become significant. Otherwise, as it was shown in the
gain G in (17) is chosen so that previous section, it is only an issue of ti
and the quality of regional response at which the inter-
connected system would settle.
In principle one could implement a coordination
the closed-loop pilot point response will be according to
scheme relevant for a system-wide performance criter
vp = CC,K(Vp - V p ) in either an entirely decentralized setting (at a regio
(19)
level), or one could have a centralized scheme. The later
Gain K i s now chosen at *he regional level, for known implementation is often referred to as a tertiary level.
C and C, of this region, so that the desired response is On the French power network, the centralized scheme
achieved. For example, it is very simple to choose K so would be associated with the national cont
that the regional pilot voltages reach their steady state Paris. A new framework for system-wide coordination
within 3 minutes, no matter what else is happening on and the conditions under which it could be implemented
the system. in a decentralized way are discussed next.
Notice that this control scheme would be extremely
simple to implement by enhancing an already exist- A. Proposed Decentralized Implementation of
ing secondary controller by an additional feedback sig- System-wide Voltage Controls
nal @FL, which would use measurements of line flow
changes into the region. To start with, since the main objective of reactive
power/ voltage inter-regional coordination is to manage
*This statement is qualified in the sense that it strictly holds
only under the assumption that the sensitivity matrix of the in- most effectively voltage control constraints that can not
terconnected system remains positive definite. If this is not met, be avoided by using only regional reserves, any poten-
more complicated control strategies are needed. tially useful system-wide criterion for voltage manage-
1855
ment has to include voltage control constraints. Denot- Under certain conditions on the chosen criterion a
ing by uivector of voltage controI deviations from their decentralized up-dating of regional voltage controls in
most desired, optimal values, in region i terms of their measured reactive power tie-line flows ac-
cording to Equation (24) leads to a system-wide opti-
u [ K ]= V Z t [ K ]- v;pt (20) mum of the performance criterion (21) which is the sum
the simplest effective system-wideperformance criterion of all regional performance criteria [14]. These condi-
would be of the form tions reflect mutual dependence of the scheme on the
performance criterion chosen, strength of electrical in-
T T
terconnections among the regions and the rate at which
the coordinating control is implemented. When these
%=I 2= 1
conditions are met a tertiary, centralized implementa-
where r is the total number of regions and control vector tion becomes unnecessary. Moreover for more general
U consists of control subvectors of all individual regions. criterion a partially decentralized scheme can be used
The basic task of the coordination scheme is to compute for tertiary voltage coordination as shown in [14].
system-wide voltage control set values Vgt so that the The system-wide optimization should not be imple-
system-wide performance criterion (21) is optimized, i.e mented at any rate Ti higher than the rate associated
so that the voltage control settings on active generators with the settling time needed at the secondary level TS
and the correspondingpilot point set values deviate least to respond to the newly scheduled set points. For typi-
from their optimal values. Recall that the regional con- cal present implementation of the automated secondary
trollers attempt to reach these set values according to controllers this implies that Tt should not be shorter
the feedback law (15). As long as all voltage controls than 3 minutes, which is present settling time of the
are within their acceptable constraints SVC on the French network.
VfPt = Vf;et[ K ] ~
(22) B. Proposed Optimization at the Tertiary Level
This claim will be clearly illustrated in the section on In the most general case, when the constraints on
numerical simulations. some relevant output variables are hard, a general
Next, we use a conjecture, which is rigorously proven system-wide performance criterion of the type
in [14], that for a wide class of system-wideperformance
criteria which are additive in terms of regional perfor- (YW + ll)TRYIK + 11
mance criteria of the same type, and which are functions J = +(Vp[K+ l])TNVp[K+ 11 (25)
of control vectors only, an entirely decentralized coordi- +
+(u[K l])TMU[K + 11
nation of voltage controls is possible which leads to a needs to be used for which a decentralized implementa-
system-wide optimum. The basic scheme of such a de- tion is out of the question. The most typical example
centralized approach is described next. of such performance criterion is the total transmission
Consider an administratively separated region i loss [7]. This is computationally a much harder prob-
within an interconnected system. The task is to deter- lem, since a centralized information structure is needed
mine controls U ' , in order to minimize a cost function about the inter-connected system level. Using similar
of the form (21), where i = I , 11,...T . The relevant modeling for the entire system as for individual regions,
voltages and controls in each region are related via sys- a centralized implementation, again in terms of mini-
tem constraints given in (7). A discrete-time version of mum system-wide information structure, is possible.
