Instruction manual
GRD200---
S, G, and T positions
TOSHIBA ENERGY SYSTEMS & SOLUTIONS CORPORATION
Safety Precautions
Before using this equipment, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GR
equipment. Before installing and using the equipment, this chapter must be thoroughly read
and understood.
Explanation of symbols used
Signal words such as DANGER, WARNING, and CAUTION, will be followed by
important safety information that must be carefully reviewed.
DANGER
•Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to
be opened while the primary system is live. Opening the CT circuit will produce a
dangerously high voltage.
WARNING
•Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage
generated is dangerous.
•Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power
supply. It takes approximately 30 seconds for the voltage to discharge.
•Fiber optic
CLASS 1 LASER PRODUCT.
ii
6F2S1927 (0.18)
CAUTION
•Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
•Operating environment
The equipment must only be used within the range of ambient temperature, humidity and
dust detailed in the specification and in an environment free of abnormal vibration.
•Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check
that they conform to the equipment ratings.
•Printed circuit board
Do not attach and remove printed circuit boards when the DC power to the equipment is
on, as this may cause the equipment to malfunction.
•External circuit
When connecting the output contacts of the equipment to an external circuit, carefully
check the supply voltage used in order to prevent the connected circuit from overheating.
•Connection cable
Carefully handle the connection cable without applying excessive force.
•Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
•Short-wire (Short-bar)
Do not remove the short-wire/short-bar(s) connected to the frame earth (FG) at the terminal
block on the rear of cases.
•Electric wire between #35 - #37 on the power-supply terminal block
Make sure the wire is connected.
(Exception: This wire needs to be detached for performing the dielectric voltage test.)
iii
6F2S1927 (0.18)
•Disposal
This equipment contains neither expendable supplies nor parts that can be recycled. When
disposing of this equipment, the customer must contact an operator responsible for
industrial waste disposal, and request that the operator dispose of this equipment in
accordance with the local waste disposal regulations; otherwise the person who disposes
of this equipment may be punished under local regulations. When disposing of this
equipment is practiced by the customer acting on their own behalf, it must be done so in a
safe manner according to local regulations. For further information in terms of the disposal,
the customer shall contact to a local dealer and sales staff at Toshiba Energy Systems &
Solutions Corporation (Toshiba ESS, Japan).
This equipment contains neither expendable supplies nor recyclables.
•Plastics material
This equipment contains the following plastics material.
- ABS, Polycarbonate, Acrylic resins, Nylon 66, and others.
•Equipment operation
The user shall have responsibilities to use and install the equipment where the
specifications are designated by the manufacture. Never operate the equipment on the
condition where the manufacture cannot intend. Otherwise, the safety function furnished
into the equipment may not be operated properly.
•Symbols
Symbol Description
iv
6F2S1927 (0.18)
•Copyright
© Toshiba Energy Systems & Solutions Corporation 2020.
All rights reserved.
•Registered Trademarks
Product/Equipment names (mentioned herein) may be trademarks of their respective
companies.
v
6F2S1927 (0.18)
Contents
1 Introduction ............................................................................................................................................ 1
Relay applications ........................................................................................................................... 3
Control and monitoring application ............................................................................................... 5
Monitoring and recording functions............................................................................................... 6
Hardware overview ......................................................................................................................... 6
Symbols used in logical diagrams .................................................................................................. 8
Abbreviation .................................................................................................................................. 12
Function Block (FB), Function ID, Signal number (Data ID) .................................................... 14
2 Relay application .................................................................................................................................. 16
Overcurrent protection (OC)......................................................................................................... 17
2.1.1 Relay polarity ......................................................................................................................... 18
2.1.2 Inverse time and definite time delay characteristic ............................................................ 21
2.1.3 Threshold value for operation ............................................................................................... 28
2.1.4 Reset Ratio.............................................................................................................................. 28
2.1.5 Miscellaneous functions......................................................................................................... 28
2.1.6 Scheme logic ........................................................................................................................... 30
2.1.7 Setting ..................................................................................................................................... 32
2.1.8 Signal ...................................................................................................................................... 37
Earth fault protection (EF) ........................................................................................................... 40
2.2.1 Relay polarity ......................................................................................................................... 41
2.2.2 Inverse time and definite time delay characteristic ............................................................ 43
2.2.3 Threshold level for operation ................................................................................................ 48
2.2.4 Reset Ratio.............................................................................................................................. 48
2.2.5 Miscellaneous functions......................................................................................................... 48
2.2.6 Scheme logic ........................................................................................................................... 49
2.2.7 Setting ..................................................................................................................................... 51
2.2.8 Signal ...................................................................................................................................... 56
Inrush current detection function (ICD)...................................................................................... 58
2.3.1 Operation and characteristic................................................................................................. 59
2.3.2 Scheme logic ........................................................................................................................... 59
2.3.3 Setting ..................................................................................................................................... 60
2.3.4 Signal ...................................................................................................................................... 61
Sensitive earth fault protection (SEF) ......................................................................................... 62
2.4.1 Relay polarity ......................................................................................................................... 63
2.4.2 Inverse time and definite time delay characteristic ............................................................ 65
2.4.3 Threshold level for operation ................................................................................................ 72
2.4.4 Reset Ratio.............................................................................................................................. 72
2.4.5 Miscellaneous functions......................................................................................................... 72
vi
6F2S1927 (0.18)
vii
6F2S1927 (0.18)
viii
6F2S1927 (0.18)
ix
6F2S1927 (0.18)
x
6F2S1927 (0.18)
xi
6F2S1927 (0.18)
xii
6F2S1927 (0.18)
xiii
6F2S1927 (0.18)
xiv
6F2S1927 (0.18)
xv
6F2S1927 (0.18)
xvi
6F2S1927 (0.18)
xvii
6F2S1927 (0.18)
xviii
6F2S1927 (0.18)
xix
6F2S1927 (0.18)
xx
6F2S1927 (0.18)
xxi
6F2S1927 (0.18)
1 Introduction
Contents Page
Abbreviation 14
Control 5
Function identifies and signals (FB) 14
Hardware overview 6
Monitoring and metering functions 6
Protection functions 3
Symbols used in logical diagrams 8
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
1
6F2S1927 (0.18)
GRD200—Multi function protection IED—has been designed for protection and control of low
and medium voltage system. The IED can adapt to not only distribution lines and transmission
lines but also versatile system, such as renewable energy system and railway application
system. The IED has also designed for extensive hardware and modular software combinations.
User, thus, can be provided functions flexibly; and user can obtain good performance, high
quality and high reliability. The functions, which the IED includes, are divided into the
following chunks:
Relay application;
Control and monitoring application;
Recording function;
Monitoring function.
Figure 1.1-1 illustrates the GRD200 IED, which are grouped by the application and the size,
which can be selected by the ordering code. The above functions are discussed in this
instruction manual.
GRD200-3D software model (w/ control) GRD200-3E software model (w/ control)
GRD200-3F software model (w/o control)
Current relay with 3-phase reclosing Voltage plus 1+3-phase reclosing relay
plus Control functions
Small case (1/3 size) Large case (1/1, 3/4 or 1/2 size)
GRD200-30 software model (w/ control) GRD200-36 software model (w/o control)
GRD200-32 software model (w/o control)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 2 -
6F2S1927 (0.18)
Relay applications
The GRD200 relay can provide several main/backup protection applications for feeder or a
machine, motor or transformer, etc. The applications are chosen by the selection of software
models. The user is able to set the protection functions simply and effectively.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 3 -
6F2S1927 (0.18)
setting group in normal operations, for a period after energizing the system.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 4 -
6F2S1927 (0.18)
operation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 5 -
6F2S1927 (0.18)
Monitoring function:
This function supervises status of protection functions, and displays power system quantities.
It also shows failure information in the CT.
Hardware overview
The IED has human machine interface (HMI), which is made of LCD screen, indication lights,
operation and function keys, monitoring jacks, and a USB connector. Voltage, current input
terminals, and binary input and output circuits are provided on the rear..
HMI features:
- Menu-driven human interfaces for settings or viewing of stored data.
- A standard LCD or a large LCD (MIMIC) screen, LEDs, function keys and operation keys
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 6 -
6F2S1927 (0.18)
Communication features:
- USB for GR-TIEMS
- 100BASE-TX(or FX) for SAS in the IEC 61850 protocol
- RS485 or the fiber optic I/F in the IEC 60870-5-103 protocol
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 7 -
6F2S1927 (0.18)
3. Marked with : PLC connection points designated by Element ID and its name
Element ID (or Signal No.) Signal name corresponding to Element or Signal No.(Data ID)
Note that the symbol can be used for the reception point coming from the output of PLC
logics.
4. Marked with : Mapping points designated by Signal No. (Data ID) and its name
Signal number (Data ID) Signal name corresponding to Signal No. (Data ID)
1Note that the symbol can be used as a signal reception-point coming from the SAS. The
reception point is mapped to the LN of the IEC61850.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 8 -
6F2S1927 (0.18)
XXX
t 0
Variable timer (XXX ─ YYY: Setting range)
XXX ─ YYY
Delayed drop-off timer
0 t Fixed timer (XXX: Set time)
XXX
0 t
Variable timer (XXX ─ YYY: Setting range)
XXX ─YYY
One-shot timer
A Output A
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 9 -
6F2S1927 (0.18)
A B Output
A
1 1 1
& Output
B 1 0 0
0 1 0
0 0 0
OR gate
A B Output
A
1 1 1
≥1 Output
B 1 0 1
0 1 1
0 0 0
XOR gate
A B Output
A
1 1 0
=1 Output
B 1 0 1
0 1 1
0 0 0
Signal inversion
A Output
0 1
A 1 Output
1 0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 10 -
6F2S1927 (0.18)
A S 0 0 No change
Output 1 0 1
B R 0 1 0
1 1 0
Switch Output
+ Output
On On 1
Off 0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 11 -
6F2S1927 (0.18)
Abbreviation
Abbreviation Description
ADC Analog to digital converter
CB Circuit Breaker
CT Current Transformer
DS Disconnecting Switch
EF Earth Fault
ES Earthing Switch
LCD Liquid Crystal Display for IED screen (standard LCD screen)
NA Not Applicable
SC Station Computer
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 12 -
6F2S1927 (0.18)
Abbreviation Description
UTC Coordinated Universal Time
VT Voltage Transformer
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 13 -
6F2S1927 (0.18)
FB (Function ID=123456)
80000xxxx0 8000xxxxxx
A & ≥1 XX1_OPT
81000xxxx1
XX1 B &
82000xxxx2
C
&
Element ID Signal name
&
8000011xxx0 XX_BLOCK 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 14 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 15 -
6F2S1927 (0.18)
2 Relay application
Contents Pages Pages
Autoreclose (ARC) 272 Pilot scheme with EF relay(DEFCAR) 197
-Blocking reclose in CBF 91 Sensitive earth fault (SEF) 62
-Blocking reclose in EF 48 Switch on to fault with OC (SOTF-OC) 84
-Blocking reclose in OC 28 Synch check relay(VCHK) 345
-Blocking reclose in OCN 109 -VCHK for 1CB 346
-Blocking reclose in OCV 246 -VCHK for 1.5CB 347
-Blocking reclose in SEF 72 Thermal overload protection(THM) 119
-Three-phase reclosing relay 272 Trip circuit(TRC) 366
-Single and three-phase reclosing relay 300 -Three-phase trip circuit 366
Broken conductor detection(BCD) 130 -Segregated-phase trip circuit 376
Circuit breaker failure (CBF) 88 Under current relay(UC) 96
Cold load protection(CLP) 125 Under voltage phase-to-neutral(UV) 175
Common protection(PROT-COMM) 398 Under voltage in phase-to-phase(UVS) 186
-Selection of breaker system 399 VT failure(VTF) 387
-CB setting 399
-DS setting 403
CT failure(CTF) 393
Earth fault(EF) 40
Fault locator(FL) 257
Frequency relay(FRQ) 208
Inrush current detection(ICD) 58
Over current depending voltage(OCV) 235
Over current in negative(OCN) 101
Over current (OC) 17
Over voltage in ground fault(OVG) 157
Over voltage in negative sequence(OVN) 166
Over voltage in phase-to-neutral(OV) 137
Over voltage in phase-to-phase(OVS) 147
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 16 -
6F2S1927 (0.18)
To simplify the description, only OC1 is discussed but is applicable to the other OCs;
hence, read the expression for OC1 as OC2, OC3, and OC4 at each stage unless a special
explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.1-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.1.1 Non-directional ✓ ✓ ✓ ✓ ✓ NA NA
2.1.1 Directional ✓ ✓ ✓ NA NA NA NA
2.1.5 Blocking by VTF ✓ ✓ ✓ NA NA NA NA
– Number of steps 4 4 4 4 4 NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 17 -
6F2S1927 (0.18)
Reference voltage or
θ1 Polarizing voltage2 (Vpol)
A reference signal, that is, a polarization signal is required by the directional OC element,
the reference signal is derived from a phase-to-phase voltage: for example, the directional OC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 18 -
6F2S1927 (0.18)
element for phase-A (OC-A) uses the phase-B-to-phase-C voltage rotated by 90° (VBC90°) in
the leading direction, this reference signal is illustrated in Figure 2.1-2. The direction of the
current in the protected circuit, in this case the phase-A current (IA), is determined from the
angle measured for IA against VBC90°. The purpose of using VBC in the 90° leading position
is so that the reference voltage (VBC90°) takes the same direction as the phase-A voltage (VA)
because the directional-sensing element requires a reference quantity that is reasonably
constant against which the current in the protected circuit can be compared. As a result, when
a fault occurs, the fault current IA will lag VBC90°. Similarly, for the phase-B directional OC
element (OC-B) where the object current is (IB) the reference voltage (VCA90°) is adopted. The
phase-C directional element (OC-C) uses the same approach as the OC-A and OC-B elements.
Table 2.1-2 shows the relationship between each current and its respective reference voltage.
VBC90°
Leading 90°
VA
VBC
VBC
For a close-in three-phase fault, the three reference voltages VBC90°, VCA90° and
VAB90° may fall below the minimum threshold voltage for the directional OC element. In
order to cover this case, a voltage memory function is used to provide a polarizing signal. The
polarizing signals are provided during three-phase faults so that the OC element is able to
determine the direction of the fault. In addition, the directional element function determines
its output based on the loss of voltage memory and is effective while the fault current flows in
accordance with Figure 2.1-3.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 19 -
6F2S1927 (0.18)
Amplitude calculation
|Vpol| Set voltage (OV-Vpol)
A setting and a scheme switch, as well as the non-directional OC element, provide the
settings for the directional OC element: for example, the user can set the threshold value of
the OC at stage 1 with the setting [OC1] and Forward can be set for the scheme switch [OC1-
Dir]. Setting of the sensing angle (θ) is configured by the setting [OC1-Angle] with the value of
θ set in the range of 0–180°. Figure 2.1-4 shows an example of an angle and a characteristic
set with θ.
Reverse
θ=30°
θ=90°
Max. torque
Forward
Reverse Forward Reverse Forward
Forward Reverse
Reverse
Vpol Vpol
Forward
θ=170°
θ=100°
θ=100° θ=170°
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 20 -
6F2S1927 (0.18)
The user can select which characteristic will be applied to each stage of the OC element
by setting a scheme switch. We shall see the scheme switch later.
With inverse time operation, provided that the fault current has the magnitude required
to enable the determination of the location of the fault and provided that the fluctuation in the
impedance of the power source does not affect the correct determination, an inverse time OC
function provides an effective protection. With regard to the inverse time characteristic, for
example, the function can provide a fast trip for close-in faults, but will enable a delayed trip
for remote faults. The characteristic curve of the inverse time element can be selected from
among 10 characteristic curves† in conformance with IEC, IEEE, US, and UK standards.
With dependent time resetting selected, if during the resetting period the energizing
current exceeds the threshold current of the OC element, then the OC element will pick-up.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 21 -
6F2S1927 (0.18)
The OC element will reset later in a period determined by the characteristics of dependent
time resetting. In other words, the user can choose the behavior of the OC element for either
faults that are repetitive intermittent or faults that occur in rapid succession. The
characteristic for dependent time resetting is selectable from five dependent time
characteristics in conformance with IEEE and US standards.
When definite time resetting is selected with the operation of the inverse time OC
selection and the reset time set to zero (instantaneous), no intentional delay is added for the
resetting: that is, when the energizing current falls below the reset threshold of the OC element,
the OC element returns to its reset condition. If a value is set to the reset time in seconds, the
resetting of the OC element is delayed by the reset time.
The operating time of the definite time OC element is set depending on the distance from
the power source and should be set shorter for relays furthest from the power source. Definite
time OC protection provides selectivity dependent on the difference between relay operating
times. It is limited to use in networks with a power source at one side only i.e. in radial
networks. The threshold values can be set identically at each terminal, but preferably, the
threshold value is reduced, little-by-little to provide a margin in terms of the current sensitivity
of the OC element. Moreover, a higher sensitivity of threshold current is required for a
protective relay that is located remote from the power source, that is, the threshold of the
definite time OC element is required to be lower than the ordinary threshold.
The operate time of the definite time OC element is constant irrespective of the
magnitude of the fault current and the threshold level of operation of the definite time OC
element with an on-delay timer provides a selective protection. As a result, the circuit breaker
(CB) at the remote terminal far from the power source can be tripped in the shortest time. The
on-delay timer, which generates a delay in starting the operation of the OC element, provides
a time grading margin (Tc); Tc is discussed later.
Definite time resetting as well as the on-delay starting setting of the definite time OC
element is provided. The operate time for the on-delay timer for starting and for the resetting
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 22 -
6F2S1927 (0.18)
(ii) DT characteristic
The operate time in the DT characteristic will be a constant time and is not affected by the
level of current. The reset time is set to zero so that resetting is performed immediately. The
user can set the operate time using a setting; it is discussed in in sections (vi) and (vii).
k
t(I) = TMS × {[ α ] + 𝑐} (2.1-1)
(𝐼⁄𝐼 ) − 1
𝑠
where:
t = operate time with constant current I (seconds),
I = operate (energizing) current (amperes),
Is = overcurrent setting (amperes),
TMS = time multiplier setting number,
k, α, c = constants defining curve.
The nine pre-programmed standard characteristic curves are defined in Table 2.1-3. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each OC stage. Figure 2.1-5 illustrates these characteristic curves. For example, the user
should set one for the scheme switch [OC1-Timer]. (“IEC-NI" is for IEC Normal Inverse
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 23 -
6F2S1927 (0.18)
characteristic; “IEC-VI” for IEC Very inverse; “IEC-EI” for IEC Extremely Inverse; “UK-LTI” for
UK Long Time Inverse; “IEEE-MI” for IEEE Moderately Inverse; “IEEE-VI” for IEEE Very
Inverse; “IEEE-EI” for IEEE Extremely Inverse; “US-CO8” for US CO8 Inverse; “US-CO2” for
US CO2 Short Time Inverse, and “Original” for user-programmable characteristic.)
In the IDMT, the user can also program the characteristic using time-multiplier-setting
(TMS) for the required operate time. For example, when the IEC characteristic is selected, the
user can set the TMS value using the setting [OC1-TMS-IEC] (incidentally, the default value
for the TMS is 1.00). The other TMSs are also available by the [OC1-TMS-UK], [OC1-TMS-
IEEE], [OC1-TMS-US] and [OC1-TMS-ORG].
Table 2.1-3 Constants for IDMT
Curve type k c
Curve Description α
(IEC 60255-151) sec sec
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 24 -
6F2S1927 (0.18)
Instantaneous activation
The operate time of the instantaneous characteristic is achieved by setting zero for the [TOC1],
but the instantaneous one can also obtained when the logic signal ‘1(High)’ is programmed to
be injected at PLC connection point “OC1_INST_OP”.
kr
t(I) = RTMS × [ β
] (2.1-2)
1 − (𝐼⁄𝐼 )
𝑠
where,
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
RTMS = time multiplier setting for resetting,
kr = time required to reset fully after complete operation when the energizing current is
zero (seconds),
β = constants defining curve.
For the IEEE standard, the user should use the setting [OC1-RTMS-IEEE] (incidentally,
the default value is 1.000). For the US standard and the original, settings [OC1-RTMS-US] and
[OC1-RTMS-ORG] are provided, respectively (For more information w.r.t the value for kr and
β, see Table 2.1-4; Figure 2.1-6 shows the characteristic curves).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 25 -
6F2S1927 (0.18)
energized current is smaller than the setting [OC1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OC1-Rtimer]=DEF (definite-time-reset), the integrated value shall
be zero when an energized current is smaller than the setting [OC1], when the
small energized current is continued for timer setting [TOC1R]. The integrated
value will not be zero when the energized current does not flow small for the
setting [TOC1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is set
unconditionally in the IEC and UK (see Table 2.1-5).
Figure 2.1-7 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OC1], will make an integrating value, which can determine how the element operates. If the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 26 -
6F2S1927 (0.18)
energized quantity (I) falls below the threshold setting [OC1], the element operation will
return to its reset stage after the time t(I) calculated in Equation (2.1-2).
Time
Energizing current
Energizing current
cleared by tripping
Measuring quantity 0A
Inverse-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEP
Integrator
Trip signal
Definite-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEF
Integrator
Trip signal
Reset time
Integration will be kept in timer [TOC1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [OC1] within [TOC1R]. does not become larger than [OC1] in [TOC1R].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 27 -
6F2S1927 (0.18)
DT
✓
Scheme switch [OC1-Timer]
IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓
✓
Scheme switch
N.A
[OC1-Rtimer]
N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 28 -
6F2S1927 (0.18)
the scheme switch [OC1-OPMD]. Conversely, when a trip is only required for faults that occur
in two or more phases, 2OUTOF3 (a fault occurs in two or more phases) is set for the scheme
switch [OC1-OPMD].
Table 2.1-6 Fault type and tripping mode
Fault type Setting [OC1-OPMD]
Phase-A Phase-B Phase-C 3POR 2OUTOF3
X – – ✓ No trip
– X – ✓ No trip
– – X ✓ No trip
X X – ✓ ✓
– X X ✓ ✓
X – X ✓ ✓
X X X ✓ ✓
Note: A tick (✓) indicates that a trip is issued when faults are detected.
A mark (X) indicates the occurrence of a fault on a particular phase. A mark
shown thus (–) indicates that no fault has occurred on that particular phase.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 29 -
6F2S1927 (0.18)
≥1
IEEE-VI OC1-ARCBlk Block
&
IEEE-EI
US-C02
Block-3P US-C08
OC1-2PBlk
Block-PerP
ORIGINAL
OC1-EN On
From VTF
VTF_DETECT
OC1-VTFBlk Block &
≥1
8000011BB0
800001EBB0 OC1_BLOCK
8000011BB1
800001EBB4 OC1_INST_OP
Table 2.1-7 Signal behaviors of PLC monitoring points ‘OC1-OR’ and ‘OC1PU-OR’
Setting [OC1_Timer]
PLC monitoring points
DT IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
OC1-OR ○
1 ○
3
OC1PU-OR ○
2 ○
4
1 :
○ A pick-up signal is generated instantly when the element operates.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 30 -
6F2S1927 (0.18)
2 :
○ No signal due that the PU element is killed. Use ‘OC1-OR’ in place of this.
3 :
○ A pick-up signal is generated, but delayed with the IDMT characteristic.
4 :
○ A pick-up signal is generated instantly.
OC1-OPT-ALARM ≥1 OC-OPT-ALARM
OC2-OPT- ALARM
OC3-OPT- ALARM
OC4-OPT- ALARM
OC1-ARC-BLOCK ≥1 OC-ARC-BLOCK
OC2- ARC-BLOCK
OC3- ARC-BLOCK
OC4- ARC-BLOCK
OC1-OPT-AR ≥1 OC-OPT-AR
OC1-OPT-BR OC-OPT-BR
OC1-OPT-CR OC-OPT-CR
OC2-OPT-AR
≥1
OC2-OPT-BR
OC2-OPT-CR
OC3-OPT-AR
≥1
OC3-OPT-BR
OC3-OPT-CR
OC4-OPT-AR
OC4-OPT-BR
OC4-OPT-CR
To Recording
OC1-OPT OC1-OPT
OC2-OPT OC2-OPT
OC3-OPT OC3-OPT
OC4-OPT OC4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 31 -
6F2S1927 (0.18)
2.1.7 Setting
OC (Function ID: 440001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OC1-EN Off / On - OC1 protection scheme switch Off
OC2-EN Off / On - OC2 protection scheme switch Off
OC3-EN Off / On - OC3 protection scheme switch Off
OC4-EN Off / On - OC4 protection scheme switch Off
OC1 NonDir / Forward /
OC1-Dir - OC1 directional characteristic NonDir
Reverse
OC1-Angle 0 - 180 deg OC1 directional characteristic angle 45
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OC1-Timer IEEE-MI / IEEE-VI / - OC1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OC1 A OC1 threshold (in DT mode) 1.00 5.00
50.00 250.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
TOC1 0.00 - 300.00 s OC1 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-IEC 0.010 - 50.000 - OC1 time multiplier of IEC inverse curve 1.000
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
UK 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-UK 0.010 - 50.000 - OC1 time multiplier of UK inverse curve 1.000
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-
0.010 - 50.000 - OC1 time multiplier of IEEE inverse curve 1.000
IEEE
OC1-Rtimer DEF / DEP - OC1 reset delay type of IEEE DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1-RTMS- OC1 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-US 0.010 - 50.000 - OC1 time multiplier of US inverse curve 1.000
OC1-Rtimer DEF / DEP - OC1 reset delay type of US DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1 dependent reset time multiplier of US
OC1-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
OC1 A OC1 threshold (in IDMT mode) 1.00 5.00
5.00 25.00
OC1-DPR 10 - 100 % OC1 drop-out/pick-up ratio 100
OC1-TMS-ORG 0.010 - 50.000 - OC1 time multiplier of ORG inverse curve 1.000
OC1-Rtimer DEF / DEP - OC1 reset delay type of US DEF
TOC1R 0.00 - 300.00 s OC1 definite time reset delay 0.00
OC1-RTMS- OC1 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OC1-k 0.00000 - 500.00000 - OC1 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 32 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 33 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 34 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 35 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 36 -
6F2S1927 (0.18)
2.1.8 Signal
Signal monitoring points
OC(Function ID: 440001)
Element ID Name Description
8500001B62 OC-ARC-BLOCK Autoreclose block signal by OC protection operation
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 37 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 38 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 39 -
6F2S1927 (0.18)
To simplify the description, only EF1 is discussed but is applicable to the other EFs; hence,
read the expression for EF1 as EF2, EF3 and EF4 at each EF stage unless a special explanation
or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.2-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.2.1 Non-directional ✓ ✓ ✓ ✓ ✓ NA NA
2.2.1 Directional ✓ ✓ ✓ NA NA NA NA
2.2.5 Blocking by VTF ✓ ✓ ✓ NA NA NA NA
– Number of steps 4 4 4 4 4 NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 40 -
6F2S1927 (0.18)
Reference voltage or
θ Polarizing voltage (−3Vo)
φ
A setting and a scheme switch, as well as the non-directional EF element, provide the
settings for the directional EF element: for example, the user can set the threshold value (IEF)
for stage 1 with the setting [EF1-DT] and Forward can be set for the scheme switch [EF1-Dir].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 41 -
6F2S1927 (0.18)
Setting of the sensing angle (θ) is configured by the setting [EF1-Angle] with the value of θ set
in the range of 0–180°. Figure 2.2-2 shows an example of an angle and a characteristic using
the θ. The operation of the EF element is based upon the following equation.
3𝐼0 ≥ 𝐼𝐸𝐹 (2.2-1)
3𝐼0 × cos(φ − θ) ≥ 0 (2.2-2)
3𝑉0 ≥ 𝐸𝐹_𝑉𝑝𝑜𝑙 (2.2-3)
where
3Io = residual current
3Vo = residual voltage
−3Vo = reference voltage (or polarizing voltage)
φ= lagging angle
θ = EF setting angle
IEF = Setting value of the EF element ([EF1-DT] and the others)
EF_Vpol = Setting value of the polarizing voltage ([EF1-Vpol])
Note: In the case of an internal fault, the phase angle is equal to the angle of the zero-
sequence impedance of the system, in a directly-earthed system this value is in
the range of approximately 50° to 90°. The sensing angle θ of the EF element can
be set between 0° to 180°. The minimum voltage necessary to maintain
directionality can be set from 0.5 to 100.0 V.
Reverse
θ=30°
θ=90°
Angle line
Forward
Reverse Forward Reverse Forward
Forward Reverse
Reverse
−3Vo −3Vo
Forward
θ=170°
θ=100°
θ=100° θ=170°
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 42 -
6F2S1927 (0.18)
The user can select which characteristic will be applied to each stage of the EF
element by setting a scheme switch. We shall see the scheme switches later.
(i) DT characteristic
The operate time in the DT characteristic will be a constant time and is not affected by the
level of current. The reset time is set to zero so that resetting is performed immediately. The
user can set the operate time using a setting; it is discussed in section (iv).
The reset time of the IDMT is user selectable; either inverse-time-reset or definite-time-
reset is selected. For the inverse-time-rest, the user can choose the reset time for the preset
characteristic from six characteristic curves; i.e. IEEE and US standard five pre-installed
characteristic curves and one user original characteristic carver where the user can set the
equation parameters. The inverse-time-reset curve equation and parameters will be discussed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 43 -
6F2S1927 (0.18)
in section (v).
k
𝑡(𝐼) = 𝑇𝑀𝑆 × {[ α ] + c} (2.2-4)
(I⁄I ) − 1
s
where:
t = operating time for constant current I (seconds),
I = energizing current (amperes),
Is = earth fault current setting (amperes),
TMS = time multiplier setting,
k, α, c = constants defining curve.
The nine pre-programmed standard characteristic curve are defined in Table 2.2-2. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each EF stage. Figure 2.2-3 illustrates these characteristic curves. For example, the user
should set one for the scheme switches [EF1-Timer]. (That is, “IEC-NI” is for IEC Normal
Inverse, “IEC-VI” for IEC Very Inverse, “IEC-EI” for IEC Extremely Inverse, “UK-LTI” for UK
Long Time Inverse, “IEEE-MI “ for IEEE Moderately Inverse, “IEEE-VI” for IEEE Very Inverse,
“IEEE-EI” for IEEE Extremely Inverse, “US-CO2” for US CO2 short time inverse, “US-CO8” for
US CO8 inverse, and “Original” for user-programmable characteristic.)
In the IDMT operation, the user can also program the characteristic using time-
multiplier-setting (TMS) for the required operate time. For example, the IEC characteristic is
selected, the user can set the TMS value using the setting [EF1-TMS-IEC] (incidentally, the
default value of the TMS is 1.00). The other TMSs are also available by the [EF1-TMS-UK],
[EF1-TMS-IEEE], [EF1-TMS-US] and [EF1-TMS-ORG].
Table 2.2-2 Constants for IDMT
Curve type
Curve Description k α c
(IEC 60255-151)
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 44 -
6F2S1927 (0.18)
Time characteristic
The user should set DT for the scheme switch [EF1-Timer]. The value of the required operate
time is set for the setting [TEF1] in the range 0.00–300.00s.
Instantaneous activation
The instantaneous operation characteristic is achieved by setting zero for the [TEF1], but the
instantaneous one can be also obtained when the logic signal ‘1(High)” is programmed to be
injected at the PLC connection point “EF1_INST_OP”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 45 -
6F2S1927 (0.18)
defines the reset time for the inverse-time-reset characteristic (ref. IEC 60255-151):
kr
𝑡(I) = 𝑅𝑇𝑀𝑆 × [ β
] (2.2-2)
I
1 − ( ⁄I )
s
where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.
For setting RTMS for the IEEE standard, the user can use setting [EF1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [EF1-RTMS-US] and [EF1-RTMS-
ORG] are provided for the US standard and the original, respectively (For more information
w.r.t the values for the kr and β, see Table 2.2-3; Figure 2.2-4 shows the characteristic curves).
Table 2.2-3 Constants for inverse-time-reset characteristics
Curve Type kr
Curve Description β
IEC 60255-151 sec
A IEC Normal Inverse (IEC-NI‡) N/A N/A
B IEC Very Inverse (IEC-VI‡) N/A N/A
C IEC Extremely Inverse (IEC-EI‡) N/A N/A
- UK Long Time Inverse (UK-LTI‡) N/A N/A
D IEEE Moderately Inverse (IEEE-MI) 4.85 2
E IEEE Very Inverse (IEEE-VI) 21.6 2
F IEEE Extremely Inverse (IEEE-EI) 29.1 2
- US CO8 inverse (US-CO8) 5.95 2
- US CO2 short time inverse (US-CO2) 2.261 2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 46 -
6F2S1927 (0.18)
Figure 2.2-5 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[EF1], will make an integrating value, which can determine how the element operates. If the
energized quantity (I) falls below the threshold setting [EF1], the element operation will return
to its reset stage after the time t(I) calculated in Equation (2.2-2).
Time
Energizing current
Energizing current
cleared by tripping
Measuring quantity 0A
Inverse-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEP
Integrator
Trip signal
Definite-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEF
Integrator
Trip signal
Reset time
Integration will be kept in timer [TEF1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [EF1] within [TEF1R]. does not become larger than [EF1] in [TEF1R].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 47 -
6F2S1927 (0.18)
DT
✓
Scheme switch [EF1-Timer]
IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓
✓
Scheme switch
N.A
[EF1-Rtimer]
N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 48 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 49 -
6F2S1927 (0.18)
8000011C23
EF1†
8000011C27
For DT characteristic
EF1PU†
EF1 TEF1
&
8000011B60 To Grouping logic
& &
t 0
EF1-OPT-ALARM ≥1 EF-OPT-ALARM
EF2-OPT- ALARM
EF3-OPT- ALARM
EF4-OPT- ALARM
EF1-ARC-BLOCK ≥1 EF-ARC-BLOCK
EF2- ARC-BLOCK
EF3- ARC-BLOCK
EF4- ARC-BLOCK
To Recording
EF1-OPT EF1-OPT
EF2-OPT EF2-OPT
EF3-OPT EF3-OPT
EF4-OPT EF4OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 50 -
6F2S1927 (0.18)
2.2.7 Setting
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF1-EN Off / On - EF1 protection scheme switch Off
EF2-EN Off / On - EF2 protection scheme switch Off
EF3-EN Off / On - EF3 protection scheme switch Off
EF4-EN Off / On - EF4 protection scheme switch Off
EF1 NonDir / Forward /
EF1-Dir - EF1 directional characteristic NonDir
Reverse
Fwd/ EF1-Angle 0 - 180 deg EF1 directional characteristic angle 45
Rev EF1-Vpol 0.5 - 100.0 V EF1 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF1-Timer IEEE-MI / IEEE-VI / - EF1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF1 A EF1 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
TEF1 0.00 - 300.00 s EF1 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-IEC 0.010 - 50.000 - EF1 time multiplier of IEC inverse curve 1.000
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-UK 0.010 - 50.000 - EF1 time multiplier of UK inverse curve 1.000
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-
0.010 - 50.000 - EF1 time multiplier of IEEE inverse curve 1.000
IEEE
EF1-Rtimer DEF / DEP - EF1 reset delay type of IEEE DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1-RTMS- EF1 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-US 0.010 - 50.000 - EF1 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF1 reset delay type of US DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1 dependent reset time multiplier of US
EF1-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF1 A EF1 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF1-DPR 10 - 100 % EF1 drop-out/pick-up ratio 100
EF1-TMS-ORG 0.010 - 50.000 - EF1 time multiplier of Original inverse curve 1.000
EF1-Rtimer DEF / DEP - EF1 reset delay type of ORG DEF
TEF1R 0.00 - 300.00 s EF1 definite time reset delay 0.00
EF1-RTMS- EF1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 51 -
6F2S1927 (0.18)
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF1-k 0.00000 - 500.00000 - EF1 user original curve coefficient 0.00000
EF1-a 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
EF1-c 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
EF1-kr 0.00000 - 500.00000 - EF1 user original curve coefficient 0.00000
EF1-b 0.00000 - 10.00000 - EF1 user original curve coefficient 0.00000
Output EF1-VTFBlk Non / Block - EF1 operation block by VTF Non
EF1-CTFBlk Non / Block - EF1 operation block by CTF Non
EF1-UseFor Trip / Alarm - EF1 used for trip or alarm Trip
EF1-ARCBlk Non / Block - Autoreclose block by EF1 Block
EF2 NonDir / Forward /
EF2-Dir - EF2 directional characteristic NonDir
Reverse
Fwd/ EF2-Angle 0 - 180 deg EF2 directional characteristic angle 45
Rev EF2-Vpol 0.5 - 100.0 V EF2 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF2-Timer IEEE-MI / IEEE-VI / - EF2 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF2 A EF2 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
TEF2 0.00 - 300.00 s EF2 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-IEC 0.010 - 50.000 - EF2 time multiplier of IEC inverse curve 1.000
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-UK 0.010 - 50.000 - EF2 time multiplier of UK inverse curve 1.000
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-
0.010 - 50.000 - EF2 time multiplier of IEEE inverse curve 1.000
IEEE
EF2-Rtimer DEF / DEP - EF2 reset delay type of IEEE DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2-RTMS- EF2 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-US 0.010 - 50.000 - EF2 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF2 reset delay type of US DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2 dependent reset time multiplier of US
EF2-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF2 A EF2 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF2-DPR 10 - 100 % EF2 drop-out/pick-up ratio 100
EF2-TMS-ORG 0.010 - 50.000 - EF2 time multiplier of Original inverse curve 1.000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 52 -
6F2S1927 (0.18)
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF2-Rtimer DEF / DEP - EF2 reset delay type ORG DEF
TEF2R 0.00 - 300.00 s EF2 definite time reset delay 0.00
EF2-RTMS- EF2 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF2-k 0.00000 - 500.00000 - EF2 user original curve coefficient 0.00000
EF2-a 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
EF2-c 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
EF2-kr 0.00000 - 500.00000 - EF2 user original curve coefficient 0.00000
EF2-b 0.00000 - 10.00000 - EF2 user original curve coefficient 0.00000
Output EF2-VTFBlk Non / Block - EF2 operation block by VTF Non
EF2-CTFBlk Non / Block - EF2 operation block by CTF Non
EF2-UseFor Trip / Alarm - EF2 used for trip or alarm Trip
EF2-ARCBlk Non / Block - Autoreclose block by EF2 Block
EF3 NonDir / Forward /
EF3-Dir - EF3 directional characteristic NonDir
Reverse
Fwd/ EF3-Angle 0 - 180 deg EF3 directional characteristic angle 45
Rev EF3-Vpol 0.5 - 100.0 V EF3 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF3-Timer IEEE-MI / IEEE-VI / - EF3 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF3 A EF3 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
TEF3 0.00 - 300.00 s EF3 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-IEC 0.010 - 50.000 - EF3 time multiplier of IEC inverse curve 1.000
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-UK 0.010 - 50.000 - EF3 time multiplier of UK inverse curve 1.000
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-
0.010 - 50.000 - EF3 time multiplier of IEEE inverse curve 1.000
IEEE
EF3-Rtimer DEF / DEP - EF3 reset delay type of IEEE DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3-RTMS- EF3 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-US 0.010 - 50.000 - EF3 time multiplier of US inverse curve 1.000
EF4-Rtimer DEF / DEP - EF3 reset delay type of US DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3 dependent reset time multiplier of US
EF3-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 53 -
6F2S1927 (0.18)
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ORG 0.02 - 0.10 -
EF3 A EF3 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF3-DPR 10 - 100 % EF3 drop-out/pick-up ratio 100
EF3-TMS-ORG 0.010 - 50.000 - EF3 time multiplier of Original inverse curve 1.000
EF3-Rtimer DEF / DEP - EF3 reset delay type of ORG DEF
TEF3R 0.00 - 300.00 s EF3 definite time reset delay 0.00
EF3-RTMS- EF3 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF3-k 0.00000 - 500.00000 - EF3 user original curve coefficient 0.00000
EF3-a 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
EF3-c 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
EF3-kr 0.00000 - 500.00000 - EF3 user original curve coefficient 0.00000
EF3-b 0.00000 - 10.00000 - EF3 user original curve coefficient 0.00000
Output EF3-VTFBlk Non / Block - EF3 operation block by VTF Non
EF3-CTFBlk Non / Block - EF3 operation block by CTF Non
EF3-UseFor Trip / Alarm - EF3 used for trip or alarm Trip
EF3-ARCBlk Non / Block - Autoreclose block by EF3 Block
EF4 NonDir / Forward /
EF4-Dir - EF4 directional characteristic NonDir
Reverse
Fwd/ EF4-Angle 0 - 180 deg EF4 directional characteristic angle 45
Rev EF4-Vpol 0.5 - 100.0 V EF4 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
EF4-Timer IEEE-MI / IEEE-VI / - EF4 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
EF4 A EF4 threshold (in DT mode) 0.30 1.50
50.00 250.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
TEF4 0.00 - 300.00 s EF4 operating delay time (in DT mode) 1.00
IEC 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-IEC 0.010 - 50.000 - EF4 time multiplier of IEC inverse curve 1.000
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
UK 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-UK 0.010 - 50.000 - EF4 time multiplier of UK inverse curve 1.000
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-
0.010 - 50.000 - EF4 time multiplier of IEEE inverse curve 1.000
IEEE
EF4-Rtimer DEF / DEP - EF4 reset delay type of IEEE DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4-RTMS- EF4 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-US 0.010 - 50.000 - EF4 time multiplier of US inverse curve 1.000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 54 -
6F2S1927 (0.18)
EF(Function ID:441001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
EF4-Rtimer DEF / DEP - EF4 reset delay type of US DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4 dependent reset time multiplier of US
EF4-RTMS-US 0.010 - 50.000 - 1.000
inverse curve
ORG 0.02 - 0.10 -
EF4 A EF4 threshold (in IDMT mode) 0.30 1.50
5.00 25.00
EF4-DPR 10 - 100 % EF4 drop-out/pick-up ratio 100
EF4-TMS-ORG 0.010 - 50.000 - EF4 time multiplier of Original inverse curve 1.000
EF4-Rtimer DEF / DEP - EF4 reset delay type of ORG DEF
TEF4R 0.00 - 300.00 s EF4 definite time reset delay 0.00
EF4-RTMS- EF4 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
EF4-k 0.00000 - 500.00000 - EF4 user original curve coefficient 0.00000
EF4-a 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
EF4-c 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
EF4-kr 0.00000 - 500.00000 - EF4 user original curve coefficient 0.00000
EF4-b 0.00000 - 10.00000 - EF4 user original curve coefficient 0.00000
Output EF4-VTFBlk Non / Block - EF4 operation block by VTF Non
EF4-CTFBlk Non / Block - EF4 operation block by CTF Non
EF4-UseFor Trip / Alarm - EF4 used for trip or alarm Trip
EF4-ARCBlk Non / Block - Autoreclose block by EF4 Block
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 55 -
6F2S1927 (0.18)
2.2.8 Signal
Signal monitoring point
EF(Function ID: 441001)
Element ID Name Description
8500001B62 EF-ARC-BLOCK Block for issuing autoreclose signal in the EF function
8200011B62 EF1-ARC-BLOCK Block for issuing autoreclose signal in the EF1 element
8200021B62 EF2-ARC-BLOCK Block for issuing autoreclose signal in the EF2 element
8200031B62 EF3-ARC-BLOCK Block for issuing autoreclose signal in the EF3 element
8200041B62 EF4-ARC-BLOCK Block for issuing autoreclose signal in the EF4 element
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 56 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 57 -
6F2S1927 (0.18)
†Note:The second harmonic current is present all inrush currents in three-phases. The
proportion of the second harmonic current varies with the degree of the
energizing, but the ratio of the second harmonic current to the fundamental
current can be about 20% or greater during energizing.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.3-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 58 -
6F2S1927 (0.18)
|I1f|ICD–OC
I1f
0 ICD–OC
As shown in Figure 2.3-1, the user should set both the [ICD-2f] and [ICD-OC] when the
second harmonic inrush current should be detected. The user should set On for the scheme
switch [ICD-EN] to enable the ICD operation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 59 -
6F2S1927 (0.18)
2.3.3 Setting
ICD(Function ID: 480001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ICD-EN Off / On - ICD function scheme switch Off
ICD-2f 10 - 50 % Sensitivity of 2f 15
0.10 - 0.50 -
ICD-OC A Threshold of fundamental current 0.50 2.50
5.00 25.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 60 -
6F2S1927 (0.18)
2.3.4 Signal
Signal monitoring point
ICD(Function ID: 480001)
Element ID Name Description
8000001C20 ICD-A ICD relay element operated (phase-A)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 61 -
6F2S1927 (0.18)
†Note:The relay for the restricted earth fault in the transformer can use such quantity
supplied from the core-balanced CT, when Metrosils (varistors) and setting-
resistors are used externally.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.4-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.4.1(i) Non-directional ✓ ✓ ✓ ✓ ✓ NA NA
2.4.1(ii) Directional ✓ ✓ ✓ NA NA NA NA
2.4.5 Blocking by VTF ✓ ✓ ✓ NA NA NA NA
2.4.6 Petersen coil ✓ ✓ ✓ NA NA NA NA
– Number of steps 4 4 4 4 4 NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 62 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 63 -
6F2S1927 (0.18)
A setting and a scheme switch, as well as the non-directional SEF element, provide the
settings for the directional SEF element: for example, the user can set the threshold value
(ISEF) for stage 1 with the setting [SEF1] when the scheme switch [SEF1-Dir]=Forward. Setting
of the sensing angle (θ) is configured by the setting [SEF1-Angle] with the value of θ set in the
range of 0–180°. Figure 2.4-2 shows an example of an angle and a characteristic using the θ.
The operation of the SEF element is based upon the following equation.
Ie ≥ ISEF (2.4-1)
Ie × cos(φ − θ) ≥ 0 (2.4-2)
Ve ≥ SEF_Vpol (2.4-3)
where
Ie = Residual current
Ve = Residual voltage
Vpol = reference voltage (or polarizing voltage; Ve180°)
φ= lagging angle
θ = SEF1 setting angle ([SEF1-Angle])
ISEF = Setting value of the SEF1 element ([SEF1])
SEF_Vpol = Setting value of the polarizing voltage ([SEF1-Vpol])
Note: In the case of an internal fault, the phase angle is equal to the angle of the zero-
sequence impedance of the system, in a directly-earthed system this value is in
the range of approximately 50° to 90°. The sensing angle θ of the SEF element can
be set between 0° to 180°. The minimum voltage necessary to maintain
directionality should be applied from 0.5 to 100.0 V.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 64 -
6F2S1927 (0.18)
Reverse
Ve180°
Ve180° Ve180°
θ=30°
θ=90°
Angle line
Forward
Reverse Forward Reverse Forward
Forward Reverse
Reverse
Ve180°
Ve180°
Forward
θ=170°
θ=100°
θ=100° θ=170°
For the reset time delay of IDMT characteristics, either inverse (dependent)-time-
reset (i.e., DEP) or definite(independent)-time-reset (i.e., DEF) can be characterized by the
setting.
The user can select which characteristic will be applied to each stage of the SEF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 65 -
6F2S1927 (0.18)
element by setting a scheme switch that will be explained later in this section.
(i) DT characteristic
The DT operates time characteristic is a constant one and will not be affected by the level of
energizing current. The reset time is set to be zero so that resetting is performed immediately.
The user can have time settings discussed in section (iv).
In IEEE, US, and ORG time characteristics, the users can select a reset characteristic
time: independent (definite)-time-reset (DT) or inverse-time-reset (DEP) or definite-time-reset
(DEF). The inverse-time-reset (DEP) equation and parameters will be explained in section (v).
k
𝑡(𝐼) = 𝑇𝑀𝑆 × {[ α ] + c} (2.4-4)
(I⁄I ) − 1
s
where:
t = operating time for constant current I (seconds),
I = energizing current (amperes),
Is = earth fault current setting (amperes),
TMS = time multiplier setting,
k, α, c = constants defining curve.
The nine pre-programmed standard characteristic curve are defined in Table 2.4-2. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each SEF stage. Figure 2.4-3 IDMT Characteristics curves illustrates these characteristic
curves. For example, the user should set one for the scheme switch [SEF1-Timer]. (That is,
“IEC-NI” for IEC Normal Inverse, “IEC-VI” for IEC Very Inverse, “IEC-EI” for IEC Extremely
Inverse, “UK-LTI” for UK Long Time Inverse, “IEEE-MI “ for IEEE Moderately Inverse, “IEEE-
VI” for IEEE Very Inverse, “IEEE-EI” for IEEE Extremely Inverse, “US-CO2” for US CO2 short
time inverse, “US-CO8” for US CO8 inverse, and “Original” for user-programmable
characteristic.)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 66 -
6F2S1927 (0.18)
In the IDMT, the user can also program the characteristic using time-multiplier-setting
(TMS) for the required operate time. The value of TMS is set for a characteristic: for example,
the user can set the TMS value using the setting [SEF1-TMS-IEC] (incidentally, the default
value of the TMS is 1.00). The other TMSs are also available by the [SEF1-TMS-UK], [SEF1-
TMS-IEEE], [SEF1-TMS-US] and [SEF1-TMS-ORG].
Table 2.4-2 Constants for IDMT
Curve type
Curve Description k α c
(IEC 60255-151)
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 67 -
6F2S1927 (0.18)
Time characteristic
The user should set DT for the scheme switch [SEF1-Timer]. The value of the required operate
time is set for the setting [TSEF1] in the range 0.00–300.00s.
Instantaneous activation
The operate time of the instantaneous characteristic is achieved by setting zero for the [TEF1],
but the instantaneous one can be also obtained when the logic signal ‘1(High)” is programmed
to be injected at the PLC connection point “SEF1_INST_OP”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 68 -
6F2S1927 (0.18)
kr
𝑡(I) = 𝑅𝑇𝑀𝑆 × [ β
] (2.4-2)
I
1 − ( ⁄I )
s
where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.
For setting RTMS for the IEEE standard, the user can use setting [SEF1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, setting [SEF1-RTMS-US] and [SEF1-RTMS-
ORG] are provided for the US standard and the original, respectively (For more information
w.r.t the values for the kr and β, see Table 2.4-3; Figure 2.4-4 shows the characteristic curves)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 69 -
6F2S1927 (0.18)
shall be zero when an energized current is smaller than the setting [SEF1], when
the small energized current is continued for timer setting [T SEF1R]. The
integrated value will not be zero when the energized current does not flow small
for the setting [T SEF1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is
set unconditionally in the IEC and UK (see Table 2.4-4).
