PROJECT: PROPOSED OFFICE BUILDING

LOCATION: CABRERA DRIVE CORNER LEGAZPI STREET, ASEANA BUSINESS PARK, PARANAQUE CITY
OWNER: SINOCAN REALTY CORP

1.) Provide vandex capillary type waterproofing and reglet capillary plug.
2.) Verify PC-5 thickness. Plan=1900mm Section= 1800mm, which will Govern?
3.) Verify PC-17 thickness. Plan=1400mm Section= 1000mm, which will Govern?
4.) Verify TB(T), TB(B), BB(T), and BB(B) diameters and spacing for PC-17.
Differ to Plan and Section
5.) SW-1 thickness differs from the architectural plan by 200mm.
6.) SW-2 thickness and alignment differs from the architectural plan.
7.) SW-3 thickness and alignment differs from the architectural plan.
8.) Provide separator beams.
9.) Verify. 450 pile size
10.) Verify beam. (if needed)
11.) Move beam conflict to stair width
12.) Move beam conflict to curtain wall glass
13.) Move beam conflict to hoistway
14.) Verify Planted column location and detail