Professional Documents
Culture Documents
P15. - Dynamic Performance of Air Conditioners With Variable Frequency Drive
P15. - Dynamic Performance of Air Conditioners With Variable Frequency Drive
Fig. 5. Voltage (V) and real power (P) versus time during 70% ramp-
down voltage
Fig. 6. Voltage (V) and current (I) versus time during 12-cycle under-
voltage transients
6. All AC-VFDs rides through 0.8 p.u. under-voltages
for 130 cycles, except AC-VFD#6 that shutdown
when the voltage was recovering
Fig. 9. Frequency (F) and current (I) versus time during 130-cycle
under-frequency transients
3. AC-VFD#2’s electrical current increments during
under-frequency events, this performance is not
desirable since it will increase the stress into the grid
during under-frequencies.
4. AC-VFD#4 electrical current decrements during
under-frequency events, this performance is
beneficial to the grid since it will decrease load
during under-frequencies.
Fig. 7. Voltage (V) and current (I) versus time during 130-cycle
undervoltage transients
Fig. 12. Frequency (F) and current (I) versus time during 130-cycle TABLE 4. AC-VFD Total Harmonic Distortion
over-frequency transients (AC-VFD#2 and 4)
#
F<3KHz F<6KHz F<12KHz F<24KHz
H. Harmonics Generation
L1 L2 L1 L2 L1 L2 L1 L2
In order to calculate the AC-VFDs’ harmonics 1 14 14 14 14 14 14 14 14
generation, an extremely high sampling data was 2 39 39 39 39 39 39 39 39
captured from each of the tests, 1 million samples per 3 28 28 28 28 28 28 28 28
second (16,666 samples/cycle). Fig. 13 shows all the AC- 4 12 12 12 12 12 12 12 12
VFDs current and the voltage sinusoidal waveform. This 5 16 16 16 16 16 16 17 17
data shows high harmonic levels on all the AC-VFDs. 6 45 45 46 46 46 46 46 46
Fig. 14 has all AC-VFDs current harmonics calculations 7 14 14 14 14 14 14 14 14
(based of the fundamental) up to the 19th harmonic. The
key findings are the following:
1. All AC-VFDs have high harmonics current I. Conservation Voltage Reduction (CVR)
contribution. This test was performed to assess the AC-VFDs’
2. AC-VFD#2 & 6 have extremely high 3rd harmonics performance during conservation voltage reduction
(>35% of fundamental). (CVR). The CVR consisted of steps of 1% (0.01 p.u.) for
3. AC-VFD#2, 3, 5, & 6 have high 5th harmonics (>10% 5 seconds from steady state to 90%. Fig. 15, 16, 17, & 18
of fundamental). have the AC-VFDs electrical characteristics during the
4. AC-VFD#2, 3, & 6 have high 7th harmonics (>4% of CVR. The key findings are the following:
fundamental). 1. All AC-VFDs electrical current increases during the
CVR event.
VI. REFERENCES
Fig. 18. Voltage (V), real and reactive power (P & Q) versus time during [1] Euromonitor International. “Consumer Appliances in the US
CVR (AC-VFD#4) Report.” Internet: www.euromonitor.com/consumer-appliances-
in-the-us/report, October 2, 2012.
[2] Bravo, R.J.; et all; “Three phase solar photovoltaic inverter
IV. RECOMMENDATIONS testing,” IEEE PES Power Systems Conference and Exposition;
It is imperative that electric loads have no or minimum Vancouver, BC; July 2013
negative effects in the grid. In order to minimize AC-
VFDs impacts on the grid, they need to be designed with
the following characteristics:
1. Harmonics generation: All the AC-VFD units have
high harmonics current contribution. These units