Figure 2.4-5 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[SEF1], will make an integrating value, which can determine how the element operates. If the
energized quantity (I) falls below the threshold setting [SEF1], the element operation will
return to its reset stage after the time t(I) calculated in Equation (2.4-2).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 70 -
6F2S1927 (0.18)
Time
Energizing current
Energizing current
cleared by tripping
Measuring quantity 0A
Inverse-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEP
Integrator
Trip signal
Definite-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEF
Integrator
Trip signal
Reset time
Integration will be kept in timer [TSEF1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [SEF1] within [TSEF1R]. does not become larger than [SEF1] in [TSEF1R].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 71 -
6F2S1927 (0.18)
Table 2.4-4 Type and standard board in the SEF1 (A tick represents a selectable function)
IDMT
Characteristics DT
IEC-NI IEC-VI IEC-EI UK-LTI IEEE-MI IEEE-VI IEEE-EI US-CO2 US-CO8 Original
DT
✓
Scheme switch [SEF1-Timer]
IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓
✓
Scheme switch
N.A
[SEF1-Rtimer]
N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 72 -
6F2S1927 (0.18)
harmonic associated with magnetizing inrush is present. Non is set for the scheme switch
[SEF1-2fBlk] as the default setting. For more information about the ICD function, see Chapter
Relay application: Inrush current detection function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 73 -
6F2S1927 (0.18)
Operation zone
o
SEF-Vpol (Ve180°)
SEF1-EN On
Operation zone
o
SEF-Vpol (Ve180°)
The RP element will be characterized by Watt metric setting; hence, a value, which is ruled by
the scalar product of an entering current (Ie) and applied voltage (Ve), should be set for the
setting [RP1].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 74 -
6F2S1927 (0.18)
in Figure 2.4-7; Figure 2.4-8 shows grouping commands for the trip circuit (TRC). The SEF1
signal is generated when the pickup current exceeds a threshold, and then trip signals are
injected into the TRC. (For more information, see Chapter Relay application: Trip circuit
function)
RPRRY ON
RPFRY ON
From ICD RP1R ON
RP1F ON
ICD-OR 8000011C23
&
SEF1-2PBlk SEF1†
8000011C27
Block SEF1PU†
TSEF1
For DT characteristic 8000011C23
t 0
SEF1 & &
& & 0.00-300.00s ≥1
VTF_DETECT & 1
SEF1-VTFBlk Block ≥1
8000011B63
800001EBBO SEF1_BLOCK
8000011B64
800001EBB1 SEF1_INST_OP
SEF1_Type DT
IEC-NI
IEC-VI ≥1
Trip
IEC-EI SEF1-UseFor
Alarm
UK-LTI
SEF1-ARCBlk
IEEE-MI Block
IEEE-VI
Trip
IEEE-EI SEF1S2-UseFor
Alarm
US-C02
US-C08
ORIGINAL
Table 2.4-5 Signal behaviors of PLC monitoring points ‘SEF1’ and ‘SEF1PU’
Setting [SEF1_Timer]
PLC monitoring points
DT IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
SEF1 ○
1 ○
3
SEF1PU ○
2 ○
4
1 :
○ A pick-up signal is generated instantly when the element operates.
2 :
○ No signal due that the PU element is killed. Use ‘SEF1’ in place of that.
3 :
○ A pick-up signal is generated, but delayed with the IDMT characteristic.
4 :
○ A pick-up signal is generated instantly.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 75 -
6F2S1927 (0.18)
SEF2-OPT-TRIP
SEF3-OPT-TRIP
SEF4-OPT-TRIP
SEF1-OPT-ALARM ≥1
SEF1S2-OPT-ALARM SEF-OPT-ALARM
SEF2-OPT- ALARM
SEF3-OPT- ALARM
SEF4-OPT- ALARM
SEF1-ARC-BLOCK ≥1 SEF-ARC-BLOCK
SEF2- ARC-BLOCK
SEF3- ARC-BLOCK
SEF4- ARC-BLOCK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 76 -
6F2S1927 (0.18)
2.4.9 Setting
SEF(Function ID: 442001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
SEF1 SEF1-EN Off / On - SEF1 protection enable Off
SEF1 Directio NonDir / Forward /
SEF1-Dir - SEF1 selection of protection direction Non
n Reverse
Pol. SEF1-Angle 0 - 180 deg SEF1 polarizing angle in directional element 45
SEF1-Vpol 3.0 V SEF1 polarizing vol. in directional element 3.0
RP RP1-EN Off / On - Enabling RP in directional protection Off
RP1 0.00 – 100.00 W Threshold of residual power element 0.00
SEF1 characteristic DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
SEF1-Timer IEEE-MI / IEEE-VI / - SEF1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT SEF1 0.002 - 1.000 A SEF1 threshold (in DT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
TSEF1 0.00 - 300.00 s SEF1 operating delay time (in DT mode) 1.00
IEC SEF1 0.002 - 0.100 A SEF1 threshold (in IDMT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
SEF1-TMS-
0.010 - 50.000 - SEF1 time multiplier of IEC inverse curve 1.000
IEC
TSEF1R 0.00 - 300.00 s SEF1 definite time reset delay 0.00
UK SEF1 0.002 - 0.100 A SEF1 threshold (in IDMT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
SEF1-TMS-UK 0.010 - 50.000 - SEF1 time multiplier of UK inverse curve 1.000
TSEF1R 0.00 - 300.00 s SEF1 definite time reset delay 0.00
IEEE SEF1 0.002 - 0.100 A SEF1 threshold (in IDMT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
SEF1-TMS-
0.010 - 50.000 - SEF1 time multiplier of IEEE inverse curve 1.000
IEEE
Rtimer SEF1-Rtimer DEF / DEP - SEF1 reset delay type of IEEE DEF
TSEF1R 0.00 - 300.00 s SEF1 definite time reset delay 0.00
SEF1-RTMS- SEF1 dependent reset time multiplier of IEEE
0.010 - 50.000 - 1.000
IEEE inverse curve
US SEF1 0.002 - 0.100 A SEF1 threshold (in IDMT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
SEF1-TMS-US 0.010 - 50.000 - SEF1 time multiplier of US inverse curve 1.000
Rtimer SEF1-Rtimer DEF / DEP - SEF1 reset delay type of US DEF
TSEF1R 0.00 - 300.00 s SEF1 definite time reset delay 0.00
SEF1-RTMS- SEF1 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG SEF1 0.002 - 0.100 A SEF1 threshold (in IDMT mode) 0.010
SEF1-DPR 10 - 100 % SEF1 drop-out/pick-up ratio 100
SEF1-TMS-
0.010 - 50.000 - SEF1 time multiplier of Original inverse curve 1.000
ORG
SEF1-Rtimer DEF / DEP - SEF1 reset delay type of ORG DEF
Rtimer TSEF1R 0.00 - 300.00 s SEF1 definite time reset delay 0.00
SEF1-RTMS- SEF1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
SEF1-k 0.00000 - 500.00000 - SEF1 user original curve coefficient 0.00000
SEF1-a 0.00000 - 10.00000 - SEF1 user original curve coefficient 0.00000
SEF1-c 0.00000 - 10.00000 - SEF1 user original curve coefficient 0.00000
SEF1-kr 0.00000 - 500.00000 - SEF1 user original curve coefficient 0.00000
SEF1-b 0.00000 - 10.00000 - SEF1 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 77 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 78 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 79 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 80 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 81 -
6F2S1927 (0.18)
2.4.10 Signal
Signal monitoring point
SEF(Function ID: 442001)
Element ID Name Description
8000011C23 SEF1 SEF1 relay element operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 82 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 83 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.5-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 84 -
6F2S1927 (0.18)
The SOTF-OC function is active when On is set for the setting [SOTFOC-EN]. Setting
[SOTF-test] is used for the mandatory condition of cold load when testing. When wishing to
add another condition into the logic for the SOTF operation, the user can inject the signal using
PLC connection point “ADD.SOTF.EN”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 85 -
6F2S1927 (0.18)
800000EBB1 OC-RTP.EN
8000001B60
≥1
SOTFOC-ARC-BLOCK
≥1
8000011C20
From ICD
ICD-A & ≥1
ICD-B & ≥1
To Recording
ICD-C & ≥1
SOTFOC-TRIP
≥1
&
OCSOTF-2PBlk Block-PerP
Block-3P
SOTFOC-EN On
DEAD_LINE_DETECT
≥1
800000EBB2 ADD.SOTF_EN 0 t
SOTF-Test On 0.5s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 86 -
6F2S1927 (0.18)
2.5.2 Setting
SOTF-OC(Function ID: 454001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
SOTFOC-EN Off / On - SOTF-OC protection enable Off
0.02 - 0.10 -
OCSOTF A OC relay for SOTF threshold 1.20 6.00
3.00 15.00
Non / Block-3P /
OCSOTF-2fBlk - OCSOTF operation block by 2f-detection Non
Block-PerP
2.5.3 Signal
Monitoring point for operation
SOTF-OC(Function ID: 454001)
Element ID Name Description
8000001BB2 ADD.SOTF_EN Additional SOTFOC enable
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 87 -
6F2S1927 (0.18)
Although a trip command will have been issued by other protection functions, the CBF
protection has own relay elements and own timers that are used to detect the continuing
presence of a fault following the issuance of the trip command. The relay elements are termed
OCCBF† and EFCBF†, which run as protection functions within CBF.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.6-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 88 -
6F2S1927 (0.18)
The operation of these elements is reset if the threshold values of currents, applied by
the settings [OCCBF] and [EFCBF], are below 80% of their setting value.
There are two operation modes (internal and external mode) for “re-trip”; the user can
select the desired mode using scheme switch [CBF-Retrip]:
Internal mode
If On is set for scheme switch [CBF-Retrip] the CBF function is armed for issuing a
“re-trip” signal. The OCCBF and EFCBF control the “re-trip” signal along with trip
signals coming from other functions.
External mode
When On-T is set for scheme switch [CBF-Retrip], the CBF function is armed for
issuing a “re-trip” following tripping by external protection functions only. The
external protection functions can operate using PLC connection points in the TRC
function. If external mode is selected, an external CBF start-signal must be present
continuously for as long as the fault is present.
For the re-trip operation, On should be set for both scheme switches [OCCBF] and
[EFCBF]. When a delay timer is needed for “re-trip”, a setting [TCBF-RE] is available. A setting
time can be chosen between 0 and 300.000sec, the time setting to be applied must be
determined in accordance with the response time of the CB. The setting time is addressed later.
(section 2.6.5)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 89 -
6F2S1927 (0.18)
One of the benefits of the “re-trip” function is that it can used to avoid accidental tripping
of an adjacent CB or an upstream CB. This is particularly requisite during maintenance and
testing of the system.
Retrip
2.6.3 Backup feature Normal trip
to trip again. If “re-trip” cannot remove the fault, CBF will issue a “back-trip” command. Back-
tripping is used as a last resort to remove the fault.
On
Trip signal
Off Trip signal Trip signal Off
Normal trip Re-trip
Target CB Closed
Toc Tcb
Run
OCCBF element Stop Toc Toc Stop
Timer#1
Start TCBF-RE
Timer#1 (TCBF-RE) Off
On
Operation of Re-trip Off Off
Timer#2
Start TCBF-TP
Timer#2 (TCBF-TP) Off
On
CBF trip signal Off Off
Figure 2.6-1 Timing chart for re-trip and back trip during CBF operation
Figure 2.6-1 is a sequence diagram for the CBF function; the overall sequence illustrated
shows a target CB failing to remove a fault with the consequence that back tripping of the
adjacent CB(s) is required following operation of the CBF protection to finally clear the fault.
The CBF function is initiated via a signal from other protection functions.
If the target CB is tripped normally on receipt of a trip signal so that the fault is removed,
both OCCBF and EFCBF will reset before the time settings of timer #1 and timer #2 have
elapsed.
Following the issue of the first trip signal, if either OCCBF or EFCBF were to continue
to operate and if timer #1 were to time out according to the timer setting value [TCBF-RE], a
“re-trip” command would be issued to the target CB. If the target CB were to open to clear the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 90 -
6F2S1927 (0.18)
fault in response to the “re-trip” command, OCCBF and EFCBF would reset and the CBF
sequence is stopped.
If the target CB were to fail to remove the fault with the “re-trip” command, and if
OCCBF or EFCBF continued to operate and if the timer #2 were to time out in accordance with
the setting time applied [TCBF-TP], CBF will issue a trip command to the adjacent CB(s) to
clear the fault, as a last resort.
†Note:The IED issues GEN.TRIP signals in trip circuit function (TRC), which is
discussed in Chapter Relay application: Trip circuit.
When wishing to issue the CBF trip command without the GEN.TRIP-* commands, the
IED can issue it with external signals come from other relay devices. The user should inject
the external signals at PLC connection points ‘EXT.CBF_START*’.
On the other hand, when wishing to issue the CBF trip command without the operation
of OCCBF or EFCBF element, the IED can also issue it with external signals using PLC
connection points ‘SUB.CBF1*’. This technique will be achieved when the user programs to
inject a ‘CB close (closed) state signal’ at the ‘SUB.CBF1*’ points. It is useful if the CBF
function cannot determine the conditions of breaker failures, when OCCBF element fails to
detect small fault currents.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 91 -
6F2S1927 (0.18)
CBF_START-A
CBF_START-B
CBF_START-C
8000011C20
TCBF-RE
OCCBF A
& t 0
≥1 & CBF_RETRIP-A
8100011C21 & ≥1 ≥1 ○
1
B
& ≥1 t 0 CBF_RETRIP-B
&
8200011C22 & ≥1 ≥1
C
& t 0
≥1 & CBF_RETRIP-C
& ≥1 ≥1
OCCBF-EN ON 0.000-300.000s
8400011C27
EFCBF & ≥1 CBF_RETRIP
&
EFCBF-EN &
ON
To TRC
8000001BB8 & 8000011B20
800000EBB8 SUB.CBF1-A ≥1 CBF_RETRIP-A
8100001BB9 8100011B21
810000EBB9 SUB.CBF1-B ≥1 CBF_RETRIP-B
8200001BBA 8200011B22
820000EBBA SUB.CBF1-C ≥1 CBF_RETRIP-C
8300001BBB 8300011B23
830000EBBB SUB.CBF1 CBF_RETRIP
From
TRC GEN.TRIP-A &
≥1
TRC
GEN.TRIP-B
≥1 &
GEN.TRIP-C
≥1 &
8000011BB0 OFF
800001EBB0 EXT.CBF_START-A ON &
CBF-Retrip
8100011BB1 ON-T
810001EBB1 EXT.CBF_START-B &
8200011BB2 CBF-EN ON CBF-EN-ON
820001EBB2 EXT.CBF_START-C
8300011BB3
830001EBB3 EXT.CBF_START
810001EBB5 CBF-RE_INST
≥1 CBF_ARC-BLOCK
CBF-RETRIP
OFF
ON &
CBF-Trip ON-AftRe
&
CBF-EN-ON
CBF1-NON_BLOCK
820001EBB6 CBF-TP_INST
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 92 -
6F2S1927 (0.18)
The time settings [TCBF-RE] and [TCBF-TP] are determined in relation to the opening
time of the target CB and the reset time of the OCCBF or EFCBF elements (see Toc and Tcb
in Figure 2.6-1). The following description illustrates a setting calculation example when “re-
trip” is used:
Setting of TCBF-TP =TCBF-RE + Output relay operating time + Breaker opening time +
OCCBF/EFCBF reset time + Margin
=70ms + 10ms + 40ms + 10ms + 10ms
=140ms
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 93 -
6F2S1927 (0.18)
2.6.6 Setting
CBF(Function ID: 453001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CBF-EN Off / On - CBF protection scheme switch Off
OC OCCBF-EN Off / On - Current flow is judged by OC relay operation On
0.10 - 0.50 - OCCBF relay operating level (Current flow
OCCBF A 1.00 5.00
5.00 25.00 judgment)
EF EFCBF-EN Off / On - Current flow is judged by EF relay operation Off
0.10 - 0.50 - EFCBF relay operating level (Current flow
EFCBF A 1.00 5.00
5.00 25.00 judgment)
Timer TCBF-RE 0.000 - 300.000 s CBF retrip timer 0.150
TCBF-TP 0.000 - 300.000 s CBF trip timer 0.200
Output CBF-Retrip Off / On / On-T - CBF retrip operation mode On
CBF-Trip Off / On / On-AftRe - CBF trip operation mode On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 94 -
6F2S1927 (0.18)
2.6.7 Signal
Signal monitoring points
CBF(Function ID: 453001)
Element ID Name Description
8100011BB5 CBF-RE_INST CBF instantaneously retrip
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 95 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.7-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.7.2 Blocking by CTF ✓ ✓ ✓ NA NA NA NA
– Number of steps 2 2 2 2 2 – –
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 96 -
6F2S1927 (0.18)
Threshold value
Operating zone
0.04In
0 0 I
I
A definite time delay can be programmed by applying a value of delay time using setting
[TUC1], the user can choose a value between 0 and 300s.
These features are described for the UC1 function, UC2 is exactly the same as UC1.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 97 -
6F2S1927 (0.18)
≥1 UC1-OR
8000011C20
A
S & TUC1 8014001001
UC1 B 8100011C21 1 &
& t 0 UC1-OPT-A
R &
C
S & 8114011001
8200011C22 1 & t 0
& UC1-OPT-B
R &
8214021001
S &
1 & t 0 UC1-OPT-C
& R &
UC1-EN 0.00-300.00s
A On
I>Iset B 8000011B64
C ≥1 UC1-OPT
& UC1-OPT-TRIP
A
I<0.04In B
Trip
C UC1-UseFor UC1-OPT-ALARM
&
Alarm
From CTF
CTF_DETECT
&
UC1-CTFBlk
Block ≥1 1
800001EBB0 UC1_BLOCK
≥1
UC2-OR
8400021C20
A 8400021B61
S & TUC2
UC2 B 8500021C21 1 &
& t 0 UC2-OPT-A
R &
C
S & 8500021B62
8600021C22 &
1 & t 0
R & UC2-OPT-B
8600021B63
S &
1 & t 0 UC2-OPT-C
& R &
UC2-EN On 0.00-300.00s
A
I>Iset B 8100021B64
C ≥1 UC2-OPT
&
UC2-OPT-TRIP
&
UC2-CTFBlk Trip
UC2-UseFor & UC2-OPT-ALARM
Block ≥1 1 Alarm
81002EBB0 UC2_BLOCK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 98 -
6F2S1927 (0.18)
2.7.4 Setting
UC(Function ID: 450001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
UC1-EN Off / On - UC1 protection enable Off
UC2-EN Off / On - UC2 protection enable Off
UC1 0.10 - 0.50 -
UC1 A UC1 threshold 0.20 1.00
2.00 10.00
TUC1 0.00 - 300.00 s UC1 operating delay time 1.00
Output UC1-CTFBlk Non / Block - UC1 operation block by CTF Non
UC1-UseFor Trip / Alarm - UC1 used for trip or alarm Trip
UC2 0.10 - 0.50 -
UC2 A UC2 threshold 0.20 1.00
2.00 10.00
TUC2 0.00 - 300.00 s UC2 operating delay time 1.00
Output UC2-CTFBlk Non / Block - UC2 operation block by CTF Non
UC2-UseFor Trip / Alarm - UC2 used for trip or alarm Trip
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 99 -
6F2S1927 (0.18)
2.7.5 Signal
Signal monitoring point
UC(Function ID: 450001)
Element ID Name Description
8800001B65 UC-OPT-A UC protection operated (phase-A)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 100 -
6F2S1927 (0.18)
To simplify the description, only OCN1 is discussed but is applicable to the other OCNs;
hence, read the expression for OCN1 as OCN2, OCN3, and OCN4 at each stage unless a special
explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.8-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.8.1 Non-directional ✓ ✓ ✓ ✓ ✓ NA NA
2.8.1 Directional ✓ ✓ ✓ NA NA NA NA
2.8.5 Blocking by VTF ✓ ✓ ✓ NA NA NA NA
2.8.5 Blocking by CTF ✓ ✓ ✓ NA NA NA NA
– Number of steps 4 4 4 4 4 NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 101 -
6F2S1927 (0.18)
Reference voltage or
θ Polarizing voltage (−V2)
φ
I2
A setting and a scheme switch, as well as the non-directional OCN element, provide the
settings for the directional OCN element: for example, the user can set the threshold value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 102 -
6F2S1927 (0.18)
(IOCN) for stage 1 with the setting [OCN1] and Forward can be set for the scheme switch [OCN1-
Dir]. Setting of the sensing angle (θ) is configured by the setting [OCN1-Angle] with the value
of θ in the range of 0–180°. Figure 2.8-2 shows an example of an angle and a characteristic
using the θ.
The operation decision of OCN uses the following equation:
𝐼2 ≥ 𝐼𝑂𝐶𝑁 (2.8-1)
𝐼2 × cos(φ − θ) ≥ 0 (2.8-2)
𝑉2 ≥ 𝑂𝐶𝑁_𝑉𝑝𝑜𝑙 (2.8-3)
where
I2 = Negative phase sequence current
V2 = Negative phase sequence voltage
−V2 = reference voltage (or polarizing voltage)
Φ = lagging angle
θ = OCN setting angle ([OCN1-Angle])
IOCN = Setting value of OCN ([OCN1] and the others])
OCN_Vpol = Setting value of the polarizing voltage ([OCN1-Vpol])
Note: The phase angle in the event of an internal fault is equal to the angle of the zero-
sequence impedance of the system; this value ranges approximately from 50° to
90°. The θ of OCN can be set from 0° to 180°. The minimum voltage necessary to
maintain directionality can be set from 0.5 to 180 V.
Reverse
θ=30°
θ=90°
Angle line
Forward
Reverse Forward Reverse Forward
Forward Reverse
Reverse
Vpol Vpol
Forward
θ=170°
θ=100°
θ=100° θ=170°
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 103 -
6F2S1927 (0.18)
For the reset time delay in the IDMT, either inverse (dependent)-time-reset or
definite(independent)-time-reset is characterized by the setting.
The user can select which characteristic will be applied to each stage of the OCN
element using scheme switches. We shall see the scheme switches later.
(i) DT characteristic
The operate time in the DT characteristic will be a constant time; it is not affected by the level
of the negative-sequence current. The reset time is set to zero so that resetting is performed
immediately. The user can set the operate time using a setting; it is discussed in sections (iv).
The reset time of the IDMT is also user-selectable; either inverse-time-reset or definite-
time-reset is selected. For the inverse-time-rest, the user can choose the reset time for the
preset characteristic from six characteristic curves; i.e. IEEE and US standard five pre-
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 104 -
6F2S1927 (0.18)
installed characteristic curves and one user-original characteristic carver where the user can
set the equation parameters. The inverse-time-reset curve equation and parameters will be
discussed in section (v).
k
𝑡(𝐼) = 𝑇𝑀𝑆 × {[ α ] + c} (2.8-4)
(I⁄I ) − 1
s
where:
t = operating time for constant current I (seconds),
I = energizing current (amperes),
Is = earth fault current setting (amperes),
TMS = time multiplier setting,
k, α, c = constants defining curve.
The nine pre-programmed standard characteristic curve are tabulated in Table 2.8-2;
additionally, one original (user-programmable) curve can be applied. One curve can be chosen
for each OCN stage by setting. Figure 2.8-3 illustrates these characteristic curves. For example,
the user should set one for the scheme switch [OCN1-Timer]: “IEC-NI” for IEC Normal Inverse,
“IEC-VI” for IEC Very Inverse, “IEC-EI” for IEC Extremely Inverse, “UK-LTI” for UK Long Time
Inverse, “IEEE-MI “ for IEEE Moderately Inverse, “IEEE-VI” for IEEE Very Inverse, “IEEE-EI”
for IEEE Extremely Inverse, “US-CO2” for US CO2 short time inverse, “US-CO8” for US CO8
inverse, and “Original” for user-programmable characteristic.
In the IDMT operation, the user can also program the characteristic using time-
multiplier-setting (TMS) for the required operate time. For example, when the IEC
characteristic is selected, the user can set the TMS value using the setting [OCN1-TMS-IEC]
(incidentally, the default value of the TMS is 1.00). The other TMSs are also available by the
[OCN1-TMS-UK], [OCN1-TMS-IEEE], [OCN1-TMS-US] and [OCN1-TMS-ORG].
Table 2.8-2 Constants for IDMT
Curve type
Curve Description k α c
(IEC 60255-151)
A IEC Normal Inverse (IEC-NI) 0.14 0.02 0
B IEC Very Inverse (IEC-VI) 13.5 1 0
C IEC Extremely Inverse (IEC-EI) 80 2 0
- UK Long Time Inverse (UK-LTI) 120 1 0
D IEEE Moderately Inverse (IEEE-MI) 0.0515 0.02 0.114
E IEEE Very Inverse (IEEE-VI) 19.61 2 0.491
F IEEE Extremely Inverse (IEEE-EI) 28.2 2 0.1217
- US CO8 inverse (US-CO8) 5.95 2 0.18
- US CO2 short time inverse (US-CO2) 0.02394 0.02 0.01694
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 105 -
6F2S1927 (0.18)
Time characteristic
The user should set DT for the scheme switch [OCN1-Timer]. The value of the required operate
time is set for the setting [TOCN1] in the range 0.00–300.00s.
Instantaneous activation
The instantaneous operation characteristic is achieved by setting zero for the [TOCN1], but the
instantaneous one can be also obtained when the logic signal “1 (High)” is programmed to be
injected at PLC connection point “OCN1_INST_OP”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 106 -
6F2S1927 (0.18)
defines the reset time for the inverse-time-reset characteristic (ref. IEC 60255-151):
kr
𝑡(I) = 𝑅𝑇𝑀𝑆 × [ β
] (2.8-2)
I
1 − ( ⁄I )
s
where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.
For setting RTMS for the IEEE standard, the user can use setting [OCN1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [OCN1-RTMS-US] and [OCN1-
RTMS-ORG] are provided for the US standard and the original, respectively (For more
information w.r.t the values for kr and β, see Table 2.8-3; Figure 2.8-4 shows the characteristic
curves).
Table 2.8-3 Constants for inverse-time-reset characteristics
Curve Type kr β
Curve Description
IEC 60255-151 (sec)
A IEC Normal Inverse (IEC-NI‡) N/A N/A
B IEC Very Inverse (IEC-VI‡) N/A N/A
C IEC Extremely Inverse (IEC-EI‡) N/A N/A
- UK Long Time Inverse (UK-LTI‡) N/A N/A
D IEEE Moderately Inverse (IEEE-MI) 4.85 2
E IEEE Very Inverse (IEEE-VI) 21.6 2
F IEEE Extremely Inverse (IEEE-EI) 29.1 2
- US CO8 inverse (US-CO8) 5.95 2
- US CO2 short time inverse (US-CO2) 2.261 2
†Note: To select the inverse-time-reset characteristic, set [OCN1-Rtimer]=DEP.
Conversely set [OCN1-Rtimer]=DEF to select definite-time-reset characteristic,.
Note: For the setting [OCN1-Rtimer]=DEP (inverse-time-reset), the integrated value will
be reduced in accordance to the magnitude of an energized current, when the
energized current is smaller than the setting [OCN1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OCN1-Rtimer]=DEF (definite-time-reset), the integrated value
shall be zero when an energized current is smaller than the setting [OCN1], when
the small energized current is continued for timer setting [TOCN1R]. The
integrated value will not be zero when the energized current does not flow small
for the setting [TOCN1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is
set unconditionally in the IEC and UK (see Table 2.8-4).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 107 -
6F2S1927 (0.18)
Energizing current
Energizing current
cleared by tripping
Measuring quantity 0A
Inverse-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEP
Integrator
Trip signal
Definite-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEF
Integrator
Trip signal
Reset time
Integration will be kept in timer [TOCN1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [OCN1] within [TOCN1R]. does not become larger than [OCN1] in [TOCN1R].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 108 -
6F2S1927 (0.18)
DT
✓
Scheme switch [OCN1-Timer]
IEC-NI
IEC-VI ✓
IEC-EI ✓
UK LTI ✓
IEEE-MI ✓
IEEE-VI ✓
IEEE-EI ✓
US-CO2 ✓
US-CO8 ✓
Original ✓
DEF N.A ✓† ✓† ✓† ✓† ✓ ✓ ✓ ✓ ✓ ✓
✓
Scheme switch
[OCN1-Rtimer]
N.A
N.A ✓
N.A ✓
DEP
N.A ✓
N.A ✓
N.A ✓
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 109 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 110 -
6F2S1927 (0.18)
8000011C23
OCN1†
8000011C27
For DT characteristic OCN1PU†
OCN1 TOCN1
&
8000011B60 To Grouping logic
& &
t 0
8000011BB0
ORIGINAL
800001EBB0 OCN1_BLOCK
8000011BB1
800001EBB1 OCN1_INST_OP
○
1 : A pick-up signal is generated instantly when the element operates.
○
2 : No signal due that the PU element is killed. Use ‘OCN1’ in place of this.
○
3 : A pick-up signal is generated, but delayed with the IDMT characteristic.
○
4 : A pick-up signal is generated instantly.
OCN1-OPT-ALARM ≥1 OCN-OPT-ALARM
OCN2-OPT- ALARM
OCN3-OPT- ALARM
OCN4-OPT- ALARM
OCN1-ARC-BLOCK ≥1 OCN-ARC-BLEFK
OCN2- ARC-BLOCK
OCN3- ARC-BLOCK
OCN4- ARC-BLOCK To Recording
OCN1-OPT OCN1-OPT
OCN2-OPT OCN2-OPT
OCN3-OPT OCN3-OPT
OCN4-OPT OCN4OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 111 -
6F2S1927 (0.18)
2.8.7 Setting
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN1-EN Off / On - OCN1 protection scheme switch Off
OCN2-EN Off / On - OCN2 protection scheme switch Off
OCN3-EN Off / On - OCN3 protection scheme switch Off
OCN4-EN Off / On - OCN4 protection scheme switch Off
OCN1 NonDir / Forward /
OCN1-Dir - OCN1 directional characteristic NonDir
Reverse
Fwd/ OCN1-Angle 0 - 180 deg OCN1 directional characteristic angle 45
Rev OCN1-Vpol 0.5 - 25.0 V OCN1 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN1-Timer IEEE-MI / IEEE-VI / - OCN1 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN1 A OCN1 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
TOCN1 0.00 - 300.00 s OCN1 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of IEC inverse curve 1.000
IEC
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of UK inverse curve 1.000
UK
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of IEEE inverse curve 1.000
IEEE
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of IEEE DEF
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-US 0.010 - 50.000 - OCN1 time multiplier of US inverse curve 1.000
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of US DEF
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN1 A OCN1 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN1-DPR 10 - 100 % OCN1 drop-out/pick-up ratio 100
OCN1-TMS-
0.010 - 50.000 - OCN1 time multiplier of US inverse curve 1.000
ORG
OCN1-Rtimer DEF / DEP - OCN1 reset delay type of ORG DEF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 112 -
6F2S1927 (0.18)
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
TOCN1R 0.00 - 300.00 s OCN1 definite time reset delay 0.00
OCN1-RTMS- OCN1 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN1-k 0.00000 - 500.00000 - OCN1 user original curve coefficient 0.00000
OCN1-a 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
OCN1-c 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
OCN1-kr 0.00000 - 500.00000 - OCN1 user original curve coefficient 0.00000
OCN1-b 0.00000 - 10.00000 - OCN1 user original curve coefficient 0.00000
Output OCN1-2fBlk Non / Block - OCN1 operation block by 2f-detection Non
OCN1-VTFBlk Non / Block - OCN1 operation block by VTF Non
OCN1-CTFBlk Non / Block - OCN1 operation block by CTF Non
OCN1-UseFor Trip / Alarm - OCN1 used for trip or alarm Trip
OCN1-ARCBlk Non / Block - Autoreclose block by OCN1 Block
OCN2 NonDir / Forward /
OCN2-Dir - OCN2 directional characteristic NonDir
Reverse
Fwd/ OCN2-Angle 0 - 180 deg OCN2 directional characteristic angle 45
Rev OCN2-Vpol 0.5 - 25.0 V OCN2 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN2-Timer IEEE-MI / IEEE-VI / - OCN2 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN2 A OCN2 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
TOCN2 0.00 - 300.00 s OCN2 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of IEC inverse curve 1.000
IEC
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of UK inverse curve 1.000
UK
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of IEEE inverse curve 1.000
IEEE
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of IEEE DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
OCN2-RTMS- OCN2 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-US 0.010 - 50.000 - OCN2 time multiplier of US inverse curve 1.000
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of US DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 113 -
6F2S1927 (0.18)
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN2-RTMS- OCN2 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN2 A OCN2 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN2-DPR 10 - 100 % OCN2 drop-out/pick-up ratio 100
OCN2-TMS-
0.010 - 50.000 - OCN2 time multiplier of US inverse curve 1.000
ORG
OCN2-Rtimer DEF / DEP - OCN2 reset delay type of ORG DEF
TOCN2R 0.00 - 300.00 s OCN2 definite time reset delay 0.00
OCN2-RTMS- OCN2 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN2-k 0.00000 - 500.00000 - OCN2 user original curve coefficient 0.00000
OCN2-a 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
OCN2-c 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
OCN2-kr 0.00000 - 500.00000 - OCN2 user original curve coefficient 0.00000
OCN2-b 0.00000 - 10.00000 - OCN2 user original curve coefficient 0.00000
Output OCN2-2fBlk Non / Block - OCN2 operation block by 2f-detection Non
OCN2-VTFBlk Non / Block - OCN2 operation block by VTF Non
OCN2-CTFBlk Non / Block - OCN2 operation block by CTF Non
OCN2-UseFor Trip / Alarm - OCN2 used for trip or alarm Trip
OCN2-ARCBlk Non / Block - Autoreclose block by OCN2 Block
OCN3 NonDir / Forward /
OCN3-Dir - OCN3 directional characteristic NonDir
Reverse
Fwd/ OCN3-Angle 0 - 180 deg OCN3 directional characteristic angle 45
Rev OCN3-Vpol 0.5 - 25.0 V OCN3 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN3-Timer IEEE-MI / IEEE-VI / - OCN3 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN3 A OCN3 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
TOCN3 0.00 - 300.00 s OCN3 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of IEC inverse curve 1.000
IEC
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of UK inverse curve 1.000
UK
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of IEEE inverse curve 1.000
IEEE
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of IEEE DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 114 -
6F2S1927 (0.18)
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
OCN3-RTMS- OCN3 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-US 0.010 - 50.000 - OCN3 time multiplier of US inverse curve 1.000
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of US DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
OCN3-RTMS- OCN3 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN3 A OCN3 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN3-DPR 10 - 100 % OCN3 drop-out/pick-up ratio 100
OCN3-TMS-
0.010 - 50.000 - OCN3 time multiplier of US inverse curve 1.000
ORG
OCN3-Rtimer DEF / DEP - OCN3 reset delay type of ORG DEF
TOCN3R 0.00 - 300.00 s OCN3 definite time reset delay 0.00
OCN3-RTMS- OCN3 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN3-k 0.00000 - 500.00000 - OCN3 user original curve coefficient 0.00000
OCN3-a 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
OCN3-c 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
OCN3-kr 0.00000 - 500.00000 - OCN3 user original curve coefficient 0.00000
OCN3-b 0.00000 - 10.00000 - OCN3 user original curve coefficient 0.00000
Output OCN3-2fBlk Non / Block - OCN3 operation block by 2f-detection Non
OCN3-VTFBlk Non / Block - OCN3 operation block by VTF Non
OCN3-CTFBlk Non / Block - OCN3 operation block by CTF Non
OCN3-UseFor Trip / Alarm - OCN3 used for trip or alarm Trip
OCN3-ARCBlk Non / Block - Autoreclose block by OCN3 Block
OCN4 NonDir / Forward /
OCN4-Dir - OCN4 directional characteristic NonDir
Reverse
Fwd/ OCN4-Angle 0 - 180 deg OCN4 directional characteristic angle 45
Rev OCN4-Vpol 0.5 - 25.0 V OCN4 polarizing voltage level 3.0
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
OCN4-Timer IEEE-MI / IEEE-VI / - OCN4 delay type DT
IEEE-EI / US-CO2 /
US-CO8 / Original
DT 0.02 - 0.10 -
OCN4 A OCN4 threshold (in DT mode) 0.40 2.00
50.00 250.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
TOCN4 0.00 - 300.00 s OCN4 operating delay time 1.00
IEC 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of IEC inverse curve 1.000
IEC
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of UK inverse curve 1.000
UK
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 115 -
6F2S1927 (0.18)
OCN(Function ID:443001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
IEEE 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of IEEE inverse curve 1.000
IEEE
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of IEEE DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-US 0.010 - 50.000 - OCN4 time multiplier of US inverse curve 1.000
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of US DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCN4 A OCN4 threshold (in IDMT mode) 0.40 2.00
5.00 25.00
OCN4-DPR 10 - 100 % OCN4 drop-out/pick-up ratio 100
OCN4-TMS-
0.010 - 50.000 - OCN4 time multiplier of US inverse curve 1.000
ORG
OCN4-Rtimer DEF / DEP - OCN4 reset delay type of ORG DEF
TOCN4R 0.00 - 300.00 s OCN4 definite time reset delay 0.00
OCN4-RTMS- OCN4 dependent reset time multiplier of ORG
0.010 - 50.000 - 1.000
ORG inverse curve
OCN4-k 0.00000 - 500.00000 - OCN4 user original curve coefficient 0.00000
OCN4-a 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
OCN4-c 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
OCN4-kr 0.00000 - 500.00000 - OCN4 user original curve coefficient 0.00000
OCN4-b 0.00000 - 10.00000 - OCN4 user original curve coefficient 0.00000
Output OCN4-2fBlk Non / Block - OCN4 operation block by 2f-detection Non
OCN4-VTFBlk Non / Block - OCN4 operation block by VTF Non
OCN4-CTFBlk Non / Block - OCN4 operation block by CTF Non
OCN4-UseFor Trip / Alarm - OCN4 used for trip or alarm Trip
OCN4-ARCBlk Non / Block - Autoreclose block by OCN4 Block
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 116 -
6F2S1927 (0.18)
2.8.8 Signal
Signal monitoring point
OCN(Function ID: 443001)
Element ID Name Description
OCN-ARC-BLOCK 8500001B62 Autoreclose block signal by OCN protection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 117 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 118 -
6F2S1927 (0.18)
THM has an exponential characteristics in accordance with the IEC 60255-149 standard.
THM determines both the I2R loss and the cooling effect of the coolant simultaneously; THM
also determines the pre-load condition and signals a trip signal when an overload condition
arises.
THM issues a trip signal in accordance with an alarm stage that reflects the temperature
of the thermal overload condition. The alarm stage is configured using a setting; hence, the
user should determine the appropriate setting so that a trip signal can be issued before the
apparatus is overheated
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.9-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 119 -
6F2S1927 (0.18)
Thermal state 0% is the cold state, whereas 100% reflects the thermal limit—which is
the point at which no further temperature rise can be tolerated safely and the system should
be disconnected. The thermal limit for any given system is subject to setting [THM], which
determines the value of overload current. The THM signals a trip when the value of θ is at
100%.
where,
q: Unbalance factor; the unbalance factor is used for motor/generator protection; the
user should set q=0 when setting [THM-q] except when it is applied to
motor/generator protection.
†Note:If the user prefers to use the thermal characteristic for the THM function specified
in IEC 60255-8, set Max phase for the scheme switch [THM-Itype]. In this case,
THM is determined using the largest of the three-phase currents.
The period of time for a trip to occur depends not only on the degree of overload, but also
on the degree of load current as far as reaching the overload state. The period of the trip, that
is, depends on whether the overload is applied from ‘cold’ or ‘hot’. THM has thresholds for
alarm and trip; hence, the two thresholds exist independently.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 120 -
6F2S1927 (0.18)
In Equation (2.9-3), cold curves are special versions of the hot curves where Ip is zero,
catering for the situation where a cold system is switched onto an immediate overload.
Figure 2.9-1.a shows the cold state where an overload has been switched onto a previously
un-loaded system. Figure 2.9-1.b shows the hot state where an overload is switched onto a
system that has previously been loaded to 90% of its capacity. The figures are in conformity
with the IEC 60255-149 curves, and these curves are drawn in a range of settings of the time
constant ().
a.Thermal Curves (Cold Curve - no prior load) b. Thermal Curves (Hot Curve - 90% prior load))
100
50
20
10
5
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 121 -
6F2S1927 (0.18)
The threshold level for the alarm is set using setting [THM-Alarm] as a percentage of the
tripping threshold. The alarm signal is disabled when Off is set for scheme switch [THMA-EN].
The trip signal is prevented when Off is set for scheme switch [THMT-EN]. PLC signals
THMA_BLOCK and THMT_BLOCK are used to block the operation of THM.
≥1 THM-OPT-TRIP
A 8100021C23 & & 8100021B60
THM 8400011B23
B THM-OPT-ALARM
&
& &
THMA-EN ON
& THM-ARC-BLOCK
THMT-EN ON
800001EBB0 THMA_BLOCK 1
810002EBB0 THMT_BLOCK 1
Trip
THMA-UseFor
Alarm
When wishing to have a test about pre-load current (Ip), the user should set a test value for
the setting [THM-IP] followed by setting [THM-Test]=On.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 122 -
6F2S1927 (0.18)
2.9.4 Setting
THM (Function ID: 451001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
THM-EN Off / On - Thermal protection scheme switch Off
0.40 - 2.00 -
THM A Thermal overload current 1.00 5.00
2.00 10.00
TTHM 0.5 - 500.0 min Thermal time constant 10.0
Type Max phase/
THM-Itype - Selection of THM equations Equivalent
Equivalent
THM-q 0 - 10 - Factor when Equivalent selected 0
SW THMT-EN Off / On - Thermal protection Off
THM-UseFor Trip / Alarm - THM used for trip or alarm Trip
ALM THMA-EN Off / On - Thermal alarm switch Off
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 123 -
6F2S1927 (0.18)
2.9.5 Signal
Signal monitoring point
THM(Function ID: 451001)
Element ID Name Description
8000011C23 THM-A THM relay element operated (Alarm)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 124 -
6F2S1927 (0.18)
In the steady state operation, the load current through a transmission-line is smaller
than the total of the rated loads that connected to the transmission-line. The load current can
reach as high as times of the maximum load current for a moment when the entire loads are
energized after a long interruption, but the load current can decreases within three or four
seconds. It is accounted that the load current at the energizing time is 1.5 times larger than a
normal peak load. Thus, it is necessary for some protective functions to have a few setting
groups that discriminate between the inrush current on cold load restoration and the fault
current. For instance, the function of overcurrent protection (OC) with the CLP is immune
during the inrush period. The OC is discussed separately. (See chapter Relay application:
Overcurrent protection)
The CLP can have eight setting groups for cold load state in order that the CLP can
follows the transition from one state to another state. Thus, the CLP can make some protective
functions switch to another higher setting group including time delay. The CLP also can halt
with setting. The group selection of the CLP is performed with scheme switch [CLP-SG].
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.10-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 125 -
6F2S1927 (0.18)
Under the normal operation, where the CB is closed, the CLP stays in STATE 0, and the
OC operates with a normal setting group.
When the CB opens, the scheme moves into STATE_1, then Cold-load-enable-timer
(TCLP) runs. If the CB closes again while the TCLP is running, the scheme will re-enter into
STATE_0. If the TCLP expires and the load is in cold, the scheme moves into STATE_2. When
the CB closes again, the scheme moves into STATE_3.
At STATE_2 and STATE_3, the setting group of the CLP is applied. The operation of the
CLP is forbidden by placing set of OFF for the scheme switch [CLP-EN].
Accelerated reset of the CLP is also possible. As being at STATE_3, poly-phase currents
are monitored by the function of inrush current detection (ICD). If poly-phase currents plunge
below the setting of ICD threshold, and when the duration of the plunge is longer than setting
[TCLP_DO], then the scheme automatically reverts into STATE_0. By placing set of ON for
scheme switch [CLP-DOEN], it is possible for the reset function to accelerate.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 126 -
6F2S1927 (0.18)
STATE 0
CB status: Closed
Settings: Normal
Monitor CB status
CB opens CB closes
within
T CLE time
STATE 1
CB status: Open
Settings: Normal
STATE 3
STATE 2 CB closes CB status: Closed
CB status: Open Settings: Cold Load
Settings: Cold Load
Run T CLR timer
Monitor CB status CB opens Monitor CB status
within Monitor load current I L
CLR time
From PROT_COMM
CB-DS_CONDITION
CB_ALLPH_OPEN
CB_ANYPH_CLOSE
STATE CONDITION
8000001B60 Change to
& & STATE 1
STATE 0
TCLP_EN
8100001B61 t 0 Change to
& 1 STATE 2
STATE 1 &
0 - 10000s 1
& Change to
& Change to
1 STATE 0
Setting Group1
8200001B62
STATE 2 & Change to
& Change to
& Setting Group2
STATE 3
+
"ON" 0 - 10000s TCLP_DO & Change to
Setting Group5
t 0
& Group1
8000001C20
A 0.00 - 100.00s
Group2 & Change to
1 1 Group3 Setting Group6
OCCLP 8100001C21
B Group4
8200001022 Group5 & Change to
C CLP-Test Group6 Setting Group7
+ CLP-SG Group7
[CLP-DOEN] Group8 & Change to
+ Setting Group8
+
"ON"
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 127 -
6F2S1927 (0.18)
2.10.2 Setting
CLP(Function ID: 481001) at Common
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CLP-EN Off / On - Cold load protection scheme switch Off
CLP Group1 / Group2 /
Group3 / Group4 /
CLP-SG - Applied setting group at cold load mode Group1
Group5 / Group6 /
Group7 / Group8
TCLP-EN 0 - 10000 s Cold load enable time 100
TCLP-RESET 0 - 10000 s Cold load reset time 100
DOEN CLP-DOEN Off / On - Cold load drop-out enable Off
0.02 - 0.10 -
OCCLP A Cold load drop-out current threshold 0.50 2.50
3.00 15.00
TCLP-DO 0.00 - 100.00 s Cold load drop-out time 0.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 128 -
6F2S1927 (0.18)
2.10.3 Signal
PLC monitoring point
CLP(Function ID: 481001)
Element ID Name Description
8000001C20 OCCLP-A OCCLP relay element operated (phase-A)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 129 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.11-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ NA NA
2.11.3(ii) Blocking by VTF ✓ ✓ ✓ NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 130 -
6F2S1927 (0.18)
k1 1– k1
I1F I1F
k1Z1 (1-k1)Z1
E1A
E1B
Zero sequence
I1F
k1Z1 k2Z2 (1-k2)Z2 (1-k1)Z1
K0Z0 (1-k0)Z0
E1A E1B
I1F Z2
Z1
E1A Z0 E1B
The series fault results in positive sequence current (I1F), negative sequence current (I2F)
and zero phase sequence current (I0F) in the single-phase. These are given by
𝐼1𝐹 + 𝐼2𝐹 + 𝐼0𝐹 = 0 (2.11-1)
𝑍2𝐹 𝐼2𝐹 ∙ 𝑍0𝐹 𝐼0𝐹 = 0 (2.11-2)
𝐸1𝐴 ∙ 𝐸1𝐵 = 𝑍1𝐹 𝐼1𝐹 ∙ 𝑍2𝐹 𝐼2𝐹 (2.11-3)
where,
E1A, E1B: power source voltage
Z1: positive sequence impedance
Z2: negative sequence impedance
Z0: zero sequence impedance
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 131 -
6F2S1927 (0.18)
From Equation (2.11-1), (2.11-2), and (2.11-3), the following equations are derived:
𝑍2 + 𝑍0
𝐼1𝐹 = (𝐸 − 𝐸1𝐵 ) (2.11-4)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴
−𝑍0
𝐼2𝐹 = (𝐸 − 𝐸1𝐵 ) (2.11-5)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴
−𝑍2
𝐼0𝐹 = (𝐸 − 𝐸1𝐵 ) (2.11-6)
𝑍1 𝑍2 + 𝑍1 𝑍0 + 𝑍2 𝑍0 1𝐴
The magnitude of the fault current depends on the impedance across the system, the
difference in phase angle, and the magnitude between the power source voltages behind both
ends.
As noted earlier, the BCD element detects the presence of a fault by measuring the ratio
between the negative sequence current and the positive sequence current (I2F/I1F). The ratio is
obtained from the negative sequence impedance (Z2) and the zero sequence impedance (Z0);
hence, the equation of the ratio is expressed as follows:
𝐼2𝐹 |𝐼2𝐹 | 𝑍0
= = (2.11-7)
𝐼1𝐹 |𝐼1𝐹 | 𝑍2 + 𝑍0
A ratio value of 0.5 or higher is obtained when the zero sequence impedance is larger
than the negative sequence impedance. The ratio, thus, is close to 1.0 if the system is high-
impedance earthed or a single-end earthed system.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 132 -
6F2S1927 (0.18)
I2
|𝐼2 |
൘|𝐼 | ≥ 𝐵𝐶𝐷 𝑠𝑒𝑡𝑡𝑖𝑛𝑔
1
BCD
|𝐼1 | ≥ 0.04 × 𝐼𝑛 &
|𝐼2 | ≥ 0.01 × 𝐼𝑛
0.01×In
o I1
0.04×In
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 133 -
6F2S1927 (0.18)
Normal power system levels of negative phase sequence restrict the setting value of
[BCD]. The BCD function continuously determines the ratio (I2F/I1F). User can check the
present ratio along with the maximum value (I21 max) that has been examined for 15 minutes
ago. We recommend that user should distinguish the present ratio against the value on
commissioning stage; and user should set a value for [BCD] from 130% to 150% of the ratio has
been checked.
Note: The ratio (I2F/ I1F) is displayed only when the current in positive-sequence (or load
current) on the secondary circuit is larger than 2% of the rated current on
secondary circuit.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 134 -
6F2S1927 (0.18)
2.11.5 Setting
Setting of BCD(Function ID: 452001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
BCD-EN Off / On - BCD protection scheme switch Off
BCD BCD 0.10 - 1.00 - BCD relay operating value (I2/I1) 0.20
TBCD 0.00 - 300.00 s BCD operating delay time 1.00
Output BCD-2fBlk Non / Block - BCD operation block by 2f-detection Non
BCD-CTFBlk Non / Block - BCD operation block by CTF Non
BCD-UseFor Trip / Alarm - BCD used for trip or alarm Trip
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 135 -
6F2S1927 (0.18)
2.11.6 Signal
Signal monitoring point
BCD(Function ID: 452001)
Element ID Name Description
8000001C23 BCD BCD relay element operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 136 -
6F2S1927 (0.18)
To simplify the description, only OV1 is discussed, but the expression is applicable to
other OVs; hence, read the expression for OV1 as the other stages unless a special explanation
or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.12-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 137 -
6F2S1927 (0.18)
Pickup
V
Dropoff
0 V
Pick-up characteristic
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 138 -
6F2S1927 (0.18)
level of the voltage condition. Figure 2.12-2 shows the invers time characteristic of the OV
element when a multiplier setting [OV1-TMS] is used. The OV element uses Equation (2.12-1)
to be in conformity to IEC 60255-127:
𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.12-1)
(𝑉⁄𝑉 ) − 1
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve
If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.12-2. For
example, the user-programmable (original) curve in the OV1 element will be acquired when
Original is set for the scheme switch [OV1-Timer], and when values of respective constants are
set for [OV1-k], [OV1-a], and [OV1-C].
1000.000
100.000
Operating Time (secs)
10.000
TMS = 10
TMS = 5
1.000
TMS = 2
TMS = 1
0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 139 -
6F2S1927 (0.18)
Reset feature
The user should set the time for resetting. Figure 2.12-3 shows that examples of the pick-up
and the drop-off relevant to both the fault occurrences and the operation time. The value of the
time counter furnished in the OV1 element is incremented if faults occur.
As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OV1 element is paralyzed in the reset time
set by [TOV1R].
If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OV1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOV1R].
When the user requires resetting the operation of the OV1 element immediately, setting
zero for the settings [TOV1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OV1 element is reset promptly.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 140 -
6F2S1927 (0.18)
T3
Tripping
T1 T1 T1 T1
T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time
Figure 2.12-3 Faults occurrences and reset operation when IDMT being applied
†Note:For more information about the trip circuit, see Chapter Relay application: Trip
circuit.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 141 -
6F2S1927 (0.18)
generates a pick-up signal when the entering voltage is excesses of the threshold anytime. For
example, in the IDMT characteristic, the user can measure the pickup time after the excess
using both PLC monitoring points “8000011C20” and “8000011C24”.