this constraint is obtainable by integrating the model The model
(7) between two successive implementation steps K and
+
( K 1) of coordinating controls and is of a general form y[K+ 11 = y[K]+PCwKs(CCw)-l(VPIK+11--VP[K])
V j [ K+ 11 = Aiui[K]+ BiFi[K]+ L%[K] (23)
(26)
represents the algebraic relationship between the devi-
where A z ,B2, L: are constants, Fi is the vector Qf tie- ations in set points of flows and pilot point voltages on
line flows into the region i. The result of this decentral- the interconnected system. We refer to it as an aggre-
ized optimization process is : gate model since it suppresses constraints which are
not of direct interest for the coordination. However,
ui[K + 11 = f ( F " K ] ) (24) this model is centralized since it requires full knowledge
of the inter-connected system matrices Cw, P and C.
One can then compute the system-wide pilot-nodes set
For notational simplicity we denote
pointe using Equation (23) at each regional level for the
+
next implementation at step ( K 1). These new set- L = PCwK(CCw)-l (27)
points are solely based on regional flow measurements
at current step K . This matrix L is computed using the inter-connected
system Jacobian.
31t is worth recognizing that this conjecture is the basis for
the present decentralized real power tie-line flow scheduling in the Equality constraint (26) is essential €or the efficient
United States. optimization of the interconnected system.
1856
COULAS71
TRI.PS61
TAVELS71
SEPTES61
CHAFFS71
~ P.CORS71
GIVORS61
P.BOL%I @ +Q i o PRATCS63 CPNIES61
B ALBERS71
b'igure 1: Tie lines on the studied network
Table 1: Pilot-nodes and units in the studied regions
________-__------ __-____-____
-, . . . . . . . . . , . . . . . . . .
TAVELFII i l l
................................. .....
0 100 200 300 400 500
Timdsec
(b) Unit voltages
0 lo00 1500
Timdsec
[a) Scheduling with higher voltages
0 200 300 400
Timdsec
(c) Unit voltages
41 14 -1
ALHEKS7 I (4)
___ t/ CPNIES71 (4)
...
loo0 1500
1.-_......................................... * ...............
~ ..-.:-.’ . -1
Time/sec
(b) Scheduling with lower voltages
where AV,,, denotes the corrective action in region 2. 1) Due to the static nature of the network constraints, all
Thus, the proposed scheme reduces the effects in region 1 deviations for different quantities must be defined for the
due to region 2 from C C u ~ ~ ( A V g ~ i + A VtogCCvi2AVg2,,
~,) same time interval. For example, the voltage deviation is
which, taking into account the predominant effect of the defined as:
local action, constitutes an important coupling reduction.
Other coordination schemes are also possible, for instance AI’C: = VG ( k + 1) - I G ( k )
a control law in which the corrective term is designed to ay noticed in (2) of the discussions. The line flow is defined
minimize voltage changes a t frontier buses (with other for the same time interval, i.e.,
control regions). Notice that with this scheme, no infor-
mation is required from neighbouring regions. AFL = FL ( k + 1) - F L ( ~ )
3) Another point of discussion refers to expression (18) of With the consistent definition, the feedback control law
the paper, in which the authors consider the inversion of can be explicitly written as:
the matrix (CC,), so it is assumed that the number of
pilot buses is equal to the number of control generators, A\b(k) = IC (I>(k) - \,yet)+G(F’(k+ 1)- F L ( ~ ) )
so that (CCu)is an square matrix.
Usually, the required number of pilot buses is much smaller instead of (1) in the discussions. This, of
than the number of control generators. In [l] a suitable mea,surenient of the line flow at, the same ti
objective function to select pilot buses is proposed. It would argue that this is not practical. With the line flows
is shown that a reduced set of appropriate selected pilot varying not rapidly, it does not make much difference to
buses saturates the objective function so is useless to con- use a delayed version of the line flows.
sider a greater number of pilot buses. The same conclusion
can be obtained considering an objective function such as 2) It, is true that any generat,or voltage changes in one area
the one proposed by one of the authors in reference [I21 will affect the rest of the system. However, this effm~,is
of the paper under discussion. s e n by any area in the form of changes in tie-line flows.
This is exactly one of the motivations for the proposed
In addition, the freedom degrees between the number of contsol scheme. No detailed information on t,h
required pilot buses and the number of control generators ling generator voltages of other areas is needed. If one can
could be used to coordinate reactive power reserves to measure the tie-line flows, and use them in the feedhack
improve the security margin to the voltage collapse. signal for controls, then any variations iri the rest of the
We would appreciate any comments on the previous is- system can be completely cancelled in the pilots (not in all
sues. voltages), provided that nieasurenients at the same instant
are available.