DT
IDMT
OV1-Timer Original ≥1
OV1-EN On
To Grouping logic
8000011C20 TOV1 8000011B62
A & & t 0
8100011C21 & OV1-OPT-A
≥1 8100011B63
OV1 B & t 0
8200011C22 & & OV1-OPT-B
≥1
C 8200011B64
& & &
t 0
≥1 OV1-OPT-C
8000011B60
0.00 to 300.00s
≥1
8000011C24 8000011B65
A & OV1-OPT
8100011C25 ≥1
OV1 PU B &
8200011C26
8000011B23
C & OV1-OPT-TRIP
&
8100011B66
8000011B61 & OV1-OPT-ALARM
≥1
OV1-ARC-BLOCK
800001EBB0 OV1_BLOCK ≥1 1
OV1-VTFBlk Block
& Trip
From VTF OV1-UseFor
Alarm
VTF_DETECT
OV1-OPT-AR ≥1 OV-OPT-AR
OV1-OPT-BR OV-OPT-BR
OV1-OPT-CR OV-OPT-CR
OV2-OPT-AR
≥1
OV2-OPT-BR
OV2-OPT-CR
OV3-OPT-AR
≥1
OV3-OPT-BR
OV3-OPT-CR
OV4-OPT-AR
OV4-OPT-BR
OV4-OPT-CR To Recording
OV1-OPT
OV1-OPT
OV2-OPT
OV2-OPT
OV3-OPT
OV3-OPT
OV4-OPT
OV4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 142 -
6F2S1927 (0.18)
2.12.6 Setting
Setting of OV(Function ID: 460101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
OV1-EN Off / On - OV1 protection scheme switch Off
OV2-EN Off / On - OV2 protection scheme switch Off
OV3-EN Off / On - OV3 protection scheme switch Off
OV4-EN Off / On - OV4 protection scheme switch Off
OV1 OV1-Timer DT / IDMT / Original - OV1 delay type DT
DT OV1 1.0 - 220.0 V OV1 threshold 120.0
TOV1 0.00 - 300.00 s OV1 operating delay time (in DT mode) 1.00
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
IDMT OV1 1.0 - 220.0 V OV1 threshold 120.0
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
OV1-TMS 0.010 - 100.000 - OV1 time multiplier (in IDMT mode) 1.000
TOV1R 0.0 - 300.0 s OV1 definite time reset delay 0.0
ORG OV1 1.0 - 220.0 V OV1 threshold 120.0
OV1-DPR 10 - 100 % OV1 drop-out/pick-up ratio 100
OV1-TMS 0.010 - 100.000 - OV1 time multiplier (in ORG mode) 1.000
TOV1R 0.0 - 300.0 s OV1 definite time reset delay 0.0
OV1-k 0.00000 - 500.00000 - OV1 user original curve coefficient 0.00000
OV1-a 0.00000 - 10.00000 - OV1 user original curve coefficient 0.00000
OV1-c 0.00000 - 10.00000 - OV1 user original curve coefficient 0.00000
Output OV1-VTFBlk Non / Block - OV1 operation block by VTF Non
OV1-UseFor Trip / Alarm - OV1 used for trip or alarm Trip
OV2 OV2-Timer DT / IDMT / Original - OV2 delay type DT
DT OV2 1.0 - 220.0 V OV2 threshold 120.0
TOV2 0.00 - 300.00 s OV2 operating delay time (in DT mode) 1.00
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
IDMT OV2 1.0 - 220.0 V OV2 threshold 120.0
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
OV2-TMS 0.010 - 100.000 - OV2 time multiplier (in IDMT mode) 1.000
TOV2R 0.0 - 300.0 s OV2 definite time reset delay 0.0
ORG OV2 1.0 - 220.0 V OV2 threshold 120.0
OV2-DPR 10 - 100 % OV2 drop-out/pick-up ratio 100
OV2-TMS 0.010 - 100.000 - OV2 time multiplier (in ORG mode) 1.000
TOV2R 0.0 - 300.0 s OV2 definite time reset delay 0.0
OV2-k 0.00000 - 500.00000 - OV2 user original curve coefficient 0.00000
OV2-a 0.00000 - 10.00000 - OV2 user original curve coefficient 0.00000
OV2-c 0.00000 - 10.00000 - OV2 user original curve coefficient 0.00000
Output OV2-VTFBlk Non / Block - OV2 operation block by VTF Non
OV2-UseFor Trip / Alarm - OV2 used for trip or alarm Trip
OV3 OV3-Timer DT / IDMT / Original - OV3 delay type DT
DT OV3 1.0 - 220.0 V OV3 threshold 120.0
TOV3 0.00 - 300.00 s OV3 operating delay time (in DT mode) 1.00
OV3-DPR 10 - 100 % OV3 drop-out/pick-up ratio 100
IDMT OV3 1.0 - 220.0 V OV3 threshold 120.0
OV3-DPR 10 - 100 % OV3 drop-out/pick-up ratio 100
OV3-TMS 0.010 - 100.000 - OV3 time multiplier (in IDMT mode) 1.000
TOV3R 0.0 - 300.0 s OV3 definite time reset delay 0.0
ORG OV3 1.0 - 220.0 V OV3 threshold 120.0
OV3-DPR 10 - 100 % OV3 drop-out/pick-up ratio 100
OV3-TMS 0.010 - 100.000 - OV3 time multiplier (in ORG mode) 1.000
TOV3R 0.0 - 300.0 s OV3 definite time reset delay 0.0
OV3-k 0.00000 - 500.00000 - OV3 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 143 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 144 -
6F2S1927 (0.18)
2.12.7 Signal
Signal monitoring point
OV(Function ID: 460101)
Element ID Name Description
8800001B62 OV-OPT-A OV protection operated (phase-A)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 145 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 146 -
6F2S1927 (0.18)
To simplify the description, only OVS1 is discussed, but the expression is applicable to
other OVSs; hence, read the expression for OVS1 as the other stages unless a special
explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.13-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 147 -
6F2S1927 (0.18)
Pickup
V
Dropoff
0 V
For example, with regard to the OVS1 element, suppose the user sets a pick-up value in
P.U for setting [OVS1]. Then the user should set a drop-off value using setting [OVS1-DPR],
which configures the ratio of the PU to the DO.
Operation feature
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 148 -
6F2S1927 (0.18)
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
level of the voltage condition. Figure 2.13-2 shows the invers time characteristic of the OVS
element when a multiplier setting is used. The OVS element uses Equation (2.13-1) to be in
conformity to IEC 60255-127:
𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.13-1)
(𝑉⁄𝑉 ) − 1
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve
If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.13-2. For
example, the user-programmable (original) curve in the OVS1 element will be acquired when
Original is set for the scheme switch [OVS1-Timer], and when values of respective constants
are set for [OVS1-k], [OVS1-a], and [OVS1-C].
1000.000
100.000
Operating Time (secs)
10.000
TMS = 10
TMS = 5
1.000
TMS = 2
TMS = 1
0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 149 -
6F2S1927 (0.18)
As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OVS1 element is paralyzed in the reset time
set by [TOVS1R].
If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OVS1 element will issue a trip signal after a certain delay.
After issuing the trip signal, if a series of fault completely disappears after issuing the trip
signal, the value of the time counter will be expired after the reset time [TOVS1R].
When the user requires resetting the operation of the OVS1 element immediately, setting
zero for the settings [TOVS1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OVS1 element is reset promptly.
Condition fault occurrence
Intermittent fault Series faults
T3
Tripping
T1 T1 T1 T1
T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time
Figure 2.13-3 Faults occurrences and reset operation when IDMT being applied
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 150 -
6F2S1927 (0.18)
†Note:For more information of the trip circuit, see Chapter Relay application: Trip
circuit.
OVS1-EN On
To Grouping logic
8000011C20 TOVS1 8000011B62
AB & & t 0
8100011C21 & OVS1-OPT-AB
≥1 8100011B63
OVS1 BC & t 0
8200011C22 & & OVS1-OPT-BC
≥1
CA 8200011B64
& & &
t 0
≥1 OVS1-OPT-CA
8000011B60
≥1 0.00 to 300.00s
8000011C24 8000011B65
AB & OVS1-OPT
8100011C25 ≥1
OVS1 PU BC &
8200011C26
8000011B23
CA & OVS1-OPT-TRIP
&
8100011B66
8000011B61 & OVS1-OPT-ALARM
≥1
OVS1-ARC-BLOCK
800001EBB0 OV1_BLOCK ≥1 1
OVS1-VTFBlk Block
& Trip
From VTF OVS1-UseFor
Alarm
VTF_DETECT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 151 -
6F2S1927 (0.18)
OVS1-OPT-AR ≥1 OVS-OPT-AR
OVS1-OPT-BR OVS-OPT-BR
OVS1-OPT-CR OVS-OPT-CR
OVS2-OPT-AR
≥1
OVS2-OPT-BR
OVS2-OPT-CR
OVS3-OPT-AR
≥1
OVS3-OPT-BR
OVS3-OPT-CR
OVS4-OPT-AR
OVS4-OPT-BR
To Recording
OVS4-OPT-CR
OVS1-OPT OVS1-OPT
OVS2-OPT OVS2-OPT
OVS3-OPT OVS3-OPT
OVS4-OPT OVS4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 152 -
6F2S1927 (0.18)
2.13.6 Setting
Setting of OVS(Function ID: 461101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
OVS1-EN Off / On - OVS1 protection scheme switch Off
OVS2-EN Off / On - OVS2 protection scheme switch Off
OVS3-EN Off / On - OVS3 protection scheme switch Off
OVS4-EN Off / On - OVS4 protection scheme switch Off
OVS1 OVS1-Timer DT / IDMT / Original - OVS1 delay type DT
DT OVS1 1.0 - 220.0 V OVS1 threshold 120.0
TOVS1 0.00 - 300.00 s OVS1 operating delay time (in DT mode) 1.00
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
IDMT OVS1 1.0 - 220.0 V OVS1 threshold 120.0
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
OVS1-TMS 0.010 - 100.000 - OVS1 time multiplier (in IDMT mode) 1.000
TOVS1R 0.0 - 300.0 s OVS1 definite time reset delay 0.0
ORG OVS1 1.0 - 220.0 V OVS1 threshold 120.0
OVS1-DPR 10 - 100 % OVS1 drop-out/pick-up ratio 100
OVS1-TMS 0.010 - 100.000 - OVS1 time multiplier (in ORG mode) 1.000
TOVS1R 0.0 - 300.0 s OVS1 definite time reset delay 0.0
OVS1-k 0.00000 - 500.00000 - OVS1 user original curve coefficient 0.00000
OVS1-a 0.00000 - 10.00000 - OVS1 user original curve coefficient 0.00000
OVS1-c 0.00000 - 10.00000 - OVS1 user original curve coefficient 0.00000
Output OVS1-VTFBlk Non / Block - OVS1 operation block by VTF Non
OVS1-UseFor Trip / Alarm - OVS1 used for trip or alarm Trip
OVS2 OVS2-Timer DT / IDMT / Original - OVS2 delay type DT
DT OVS2 1.0 - 220.0 V OVS2 threshold 120.0
TOVS2 0.00 - 300.00 s OVS2 operating delay time (in DT mode) 1.00
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
IDMT OVS2 1.0 - 220.0 V OVS2 threshold 120.0
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
OVS2-TMS 0.010 - 100.000 - OVS2 time multiplier (in IDMT mode) 1.000
TOVS2R 0.0 - 300.0 s OVS2 definite time reset delay 0.0
ORG OVS2 1.0 - 220.0 V OVS2 threshold 120.0
OVS2-DPR 10 - 100 % OVS2 drop-out/pick-up ratio 100
OVS2-TMS 0.010 - 100.000 - OVS2 time multiplier (in ORG mode) 1.000
TOVS2R 0.0 - 300.0 s OVS2 definite time reset delay 0.0
OVS2-k 0.00000 - 500.00000 - OVS2 user original curve coefficient 0.00000
OVS2-a 0.00000 - 10.00000 - OVS2 user original curve coefficient 0.00000
OVS2-c 0.00000 - 10.00000 - OVS2 user original curve coefficient 0.00000
Output OVS2-VTFBlk Non / Block - OVS2 operation block by VTF Non
OVS2-UseFor Trip / Alarm - OVS2 used for trip or alarm Trip
OVS3 OVS3-Timer DT / IDMT / Original - OVS3 delay type DT
DT OVS3 1.0 - 220.0 V OVS3 threshold 120.0
TOVS3 0.00 - 300.00 s OVS3 operating delay time (in DT mode) 1.00
OVS3-DPR 10 - 100 % OVS3 drop-out/pick-up ratio 100
IDMT OVS3 1.0 - 220.0 V OVS3 threshold 120.0
OVS3-DPR 10 - 100 % OVS3 drop-out/pick-up ratio 100
OVS3-TMS 0.010 - 100.000 - OVS3 time multiplier (in IDMT mode) 1.000
TOVS3R 0.0 - 300.0 s OVS3 definite time reset delay 0.0
ORG OVS3 1.0 - 220.0 V OVS3 threshold 120.0
OVS3-DPR 10 - 100 % OVS3 drop-out/pick-up ratio 100
OVS3-TMS 0.010 - 100.000 - OVS3 time multiplier (in ORG mode) 1.000
TOVS3R 0.0 - 300.0 s OVS3 definite time reset delay 0.0
OVS3-k 0.00000 - 500.00000 - OVS3 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 153 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 154 -
6F2S1927 (0.18)
2.13.7 Signal
Signal monitoring point
OVS(Function ID: 461101)
Element ID Name Description
8C00001B62 OVS-OPT-AB OVS protection operated (phase-AB)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 155 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 156 -
6F2S1927 (0.18)
The low voltage settings, which may be applied for OVG elements, are susceptible to any
third harmonic component that may be superimposed on input signals. Therefore, the function
incorporates filters to suppress the third harmonic component.
To simplify the description, only OVG1 is discussed but is applicable to OVG2 and the
others; hence, read the expression for OVG1 as other stages unless a special explanation or
instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.14-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 157 -
6F2S1927 (0.18)
Pickup
V
Dropoff
0 V
For example, with regard to the OVG1 element, suppose the user sets a pick-up value in
P.U for setting [OVG1]. Then the user should set a drop-off value using setting [OVG1-DPR],
which configures the ratio of the PU to the DO.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 158 -
6F2S1927 (0.18)
Operation feature
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
level of the voltage condition. Figure 2.14-2 shows the invers time characteristic of the OVG
element when a multiplier setting is used. The OVG element uses Equation (2.14-1) to be in
conformity to IEC 60255-127:
𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.14-1)
(𝑉⁄𝑉 ) − 1
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve
If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.14-2. For
example, the user-programmable (original) curve in the OVG1 element will be acquired when
Original is set for the scheme switch [OVG1-Timer], and when values of respective constants
are set for [OVG1-k], [OVG1-a], and [OVG1-C].
1000.000
100.000
Operating Time (secs)
10.000
TMS = 10
TMS = 5
1.000
TMS = 2
TMS = 1
0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 159 -
6F2S1927 (0.18)
As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OVG1 element is paralyzed in the reset time
set by [TOVG1R].
If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OVG1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOVG1R].
When the user requires resetting the operation of the OVG1 element immediately, setting
zero for the settings [TOVG1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OVG1 element is reset promptly.
Intermittent fault Series faults
Condition fault occurrence
T3
Tripping
T1 T1 T1 T1
T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time
Figure 2.14-3 Faults occurrences and reset operation when IDMT being applied
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 160 -
6F2S1927 (0.18)
†Note:For more information of the trip circuit, see Chapter Relay application: Trip
circuit.
OVG1-EN On
To Grouping logic
8000011C23 TOVG1
& 8000011B60
OVG1 & t 0
& OVG1-OPT
≥1
0.00 to 300.00s
8000011C27
OVG1 PU
&
≥1 8000011B23
800001EBB0 OVG1_BLOCK
& OVG1-OPT-TRIP
Block 8100021B66
OVG1-VTFBlk &
& OVG1-OPT-ALARM
1
From VTF
VTF_DETECT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 161 -
6F2S1927 (0.18)
OVG1-OPT-ALARM ≥1 OVG-OPT-ALARM
OVG2-OPT- ALARM
OVG3-OPT- ALARM
OVG4-OPT- ALARM
OVG-ARC-BLOCK
To Recording
OVG1-OPT OVG1-OPT
OVG2-OPT OVG2-OPT
OVG3-OPT OVG3-OPT
OVG4-OPT OVG4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 162 -
6F2S1927 (0.18)
2.14.6 Setting
Setting of OVG(Function ID: 462101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
OVG1-EN Off / On - OVG1 protection scheme switch Off
OVG2-EN Off / On - OVG2 protection scheme switch Off
OVG3-EN Off / On - OVG3 protection scheme switch Off
OVG4-EN Off / On - OVG4 protection scheme switch Off
OVG1 OVG1-Timer DT / IDMT / Original - OVG1 delay type DT
DT OVG1 1.0 - 220.0 V OVG1 threshold 20.0
TOVG1 0.00 - 300.00 s OVG1 operating delay time (in DT mode) 1.00
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
IDMT OVG1 1.0 - 220.0 V OVG1 threshold 20.0
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
OVG1-TMS 0.010 - 100.000 - OVG1 time multiplier (in IDMT mode) 1.000
TOVG1R 0.0 - 300.0 s OVG1 definite time reset delay 0.0
ORG OVG1 1.0 - 220.0 V OVG1 threshold 20.0
OVG1-DPR 10 - 100 % OVG1 drop-out/pick-up ratio 100
OVG1-TMS 0.010 - 100.000 - OVG1 time multiplier (in ORG mode) 1.000
TOVG1R 0.0 - 300.0 s OVG1 definite time reset delay 0.0
OVG1-k 0.00000 - 500.00000 - OVG1 user original curve coefficient 0.00000
OVG1-a 0.00000 - 10.00000 - OVG1 user original curve coefficient 0.00000
OVG1-c 0.00000 - 10.00000 - OVG1 user original curve coefficient 0.00000
Output OVG1-VTFBlk Non / Block - OVG1 operation block by VTF Non
OVG1-UseFor Trip / Alarm - OVG1 used for trip or alarm Trip
OVG2 OVG2-Timer DT / IDMT / Original - OVG2 delay type DT
DT OVG2 1.0 - 220.0 V OVG2 threshold 20.0
TOVG2 0.00 - 300.00 s OVG2 operating delay time (in DT mode) 1.00
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
IDMT OVG2 1.0 - 220.0 V OVG2 threshold 20.0
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
OVG2-TMS 0.010 - 100.000 - OVG2 time multiplier (in IDMT mode) 1.000
TOVG2R 0.0 - 300.0 s OVG2 definite time reset delay 0.0
ORG OVG2 1.0 - 220.0 V OVG2 threshold 20.0
OVG2-DPR 10 - 100 % OVG2 drop-out/pick-up ratio 100
OVG2-TMS 0.010 - 100.000 - OVG2 time multiplier (in ORG mode) 1.000
TOVG2R 0.0 - 300.0 s OVG2 definite time reset delay 0.0
OVG2-k 0.00000 - 500.00000 - OVG2 user original curve coefficient 0.00000
OVG2-a 0.00000 - 10.00000 - OVG2 user original curve coefficient 0.00000
OVG2-c 0.00000 - 10.00000 - OVG2 user original curve coefficient 0.00000
Output OVG2-VTFBlk Non / Block - OVG2 operation block by VTF Non
OVG2-UseFor Trip / Alarm - OVG2 used for trip or alarm Trip
OVG3 OVG3-Timer DT / IDMT / Original - OVG3 delay type DT
DT OVG3 1.0 - 220.0 V OVG3 threshold 20.0
TOVG3 0.00 - 300.00 s OVG3 operating delay time (in DT mode) 1.00
OVG3-DPR 10 - 100 % OVG3 drop-out/pick-up ratio 100
IDMT OVG3 1.0 - 220.0 V OVG3 threshold 20.0
OVG3-DPR 10 - 100 % OVG3 drop-out/pick-up ratio 100
OVG3-TMS 0.010 - 100.000 - OVG3 time multiplier (in IDMT mode) 1.000
TOVG3R 0.0 - 300.0 s OVG3 definite time reset delay 0.0
ORG OVG3 1.0 - 220.0 V OVG3 threshold 20.0
OVG3-DPR 10 - 100 % OVG3 drop-out/pick-up ratio 100
OVG3-TMS 0.010 - 100.000 - OVG3 time multiplier (in ORG mode) 1.000
TOVG3R 0.0 - 300.0 s OVG3 definite time reset delay 0.0
OVG3-k 0.00000 - 500.00000 - OVG3 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 163 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 164 -
6F2S1927 (0.18)
2.14.7 Signal
Signal monitoring point
OVG(Function ID: 462101)
Element ID Name Description
8400001B61 OVG-OPT-ALARM Alarm signal by OVG protection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 165 -
6F2S1927 (0.18)
To simplify the description, only OVN1 is discussed but is applicable to the other OVNs;
hence, read the expression for OVN1 as OVN2, OVN3 and OVN4 at each OVN stage unless a
special explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.15-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 166 -
6F2S1927 (0.18)
Pickup
V
Dropoff
0 V
For example, with regard to the OVN1 element, suppose the user sets a pick-up value in
P.U for setting [OVN1]. Then the user should set a drop-off value using setting [OVN1-DPR],
which configures the ratio of the PU to the DO.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 167 -
6F2S1927 (0.18)
Operation feature
The operate time of the inverse (dependent) time characteristic is inversely proportional to the
level of the voltage condition. Figure 2.13-2 shows the invers time characteristic of the OVN
element when a multiplier setting is used. The OVN element uses Equation (2.13-1) to be in
conformity to IEC 60255-127:
𝑘
t(G) = TMS × {[ 𝑎 ] + 𝑐} (2.15-1)
(𝑉⁄𝑉 ) − 1
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage), and
TMS = time multiplier setting to adjust a curve
If the user will require a user-programmable (original) curve in the inverse time
characteristic, it is provided when the constants of k, a, c are set, as shown in Table 2.13-2. For
example, the user-programmable (original) curve in the OVN1 element will be acquired when
Original is set for the scheme switch [OVN1-Timer], and when values of respective constants
are set for [OVN1-k], [OVN1-a], and [OVN1-C].
1000.000
100.000
Operating Time (secs)
10.000
TMS = 10
TMS = 5
1.000
TMS = 2
TMS = 1
0.100
1 1.5 2 2.5 3
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 168 -
6F2S1927 (0.18)
As for an intermittent fault (the former in the figure), the time counter will not reach the
trip level. In the other words, the operation of the OVN1 element is paralyzed in the reset time
set by [TOVN1R].
If a series of fault occurs repeatedly (the latter in the figure), and if the value of the time
counter reaches at trip level, the OVN1 element will issue a trip command after a certain delay.
After issuing the trip command, if a series of fault completely disappears after issuing the trip
command, the value of the time counter will be expired after the reset time [TOVN1R].
When the user requires resetting the operation of the OVN1 element immediately, setting
zero for the settings [TOVN1R] is needed. Consequently, when a voltage falls below the reset
threshold (drop-off), the operation of the OVN1 element is reset promptly.
Tripping
T1 T1 T1 T1
T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time
Figure 2.15-3 Faults occurrences and reset operation when IDMT being applied
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 169 -
6F2S1927 (0.18)
†Note:For more information of the trip circuit, see Chapter Relay application: Trip
circuit.
OVN1-OPT-ALARM ≥1 OVN-OPT-ALARM
OVN2-OPT- ALARM
OVN3-OPT- ALARM
OVN4-OPT- ALARM
OVN-ARC-BLOCK
To Recording
OVN1-OPT OVN1-OPT
OVN2-OPT OVN2-OPT
OVN3-OPT OVN3-OPT
OVN4-OPT OVN4-OPT
Figure 2.15-4 and
Figure 2.15-5 show the OVN function logic. Signal connection point “OVN1_BLOCK” is
provided for the block of the operation of the OVN1 elements.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 170 -
6F2S1927 (0.18)
DT
IDMT
OVN1-Timer Original ≥1
OVN1-EN On
To Grouping logic
8000011C23 TOVN1
& 8000011B60
OVN1 & t 0
& OVN1-OPT
≥1
0.00 to 300.00s
8000011C27
OVN1 PU
&
≥1 8000011B23
800001EBB0 OVN1_BLOCK
& OVN1-OPT-TRIP
Block 8100021B66
OVN1-VTFBlk &
& OVN1-OPT-ALARM
1
From VTF
VTF_DETECT
OVN1-OPT-ALARM ≥1 OVN-OPT-ALARM
OVN2-OPT- ALARM
OVN3-OPT- ALARM
OVN4-OPT- ALARM
OVN-ARC-BLOCK
To Recording
OVN1-OPT OVN1-OPT
OVN2-OPT OVN2-OPT
OVN3-OPT OVN3-OPT
OVN4-OPT OVN4-OPT
2.15.6 Application
Negative sequence voltage is used to detect unbalance in the system, such as three-phase motor.
When a loss of phase occurs, the motor results in the state of voltage unbalance. The voltage
unbalance produces negative sequence currents; the appearance of the negative sequence
brings the influence of its raising temperature on the motor. Another influence of the negative
sequence produces magnetic flux in air gap of the motor, and makes the motor to rotate in the
opposite direction. Thereby, the OVN is used to prevent its damage, and the feature of the OVN
detects the negative sequence.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 171 -
6F2S1927 (0.18)
2.15.7 Setting
Setting of OVN(Function ID: 464101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
OVN1-EN Off / On - OVN1 protection scheme switch Off
OVN2-EN Off / On - OVN2 protection scheme switch Off
OVN3-EN Off / On - OVN3 protection scheme switch Off
OVN4-EN Off / On - OVN4 protection scheme switch Off
OVN1 OVN1-Timer DT / IDMT / Original - OVN1 delay type DT
DT OVN1 1.0 - 220.0 V OVN1 threshold 120.0
TOVN1 0.00 - 300.00 s OVN1 operating delay time (in DT mode) 1.00
OVN1-DPR 10 - 100 % OVN1 drop-out/pick-up ratio 100
IDMT OVN1 1.0 - 220.0 V OVN1 threshold 120.0
OVN1-DPR 10 - 100 % OVN1 drop-out/pick-up ratio 100
OVN1-TMS 0.010 - 100.000 - OVN1 time multiplier (in IDMT mode) 1.000
TOVN1R 0.0 - 300.0 s OVN1 definite time reset delay 0.0
ORG OVN1 1.0 - 220.0 V OVN1 threshold 120.0
OVN1-DPR 10 - 100 % OVN1 drop-out/pick-up ratio 100
OVN1-TMS 0.010 - 100.000 - OVN1 time multiplier (in ORG mode) 1.000
TOVN1R 0.0 - 300.0 s OVN1 definite time reset delay 0.0
OVN1-k 0.00000 - 500.00000 - OVN1 user original curve coefficient 0.00000
OVN1-a 0.00000 - 10.00000 - OVN1 user original curve coefficient 0.00000
OVN1-c 0.00000 - 10.00000 - OVN1 user original curve coefficient 0.00000
Output OVN1-VTFBlk Non / Block - OVN1 operation block by VTF Non
OVN1-UseFor Trip / Alarm - OVN1 used for trip or alarm Trip
OVN2 OVN2-Timer DT / IDMT / Original - OVN2 delay type DT
DT OVN2 1.0 - 220.0 V OVN2 threshold 120.0
TOVN2 0.00 - 300.00 s OVN2 operating delay time (in DT mode) 1.00
OVN2-DPR 10 - 100 % OVN2 drop-out/pick-up ratio 100
IDMT OVN2 1.0 - 220.0 V OVN2 threshold 120.0
OVN2-DPR 10 - 100 % OVN2 drop-out/pick-up ratio 100
OVN2-TMS 0.010 - 100.000 - OVN2 time multiplier (in IDMT mode) 1.000
TOVN2R 0.0 - 300.0 s OVN2 definite time reset delay 0.0
ORG OVN2 1.0 - 220.0 V OVN2 threshold 120.0
OVN2-DPR 10 - 100 % OVN2 drop-out/pick-up ratio 100
OVN2-TMS 0.010 - 100.000 - OVN2 time multiplier (in ORG mode) 1.000
TOVN2R 0.0 - 300.0 s OVN2 definite time reset delay 0.0
OVN2-k 0.00000 - 500.00000 - OVN2 user original curve coefficient 0.00000
OVN2-a 0.00000 - 10.00000 - OVN2 user original curve coefficient 0.00000
OVN2-c 0.00000 - 10.00000 - OVN2 user original curve coefficient 0.00000
Output OVN2-VTFBlk Non / Block - OVN2 operation block by VTF Non
OVN2-UseFor Trip / Alarm - OVN2 used for trip or alarm Trip
OVN3 OVN3-Timer DT / IDMT / Original - OVN3 delay type DT
DT OVN3 1.0 - 220.0 V OVN3 threshold 120.0
TOVN3 0.00 - 300.00 s OVN3 operating delay time (in DT mode) 1.00
OVN3-DPR 10 - 100 % OVN3 drop-out/pick-up ratio 100
IDMT OVN3 1.0 - 220.0 V OVN3 threshold 120.0
OVN3-DPR 10 - 100 % OVN3 drop-out/pick-up ratio 100
OVN3-TMS 0.010 - 100.000 - OVN3 time multiplier (in IDMT mode) 1.000
TOVN3R 0.0 - 300.0 s OVN3 definite time reset delay 0.0
ORG OVN3 1.0 - 220.0 V OVN3 threshold 120.0
OVN3-DPR 10 - 100 % OVN3 drop-out/pick-up ratio 100
OVN3-TMS 0.010 - 100.000 - OVN3 time multiplier (in ORG mode) 1.000
TOVN3R 0.0 - 300.0 s OVN3 definite time reset delay 0.0
OVN3-k 0.00000 - 500.00000 - OVN3 user original curve coefficient 0.00000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 172 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 173 -
6F2S1927 (0.18)
2.15.8 Signal
Signal monitoring point
OVN(Function ID: 464101)
Element ID Name Description
8400001B61 OVN-OPT-ALARM Alarm signal by OVN protection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 174 -
6F2S1927 (0.18)
Each UV stage (element) detects the under-voltage condition of phase-to-earth. The user
can set a threshold and the ratio of a drip-out voltage (DO) to a pick-up voltage (PU) in the UV
element. To simplify the description, only the UV1 element is described, but the expression is
applicable to the other elements; hence, read the expression for the UV1 element as the others
unless a special explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.16-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 175 -
6F2S1927 (0.18)
The inner circle shows the area in which the UV function is blocked when the value of
the block voltage is set for [UVBLK]. Setting [TUVBLK] is also provided so that the user can
delay blocking the UV1 and UV2 elements using the setting.
Drop-off
Pickup
o V
UV block
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 176 -
6F2S1927 (0.18)
𝑘
t(G) = TMS × {[ 𝑎] + 𝑐} (2.16-1)
1 − (𝑉⁄𝑉 )
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage),
TMS = time multiplier setting.
1000.000
100.000
Operating Time (secs)
TMS=10
10.000
TMS=5
TMS=2
TMS=1
1.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 177 -
6F2S1927 (0.18)
As for an intermittent fault (the former in the figure), the time counter does not reach
the trip level. In the other word, the UV1 element will be paralyzed in the reset time [TUV1R].
If a series of fault occurs, the time counter increase corresponding to the duration of series
faults. When the time counter reaches the trip level, then the UV1 element issues a trip
command after a certain delay. After issuing the trip command, if a series of fault disappears
completely, the operation of the UV1 element is expired after the reset time [TUV1R].
When the user requires resetting the operation of the UV1 element immediately, setting
zero for the settings [TUV1R] is needed. Consequently, when a voltage is recovered over the
reset threshold (drop-off), the operation of the UV1 element is reset promptly.
Intermittent fault A series fault
Condition fault occurrence
T3
Tripping
T1 T1 T1 T1
T2 T2
T1: Resetting time set by the user Increment process in time Reset of time counter
T2: Actual resetting time in the relay operation counter
T3: Time gap between fault occurrence and relay start time Value maintenance of time counter
Figure 2.16-3 Faults occurrences and reset operation when IDMT being applied
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 178 -
6F2S1927 (0.18)
†Note:For more information about tripping, see Chapter Relay application: Trip circuit.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 179 -
6F2S1927 (0.18)
8000011B65
8000011B24 & UV1-OPT
≥1
A
8100011B25 &
UV1 PU B 8000011B23
8200011B26
& & UV1-OPT-TRIP
C 8000011B66
& UV1-OPT-ALARM
≥1 8000011B61
On Trip
UV1-EN UV1-UseFor
Alarm
DT
IDMT
Original ≥1
UV1-Timer
800001EBB0 UV1_BLOCK
≥1
UV1-VTFBlk 1
Block
&
From VTF
VTF_DETECT To UV2, UV3, UV4 logics
8000011B60 VTF_DETECT
A &
8100011B61
TUVBLK
UVBLK B t 0
8200011B62 NON UVBLK
1 ≥1
C
0.00 to
300.00s
UVBLK-EN On
UV-Test On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 180 -
6F2S1927 (0.18)
UV1-OPT-ALARM ≥1 UV-OPT-ALARM
UV2-OPT- ALARM
UV3-OPT- ALARM
UV4-OPT- ALARM
UV-ARC-BLOCK
UV1-OPT-AR ≥1 UV-OPT-AR
UV1-OPT-BR UV-OPT-BR
UV1-OPT-CR UV-OPT-CR
UV2-OPT-AR
≥1
UV2-OPT-BR
UV2-OPT-CR
UV3-OPT-AR
≥1
UV3-OPT-BR
UV3-OPT-CR
UV4-OPT-AR
UV4-OPT-BR
UV4-OPT-CR
To Recording
UV1-OPT UV1-OPT
UV2-OPT UV2-OPT
UV3-OPT UV3-OPT
UV4-OPT UV4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 181 -
6F2S1927 (0.18)
2.16.5 Setting
Setting of UV(Function ID: 470101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
BLK UVBLK Off / On - Operation canceled when UVBLK operated Off
UVBLK 10.0 V Threshold of UVBLK element 10.0
TUVBLK 10.00 S UVBLK operation delay timer 10.00
UV1-EN Off / On - UV1 protection scheme switch Off
UV2-EN Off / On - UV2 protection scheme switch Off
UV3-EN Off / On - UV3 protection scheme switch Off
UV4-EN Off / On - UV4 protection scheme switch Off
UV1 UV1-Timer DT / IDMT / Original - UV1 delay type DT
DT UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
TUV1 0.00 - 300.00 s UV1 operating delay time (in DT mode) 1.00
IDMT UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
UV1-TMS 0.010 - 100.000 - UV1 time multiplier (in IDMT mode) 1.000
TUV1R 0.0 - 300.0 s UV1 definite time reset delay 0.0
ORG UV1 5.0 - 130.0 V UV1 threshold 60.0
UV1-DPR 100 - 120 % UV1 drop-out/pick-up ratio 100
UV1-TMS 0.010 - 100.000 - UV1 time multiplier (in ORG mode) 1.000
UV1-k 0.00000 - 500.00000 - UV1 user original curve coefficient 0.00000
UV1-a 0.00000 - 10.00000 - UV1 user original curve coefficient 0.00000
UV1-c 0.00000 - 10.00000 - UV1 user original curve coefficient 0.00000
TUV1R 0.0 - 300.0 s UV1 definite time reset delay 0.0
Output UV1-VTFBlk Non / Block - UV1 operation block by VTF Non
UV1-UseFor Trip / Alarm - UV1 used for trip or alarm Trip
UV2 UV2-Timer DT / IDMT / Original - UV2 delay type DT
DT UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
TUV2 0.00 - 300.00 s UV2 operating delay time (in DT mode) 1.00
IDMT UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
UV2-TMS 0.010 - 100.000 - UV2 time multiplier (in IDMT mode) 1.000
TUV2R 0.0 - 300.0 s UV2 definite time reset delay 0.0
ORG UV2 5.0 - 130.0 V UV2 threshold 60.0
UV2-DPR 100 - 120 % UV2 drop-out/pick-up ratio 100
UV2-TMS 0.010 - 100.000 - UV2 time multiplier (in ORG mode) 1.000
UV2-k 0.00000 - 500.00000 - UV2 user original curve coefficient 0.00000
UV2-a 0.00000 - 10.00000 - UV2 user original curve coefficient 0.00000
UV2-c 0.00000 - 10.00000 - UV2 user original curve coefficient 0.00000
TUV2R 0.0 - 300.0 s UV2 definite time reset delay 0.0
Output UV2-VTFBlk Non / Block - UV2 operation block by VTF Non
UV2-UseFor Trip / Alarm - UV2 used for trip or alarm Trip
UV3 UV3-Timer DT / IDMT / Original - UV3 delay type DT
DT UV3 5.0 - 130.0 V UV3 threshold 60.0
UV3-DPR 100 - 120 % UV3 drop-out/pick-up ratio 100
TUV3 0.00 - 300.00 s UV3 operating delay time (in DT mode) 1.00
IDMT UV3 5.0 - 130.0 V UV3 threshold 60.0
UV3-DPR 100 - 120 % UV3 drop-out/pick-up ratio 100
UV3-TMS 0.010 - 100.000 - UV3 time multiplier (in IDMT mode) 1.000
TUV3R 0.0 - 300.0 s UV3 definite time reset delay 0.0
ORG UV3 5.0 - 130.0 V UV3 threshold 60.0
UV3-DPR 100 - 120 % UV3 drop-out/pick-up ratio 100
UV3-TMS 0.010 - 100.000 - UV3 time multiplier (in ORG mode) 1.000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 182 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 183 -
6F2S1927 (0.18)
2.16.6 Signal
Signal monitoring point
UV(Function ID: 470101)
Element ID Name Description
8000001BB0 CB_APH_OPEN Circuit Breaker detection (phase-A)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 184 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 185 -
6F2S1927 (0.18)
Each UVS element detects the under-voltage condition of phase-to-phase. The user can
set a threshold and the ratio of a drip-out voltage (DO) to a pick-up voltage (PU) in the UVS
element. To simplify the description, only the UVS1 element is described, but the expression
is applicable to the other elements; hence, read the expression for the UVS1 element as the
others unless a special explanation or instruction has been provided.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.17-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA ✓ NA
– Number of steps 4 4 4 NA NA 4 NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 186 -
6F2S1927 (0.18)
The inner circle shows the area in which the UVS function is blocked when the value of
the block voltage is set for [UVSBLK]. Setting [TUVSBLK] is also provided so that the user can
delay blocking the UVS1 and UVS2 elements using the setting.
Drop-off
Pickup
o V
UVS block
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 187 -
6F2S1927 (0.18)
Pick-up characteristic
The IDMT characteristic is applied when the operation of the UVS1 element is required
inversely in accordance with the level of input voltage. The IDMT characteristic curve is
illustrated in Figure 2.17-2 using a value of time multiplier is set for [UV1-TMS]. It is followed
to Equation (2.17-1) in conformed in IEC 60255-127
𝑘
t(G) = TMS × {[ 𝑎] + 𝑐} (2.17-1)
1 − (𝑉⁄𝑉 )
𝑠
where,
t = operating time (seconds),
V = energizing voltage (voltage),
Vs = pickup voltage setting (voltage),
TMS = time multiplier setting.
1000.000
100.000
Operating Time (secs)
TMS=10
10.000
TMS=5
TMS=2
TMS=1
1.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 188 -
6F2S1927 (0.18)
Drop-off characteristic
The user should set the time for resetting in the IDMT characteristic. Figure 2.17-3 shows
examples of the pick-up and the drop-off relevant to both the fault occurrences and the
operation time. The UVS1 element has a time counter that increases in response to the fault
occurrence and duration. This figure also shows the increment degree of the time counter for
the fault occurrences.
As for an intermittent fault (the former in the figure), the time counter does not reach
the trip level. In the other word, the UVS1 element will be paralyzed in the reset time
[TUVS1R].
If a series of fault occurs, the time counter increase corresponding to the duration of series
faults. When the time counter reaches the trip level, then the UVS1 element issues a trip
command after a certain delay. After issuing the trip command, if a series of fault disappears
completely, the operation of the UVS1 element is expired after the reset time [TUVS1R].
When the user requires resetting the operation of the UVS1 element immediately, setting
zero for the settings [TUVS1R] is needed. Consequently, when a voltage is recovered over the
reset threshold (drop-off), the operation of the UVS1 element is reset promptly.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 189 -
6F2S1927 (0.18)
T3
Tripping
T1 T1 T1 T1
T2 T2
Increment process in time Reset of time counter
T1: Resetting time set by the user counter
T2: Actual resetting time in the relay operation Value maintenance of time counter
T3: Time gap between fault occurrence and relay start time
Figure 2.17-3 Faults occurrences and reset operation when DT being applied
†Note:For more information about tripping, see Chapter Relay application: Trip circuit.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 190 -
6F2S1927 (0.18)
8000011B65
8000011B24 & UVS1-OPT
≥1
AB
8100011B25 &
UVS1 PU BC 8000011B23
8200011B26
& & UVS1-OPT-TRIP
CA 8000011B66
& UVS1-OPT-ALARM
≥1 8000011B61
On Trip
UVS1-EN UVS1-UseFor
Alarm
DT
IDMT
Original ≥1
UVS1-Timer
800001EBB0 UVS1_BLOCK
≥1
UVS1-VTFBlk 1
Block
&
From VTF
VTF_DETECT To UVS2, UVS3, UVS4 logics
8000011B60 VTF_DETECT
AB &
8100011B61
UVSBLK BC TUVSBLK
8200011B62
t 0 ≥1 NON UVSBLK
CA 1
0.00 to
UVSBLK-EN On 300.00s
UVS-Test On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 191 -
6F2S1927 (0.18)
UVS1-OPT-ALARM ≥1 UVS-OPT-ALARM
UVS2-OPT- ALARM
UVS3-OPT- ALARM
UVS4-OPT- ALARM
UVS-ARC-BLOCK
UVS1-OPT-AR ≥1 UVS-OPT-AR
UVS1-OPT-BR UVS-OPT-BR
UVS1-OPT-CR UVS-OPT-CR
UVS2-OPT-AR
≥1
UVS2-OPT-BR
UVS2-OPT-CR
UVS3-OPT-AR
≥1
UVS3-OPT-BR
UVS3-OPT-CR
UVS4-OPT-AR
UVS4-OPT-BR
UVS4-OPT-CR
To Recording
UVS1-OPT UVS1-OPT
UVS2-OPT UVS2-OPT
UVS3-OPT UVS3-OPT
UVS4-OPT UVS4-OPT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 192 -
6F2S1927 (0.18)
2.17.5 Setting
Setting of UVS(Function ID: 471101)
Range Default
Setting device Unit Contents Note
1A rating 5A rating 1A 5A
BLK UVSBLK-EN Off / On - Operation canceled when UVSBLK operated Off
UVSBLK 5.0 – 20.0 V Threshold of UVSBLK element 10.0
TUVBLK 0.00 – 300.00 s UVSBLK operation delay timer 10.00
UVS1-EN Off / On - UVS1 protection scheme switch Off
UVS2-EN Off / On - UVS2 protection scheme switch Off
UVS3-EN Off / On - UVS3 protection scheme switch Off
UVS4-EN Off / On - UVS4 protection scheme switch Off
UVS1 UVS1-Timer DT / IDMT / Original - UVS1 delay type DT
DT UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
TUVS1 0.00 - 300.00 s UVS1 operating delay time (in DT mode) 1.00
IDMT UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
UVS1-TMS 0.010 - 100.000 - UVS1 time multiplier (in IDMT mode) 1.000
TUVS1R 0.0 - 300.0 s UVS1 definite time reset delay 0.0
ORG UVS1 5.0 - 130.0 V UVS1 threshold 60.0
UVS1-DPR 100 - 120 % UVS1 drop-out/pick-up ratio 100
UVS1-TMS 0.010 - 100.000 - UVS1 time multiplier (in ORG mode) 1.000
UVS1-k 0.00000 - 500.00000 - UVS1 user original curve coefficient 0.00000
UVS1-a 0.00000 - 10.00000 - UVS1 user original curve coefficient 0.00000
UVS1-c 0.00000 - 10.00000 - UVS1 user original curve coefficient 0.00000
TUVS1R 0.0 - 300.0 s UVS1 definite time reset delay 0.0
Output UVS1-VTFBlk Non / Block - UVS1 operation block by VTF Non
UVS1-UseFor Trip / Alarm - UVS1 used for trip or alarm Trip
UVS2 UVS2-Timer DT / IDMT / Original - UVS2 delay type DT
DT UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
TUVS2 0.00 - 300.00 s UVS2 operating delay time (in DT mode) 1.00
IDMT UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
UVS2-TMS 0.010 - 100.000 - UVS2 time multiplier (in IDMT mode) 1.000
TUVS2R 0.0 - 300.0 s UVS2 definite time reset delay 0.0
ORG UVS2 5.0 - 130.0 V UVS2 threshold 60.0
UVS2-DPR 100 - 120 % UVS2 drop-out/pick-up ratio 100
UVS2-TMS 0.010 - 100.000 - UVS2 time multiplier (in ORG mode) 1.000
UVS2-k 0.00000 - 500.00000 - UVS2 user original curve coefficient 0.00000
UVS2-a 0.00000 - 10.00000 - UVS2 user original curve coefficient 0.00000
UVS2-c 0.00000 - 10.00000 - UVS2 user original curve coefficient 0.00000
TUVS2R 0.0 - 300.0 s UVS2 definite time reset delay 0.0
Output UVS2-VTFBlk Non / Block - UVS2 operation block by VTF Non
UVS2-UseFor Trip / Alarm - UVS2 used for trip or alarm Trip
UVS3 UVS3-Timer DT / IDMT / Original - UVS3 delay type DT
DT UVS3 5.0 - 130.0 V UVS3 threshold 60.0
UVS3-DPR 100 - 120 % UVS3 drop-out/pick-up ratio 100
TUVS3 0.00 - 300.00 s UVS3 operating delay time (in DT mode) 1.00
IDMT UVS3 5.0 - 130.0 V UVS3 threshold 60.0
UVS3-DPR 100 - 120 % UVS3 drop-out/pick-up ratio 100
UVS3-TMS 0.010 - 100.000 - UVS3 time multiplier (in IDMT mode) 1.000
TUVS3R 0.0 - 300.0 s UVS3 definite time reset delay 0.0
ORG UVS3 5.0 - 130.0 V UVS3 threshold 60.0
UVS3-DPR 100 - 120 % UVS3 drop-out/pick-up ratio 100
UVS3-TMS 0.010 - 100.000 - UVS3 time multiplier (in ORG mode) 1.000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 193 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 194 -
6F2S1927 (0.18)
2.17.6 Signal
Signal monitoring point
UVS(Function ID: 471101)
Element ID Name Description
8000001BB0 CB_APH_OPEN A phase CB open
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 195 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 196 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.18-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features NA ✓ ✓ NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 197 -
6F2S1927 (0.18)
When POP receives a trip permission signal, POP issues a trip signal on condition that
DEFCF has operated. To assure issuing a trip signal at the opposite terminal, POP continues
to send a trip permission signal for setting [TSBCT-DEF] after DEFCF stops. (Figure 2.18-2)
DEFCR is used for CRL as a revers looking element; DEFCF is used as a forward looking
element, as shown in Figure 2.18-3. When DEFCR runs but DEFCF continues to stop for 20
ms or more—even if DEFCF starts to run or DEFCR stops later—tripping CB at local terminal
or transmission of the trip permission signal is blocked for setting [TREBK-DEF].
In POP, users can delay the DEFCAR sending using settings [TDEFCF] and [TDEFCB].
Users can also delay the DEFCAR tripping using setting [TDEFC]. Thus, if users wish to carry
out the DEFCAR sending and the DEFCAR tripping separately, users should set a value for
the setting [TDEFCF] and another value for the setting [TDEFC]. For example, when 0 ms set
for the [TDEFCF] and 50 ms set for the [TDEFC], the DEFCAR sending is performed faster
than the DEFCAR tripping.
POP can provide ECHO and WKIT functions, which are used for the line having weak
infeed terminals. ECHO allows fast CB tripping at the terminal on which DEFCF has operated
when applied to the line having an open terminal or a weak infeed earth fault current terminal.
(Figure 2.18-4 to Figure 2.18-7)
When a trip permission signal is received if neither DEFCF nor DEFCR operates, ECHO
sends back the received signal to the opposite terminal. When CB is open, ECHO also sends
back the trip permission signal.
Once DEFCF or DEFCR operates, ECHO inhibits to send the echo signal for 250 ms by
delayed drop-off timer T1 even after DEFCF and DEFCR stop to operate.
In order to prevent any spurious echo signal from looping round between terminals in a
healthy state, sending ECHO signal is restricted for 200 ms by delayed pick-up timer T2. Echo
can operate using scheme switch [DEF-ECHO] On.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 198 -
6F2S1927 (0.18)
To CRL
TDEFCB 8400001B68
From EF (EF2)
t 0 DEFCR-X
DEFCR &
-CX 0.00 to 0.30s
8300001B67
≥1 DEFCF-X
From VTF
≥1 To carrier send circuit
VTF_DETECT
From PROT COMMON 1 DEFCAR-CS-A_POUP
CB_LOSS_PHASE DEFCAR-CS-B_POUP
DEFCAR-CS-C_POUP
8000001B74
& DEFCAR-OPT-AR
8100001B75
& DEFCAR-OPT-BR
8200001B76
& DEFCAR-OPT-CR
TDEFCF TDEFC 8300001B77
DEFCF t 0
0 8000001B6A DEFCAR-OPT-S
& & &
t
-CX &
From PROT-COMMON ≥1 8000001B20
& &
t 0 t 0 8100001B6B ≥1 DEFCAR-TRIP-A
OCD-AT S & & ≥1 8100001B21
& 8200001B6C
-CX R ≥1 t 0 ≥1 DEFCAR-TRIP-B
≥1 & t 0
≥1 8200001B22
OCT-BT & &
S ≥1 DEFCAR-TRIP-C
-CX 0.00 to 0.30s 0.00 to 0.30s
R ≥1 ≥1
OCT-CT S Week infeed ≥1
-CX R ≥1 ≥1 trip logic &
(WIKT)
1 ≥1 1
Current
800000EBBB EFF PHSEL-A Reversal 1
Logic ≥1
800000EBBC EFF PHSEL-B (CRL)
DEFCAR_TPMD
800000EBBD EFF PHSEL-C 3P
1P DEFCAR-TPMD=1P
8100001B77
& DEFCAR-ARC-BLOCK
Permission signals received: ≥1
From Terminal 1
DEFCAR-ARCBlk
800000EBB5 INT.DEFCAR-R1-A =1 To TRC
≥1 ≥1
& Block
810000EBB6 INT.DEFCAR-R1-B =1 ≥1 ≥1
&
820000EBB7 INT.DEFCAR-R1-C =1 ≥1 ≥1 &
EZT.DISCAR-R1 =1
From Terminal 2
DEFCAR_PERM1-A
840000EBB8 INT.DEFCAR-R2-A =1 ≥1 ≥1 DEFCAR_PERM1-B
DEFCAR_PERM1-C
850000EBB9 INT.DEFCAR-R2-B =1 ≥1 ≥1
860000EBBA INT.DEFCAR-R2-C =1 ≥1 ≥1
DEFCAR_PERM2-A
EZT.DISCAR-R2
=1 DEFCAR_PERM2-B
DEFCAR UOP
DEFCAR_PERM2-C
POP
CH2-USE 1
CAR_BLOCK
≥1
1
800000EBB0 DEFCAR_BLK
810000EBC1 DEFCAR_3PTP
800000EBC0 DEFCAR_ARCBLOCK
TSBCT-DEF
t 0
DEFCAR-OPT-A
t 0
DEFCAR-OPT-B
t 0
DEFCAR-OPT-C
0.00 to 1.00s
8000001B79
DEFCAR-CS-A_POUP ≥1 =1 INT.DEFCAR-S-A
8100001B7A
DEFCAR-CS-B_POUP ≥1 =1 INT.DEFCAR-S-B
8200001B7B
DEFCAR-CS-C_POUP INT.DEFCAR-S-C
≥1 =1
≥1
ECHO logic =1
& ≥1 &
≥1 8F00001B7C
1
DEFCAR-S
≥1 & &
800000EBC2 DEFCAR_F.BLOCK
1
810000EBC3 DEFCAR_PERMIT
DEFCAR UOP
POP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 199 -
6F2S1927 (0.18)
TREBK-DEF 8000001B69
t 0 t 0
DEFCF-X & DEF-REVBLK
≥1
-CX 1 -CX
DEFCR-X 0.02s 0.0s
-CX
0 t
UVLG-A
≥1 & WKIT-A_CONDITION
0 t
UVLG-B
≥1 & WKIT-B_CONDITION
0 t
UVLG-C
≥1 & WKIT-C_CONDITION
≥1
≥1 1
UVLS-AB
UVLS-BC TWICOORD
UVLS-CA t 0
&
DEAL_LINE_DEDTECT
1 0.000 to 0.100 s
DEFCAR_PARM1-A
& ≥1
DEFCAR_PARM1-B
& ≥1
DEFCAR_PARM1-C
&
≥1
From CARRIER-COMMON
CH2-USE 1
ECHO1_CONDITION &
DEF-WKIT On
CAR
From CARRIER-COMMON
WKIT-A_CONDITION
WKIT-B_CONDITION
WKIT-C_CONDITION
POP
≥1
UOP
DEFCAR BOP
From CARRIER_COMMON
T1
DEFCFX
≥1 0 t
1 & ECHO1_CONDITION
DEFCRX
0.25s
From PROT-COMMON
CB_ANYPH_CLOSE
TCARECCB
t 0 ECHO2_CONDITION
CB_ANYPH_OPEN
0.00 to 200.00s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 200 -
6F2S1927 (0.18)
0.05s 0.2s
8200001B6F
& DEF-ECHO_CS-C
From Terminal 2 ≥1
0 t t 0
& 1
840000EBB8 INT.DEFCAR-R2-A =1
0.05s 0.2s
850000EBB9 INT.DEFCAR-R2-B =1 &
POP
DEFCAR ≥1
UOP
ECHO1_CONDITION &
DEF-ECHO On
0 t t 0
& ≥1 1
0.05s 0.2s
≥1
&
&
& ≥1
0 t t 0
1
0.05s 0.2s
& &
0 t t 0
& 1
0.05s 0.2s
&
ECHO2_CONDITION &
The delayed pick-up timer [TCHD-DEF] is provided to allow for the transmission delay of the
trip block signal from the opposite terminal. Therefore, user should set a time depending on
the delay of communication channel.
Setting [TCHD-DEF] = maximum signal transmission delay time†+ 5ms
†Note: Including operation time of circuits of Binary IO modules; these circuits are used
to send/receive a trip blocking signal.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 201 -
6F2S1927 (0.18)
To CRL
TDEFCB 8400001B68
From EF (EF2) DEFCR-X
t 0
DEFCR &
-CX 0.00 to 0.30s
From VTF 8300001B67
≥1 ≥1 DEFCF-X
VTF_DETECT
From PROT COMMON 1
CB_LOSS_PHASE
From EF (EF1)
TDEFCF 8000001B64
DEFCF t 0 DEFCF-AX
& &
-CX
From PROT-COMMON 8100001B65
& t 0 DEFCF-BX
&
OCD-AT S
& t 0 8200001B66
-CX R ≥1 &
≥1
DEFCF-CX
OCT-BT S
-CX 0.00 to 0.30s
R ≥1 ≥1
OCT-C S
-CX R ≥1 ≥1
1 ≥1 1
8000001B74
& DEFCAR-OPT-A
8100001B75
& DEFCAR-OPT-B
8200001B76
& DEFCAR-OPT-C
TCHD-DEF TDEFC
t 0 8000001B6A
DEFCF-AX & t 0
& 8000001B20
t 0 8100001B6B ≥1
DEFCF-BX t 0 ≥1 DEFCAR-TRIP-A
& & ≥1 8100001B21
8200001B6C
DEFCF-CX t 0 ≥1 DEFCAR-TRIP-B
t 0 8200001B22
& ≥1
& ≥1 DEFCAR-TRIP-C
0.00 to 0.100s
0.00 to 0.30s
Week infeed ≥1
trip logic &
Current
Reversal 1
detection ≥1
logic
DEFCAR_TPMD
3P
1P
8100001B77
Permission signals received: ≥1 & DEFCAR-ARC-BLOCK
From Terminal 1
=1 DEFCAR-ARCBlk
800000EBB5 INT.DEFCAR-R1-A ≥1 ≥1 To TRC
& Block
850000EBB6 INT.DEFCAR-R1-B =1 ≥1 ≥1
&
820000EBB7 INT.DEFCAR-R1-C =1 ≥1 ≥1 &
800000EBB1 DEFCAR-R1 =1
From Terminal 2
DEFCAR_PERM1-A
840000EBB8 INT.DEFCAR-R2-A =1 ≥1 ≥1 DEFCAR_PERM1-B
DEFCAR_PERM1-C
850000EBB9 INT.DEFCAR-R2-B =1 ≥1 ≥1
860000EBBA INT.DEFCAR-R2-C =1 ≥1 ≥1
DEFCAR_PERM2-A
810000EBB3 DEFCAR-R2 DEFCAR_PERM2-B
=1
DEFCAR DEFCAR_PERM2-C
BOP To ECHO/EIKT
From Terminal 2
CH1-USE 1
CH2-USE
CAR_BLOCK
≥1
1
800000EBB0 DEFCAR_BLK
810000EBC1 DEFCAR_3PTP
800000EBC0 DEFCAR_ARCBLOCK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 202 -
6F2S1927 (0.18)
DEF-REVBLK
& 8000001B79
& INT.DEFCAR-S-A
& 1
8100001B7A
& INT.DEFCAR-S-B
& 1 8200001B7B
& INT.DEFCAR-S-C
1
TSBCT-DEF
t 0
DEFCAR-OPT-A
t 0
DEFCAR-OPT-B ≥1
t 0
DEFCAR-OPT-C
8F00001B7C
800000EB55 DEFCAR_F.BLOCK ≥1 &
& DEFCAR-S
810000EB56 DEFCAR_PERMIT
1
DEFCAR BOP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 203 -
6F2S1927 (0.18)
2.18.4 Setting
CARCOM(Function ID: 438001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Carrier_COM CAR-CHNUM 2-TERM / 3-TERM - Carrier scheme terminal number 2-TERM
TCARECCB 0.00 - 200.00 s Echo enable timer from CB opened 0.10
TWICOORD 0.000 - 0.100 s Time coordination for UV relay operation 0.000
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 204 -
6F2S1927 (0.18)
2.18.5 Signal
Signal monitoring point
CARRIER_COMMON (Function ID: 438001)
Element ID Name Description
8000001BB0 CAR_BLOCK Carrier block signal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 205 -
6F2S1927 (0.18)
8000001B69 DEF-REVBLK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 206 -
6F2S1927 (0.18)
8000001BB5 INT.DEFCAR-R1-A DEF carrier of A phase received from remote 1 (Integral type)
8100001BB6 INT.DEFCAR-R1-B DEF carrier of B phase received from remote 1 (Integral type)
8200001BB7 INT.DEFCAR-R1-C DEF carrier of C phase received from remote 1 (Integral type)
8400001BB8 INT.DEFCAR-R2-A DEF carrier of A phase received from remote 2 (Integral type)
8500001BB9 INT.DEFCAR-R2-B DEF carrier of B phase received from remote 2 (Integral type)
8600001BBA INT.DEFCAR-R2-C DEF carrier of C phase received from remote 2 (Integral type)
800000EBB5 INT.DEFCAR-R1-A DEF carrier of A phase received from remote 1 (Integral type)
810000EBB6 INT.DEFCAR-R1-B DEF carrier of B phase received from remote 1 (Integral type)
820000EBB7 INT.DEFCAR-R1-C DEF carrier of C phase received from remote 1 (Integral type)
840000EBB8 INT.DEFCAR-R2-A DEF carrier of A phase received from remote 2 (Integral type)
850000EBB9 INT.DEFCAR-R2-B DEF carrier of B phase received from remote 2 (Integral type)
860000EBBA INT.DEFCAR-R2-C DEF carrier of C phase received from remote 2 (Integral type)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 207 -
6F2S1927 (0.18)
To simplify the description, only stage 1 is discussed, but is applicable to the other stages;
hence, read the express for stage 1 as the other stages unless a special explanation or
instruction has been produced.
─────────────────────────────────────────────────────────────────
Note: The feature of FRQ with 6 stages is available in 3D model.. The features of FRQ 8
stages plus Rapid change detection (RCD) are available in 36, and 3E, 3F models (refer to the
succeeding section). To determine whether a particular feature has been implemented within
an IED, identify the IED ordering number; and check the order number for the “G&T position”
whilst referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.19-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.19 FRQ with 6 stages ✓ NA NA NA NA NA NA
2.20 FRQ with 8 stages plus RCD NA ✓ ✓ NA NA ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 208 -
6F2S1927 (0.18)
The user can select the stage 1 to detect either over-frequency state or under-frequency
state using scheme switch [FRQ1-Chara]. For example, If OverFrq is set for the scheme switch
[FRQ1-Chara], the stage 1 determines the over-frequency state when an over frequency is
observed (Figure 2.19-1(a)); the user can set the threshold value into [FRQ1]. Conversely, if
UnderFrq is set for the scheme switch, the stage 1 determines the under-frequency state when
an under frequency is observed (Figure 2.19-1(b)). The user can use a delay timer to postpone
to issue a trip signal using setting [TFRQ1].
Hz Hz
OF stage 1
operation zone
frequency
Pickup
frequency
Pickup
UF stage 1
operation zone
o o
V V
Pickup voltage (FRQBLK) Pickup voltage (FRQBLK)
a. Over frequency element at Stage 1 b. Under frequency element at Stage 1
Regarding the operation of the UF and OF elements, the user should notice the element
not to pick-up when the measured voltage is below the threshold value set with the [FRQBLK]
in positive sequence. Any operation of the FRQ function is blocked when an acquired voltage
is smaller than the pickup voltage to be set.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 209 -
6F2S1927 (0.18)
The under-voltage block (FRQBLK) element is used to block the FRQ operation, as
mentioned earlier (section 2.19.1(i)).
To DFRQ
8700001C23
FRQBLK
(UVBLK)
1 NON FRQBLK
8000011BB1
8000011C23 TFRQ1 8000011B60
& ≥1 t 0
OF & & 800001EBB1 FRQ-S1-OPT FRQ-S1-OPT
FRQ1 1
0.00 - 300.00s To TRC
Trip
UF & ≥1
FRQ1-UseFor
& Alarm FRQ-OPT-TRIP
OverFrq &
UnderFrq
FRQ1-Chara
FRQ-OPT-ALARM
8100021C23 8100021B60 8100021BB1
TFRQ2
& ≥1 t 0 FRQ-ARC-BLOCK
OF & & 810002EBB1 FRQ-S2-OPT FRQ-S2-OPT
FRQ2 1
0.00 - 300.00s
Trip
UF &
FRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
FRQ2-Chara
8500061BB1
8500061C23 TFRQ6 8500061B60
& ≥1 t 0
OF & & 850006EBB1 FRQ-S6-OPT FRQ-S6-OPT
FRQ6 1
0.00 - 300.00s
Trip
UF &
FRQ6-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
FRQ6-Chara
On
FRQ1-EN
On
FRQ2-EN
On
FRQ6-EN
800001EBB0 FRQ1-BLOCK 1
810002EBB0 FRQ2-BLOCK 1
850006EBB0 FRQ6-BLOCK 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 210 -
6F2S1927 (0.18)
The user can set the state 1 to detect whether a frequency to be rising or to be descending
using scheme switch [DFRQ1-Chara]. For example, when Rise is set for the scheme switch
[DFRQ1-Chara], the DFRQ examines the gradient of frequency-change (Δf/Δt) in up.
Conversely, when Down is set for the scheme switch, the DFRQ examines the gradient of
frequency-change (Δf/Δt) in down. Setting [DFREQ1] is used to configure an operation
threshold; the operation threshold is configured with Hertz per second.
The operation of the RISE/DOWN elements is blocked when the FRQBLK element runs.
That is, if an obtained voltage is below the setting [FRQBLK], any operation of the DFRQ
function is blocked. The FRQBLK element is discussed in section 2.19.1(i).
Hz
Δf
Δt
sec
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 211 -
6F2S1927 (0.18)
The signal of the under-voltage block (FRQBLK) element is provided from the FRQ logic.
From FRQ
NON FRQBLK
8000111BB1
8000111C23 8000111B60
& ≥1 & & 800011EBB1 FRQ-S1-OPT DFRQ-S1-OPT
RISE
DFRQ1 1
Trip To TRC
DOWN & ≥1
DFRQ1-UseFor
& Alarm DFRQ-OPT-TRIP
OverFrq &
UnderFrq
FFRQ1-Chara
DFRQ-OPT-ALARM
8100121C23 8100121B60 8100121BB1
& ≥1 & & 810012EBB1 FRQ-S2-OPT DFRQ-S2-OPT DFRQ-ARC-BLOCK
RISE
DFRQ2 1
Trip
DOWN &
DFRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
DFRQ2-Chara
8500161BB1
8500161C23 8500161B60
RISE & ≥1 & & 850016EBB1 FRQ-S6-OPT DFRQ-S6-OPT
DFRQ6
1
Trip
DOWN &
DFRQ6-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
DFRQ6-Chara
On
DFRQ1-EN
On
DFRQ2-EN
On
DFRQ6-EN
800011EBB0 DFRQ1-BLOCK 1
810012EBB0 DFRQ2-BLOCK 1
850016EBB0 DFRQ6-BLOCK 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 212 -
6F2S1927 (0.18)
2.19.3 Setting
FRQ(Function ID: 475001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FRQ-EN Off / On - FRQ protection enable Off
FRQ FRQBLK 40.0 - 100.0 V Threshold to cancel FRQ operations 40.0
FRQ1-EN Off / On - FRQ1 protection enable Off
FRQ2-EN Off / On - FRQ2 protection enable Off
FRQ3-EN Off / On - FRQ3 protection enable Off
FRQ4-EN Off / On - FRQ4 protection enable Off
FRQ5-EN Off / On - FRQ5 protection enable Off
FRQ6-EN Off / On - FRQ6 protection enable Off
DFRQ1-EN Off / On - DFRQ1 protection enable Off
DFRQ2-EN Off / On - DFRQ2 protection enable Off
DFRQ3-EN Off / On - DFRQ3 protection enable Off
DFRQ4-EN Off / On - DFRQ4 protection enable Off
DFRQ5-EN Off / On - DFRQ5 protection enable Off
DFRQ6-EN Off / On - DFRQ6 protection enable Off
FRQ1 FRQ1-Chara OverFrq / UnderFrq - The selection of FRQ1 character UnderFrq
FRQ1 -10.00 - 10.00 Hz FRQ1 threshold -1.00
TFRQ1 0.00 - 300.00 s FRQ1 operating delay time 1.00
Output FRQ1-UseFor Trip / Alarm - FRQ1 used for trip or alarm Trip
FRQ2 FRQ2-Chara OverFrq / UnderFrq - The selection of FRQ2 character UnderFrq
FRQ2 -10.00 - 10.00 Hz FRQ2 threshold -1.00
TFRQ2 0.00 - 300.00 s FRQ2 operating delay time 1.00
Output FRQ2-UseFor Trip / Alarm - FRQ2 used for trip or alarm Trip
FRQ3 FRQ3-Chara OverFrq / UnderFrq - The selection of FRQ3 character UnderFrq
FRQ3 -10.00 - 10.00 Hz FRQ3 threshold -1.00
TFRQ3 0.00 - 300.00 s FRQ3 operating delay time 1.00
Output FRQ3-UseFor Trip / Alarm - FRQ3 used for trip or alarm Trip
FRQ4 FRQ4-Chara OverFrq / UnderFrq - The selection of FRQ4 character UnderFrq
FRQ4 -10.00 - 10.00 Hz FRQ4 threshold -1.00
TFRQ4 0.00 - 300.00 s FRQ4 operating delay time 1.00
Output FRQ4-UseFor Trip / Alarm - FRQ4 used for trip or alarm Trip
FRQ5 FRQ5-Chara OverFrq / UnderFrq - The selection of FRQ5 character UnderFrq
FRQ5 -10.00 - 10.00 Hz FRQ5 threshold -1.00
TFRQ5 0.00 - 300.00 s FRQ5 operating delay time 1.00
Output FRQ5-UseFor Trip / Alarm - FRQ5 used for trip or alarm Trip
FRQ6 FRQ6-Chara OverFrq / UnderFrq - The selection of FRQ6 character UnderFrq
FRQ6 -10.00 - 10.00 Hz FRQ6 threshold -1.00
TFRQ6 0.00 - 300.00 s FRQ6 operating delay time 1.00
Output FRQ6-UseFor Trip / Alarm - FRQ6 used for trip or alarm Trip
DFRQ1 DFRQ1-Chara Rise / Down - The selection of DFRQ1 character Down
DFRQ1 0.1 - 15.0 Hz/s DFRQ1 threshold 0.5
Output DFRQ1-UseFor Trip / Alarm - DFRQ1 used for trip or alarm Trip
DFRQ2 DFRQ2-Chara Rise / Down - The selection of DFRQ2 character Down
DFRQ2 0.1 - 15.0 Hz/s DFRQ2 threshold 0.5
Output DFRQ2-UseFor Trip / Alarm - DFRQ2 used for trip or alarm Trip
DFRQ3 DFRQ3-Chara Rise / Down - The selection of DFRQ3 character Down
DFRQ3 0.1 - 15.0 Hz/s DFRQ3 threshold 0.5
Output DFRQ3-UseFor Trip / Alarm - DFRQ3 used for trip or alarm Trip
DFRQ4 DFRQ4-Chara Rise / Down - The selection of DFRQ4 character Down
DFRQ4 0.1 - 15.0 Hz/s DFRQ4 threshold 0.5
Output DFRQ4-UseFor Trip / Alarm - DFRQ4 used for trip or alarm Trip
DFRQ5 DFRQ5-Chara Rise / Down - The selection of DFRQ5 character Down
DFRQ5 0.1 - 15.0 Hz/s DFRQ5 threshold 0.5
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 213 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 214 -
6F2S1927 (0.18)
2.19.4 Signal
Signal monitoring point
FRQ(Function ID: 475001)
Element ID Name Description
8400101B61 DFRQ-OPT-ALARM Alarm signal by DFRQ protection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 215 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 216 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 217 -
6F2S1927 (0.18)
This FRQ function also has rapid change detection (RCD) so that the user can block
excessive FRQ operation when an out of step phenomena occurs.
To simplify the FRQ/DFRQ descriptions, only stage 1 is discussed, but is applicable to the
other stages; hence, read the express for stage 1 as the other stages unless a special
explanation or instruction has been produced.
─────────────────────────────────────────────────────────────────
Note: The ‘FRQ/DFRQ with 8 stages’ feature is only available in 36, and 3E, 3F models.
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.20 FRQ with 8 stages plus RCD NA ✓ ✓ NA NA ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 218 -
6F2S1927 (0.18)
The user can select the stage 1 to detect either over-frequency state or under-frequency
state using scheme switch [FRQ1-Chara]. For example, If OverFrq is set for the scheme switch
[FRQ1-Chara], the stage 1 determines the over-frequency state when an over frequency is
observed (Figure 2.20-1 (a)); the user can set the threshold value into [FRQ1]. Conversely, if
UnderFrq is set for the scheme switch, the stage 1 determines the under-frequency state when
an under frequency is observed (Figure 2.20-1 (b)). The user can use a delay timer to postpone
to issue a trip signal using setting [TFRQ1].
Hz Hz
OF stage 1
operation zone
frequency
Pickup
frequency
Pickup
UF stage 1
operation zone
o o
V V
Pickup voltage (FRQUVBLK) Pickup voltage (FRQUVBLK)
a. Over frequency element at Stage 1 b. Under frequency element at Stage 1
Regarding the operation of the UF and OF elements, the user should notice the element
not to pick-up when the measured voltage is below the threshold value set with the
[FRQUVBLK] in positive sequence. Any operation of the FRQ function is blocked when an
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 219 -
6F2S1927 (0.18)
The under-voltage block (FRQUVBLK) element is used to block the FRQ operation, as
mentioned earlier (section 2.20.1(i)).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 220 -
6F2S1927 (0.18)
To DFRQ
8700001C23
FRQUVBLK
(UVBLK)
1 NON FRQBLK
8000011BB1
8000011C23 TFRQ1 8000011B60
& ≥1 t 0
OF & & 800001EBB1 FRQ-S1-OPT FRQ-S1-OPT
FRQ1 1
0.00 - 300.00s To TRC
Trip
UF & ≥1
FRQ1-UseFor
& Alarm FRQ-OPT-TRIP
OverFrq &
UnderFrq
FRQ1-Chara
FRQ-OPT-ALARM
8000021C23 8100021B60 8100021BB1
TFRQ2
& ≥1 t 0 FRQ-ARC-BLOCK
OF & & 810002EBB1 FRQ-S2-OPT FRQ-S2-OPT
FRQ2 1
0.00 - 300.00s
Trip
UF &
FRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
FRQ2-Chara
8700081BB1
8700061C23 TFRQ8 8700061B60
& ≥1 t 0
OF & & 8700081BB1 FRQ-S8-OPT FRQ-S8-OPT
FRQ8 1
0.00 - 300.00s
Trip
UF &
FRQ8-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
FRQ8-Chara
On
FRQ1-EN
On
FRQ2-EN
On
FRQ8-EN
800001EBB0 FRQ1-BLOCK 1
810002EBB0 FRQ2-BLOCK 1
870008EBB0 FRQ8-BLOCK 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 221 -
6F2S1927 (0.18)
The user can set the state 1 to detect whether a frequency to be rising or to be descending
using scheme switch [DFRQ1-Chara]. For example, when Rise is set for the scheme switch
[DFRQ1-Chara], the DFRQ examines the gradient of frequency-change (Δf/Δt) in up.
Conversely, when Down is set for the scheme switch, the DFRQ examines the gradient of
frequency-change (Δf/Δt) in down. Setting [DFREQ1] is used to configure an operation
threshold; the operation threshold is configured with Hertz per second.
The operation of the RISE/DOWN elements is blocked when the FRQBLK element runs.
That is, if an obtained voltage is below the setting [FRQBLK], any operation of the DFRQ
function is blocked. The FRQBLK element is discussed in section 2.20.1(i).
Hz
Δf
Δt
sec
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 222 -
6F2S1927 (0.18)
scheme switch [DFRQ1-UseFor]. However, when an alarm signal is required in place of the
trip signal, the user should set Alarm for scheme switch [DFRQ1-UseFor]. The TRC function
is discussed separately. (See Chapter Relay application: Trip circuit)
The signal of the under-voltage block (FRQBLK) element is provided from the FRQ logic.
From FRQ
NON FRQBLK
8000111BB1
8000111C23 8000111B60
& ≥1 & & 800011EBB1 FRQ-S1-OPT DFRQ-S1-OPT
RISE
DFRQ1 1
Trip To TRC
DOWN & ≥1
DFRQ1-UseFor
& Alarm DFRQ-OPT-TRIP
OverFrq &
UnderFrq
FFRQ1-Chara
DFRQ-OPT-ALARM
8100121C23 8100121B60 8100121BB1
& ≥1 & & 810012EBB1 FRQ-S2-OPT DFRQ-S2-OPT DFRQ-ARC-BLOCK
RISE
DFRQ2 1
Trip
DOWN &
DFRQ2-UseFor
& Alarm
OverFrq &
UnderFrq
DFRQ2-Chara
8700181BB1
8700181C23 8700181B60
RISE & ≥1 & & 870018EBB1 FRQ-S8-OPT DFRQ-S8-OPT
DFRQ8
1
Trip
DOWN &
DFRQ8-UseFor
& Alarm
OverFrq & ≥1
UnderFrq
DFRQ8-Chara
On
DFRQ1-EN
On
DFRQ2-EN
On
DFRQ8-EN
800011EBB0 DFRQ1-BLOCK 1
810012EBB0 DFRQ2-BLOCK 1
870018EBB0 DFRQ8-BLOCK 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 223 -
6F2S1927 (0.18)
Figure 2.20-5 illustrates that ‘Over loading due for Power shedding’ is not steeper than
the decline of ‘Out of step’ or ‘Loss of synchronism’ (see also Figure 2.20-6). Therefore, with the
RCD and PLC programing, the user can program such that the FRQ function only issues a trip
signal for ‘Over loading or Power shedding’. For your information, the RDC function is designed
not to operate when the FRQ has experiencing changing phase angle rapidly.
Lapse time (sec)
Δf/Δt=0.5Hz/0.2sec
1.0 =2.5Hz/s
Expecting time in
Power shedding
at 40%
0.1
Figure 2.20-5 Lapse time (Δt) and Power shedding (%) for Δf change
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 224 -
6F2S1927 (0.18)
x=1 x=0
F(x=0.8) F(x=0.6) F(x=0.4) F(x=0.2)
t t t t
Tendency Tendency
Downing frequency Rising frequency
f0 – 1.0
f0 – 1.5
f0 – 2.0
f0 – 2.5
f0 – 3.0
f0 – 3.5
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
time (sec)
For the operation for the FRQ1, for example, the user should program to inject the block
signal to the connection point “FRQ1-BLOCK” (see Figure 2.20-2); set On for the [FRQ-RCD-
EN]. Similar approaches are also required for the other FRQ2–8 schemes.
Note: In the under-frequency phenomenon, blocking is not carried out if phase angle
changes rapidly. The FRQ trip can be permitted only for rapid phase angle change.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 225 -
6F2S1927 (0.18)
8000211C2E 8000221C27
OF & ≥1 1
FRQ
-RCD-
8100211C2F
AR UF
&
On
FRQ-RCD-EN
f0 + 1.0 Setting[FRQ-RCD-AR-OF]
f0 + 0.5
Nominal (f0)
f0 – 0.5
f0 – 1.0 Setting[FRQ-RCD-AR-UF]
f0 – 1.5
f0 – 2.0
f0 – 2.5
Time (sec)
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(1) RCD: RCD element (Δf/Δt) is to monitor the change ratio of the frequency to the
time; the detection is regulated with setting [FRQ-RCD] (Hz/s). If the
frequency (f0) is changed rapidly rather than the [FRQ-RCD], ‘FRQ-RC’
signal will be generated. The ‘FRQ-RC’ signal will be generated for both
raising and downing.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 226 -
6F2S1927 (0.18)
change; the signal is reset when the frequency comes back from the active
rage.
f0 – 0.5
f0 – 1.0
f0 – 1.5
f0 – 2.0
f0 – 2.5
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Time (sec)
f0 – 0.5
f0 – 1.0
f0 – 1.5
f0 – 2.0
f0 – 2.5
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Time (sec)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 227 -
6F2S1927 (0.18)
Setting [FRQ-RCD]: Figure 2.20-11 examples another example when the [FRQ-
RCD] has 20 Hz/s setting. The ‘FRQ-RC’ signal will be generated during the ‘Loss
of synchronism’, when the Δf/Δt is larger or more than the setting.
Frequency(Hz)
f0 + 3.0
Downing(Δf/Δt=20Hz/s) Rising(Δf/Δt=20Hz/s)
f0 + 2.5
f0 + 2.0
f0 + 1.5
f0 + 1.0
f0 + 0.5
Nominal (f0)
f0 – 0.5
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Time (sec)
f0 + 2.5
f0 + 2.0
f0 + 1.5
f0 + 1.0
f0 + 0.5
Nominal (f0)
[FRQ-RCD-AR-OF]=+0.5Hz
f0 – 0.5
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Time (sec)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 228 -
6F2S1927 (0.18)
2.20.4 Setting
FRQ(Function ID:475101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FRQ-EN Off / On - FRQ protection enable Off
FRQ FRQUVBLK 40.0 - 100.0 V Voltage level of FRQ protection blocking 40.0
FRQ1-EN Off / On - FRQ1 protection enable Off
FRQ2-EN Off / On - FRQ2 protection enable Off
FRQ3-EN Off / On - FRQ3 protection enable Off
FRQ4-EN Off / On - FRQ4 protection enable Off
FRQ5-EN Off / On - FRQ5 protection enable Off
FRQ6-EN Off / On - FRQ6 protection enable Off
FRQ7-EN Off / On - FRQ7 protection enable Off
FRQ8-EN Off / On - FRQ8 protection enable Off
DFRQ1-EN Off / On - DFRQ1 protection enable Off
DFRQ2-EN Off / On - DFRQ2 protection enable Off
DFRQ3-EN Off / On - DFRQ3 protection enable Off
DFRQ4-EN Off / On - DFRQ4 protection enable Off
DFRQ5-EN Off / On - DFRQ5 protection enable Off
DFRQ6-EN Off / On - DFRQ6 protection enable Off
DFRQ7-EN Off / On - DFRQ7 protection enable Off
DFRQ8-EN Off / On - DFRQ8 protection enable Off
FRQ-RCD-EN Off / On - FRQ Rapid Change Detector Scheme enable Off
FRQ1 FRQ1-Chara OverFrq / UnderFrq - The selection of FRQ1 character UnderFrq
FRQ1 -10.00 - 10.00 Hz FRQ1 threshold -1.00
TFRQ1 0.00 - 300.00 s FRQ1 operating delay time 1.00
Output FRQ1-UseFor Trip / Alarm - FRQ1 used for trip or alarm Trip
FRQ2 FRQ2-Chara OverFrq / UnderFrq - The selection of FRQ2 character UnderFrq
FRQ2 -10.00 - 10.00 Hz FRQ2 threshold -1.00
TFRQ2 0.00 - 300.00 s FRQ2 operating delay time 1.00
Output FRQ2-UseFor Trip / Alarm - FRQ2 used for trip or alarm Trip
FRQ3 FRQ3-Chara OverFrq / UnderFrq - The selection of FRQ3 character UnderFrq
FRQ3 -10.00 - 10.00 Hz FRQ3 threshold -1.00
TFRQ3 0.00 - 300.00 s FRQ3 operating delay time 1.00
Output FRQ3-UseFor Trip / Alarm - FRQ3 used for trip or alarm Trip
FRQ4 FRQ4-Chara OverFrq / UnderFrq - The selection of FRQ4 character UnderFrq
FRQ4 -10.00 - 10.00 Hz FRQ4 threshold -1.00
TFRQ4 0.00 - 300.00 s FRQ4 operating delay time 1.00
Output FRQ4-UseFor Trip / Alarm - FRQ4 used for trip or alarm Trip
FRQ5 FRQ5-Chara OverFrq / UnderFrq - The selection of FRQ5 character UnderFrq
FRQ5 -10.00 - 10.00 Hz FRQ5 threshold -1.00
TFRQ5 0.00 - 300.00 s FRQ5 operating delay time 1.00
Output FRQ5-UseFor Trip / Alarm - FRQ5 used for trip or alarm Trip
FRQ6 FRQ6-Chara OverFrq / UnderFrq - The selection of FRQ6 character UnderFrq
FRQ6 -10.00 - 10.00 Hz FRQ6 threshold -1.00
TFRQ6 0.00 - 300.00 s FRQ6 operating delay time 1.00
Output FRQ6-UseFor Trip / Alarm - FRQ6 used for trip or alarm Trip
FRQ7 FRQ7-Chara OverFrq / UnderFrq - The selection of FRQ7 character UnderFrq
FRQ7 -10.00 - 10.00 Hz FRQ7 threshold -1.00
TFRQ7 0.00 - 300.00 s FRQ7 operating delay time 1.00
Output FRQ7-UseFor Trip / Alarm - FRQ7 used for trip or alarm Trip
FRQ8 FRQ8-Chara OverFrq / UnderFrq - The selection of FRQ8 character UnderFrq
FRQ8 -10.00 - 10.00 Hz FRQ8 threshold -1.00
TFRQ8 0.00 - 300.00 s FRQ8 operating delay time 1.00
Output FRQ8-UseFor Trip / Alarm - FRQ8 used for trip or alarm Trip
DFRQ1 DFRQ1-Chara Rise / Down - The selection of DFRQ1 character Down
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 229 -
6F2S1927 (0.18)
FRQ(Function ID:475101)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
DFRQ1 0.1 - 15.0 Hz/s DFRQ1 threshold 0.5
Output DFRQ1-UseFor Trip / Alarm - DFRQ1 used for trip or alarm Trip
DFRQ2 DFRQ2-Chara Rise / Down - The selection of DFRQ2 character Down
DFRQ2 0.1 - 15.0 Hz/s DFRQ2 threshold 0.5
Output DFRQ2-UseFor Trip / Alarm - DFRQ2 used for trip or alarm Trip
DFRQ3 DFRQ3-Chara Rise / Down - The selection of DFRQ3 character Down
DFRQ3 0.1 - 15.0 Hz/s DFRQ3 threshold 0.5
Output DFRQ3-UseFor Trip / Alarm - DFRQ3 used for trip or alarm Trip
DFRQ4 DFRQ4-Chara Rise / Down - The selection of DFRQ4 character Down
DFRQ4 0.1 - 15.0 Hz/s DFRQ4 threshold 0.5
Output DFRQ4-UseFor Trip / Alarm - DFRQ4 used for trip or alarm Trip
DFRQ5 DFRQ5-Chara Rise / Down - The selection of DFRQ5 character Down
DFRQ5 0.1 - 15.0 Hz/s DFRQ5 threshold 0.5
Output DFRQ5-UseFor Trip / Alarm - DFRQ5 used for trip or alarm Trip
DFRQ6 DFRQ6-Chara Rise / Down - The selection of DFRQ6 character Down
DFRQ6 0.1 - 15.0 Hz/s DFRQ6 threshold 0.5
Output DFRQ6-UseFor Trip / Alarm - DFRQ6 used for trip or alarm Trip
DFRQ7 DFRQ7-Chara Rise / Down - The selection of DFRQ7 character Down
DFRQ7 0.1 - 15.0 Hz/s DFRQ7 threshold 0.5
Output DFRQ7-UseFor Trip / Alarm - DFRQ7 used for trip or alarm Trip
DFRQ8 DFRQ8-Chara Rise / Down - The selection of DFRQ8 character Down
DFRQ8 0.1 - 15.0 Hz/s DFRQ8 threshold 0.5
Output DFRQ8-UseFor Trip / Alarm - DFRQ8 used for trip or alarm Trip
RCD FRQ-RCD 5.0 - 30.0 Hz/s FRQ Rapid Change Detector 20.0
FRQ-RCD-AR- FRQ Rapid Change Detector Active Area For
0.00 - 10.00 Hz 1.00
OF OF
FRQ-RCD-AR- FRQ Rapid Change Detector Active Area For
-10.00 - 0.00 Hz -1.00
UF UF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 230 -
6F2S1927 (0.18)
2.20.5 Signal
Signal monitoring point
FRQ(Function ID: 475101)
Element ID Name Description
8000211C23 FRQ-RCD Rapid change detector operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 231 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 232 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 233 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 234 -
6F2S1927 (0.18)
In the OCV function one of two features is selected during the operation: (1) the voltage
controlled OCV and (2) the voltage restraint OCV. The OCV function works as (1) when an
input voltage is lower than the OCV setting, whereas the sensitivity of the OCV function is
adjusted proportionally in response to an input voltage when the OCV function works as (2).
The user can set an operating value using the OCV setting; the value can be chosen from 20%
to 100% of the input voltage.
The OCV function consists of four stages (i.e., OCV1 element to OCV4 element). For
simplicity, the OCV1 element is discussed, but the other elements are identical to the OCV1
element.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.21-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA NA NA
– Number of steps 4 4 4 NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 235 -
6F2S1927 (0.18)
The user can set the threshold value of the non-directional OC element for stage 1 using
setting [OCV1-I]. Nondir is set for the scheme switch [OCV1-Dir].
Reference voltage or
θ Polarizing voltage (Vpol)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 236 -
6F2S1927 (0.18)
The OCV element reset time delay characteristic will be either dependent time reset or
definite time reset.
The user can select which characteristic will be applied to each stage of the OCV element
by setting a scheme switch that will be explained later in this section.
With inverse time operation, provided that the fault current has the magnitude required
to enable the determination of the location of the fault and provided that the fluctuation in the
impedance of the power source does not affect the correct determination, an inverse time OCV
function provides an effective protection. With regard to the inverse time characteristic, for
example, the function can provide a fast trip for close-in faults, but will enable a delayed trip
for remote faults. The characteristic curve of the inverse time element can be selected from
among 10 characteristic curves† in conformance with IEC, IEEE, US, and UK standards.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 237 -
6F2S1927 (0.18)
With dependent time resetting selected, if during the resetting period the energizing
current exceeds the threshold current of the OCV element, then the OCV element will pick-up.
The OCV element will reset later in a period determined by the characteristics of dependent
time resetting. In other words, the user can choose the behavior of the OCV element for either
faults that are repetitive intermittent or faults that occur in rapid succession. The
characteristic for dependent time resetting is selectable from five dependent time
characteristics in conformance with IEEE and US standards.
When definite time resetting is selected with the operation of the inverse time OCV
selection and the reset time set to zero (instantaneous), no intentional delay is added for the
resetting: that is, when the energizing current falls below the reset threshold of the OCV
element, the OCV element returns to its reset condition. If a value is set to the reset time in
seconds, the resetting of the OCV element is delayed by the reset time.
The operating time of the definite time OCV element is set depending on the distance
from the power source and should be set shorter for relays furthest from the power source.
Definite time OCV protection provides selectivity dependent on the difference between relay
operating times. It is limited to use in networks with a power source at one side only i.e. in
radial networks. The threshold values can be set identically at each terminal, but preferably,
the threshold value is reduced, little-by-little to provide a margin in terms of the current
sensitivity of the OCV element. Moreover, a higher sensitivity of threshold current is required
for a protective relay that is located remote from the power source, that is, the threshold of the
definite time OCV element is required to be lower than the ordinary threshold.
The operate time of the definite time OCV element is constant irrespective of the
magnitude of the fault current and the threshold level of operation of the definite time OCV
element with an on-delay timer provides a selective protection. As a result, the circuit breaker
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 238 -
6F2S1927 (0.18)
(CB) at the remote terminal far from the power source can be tripped in the shortest time. The
on-delay timer, which generates a delay in starting the operation of the OCV element, provides
a time grading margin (Tc); Tc is discussed later.
Definite time resetting as well as the on-delay starting setting of the definite time OCV
element is provided. The operate time for the on-delay timer for starting and for the resetting
time is set using the OCV element settings.
The reset time of the dependent time delay OCV element is user selectable; the reset time
options are dependent time reset characteristics or definite time reset characteristic. For
dependent time reset, the user can choose the reset time for the preset characteristic from six
characteristic curves; i.e. IEEE and US standard five pre-installed characteristic curves and
one user original characteristic curve where the user can set the equation parameters. The
dependent time reset characteristic curve equation and parameters will be explained in section
(vi). The definite time reset characteristic ones will be explained in section (vii).
The nine pre-programmed standard characteristic curves are defined in Table 2.21-3. In
addition, one original (user-programmable) curve can be applied. One curve can be chosen for
each OCV stage. Figure 2.21-2 illustrates these characteristic curves. For example, the user
should set one of the following scheme switches to [OCV1-Timer]. The scheme switches are
“IEC-NI" for IEC Normal Inverse characteristic, “IEC-VI” for IEC Very inverse, “IEC-EI” for IEC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 239 -
6F2S1927 (0.18)
Extremely Inverse, “UK-LTI” for UK Long Time Inverse, “IEEE-MI” for IEEE Moderately
Inverse, “IEEE-VI” for IEEE Very Inverse, “IEEE-EI” for IEEE Extremely Inverse, “US-CO8” for
US CO8 Inverse, “US-CO2” for US CO2 Short Time Inverse and “Original” for user-
programmable characteristic.
A time multiplier (TMS) setting is required for the inverse time delay and the value of
TMS can be set for the required operate time. The value of TMS is set for a characteristic: for
example, the user can set TMS in the OCV1 element according to the IEC standard using the
scheme switch [OCV1-TMS-IEC]; the default value for the TMS is 1.00. The other TMSs for the
OC1 element are also set using the scheme switches [OCV1-TMS-UK], [OCV1-TMS-IEEE],
[OCV1-TMS-US] and [OCV1-TMS-ORG].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 240 -
6F2S1927 (0.18)
Time characteristic
The user should set scheme switches [OCV1-Timer] DT (Definite Time) to select the
independent time characteristic. The value of the required operate time is set using the setting
TOCV1 in the range 0.00–300.00s.
Instantaneous activation
The operate time of the instantaneous characteristic is achieved by setting the independent
time setting to zero as described above.
kr
𝑡𝑟𝑒 = RTMS × [ β
] (2.21-1)
1 − (𝐼⁄𝐼 )
𝑠
where,
tre = time required for the element to reset fully after complete operation (seconds)
I = energizing current (amperes)
Is = threshold setting (amperes)
RTMS = time multiplier setting for resetting
kr = time required to reset fully after complete operation when the energizing current is
zero (seconds)
β = constants defining curve
For setting RTMS for the IEEE standard, the user can use setting [OCV1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [OCV1-RTMS-US] and [OCV1-
RTMS-ORG] are provided for the US standard and the original, respectively (for more
information w.r.t the values for kr and β, see Table 2.21-4; Figure 2.21-3 shows the
characteristic curves.)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 241 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 242 -
6F2S1927 (0.18)
Figure 2.21-4 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OCV1-I], will make an integrating value, which can determine how the element operates. If
the energized quantity (I) falls below the threshold setting [OCV1-I], the element operation
will return to its reset stage after the time t(I) calculated in Equation (2.21-1).
Time
Energizing current
Energizing current
cleared by tripping
Measuring quantity 0A
Inverse-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEP
Integrator
Trip signal
Definite-time-reset characteristic
Stage to element
return
Setting
[*-Rtimer]=DEF
Integrator
Trip signal
Reset time
Integration will be kept in timer [TOCV1R].
The integration will start again when the energizing current The integration will be reset when the energizing current
becomes larger than [OCV1-I] within [TOCV1R]. does not become larger than [OCV1-I] in [TOCV1R].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 243 -
6F2S1927 (0.18)
Operating Zone
OCV-I
V
OCV-V times 1.05
For k
𝑡𝑜𝑝 = TMS × {[ α ] + 𝑐} (2.21-2)
operation (𝐼⁄𝐼 × 𝑉 ) − 1
𝑠 𝑟𝑒𝑠
For kr
𝑡𝑟𝑒 = RTMS × [ β
] (2.21-3)
resetting 1 − (𝐼⁄𝐼 × 𝑉 )
𝑠 𝑟𝑒𝑠
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 244 -
6F2S1927 (0.18)
where:
top = operate time with constant current I (seconds)
tre = reset time with constant current I (seconds)
I = operate (energizing) current (amperes)
Is = overcurrent setting (amperes); set by [OCV1-I]
Vs= voltage setting; set by [OCV1-V]
TMS = time multiplier setting number
k, α, c = constants defining curve
Vres = calculated in accordance with the ratio “V/Vs” and “Is”. That is,
1 ≤ V/Vs: Vres = Is × 1.00
0.2 ≤ V/Vs ≤ 1: Vres = Is × ratio “V/Vs”
V/Vs ≤ 0.2: Vres = Is × 0.2
OCV-I
OCV-I×1.0
Operating Zone
OCV-I×0.2
OCV-V/V
0.2 1.0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 245 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 246 -
6F2S1927 (0.18)
8000011C20
To Grouping logic
A & &
8100011C21 &
OCV1 &
B & OCV1-OPT-A
&
8200011C22 &
&
C & & OCV1-OPT-B
&
&
8000011C24 OCV1-OPT-C
≥1
A & & & ≥1
8100011C25 &
OCV1 PU B & & &
8200011C26
&
C & & & 8000011B68
≥1
& & OCV1-OPT
&
From ICD
ICD-A &
& ≥1 OCV1-OPT-TRIP
3POR
ICD-B OCV1-OPMD
&
& ≥1 2OUTOF3 OCV1-OPT-ALARM
Block-3P
OCV1-2PBlk
Block-PerP OCV1-PU-AR
Controlled OCV1-PU-BR
OCV1-EN ≥1
Restraint
OCV1-PU-CR
From VTF
VTF_DETECT
&
OCV1-VTFBlk
Block ≥1
800001EBB4 OCV1_BLOCK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 247 -
6F2S1927 (0.18)
OCV1-OPT-ALARM ≥1 OCV-OPT-ALARM
OCV2-OPT- ALARM
OCV3-OPT- ALARM
OCV4-OPT- ALARM
OCV1-ARC-BLOCK ≥1 OCV-ARC-BLOCK
OCV2- ARC-BLOCK
OCV3- ARC-BLOCK
OCV4- ARC-BLOCK
OCV1-PU-AR ≥1 ≥1 OCV-OPT-AR
OCV1-PU-BR ≥1
OCV-OPT-BR
OCV1-PU-CR ≥1
OCV-OPT-CR
OCV1-OPT
OCV2-PU-AR ≥1
≥1
OCV2-PU-BR ≥1
OCV2-PU-CR ≥1
OCV2-OPT
OCV3-PU-AR ≥1
≥1
OCV3-PU-BR ≥1
OCV3-PU-CR ≥1
OCV3-OPT
OCV4-PU-AR ≥1
OCV4-PU-BR ≥1
OCV4-PU-CR ≥1
To Recording
OCV4-OPT
OCV1-OPT-AR
OCV1-OPT-BR
OCV1-OPT-CR
OCV2-OPT-AR
OCV2-OPT-BR
OCV2-OPT-CR
OCV3-OPT-AR
OCV3-OPT-BR
OCV3-OPT-CR
OCV4-OPT-AR
OCV4-OPT-BR
OCV4-OPT-CR
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 248 -
6F2S1927 (0.18)
2.21.7 Setting
OCV (Function ID: 444001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Off / Controlled /
OCV1-EN - OCV1 protection switch Off
Restraint
Off / Controlled /
OCV2-EN - OCV2 protection switch Off
Restraint
Off / Controlled /
OCV3-EN - OCV3 protection switch Off
Restraint
Off / Controlled /
OCV4-EN - OCV4 protection switch Off
Restraint
OCV1 FWD NonDir / Forward /
OCV1-Dir - OCV1 directional characteristic NonDir
REV Reverse
OCV1-Angle 0 - 180 deg OCV1 directional characteristic angle 45
IEC-NI / IEC-VI / IEC-
EI / UK-LTI / IEEE-
OCV1-Timer MI / IEEE-VI / IEEE- - OCV1 delay type IEC-NI
EI / US-CO2 / US-CO8
/ Original
IEC 0.02 - 0.10 -
OCV1-I A OCV1 I threshold 1.00 5.00
5.00 25.00
OCV1-V 10.0 - 220.0 V OCV1 V threshold 70.0
OCV1-TMS-
0.010 - 50.000 - OCV1 time multiplier of IEC inverse curve 1.000
IEC
TOCV1R 0.00 - 300.00 s OCV1 definite time reset delay 0.00
UK 0.02 - 0.10 -
OCV1-I A OCV1 I threshold 1.00 5.00
5.00 25.00
OCV1-V 10.0 - 220.0 V OCV1 V threshold 70.0
OCV1-TMS-UK 0.010 - 50.000 - OCV1 time multiplier of UK inverse curve 1.000
TOCV1R 0.00 - 300.00 s OCV1 definite time reset delay 0.00
IEEE 0.02 - 0.10 -
OCV1-I A OCV1 I threshold 1.00 5.00
5.00 25.00
OCV1-V 10.0 - 220.0 V OCV1 V threshold 70.0
OCV1-TMS-
0.010 - 50.000 - OCV1 time multiplier of IEEE inverse curve 1.000
IEEE
OCV1-Rtimer DEF / DEP - OCV1 reset delay type of IEEE DEF
TOCV1R 0.00 - 300.00 s OCV1 definite time reset delay 0.00
OCV1-RTMS- OCV1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
IEEE IEEE inverse curve
US 0.02 - 0.10 -
OCV1-I A OCV1 I threshold 1.00 5.00
5.00 25.00
OCV1-V 10.0 - 220.0 V OCV1 V threshold 70.0
OCV1-TMS-US 0.010 - 50.000 - OCV1 time multiplier of US inverse curve 1.000
OCV1-Rtimer DEF / DEP - OCV1 reset delay type of US DEF
TOCV1R 0.00 - 300.00 s OCV1 definite time reset delay 0.00
OCV1-RTMS- OCV1 dependent reset time multiplier of US
0.010 - 50.000 - 1.000
US inverse curve
ORG 0.02 - 0.10 -
OCV1-I A OCV1 I threshold 1.00 5.00
5.00 25.00
OCV1-V 10.0 - 220.0 V OCV1 V threshold 70.0
OCV1-TMS- OCV1 time multiplier of Original inverse
0.010 - 50.000 - 1.000
ORG curve
OCV1-Rtimer DEF / DEP - OCV1 reset delay type of IEEE DEF
TOCV1R 0.00 - 300.00 s OCV1 definite time reset delay 0.00
OCV1-RTMS- OCV1 dependent reset time multiplier of
0.010 - 50.000 - 1.000
ORG Original inverse curve
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 249 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 250 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 251 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 252 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 253 -
6F2S1927 (0.18)
2.21.8 Signal
Signal monitoring points
OCV(Function ID: 444001)
Element ID Name Description
8500001B62 OCV-ARC-BLOCK Autoreclose block signal by OCV protection operation
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 254 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 255 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 256 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.22-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 257 -
6F2S1927 (0.18)
The accuracy† of the FL calculation is influenced by both the line impedance (Z) and the
fault current (If). Thus, the user should note that the FL computation maintains an accuracy
of better than ± 2.5 km (1.6 mile) for the distance GF shown in Figure 1.1-1 for up to 100km
(62 mile)‡ of the length of the line regardless of the setting of the length of the line GH ( 0 to
500 km (310 mile)). The accuracy of the FL calculation is better than ± 2.5% when the fault is
located 100 km to 500 km from the FL function, provided that the length of the line GH is
between 100 km to 500 km.
The FL calculation runs separately for phase-to-phase faults and earth-faults. Hence, the
selection of algorithm depends upon the type of fault that occurs.
†Note: Both line impedance and rated-current affect the accuracy of the FL computation.
If the VCT is set for 1 ampere rated-current operation, the accuracy of the FL
computation can be maintained provided that the ratio of the reactance of the
series-impedance per unit-length is greater than 0.05, provided that the fault
current that flows is greater than 2 ampere on the secondary side of the CT
circuit. For the VCT being set for 5 ampere rated-current, the same FL accuracy
can be kept when the ratio of the reactance of the series-impedance per-unit-
length is greater than 0.01, provided that the fault current that flows is greater
than 10 ampere. For more information on the rated-current of the VCT, see
chapter Technical description: Transformer module.
‡Note:In order to maintain the accuracy of the FL computation, the user can use
compensation factors when unbalanced impedances are occurred in the
transmission line. (2.66.1.0)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 258 -
6F2S1927 (0.18)
Line GH
t
Distance GF
TT
t
Bus G If Bus H
Line 1
Fault F TT
FL TT t IL
t t
Source Load/Source
Line 2
G’ TT H’
t
Figure 2.22-1 Relationship between fault location and local IED in parallel line
2Ia − Ib – Ic
Iα = (2.22-1)
3
(2.22-3)
where,
Vα: Fault voltage (=Va0)
Iα: Fault current
Iα’: Current change before and after fault occurrence
Iα”: Complex conjugate of Iα’
Ia,Ib,Ic: Fault currents in phase-‘a’, phase-‘b’, and phase-‘c’
ILa,ILb,ILc: Load currents in phase-‘a’, phase-‘b’, and phase-‘c’
I0s: Zero-sequence current on the local line i.e. ‘Line 1’
R 1: Resistance component of positive-sequence self-impedance (Z1), [FL_R1]
X1: Reactance component of positive-sequence self-impedance (Z1), [FL_X1]
R 0: Resistance component of zero-sequence self-impedance (Z0), [FL_R0]
X0: Reactance component of zero-sequence self-impedance (Z0), [FL_X0]
Ka: Compensation factor for phase-‘a’ in an unbalanced 3-phase line,
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 259 -
6F2S1927 (0.18)
[FL_Ka]
Im(): Imaginary part when a value is placed in parentheses
Re(): Real part when a value is placed in parentheses
L: Length of line GH in kilometers or miles, [FL_line_km] / [FL_line_mile]
•: Symbol of Vector product
Equation (2.22-3) is used generally when the transmission lines are treated as having
lumped constants. The user should consider the influence of the distributed capacitance of the
transmission line. Therefore, when the distance to the fault (GF) is greater than 100km (62
mile), the FL computation introduces another fault distance (GF = χ") using Equation (2.22-4).
χ3
χ" = χ − k 2 × (2.22-4)
3
where,
k: Propagation constant is pre-fixed by the manufacturer of the transmission line.
(k=0.001𝑘𝑚−1). (2.66.1.4)
Ibc = Ib − Ic (2.22-5)
Vbc = Vb − Vc (2.22-6)
Im (Vbc ∙ If ") × L
χ= (2.22-8)
{𝑅𝑒(R1 ∙ Ibc ∙ If ") + 𝐼𝑚(X1 ∙ Ibc ∙ If ")} × K bc
where,
If’: Current change before and after fault occurrence
If”: Complex conjugate of If’
Ibc: Fault current in phase-‘b’-to-phase-‘c’
Vbc: Fault voltage in phase-‘b’-to-phase-‘c’
ILb,ILc: Load currents in phase-‘b’ and phase-‘c’ before fault occurrence
Kbc: Compensation factor for phase-bc in an unbalanced 3-phase line, [FL_Kbc]
•: Symbol of Vector product
Equation (2.22-8) is a general expression used when the transmission lines are treated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 260 -
6F2S1927 (0.18)
as having lumped constants; Equation (2.22-8) is sufficient to compute the fault distance (GF =
χ) for faults that occur within 100km (62 mile) of the length of the transmission line. When the
fault distance is greater than 100km (62 mile), Equation (2.22-4) is used to obtain a
compensated value for the fault distance (GF = χ"). (2.66.1.2)
FL ****.*km
***% OB / NC
c. Fault information
b. Fault distance in percent
†Note:The user should note that the fault distance is based on the location of the local
IED (see Figure 2.22-1). Figure 2.22-2 is shown in kilometers, but the user can
change that so that the fault distance is expressed in miles. The setting is
discussed later. (See section 2.22.3(iv))
‡Note:We shall discuss the trigger signal in the succeeding section.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 261 -
6F2S1927 (0.18)
As shown in Figure 2.22-1, a single IED is located near Bus G. When a fault (F) occurs
on the line GH, the fault distance (GF) is calculated in percent using the following equation.
†Note:The FL function can determine the convergence in the computation when the
difference between the maximum value and the minimum value is less than 0.2
km. For the convergence decision, the values are calculated three times: a value
calculated for the current samples, a value three samples prior to the current
samples and a value six samples prior to the current samples. (2.66.2)
†Note:For impedance settings, the user should convert the primary values to secondary
values with regard to the line VT and CT. Set impedances as total-impedances; do
not set impedances as impedance per distance-unit.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 262 -
6F2S1927 (0.18)
where,
Z1: Positive-sequence series-impedance
Z0: Zero-sequence series-impedance
Zaa,Zbb,Zcc: Self-impedances for each phase conductor
Zab,Zbc,Zca: Mutual-impedances between phases
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 263 -
6F2S1927 (0.18)
Zaa + Zbb
− Zab
K ab = 2 (2.22-12)
Z1
Zbb + Zcc
− Zbc
K bc = 2 (2.22-13)
Z1
Zcc + Zaa
− Zca
K ca = 2 (2.22-14)
Z1
Zab + Zca
Zaa −
Ka = 2 (2.22-15)
Z1
Zbc + Zab
Zbb −
Kb = 2 (2.22-16)
Z1
Zca + Zbc
Zcc −
Kc = 2 (2.22-17)
Z1
where,
Zaa: Phase-‘a’ self-impedance on line GH (=Zbb=Zcc)
Zab: Mutual-impedances between phase-‘a’ and phase-‘b’ on line GH (=Zbc=Zca)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 264 -
6F2S1927 (0.18)
Setting self-impedances
With regard to the self-impedances, the user should set the resistance of the self-
impedances for settings [FL_Raa], [FL_Rbb] and [FL_Rcc] and set the reactance of the
self-impedances for settings [FL_Xaa], [FL_Xbb] and [FL_Xcc].
Setting mutual-impedances
With regard to setting the mutual-impedances, the user should set the resistance of the
mutual-impedance for settings [FL_Rab], [FL_Rbc] and [FL_Rca] and set the reactance
of the mutual-impedances for settings [FL_Xab], [FL_Xbc], and [FL_Xca].
Figure 2.22-3 illustrates the relationship between the location of faults relative to the
direction of FL computations. The user should set the scheme switch [FL_Dir] Forward if the
fault location computation is required for faults that occur in the forward direction. Conversely,
set [FL_Dir] Reverse if the fault location computation is required for faults that occur in the
reverse direction.
Bus G Bus G
Fault Fault If
If
IED IED
IEF
IEF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 265 -
6F2S1927 (0.18)
Table 2.22-3 Setting [FL_DIR] corresponding to the setting of OC and other relay elements
Direction of the relay (OC element etc) Scheme switch [FL_DIR]
Forward Forward
Reverse Reverse
Non-dir Forward / Reverse
We recommend that the input current be compensated using the residual current from
the adjacent line; compensation using the residual current improves the accuracy of the FL
computation. (Set scheme switch [FL-Z0B] to Off)
If the residual current of the adjacent line is not available, the user should set the scheme
switch [FL-Z0B] On so that the FL result is compensated using the zero-sequence source-
impedances for an earth fault. Table 2.22-4 summarizes the compensation methods provided
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 266 -
6F2S1927 (0.18)
together with a brief description of each method and the settings necessary for an earth fault.
Table 2.22-4 Method and setting of earth fault compensation
The trigger signals are provided by the following functions: (a) Over current protection
function and (b) External protection function. With regard to the signals from external
protection function, the user is allowed to program triggers for data-saving and calculation
using Data IDs. The following Data IDs (i.e. PLC connection points) are provided in order that
the trigger is able to initiate the start of the FL calculation.
Data ID “FL_RecF” and “FL_RecR”: Trigger for data save
Data ID “FL_LocF” and “FL_LocR”: Trigger for of calculation
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 267 -
Z1S DIR
6F2S1927 (0.18)
Forward
310022EC60 FLZ_RecF Trigger signal for data
& recording in the forward
direction
Reverse
310022EC61 FLZ_RecR
Trigger signal for data
& recording in the reverse
direction
Forward
Trigger signal for
310022EC62 FLZ_LocF & computation in the
forward direction
Reverse
310022EC63 FLZ_LocR Trigger signal for
& computation in the
reverse direction
Forward
FL-DIR Reverse
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 268 -
6F2S1927 (0.18)
2.22.5 Setting
FL-Z (Function ID: 495001) at Common
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
FL_EN Off / On - Fault locator enable On
FL_Dir Forward / Reverse - Metering direction Forward
Impeda
FL_ImpSet Symmetrical / Matrix - Selection in the setting mode of impedance Symmetrical
nce
Line 0.00 - 0.00 -
FL_Xaa - Reactance component of line (Xaa) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_Xbb - Reactance component of line (Xbb) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_Xcc - Reactance component of line (Xcc) 10.50 2.10
1000.00 200.00
0.00 - 0.00 -
FL_Xab - Reactance component of line (Xab) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_Xbc - Reactance component of line (Xbc) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_Xca - Reactance component of line (Xac) 0.50 0.10
1000.00 200.00
0.00 - 0.00 -
FL_Raa - Resistance component of line (Raa) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_Rbb - Resistance component of line (Rbb) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_Rcc - Resistance component of line (Rcc) 1.10 0.21
1000.00 200.00
0.00 - 0.00 -
FL_Rab - Resistance component of line (Rab) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_Rbc - Resistance component of line (Rbc) 0.10 0.01
1000.00 200.00
0.00 - 0.00 -
FL_Rca - Resistance component of line (Rac) 0.10 0.01
1000.00 200.00
0.00 - 0.00 - Reactance component of line positive sequence
FL_X1 - 10.00 2.00
1000.00 200.00 impedance
0.00 - 0.00 - Resistance component of line positive
FL_R1 - 1.00 0.20
1000.00 200.00 sequence impedance
0.00 - 0.00 - Reactance component of line zero sequence
FL_X0 - 34.00 6.80
1000.00 200.00 impedance
0.00 - 0.00 - Resistance component of line zero sequence
FL_R0 - 3.50 0.70
1000.00 200.00 impedance
FL_Kab 50 - 150 % Impedance imbalance compensation factors 100
FL_Kbc 50 - 150 % Impedance imbalance compensation factors 100
FL_Kca 50 - 150 % Impedance imbalance compensation factors 100
FL_Ka 50 - 150 % Impedance imbalance compensation factors 100
FL_Kb 50 - 150 % Impedance imbalance compensation factors 100
FL_Kc 50 - 150 % Impedance imbalance compensation factors 100
Z0B Zero sequence compensation of the parallel
FL_Z0B Off / On - Off
line
0.00 - 0.00 - Zero sequence back source impedance at local
FL_Z0B_L - 10.00 2.00
1000.00 200.00 terminal
0.00 - 0.00 - Zero sequence back source impedance at
FL_Z0B_R - 10.00 2.00
1000.00 200.00 remote terminal
0.00 - 0.00 - Reactance component of line mutual zero
FL_X0m - 10.00 2.00
1000.00 200.00 sequence impedance
0.00 - 0.00 - Resistance component of line mutual zero
FL_R0m - 1.00 0.20
1000.00 200.00 sequence impedance
Unit FL_Unit km / mile - Selection of line length unit km
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 269 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 270 -
6F2S1927 (0.18)
2.22.6 Signal
Signal monitoring point
FL-Z (Function ID: 495001)
Element ID Name Description
8000101349 FLTFLAG Fault locator update flag
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 271 -
6F2S1927 (0.18)
In reclosing, whenever a fault occurs on the line, a CB is tripped to clear the fault and
recloses after a time delay. Generally, 80 to 90% of faults that do occur on lines are temporary
or transient faults, which can be cleared by the tripping and subsequent reclosing of the CB.
The remaining 10 to 20% of faults are either semi-permanent or permanent faults, such as
open conductor faults etc., which cannot be cleared by the opening and subsequent closing of
the CB.
Given the important purpose of autoreclose and the very significant problems mentioned
above, it is extremely important to distinguish between the temporary/transient fault and the
permanent fault and hence, we must select either the single-shot scheme or the multi-shot
scheme.
─────────────────────────────────────────────────────────────────
Note: This section illustrates the function about three-phase auto-reclose scheme, which is
available except 36 and 39 models. For the 36 or 39 modes (i.e., single and three-phase
autoreclose), return to the preceding section.
Table 2.23-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.23 Three-phase scheme ✓ ✓ ✓ ✓ ✓ NA NA
2.24 Single and three-phase scheme NA NA NA NA NA ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 272 -
6F2S1927 (0.18)
2.23.1 Outline
The ARC function provides the following features mainly for sub-transmission and distribution
lines:
1. Three-phase autoreclosing command, this can be issued upon the reception of a trip
signal from the trip circuit (TRC) designed for three-phase tripping. Note that the ARC
function here is not designed to reclose the CB on a per-phase tripping basis. The ARC
function will operate regardless of the faulted phases, whether it is for a single-phase
fault or a multi-phase fault.
4. Permissive voltage check and check synchronism, the reclosing command for ‘shot1’ is
issued following the reception of a permissive signal from the voltage check function
(VCHK), this function checks for the existence, absence and synchronism of voltages on
the line. The user can program the generation of the permissible signal using settings
in the VCHK function.
Step1:
Two instantaneous trips and two subsequent reclosures for CB(G) and CB(H). Step1
ensures the integrity and reliability of the power system for temporary faults.
Step2:
One coordinated IDMT/DT time delayed trip is performed for the CBs by Relay(G) and
Relay(H). Coordinated tripping provides time delayed clearing of a semi-permanent
Fault F, which may be caused by a foreign object that has fallen across the line (e.g. a
twig from a tree branch), and which may be burnt out/dislodged to clear the fault.
During step2 of the scheme above, Relay(G) should not incorrectly determine that the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 273 -
6F2S1927 (0.18)
auto-reclose was successful, i.e. ‘ARC close success’ and reset its ARC function. Shot
number coordination ensures that this does not occur and synchronizes the shot
numbers of Relay(A) and Relay(H).
Relay(G) Relay(H)
2.23.2 Terminology
(i) Relay operation period
The time interval commencing from the instant of the relay picking-up for the fault current to
the instant of the relay dropping-off following the cessation of the fault current.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 274 -
6F2S1927 (0.18)
stage.
The dead times for sequential operation of the autoreclose scheme ‘ARC SHOT2’ to ‘ARC
SHOT5’, are provided by delay timers [TD_MS2]–[TD_MS5], respectively.
(ix) Final trip stage to abandon CB reclosure (signal ‘ARC FT’ and setting
TRR)
TRR is the time interval from the initiation of an ARC to abandoning the issue of ‘ARC SHOT1’.
That is, the permissive signal ‘ARC-VCHK1’ must be issued by the VCHK function within the
time interval of TRR at the end of the dead time (i.e. TRR has not timed out), otherwise the
ARC function abandons the reclosure of the CB. That is, if TSHOT has timed out and the ‘ARC-
VCHK1’ permissive signal has not been issued within TRR time, the TRR signal ends up in
‘Final Trip (FT)’. Note that the timer setting of the [TRR] timer should be set greater than that
applied to the dead time delay timer [TSHOT] to ensure that the dead time has fully expired,
see 2.23.4(iii).
(x) Reset for tripping failure (signal ‘ARC RESET’ and setting TRESET)
Subsequent to the reception of the ‘GEN.TRIP’ signal, a check is required to determine whether
the CB has opened. If the CB has not opened within the time setting of timer [TRESET], then
“CB fail to open” is indicated by the ‘ARC RESET’ signal, which also resets the operation of the
ARC. The duration of the setting applied to the [TRESET] timer must be less than the setting
applied to the ARC dead time delay timers (e.g. [TSHOT]).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 275 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 276 -
6F2S1927 (0.18)
TRC function. If an external relay can generate an ‘ARC_START’ signal, the user
can adopt it by programing the binary input circuit (BI) in the PLC function.
Another consideration required for this setting is that after the CB has gone through a
successful ARC cycle; the maximum allowable successive close-open operations are achieved
with the setting. In this case, the minimum time delay required before the CB is ready for the
next ARC cycle becomes the setting criteria for the [TREADY] timer.
Where the incidence of recurrent lightning strikes is experienced, a shorter reclaim time
will prevent the ARC function going into an unnecessary lock out. On the other hand, caution
is required when considering the exposure of the CB to an excessive number of ARC cycles
caused by recurrent faults which will result in an increase in the frequency of the maintenance
cycle.
In summary, the time required for the CB to be ready for the next cycle of ARC is the
minimum setting that can be applied to the reclaim timer [TREADY] in the ARC function. The
criteria for setting the reclaim timer is described in the Application Guidelines in section 2.23.8
and includes the setting example under 2.23.8(ii)-3.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 277 -
6F2S1927 (0.18)
or more multi-shot schemes (i.e. ‘ARC SHOT3–5’) are not illustrated. That is, the schemes for
‘ARC SHOT3–5’ are similar in operation but are not illustrated
To BO
ARC CLOSE COMMAN
ARC RESET
800000EBBE ARC_BLOCK
From TRC
≥1 Final trip stage
ARC IN-PROG OR &
GEN.ARC-BLOCK ARC FT
≥1
GEN.TRIP
≥1
800000EBB2 EXT.ARC_START
From PROT_COMM
CB_ALLPH_CLOSE
≥1
800000EBB4 CB-ARC READY
TRESET
& t 0
≥1
From VCHK
ARC-VCHK
(iv)ARC SHOT2 ≥1
ARC CLOSE FAIL
S ARC-S2 IN-PROG ARC NOT IN PROG
&
R ARC SHOT2
ARC SHOT RS
ARC-S2 COND
ARC CLOSE SUCCESS
ARC-S2 TRR
Figure 2.23-2 Overall logic of ARC function for issue of ‘ARC SHOT1’ and ‘ARC SHOT2’
If it is required that the ARC function be removed from service by the operation of an
external signal, the PLC connection point ‘ARC-OFF’ is provided so that the user can introduce
an ‘Off” signal. One more external signal can place the ARC function in service using the PLC
connection point ‘ARC-ON’. For example, the user may wish to select ‘On’ or ‘Off’ by pressing
buttons mounted on a relay/control panel, using these PLC connection points. Note that either
of the signals introduced at the PLC connection points overrides the selection made by the
scheme switch [ARC-EN].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 278 -
6F2S1927 (0.18)
& ≥1 ARC=ON
The timer [TREADY] shown in Figure 2.23-3 is the reclaim timer and is used to delay the
operation of the ARC, as discussed in section 2.23.2(xiii).
If the ‘ARC READY’ signal is not generated while signals ‘ARC_START’ and ‘SHOT_1ST’
are set to TRUE, (Logic level being high‘1’) in the Initiation logic, see Figure 2.23-2, the ARC
operation is locked out, (indicated by signal ‘ARC FT’ in Figure 2.23-2). The
‘CB_ALLPH_CLOSE’ signal is used so that the CB closed condition is determined. The PLC
connection point ‘CB-ARC READY’ is active when the CB provides the ready signal.
8100001B60
800000EBB2 EXT.ARC_START EXT_START_SIGNAL
&
1 &
To Final trip stage
From TRC 1
≥1 & ARC UNREADY
GEN.TRIP
0.01s
ARC SHOT_1ST
Start-up logic ARC SHOT OVER &
SHOT NUMBER OVER
ARC_START
Start-up logic ARC READY
To ARC SHOT1 logic
8000001B61 To ARC SHOT2 logic
ARC_START
Start-up logic ARC=ON & 8200001B64
&
S ARC IN-PROG
800000EBB3 ARC NO ACT 1
R
To Shot counter logic
Shot counter logic SHOT_1ST
1 ARC NOT_IN-PROG
From reset point ARC RS
When the input signals ‘ARC_START’, ‘SHOT_1ST’ and ‘ARC READY’ are active at the
same time, a flip-flop circuit issues the ‘ARC IN-PROG’ signal. The signals ‘ARC IN-PROG’
and ‘ARC_START’ will be issued when the ‘SHOT_1ST’ shot is issued from the Shot counter
logic.
8000001BB5 TSHOT
≥1
Always ‘1’ † 800000EBB5 ARC_MAIN_START t 0
&
&
ARC-S1 IN-PROG 0.01 – 300.00 s
Flip-flop
0.01 – 310.00 s
TSHOT_SUB
& t 0
8100001BB8
Signal generated by the 810000EBB8 ARC_SUB_COND
user’s PLC programing
a default. When the VCHK function is not implemented, Logic ‘1’ signal (Always
high(TRUE)) is applied.
§Note:In terms of setting, the value applied to the [TRR] timer should be longer than
that applied to the [TSHOT] timer. Setting [TSHOT_SUB] timer may be required
if the PLC signal is injected by the user programing.
ARC SHOT2
TD_MS2
0.01 – 300.00s
To Final trip stage
TRR_MS2
t 0
ARC-S2 TRR
0.01 – 310.00s
800000EBBD CB_MANUAL_CLOSE‡
‡Note: PLC connection point ‘CB_MANUAL_CLOSE’ is provided so that the user can
utilize the ARC function to close the CB manually if an external switch (such as a
push button on a relay/control panel) is required for manual operation.
To Initiation logic
Initiation logic ARC NOT_IN-PROG ≥1 TARCDSUC
Initiation logic ARC_START t 0
S
& ARC SHOT RS
R
0.10-100.0s 8000001B70
0.1s
From PROT_COMM
t 0
CB_ALLPH_CLOSE
0.02s
ARC-SucChk Off
On
STEP1 SHOT_2ND
8200001B73
SHOT2 logic ARC SHOT2 CLOCK STEP2 SHOT_3RD
8300001B74
SHOT3 logic ARC SHOT3 ≥1
SHOT4 logic ARC SHOT4 STEP3 SHOT_4TH
SHOT5 logic 8400001B75
ARC SHOT5
STEP4 SHOT_5TH
8500001B76
Shoot number ARC COORD
coordination logic† STEP5 SHOT NUMBER OVER
Figure 2.23-9 Shot counter logic for SHOT1 and SHOT2 logic blocks
The user can select the number of shots desired for autoreclosing using the scheme switch
[ARC-NUM], as cited in section 2.23.4(i). When a single-shot scheme (S1) is preferred, setting
S1 is used to generate only a single shot (SHOT_1ST). When a multi-shot scheme is required
(e.g. S2 is preferred), the Shot counter logic will increment the count until the issue of the
‘SHOT_2ND’ signal is complete (that is, when S2 is set, the ‘ARC CLOSE COMMAND’ signal
will be issued at the first and second sequence). If after the second sequence the fault persists,
the final trip (signal ‘ARC FT’) is issued by the ARC function, see Figure 2.23-2.
Closed
CB status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC IN-PROG
ARC-S1 IN-PROG
ARC SHOT2
ARC-S3 IN-PROG
ARC SHOT3
ARC FT
Figure 2.23-10 Single shot scheme [ARCNUM]=S1 for an Arcing fault; operation is successful
Note: As cited in section 2.23.4(iii), the permissive signal ‘ARC-VCHK’ is required for
operation, but is omitted here for the sake of clarity. The pulse width of the ‘ARC
CLOSE COMMAND’ signal is defined using the setting [TCCW].
Fault current
Closed
CB Status CB fails to be closed.
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC IN-PROG
ARC-S1 IN-PROG
ARC-S2 IN-PROG
ARC SHOT2
ARC-S3 IN-PROG
ARC SHOT3
Figure 2.23-11 Single shot scheme [ARCNUM]=S1 for an Arcing fault; CB fails to reclose
Note: As described in section 2.23.4(iii), the permissive signal ‘ARC-VCHK’ is required
for the ARC SHOT1 operation, but is omitted here for the sake of clarity.
Closed
CB Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC IN-PROG
ARC-S1 IN-PROG
ARC-S2 IN-PROG
ARC SHOT2
ARC-S3 IN-PROG
ARC SHOT3
ARC FT
Figure 2.23-12 Single shot ARC scheme [ARCNUM]=S1 for Permanent fault
Note: As described in section 2.23.4(iii), the permissive signal ‘ARC-VCHK’ is required
for the ARC SHOT1 operation, but is omitted here for the sake of clarity.
(iv) Single shot scheme for an Arcing fault; fault removed by a backup
CB
Figure 2.23-13 shows the single shot scheme for an Arcing fault, but tripping is not executed
due to the failure of the CB. Therefore, the operation of the ARC function is reset in the setting
time [TRESET] before the duration of dead timer [TSHOT] expires. Consequently, the ARC
function determines that the local CB cannot be tripped to clear the fault.
Fault current
Fault cleared by tripping the backup CB at the remote end†
Closed
CB Status CB at the local end fails to open
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC IN-PROG
ARC-S1 IN-PROG
ARC-S2 IN-PROG
ARC SHOT2
ARC-S3 IN-PROG
ARC SHOT3
CB ALLPH Closed
CLOSE Open
ARC FT
Reset
ARC RESET [TRESET]
)
Figure 2.23-13 Single shot scheme [ARCNUM]=S1 for an Arcing fault; remote CB† tripped
†Note:the fault is removed by the tripping of the CB at the remote end; hence, the fault
current will no longer flow.
Fault current
Closed
CB Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC IN-PROG
ARC-S1 IN-PROG
ARC-S2 IN-PROG
ARC-S3 IN-PROG
Closed
CB ALLPH
Open
CLOSE
Lateral branch
Busbar G
Fuse Permanent Fault F
G R Main feeder
Fuse
ARC ARC
Relay OCG in DTG (1), DTG (2), IDMTG(3), IDMTG(4) Relay OCR in DTR (1), DTR (2), IDMTR(3), IDMTR(4)
S
Sectionalizer
Lateral branch
Upon the occurrence of a permanent fault ‘F’, both relays G and R will issue a DT(2) trip
following a DT(1) trip for their respective CBs; that is, in the first instance a reclose shot, (ARC
SHOT1) will be issued by both relays. Then, a second reclose shot (ARC SHOT2) will also be
issued by both the relays.
For the third reclose shot (ARC SHOT3), the difference between the settings of the
IDMT(3) characteristic for relays G and R will alter the operating times of their respective ARC
functions. Given that the pickup time in IDMTG(3) is delayed in comparison to the pickup time
in IDMTR(3), the third reclosing (ARC SHOT3) will be performed only by relay R, whereas relay
G neither issues a trip command nor an ARC shot. Consequently, relay G may now determine
that the operation of its ARC sequence has been successful and hence relay G will reset to
return to the beginning of its sequence ‘ARC ready’ (i.e. the ARC function at relay G will
commence from the first reclose shot ‘ARC SHOT1’). Conversely, relay R is unable to issue a
fourth reclose shot (ARC SHOT4) because the delayed operation of IDMTR(4) means that it will
not have sufficient time to operate for the fault. This is because, following the tripping for the
first DTG(1), relay G issues the first reclose shot (ARC SHOT1), but its shot sequence is not
correct. Figure 2.23-16 illustrates how tripping and reclosing are not performed correctly; thus
erroneous coordination between the ARC operations at relay G and relay R is experienced.
In order to avoid the mismatch in coordination between relays G and R described above,
it is necessary to match the shot numbers between relay G and relay R; a coordination function
provided to match the shot number in the ARC function, as illustrated in Figure 2.23-17.
1st trip 2nd trip 3rd and 4th tripping are not
performed.
CO-OC element
Current
Pick up Inflow
Drop off Fault current
Unfaulted current
Unfaulted current
The matching of shot numbers is achieved by distinguishing a different duration for the
pick-up and drop-off of fault current using an over current element (CO-OC) or an earth fault
element (OC-EF), which are arranged within the ARC function as shown in Figure 2.23-17.
The user must set the thresholds of the CO-OC and CO-EF relays using settings [CO-OC] and
[CO-EF], respectively. To engage the coordination feature, set the [ARCCO-OCEN] or [ARCCO-
EFEN] to On, the switches of which are shown in Figure 2.23-18.
t 0
From shot-counter logic SHOT_3RD &
TCORST2†
From shot-counter logic SHOT_4TH & t 0
≥1
TCORST3†
From shot-counter logic SHOT_5TH & t 0
TCORST4†
From shot-counter logic SHOT_6TH t 0
&
TCORST5†
If the majority of the faults are transient, (e.g. due to lightning), then applying a single-
shot scheme would be appropriate.
If a significant percentage of faults on the distribution line are semi-permanent (e.g. due
to foreign objects like a small tree branch or small animal that may have fallen across the line),
then adopting a multi-shot scheme becomes advantageous.
If transient or semi-permanent faults are rare (e.g. overhead distribution line in urban
areas or a feeder which has a significant portion of cable), then non-use of the ARC function
will be appropriate.
CB characteristics
The capability of a CB for ARC duty must be checked. The CB characteristics such as the
number of successive open-close (OC) duty cycles and the dead time required between an open-
close operation will determine the number of ARC shots employed and the minimum dead time
before an ARC shot can be given.
De-ionization time
The time taken for de-ionization of the fault arc path is an important consideration for
determining the dead time before an ARC shot can be given. The de-ionization period depends
upon the system voltage, the fault current and the duration of the fault. Capacitive coupling
between the unfaulted phase and the faulted phase will increase the de-ionizing time; however,
this is not applicable for a relay for distribution systems, because tripping is always three-
phase. A de-ionization time of at least 100ms may be considered for distribution voltages (66KV
and below).
System stability
The intrinsic stability of an interconnected power system will determine the maximum dead
time allowable before the ARC shot must be issued. This may not apply to conventional
distribution systems where the generating source is remote from the load centers. However,
with distributed generation located closer to load centers, stability becomes an important
consideration. Transient stability studies can establish the maximum dead time allowed for
these systems.
Where the incidence of recurrent lightning strikes is experienced, a shorter reclaim time
will prevent the ARC function going into an unnecessary lock out. On the other hand, caution
is required when considering the exposure of the CB to an excessive number of ARC cycles
caused by recurrent faults thus increasing the frequency of maintenance that will be required.
The time necessary for the CB to be ready for the next cycle of ARC will determine the
minimum time required in determining the setting of the reclaim time for the ARC function.
The criteria for setting the reclaim time is described in (ii)-3 below.
Note:
1. Stability criterion may not be applicable for a highly interconnected power
system where loss of one line does not endanger system stability.
2. Stability criterion will not apply to radial distribution feeders with no
downstream generating source.
When a CB is closed for the first time subsequent to the maintenance of a distribution
line, the closure should be successful (that is, the CB is closed on to healthy line). Then the
minimum time setting of the TREADY timer should be longer than the time required to judge
that the CB has closed successfully; say a setting of 5 seconds will be appropriate.
Another consideration is, for the setting required after the CB has gone through a
successful ARC cycle and the maximum allowable successive close-open operations have been
used. In this case, the minimum time delay required before the CB is ready for the next ARC
cycle becomes the setting criteria for the [TREADY] timer. In the example considered, this
minimum time delay is 30 seconds so in order to provide some margin a setting of 35.0 seconds
has been chosen.
A=CBopeningtime+Deionizingtime-CBclosingtime (2.23-1)
B=CBopeningtime+Protectionresettime (2.23-2)
C=CBopeningtime+Tripmechanismresettime (2.23-3)
D=CBopeningtime+MinimumdeadtimerequiredbyCBbeforeShot1 (2.23-4)
Note: The user can choose [TSHOT_SUB] using PLC signals ARC_SUB_START and
Note: The difference between the setting [TCCW] and the CB closing time, (in this case
20ms) should be lower than ‘the protection operation time + CB opening time’.
This is to ensure that for CBs without an anti-pumping feature, the close pulse is
not present if the CB were to re-trip on closure.
Note: The ARC coordination function may be enabled if there is another downstream CB
with which shot coordination is required. The function is enabled by setting ‘On’
for scheme switches [ARCCO-OCEN] and [ARCCO-EFEN]. The default settings for
overcurrent pickup (CO-OC=1.0/5.0 A) and earth fault pickup (CO-EF=0.30/1.5 A)
should be adequate for most applications.
2.23.9 Setting
ARC(Function ID:4A7001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ARC-EN Off / On - Auto reclose mode in 1CB-system Off
ARC ARC-NUM S1 / S2 / S3 / S4 / S5 - Auto reclose maximum shot number S1
Check ARC-SucChk Off / On - Autoreclose success checking enable On
TARCDSUC 0.10 - 100.00 s Autoreclose success checking time 0.30
TRESET 0.01 - 300.00 s Autoreclose reset time under CB closed 0.30
TREADY 0.0 - 600.0 s Autoreclose ready check time 60.0
TSHOT 0.01 - 300.00 s Autoreclose SHOT dead time 0.60
TSHOT_SUB 0.01 - 300.00 s Autoreclose sub-SHOT dead time 300.00
TRR 0.01 - 310.00 s Autoreclose reset time 2.00
TCCW 0.01 - 10.00 s Autoreclose ARC command pulse width 0.20
Multi MultiShot-EN Off / On - Autoreclose multi shot enable Off
-shot TD_MS2 0.01 - 300.00 s 2nd shot ARC dead time 20.00
TRR_MS2 0.01 - 310.00 s 2nd shot ARC reset time 30.00
TD_MS3 0.01 - 300.00 s 3rd shot ARC dead time 20.00
TRR_MS3 0.01 - 310.00 s 3rd shot ARC reset time 30.00
TD_MS4 0.01 - 300.00 s 4th shot ARC dead time 20.00
TRR_MS4 0.01 - 310.00 s 4th shot ARC reset time 30.00
TD_MS5 0.01 - 300.00 s 5th shot ARC dead time 20.00
TRR_MS5 0.01 - 310.00 s 5th shot ARC reset time 30.00
Coordin
ARCCO-OCEN Off / On - Autoreclose OC enable Off
ation
0.02 - 0.10 -
CO-OC A Autoreclose OC threshold 1.00 5.00
50.00 250.00
ARCCO-EFEN Off / On - Autoreclose EF enable Off
0.02 - 0.10 -
CO-EF A Autoreclose EF threshold 0.30 1.50
50.00 250.00
2.23.10 Signal
Signal monitoring points
ARC(Function ID: 4A7001)
Element ID Name Description
8100001B60 EXT_START_SIGNAL ARC operation is initiated by an external relay
8000001B6B FT ARC UNREADY ARC operation locked out because ARC is not ready.
8400001B6C ARC FT Final trip command issued after ARC operation is locked out.
8000001B71 SHOT_1ST Counter in the shot counter logic does not run
8400001B75 SHOT_5TH Clock hand in the shot counter logic is running for fourth round
8000001BB3 ARC NO ACT Request not to operate ARC from an external relay
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 298 -
6F2S1927 (0.18)
800000EBB2 EXT.ARC_START Receipt point from an external relay for starting ARC
800000EBB4 CB-ARC READY Signal injection point indicating that the CB is ready to be reclosed
800000EBB6 ARC_MAIN_COND Point for the permissive signal to issue the first ARC shot
810000EBB8 ARC_SUB_COND Point for the sub permissive signal to issue the first ARC shot
810000EBB9 ARC-S2 COND Point for the permissive signal to issue the second ARC shot
820000EBBA ARC-S3 COND Point for the permissive signal to issue the third ARC shot
830000EBBB ARC-S4 COND Point for the permissive signal to issue the fourth ARC shot
840000EBBC ARC-S5 COND Point for the permissive signal to issue the fifth ARC shot
.69)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 299 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: This section illustrates the function about single and three-phase auto-reclose scheme,
which is available in 36 and 39 models. For the others (i.e., three-phase auto-reclose
without single-phase autoreclose), jump to the succeeding section.
Table 2.24-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.24 Single and three-phase scheme NA NA NA NA NA ✓ ✓
2.23 Three-phase scheme ✓ ✓ ✓ ✓ ✓ NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 300 -
6F2S1927 (0.18)
2.24.1 Outline
Table 2.24-2 summarizes the reclosing operations and the modes in the ARC function. The
ARC function can operate for both a single CB arrangement and double CBs (1.5CB)
arrangement; hence, the ARC function is grouped into two logics: ARC1 for CB#1 and ARC2
for CB#2. Note that multi-shots scheme is only available for 1CB arrangement (CB#1). The
‘ORIGINAL’ is provided for the user’s programing.
Table 2.24-2 ARC operation modes and shot numbers
1CB or 1.5CB arrangement
Reclosing
Shot number 1CB 1.5CB
mode
ARC1 ARC2 ARC1&2
SPAR X (N.A) x
ARC1 SHOT1
TPAR X (N.A) x
or/and
SPAR&TPAR X (N.A) x
ARC2 SHOT
ORIGINAL X (N.A) x
ARC1 SHOT2 X (N.A) (N.A)
ARC1 SHOT3 X (N.A) (N.A)
ARC1 SHOT4 X (N.A) (N.A)
ARC1 SHOT5 X (N.A) (N.A)
x: Operation is applicable N.A: Operation is not applicable
CB#1
Line Busbar G
Line VT Bus VT
CB#1 Reclosing for CB#1
Relay(G)
Bus VT VCHK1(G) VCHK1(G)
Line VT
ARC1(G)
VCHK2(G)
ARC1(G) ARC2(G)
Reclosing CB#1
Line1
Busbar G
CB#2
Reclosing for CB#2
Line VT
Line2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 301 -
6F2S1927 (0.18)
†Note:VCHK are automatically applied in the TPAR mode (for ARC1 SHOT1 and ARC2
SHOT). For more information, see Chapter Relay application: Voltage check for
auto reclose.
For the TPAR mode in the 1.5CB arrangement, synchronism check and voltage check
(VCHH) between the bus bar (for bus CB#1) and the line or between the two lines (for center
CB#2) are required. The reclosing order between CB#1 and CB#2 can be selected using setting
[ARC-ORDER]; that is, CB#1 recloses first followed by CB#2 (i.e., [ARC-ORDER]=CB1)or vice
versa (i.e., [ARC-ORDER]=CB2). Simultaneous closure of CB#1 and CB#2 can also be selected
(i.e., [ARC-ORDER]=SIMUL).
stage, which the ARC issues a three-phase trip command (CB1_94TT or CB2_94TT) for the
TRC function; the ARC function abandons to reclose the CB#1 and CB#2 (ARC1 FT or ARC2
FT).
CB is not ready for ARC operation
Failure to issue ARC shot
ARC block command has come through PLC connection points
Multi-phase trip in SPAR mode
Evolving fault (single phase to multiphase) in SPAR and TPAR mode
Final trip selected for 3-phase fault (user settable)
ARC close fail
Shot number over
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 304 -
6F2S1927 (0.18)
2.24.2 Terminology
The terminology and signals outlined below are applicable for single CB#1 system. Signals
applicable for CB#2 in a two (2) CB system are similar and are not included for clarity.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 305 -
6F2S1927 (0.18)
The dead times for sequential operation of the autoreclose scheme ‘ARC1 SHOT2’ to
‘ARC1 SHOT5’, are provided by delay timers [TD_MS2]–[TD_MS5], respectively.
†Note:delay timer [TTPAR] is available when the ARC function operates in TPAR mode.
For the operation in other SPAR and ORGAR modes, the user should also set
values for delay timers [TSPAR1] and [TORGAR1].
(ix) Final trip stage to abandon CB reclosure (Signal ‘ARC1 FT’ and
setting TRR1, TRR_MS2–5)
TRR1 is the time from the ARC1 initiation to abandoning issuing the ‘ARC1 SHOT1’. In TPAR†
mode the permissive signal ‘ARC1-VCHK’ must be issued by the VCHK function within the
time interval of TRR1 at the end of the dead time (i.e., TRR1 has not timed out), otherwise the
ARC function abandons the reclosure of CB#1. That is, if TTPAR1 has timed out and ‘ARC1-
VCHK’ permissive has not been issued within TRR1 time, TRR1 signal yielded in the TPAR
mode ends up ‘Final Trip (ARC1 FT)’. Note that the timer setting of the [TRR1] timer should
be set greater than that applied to the dead time delay timer [TTPAR1] to ensure that the dead
time has fully expired.
Likewise, for shots 2–5 the timers [TRR_MS2] and others issue the signal for ‘Final Trip
(ARC1 FT)’ if the respective shots are not issued within the set time.
†Note:We can see similar ARC behavior in the other SPAR, MPAR, and ORGAR modes.
(x) Reset for tripping failure (Signal ‘ARC1 RESET’ and setting TRESET)
Subsequent to the reception of the ‘GEN.TRIP’ signal, a check is required to determine whether
the CB#1 has opened. If the CB#1 has not opened within the time setting of timer [TRESET],
then “CB#1 failing to be opened” is judeged by the ‘ARC1 RESET’ signal, which also resets the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 306 -
6F2S1927 (0.18)
reclose operation of the CB#1. The duration of the setting applied to the [TRESET] timer must
be less than the setting applied to the ARC dead time delay timers (e.g. [TTPAR] etc.).
If the CB fails to close within the setting of timer [TARCSUC],an ‘ARC1 CLOSE FAIL’ signal
is issued and the ARC1 function moves to the ‘Final trip (ARC1 FT)’ stage.
Note: a CB failure to close condition cannot be detected; the user shall incorporate the
check scheme externally.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 307 -
6F2S1927 (0.18)
Respective signals ‘ARC1-S* IN-PROG’ are defined for the operation of respective shots. A
common ‘ARC1 IN-PROG OR’ is also issued.
Another consideration required for this setting is that after the CB has gone through a
successful ARC cycle; the maximum allowable successive close-open operations are achieved
with the setting. In this case, the minimum time delay required before the CB is ready for the
next ARC cycle becomes the setting criteria for the [TREADY] timer.
Where the incidence of recurrent lightning strikes is experienced, a shorter reclaim time
will prevent the ARC function going into an unnecessary lock out. On the other hand, caution
is required when considering the exposure of the CB to an excessive number of ARC cycles
caused by recurrent faults which will result in an increase in the frequency of the maintenance
cycle.
In summary, the time required for the CB to be ready for the next cycle of ARC is the minimum
setting that can be applied to the reclaim timer [TREADY] in the ARC function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 308 -
6F2S1927 (0.18)
To send the ‘3PTP PERM’ signal for the main relay, output ‘3PTP PERM’ signal via a BO circuit
that is connected with the main relay. Figure 2.24-3 illustrates the 3PTP PERM logic.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 309 -
6F2S1927 (0.18)
Fault occurred
Fault in Phase-A
Tripping in Phase-A
Tripping in Phase-B
Tripping in Phase-C
GRD200 relay
ARC initiated
Timer [T3PTP]
T3PTP 8100001B85
Initiation for CB#1
t 0
ARC1 IN-PROG ≥1 3PTP PERM
0.01 – 10.00
ARC1 UNREADY
≥1
ARC1-Mode input
ARC1-MODE=FT
≥1
ARC1-MODE= TPAR
Shot counter
SHOT_2ND
SHOT_3RD ≥1
SHOT_4TH
SHOT_5TH
SHOT_6TH
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 310 -
6F2S1927 (0.18)
Each functional block diagram is grouped into a number of logic blocks; four typical functional
block diagrams are illustrated below:
(i) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the SPAR mode
(ii) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the TPAR mode
(iii) Issuing ‘ARC SHOT1’ and ‘ARC SHOT2’ in 1 CB of the SPAR and TPAR mode
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 311 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 312 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
≥1
Start
Multi-phase Trip in SPAR1
GEN.TRIP-A 3
&
GEN.TRIP-B &
GEN.TRIP-C
Condition as to CB#1
800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC
6 ARC1 FT
TRIP-MPH
800000EBB1 EXT.ARC_START-B
TRIP-1PH CB1_94TT
TRIP-1PH C
ARC1 SPAR_COND
800000EBB2 EXT.ARC_START-C B SPAR
ARC START ARC1-S1 IN-PROG ≥1
CB1_ALLPH_CLOSE
≥1
CONSTANT_1
TRESET1
≥1 & t 0
810001EBC9 ARC1-S2 COND
GRD200 software:
Figure 2.24-4 ARC SHOT1 and SHOT2’ in SPAR mode of 1CB system
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 314 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
&
Start
GEN.TRIP-A
3
GEN.TRIP-B
GEN.TRIP-C
Condition as to CB#1
800000EBB0 EXT.ARC_START-A ARC1 IN-PROG OR To TRC
6
ARC1 FT
800000EBB1 EXT.ARC_START-B
TRIP-ANYPH TRIP-ANYPH CB1_94TT
ARC1 TPAR_COND C
800000EBB2 EXT.ARC_START-C B TPAR
ARC START ARC1-S1 IN-PROG ≥1
ARC1 SHOT2
8
ARC1-S2 TRR
ARC1-Mode input ARC-SucChk
1
ON
TPAR B Shot Counter
≥1
820001EBB2 ARC1_MODE-TPAR
5 Reclose sequence
ARC1-MODE=NO-OFF ARC1 NOT_IN-PROG
11 TPAR1_START
Shot number ARC-ORDER
From PROT_COMM ARC1 SHOT1 SHOT_1ST D
2 CB1
ARC-NUM
CB-System ARC1 SHOT2 SHOT-2ND
CB-SYSTEM=1CB 1CB A
1CB S2
GRD200 software:
Figure 2.24-5 ARC SHOT1 and SHOT2 in TPAR mode of 1CB system
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 316 -
800001EBCF ARC1_BLOCK To BO
≥1 ARC1 CLOSE COMMAND
820000EBB4 ARC_BLOCK
ARC1 BLOCK COM
From TRC
GEN.ARC-BLOCK ARC1 RESET
&
Start
GEN.TRIP-A
3
GEN.TRIP-B
GEN.TRIP-C Condition as to CB#1
Figure 2.24-6 ARC SHOT1 and SHOT2 in SPAR&TPAR mode of 1CB system
GRD200 software:
6F2S1927 (0.18)
&
≥1
Condition
&
ARC1-MODE=SPAR
≥1
&
OFF ARC1-MODE=TPAR
≥1
FT
SPAR &
TPAR ≥1 ARC1-MODE=S&T
SPAR&TPAR
ARC1-MODE ≥1 ARC1-MODE=SPAR+S&T
ORIGINAL
&
≥1
Start
ARC1-MODE=NO-OFF
≥1
800001EBB0 ARC1_MODE-OFF &
≥1 Initiation
820001EBB2 ARC1_MODE-SPAR
& ARC1-MODE=ON
ARC1-MODE=OFF
800001EBB7 ARC1_MODE-S&T &
Original
ARC1-MODE=ORG
860001EBB6
800001EBB7 ARC1_MODE-ORG &
8800011B62 To TRC
≥1
Signal ‘1’ is generated when there is no contradiction between the CB1_BRIDGE
various signals, that is only one signal is picking up.
When FT is selected, the ARC function send ‘CB1_BRIDGE’ signal for the TRC function
to be the CB being tripped in three-phases, regardless of the condition of the tripped phase,
the operation of respective protection elements, and the ARC settings; the ARC function does
not operate (i.e., ARC1-FT).
When TPAR is selected, the TRC and the ARC functions operate by the rule that the CB
is tripped in three-phases and can be reclosed. That is, ‘CB1_BRIDGE’ signal is sent for the
TRC function so that the CB will be tripped in three-phases forcibly even if a GEN.TRIP-A
(TRIP COMMAND-A) signal is only generated in the TRC function (as well as GEN.TRIP-B
and GEN.TRIP-C). Note the CB will be tripped in three-phases forcibly, even if a single-phase
fault is detected and instructed a single-phase tripping by the relay applications.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 318 -
6F2S1927 (0.18)
&
≥1 &
&
≥1 &
&
≥1 & ARC2-MODE=SPAR
& Condition
OFF
≥1 & ARC2-MODE=TPAR
FT
SPAR &
TPAR ≥1 & ARC2-MODE=S&T
SPAR&TPAR
ARC2-MODE ≥1 ARC2-MODE=SPAR+S&T
ORIGINAL
&
ARC2-MODE=MPAR
≥1 &
Start
ARC2-MODE=NO-OFF
800002EBB0 ARC2_MODE-OFF &
≥1
ARC2-MODE=OFF
800002EBB7 ARC2_MODE-S&T &
≥1
Original
ARC2-MODE=ORG
860002EBB6
800001EBB7 ARC2_MODE-ORG &
CB-SYSTEM=1CB
8800021B62 To TRC
≥1 CB2_BRIDGE
810002EBB9 CB2 F.BRIDGE
READY
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 319 -
6F2S1927 (0.18)
& ARC-NUM=S2
S1
& ARC-NUM=S3
S2
S3
S4 & ARC-NUM=S4
ARC-NUM
S5
& ARC-NUM=S5
From PROT-COMMON
CB-SYSTEM=1 CB
CB-SYSTEM=2 CB
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 320 -
6F2S1927 (0.18)
1
800000EBB5 RYOP-A 8500001B6C
≥1 ARC2 FT CB2_94TT
&
0 t
800001EBCF ARC1_BLOCK ≥1 ARC1 FT CB1_94TT
&
0.1s
810002EBB7 ARC2_BLOCK
0 t ARC2 FT CB2_94TT
≥1
820000EBB4 ARC_BLOCK
&
0.1s 8300001B64
From TRC
GEN.ARC-BLOCK & EXT.ARC_START
≥1
8400001B65 Initiation
GEN.TRIP-A
≥1 & 1 ARC START
≥1
GEN.TRIP-B
≥1 & 1
GEN.TRIP-C
≥1 & 1
0.01s
800000EBB0 EXT.ARC_START-A Condition
8000001B66
810000EBB1 EXT.ARC_START-B S
TRIP-ANYPH
≥1
820000EBB2 EXT.ARC_START-C R
To Multiphase
S 8100001B67 trip in SPAR
R & TRIP-1PH
ARC1-MODE input 1 ≥1
S
ARC1-MODE=NO-OFF 1
R
ARC2-MODE input ≥1
ARC2-MODE=NO-OFF &
&
1
800000EBB3 ARC NO ACT 1
1
&
1
To Evolving fault
8200001B68 logic
&
≥1 TRIP-MPH
&
Initiation
&
ARC1 IN-PROG OR
8300001B69
& TRIP-3PH
ARC1-S1 IN-PROG MPAR judgment
≥1
Reclose sequence
ARC2-S1 IN-PROG 1 NON ARC-S1_ IN-PROG
If the scheme switch [FT-3P FAULT] is set to On, ‘CB1_94TT’ and ‘CB2_94TT’ signals are
generated and introduce the three-phase tripping (final trip) for the TRC function during the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 321 -
6F2S1927 (0.18)
ARC1 and ARC2 functions being generating ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’
signals. The switch [FT-3P FAULT] requires signals of the external relay; PLC connection
points ‘RYOP-A, RYOP-B, and RYOP-C’ are used to get the signals.
Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are generated when ‘ARC BLOCK’
signals are injected, provided ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’ signals is being
generated.
If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and
the CB#2, the ARC function can generate the ‘CB1_94TT’ and ‘CB2_94TT’ signals when an
external device is able to detect the consistency; use PLC connection points ‘F.CB1_94TT’ and
‘F.CB2_94TT’ for the operation of the inconsistency.
The Start logic can receive a stop signal not to operate the ARC function; use PLC
connection point ‘ARC NO ACT’.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 322 -
6F2S1927 (0.18)
S ARC1-S5 IN-PROG
SHOT_5TH &
R
Shot1–Shot5 logics for CB#1
Done issuing
ARC1 SHOT1 TRESET
&
≥1 t 0
A
ARC1 SHOT2 & &
0.0-300.0s
ARC1 SHOT3 &
8800021B62
To TRC
CB2_BRIDGE
8000021B69
& FT ARC2 UNREADY ARC2 FT CB2_94TT
From PROT-COMMON
TREADY2
CB2_ALLPH_CLOSE 8000021B60
& t 0
ARC2 READY
810002EBB8 CB2-ARC READY
1 To CB#2 bridge, Final trip logic
0.0-600.0s &
ARC2-MODE input logic
ARC2 UNREADY
ARC2-MODE=ON
To Start
& ARC2-S1 IN-PROG
8200021B61
S
To Shot logic for CB#2
& R
S ARC2-S1 IN-PROG
800000EBB3 ARC NO ACT
1 ≥1
R
Success check
≥1 8700011B70 Initiation for CB#2
ARC1 RS
ARC2 RS TRESET
8700021B6C t 0
A ARC1 RESET ≥1 B
&
B ARC2 RESET
0.0-300.0s
ARC2 SHOT
If the ‘ARC1 UNREADY’ signal is present, Initiation logic abandons to reclose the CB#1;
then, the status of the ARC function reaches the Final Trip stage (FT); three-phase trip signal
(CB1_94TT) is generated transferred for the TRC function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 323 -
6F2S1927 (0.18)
The ‘CB1-BRIDGE’ signal is used to combine any ‘per-phase trip signal’ into the three-
phase trip signal in the TRC function. Thus, the CB will be tripped in three-phases forcibly
even if a GEN.TRIP-A (TRIP COMMAND-A) signal is only generated in the TRC function
during the ‘ARC1 UNREADY’ being decided (as well as GEN.TRIP-B or GEN.TRIP-C).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 324 -
6F2S1927 (0.18)
Shot number
8000001B81 To Fault record
ARC-NUM=S1
OFF
S1
S2
S3
S4
SHOTNUM-TEST S5
S6
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 325 -
6F2S1927 (0.18)
& TPAR
&
≥1 ARC1_TPAR_COND
TRIP-ANYPH ARC2_TPAR_COND
&
&
TRIP-MPH
&
&
&
&
≥1
To TRC
CB1_94TT
&
& CB2_94TT
ARC1-MODE input
MPH-TRIP
OFF & IN SPAR1 ARC1 FT CB1_94TT
FT ARC1-MODE=SPAR
ORIGINAL ARC1-MODE=TPAR
SPAR
ARC1-MODE=S&T
ARC1-MODE TPAR
SPAR&TPAR ≥1 ARC1-MODE=SPAR+S&T
ARC2-MODE input
MPH-TRIP
OFF ARC2-MODE=SPAR & IN SPAR2 ARC2 FT CB2_94TT
FT
ORIGINAL ARC2-MODE=TPAR
SPAR ARC2-MODE=S&T
ARC2-MODE TPAR
SPAR&TPAR ARC2-MODE=SPAR+S&T
≥1
&
EVOLV_FAULT
8200001B6A & TIME OVER1 ARC1 FT CB1_94TT
&
TEVLV
t 0 & EVOLV_FAULT
TIME OVER2 ARC2 FT CB2_94TT
&
0.01-300.00s
Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are unconditionally generated when a
single phase tripping occurs in TPAR.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 326 -
6F2S1927 (0.18)
Condition of CB#1
800001EBBA SPAR1_COND
ARC1_SPAR_COND
TSPAR1_SUB
t 0
&
800001EBBB SPAR1_SUB_START
0.01 – 300.00 s &
800001EBBC SPAR1_SUB_COND
Always ‘1’
TSPAR2
ARC2-S1 IN-PROG t 0 8000021B63
& ARC2_SPAR
&
800002EBB9 SPAR2_START 0.01 – 300.00 s
& ≥1
Condition of CB#2
800002EBBA SPAR2_COND
ARC2_SPAR_COND
TSPAR2_SUB
t 0
&
800002EBBB SPAR2_SUB_START
0.01 – 300.00 s &
800002EBBC SPAR2_SUB_COND
TRR1
To TRC
t 0
ARC1-S1 TRR ARC1-FT CB1_94TT
0.01 – 310.00 s
TRR2
t 0
ARC2 TRR ARC2-FT CB2_94TT
0.01 – 310.00 s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 327 -
6F2S1927 (0.18)
ARC1-VCHK
ARC2-VCHK
For Issuing for CB
From Initiation TTPAR1
8000011B63
t 0
& ARC1_TPAR
ARC1 IN-PROG ARC1-S1 IN-PROG
&
810001EBBD TPAR1_START 0.01 – 300.00 s
& ≥1
From Condition in CB#1
ARC1_TPAR_COND
810001EBBE TPAR1_COND
TTPAR1_SUB
t 0
&
&
810001EBBF TPAR1_SUB_START
0.01 – 300.00 s
810001EBC0 TPAR1_SUB_COND
TPAR2_START
TRR1 To TRC
t 0 ARC1-S1 TRR CB1_94TT
ARC1-FT
0.01 – 310.00 s
TRR2
t 0 ARC2 TRR ARC2-FT CB2_94TT
0.01 – 310.00 s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 328 -
6F2S1927 (0.18)
ARC1-VCHK
ARC2-VCHK Issuing for CB#1
TSPAR1
Condition in CB#1 t 0 8000011B63
ARC1_SPAR_COND & ARC1_SPAR
&
ARC1_TPAR_COND 800001EBB9 SPAR1_START 0.01 – 300.00 s
& ≥1
From Initiation
ARC1 IN-PROG
800001EBBA SPAR1_COND
ARC1-S1 IN-PROG
TSPAR1_SUB
t 0
&
800001EBBB SPAR1_SUB_START 0.01 – 300.00 s &
800001EBBC SPAR1_SUB_COND
TTPAR1
8000011B63
t 0
& & ARC1_TPAR
810001EBBD TPAR1_START 0.01 – 300.00 s
& ≥1
810001EBBE TPAR1_COND
TTPAR1_SUB
t 0
&
&
810001EBBF TPAR1_SUB_START
Condition in CB#2 0.01 – 300.00 s
ARC2_SPAR_COND
810001EBC0 TPAR1_SUB_COND
ARC2_TPAR_COND Issuing for CB#2
TSPAR2
t 0 8000021B63
& ARC2_SPAR
From Initiation &
800001EBB9 SPAR2_START 0.01 – 300.00 s
ARC2-S1 IN-PROG & ≥1
800001EBBA SPAR2_COND
TSPAR2_SUB
t 0
&
800001EBBB SPAR2_SUB_START
0.01 – 300.00 s &
800001EBBC SPAR2_SUB_COND
TTPAR2
8000021B64
t 0
& & ARC2_TPAR
S1 IN-PROG 810002EBBE TPAR2_START 0.01 – 300.00 s
& ≥1
810002EBBF TPAR2_COND
TTPAR2_SUB
t 0
&
From Reclose sequence &
TPAR1_START 810002EBC0 TPAR2_SUB_START
0.01 – 300.00 s
0.01 – 310.00 s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 329 -
6F2S1927 (0.18)
(xi) Shot2 to Shot5 for CB#1 –settings (TD_MS2, TRR2 and others)
The ARC1 logic for shot 2-shot5 is illustrated in Figure 2.24-17. Shots 2-5 are applicable for a
CB#1 only. For example, two shots (Shot2 and Shot3, i.e., [ARC_NUM]=S3) are required
following the Shot1, the user should set the [TS_MS2]/[TS_MS3] and [TRR2]/[TRR3]. The user
should program to inject a permission signal for the Shot2 and Shot3 at PLC connection points
‘ARC1-S2 COND’ and ‘ARC1-S3 COND’, as shown in Figure 2.24-17. Note that the CB will be
tripped in three-phases forcibly even if a GEN.TRIP-A (TRIP COMMAND-A) signal is only
generated, because the ‘CB1_BRIDGE’ signal is generated during the Shot 2-Shot5.
Initiation
TD_MS2
ARC1 IN-PROG ARC1-S2 Issuing
S t 0 8100011B67
& IN-PROG
& ARC1 SHOT2
R
0.01 – 300.00 s
TD_MS3 A
ARC1-S3
& S
IN-PROG t 0 8200011B68
R
& ARC1 SHOT3
0.01 – 300.00 s
& S B
ARC1-S4 TD_MS4
R IN-PROG t 0 8300011B69
Shot counter & ARC1 SHOT4
& S 0.01 – 300.00 s
SHOT_2ND
R C
SHOT_3RD ARC1-S5 TD_MS5
SHOT_4TH IN-PROG t 0 8400011B6A
SHOT_5TH & ARC1 SHOT5
0.01 – 300.00 s
≥1 D
Shot number
TRR2
ARC-NUM To TRC
t 0
ARC1-S2 TRR ARC1 FT CB1_94TT
A Done issuing ARC1 SHOT2
0.01 – 310.00 s
B Done issuing ARC1 SHOT3
TRR3
C Done issuing ARC1 SHOT4
t 0 ARC1 FT CB1_94TT
ARC1-S3 TRR
D Done issuing ARC1 SHOT5
8100011B67 0.01 – 310.00 s
810001EBC9 ARC1-S2 COND
TRR 4
8100011B68
t 0 ARC1-S4 TRR ARC1 FT CB1_94TT
810001EBCA ARC1-S3 COND
8100011B69
810001EBCB ARC1-S4 COND 0.01 – 310.00 s
8100011B6A TRR 5
810001EBCC ARC1-S5 COND t 0 ARC1-S5 TRR ARC1 FT CB1_94TT
0.01 – 310.00 s
8800011B62
CB1_BRIDGE
Shot2–Shot5 for CB#1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 330 -
6F2S1927 (0.18)
800001EBCD CB1_MANUAL_CLOSE
0.01-10.00s
810002EBCA CB2_MANUAL_CLOSE
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 331 -
6F2S1927 (0.18)
0.1s
CB1_ALLPH_CLOSE
ARC-SUCCHK=OFF
CB2_ALLPH_CLOSE Initiation
ARC1 SHOT RS ARC1 RS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 332 -
6F2S1927 (0.18)
Initiation
FT ARC1 UNREADY S 8800011B74 For user’s programming
≥1
R ARC1-SUB_INIT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 333 -
6F2S1927 (0.18)
Fault current
Closed
CB#1 status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
ARC1 FT
Figure 2.24-21 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; operation is successful
Note: The permissive signal ‘ARC1-VCHK’ is required in the TPAR mode, but is omitted
here for the sake of clarity. The pulse width of the ‘ARC1 CLOSE COMMAND’
signal is defined using the setting [TCCW1].
(ii) Single shot scheme for an Arcing fault; CB#1 fails to reclose
Figure 2.24-22 also shows the single shot scheme. However, the CB#1 fails to reclose on
receiving the ‘ARC1 CLOSE COMMAND’ so that the ARC function initiates the ‘ARC1 CLOSE
FAIL’ signal within the setting time [TARCDSUC]. Consequently, the ARC function goes to the
final trip (ARC1 FT) stage so that the ARC will not issue another ‘ARC1 CLOSE COMMAND’
signal hereafter.
Fault current
Closed
CB#1 Status CB fails to be closed.
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
Figure 2.24-22 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; CB#1 fails to reclose
Note: The permissive signal ‘ARC1-VCHK’ is required in the TPAR mode for the ARC1
Closed
CB#1 Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
ARC1 FT
Figure 2.24-23 Single shot ARC scheme [ARC-NUM]=S1 for Permanent fault
Note: The permissive signal ‘ARC1-VCHK’ is required for the ARC SHOT1 operation, but
is omitted here for the sake of clarity.
(iv) Single shot scheme for an Arcing fault; fault removed by a backup
CB
Figure 2.24-24 shows the single shot scheme for an Arcing fault, but tripping is not executed
due to the failure of the CB#1. Therefore, the operation of the ARC function is reset in the
setting time [TRESET] before the duration of dead timer [TTPAR1] expires. Consequently, the
ARC function determines that the local CB#1 cannot be tripped to clear the fault.
Fault current
Fault cleared by tripping the backup CB at the remote end†
Closed
CB#1 Status CB at the local end fails to open
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1-S2 IN-PROG
ARC1 SHOT2
ARC1-S3 IN-PROG
ARC1 SHOT3
ARC1 CLOSE
COMMAND
ARC1 FT
Reset
ARC RESET [TRESET]
)
Figure 2.24-24 Single shot scheme [ARC-NUM]=S1 for an Arcing fault; remote CB† tripped
†Note:the fault is removed by the tripping of the CB at the remote end; hence, the fault
current will no longer flow.
Fault current
Closed
CB#1 Status
Open
Operated
Relay operation
Issued
GEN.TRIP
ARC1 IN-PROG
ARC1-S1 IN-PROG
ARC1-S2 IN-PROG
ARC1-S3 IN-PROG
Closed
CB1 ALLPH
Open
CLOSE
2.24.6 Setting
ARC(Function ID:4A6001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
Comm Off / FT / SPAR /
TPAR / SPAR&TPAR
ARC1-MODE - Auto reclose mode in 1CB-system Off
/MPAR(NA†) /
Original
Off / FT / SPAR /
TPAR / SPAR&TPAR Auto reclose mode of Center-CB in 2CB-
ARC2-MODE - Off
/MPAR(NA†) / system
Original
FT / TPAR / ARC operation in multi phase ARC NO-LINK
ARC-MANOLK - FT
SPAR&TPAR condition
ARC-ORDER SIMUL / CB1 / CB2 - Turn of the 3-phase autoreclosing circuit start SIMUL
ARC-NUM S1 / S2 / S3 / S4 / S5 - Auto reclose maximum shot number S1
Check ARC-SucChk Off / On - Autoreclose success checking enable On
TARCSUC 0.10 - 100.00 s Autoreclose success checking time 0.30
FT-3pFault Off / On - Execute final trip in 3-phase fault mode Off
TRESET 0.01 - 300.00 s Autoreclose reset time under CB closed 0.30
TEVLV 0.01 - 300.00 s Evolving fault waiting time 0.30
T3PTP 0.01 - 10.00 s IN-PROG duration time for 3PTP 1.00
ARC1 ARC1-EN Off / On - 0 Off
Time TREADY1 0.0 - 600.0 s Autoreclose1 ready check time 60.0
TSPAR1 0.01 - 300.00 s Autoreclose1 SPAR dead time 0.80
TSPAR1_SUB 0.01 - 300.00 s Autoreclose1 sub-SPAR dead time 300.00
TTPAR1 0.01 - 300.00 s Autoreclose1 TPAR dead time 0.60
TTPAR1_SUB 0.01 - 300.00 s Autoreclose1 sub-TPAR dead time 300.00
TORGAR1 0.01 - 300.00 s Autoreclose1 user original ARC dead time 300.00
TORGAR1_SU
0.01 - 300.00 s Autoreclose1 sub user original ARC dead time 300.00
B
TRR1 0.01 - 310.00 s Autoreclose1 reset time 2.00
TCCW1 0.01 - 10.00 s Autoreclose1 ARC command pulse width 0.20
ARC2 ARC2-EN Off / On - 0 Off
Time TREADY2 0.0 - 600.0 s Autoreclose2 ready check time 60.0
TSPAR2 0.01 - 300.00 s Autoreclose2 SPAR dead time 0.80
TSPAR2_SUB 0.01 - 300.00 s Autoreclose2 sub-SPAR dead time 300.00
TTPAR2 0.01 - 300.00 s Autoreclose2 TPAR dead time 0.60
TTPAR2_SUB 0.01 - 300.00 s Autoreclose2 sub-TPAR dead time 300.00
TORGAR2 0.01 - 300.00 s Autoreclose2 user original ARC dead time 300.00
TORGAR2_SU
0.01 - 300.00 s Autoreclose2 sub user original ARC dead time 300.00
B
TRR2 0.01 - 310.00 s Autoreclose2 reset time 2.00
TCCW2 0.01 - 10.00 s Autoreclose2 ARC command pulse width 0.20
Multi MultiShot-EN Off / On - 0 Off
Time TD_MS2 0.01 - 300.00 s 2nd shot ARC dead time 20.00
TRR_MS2 0.01 - 310.00 s 2nd shot ARC reset time 30.00
TD_MS3 0.01 - 300.00 s 3rd shot ARC dead time 20.00
TRR_MS3 0.01 - 310.00 s 3rd shot ARC reset time 30.00
TD_MS4 0.01 - 300.00 s 4th shot ARC dead time 20.00
TRR_MS4 0.01 - 310.00 s 4th shot ARC reset time 30.00
TD_MS5 0.01 - 300.00 s 5th shot ARC dead time 20.00
TRR_MS5 0.01 - 310.00 s 5th shot ARC reset time 30.00
†Neglect “MPAR mode” in GRD200A.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 338 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 339 -
6F2S1927 (0.18)
2.24.7 Data ID
Signal monitoring point
ARC(Function ID: 4A6001)
Element ID Name Description
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 340 -
6F2S1927 (0.18)
8200001B6A EVOLV-FAULT TIME OVER Time over of evolved fault under S&T mode
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 341 -
6F2S1927 (0.18)
8000001B84 SHOT_MULTI Signal of the second and the following ARC shots
(2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 342 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 343 -
6F2S1927 (0.18)
.69)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 344 -
6F2S1927 (0.18)
Line VT
Reclosing
Bus VT
VCHK(G) ARC(G)
Permissive
VCHK1 and VCHK2(Single CB or 1.5CB) [36 and 39 models]
Busbar G CB#1 Busbar H
Line1
Line VT
Bus VT
VCHK1(G ARC1(G)
)
Permissive
Busbar G
Bus VT
Line VT1
VCHK1(G)
Busbar H
CB#1 ARC1(G)
Line1
Line VT2
VCHK2(G)
CB#2 ARC2(G)
Line2
CB
─────────────────────────────────────────────────────────────────
Note: The VCHK operation is dependent upon the selection of models; several models do not
support it. For more information, see Appendix: Ordering.
Table 2.25-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.25.1 Single CB (VCHK) ✓ ✓ ✓ NA NA NA NA
2.25.2 1.5CB system (VCHK1/2) NA NA NA NA NA ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
Check zone A1 B1 C1 D1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 346 -
6F2S1927 (0.18)
A1, C1, D1: Voltage check A2, C2, D2: Voltage check
a. VCHK1 check zone B1: Synchronism check b. VCHK2 check zone B2: Synchronism check
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 347 -
6F2S1927 (0.18)
S = SYN-Angle(SYN1-Angle)
S = SYN2-Angle
VL1 VL1
s s
1 VB 2
VL2
V1 V2
VCHK-OVB or VCHK-OVL2 or
VCHK-OVL VCHK-OVL
a. SYN(SYN1) b. SYN2
This function performs three checks: (1) checking voltage difference, (2) checking
frequency difference, and (3) checking phase difference. The following variables represent
algebraic expression used in these checking:
VB = Bus-bar voltage
VL1 = Line1 voltage
VL2 = Line2 voltage
ΔV1 = Voltage difference between Bus-bar and Line1
ΔV2 = Voltage difference between Line2 and Line1
fVB = frequency of VB
fVL = frequency of VL1
fVL2 = frequency of VL2
f= slip cycle
Δf1 = frequency difference between Bus-bar and Line1
Δf2 = frequency difference between Line2 and Line1
θ1= phase difference between VB and VL1
θ2 = phase difference between VL2 and VL1
SYN1-dV = Voltage difference setting [SYN-dV(SYN1-dV)]
SYN2-dV = another voltage difference setting [SYN2-dV]
VCHK-OVB = voltage setting for Bus-bar [VCHK-OVB]
VCHK-OVL = voltage setting for Line1 [VCHK-OVL]
VCHK-OVL2 =voltage setting for Line2 [VCHK-OVL2]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 348 -
6F2S1927 (0.18)
The VCHK can have the decision of synchronism between the running voltage and the
incoming voltage when the following items (i) to (iv) are satisfied:
(i) Voltage magnitudes
The magnitude of the running voltage and the incoming voltage are greater than
the SYN(SYN1) and SYN2 settings:
For SYN(SYN1): VB ≥ [VCHK-OVB] and VL ≥ [VCHK-OVL]
For SYN2: VL2 ≥ [VCHK-OVL2] and VL ≥ [VCHK-OVL]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 349 -
6F2S1927 (0.18)
VTratioatLine
K = VTratioatbusbar
whereas, ‘VT ratio at Line’ is obtained from the actual value in VCT
ratio setting corresponding with scheme switch [SYN-VLine], and ‘VT ratio
at busbar’ is obtained from the actual one corresponding with the scheme
switch [SYN-VBus]. We shall see the scheme switches in the succeeding
section.
Note: When Off is set for the scheme switch [SYN-dfEN(SYN1-dfEN)], the
VCHK(VCHK1) abandons the frequency difference condition from
synchronism requirements. Similarly, the frequency difference condition is
not valid when [SYN2-dfEN] = Off.
Setting [SYN-Angle(SYN1-Angle)]
∆f > (2.25-1)
180° × Setting [T_SYN(T_SYN1)]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 350 -
6F2S1927 (0.18)
where,
Δf= Frequency-difference (or cycle-slip in Hertz)
2 × Setting [SYN-Angle(SYN1-Angle)] 1
Time = × (2.25-3)
360° ∆f[Hz]
Setting [T_SYN(T_SYN1)]
2 × Setting [SYN-Angle(SYN1-Angle)] 1 (2.25-4)
< ×
360° ∆f[Hz]
Equations rearrangements:
Setting [T_SYN(T_SYN1)]
Setting [SYN-Angle(SYN1-Angle)] 1 (2.25-5)
< ×
180° ∆f[Hz]
1 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [T_SYN(T_SYN1)] 1
> ÷ (2.25-6)
∆𝑓[𝐻𝑧] Setting [SYN-Angle(SYN1-Angle)] 180°
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [T_SYN(T_SYN1)]
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYN-Angle(SYN1-Angle)] 1 (2.25-7)
< ×
180° ∆𝑓[𝐻𝑧]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 351 -
6F2S1927 (0.18)
VL : fVL=50.02Hz
VB : fVB=50.00Hz
time
Δf Δf Δf
VL
50s SYN1-Angle
VB Synchronism zone
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 352 -
6F2S1927 (0.18)
1Note: For more information on VCT, see Chapter Technical description: Transfer
module. For external connection, see Appendix: Typical external connection.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 353 -
6F2S1927 (0.18)
Line1
VCT1
Line VT
(Phase-A)
Va
VL1 (Va)
VL2 (Vb)
Bus-bar VT
Bus-bar
(Three-phase)
Vc Vb
VL3 (Vc)
a. Phasor diagram in Line1
Vs (Vs)
Vs
V Line1 (Vs)2
VBus-bar (Va)3
Figure 2.25-6 Example 1: Input voltages and respective phasor diagram for SYN(SYN1)
1Note: The structure of VCT is dependent on the VCT type. (See chapter Technical
description: Transformer module)
2 Note:VBus-bar is Running voltage.
3Note: V
Line1 is Incoming voltage.
Figure 2.25-6 shows the VCT input voltages and phases from Bus-bar and Line, and
shows the phase relationship between the running voltage and the incoming voltage. In this
case, configure the settings in accordance with Figure 2.25-6 and Table 2.25-7.
Table 2.25-7 Setting for example 1
Output voltage at VT Bus-bar VT= Three phase
Line VT= Phase-A
Input voltage at VCHK Running voltage (Va)= Phase-A (Bus-bar VT)
Incoming voltage (Vs)= Phase-A (Line1 VT)
VCHK Setting4 [SYN-VBus] = V-L1
[SYN-VLine]= Vs
4Note: Set Vs for the scheme switch [SYN-VLine]. This is because Vs and V-L1 are in the
same phase.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 354 -
6F2S1927 (0.18)
Line1 VCT
Line VT
(Phase B-C)
Va
Va (VL1)
Vb (VL2)
Bus-bar VT Vc
(Three Phase)
Bus-bar
Vb
Vc (VL3) Vbc
a. Phasor diagram in Bus-bar
Vs (Vs) Vs
VLine1 (Vs)1
VBus-bar (Vbc)2
Figure 2.25-7 Example 2: Input voltages and respective phasor diagram for SYN(SYN1)
1 Note: VBus-bar is Running voltage.
2Note: VLine1 is Incoming voltage.
Similarly, Figure 2.25-7 shows the VCT input voltages and phases from Bus-bar and
Line1. In this case, configure the settings in accordance with Figure 2.25-7 and Table 2.25-8.
Table 2.25-8 Setting for example 2
Output voltage at VT Bus-bar VT= Three phase
Line VT= Phase-BC
Input voltage at VCHK Running voltage(Vb and c)= Phase-B and C (Bus-bar VT)
Incoming voltage (Vs)= Phase-BC (Line VT)
VCHK Setting3 [SYN-VBus] = V-L23
[SYN-VLine]= Vs
3Note: Vs is set for the scheme switch [SYN-VLine]. This is because the resultant phase
of V-L2, V-L3 and Vs is same.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 355 -
6F2S1927 (0.18)
Line1
VCT
Line VT
(Three phase)
Va (VL1) Va
Vb (VL2)
Bus-bar VT
Bus-bar
(Phase C)
Vc Vb
Vc (VL3)
a. Phasor diagram in line1
Vs (Vs) Vs
VLine (Vc)1
VBus-bar (Vs)2
Figure 2.25-8 Example 3: Input voltages and respective phasor diagram for SYN(SYN1)
1 Note: VBus-bar is Running voltage.
2Note: VLine1 is Incoming voltage.
The configuration of inputs voltages and phases is done as shown in Figure 2.25-8. In
this case, configure the settings in accordance with Figure 2.25-8 and Table 2.25-9.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 356 -
6F2S1927 (0.18)
Bus-bar
VCT
Bus-bar VT
(Phase-B)
Line VT
(Three-phase) VL2 (V-L2)
VL3 VL2
VL3 (V-L3)
a. Phasor diagram in Line
Line2
VS (Vs) VS
Line2 VT
(Phase-B) b. Phasor diagram in Busbar
VS2 (Vs2)
VS2
VBus-bar (VS)
VLine2 (VS2)
Figure 2.25-9 Input voltages and respective phasor diagram for SYN1 and SYN2
1Note: V
Bus-bar is Running voltage. VLine is Incoming voltage.
2Note: V
Line2 is Running voltage. VLine1 is Incoming voltage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 357 -
6F2S1927 (0.18)
When VCHK1 and VCHK2 are used in 1.5CB system, set the scheme switches [SYN-
VLine], [SYN-VBus], and [SYN-VLine2]. For example, the settings in Figure 2.25-9 are applied
when VCHK 1 and VCHK2 are applied in the 1.5CB system.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 358 -
6F2S1927 (0.18)
T_DB_DL
8100011B61 UVL 8200011B70
& t 0
UVL &
0.01-100.00S
On
ARC-DB_DL(ARC1-DB_DL)
8300011B71
OVB
T_SYN(T_SYN1) 8300011B72
&
t 0 &
OVL
0.01-100.00S
SYN-dƟ 8400011B64
ARC-SYN(ARC1-SYN1) On
(SYN1-dƟ
)
)
8500011B65 ARC-NOVCHK(ARC1-NOVCHK) On
SYN-dV )
(SYN1-dV
)
SYN-df 8600011B66
(SYN1-df)
SYN-dfEN ≥1
(SYN1-dfEN) On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 359 -
6F2S1927 (0.18)
OVL
T_DL2_DL
UVL 8200021B6A
& t 0
&
0.01-100.00S
ARC2-DL2_DL ON
8300021B6B
OVL2
T_SYN2 8300021B6C
&
t 0 &
OVL
0.01-100.00S ARC2-SYN2 ON
8400021B62
SYN2-dƟ
8500021B63 ARC2-NOVCHK ON
SYN2-dV
8600021B64
SYN2-df
≥1
SYN2-dfEN
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 360 -
6F2S1927 (0.18)
2.25.7 Setting
VCHK(Function ID:4A8001) for 3D, 3E, and 3F software models
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
ARC-VCHK-
Off / On - VCHK enabling switch Off
EN
VCHK V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1(NA†) / V2-
L2(NA†) / V2-L3(NA†)
SYN-Vbus - Running Voltage V3
/ V2-L12(NA†) / V2-
L23(NA†) / V2-
L31(NA†) /
Vs / Vs2
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
V2-L1(NA†) / V2-
L2(NA†) / V2-L3(NA†)
SYN-Vline - Incoming Voltage V-L1
/ V2-L12(NA†) / V2-
L23(NA†) / V2-
L31(NA†) /
Vs / Vs2
VCHK-OVB 10 - 150 V Voltage for the checking Live-Bus 51
VCHK-UVB 10 - 150 V Voltage for the checking Dead-Bus 13
VCHK-OVL 10 - 150 V Voltage for the checking Live-Line 51
VCHK-UVL 10 - 150 V Voltage for the checking Dead-Line 13
SYN-Angle 0 - 75 deg Difference angle for the checking SYN 30
SYN-dV 0 - 150 V Difference voltage for the checking SYN 150
df Switch for the checking SYN for difference
SYN-df Off / On - Off
frequency
SYN-df 0.01 - 2.00 Hz Difference frequency for the checking SYN 1.00
Voltage check Live-Bus & Dead-Line is
ARC-LB_DL Off / On - Off
applied to ARC
Voltage check Dead-Bus & Live-Line is
ARC-DB_LL Off / On - Off
applied to ARC
Voltage check Dead-Bus & Dead-Line is
ARC-DB_DL Off / On - Off
applied to ARC
ARC-SYN Off / On - Voltage check SYN is applied to ARC Off
ARC-NOVCHK Off / On - Voltage check is not applied to ARC On
Time T_LB_DL 0.01 - 100.00 s Voltage check time Live-Bus and Dead-Line 0.05
T_DB_LL 0.01 - 100.00 s Voltage check time Dead-Bus and Live-Line 0.05
T_DB_DL 0.01 - 100.00 s Voltage check time Dead-Bus and Dead-Line 0.05
T_SYN 0.01 - 100.00 s Voltage check time SYN1 1.00
T_OVL3P 0.01 - 100.00 s Voltage check time 3phase Live-line 0.05
†Selection is not available in GRD200 relay.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 361 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 362 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 363 -
6F2S1927 (0.18)
2.25.8 Data ID
Signal monitoring point for 3D, 3E, and 3F software models
VCHK(Function ID: 4A8001)
Element ID Name Description
8000011B23 ARC-VCHK Voltage check for autoreclose
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 364 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 365 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The section here illustrates a tripping circuit for three-phase breaker. The trip circuit
for phase-segregated breaker is only available in 36 or 39 models (jump to section
2.27).
Table 2.26-1 TRC comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.26 Three-phase tripping ✓ ✓ ✓ ✓ ✓ NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 366 -
6F2S1927 (0.18)
FC1-CR
FC1-ABR OPT-TRIP
FC1-BCR Protection
GEN.TRIP
FC1-CAR functions
Sub-signal
FC2-TRIP-A GEN.ARC-BLOCK
generation CBF
FC2-TRIP-B
FC2-TRIP-C
ARC-D
FC2-TRIP
FC2-ARC-BLOCK GEN.TRIP_ALARM
FC2
FC2-ALARM
Alarm signal
OPT.PHASE-A Recording
FC2-AR generation
OPT.PHASE-B function
FC2-BR
OPT.PHASE-C
FC2-CR
FC2-ABR OPT.PHASE-N
FC2-BCR
FC2-CAR
CBF_RETRIP
CBF CBF_ARC-BLOCK
Figure 2.26-1 shows that the function is made with following logics:
Collection: The signals, received from the various protection functions (shown as
‘FC18’ and others; see Table 2.26-2 and Table 2.26-4), are gathered in the Trip-
command collection logic.
Generation: CB trip signal generation, Sub-signal generation for blocking ARC§, and
Alarm-signal generation logics are provided.
A binary output (BO†) circuit must be selected in order to energize the trip coil of the CB.
That is, the user should make the connection between the CB trip coil and the BO; the drive
signal should be outputted (i.e., ‘TRIP COMMAND’ †). The Alarm-signal generation logic
operates to provide a trigger signal for the recording function‡.
†Note:The internal connection between the TRC function and the BIO should be
performed in the BIO settings or the PLC programming. As the PLC monitoring
point “TRIP COMMAND” is designated using Element ID ‘8300001B78’, the user
must program it for a preferred BO circuit using the settings [Input signal1] to
[Input signal8] for each BO and for each binary IO module. The externally wired
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 367 -
6F2S1927 (0.18)
connection between the BIO module and trip coil circuit is made at the IED
terminals. For more information with regard to the BO circuit concerning the
Element ID (Data ID), see Chapter Technical description: Binary IO module.
§Note: ARC and CBF functions are discussed separately. See Chapter Relay application.
‡Note: For information on recording, see Chapter Recording function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 368 -
6F2S1927 (0.18)
Table 2.26-3 illustrates CBF function can generate a re-trip signal and an ARC-BLOCK signal.
Table 2.26-3 Signals coming from CBF function
Signals issued in the CBF
Protection function Note
CBF_RETRIP CBF_ARC-BLOCK
CBF X X
Note: ‘X’ represents a Valid signal for the TRC’. ‘CBF_ARC-BLOCK’ signal is grouped
with the ‘FC*_OPT_ARC-BLOCK’ signal in the Sub-signal generation scheme.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 369 -
6F2S1927 (0.18)
The TRC logic has PLC connection points, which the user can program for issuing the
trip command. For example, if the user wishes to trip the CB using signals generated by
external relays, the signals can be connected to the TRC logic using the following PLC
connection points: TRIP-A_ADD, TRIP-B_ADD, TRIP-C_ADD and TRIP_ADD.
Protection 8000001B60
functions FC*-OPT-TRIP_A
OPT-TRIP-A
≥1
FC01
800000EBB3 TRIP-A_ADD
FC02
8100001B61
FC*-OPT-TRIP_B
OPT-TRIP-B
≥1
810000EBB4 TRIP-B_ADD
FC40
8200001B62
FC*-OPT-TRIP_C OPT-TRIP-C
≥1
820000EBB5 TRIP-C_ADD
8300001B63
OPT-TRIP
FC*-OPT-TRIP
≥1
830000EBB6 TRIP_ADD
The “GEN.TRIP” signal is transferred to the ARC function to initiate the reclose
operation of the CB.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 370 -
6F2S1927 (0.18)
830000EBB2 ADD_OPT_COM
8000001B60
Trip-command collection scheme
OPT-TRIP-A To Alarm signal generation
8100001B61
OPT-TRIP-B
GEN.TRIP
≥1
8200001B62 To ARC-D function
8300001B6F
OPT-TRIP-C
8300001B63 & ≥1 GEN.TRIP
OPT-TRIP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 371 -
6F2S1927 (0.18)
8500001B65
Protection
functions FC*-ARC-BLOCK
FC01 To ARC-D function
≥1 8500001B79
FC02
≥1 GEN.ARC-BLOCK
FC40
From CBF function
CBF CBF-ARC-BLOCK
FC*-OPT-BR ≥1 8000001B72
OPT-BR &
≥1 OPT.PHASE-B
890000EBB9 OPT.P-B_ADD
8200001B68
FC40
8000001B73
OPT-CR ≥1 &
FC*-OPT-CR OPT.PHASE-C
≥1
8A0000EBBA OPT.P-C_ADD
8000001B74
8400001B69 &
OPT.PHASE-N
FC*-OPT-ABR OPT-ABR
≥1
FC*-OPT-BCR OPT-BCR
≥1
8D0000EBBC OPT.P-BC_ADD
8600001B6B
FC*-OPT-CAR OPT-CAR
≥1
8E0000EBBD OPT.P-CA_ADD
8400001B64
FC*_OPT-ALARM GEN.ALARM ≥1
≥1
840000EBB7 OPT-ALARM_ADD
800000EBBE OPT.P-N_ADD
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 372 -
6F2S1927 (0.18)
When an additional relay, external to the IED is utilized, an alarm signal can be provided,
indicating for example a Line-to-Line (LL) fault and others. If the user wishes to record the
alarm, then PLC connection points ‘OPT.P-A_ADD’ and others can be used. If the additional
relay is designed to operate for a ground fault, use the alternative PLC connection point
‘OPT.P-N_ADD’
2.26.4 Setting
(No setting items exist)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 373 -
6F2S1927 (0.18)
2.26.5 Signal
Signal monitoring points
TRC-D (Function ID: 4A1001)
Element ID Name Description
8100001BB1 ADD_FS Additional fail-safe command
8500001B79 GEN.ARC-BLOCK Signal to block the ARC operation with the protection functions and CBF
8500001B65 OPT-ARC-BLOCK Signal to block the ARC operation generated by the protection functions
810000EBB1 ADD_FS Reception of the result signal of the check relay (fail-safe)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 374 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 375 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The section here is illustrates the trip circuit for phase-segregated breaker, which is
only available in 36 and 39. For the other models (3D,3E,3F,30, and 32), go back to
section ion. 2.26.
Table 2.27-1 TRC comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
2.27 Segregated phase tripping NA NA NA NA NA ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 376 -
6F2S1927 (0.18)
Figure 2.26-1 shows that the function is made with following logics:
Collection: The signals, received from the various protection functions (shown as
‘FC18’ and others; see Table 2.26-2 and Table 2.26-4), are gathered in the Trip-signal
collection logic.
Generation: CB trip signal generation, Sub-signal generation for blocking ARC§, and
Alarm-signal generation logics are provided.
A binary output (BO†) circuit must be selected in order to energize the trip coil of the
CB#1 and CB#2. That is, the BOs should be made the connection with the CB#1 and CB#2 trip
coils; the drive signal should be outputted (i.e., ‘TRIP-COMMAND1-A,-B,-C’ and ‘TRIP-
COMMAND2-A,-B,-C’†). The Alarm-signal generation logic operates to provide a trigger signal
for the recording function‡.
†Note:The internal connection between the TRC function and the BIO module should be
performed using the BIO settings or the PLC programming. The user can program
the connection the PLC monitoring point ‘TRIP-COMMAND1-A (8000001B20) etc.’
with preferred BO circuits using the settings [Input signal1] etc. of each BO on the
BIO module. The externally wired connection between the BIO module and trip
coil circuit is made at the IED terminals. For more information with regard to the
BO circuit concerning the Element ID (Data ID), see Chapter Technical
description: Binary IO module.
§Note: Autoreclose (ARC) and other protection functions are discussed separately. See
Chapter Relay application, respectively.
‡Note: For information on recording, see Chapter Recording function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 377 -
6F2S1927 (0.18)
FC2-OPT-TRIP-B
OPT-TRIP B
FC2-OPT-TRIP-C Protection
GEN.TRIP
FC2-OPT-TRIP functions
GEN.TRIP-A
FC2-ARC-BLOCK
FC2 GEN.TRIP-B
FC2-OPT-ALARM GEN.TRIP-C
Sub-signal
FC2-OPT-AR CBF
generation
FC2-OPT-BR GEN.ARC-BLOCK ARC
FC2-OPT-CR
FC2-OPT-ABR GEN.TRIP_ALARM
FC2-OPT-BCR
FC2-OPT-CAR Alarm signal OPT.PHASE-A Recording
generation OPT.PHASE-B function
OPT.PHASE-C
FC40-OPT-TRIP-A etc.
FC40 OPT.PHASE-N
CBF_RETRIP
CBF CBF_ARC-BLOCK
CB1_BRIDGE B
CB2_BRIDGE
ARC
CB1_94TT A
CB2_94TT
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 378 -
6F2S1927 (0.18)
UV 30 – – – X X (For 36 only) †
Table 2.26-3 illustrates CBF function generates a re-trip and blocking ARC signals.
Table 2.27-3 Signals coming from CBF function
Protection Signals issued in the CBF
Note
function CBF_RETRIP CBF_ARC-BLOCK
CBF Applicable Applicable (For 36 only)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 379 -
6F2S1927 (0.18)
The TRC logic has PLC connection points, which the user can program for issuing the
trip command. For example, if the user wishes to trip the CBs using signals generated by
external relays, the signals can be connected to the TRC logic using the following PLC
connection points: TRIP-A_ADD, TRIP-B_ADD, TRIP-C_ADD and TRIP_ADD.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 380 -
6F2S1927 (0.18)
Protection 8000001B60
functions FC*-OPT-TRIP_A
OPT-TRIP-A
≥1
FC01
800000EBB3 TRIP-A_ADD
FC02
8100001B61
FC*-OPT-TRIP_B
OPT-TRIP-B
≥1
810000EBB4 TRIP-B_ADD
FC40
8200001B62
FC*-OPT-TRIP_C OPT-TRIP-C
≥1
820000EBB5 TRIP-C_ADD
8300001B63
OPT-TRIP
FC*-OPT-TRIP
≥1
830000EBB6 TRIP_ADD
The “GEN.TRIP-A,-B,-C” signals are transferred to the ARC function to initiate the
reclose operation of the CBs.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 381 -
6F2S1927 (0.18)
To ARC
8200001BB2 GEN.TRIP-A
820000EBB2 ADD_OPT_COM GEN.TRIP-B
GEN.TRIP-C
Trip-command
collection scheme
8000001B6C
OPT-TRIP-A ≥1 8014281001 To CB#1
≥1
≥1 ≥1 TRIP COMMAND1-A
OPT-TRIP-B 8100001B6D
≥1 8014291001
≥1
≥1 TRIP COMMAND1-B
OPT-TRIP-C 8200001B6E ≥1
≥1 80142A1001
≥1 ≥1
OPT-TRIP ≥1 TRIP COMMAND1-C
≥1
& 80142C1001 To CB#2
&
≥1 TRIP COMMAND2-A
80142D1001
&
≥1 TRIP COMMAND2-B
80142E1001
& ≥1 TRIP COMMAND2-C
To Recording function
TRIP COMMAND1-A
≥1
& TRIP COMMAND1-B
TRIP COMMAND1-C
≥1
& TRIP COMMAND CB2 -A
TRIP COMMAND CB2 -B
≥1 & TRIP COMMAND CB2 -C
From CBF ≥1
&
CBF_RETRIP-A
CBF_RETRIP-B
CBF_RETRIP-C
From ARC
CB1_BRIDGE
CB2_BRIDGE
CB1_94TT
CB2_94TT
From PROT-COMMON
CB-SYSTEM=1CB
CB-SYSTEM=2CB
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 382 -
6F2S1927 (0.18)
≥1
FC40
From CBF function
CBF CBF-ARC-BLOCK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 383 -
6F2S1927 (0.18)
FC*-OPT-BR ≥1 8000001B72
OPT-BR &
≥1 OPT.PHASE-B
890000EBB9 OPT.P-B_ADD
8200001B68
FC40
8000001B73
FC*-OPT-CR OPT-CR ≥1 &
OPT.PHASE-C
≥1
8A0000EBBA OPT.P-C_ADD
8000001B74
8400001B69 &
OPT.PHASE-N
FC*-OPT-ABR OPT-ABR
≥1
FC*-OPT-BCR OPT-BCR
≥1
8D0000EBBC OPT.P-BC_ADD
8600001B6B
FC*-OPT-CAR OPT-CAR
≥1
8E0000EBBD OPT.P-CA_ADD
8400001B64
FC*_OPT-ALARM GEN.ALARM ≥1
≥1
840000EBB7 OPT-ALARM_ADD
800000EBBE OPT.P-N_ADD
When an alarm signal indicating a Line-to-Line (LL) fault and others is provided
externally, the user can also record it as the alarm by the use of PLC connection points ‘OPT.P-
A_ADD’ and others. If the additional relay being designed to operate for a ground fault is
available, use the alternative PLC connection point ‘OPT.P-N_ADD’.
2.27.4 Setting
No setting item exists in the TRC.
Tips: GRD200-36 and 39 models (i.e., 1+3-phase reclosing model) are designed for a fail-
safe relay. The TRC simply operates for three-phase tripping; therefore, there is
no setting item in the function. Incidentally, a single-phase trip command can be
issued by the main relay, when main and fail-safe relays protect the line (ref.
section 2.24.2(xvi)).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 384 -
6F2S1927 (0.18)
2.27.5 Data ID
Signal monitoring point
TRC(Function ID: 4A0001)
Element ID Name Description
8200001BB2 ADD_OPT_COM Additional operation command
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 385 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 386 -
6F2S1927 (0.18)
After the disappearance of the VT failure, the VTF function can take account of the VT
secondary circuit being in healthy condition in the three-phase; the operation of the VTF
function is reset2. Thus, the blocked relays are allowed to operate again. Incidentally, issuing
the VTF alarm is automatically removed and then the user can find resetting the VTF alarm.
1Note: The VTF function can block the operation in several relays, but it does not block
the operation in other relays. To know the blocking, refer sections of the respective
protection functions.
2Note: The user can programmable the operation using the setting and the PLC signals.
(2.62.0)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.28-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 387 -
6F2S1927 (0.18)
However, nonetheless the OCD/EFVTF relay is still running after the VTF detection,
issuing the VTF_DETECT signal is cleared, provided OPT-On is set for the settings [VTF1-EN]
and the [VTF2EN].
When issuing the VTF_DETECT signal continues longer than ten seconds, the signal
VTF_DETCT clears to generate the VTF_ALARM signal.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 388 -
6F2S1927 (0.18)
The user can select either the VTF1 or VTF2 criteria using the using the scheme switch
[VTF1EN] or [VTF2EN].
VTF1 DETECT
8000001C20
A &
8100011C60 8000001B61
≥1 ≥1 t 0
8100001C21 VTF1_ALARM
UVVTF B t 0
1 S
C 8200001C22 1 10.0s
t 0
0.015s ≥1
1 R
From PROT-CCOMMON1
0.1s
OCD-AT ≥1 S
OCD-BT
≥1
&
OCD-CT R
& 1
t 0
1 &
10.0s
On ≥1
VTF1-EN OPT-On
VTF2 DETECT
8800001C27
OVGVTF & 8200021C60 8200021C60
≥1 t 0 VTF2_ALARM
1 t 0
1 S 10.0s
8400001C28
t 0
0.015s ≥1
EFVTF 1 R
≥1 0.1s ≥1
S
800000B62
≥1 &
R
VTF_ALARM
& To Automatic supervision
1
&
On ≥1
VTF2-EN OPT-On
To OC2
To EF2
To UV2
From PROT-COMMON1
To UVS2
To OV2
CB_ALLPH_CLOSE 1 To OVS2
0. 2s To OVG2
1 To OVN2
To OCN2
8000001B61 To DEFCAR2
≥1 ≥1
VTF_DETECT
From test
AMF_OFF3 1
800000EBB0 VTF_BLOCK
8100001BB1
810000EBB1 EXTERNAL_VTF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 389 -
6F2S1927 (0.18)
3Note: AMF feature is used for the test. To generate the AMF signal, see chapter User
interface: test-submenu.
If a PLC signal is injected at the PLC connection point “VTF_BLOCK”, the operation of
the VTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_VTF; the VTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_VTF.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 390 -
6F2S1927 (0.18)
2.28.4 Setting
VTF(Function ID: 490001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
VTF1 VTF1-EN Off / On / OPT-On - VTF1 scheme switch On
UVVTF 1.0 - 220.0 V Phase under voltage revel for VTF1 detection 20.0
VTF2 VTF2-EN Off / On / OPT-On - VTF2 scheme switch On
Threshold of over voltage detection in zero-
OVGVTF 1.0 - 220.0 V 20.0
sequence phase
0.10 - 0.50 - Threshold of over current in zero-sequence
EFVTF A 0.20 1.00
50.00 250.00 phase to block VTF2 detection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 391 -
6F2S1927 (0.18)
2.28.5 Signal
Signal monitoring point
VTF(Function ID: 490001)
Element ID Name Description
8400001C2B EFVTF EFVTF relay element operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 392 -
6F2S1927 (0.18)
After the disappearance of the CT failure, the CTF function can take account of the CT
secondary circuit being in healthy condition in the three-phase; the operation of the CTF
function is reset2. Thus, the blocked relays are allowed to operate again. Incidentally, issuing
the CTF alarm is automatically removed and then the user can find resetting the CTF alarm.
1Note: The CTF function can block the operation in several relays, but it does not block
the operation in other relays. To know the blocking, refer sections of the respective
protection functions.
2Note: The user can programmable the operation using the setting and the PLC signals.
(2.63.0)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.29-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 393 -
6F2S1927 (0.18)
However, nonetheless the OVGCTF relay is still running after the CTF detection, issuing
the CTF_DETECT signal is cleared, provided OPT-On is set for the scheme switch [CTF-EN].
When issuing the CTF_DETECT signal continues longer than ten seconds, the signal
CTF_DETECT clears to generate the CTF_ALARM signal.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 394 -
6F2S1927 (0.18)
8000001C23
EFCTF
&
1 8100001B60 8000001B61
≥1 t 0
CTF_ALARM
t 0
S
10.0s To Automatic supervision
t 0
0.015s ≥1
8100001C27 1 R
OVGCTF & 0.1s
On ≥1
CTF-EN OPT-On
& 1
From PROT-CCOMMON1
CB_ALLPH_CLOSE 1 To EF2
0.02s To BCD2
To OCN2
8000001B62
To UC2
≥1 ≥1
1
CTF_DETECT
From test3
AMF_OFF 1
800000EBB0 CTF_BLOCK
8100001BB1
810000EBB1 EXTERNAL_CTF
If a PLC signal is injected at the PLC connection point “CTF_BLOCK”, the operation of
the CTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_CTF; the CTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_CTF.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 395 -
6F2S1927 (0.18)
2.29.4 Setting
CTF(Function ID: 491001)
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
CTF-EN Off / On / OPT-On - CTF scheme switch On
CTF Threshold of overvoltage in zero-sequence
OVGCTF 1.0 - 220.0 V 20.0
phase to stop CTF detection
0.10 - 0.50 - Threshold of overcurrent in zero-sequence
EFCTF A 0.20 1.00
50.00 250.00 phase to have CTF detection
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 396 -
6F2S1927 (0.18)
2.29.5 Signal
Signal monitoring point
CTF(Function ID: 491001)
Element ID Name Description
8000001B61 CTF ALARM CTF alarm operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 397 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 2.30-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
1CB scheme selected ✓ ✓ ✓ ✓ ✓ NA NA
2.30.1
Selection of 1CB or 2CBs NA NA NA NA NA ✓ ✓
CB position decision ✓ ✓ ✓ ✓ ✓ ✓ ✓
2.30.2
CBs(#1/#2) pos. decision NA NA NA NA NA ✓ ✓
2.30.3 DS position decision ✓ ✓ ✓ ✓ ✓ NA NA
2.30.4(i) Dead-line detected by UV ✓ ✓ ✓ NA NA ✓ NA
2.30.4(ii) Dead-line detected by CB ✓ ✓ ✓ ✓ ✓ ✓ NA
2.30.5 Current change relay ✓ ✓ ✓ ✓ ✓ NA NA
2.30.6 Users logic switch ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 398 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 399 -
6F2S1927 (0.18)
Note: Both CB#1 and CB#2 can be supervised when the both auxiliary swathes are
connected with the IED.
The user should set On for the scheme switch [CB-SV] when the contact supervision
feature shall operate; set the time for the [TCBSV] to define the monitoring period, which the
user can have an option among 0 to 100 sec.
1.5CB system
Figure 2.30-2 shows the decision logic for 1.5CB system.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 400 -
6F2S1927 (0.18)
8000001BB0
8300001BBE ≥1
TCBSV
8000001B93
=1 1 t 0
8000001B87 & CB1-A_FAIL
8300001BBF ≥1
0–100S
8100001BB1
8300001BBE ≥1 TCBSV
8100001B94
8100001B88 =1 1 t 0
&
8300001BBF ≥1 CB1-B_FAIL
0–100S
8200001BB2
8300001BBE ≥1 TCBSV
t 0 8200001B95
8200001B89 =1 1
& CB1-C_FAIL
8300001BBF ≥1
0–100S 8300001B96
& ≥1 CB1-FAIL
1 0.00 to 0.03s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 401 -
6F2S1927 (0.18)
8000001BB0
8300001BBE ≥1
TCBSV
8000001B93
=1 1 t 0
8000001B87 & CB1-A_FAIL
8300001BBF ≥1
0–100S
8100001BB1
8300001BBE ≥1 TCBSV
8100001B94
8100001B88 =1 1 t 0
&
8300001BBF ≥1 CB1-B_FAIL
0–100S
8200001BB2
8300001BBE ≥1 TCBSV
t 0 8200001B95
8200001B89 =1 1
& CB1-C_FAIL
8300001BBF ≥1
0–100S 8300001B96
& ≥1 CB1-FAIL
8400001BB3 8500001B98
CB2-B_FAIL CB2-B_FAIL
8400001B8A
8500001BB4 8600001B99
CB2-C_FAIL CB2-C_FAIL
8500001B8B
8700001B9A
8600001BB5
CB2-FAIL CB2-FAIL
8600001B8C
To ARC
840000EBB3 CB2-A_NO_CONT
CB2-A_CLOSE CB1-ALLPH_CLOSE
840000EBBA CB2-A_NC_CONT CB2-B_CLOSE CB2-ALLPH_CLOSE
CB2-C_CLOSE CB-SYSTEM=1CB
8400001B8C To TRC,CBF
850000EBBB CB2-B_NC_CONT CB2-A_OPEN & CB-A_OPEN
8500001B8D
& CB-B_OPEN
CB2-B_OPEN
860000EBB5 CB2-C_NO_CONT 8600001B8E
& CB-C_OPEN
CB2-C_OPEN
8700001B8F
860000EBBC CB2-C_NC_CONT & CB-ALLPH_OPEN
CB2-ALLPH_OPEN
Note: CB2 logic is similar to CB1
logic; OPEN signals are
TRUE (1) and CLOSE
signals are FALSE (0) when
this logic is used in 1CB
system.
≥1 &
To OVG, OVN, UVP, DEFCAR
NO &
≥1 TCBLOSPH 8900001B91
NC ≥1 & ≥1 t 0
CB-LOSS_PHASE
Both 1 0.00 to 0.03s
CB2-Contact
&
CB2-CONTACT=BOTH
1CB
2CB
CB-System
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 402 -
6F2S1927 (0.18)
1 DS_OPEN
≥1
NO
NC ≥1
Both
DS-Contact &
Both
DS-SV
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 403 -
6F2S1927 (0.18)
UVLG-AB
UVLG-BC
UVLG-CA
8000001B60 DEAD_LINE_DETECT
A & TDLD
8100001B61 & t 0
UVLG 8000001B9C To SOTF-OC
B ≥1
8200001B62 DEAD_LINE_DETECT
t 0
C
0.00 to 3000.00s
≥1
UVLG-OR
& UVLG-AND
8400001B63
AB
8500001B64
UVLS BC
8600001B65
CA
≥1
UVLS-OR
&
UVLS-AND
DLDbyUV On
From
DLDbyCB On
CB decision logic &
CB_ALLPH_OPEN
Figure 2.30-4 Dead line detection logic with under voltage relays
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 404 -
6F2S1927 (0.18)
The pick-up threshold is set using the [OCD], which is from 0.05 A to 0.20 A at when Rated
current† is equal to 1 ampere. When the rated current is 5 ampere, the setting range is 0.25 A
to 1.00 A.
IM
IS
IN
0.1s
Figure 2.30-6 Current change check relay logic
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 405 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 406 -
6F2S1927 (0.18)
2.30.7 Setting
PROT_COMM(Function ID: 48A001) for 3D, 3E or 3F model
Range Default
Setting items Unit Contents Note
1A rating 5A rating 1A 5A
UVLS 5.0 - 130.0 V UV phase-phase relay operating value 77.0
UVLG 5.0 - 130.0 V UV phase-ground relay operating value 45.0
0.05 - 0.25 -
OCD A OCD relay operating value 0.10 0.50
0.20 1.00
CB-Contact NO / NC / Both - Kind of injected CB contact NO
TCBLOSPH 0.00 - 0.10 s CB loss phase time 0.03
CB-SV Off / On - CB contact supervisor enable Off
TCBSV 0 - 100 s CB contact supervisor time 10
DS-Contact NO / NC / Both - Kind of injected DS contact NO
DS-SV Off / On - DS contact supervisor enable Off
TDSSV 0 - 100 s DS contact supervisor time 60
DLDbyUV Off / On - Dead line detection by under voltage Off
DLDbyCB Off / On - Dead line detection by CB open Off
TDLD 0.00 - 300.00 s Dead line detection timer 10.00
UserLogicSW1 S1 / S2 / S3 - User Logic Switch1 for General purpose S1
UserLogicSW2 S1 / S2 / S3 - User Logic Switch2 for General purpose S1
UserLogicSW3 S1 / S2 / S3 - User Logic Switch3 for General purpose S1
UserLogicSW4 S1 / S2 / S3 - User Logic Switch4 for General purpose S1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 407 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 408 -
6F2S1927 (0.18)
2.30.8 Data ID
Signal monitoring points (for 3D, 3E, 3F models)
PROT_COMMON(48A001)
Element ID Name Description
8000001B88 CB-A_CLOSE CB phase-A closed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 409 -
6F2S1927 (0.18)
Connection points in PLC logic Signal monitoring points (for 3D, 3E, 3F models)
PROT_COMMON (48A001)
Element ID Name Description
800000EBB7 CB1-A_NC_CONT CB1-A normally closed contact
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 410 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 411 -
6F2S1927 (0.18)
Connection points in PLC logic Signal monitoring points (for 30, 32 models)
PROT_COMMON (48A001)
Element ID Name Description
800000EBB7 CB1-A_NC_CONT CB1-A normally closed contact
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 412 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 413 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 414 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 415 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 416 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 417 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 418 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 419 -
6F2S1927 (0.18)
Control scheme
Figure 3.1-1 shows the control overview for the control function; there are two control stages:
“Wait for a command” and “Receiving commands”. The function will wait for a command from
the server in the first stage. During the receiving stage, the function will respond to “Select”,
“Cancel”, and “Operate” commands. Specific logic is provided for each command for each
receiving stage. A decision is required from each logic block to move to the next step (i.e., ‘Failed’
or ‘Success’). When a ‘success’ decision is determined in the operate logic, the respective
command is issued to the relevant device; the device commences with its operation (for example,
a 43-switch is changed to “ON” from “OFF”). The waiting and receiving stages loop around at
the receipt of every command.
Waiting stage
The type of control can be categorized in accordance with its origin, (Remote/Local/PLC)
and modes (SBO/DIR). That is, the respective control scheme should respond to the respective
origin and mode. The user should be aware of the context of the control action, “On (or Closing)
control” and “Off (or Open) control” in relationship to its origin and mode†.
†Note:The “On control” and “Off control” can be found in the SPOS, DPSY and other
functions. For more information on these functions, see the explanations provided
for each respective function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 420 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 421 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 422 -
6F2S1927 (0.18)
Control mode
Either Select-Before-operation (SBO) or Direct-Operate-control (DIR) is provided as a control
mode for the device. The user can select the preferred control mode.
SBOw
Selection Command
Answer#1 R esponse
Oper. Command
Operation
Answer#2 R esponse
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 423 -
6F2S1927 (0.18)
Process Server IE D
(SAS) (Control function) Target device
Selection SBOw
Command
Answer Response
Oper.
Operation
Command
Answer
Response
Process SAS IE D
(Server) (Control function) Target device
Oper.
Operation Command
Answer#1 R esponse
Device status changed
Answer#2 Command
termination
R esult
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 424 -
6F2S1927 (0.18)
SAS IE D
Process
(Server) Control function Target device
Operation
Control
Command
Answer#1
Response
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 425 -
6F2S1927 (0.18)
Control hierarchy
It is important that the user understand the meaning of the terms ‘control-right’ and ‘control-
hierarchy’ in connection with the functioning of the control and monitoring applications in the
sub-station automation system (SAS) and the sub-station control and monitoring system
(SCMS). For instance, when we wish to operate a device (such as a piece of switchgear or
others), the system has the device forbidden to operate if the system is unable to give a ‘control-
right’ for the device using the ‘control-hierarchy’. Figure 3.3-1 depicts the control-hierarchy;
the control-hierarchy is made of three control-levels, two selector-switches, and three control-
points. Either control command of three control-points is permitted so that the other
commands will be forbidden in the system. On this account, no collision of control-points exists
within the system.
Control-point in RCC
Network level
Control-point in OWS/EWS
Communication
EWS OWS
Selector switch
(43R) RCC EWS/OWS
Station level
Control-point on LCD(MIMIC)
ON/OFF operation on LCD
Bay level
Control-right
Switchgear and others
Control levels Selector switches Control points and positions of selector switches
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 426 -
6F2S1927 (0.18)
The part ○
1 and ○
2 logics are programmed so that, the control-right signal can be
distributed to the respective control applications. With regard to the DPSY01 function, PLC
connection point “DPSY01IN_TMP_28” has been programmed using DOUT_BOOL feature (for
example). Therefore, the control-right signal is transferred to the select and operate-condition
logic‡ when the user connects the control-hierarchy with the DPSY01 function using
“DPSY01IN_TMP_28”.
‡Note:The select-condition and operate-condition logic are used to decide upon the
execution of a select command or an operate command in the DPSY01 function.
For more detail, see chapter Control and monitoring application: DPSY function:
Operate condition and Select condition. As per the DPSY function, other functions,
such as SPOS, DPOS, and TOPS, have the same logic; the user is required to do
the connection.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 427 -
6F2S1927 (0.18)
○
1 Checking the bay level ○
2 Distribution of the control-right
RemoteLocalKey_43BCU
From LOCMT
DIN_UNIT UNIT_TO_BOOL SPOS01_CTRL_RIGHT
LRSW01_LR_ST FID DO
DTYPE ST DOUT_BOOL
(530001 3109001001) FID ST
DID
DTYPE
DID
DI
To SPOS01
510001 820101ED50 SPOS01IN_TMP_28 Select
condition logic
SPOS02_CTRL_RIGHT
DOUT_BOOL
Operate
FID ST
condition logic
DTYPE
DID
DI
To SPOS02
510001 820102ED50 SPOS02IN_TMP_28 Select
condition logic
Operate
condition logic
DPSY01_CTRL_RIGHT
DOUT_BOOL
FID ST
DTYPE
DID
DI
To DPSY01
511001 820201ED50 DPSY01IN_TMP_28 Select
condition logic
DPSY02_CTRL_RIGHT Operate
DOUT_BOOL condition logic
FID ST
DTYPE
DID
DI
To DPSY02
511001 820202ED50 DPSY02IN_TMP_28 Select
condition logic
TPOS02_CTRL_RIGHT Operate
DOUT_BOOL condition logic
FID ST
DTYPE
DID
DI
To TPOS02
513001 810402EE57 TPOS02IN_TMP_21 Select
condition logic
Operate
condition logic
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 428 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.4-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 429 -
6F2S1927 (0.18)
SPOS20 function
SPOS20_STD_RPT
DPOS function
≥1
Reception of “DCB”
DPOS01 function
DPOS72 function
DPOS72_STD_RPT
DPSY function
TPOS function
SOFTSW function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 430 -
6F2S1927 (0.18)
In Figure 3.4-1, the CMNCTRL1 function generates a message denoted with the number
1; Figure 3.4-2 exemplifies that the IED-1 generates the “stVal” message 1. In addition, IEDs-
2 to -10 are also required to receive message 1, this is denoted with the number 2. For
IEC61850 communication, the “stVal” messages 1 and 2 are carried by GOOSE publish and
GOOSE subscribe. Thus, for all IEDs (i.e., IED-1 to IED-10 of Figure 3.4-2), it is required to
set the GOOSE publish destination corresponding to the message.
1 2 2 2
Figure 3.4-3 demonstrates how the GOOSE publish destination is set with regard to the
DCB message. The user is required to set the destination for each respective IED by selecting
the signal “DCB SND OR”, corresponding to the GOOSE publish, this must be performed at
the respective screens in GR-TIEMS†. That is, the user should select the “stVal” item for each
IED. After setting, the user should write the setting date for each respective IED.
○
1 Selected IED
○2 Required settings in
the respective IEDs.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 431 -
6F2S1927 (0.18)
CMNCTRL2
function
PLC_O_BIT_0201 For
・Event record function
5A0101 800200EF40 PLC_BIT_0201 (5A0101 8002001F40)
・Communication (required mapping)
Information ・LEDs
cascaded§ ・IED screen display
・Binary output module
etc…
†Note:The user should recognize that the reason messages are only available for
operation with the GCS1000 control system manufactured by Toshiba.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 432 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 433 -
6F2S1927 (0.18)
3.4.5 Setting
CMNCTRL (FunctionID:5A0001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 434 -
6F2S1927 (0.18)
3.4.6 Signal
PLC connection points
CMNCTRL (Function ID: 5A0001)
Element ID Name Description
800800EDE1 ADD_DCB_SND Additional condition for double command blocking
800800EFB7 LAN_CONN_FAIL_IN
… …. …
800800EFB8 TIME_SYN_FAIL_IN
8008001FB7 LAN_CONN_FAIL
8008001FB8 TIME_SYN_FAIL
… …. …
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 435 -
6F2S1927 (0.18)
…. …. ….
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 436 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 437 -
6F2S1927 (0.18)
…. …. ….
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 438 -
6F2S1927 (0.18)
Local to remote
&
1≥
If the user does not touch the
operation/function keys on the front panel &
within 35 min. in the local control, the IED
will be changed for the remote control
unconditionally.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.5-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 439 -
6F2S1927 (0.18)
†Note:As a rule, the control commands have parameters. For example, the “Off to On”
and “On to Off” control directions that are used in commands are pre-configured
as parameters in the communication protocol. Note that the parameters vary
depending upon the respective protocol used, such as IEC61850 and others. For
IEC61850, Table 3.5-2 shows the parameters defined: the rule for control direction
can be found in “ctlVal”, the command publisher is recognized using the parameter
“origin”. For more information about the parameters, see Appendix IEC61850
MICS, PICS, PIXIT and TICS.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 440 -
6F2S1927 (0.18)
Figure 3.5-2 Example of user-preferred control scheme using PLC user logic
Note: The user-preferred control scheme implemented by users can only be operated in
the DIR mode.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 441 -
6F2S1927 (0.18)
3.5.5 Signal
Signal monitoring points
LOCRMT_SW (Function ID: 530001)
Element ID Name Description
3109001001 LRSW01_LR_ST S43BCU state
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 442 -
6F2S1927 (0.18)
1Note: For the operation, see Chapter User interface: Outline. Note that pressing the
“CLEAR” key causes the Reset of the LEDs.
2Note: For more information, see Chapter Engineering tool.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.6-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 443 -
6F2S1927 (0.18)
Operate logic
0 t
Failed
0.3s
Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 444 -
6F2S1927 (0.18)
[LEDDR1_EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 445 -
6F2S1927 (0.18)
Table 3.6-3 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
528001 820701ED50 LEDR01_CTRL_RIGHT LED Reset control hierarchy M
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 446 -
6F2S1927 (0.18)
Operate logic
Operate command
Operate logic
“Do nothing”
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 447 -
6F2S1927 (0.18)
Failed Do nothing
Failed Do nothing
Cancel logic
Cancel command
Cancel logic
Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL
From KEYINPUT
240001 31000E1730
LEDR_KEY_CLEAR
CLEAR
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 448 -
6F2S1927 (0.18)
[LEDDR1_EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 449 -
6F2S1927 (0.18)
Figure 3.6-9 Settings for LED-03 circuit provided by “Setting I/O menu” of GR-TIEMS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 450 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 451 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 452 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 453 -
6F2S1927 (0.18)
Table 3.6-6 Mapping signals required for LEDRs object for LLN0
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/LLN0$LEDRs$Oper ctlVal BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper ctlNum INT8U CO
Ctrl/LLN0$LEDRs$Oper T Timestamp CO
Ctrl/LLN0$LEDRs$Oper Test BOOLEAN CO
Ctrl/LLN0$LEDRs$Oper Check Check CO 5280017007016D08 LEDR01_CONTROL_REQ
Ctrl/LLN0$LEDRs$Oper$origin orCat orCategory CO
Ctrl/LLN0$LEDRs$Oper$origin orIdent Octet64 CO
Ctrl/LLN0$LEDRs ctlModel ctlModel CF
Ctrl/LLN0$LEDRs sboClass sboClass CF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 454 -
6F2S1927 (0.18)
3.6.6 Setting
Reset Control (Function ID: 528001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 455 -
6F2S1927 (0.18)
3.6.7 Signal
Signal monitoring points
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
8007011D53 LEDR01_SC Select command
Mapping point
TLEDRSTCTRL (Function ID: 528001)
Element ID Name Description
7007016D08 LEDR01_CONTROL_REQ Dev01 control request
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 456 -
6F2S1927 (0.18)
Closed/Open signals
GCNT01_ CNT_ VAL
Inputs 320E 011D20
Changes in device status
(e.g., operations of 43S) BI 540001 800E 01E DE 0 GCNT01_ PLC_ SGNL GCNT01
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.7-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ ✓
– Number of controls 32 32 32 32 32 32 32
✓: Applicable NA: Not applicable TBD: To be developed
Signal acquisition timing must be adjusted in accordance with the application, in that the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 457 -
6F2S1927 (0.18)
acquisition should be regulated for the nature of the signal; hence, several settings are
provided in the GCNT functions. Thirty-two independent GCNT counters† are available. That
is, counters GCNT01 to GCNT32† can operate simultaneously. The values counted are stored
in the non-volatile memory so that they are not erased if the power supply to the IED is
interrupted.
For simplicity, only the GCNT01 function is discussed; the features in the remaining GCNT02–
GCNT32 functions are identical to the GCNT01 function.
a. On (Closed) signals
Counter 1 2 … n …
Counter 1 2 … n …
Counter 1 2 … n …
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 458 -
6F2S1927 (0.18)
from 9 to 2147483647.
Counter
10 10 10
5 5 5
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 459 -
6F2S1927 (0.18)
Operate logic
Operate command
Operate logic
Output signal to BO
The GCNT01 function can issue a “Complete” signal at the output point
“GCNT01_SLD_CSCN”, when the GCNT01 function determines that the input signal
“Remote-Reset-Control” is true. If the GCNT01 function determines that the “Remote-Reset-
Control” is not true, the GCNTS01 function returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 460 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 461 -
6F2S1927 (0.18)
[GCNT01-HMI]
On
[DPOS01-EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 462 -
6F2S1927 (0.18)
Table 3.7-4 PLC Connection point (Input signals from the control hierarchy logic)
Signal Number Signal Name Description M/O
540001 800E00ED5A GCNT00IN_TMP_51 Control hierarchy for GCNT01–32 M
Table 3.7-5 PLC Monitoring points (Signal “select complete/ failed” for BIO)
Signal Number Signal Name Description
540001 8A0E011E76 GCNT01_SLD_CSCN GCNT01 Selection completed (Mapping)
540001 8A0E021E76 GCNT02_SLD_CSCN GCNT02 Selection completed (Mapping)
540001 8A0E031E76 GCNT03_SLD_CSCN GCNT03 Selection completed (Mapping)
… … …
540001 8A0E201E76 GCNT32_SLD_CSCN GCNT32 Selection completed (Mapping)
5400018B0E011E7B GCNT01_SLF_CSCN GCNT01 select failed
5400018B0E021E7B GCNT02_SLF_CSCN GCNT02 select failed
5400018B0E031E7B GCNT03_SLF_CSCN GCNT03 select failed
…. … …
5400018B0E201E7B GCNT32_SLF_CSCN GCNT32 select failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 463 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 464 -
6F2S1927 (0.18)
Operate logic
Operate command
Operate logic
Output signal to BO
The GCNT01 function can issue a “Success to cancel” signal at the monitoring point
“GCNT01_CC_SSCN”, when the GCNT01 function has determined that the signal “Remote-
cancel” is true. Another signal “Operation failed” is issued if the function is able to determine
that the signal “Remote-cancel” is not true.
Input Cancel logic in GCNT01 Output
“Do nothing”
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 465 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 466 -
6F2S1927 (0.18)
Failed Do nothing
Output signal to BO
The GCNT01 function, in Figure 3.7-11, can provide a signal at the point “GCNT01_OK_CSC”,
when the GCNT01 function determines that the signal “Remote-Reset-Control” is true.
Input Operate logic in GCNT01 Output
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
Statics-counter
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 467 -
6F2S1927 (0.18)
Failed Do nothing
Counter
10:48 1/8
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0
Output signal to BO
The GCNT01 function can provide a signal at the point “GCNT01_OK_CSC”, when the new
value applied from the sub-menu is appropriate.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 468 -
6F2S1927 (0.18)
[GCNT01-HMI]
On
[DPOS01-EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 469 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 470 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
Origin
ctlmodel (choice ”SBOes or SBOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 471 -
6F2S1927 (0.18)
Table 3.7-10 Mapping signals required for GIGO3302 object in GCNT01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$origin orCat orCategory ST 540001300e011D23 GCNT01_CNT_ORCAT
Ctrl/GGIO3302$ISCSO$origin orIdent Octet64 ST 5400016A0e011FA7 GCNT01_CNT_ORIDENT
Ctrl/GGIO3302$ISCSO stVal INT32 ST 540001320e011D20 GCNT01_CNT_VAL
Ctrl/GGIO3302$ISCSO q Quality ST 3010013110041005 Qual_Val
Ctrl/GGIO3302$ISCSO t Timestamp ST 2003019010001006 SYS_TIME
Ctrl/GGIO3302$ISCSO stSeld BOOLEAN ST 540001000E011D91 GCNT01_TMP_01
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 472 -
6F2S1927 (0.18)
Table 3.7-11 Mapping signals required for ISCSO object for GIGO3302
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO3302$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO3302$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO3302$ISCSO$Oper T Timestamp CO
Ctrl/GGIO3302$ISCSO$Oper Test BOOLEAN CO
Ctrl/GGIO3302$ISCSO$Oper Check Check CO 540001 700E016D09 GCNT01_CMM_REQ
Ctrl/GGIO3302$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO3302$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO3302$ISCSO ctlModel ctlModel CF
Ctrl/GGIO3302$ISCSO sboClass sboClass CF
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 473 -
6F2S1927 (0.18)
3.7.5 Setting
Counter (Function ID: 540001)
Setting items Range Unit Contents Default Note
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The number of counters in the GCNT depends on IED model. We omit the setting
tables of GCNT04 etc. because the setting items are the same except the device
number.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 474 -
6F2S1927 (0.18)
3.7.6 Signal
Signal monitoring points in GCNT01
GCNT (Function ID: 540001)
Element ID Name Description
000E001F41 GCNT00_CCTRL_COUNTER GCNT00 cmnctrl counter correction summarize
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the GCNT function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “GCNT02_CTR_SGUCN” point
for the 2nd device, use the description of “GCNT01_CTR_SGUCN” in place
of “GCNT02_CTR_SGUCN”. The user can obtain the ID value of
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 475 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 476 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 3.8-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 477 -
6F2S1927 (0.18)
3.8.1 Function
(i) Mode sensor
The MDCTRL function can monitor the state change (On to TEST / TEST to Off) in the IED.
To use this monitoring function, On should be set for the scheme switch [MDCTRL-EN] prior to
operation. During the operation, a select signal and an operate signal are provided for the
TEST-FB when the SAS provides a test command for the IED; hence, the MDCTRL function
comes with two time-out timers. Setting [MDCTRL-SELRST] provides a time-out timer for
canceling a select command; setting [MDCTRL-EXERST] provides a time-out timer for
canceling an operate command.
Table 3.8-3 PLC connection point (Input signal for select condition logic)
Signal Number Signal Name Description M/O
550001 821301ED50 MDCTRL01IN_TMP_28 MDCTRL control hierarchy condition M
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 478 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 479 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 480 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 481 -
6F2S1927 (0.18)
Table 3.8-5 Mapping signals required for LLNO object in MDCTRL01 function
Object_reference Attribute Type FC Signal Number Signal Name
System/LLN0$Mod$SBOw ctlVal Mod CO
System/LLN0$Mod$SBOw ctlNum INT8U CO
System/LLN0$Mod$SBOw T Timestamp CO
System/LLN0$Mod$SBOw Test BOOLEAN CO
System/LLN0$Mod$SBOw Check Check CO
System/LLN0$Mod$SBOw$origin orCat orCategory CO
System/LLN0$Mod$SBOw$origin orIdent Octet64 CO
System/LLN0$Mod$Oper ctlVal Mod CO
System/LLN0$Mod$Oper ctlNum INT8U CO
System/LLN0$Mod$Oper T Timestamp CO
System/LLN0$Mod$Oper Test BOOLEAN CO
System/LLN0$Mod$Oper Check Check CO 5500017013016D08 MDCTRL01_CONTROL_REQ
System/LLN0$Mod$Oper$origin orCat orCategory CO
System/LLN0$Mod$Oper$origin orIdent Octet64 CO
System/LLN0$Mod$Cancel ctlVal Mod CO
System/LLN0$Mod$Cancel ctlNum INT8U CO
System/LLN0$Mod$Cancel T Timestamp CO
System/LLN0$Mod$Cancel Test BOOLEAN CO
System/LLN0$Mod$Cancel$origin orCat orCategory CO
System/LLN0$Mod$Cancel$origin orIdent Octet64 CO
System/LLN0$Mod ctlModel ctlModel CF
System/LLN0$Mod sboTimeout INT32U CF
System/LLN0$Mod sboClass sboClass CF
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 482 -
6F2S1927 (0.18)
3.8.3 Setting
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 483 -
6F2S1927 (0.18)
3.8.4 Signal
Signal monitoring point
MDCTRL(Function ID: 550001)
Element ID Name Description
8013011D55 MDCTRL01_EC_OWS MDCTRL01 execute command by OWS(HMI)
8313011E89 MODE01_OEC_F_CS MDCTRL01 Test direction execute command fail condition signal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 484 -
6F2S1927 (0.18)
Mapping point
MDCTRL(Function ID: 550001)
Element ID Name Description
7013016D08 MDCTRL01_CONTROL_REQ MDCTRL01 correction request from cmm
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 485 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 486 -
6F2S1927 (0.18)
A number of devices can be controlled separately, i.e. the SPOS function has separate sets
of logic for control (i.e., SPOS01, SPOS02 etc. functions). For simplicity, only the SPOS01
function is discussed here; the features in the SPOS02 etc. functions are identical to the
SPOS01 function.
†Note:Binary IO module has binary input circuits (BIs) and binary output circuits (BOs);
the user makes the connection between the SPOS01 function and the binary IO
module using a signal number (is made of a function ID and an “Element ID”).The
signal name and number of the SPOS01 function are listed later.
Tips: If the user wishes to apply the SPOS function quickly, go to sections 4.1.4 and
4.1.5, where setting of the BI and BO circuits and the mapping of signals for IEC
61850 communication is described.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.1-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– Number of controls 20 20 NA 20 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 487 -
6F2S1927 (0.18)
Cancel logic
Select command Off from remote-end
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 488 -
6F2S1927 (0.18)
510001 7001016D08
Output signal to BO
The SPOS01 function can issue an output “Selection success” signal at the output point
“SPOS01_OSL_BO_CSF”, when the SPOS01 function determines that the “Remote-ON-
Control” signal received is true. If the SPOS01 function determines that the “Remote-ON-
Control” signal is not true, the SPOS01 function returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 489 -
6F2S1927 (0.18)
Cancel logic
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 490 -
6F2S1927 (0.18)
Output signal to BO
The SPOS01 function, in Figure 4.1-4, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF” when the SPOS01 function determines that the “Select command Off
(Remote-OFF-Control)” signal is true. If the SPOS01 function determines that the “Remote-
OFF-Control” signal is not true, the SPOS01 function returns to the “Wait for a command”
stage.
Cancel logic
Cancel command
Select command On from remote-end
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 491 -
6F2S1927 (0.18)
0.6s
[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_OSL_BO_CSF”.
Note: The signal “SPOS01_OSL_BO_CSF” is the same as the signal shown in Figure
4.1-2. If the “Local-ON-Control” signal is not true, the SPOS01 function returns to
the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 492 -
6F2S1927 (0.18)
Cancel logic
Select command On from remote-end Cancel command
Cancel logic
Select command On from front panel
0.6s
[SPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 493 -
6F2S1927 (0.18)
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the other SPOS logics, see Table 4.1-9.
Output signal to BO
When the “select condition” signal is true, the SPOS01 function can issue a “Selection success”
signal at the output-point “SPOS01_FSL_BO_CSF”.
1Note: The signal “SPOS01_FSL_BO_CSF” is the same as the signal shown in Figure
4.1-4. If the “Local-OFF-Control” signal is not true, the SPOS01 function returns
to the “Wait for a command” stage.
Cancel logic
Cancel command
Select command On from remote-end
Operate logic
Select command On by PLC
Failed Operate command
function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 494 -
6F2S1927 (0.18)
command not requiring the interlock check. That is, for the SPOS01 function, when the “select
command ‘On’ (PLC-On-Control) signal generated in the user-programmed logic is applied, and
when the interlock check is required in the select logic, use the connection point (PLC#1;e.g.,
DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2); e.g., DEV01_CL_COMMAND”. PLC#1 and PLC#2 are shown in
510001 7001016D08
Table 4.1-2.
Signals from user-PLC logic Selection logic in SPOS01 Output
1≥ &
ON-control command requiring ILK checking† To “Wait for a next
For DIR operation
(PLC#1 connection point) command”
Operate command
To BO connection
510001 800101EE33 DEV01_CL_INTERLOCK with ILK† condition
& “SPOS01_OSL_BO_CSF”
(510001_8601011DC6)
ILK† condition (“ON”) passed DIR
SPOS01-On 0 t Selection “success”
0.1s
ON-control command requiring no ILK checking† For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Selection “Failed”
510001 800101EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s
DIR
Output signal to BO
The SPOS01 function, in Figure 4.1-10, can issue a “Select success” signal at the output-point
“SPOS01_OSL_BO_CSF”1.
1Note: The signal “SPOS01_OSL_BO_CSF” is the same as that shown in Figure 4.1-2.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 495 -
6F2S1927 (0.18)
Cancel logic
Cancel command
Select command On from remote-end
Operate logic
Select command On by the PLC
function Operate command
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 496 -
6F2S1927 (0.18)
1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
510001 800101EE31 Operate command with To BO connection
DEV01_OP_INTERLOCK
ILK† condition & “SPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (510001_8601011DC6)
SPOS01-Off 0 t Selection “success”
0.1s
OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Selection “Failed”
510001 800101EE30 DEV01_OP_COMMAND &
without ILK† condition 0.6s
Select condition‡
Output signal to BO
The SPOS01 function, in Figure 4.1-12, can issue a “Select success” signal at the output point
“SPOS01_FSL_BO_CSF”1.
1Note: The output point “SPOS01_FSL_BO_CSF” is the same signal as shown in Figure
4.1-4.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 497 -
6F2S1927 (0.18)
Unmatched co
Command “ON control” received &
Command “OFF control” received &
received
SPOS01_STATE
(510001 0001011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
510001 800101EE61 SPOS01IN_TMP_31
[SPOS01-LGSLFFCT]
User configurable condition (PLC #2connection point)
Fixedlogic
510001 810101EE62 SPOS01IN_TMP_32 &
[SPOS01-CTREN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 498 -
6F2S1927 (0.18)
4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output point “GEN.TRIP” in Table
4.1-6.
5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in a command
is not identical to “IED test status”.
6Note: The “Event suppression” function can detect chattering on BI circuits. (See section
4.1.4(i)-2)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The common control (CMNCTRL) function can test and check the ‘On’ and ‘Off”
operations performed by the logic. When the user sets Off for scheme switch
(SCDEN), the operation of the logic is blocked if the logic is running in the same
operation- direction compared with the previous operation direction. (i.e., when
On (Off) is performed sequentially). On the other hand, if On is set for the scheme
switch, the logic is not blocked.
9Note: The user will need to program the PLC logic “Control hierarchy condition” The
user is also required to connect the logic condition with the select condition logic
using the connection point “SPOS01IN_TMP_28”. For more information, see
chapter “Control and monitoring application: Control hierarchy” see PLC#3 of
Table 4.1-7.
10Note: To identify the input point of the other SPOS, see Table 4.1-7 for PLC#1 and
PLC#2.
Table 4.1-2 PLC connection points (Input points for command ‘On’)
Signal Number Signal Name Description M/O
510001 800101EE32 DEV01_CL_COMMAND SPOS01 PLC On-control without checking O
510001 800102EE32 DEV02_CL_COMMAND SPOS02 PLC On-control without checking O
510001 800103EE32 DEV03_CL_COMMAND SPOS03 PLC On-control without checking O
…. …. ….
510001 800114EE32 DEV20_CL_COMMAND SPOS20 PLC On-control without checking O
510001 800101EE33 DEV01_CL_INTERLOCK SPOS01 PLC On-control checking with interlock O
510001 800102EE33 DEV02_CL_INTERLOCK SPOS02 PLC On-control checking with interlock O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 499 -
6F2S1927 (0.18)
Table 4.1-3 PLC connection points (Input points for command ‘Off’)
Signal Number Signal Name Description M/O
510001 800101EE31 DEV01_OP_INTERLOCK SPOS01 PLC Off-control checking with interlock O
510001 800102EE31 DEV02_OP_INTERLOCK SPOS02 PLC Off-control checking with interlock O
510001 800103EE31 DEV03_OP_INTERLOCK SPOS03 PLC Off-control checking with interlock O
…. …. ….
510001 800114EE31 DEV20_OP_INTERLOCK SPOS20 PLC Off-control checking with interlock O
510001 800101EE30 DEV01_OP_COMMAND SPOS01 PLC Off-control without checking O
510001 800102EE30 DEV02_OP_COMMAND SPOS02 PLC Off-control without checking O
510001 800103EE30 DEV03_OP_COMMAND SPOS03 PLC Off-control without checking O
…. …. ….
510001 800114EE30 DEV20_OP_COMMAND SPOS20 PLC Off-control without checking O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 500 -
6F2S1927 (0.18)
Table 4.1-7 PLC connection points (Input signal for select condition logic)
Signal Number Signal Name Description M/O
510001 800101EE61 SPOS01IN_TMP_31 SPOS01 additional failure condition (PLC#1) O
510001 800102EE61 SPOS02IN_TMP_31 SPOS02 additional failure condition (PLC#1) O
510001 800103EE61 SPOS03IN_TMP_31 SPOS03 additional failure condition (PLC#1) O
…. …. ….
510001 800114EE61 SPOS20IN_TMP_31 SPOS20 additional failure condition (PLC#1) O
510001 810101EE62 SPOS01IN_TMP_32 SPOS01 user configurable select condition (PLC#2) O
510001 810102EE62 SPOS02IN_TMP_32 SPOS02 user configurable select condition (PLC#2) O
510001 810103EE62 SPOS03IN_TMP_32 SPOS03 user configurable select condition (PLC#2) O
…. …. ….
510001 810114EE62 SPOS20IN_TMP_32 SPOS20 user configurable select condition (PLC#2) O
510001 820101ED50 SPOS01IN_TMP_28 SPOS01 control hierarchy condition (PLC#3) M
510001 820102ED50 SPOS02IN_TMP_28 SPOS02 control hierarchy condition (PLC#3) M
510001 820103ED50 SPOS03IN_TMP_28 SPOS03 control hierarchy condition (PLC#3) M
…. …. ….
510001 820114ED50 SPOS20IN_TMP_28 SPOS20 control hierarchy condition (PLC#3) M
Table 4.1-8 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
510001 8001011F54 SPOS01_SC_ST_ERR SPOS01 select command mode is invalid.
510001 8001021F54 SPOS02_SC_ST_ERR SPOS02 select command mode is invalid.
510001 8001031F54 SPOS03_SC_ST_ERR SPOS03 select command mode is invalid.
…. …. ….
510001 8001141F54 SPOS20_SC_ST_ERR SPOS20 select command mode is invalid.
510001 8101011F59 SPOS01_F_QLT_SPP Event suppression detected (SPOS01)
510001 8101021F59 SPOS02_F_QLT_SPP Event suppression detected (SPOS02)
510001 8101031F59 SPOS03_F_QLT_SPP Event suppression detected (SPOS03)
…. …. ….
510001 81010A1F59 SPOS20_F_QLT_SPP Event suppression detected (SPOS20)
510001 8201011F5A SPOS01_F_BI_ERR BI connection error detected(SPOS01)
510001 8201021F5A SPOS02_F_BI_ERR BI connection error detected(SPOS02)
510001 8201031F5A SPOS03_F_BI_ERR BI connection error detected(SPOS03)
…. …. ….
510001 8201141F5A SPOS20_F_BI_ERR BI connection error detected(SPOS20)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 501 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 502 -
6F2S1927 (0.18)
Operate logic
“Do nothing”
Cancel condition† &
“SPOS01_CC_FS” (510001_8701011E96)
Operation Failed
Output signal to BO
The SPOS01 function can issue an output signal “Success to cancel” at the monitoring point
“SPOS01_CC_SS”, when the SPOS01 function has determined that the “Remote-cancel” signal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 503 -
6F2S1927 (0.18)
is true. Another “Operation failed” signal is issued at the monitoring point “SPOS01_CC_FS”
if the SPOS01 function is able to determine that the “Remote-cancel” signal is not true.
Operate logic
Operation Failed
Output signal to BO
The SPOS01 function, illustrated in Figure 4.1-17, is able to issue a “Select to cancel” signal
at the monitoring point “SPOS01_CC_SS”, when the SPOS01 function determines that the
“Local-Cancel” signal is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 504 -
6F2S1927 (0.18)
[SPOS01-LGSLFFCT]
User configurable condition (PLC connection point)
Fixedlogic
510001 800101EE69 SPOS01IN_TMP_46 &
If the original logic does not meet with the requirements of the user, it can be replaced
with another logic using the connection point “User Configurable condition”:
1. Connect the user-customized logic with the “SPOS01IN_TMP_46”.
2. Set scheme switch [SPOS01-LGCNFFCT] to PLC.
Table 4.1-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
510001 8601011E95 SPOS01_CC_SS Cancel succeed in SPOS01
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 505 -
6F2S1927 (0.18)
SPOSxx-LGCNFFCT Logic selector for cancel condition in SPOSxx Fixedlogic Fixedlogic / PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 506 -
6F2S1927 (0.18)
Failed Do nothing
Select command Off from front panel Off control from front-panel
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 507 -
6F2S1927 (0.18)
“SPOS01-OEC_OK_CSF”
Command “Remote-On-Control” (510001_8001011E7F)
[SPOS01-CPW]
510001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[SPOS01-LGCFEXOT]
User configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL
[SPOS01-PLSM]*
Var To “Wait for a command”
Fix
Latch “SPOS01_EX_FFL”
[SPOS01-RST]
0 t (510001_8601011E91) ††
“SPOS01-EX_CMP”
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed
“SPOS01-FEX_BO”
(510001_8101011DD0)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 508 -
6F2S1927 (0.18)
§§Note: The “SPOS01_OEX-BO” signal is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed “signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.
Output signal to BO
The SPOS01 function, in Figure 4.1-20, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the received signal “Remote-
On-Control” is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 509 -
6F2S1927 (0.18)
Failed Do nothing
Operation Cmd.
without ILK† condition
ILK† condition (“Off”) passed S
&
SPOS01-Off R
[SPOS01-LGCFEXOT]
User Configurable condition
(PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ§ function is in progress
ASEQ_MULTI_SEL
To “Wait for a command”
[SPOS01-PLSM]*
“SPOS01_EX_FFL” † †
Var [SPOS01-RST] (510001_8601011E91)
Fix
0 t
“SPOS01-EX_CMP
(5A0101_8001011E93) 1.0s- 100.0s Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 510 -
6F2S1927 (0.18)
Output signal to BO
The SPOS01 function, in Figure 4.1-22, can issue an “Operate” signal at the output-point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the signal “Remote-Off-
Control” is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 511 -
6F2S1927 (0.18)
Select command On from the remote-end Operate command On from the local-end
Select command Off from the remote-end Operate command Off from the local-end
Failed Do nothing
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
“SPOS01-OEC_OK_CSF”
(510001_8001011E7F)
Operate Cmd.
Command “Local-On-Control” [SPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK† condition (“ON”) passed
SPOS01-On
S
&
ILK† bypassing ( Bypass) 1≥
R
ICB_STATE
[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point) & Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
ASEQ function§” is in progress PLC#2
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 512 -
6F2S1927 (0.18)
Output signal to BO
The SPOS01 function, in Figure 4.1-24, can issue an “Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the signal “Local-On-Control”
is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 513 -
6F2S1927 (0.18)
Select command Off from the remote-end Operate command Off from remote-end
Select command On from the local-end Operate command On from the local-end
Failed Do nothing
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 514 -
6F2S1927 (0.18)
[SPOS01-LGCFEXOT]
User configurable condition (PLC#2 connection point)
& Assign to BOs
Fixedlogic
510001 810101EDDA SPOS01IN_TMP_42
To PLC
& logic
PLC#2
ASEQ function§” is in progress
ASEQ_MULTI_SEL
0 t
“SPOS01-EX_CMP
(5A0101_8001011E93)
1.0s- 100.0s Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 515 -
6F2S1927 (0.18)
Output signal to BO
The SPOS01 function, in Figure 4.1-26, can issue a signal “Operate” at the output point
“SPOS01_FEX_BO”, when the SPOS01 function determines that the input signal “Local-Off-
Control” is true.
Select command Off from remote-end Operate command Off control from remote-end
Select command On from front panel Operate command On control from front-panel
Select command Off from front panel Operate command Off control from front-panel
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 516 -
6F2S1927 (0.18)
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Figure 4.1-28 depicts the operate logic when a signal “Operate Command Off (PLC-Off-
Control)” is generated by the PLC function. There are two input points for reception of this
command signal, unlike the signal “Operate Command On (PLC-On-Control)”. That is, if an
inter-lock check is required, apply the signal at connection point (PLC#3; i.e.,
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at connection point (PLC#4; i.e., DEV01_OP_COMMAND).
PLC#1 an PLC#2 shown in Table 4.1-3 should be treated as PLC#3 and PLC#4 here.
Note that the user should set PLC for scheme switch [SPOS01-LGCFEXOT]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 517 -
6F2S1927 (0.18)
4.1-17.
2. Set scheme switch [SPOS01-LGEXFFCT] to Fixedlogic.
Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “SPOS01IN_TMP_28” in
Figure 4.1-29.
Note: The output of the operate condition logic is provided separately for On-execution
and for Off-execution. To see the outputs, refer to Table 4.1-18.
SPOS01 function (Function ID: 510001)
Command blocking*1
CBK_STATE
1≥ & 1≥ &
Double Command Blocking detected*2
DCB RCV OR
To selection logic
Other devices traveling detected*3
Operate condition
Traveling OR
Unmatched condition detected *5
Function “Automatic sequence control” is in progress
ASEQ_MULTI_SEL Event suppression detected *6
= SPOS01_F_QLT_SPP
Tripping *4 (“General trip”)
(510001 810101F59)
GEN. TRIP
BI board connection error detected*7
= SPOS01_F_BI_ERR
(510001 820101F5A)
[SPOS01-CTREN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 518 -
6F2S1927 (0.18)
Table 4.1-14 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
510001 830101EE5B SPOS01IN_TMP_38 SPOS01 user configurable condition(PLC#1) O
510001 830102EE5B SPOS02IN_TMP_38 SPOS02 user configurable condition(PLC#1) O
510001 830103EE5B SPOS03IN_TMP_38 SPOS03 user configurable condition(PLC#1) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 519 -
6F2S1927 (0.18)
Table 4.1-15 PLC connection points (Input point for PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
510001 810101EDDA SPOS01IN_TMP_42 SPOS01 user configurable condition(PLC#2) O
510001 810102EDDA SPOS02IN_TMP_42 SPOS02 user configurable condition(PLC#2) O
510001 810103EDDA SPOS03IN_TMP_42 SPOS03 user configurable condition(PLC#2) O
…. …. ….
510001 810114EDDA SPOS20IN_TMP_42 SPOS20 user configurable condition(PLC#2) O
Table 4.1-16 PLC connection points (Input point for PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
510001 800101EE56 SPOS01IN_TMP_34 SPOS01 user configurable condition(PLC#3) O
510001 800102EE56 SPOS02IN_TMP_34 SPOS02 user configurable condition(PLC#3) O
510001 800103EE56 SPOS03IN_TMP_34 SPOS03 user configurable condition(PLC#3) O
…. …. ….
510001 800114EE56 SPOS20IN_TMP_34 SPOS20 user configurable condition(PLC#3) O
Table 4.1-17 PLC connection points (Input point PLC#1/#2 of additional and operate
conditions)
Signal Number Signal Name Description M/O
510001 800101EE61 SPOS01IN_TMP_31 SPOS01 additional failure condition (PLC#1) O
510001 800102EE61 SPOS02IN_TMP_31 SPOS02 additional failure condition (PLC#1) O
510001 800103EE61 SPOS03IN_TMP_31 SPOS03 additional failure condition (PLC#1) O
… … …
510001 800114EE61 SPOS20IN_TMP_31 SPOS20 additional failure condition (PLC#1) O
510001 810101EE66 SPOS01IN_TMP_41 SPOS01 user configurable operate condition (PLC#2) O
510001 810102EE66 SPOS02IN_TMP_41 SPOS02 user configurable operate condition (PLC#2) O
510001 810103EE66 SPOS03IN_TMP_41 SPOS03 user configurable operate condition (PLC#2) O
… … …
510001 810114EE66 SPOS20IN_TMP_41 SPOS20 user configurable operate condition (PLC#2) O
510001 8101141DD0 SPOS20_FEX_BO SPOS20 operate (OFF) command for Binary Output.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 520 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 521 -
6F2S1927 (0.18)
Note that the SPOS01 function commences operation when the scheme switch [SPOS01-EN]
is set to On.
“SPOS01_STATE”
Event suppression detector (510001_0001011001)
BI signal connected by
setting [SPOS01-NOPSG]
& 1≥
&
[SPOS01-EN] Status before chattering S
R “SPOS01_F_QLT_SPP”
On
(510001_8101011F59)
On
& To select and operate
condition logics
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 522 -
6F2S1927 (0.18)
Event suppression
If the status of a device “chatters” for a short time, the SPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the SPOS function;
hence, event suppression can be required to reduce the additional burden created.
[SPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[SPOS-TELD] [SPOS-TELR]
Time................. A B C D E
Figure 4.1-31 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [SPOS-NELD] is provided so
that the suppression commences at Time B. The setting [SPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [SPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [SPOS01-SPPEN].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 523 -
6F2S1927 (0.18)
Terminal and
Selection logic in SPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire
“SPOS01_SL_BO_FLG”
(510001_8501011F76)
“SPOS01_OSL_BO_CSF”
Terminal and
Operate logic in SPOS01 BO2 and BO3 circuit at IO#1 (Function ID: 200B01) wire
“SPOS01_OEX_BO”
(510001_8201011DD3)
“BO2”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8102011112) command
“Operate command On
[Input signal 2] DRIVER BO2
On” & ≥1
[Input signal 3]
“BO2-RB”
[Input signal 4] [BO2_CPL] On &
Connected by Off
(200B01_8102011113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
Figure 4.1-33 Example of operate commands connected with BO2 and BO3 at IO#1
†Note:Table 4.1-27 shows the remaining signals excepting “SPOS01_OEX_BO” and
“SPOS01_FEX_BO”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 524 -
6F2S1927 (0.18)
†Note:Table 4.1-29 shows settings for the health check feature in the other SPOS
functions.
Result of contact
BO1 circuit at & health check in SPOS01 selection
IO_SLOT1
“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [SPOS01-SLBORD]
Figure 4.1-34 Example of connection of “Select command On” for the health check feature
Operate logic in
SPOS01
Result of contact
BO2 circuit at & Health check
IO_#1
“BO2-RB”
“200B01_8102011113”
Signal designated by
setting [SPOS01-OEXBORD]
Figure 4.1-35 Example connection of “Operate Command On” for the health check
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 525 -
6F2S1927 (0.18)
Result of contact
BO3 circuit at & health check
IO_#1
“BO3-RB”
“200B01_8102021113”
Signal designated by
setting [SPOS01-FEXBORD]
Figure 4.1-36 Example connection of “Operate command off” for the health check feature
Proper setting for the contact health check (normal setting, example #1)
Figure 4.1-37 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1, BO2 and BO3 contacts. To check that the contact health check function is
working correctly, the respective points of the BO-RBs should be connected as shown in Table
4.1-22, to demonstrate that the settings are physically matched with the BO contacts.
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“SPOS01_SL_BO_FLG”
(510001_8501011F76) SW1 driven with
BO1 at IO_SLOT1
Select BO1 SW 1
command ON/OFF
“BO1-RB”
(200B01_8002001113) SW 2 On
Command
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB”
Minus (−)
(200B01_8102011113)
“SPOS01_FEX_BO”
(510001_8101011DD0)
BO3 SW3 driven with
Operate-Off BO3 at IO_SLOT1
command “BO3-RB”
(200B01_8202021113)
Figure 4.1-37 Contact health check setting and 43SW scheme for example #1
Setting for erroneous contact health check (improper setting, example #2)
Figure 4.1-38 shows a setting example for an improper setting of the 43SW scheme. The
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 526 -
6F2S1927 (0.18)
settings are implemented incorrectly, as shown in Table 4.1-23. BO1-RB is not chosen,
instead BO1 is actually chosen. In this case, the setting [SPOS01-SLBORD] is meaningless;
hence, the issue of a select command is blocked.
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
BIO module
43SW
Remote/Local-end “BO1” (not BO1-RB) Plus (+)
“SPOS01_SL_BO_FLG” mistakenly chosen with
(510001_8501011F76) “200B01_8002001112” SW1 driven with
BO1at IO_SLOT1
Select BO1 SW 1
Command
ON/OFF
SW 2 On
“SPOS01_OEX_BO” Command
(510001_8201011DD3)
SW 3 Off
Operate-On BO2 SW2 driven with Command
command BO2 at IO_SLOT1
“BO2-RB” designated with Minus (−)
“SPOS01_FEX_BO” “200B01_8102011113”
(510001_8101011DD0)
Figure 4.1-38 Contact health check setting and 43SW diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.1-39 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “SPOS01_SL_BO_FLG” is actually chosen for the
setting [SPOS01-SLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command; which is called “operated by internal select function”. The user
does not need to consider of a BO circuit for a select command, when there are no BO circuits
available.
Table 4.1-24 Extra setting example for contact health check
Example #3 Setting for example #3
“SPOS01_FEX_BO_CSF” is connected to “BO3” at IO#1 200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD] OK
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 527 -
6F2S1927 (0.18)
BIO module
43SW
Remote/Local end “SPOS01_SL_BO_FLG” Plus (+)
SW1 is not driven with
(510001_8501011F76) Plus (+)
any BO1
SW 1
Select
command Physical BO is
ON/OFF
virtualized.
“SPOS01_OEX_BO”
(510001_8201011DD3)
SW2 is driven with
BO2 at IO#1
Operate-On BO2 SW 2 On
command Command
“BO2-RB”
“SPOS01_FEX_BO” (200B01_8102011113) SW3 is driven with SW 3 Off
(510001_8101011DD0) BO3 at IO#1 Command
Figure 4.1-39 Contact health check setting and 43SW diagram for example #3
Table 4.1-25 PLC monitoring points (Output signal for event suppression function in SPOSxx)
Signal Number Signal Name Description
510001 0001011001 SPOS01_STATE Status of SPOS01
510001 0001021001 SPOS02_STATE Status of SPOS02
510001 0001031001 SPOS03_STATE Status of SPOS03
…. …. ….
510001 0001141001 SPOS20_STATE Status of SPOS20
510001 8101011F59 SPOS01_F_QLT_SPP Event suppression detected (SPOS01)
510001 8101021F59 SPOS02_F_QLT_SPP Event suppression detected (SPOS02)
510001 8101031F59 SPOS03_F_QLT_SPP Event suppression detected (SPOS03)
…. …. ….
510001 8101141F59 SPOS20_F_QLT_SPP Event suppression detected (SPOS20)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 528 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 529 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 530 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 531 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 532 -
6F2S1927 (0.18)
Table 4.1-31 Mapping signals required for SPCSO object for GIG01501
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1501$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO1501$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$SBOw Check Check CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Oper T Timestamp CO
Ctrl/GGIO1501$SPCSO$Oper Test BOOLEAN CO
5100017 001016D08 DEV01_CONTROL_REQ
Ctrl/GGIO1501$SPCSO$Oper Check Check CO
Ctrl/GGIO1501$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO1501$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO1501$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO1501$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1501$SPCSO ctlModel ctlModel CF
Ctrl/GGIO1501$SPCSO sboClass sboClass CF
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 533 -
6F2S1927 (0.18)
4.1.6 Setting
SPOS01 (FunctionID:510001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 534 -
6F2S1927 (0.18)
4.1.7 Signal
Signal monitoring points in SPOS01
SPOS01(FunctionID:510001)
Element ID Name Description
8001011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
0001001F74 SPOS_SEL_OR SPOS multi select check signal for Auto sequence
0001011001 SPOS01_STATE SPOS01 state
0001011D90 SPOS01_SLD_RPT SPOS01 selected signal(stSeld) for SAS
0001011D97 SPOS01_EX_BO_OPOK SPOS01 execute binary output signal for SAS
0001011F52 SPOS01_TRA SPOS01 travelling info
0001011F53 SPOS01_TRA_CTR SPOS01 travelling info for control
0001011F75 SPOS01_SE_RCV SPOS01 select or execute command received
3101011D00 SPOS01_MMC_ST SPOS01 state for MIMIC
3101011D01 SPOS01_LCD_ST SPOS01 state for LCD
3101011D80 SPOS01_TMP_06 SPOS01 control event data (selected)
3101011D81 SPOS01_TMP_07 SPOS01 control event data (select fail)
3101011D82 SPOS01_TMP_08 SPOS01 control event data (select release)
3101011D83 SPOS01_TMP_09 SPOS01 control event data (execute output on)
3101011D84 SPOS01_TMP_10 SPOS01 control event data (execute command ng)
3101011D86 SPOS01_TMP_11 SPOS01 control event data (execute fail)
8001011D02 SPOS01_ST_OFF SPOS01 status Off
8001011D51 SPOS01_SC_OWS SPOS01 select command by OWS(HMI)
8001011D52 SPOS01_SC_RCC SPOS01 select command by RCC
8001011D53 SPOS01_SC_RMT SPOS01 select command by Remote
8001011D54 SPOS01_SC_LCD SPOS01 select command by LCD
8001011D55 SPOS01_EC_OWS SPOS01 execute command by OWS(HMI)
8001011D56 SPOS01_EC_RCC SPOS01 execute command by RCC
8001011D57 SPOS01_EC_RMT SPOS01 execute command by Remote
8001011D58 SPOS01_EC_LCD SPOS01 execute command by LCD
8001011D59 SPOS01_EC_PLC SPOS01 execute command by PLC
8001011E76 SPOS01_SLD_CS SPOS01 selected condition signal
8001011E7D SPOS01_SLR_CS SPOS01 select release condition signal
8001011E7E SPOS01_FEC_OK_CSF SPOS01 off direction execute command OK condition signal by fixedlogic
8001011E7F SPOS01_OEC_OK_CSF SPOS01 on direction execute command OK condition signal by fixedlogic
8001011E81 SPOS01_FEC_OK_CS SPOS01 off direction execute command OK condition signal
8001011E93 SPOS01_EX_CMP SPOS01 execute complete signal
8001011F54 SPOS01_SC_ST_ERR SPOS01 select command mode err
8001011F55 SPOS01_EC_ST_ERR SPOS01 execute command mode err
8001011F56 SPOS01_NSL_CS06 SPOS01 no direction select condition signal 06
8001011F66 SPOS01_SLD_CS04 SPOS01 selected condition signal 04
8101011D03 SPOS01_ST_ON SPOS01 status On
8101011DD0 SPOS01_FEX_BO SPOS01 off direction execute binary output signal
8101011E7B SPOS01_SLF_CS SPOS01 no direction select fail condition signal
8101011E82 SPOS01_OEC_OK_CS SPOS01 on direction execute command OK condition signal
8101011E85 SPOS01_FEC_F_CSF SPOS01 off direction execute command fail condition signal by fixedlogic
8101011E86 SPOS01_OEC_F_CSF SPOS01 on direction execute command fail condition signal by fixedlogic
8101011E9A SPOS01_ECF_FCT_EIS SPOS01 execute command fail factor signal except interlock/synchronism check
8101011F59 SPOS01_F_QLT_SPP TEMP31
8101011F64 SPOS01_FSL_CS21 SPOS01 off direction select condition signal 21
8201011DD3 SPOS01_OEX_BO SPOS01 on direction execute binary output signal
8201011E88 SPOS01_FEC_F_CS SPOS01 off direction execute command fail condition signal
8201011F5A SPOS01_F_BI_ERR TEMP32
8201011F5F SPOS01_NSL_CS10 SPOS01 no direction select condition signal 10
8301011E89 SPOS01_OEC_F_CS SPOS01 on direction execute command fail condition signal
8301011E9C SPOS01_CCF_FCT_CS TEMP21
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 535 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 536 -
6F2S1927 (0.18)
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “SPOS01_SC_OWS” point for
the 2nd device, use the description of “SPOS01_SC_OWS” in place of
“SPOS02_SC_OWS”. The user can obtain the ID value of
“SPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for SPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“SPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 537 -
6F2S1927 (0.18)
†Note:The DPSY function is similar to the DPOS function; the DPSY function is required
to operate together with the synchronizing function (SYNDIF), which has relay
elements corresponding to voltages, and can coordinate the timing for closing or
opening. For more detailed information with regard to the SYNDIF function, see
Chapter Control and monitoring application: Synchronizing check for different
network.
The BO circuits are used for issuing commands; the BI circuits are used for receiving
responses; hence, the user should set the BIO† together with the DPSY function. The DPSY
function includes three logic groups: 1. Selection logic, 2. Cancel logic, and 3. Operate logic.
Tips: If the user wishes to apply the DPSY function quickly, go to sections 4.2.6 and
4.2.7, where setting of the BI and BO circuits and the mapping of signals for
IEC61850 communication is described.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.2-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA NA NA NA NA
– Number of controls 2 2 NA NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 538 -
6F2S1927 (0.18)
Two devices can be controlled separately; i.e., the DPSY function has two separate sets of logic
for control (i.e., DPSY01 and DPSY02 functions). For simplicity, only the DPSY01 function is
discussed here; the features in the DPSY02 function are identical to the DPSY01 function.
Cancel logic
Select command Open from the remote-end
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 539 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (ASEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 540 -
6F2S1927 (0.18)
This logic has the input-point “DEV01_CONTROL_REQ” for the reception of a select
command. That is, the input-point must be mapped for communication. The function will fail
to operate if mapping is not performed correctly. We will discuss how to map the input-points
for IEC61850 communication in section 4.2.7.
Output signal to BO
The DPSY01 function can issue an output signal “Selection success” at the output point
“DPSY01_OSL_BO_FLG”, when the DPSY01 function determines that the “Remote-Closing-
Control” signal received is true. If the DPSY01 function determines that the “Remote-Closing-
Control” signal is not true, the DPSY01 function returns to the “Wait for a command” stage.
The user should note that the operation decision of the SYNDIF01 function is required
for the DPSY01 function; the operation decision is determined by the measurement of running
voltage and incoming voltage. Table 4.2-2 shows the relay-elements used in the SYNDIF01
function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 541 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (ASEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 542 -
6F2S1927 (0.18)
it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
††Note: To know the input and output points of the DPSY02 logic, see Table 4.2-6 and
Table 4.2-10.
Output signal to BO
The DPSY01 function, in Figure 4.2-4, can issue a “Select success” signal at the output point
“DPSY01_FSL_BO_FLG” when the DPSY01 function determines that the “Selection command
Open (Remote-Open-Control)” signal is true. If the DPSY01 function determines that the
“Remote-Open-Control” signal is not true, the DPSY01 function returns to the “Wait for a
command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 543 -
6F2S1927 (0.18)
SYNC01-SLD_VCS‡‡
(560001 840B011F58)
1≥ Timer§§ To “Wait for a command”
SYNC‡‡ bypassing 0 t 0 t
Selection “Failed”
SCB_STATE
0.0 to 5.0 s 0.6s
[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
When the signal “select condition” is true, the DPSY01 function can issue a “Selection success”
signal at the output-point “DPSY01_OSL_BO_CSF”.
Note: The signal “DPSY01_OSL_BO_CSF” is the same as the signal shown in Figure
4.2-2. If the “Local-Closing-Control” signal is not true, the DPSY01 function
returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 544 -
6F2S1927 (0.18)
0.6s
[DPSY01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850) SBO
Select condition‡
“Automatic sequence control function (ASEQ§)” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 545 -
6F2S1927 (0.18)
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the output signals of the DPSY02 logic, see Table 4.2-10.
Output signal to BO
When the “select condition” signal is true, the DPSY01 function can issue a “Select success”
signal at the output-point “DPSY01_FSL_BO_FLG”.
1Note: The signal “DPSY01_FSL_BO_FLG” is the same as the signal shown in Figure
4.2-4. If the signal “Local-Open-Control” is not true, the DPSY01 function returns
to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 546 -
6F2S1927 (0.18)
Select condition‡
ILK condition (“Closing”) passed
DPSY01-Close
Output signal to BO
The DPSY01 function, in Figure 4.2-10, can issue a “Select success” signal at the output-point
“DPSY01_OSL_BO_CSF”1.
1Note: The signal “DPSY01_OSL_BO_CSF” is the same signal as that shown in Figure
4.2-2.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 547 -
6F2S1927 (0.18)
Select “Failed”
Select condition
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 548 -
6F2S1927 (0.18)
The DPSY01 function, in Figure 4.2-12, can issue a “Select success” signal at the output point
“DPSY01_FSL_BO_CSF”1.
1Note: The output point “DPSY01_FSL_BO_CSF” is the same signal as shown in Figure
4.2-4.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 549 -
6F2S1927 (0.18)
Unmatched con
Command “Open control” received &
Command “Closing control” received &
received
DPSY01_3PH_STATE
(511001 3102011001)
[SCDEN]*8 Same Directional
Controlling Event
OFF
Additional condition (PLC#1 connection point)
511001 800201EE61 DPSY01IN_TMP_31
[DPOS01-LGSLFFCT]
User configurable condition (PLC#2 connection point)
Fixedlogic
511001 810201EE62 DPSY01IN_TMP_32 &
[DPSY01-CTREN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 550 -
6F2S1927 (0.18)
4.2.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The Common control (CMNCTRL) function can test and check the ‘Opening’ and
‘Closing’ operations performed by the logic. When the user sets Off for scheme
switch [SCDEN], the operation of the logic is blocked if the logic is running in the
same operation-direction compared with the previous operation-direction (i.e.,
when closing (opening) is performed sequentially). On the other hand, if On is set
for the scheme switch, the logic is not blocked.
9Note: The user will need to program the PLC logic “Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point “DPSY01IN_TMP_28”. For more information, see
Chapter Control and monitoring application: Control hierarchy . See PLC#3 of
Table 4.2-8.
10Note: To identify the input points of the DPSY02, see Table 4.2-8.
Table 4.2-3 PLC connection points (Input points for Command ‘Closing’)
Signal Number Signal Name Description M/O
5A0101 800527EF40 DEV01_CL_SYNC_INTER DPSY01 PLC Close-control checking with interlock & Sync (PLC#1) O
5A0101 800551EF40 DEV02_CL_SYNC_INTER DPSY02 PLC Close-control checking with interlock & Sync (PLC#1) O
5A0101 800526EF40 DEV01_CL_SYNC DPSY01 PLC Close-control with Sync (PLC#2) O
5A0101 800550EF40 DEV02_CL_SYNC DPSY02 PLC Close-control with Sync (PLC#2) O
5A0101 800525EF40 DEV01_CL_INTERLOCK DPSY01 PLC Close-control checking with interlock(PLC#3) O
5A0101 800549EF40 DEV02_CL_INTERLOCK DPSY02 PLC Close-control checking with interlock(PLC#3) O
5A0101 800524EF40 DEV01_CL_COMMAND DPSY01 PLC Close-control none checking (PLC#4) O
5A0101 800548EF40 DEV02_CL_COMMAND DPSY02 PLC Close-control none checking (PLC#4) O
Table 4.2-4 PLC connection points (Input points for Command ‘Open’)
Signal Number Signal Name Description M/O
5A0101 800523EF40 DEV01_OP_INTERLOCK DPSY01 PLC Open-control checking with interlock(PLC#1) O
5A0101 800547EF40 DEV02_OP_INTERLOCK DPSY02 PLC Open-control checking with interlock(PLC#1) O
5A0101 800522EF40 DEV01_OP_COMMAND DPSY01 PLC Open-control without checking(PLC#2) O
5A0101 800546EF40 DEV02_OP_COMMAND DPSY02 PLC Open-control without checking(PLC#2) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 551 -
6F2S1927 (0.18)
Table 4.2-8 PLC connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
511001 800531EF40 DPSY01IN_TMP_31 DPSY01 additional failure condition(PLC#1) O
511001 800554EF40 DPSY02IN_TMP_31 DPSY02 additional failure condition(PLC#1) O
511001 800532EF40 DPSY01IN_TMP_32 DPSY01 user configurable select condition(PLC#2) O
511001 800555EF40 DPSY02IN_TMP_32 DPSY02 user configurable select condition(PLC#2) O
511001 800516EF40 DPSY01IN_TMP_28 DPSY01 control hierarchy condition(PLC#3) M
511001 800519EF40 DPSY02IN_TMP_28 DPSY02 control hierarchy condition(PLC#3) M
Table 4.2-9 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
511001 8002011F5A DPSY01_SC_ST_ERR DPSY01 Unmatched condition.
511001 8002021F5A DPSY02_SC_ST_ERR DPSY02 Unmatched condition.
511001 8102011F5F DPSY01_F_QLT_SPP Event suppression detected (DPSY01)
511001 8102021F5F DPSY02_F_QLT_SPP Event suppression detected (DPSY02)
511001 8202011F60 DPSY01_F_BI_ERR BI connection error detected(DPSY01)
511001 8202021F60 DPSY02_F_BI_ERR BI connection error detected(DPSY02)
Table 4.2-10 PLC monitoring points (Closing/Open output signals for BIO)
Signal Number Signal Name Description
511001 8602011DC6 DPSY01_OSL_BO_FLG DPSY01 select (Closing) command for Binary Output.
511001 8602021DC6 DPSY02_OSL_BO_FLG DPSY02 select (Closing) command for Binary Output.
511001 8A02011DC4 DPSY01_FSL_BO_FLG DPSY01 select (Open) command for Binary Output.
511001 8A02021DC4 DPSY02_FSL_BO_FLG DPSY02 select (Open) command for Binary Output.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 552 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 553 -
6F2S1927 (0.18)
Select command Closing from the remote-end Cancel from the remote-end
Success
Operate logic
“Do nothing”
“DPSY01_CC_FS”
(511001 8702011E96)
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 554 -
6F2S1927 (0.18)
Output signal to BO
The DPSY01 function can issue a “Success to cancel” signal at the monitoring point
“DPSY01_CC_SS”, when the DPSY01 function has determined that the “Remote-cancel” signal
is true. Another “Operation failed” signal is issued at monitoring point DPSY01_CC_FS” “if
the DPSY01 function is able to determine that the “Remote-cancel” signal is not true.
Operate logic
Cancel command
Command “Local-cancel”
& To “Wait for a command”
“DPSY01_ CC_SS”
(511001 8602011E95)
Cancel condition &
Successes to cancel
“Do nothing”
“DPSY01_CC_FS”
(511001 8702011E96)
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 555 -
6F2S1927 (0.18)
Output signal to BO
The DPSY01 function, illustrated in Figure 4.2-17, is able to issue a “Select to cancel” signal
at the monitoring point “DPSY01_CC_SS”, when the DPSY01 function determines that the
“Local-Cancel” signal is true.
[DPSY01-LGSLFFCT]
User configurable condition (PLC connection point)
Fixedlogic
511001 800201EE69 DPSY01IN_TMP_46 &
PLC#1
If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User configurable condition”:
1. Connect the user-customized logic with the “DPSY01IN_TMP_46”, which is listed
in Table 4.2-12.
2. Set scheme switch [DPSY01-LGCNFFCT] to PLC.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 556 -
6F2S1927 (0.18)
Table 4.2-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
511001 800201EE69 DPSY01IN_TMP_46 DPSY01 user configurable cancel condition O
511001 800202EE69 DPSY02IN_TMP_46 DPSY02 user configurable cancel condition O
Table 4.2-13 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
511001 8602011E95 DPSY01_CC_SS DPSY01 cancel succeed
511001 8602021E95 DPSY02_CC_SS DPSY02 cancel succeed
511001 8702011E96 DPSY01_CC_FS DPSY01 cancel failed
511001 8702021E96 DPSY02_CC_FS DPSY02 cancel failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 557 -
6F2S1927 (0.18)
Failed Do nothing
Select command Open from the remote-end Operate command Open from the remote-end
Select command Closing from the local-end Operate command Closing from the local-end
Select command Open from the local-end Operate command Open from the local-end
Select command Closing by the PLC function Operate command Closing by the PLC function
Select command Open by the PLC function Operate command Open by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 558 -
6F2S1927 (0.18)
“DPSY01_OEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7F)
“DPSY01_OEC_OK_CS”
(511001 8102011E82)
Command “Remote-Closing-Control”
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Command with ILK†
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
SYNC01-SYN_CLC
(560001 850B011F59)
Operate Command with ILK†
condition &
[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ§ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operate Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL” ‡‡
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operate Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 559 -
6F2S1927 (0.18)
*Note:The user can set the type of the output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signal-points of the DPSY02 logic, see Table
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [DPSY01-RST] has been reached.
Output signal to BO
The DPSY01 function, in Figure 4.2-20, can issue an “Operate” signal at the output point
“DPSY01_OEX_BO”, when the DPSY01 function determines that the received signal “Remote-
Closing-Control” is true.
Select command Closing from the remote-end Operate command Closing from the remote-end
Failed Do nothing
Select command Closing from the local-end Operate command Closing l from the local-end
Select command Open from the local-end Operate command Open from the local-end
Select command Closing by the PLC function Operate command Closing by the PLC function
Select command Open by the PLC function Operate command Open by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 560 -
6F2S1927 (0.18)
“DPSY01_FEC_OK_CSF” “DPYS01_FEC_OK_CS”
Command “Remote-On-Control” (511001 8002011E7E) (511001 8002011E7E)
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 561 -
6F2S1927 (0.18)
PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the outputs.
Output signal to BO
The DPSY01 function, in Figure 4.2-22, can issue an “Operate” signal at the output-point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the input signal “Remote-
Open-Control” is true.
Select command Closing from the remote-end Operate command Closing from the remote-end
Select command Open from the remote-end Operate command Open from the remote-end
Select command Closing from the local-end Operate command Closing l from the local-end Success
Operation
Signal reception from Operate logic Signal output
decision
the front panel
Failed Do nothing
Select command Open from the local-end Operate command Open from the local-end
Select command Closing by the PLC function Operate command Closing by the PLC function
Select command Open by the PLC function Operate command Open by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 562 -
6F2S1927 (0.18)
“DPSY01_OEC_OK_CSF” “DPSY01_OEC_OK_CS”
(511001 8002011E7F) (511001 8102011E82)
Command “Local-Closing-Control”
[DPSY01-CPW]
511001_7002016D08 DEV01_CONTROL_REQ Operate Command with ILK
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
ILK condition (“Closing”) passed
DPSY01-Close
ILK bypassing 1≥ S
&
ICB_STATE
R
From SYNCHK
SYNC01-SYN_CLC
(560001 850B011F59)
1≥
SYNC‡‡ bypassing
SCB_STATE
[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operation Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL”
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 563 -
6F2S1927 (0.18)
*Note:The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††Note: To identify the input and output signal-points of the DPSY02 logic, see Table
4.2-15 for PLC#1, Table 4.2-16 for PLC#2, Table 4.2-20, and Table 4.2-21 for
output signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPSY01-RST].
Output signal to BO
The DPSY01 function, in Figure 4.2-24, can issue an “Operate” signal at the output point
“DPSY01_OEX_BO”, if the DPSY01 function determines that the signal “Local-Closing-
Control” is true.
Select command Closing from the remote-end Operate command Closing from the remote-end
Select command Open from the remote-end Operate command Open from the remote-end
Select command Closing from the local-end Operate command Closing l from the local-end
Failed Do nothing
Select command Closing by the PLC function Operate command Closing by the PLC function
Select command Open by the PLC function Operate command Open by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 564 -
6F2S1927 (0.18)
To BO connection
“DPSY01_FEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7E)
“DPSY01_FEC_OK_CS”
(511001 8002011E7E)
Operate Cmd.
Command “Local-Open-Control” [DPSY01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operation Cmd.
without ILK† condition
ILK condition (“Open”) passed
DPSY01--Open
S
&
ILK bypassing 1≥
R
ICB_STATE
[DPSY01-LGCFEXOT]
& Assign to BOs
ASEQ§ function” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 565 -
6F2S1927 (0.18)
PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the outputs.
Output signal to BO
The DPSY01 function, in Figure 4.2-31, can issue an “Operate” signal at the output point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the signal “Local-Open-
Control” is true.
Select command Closing from the remote-end Operate command Closing from the remote-end
Select command Open from the remote-end Operate command Open from the remote-end
Select command Closing from the local-end Operate command Closing l from the local-end
Select command Open from the local-end Operate command Open from the local-end
Select command Closing by the PLC function Operate command Closing by the PLC function Success
Operation
PLC logic programmed Operate logic Signal output
decision
by the user l
Failed Do nothing
Select command Open by the PLC function Operate command Open by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 566 -
6F2S1927 (0.18)
“DPSY01_OEC_OK_CSF”
DPSY01 function (Function ID: 511001) (511001 8002011E7F)
“DPSY01_OEC_OK_CS”
Closing control command with ILK† and synchro checks (511001 8102011E82)
(PLC#1 connection point) [DPSY01-CPW]
511001 800201EE35 DEV01_CL_SYNC_INTER Operate Command with ILK†
condition & synchro-checking & 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Closing control command with synchro check
(PLC#2 connection point)
Operate Command with
511001 800201EE34 DEV01_CL_SYNC
synchro-checking &
ILK condition (“Closing”) passed S
&
DPSY01-Close R
From SYNCHK
Closing control command SYNC01-SYN_CLC
with interlock check (560001 850B011F59)
(PLC#3 connection point)
Operate Command with ILK†
511001 800201EE33 DEV01_CL_INTERLOCK &
condition
Closing control command with no check
(PLC#4 connection point) Operate Command without
511001 800201EE32 DEV01_CL_COMMAND condition
User configurable condition
(PLC#1 connection point)
511001 810201EE57 DPSY01IN_TMP_35
[DPSY01-LGCTRCON] &
Fixedlogic To BO connection
“DPSY01_OEX_BO” §§
Operate condition‡
(511001 8202011DD3)
[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
Detection of state-change in (511001 8002011E93)
a device S &
User configurable condition “DPSY01_EX_CMP” R Operate Completed
1≥
(PLC#2 connection point)
(511001 8002011E93)
511001 820201EE5E DPSY01IN_TMP_44 & “DPSY01_EX_FFL” ‡‡
[DPSY01-RST] PLC
(511001 8602011E91)
“DPSY01_OEC_OK_CSF”
0 t
(511001 8002011E7F)
&
1.0s- 100.0s Operate Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 567 -
6F2S1927 (0.18)
[DPSY01-PLSM], the output period of the signal is defined by the setting applied
to [DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††Note: To identify the input and output signal-points in the DPSY02 logic, see Table
4.2-3 and Table 4.2-4 for PLC#1 to PLC#4, Table 4.2-15 and Table 4.2-16 for
PLC#1/#2 for user configurable conditions, Table 4.2-20, and Table 4.2-21 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting applied to timer [DPSY01-RST].
Output signal to BO
The DPSY01 function, in Figure 4.2-28, can issue an “Operate” signal at output point
“DPSY01_OEX_BO”, when the DPSY01 function determines that the “PLC-Closing-Control”
signal is true.
Select command Closing from the remote-end Operate command Closing from the remote-end
Select command Open from the remote-end Operate command Open from the remote-end
Select command Closing from the local-end Operate command Closing from the local-end
Select command Open from the local-end Operate command Open from the local-end
Select command Closing with the PLC Operate command Closing with the PLC function
function
Operate command Open with the PLC function Success
Operation
PLC logic programmed Operate logic Signal output
decision
Select command Open with the PLC function by the user
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 568 -
6F2S1927 (0.18)
“DPSY01_FEC_OK_CSF”
(511001 8002011E7E)
DPSY01 function (Function ID: 511001)
“DPSY01_FEC_OK_CS”
Command “PLC-Open-Control” with ILK†
(511001 8002011E7E)
(PLC#4 connection point) [DPSY01-CPW]
511001 800201EE31 DEV01_OP_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-Open-Control” without ILK† 0.1 – 50.0 s
(PLC#5 connection point)
511001 800201EE30 DEV01_OP_COMMAND Operation Cmd.
without ILK† condition
S
ILK† condition (“Open”) passed &
DPSY01-Open R
User configurable condition
(PLC#3 connection point)
[DPSY01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPSY01-PLSM]*
Var
Fix To “Wait for a command”
“DPSY01_EX_CMP”
(511001 8002011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 569 -
6F2S1927 (0.18)
††Note: To identify the input and output signal-points in the DPSY02 logic, see Table
4.2-16 for PLC#2, Table 4.2-17 for PLC#3, Table 4.2-19, and Table 4.2-21 for the
outputs.
Output signal to BO
The DPSY01 function, in Figure 4.2-30, can issue an “Operate” signal at output-point
“DPSY01_FEX_BO”, when the DPSY01 function determines that the “PLC-Open-Control”
signal is true.
Note: The user must program PLC logic “Control hierarchy condition”. The Control
hierarchy condition to be provided with the user-programmed PLC logic may be
43R/L; it may be connected using PLC connection point “DPSY01IN_TMP_28” in
Figure 4.2-31.
Note: The output of the operate condition logic is provided separately for Closing-
execution and for Open-execution. To see the outputs, refer to Table 4.2-19.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 570 -
6F2S1927 (0.18)
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 571 -
6F2S1927 (0.18)
4.2.6(i)-3)
7Note: A supervision of the Binary IO module can detect connection errors for BI circuits.
8Note: The “Common control” (CMNCTRL) function can test and check the operation-
direction of logic. When the user sets Off for scheme switch [SCDEN], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
9Note: The user must program the PLC logic for “Control hierarchy condition”. The user
must connect the “Control hierarchy condition” to the select condition logic using
the connection point “DPSY01IN_TMP_28”. For more information, see Chapter
Control and monitoring application: Control hierarchy . See PLC#3 of Table 4.2-8.
Note that the logic outputs are generated separately for both the Closing-
execution and the Open-execution.
Table 4.2-15 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
511001 810201EE57 DPSY01IN_TMP_35 DPSY01 user configurable condition(PLC#1) O
511001 810202EE57 DPSY02IN_TMP_35 DPSY02 user configurable condition(PLC#1) O
Table 4.2-16 PLC connection points (Input point for PLC#2 operate command Closing)
Signal Number Signal Name Description M/O
511001 820201EE5E DPSY01IN_TMP_44 DPSY01 user configurable condition(PLC#2) O
511001 820202EE5E DPSY02IN_TMP_44 DPSY02 user configurable condition(PLC#2) O
Table 4.2-17 PLC connection points (Input point for PLC#3 operate command Closing)
Signal Number Signal Name Description M/O
511001 800201EE56 DPSY01IN_TMP_34 DPSY01 user configurable condition(PLC#3) O
511001 800202EE56 DPSY02IN_TMP_34 DPSY02 user configurable condition(PLC#3) O
Table 4.2-18 PLC connection points (Input point for operate condition logic)
Signal Number Signal Name Description M/O
511001 800201EE65 DPSY01IN_TMP_40 DPSY01 user additional condition(PLC#1) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 572 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 573 -
6F2S1927 (0.18)
Closed
Open
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation Counter, the user can set a user-
preferred value for the operation-counter. See Chapter User interface: Monitoring sub-menu
on how to operate the sub-menu.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 574 -
6F2S1927 (0.18)
(i) Receiving “change value for counter” from the remote end
Mapping of Input point required
Figure 4.2-34 depicts the logic when a “change value for counter” command is received at the
DPSY01 logic. With regard to a three-phase counter, the input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.
“DPSY01_SLD_CSCN”
(511001 8A02011F88)
Command “change value for counter”
511001_7002016D09 DEV01_3PH_REQ Operate Command
&
Operate condition‡
Figure 4.2-34 Change counter value for three-phase† with operation from the remote-end in
DPSY01
‡Note: The “operate condition” signal is provided from the operate condition logic shown
in Figure 4.2-36.
†Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.2-24. The resultant signals for the DPSY02 logic are shown in
Table 4.2-25.
Output signal to BO
The DPSY01 function can issue a “Result” signal at output point “DPSY01_SLD_CSCN”. The
counter values are issued at points “DPSY01_CNT_VAL", “DPSY01A_CNT_VAL",
“DPSY01B_CNT_VAL", and “DPSY01C_CNT_VAL".
Figure 4.2-35 Changing counter value by operation from the front panel in DPSY01
Output signal to BO
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 575 -
6F2S1927 (0.18)
The DPSY01 function can issue a “Result” signal at the output point “DPSY01_SLD_CSCN”.
Figure 4.2-36 Operate condition logic for changing the counter in DPSY01
1Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch controller. See the signal
““S4301_STATE” of Table 4.2-7.
2Note: “Double Command Blocking” (DCB) is an operation philosophy. It can be used to
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as “DCB RCV OR) in Table 4.2-7.
3Note: If the event “device-travelling” is detected, it indicates that another operator is
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as “Travelling OR” in Table 4.2-7.
4Note: If the issue of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table
4.2-7.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 576 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 577 -
6F2S1927 (0.18)
Signal “DPSY01_FEX_BO”
Signal “DPSY01_OEX_BO”
Un sensed period
Open Intermediate Closed
The user can clear the operation interval (OT1 to OT4) by key-operation of the “Operation
time” sub-menu (Figure 4.2-39) or operation from the remote-end. See chapter User interface:
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 578 -
6F2S1927 (0.18)
Monitoring sub-menu.
Operation Time DPSY1-OT1
10:48 1/26 10:48 1/5
_DPSY1-OT > DPSY_SYN-Dev1-OT1
DPSY2-OT > CANCEL ******.*** ms
DPOS1-OT > DPSY_SYN-Dev1-OT2
DPOS2-OT >
******.*** ms
DPOS3-OT > ENTER DPSY_SYN-Dev1-OT3
DPOS4-OT >
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 579 -
6F2S1927 (0.18)
Note that the DPSY01 function commences operation when the scheme switch [DPSY01-
EN] is set to On.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 580 -
6F2S1927 (0.18)
DPSY01
To select and operate
condition logics
“DPSY01_3PH_STATE”
(511001 3102011001)
Phase-A signals BI signal selected by
N/O contact setting [DPSY01A-NOPSG]
Event
signal &
& Suppression
&
1≥ detector
BI signal selected by Open
N/C contact setting [DPSY01A-NCLSG]
“DPSY01_ F_QLT_SPP”
signal & (511001 8102011F5F)
&
Phase-B signals
BI signal selected by & Faulty
N/O contact setting [DPSY01B-NOPSG]
signal &
Phase-C signals
BI signal selected by
N/O contact setting [DPSY01C-NOPSG]
signal & &
Close
BI signal selected by
N/C contact setting [DPSY01C-NCLSG]
signal &
[DPSY01-EN]
On &
[DPSY01-DEVTYPE]
3-Pole
[DPSY01-OPC]
And
&
[DPSY01-CLC]
And
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 581 -
6F2S1927 (0.18)
DPSY01
To select and operate
condition logics
“DPSY01_3PH_STATE”
(511001 3102011001)
Single phase signals BI signal selected by
N/O contact setting [DPSY01A-NOPSG]
Event
signal &
& Suppression
1≥ detector
BI signal selected by Open
N/C contact setting [DPSY01A-NCLSG]
“DPSY01_ F_QLT_SPP”
signal & (511001 8102011F5F)
&
Faulty
&
Intermediate
&
Close
[DPSY01-EN]
On &
[DPSY01-DEVTYPE]
1-Pole
Event suppression
If the status of a device “chatters” for a short time, the DPSY function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPSY function;
hence, event suppression can be required to reduce the additional burden created.
[DPSY-NELD]
Signal 2 4 6 8
from device
1 3 5 7
Suppressed
signal
[DPSY-TELD] [DPSY-TELR]
Time................. A B C D E
Figure 4.2-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time ‘B’). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [DPSY-NELD] is provided so
that the suppression commences at Time B. The setting [DPSY-TELD] is pertains to the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 582 -
6F2S1927 (0.18)
operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPSY-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to ‘E’).
To initiate event suppression the user should set On for scheme switch [DPSY01-SPPEN].
Terminal and
Select logic in DPSY01 BO1 circuit at IO#1(Function ID: 200B01) wire
“DPSY01_OSL_BO_FLG”
(5110018602011DC6)
Select logic for Select Command “BO1” Select
Signal captured by Command
Closing in DPSY01 setting [Input signal 1] ≥1 (200B01_8002001112)
Closing
[Input signal 2] DRIVER BO1
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Select logic for Select Command check
Open in DPSY01 [Input signal 7]
[Input signal 8]
Terminal and
BO2 circuit at IO#1 (Function ID: 200B01) wire
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
“BO2” Select
Signal captured by Command
setting [Input signal 1] ≥1 (200B01_8102011112)
Open
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Figure 4.2-43 Example for select commands connection with BO1 & BO2 at IO#1
†Note:Table 4.2-10 shows the remaining signals with the excepting
“DPSY01_OSL_BO_FLG” and “DPSY01_FSL_BO_FLG”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 583 -
6F2S1927 (0.18)
Terminal and
Operate logic in DPSY01 BO3 and BO4 circuit at IO#1 (Function ID: 200B01) wire
“DPSY01_OEX_BO”
(511001 8202011DD3)
Operate
“BO3” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) Closing to
the device
“Operate command [Input signal 2] DRIVER BO3
Closing” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by (200B01_8202021113)
Off
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
Figure 4.2-44 Example of operate commands connected with BO2 and BO3 at IO#1
†Note:Table 4.2-36 shows the remaining signals excepting “DPSY01_OEX_BO” and
“DPSY01_FEX_BO”.
†Note:Table 4.2-38 shows settings for the health check feature in the DPSY02 function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 584 -
6F2S1927 (0.18)
Selection logic in
DPSY01
Result of contact
BO1 circuit at & health check
IO#1
“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [DPSY01-OSLBORD]
Figure 4.2-45 Example connection of “Select command Closing” for the health check feature
Result of contact
BO1 circuit at & health check
IO#1
“BO2-RB”
(200B01_8102001113)
Signal connected by
setting [DPSY01-FSLBORD]
Figure 4.2-46 Example connection of “Select command Open” for the health check feature
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 585 -
6F2S1927 (0.18)
Selection logic in
DPSY01
Result of contact
BO3circuit at & health check
IO#1
“BO3-RB”
“200B01_8202021113”
Signal designated by
setting [DPSY01-OEXBORD]
Figure 4.2-47 Example connection of “Operate command Closing” for the health check feature
Result of contact
BO4 circuit at & health check
IO#1
“BO4-RB”
“200B01_8302031113”
Signal designated by
setting [DPSY01-FEXBORD]
Figure 4.2-48 Example connection of “Operate command Open” for the health check feature
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 586 -
6F2S1927 (0.18)
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6) SW1 is driven with
BO1 at IO#1
Select-Closing BO1 SW 1
command
“BO1-RB”
(200B01_8002001113) SW 3 Closing
“DPSY01_FSL_BO_FLG”
SW2 is driven with
(511001 8A02011DC4)
BO2 at IO#1
Select-Open BO2 SW 2
command
“BO2-RB”
(200B01_8102011113) SW 4 Open
“DPSY01_OEX_BO”
SW3 is driven with
(511001 8202011DD3)
BO3 at IO#1
Operate-Closing BO3
Minus (−)
command
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate-Open
command “BO4-RB”
(200B01_8302031113)
Figure 4.2-49 Contact health check setting and 43SW diagram for example #1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 587 -
6F2S1927 (0.18)
Settings for erroneous contact health check (improper setting, example #2)
Figure 4.2-50 shows a setting example an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.2-32, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPSY01-OSLBORD] is
meaningless; hence, the issue of a select command is blocked.
BIO module
Local/remote-end “BO1” (not BO1-RB) Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG” mistakenly chosen with
“200B01_8002001112”
(511001 8602011DC6) SW1 is driven with
BO1 at IO#1
Select command BO1 SW 1
Closing
SW 3 Closing
“DPSY01_FSL_BO_FLG” command
SW2 is driven with
(511001 8A02011DC4)
BO2 at IO#1
Select command BO2 SW 2
Open
“BO2-RB”
(200B01_8102011113) SW 4 Open
“DPSY01_OEX_BO” command
(511001 8202011DD3) SW3 is driven with
BO3 at IO#1
Operate command BO3
Minus (−)
Closing
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command
Open “BO4-RB”
(200B01_8302031113)
Figure 4.2-50 Contact health check setting and 43SW diagram for example #2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 588 -
6F2S1927 (0.18)
Settings for extra contact health check (special setting, example #3)
Figure 4.2-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPSY01_OSL_BO_FLG” is actually chosen for the
setting [DPSY01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BO
circuits available.
Table 4.2-33 Extra setting example for contact health check
Example #3 Setting for example #3
BIO module
Local/Remote-end Drivers 43SW
Plus (+)
“DPSY01_OSL_BO_FLG”
(511001 8602011DC6)
SW1 is not driven with
Select command any BO
SW 1
Closing
Physical BOs
SW 3 Closing
are virtualized. command
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4) SW2 is not driven with
any BO
Select command
SW 2
Open
SW 4 Open
“DPSY01_OEX_BO” command
(511001 8202011DD3) SW3 is driven with
BO3 at IO#1
Operate command BO3
Closing Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPSY01_FEX_BO”
(511001 8102011DD0) SW4 is driven with
Operate command BO4 BO4 at IO#1
Open “BO4-RB”
(200B01_8302031113)
Figure 4.2-51 Contact health check setting and 43SW diagram for example #3
Table 4.2-34 PLC monitoring points (Output signal for event suppression function in DPSY)
Signal Number Signal Name Description
511001 3102011001 DPSY01_3PH_STATE DPSY01 3ph_state
511001 3102021001 DPSY02_3PH_STATE DPSY02 3ph_state
511001 8102011F5F DPSY01_F_QLT_SPP Event suppression detected (DPSY01)
511001 8102021F5F DPSY02_F_QLT_SPP Event suppression detected (DPSY02)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 589 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 590 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 591 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 592 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” in the
functional constraint (FC).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 593 -
6F2S1927 (0.18)
Table 4.2-40 Mapping signals required for DPC object for CSWI1
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI1$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw ctlNum INT8U CO
Ctrl/CSWI1$Pos$SBOw T Timestamp CO
Ctrl/CSWI1$Pos$SBOw Test BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw Check Check CO
Ctrl/CSWI1$Pos$SBOw$origin orCat orCategory CO
Ctrl/CSWI1$Pos$SBOw$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$Oper ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$Oper ctlNum INT8U CO
Ctrl/CSWI1$Pos$Oper T Timestamp CO
Ctrl/CSWI1$Pos$Oper Test BOOLEAN CO
5110017002016D08 DEV01_CONTROL_REQ
Ctrl/CSWI1$Pos$Oper Check Check CO
Ctrl/CSWI1$Pos$Oper$origin orCat orCategory CO
Ctrl/CSWI1$Pos$Oper$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$Cancel ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$Cancel ctlNum INT8U CO
Ctrl/CSWI1$Pos$Cancel T Timestamp CO
Ctrl/CSWI1$Pos$Cancel Test BOOLEAN CO
Ctrl/CSWI1$Pos$Cancel$origin orCat orCategory CO
Ctrl/CSWI1$Pos$Cancel$origin orIdent Octet64 CO
Ctrl/CSWI1$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI1$Pos$SBOw ctlNum INT8U CO
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 594 -
6F2S1927 (0.18)
4.2.8 Setting
DPSY01(FunctionID:511001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 595 -
6F2S1927 (0.18)
DPSY01(FunctionID:511001)
Setting items Range Unit Contents Default Note
FixedLogic /
DPSY01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
DPSY01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
DPSY01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
DPSY01-LGFEXOT - FixedLogic
PLC output
FixedLogic / Change logic about on direction execute
DPSY01-LGOEXOT - FixedLogic
PLC output
FixedLogic /
DPSY01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
DPSY01-PLSM Fix / Var - pulse mode Fix
DPSY01-CPW 0.1 - 50.0 s control pulse width 1.0
DPSY01-RST 1.0 - 100.0 s response check timer 30.0
NA / C-On / C-
DPSY01-CNTS - count status NA
Off / C-OnOff
DPSY01-OPETMEN Off / On - Operation Time Measurement enable Off
DPSY01-APBD Process / Bay - status change origin Process
DPSY01-CTRDIR Off / On - Capable control direction On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPSY function is also available for the second device; hence, the table for 2nd
device is available, but we have omitted the 2nd table because it is similar to the
table for the 1st device with the exception of the device number.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 596 -
6F2S1927 (0.18)
4.2.9 Signal
Signal monitoring points in DPSY01
DPSY(Function ID: 511001)
Element ID Name Description
8002011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
8002001F99 DPSY00_CH_EC_LCD DPSY00 count change execute command by LCD
8002001D5E DPSY00_CH_EC_OWS DPSY00 count change execute command by OWS(HMI)
8002001D5F DPSY00_CH_EC_RCC DPSY00 count change execute command by RCC
8002001D60 DPSY00_CH_EC_RMT DPSY00 count change execute command by Remote
8002001F98 DPSY00_CH_SC_LCD DPSY00 count change select command by LCD
8002001D5B DPSY00_CH_SC_OWS DPSY00 count change select command by OWS(HMI)
8002001D5C DPSY00_CH_SC_RCC DPSY00 count change select command by RCC
8002001D5D DPSY00_CH_SC_RMT DPSY00 count change select command by Remote
0002011FB6 DPSY01A_CNT_SEL DPSY01 A count change selected signal(stSeld) for SAS
3202011D24 DPSY01A_CNT_VAL DPSY01 A-phase count value
8302011F49 DPSY01A_FLT_DET DPSY01 A-phase Faulty Detected
8302011F48 DPSY01A_FLT_STA DPSY01 A-phase Faulty Start
3102011D14 DPSY01A_LCD_ST DPSY01 A-phase state for LCD
8202011F47 DPSY01A_UDF_DET DPSY01 A-phase Undefined Detected
8202011F46 DPSY01A_UDF_STA DPSY01 A-phase Undefined Start
0002011FB7 DPSY01B_CNT_SEL DPSY01 B count change selected signal(stSeld) for SAS
3202011D28 DPSY01B_CNT_VAL DPSY01 B-phase count value
8502011F4D DPSY01B_FLT_DET DPSY01 B-phase Faulty Detected
8502011F4C DPSY01B_FLT_STA DPSY01 B-phase Faulty Start
3102011D19 DPSY01B_LCD_ST DPSY01 B-phase state for LCD
8402011F4B DPSY01B_UDF_DET DPSY01 B-phase Undefined Detected
8402011F4A DPSY01B_UDF_STA DPSY01 B-phase Undefined Start
0002011FB8 DPSY01C_CNT_SEL DPSY01 C count change selected signal(stSeld) for SAS
3202011D2C DPSY01C_CNT_VAL DPSY01 C-phase count value
8702011F51 DPSY01C_FLT_DET DPSY01 C-phase Faulty Detected
8702011F50 DPSY01C_FLT_STA DPSY01 C-phase Faulty Start
3102011D1E DPSY01C_LCD_ST DPSY01 C-phase state for LCD
8602011F4F DPSY01C_UDF_DET DPSY01 C-phase Undefined Detected
8602011F4E DPSY01C_UDF_STA DPSY01 C-phase Undefined Start
3102011001 DPSY01_3PH_STATE DPSY01 3ph_state
3102011FE5 DPSY01_APH_STATE DPSY01 aph_state
0002011F58 DPSY01_AUTO_SIG DPSY01 Auto sequence signal
3102011FEA DPSY01_BPH_STATE DPSY01 bph_state
8302011E9C DPSY01_CCF_FCT_CS DPSY01 Release poor factor
8702011E96 DPSY01_CC_FS DPSY01 cancel fail signal
8602011E95 DPSY01_CC_SS DPSY01 cancel success signal
8802011E9B DPSY01_CC_ST_ERR DPSY01 Disagreement in the mode (the test in a release command)
0002011F59 DPSY01_CMNCTRL_SIG DPSY01 control receive signal
8602011F8A DPSY01_CNT_CS07 DPSY01 count change selected fail condition signal
0002011D91 DPSY01_CNT_SEL DPSY01 count change selected signal(stSeld) for SAS
0002011F56 DPSY01_CNT_SIG DPSY01 Count correction signal
3202011D20 DPSY01_CNT_VAL DPSY01 count value
3102011FEF DPSY01_CPH_STATE DPSY01 cph_state
8002011E9E DPSY01_CTR_SGC DPSY01 control logic stage(select command check)
8002011EA0 DPSY01_CTR_SGE DPSY01 control logic stage(execute command check)
8302011E9D DPSY01_CTR_SGN DPSY01 control logic stage(unselected)
8002011E9F DPSY01_CTR_SGS DPSY01 control logic stage(selected)
8B02011F79 DPSY01_CTR_SGU DPSY01 selected signal
8902011F9B DPSY01_CTR_SGUCN DPSY01 count change selected signal
8902011FA1 DPSY01_CTR_SGURS DPSY01 reset time selected signal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 597 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 598 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 599 -
6F2S1927 (0.18)
800201EE35 DEV01_CL_SYNC_INTER dev01 close command with interlock and synchronism check bypass
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 600 -
6F2S1927 (0.18)
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the DPSY function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “DPSY01_SC_OWS” point for
the 2nd device, use the description of “DPSY01_SC_OWS” in place of
“DPSY02_SC_OWS”. The user can obtain the ID value of
“DPSY02_SC_OWS” by using the following steps:
Step 1 Find the element ID for DPSY01_SC_OWS (i.e.,
“8002011D51”).
Step 2 Identify the number at the fifth digit from the ID. (i.e.,
“1”).
Step 3 Choose a new device number. (i.e. pick the number “2” for
the 2nd device).
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8002021D51” of
“DPSY02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 601 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.3-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– CBK, ISB, and SCB switches ✓ ✓ NA ✓ NA NA NA
– Number of switches except CBK, ISB, and SCB 61 61 NA 61 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 602 -
6F2S1927 (0.18)
Figure 4.3-1 shows the eight switches and their controller functions. The statuses of the S43
switches are stored in the IED non-volatile memory; hence, the IED can retrieve their status
while power is not being supplied to the IED.
Switches for
CMDBLK ILKBYP SCBYP special purposes
(CBK) (ICB) (SCB)
The SOFTSW function can control a number of S43 software switches separately. To
simplify the explanation provided below only the SOFTSW1 function is discussed. The features
provided in CBK, ICB, SCB and SOFTSW2–61 switches are similar to the SOFTSW1 switch.
Tips: The user can operate CBK, ICB and SCB without user programming. Jump to
section 4.3.5 where we discuss how to map their signals for IEC61850
communication. When the user wishes to program the SOFTSW functions using
the S43-01–S43-61 switches, the user is required to read from section 4.3.2
onwards.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 603 -
6F2S1927 (0.18)
conditions. (See control and operation logic for the respective control applications.)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 604 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 605 -
6F2S1927 (0.18)
0 t Select “success”
0.1s
Figure 4.3-6 Select logic for ‘ON’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note:“Select condition” signal is provided from select condition scheme. For more
information, see Figure 4.3-12.
§Note:An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The SOFTSW1 function is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter Control
and monitoring application: Automatic sequence control function.
*Note:The SOFTSW1 function can run on either the “SBO mode” or the “DIR mode”. The
user can use the signal “ctlmodel” in the IEC61850 communication.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 606 -
6F2S1927 (0.18)
(ii) Receiving “select command for Off operation” from the remote end
Input point required mapping
Figure 4.3-7 shows the logic when a “Select command (Remote-OFF-Control)” signal is applied
at the SOFTSW1 function. The input-point “S4301_CONTROL_REQ” is used for the reception
of the select command (Remote-OFF-Control).
Input Select logic in SOFTSW1 Output
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.3-7 Select logic for ‘OFF’ operation from remote end in SOFTSW1†
†Note: To identify the input and output points of the other SOFTSW logics, see Table
4.3-6 and Table 4.3-9.
‡Note:“Select condition” signal is provided in Figure 4.3-12.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 607 -
6F2S1927 (0.18)
panel
Input signal
Figure 4.3-8 shows the logic when a “Select command (Local-ON-Control)” signal is applied to
the SOFTSW1 function. The input signal is provided when “On” key is pressed on the IED
front panel; the input-point is not required to be mapped. Note that the user should set scheme
switch [S4301-CTRAHMI] to SBO when the operation from the IED front panel is performed;
chapter User interface: Control sub-menu discusses how to operate.
Input Select logic in SOFTSW1 Output
0.6s
[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.3-8 Select logic for ‘ON’ operation at the IED locally in SOFTSW1†
†Note: To identify the output points of the other SOFTSW logics, see Table 4.3-9.
‡Note:Signal “select condition” is provided. See Figure 4.3-12.
§Note:The SOFTSW1 function is blocked when the ASEQ function is in operation.
(iv) Receiving “Select command for Off operation” from the front panel
Input signal
Figure 4.3-9 shows the logic when a “Select command (Local-OFF-Control)” signal is applied
to the SOFTSW1 logic. The input signal is provided when the user presses “OFF” key on the
IED front panel; the input-point is not required to be mapped.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 608 -
6F2S1927 (0.18)
& “S4301_FSD_CSF”
(522001_8D0A041F45)
DIR
0 t
Select “success”
0.1s
0.6s
[S4301-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.3-9 Select logic for ‘OFF’ operation at the IED locally in SOFTSW1†
†Note: Figure 4.3-9 is used for the discussion of SOFTSW1 logic. To identify the output
points of the other SOFTSW logics, see Table 4.3-9.
‡Note:Signal “select condition” is provided. See Figure 4.3-12.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 609 -
6F2S1927 (0.18)
510001 7001016D08
& “S4301_OSD_CSF”
(522001_8F0A411F49)
0 t Select “success”
0.1s
(vi) Receiving “Select command for Off operation” using PLC function
Input signal required to connect
Figure 4.3-11 shows the SOFTSW1 logic for a “Select command (PLC-OFF-Control)” signal.
The input signal is generated using the user-programmed PLC logic; the user can connect the
signal for the PLC connection point “S4301_CHG_TO_OFF”.
510001 7001016D08
& “S4301_FSD_CSF”
(522001_8D0A411F45)
0 t Select “success”
0.1s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 610 -
6F2S1927 (0.18)
[S4301-EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 611 -
6F2S1927 (0.18)
5Note: Criteria “unmatched conditions” are decided when “Test-bit status” in command is
not identical to “IED test status”.
6Note: The user will need to program the PLC logic “Control hierarchy condition”. The
Control hierarchy condition provided by the user-programmed PLC logic may be
43R/L; the user can connect it at PLC connection point “S4301_CTRL_RIGHT” of
Table 4.3-5.
Table 4.3-4 PLC connection point #2 (Input points for ‘Off’ control)
Signal Number Signal Name Description M/O
522001 860A01EDE0 CBK_CHG_TO_OFF PLC OFF control for CBK O
522001 860A02EDE0 ICB_CHG_TO_OFF PLC OFF control for ICB O
522001 860A03EDE0 SCB_CHG_TO_OFF PLC OFF control for SCB O
522001 860A04EDE0 S4301_CHG_TO_OFF PLC OFF control for SOFTSW1 (S43-01) O
522001 860A05EDE0 S4302_CHG_TO_OFF PLC OFF control for SOFTSW2 (S43-02) O
522001 860A06EDE0 S4303_CHG_TO_OFF PLC OFF control for SOFTSW3 (S43-03) O
…. ….. ….
522001 860A40EDE0 S4361_CHG_TO_OFF PLC OFF control for SOFTSW61 (S43-61) O
Table 4.3-5 PLC connection point #3 (Input points on select condition logic)
Signal Number Signal Name Description M/O
522001 820A01ED50 CBK_CTRL_RIGHT Control hierarchy condition in CBK M
522001 820A02ED50 ICB_CTRL_RIGHT Control hierarchy condition in ICB M
522001 820A03ED50 SCB_CTRL_RIGHT Control hierarchy condition in SCB M
522001 820A04ED50 S4301_CTRL_RIGHT Control hierarchy condition in SOFTSW1 (S43-01) M
522001 820A05ED50 S4302_CTRL_RIGHT Control hierarchy condition in SOFTSW2 (S43-02) M
522001 820A06ED50 S4303_CTRL_RIGHT Control hierarchy condition in SOFTSW3 (S43-03) M
…. ….. ….
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 612 -
6F2S1927 (0.18)
Table 4.3-9 PLC monitoring points (ON and OFF selection completion)
Signal Number Signal Name Description
522001 8F0A011F49 CBK_OSD_CSF On Selection completed in CBK
522001 8F0A021F49 ICB_OSD_CSF On Selection completed in ICB
522001 8F0A031F49 SCB_OSD_CSF On Selection completed in SCB
522001 8F0A041F49 S4301_OSD_CSF On Selection completed in SOFTSW1 (S43-01)
522001 8F0A051F49 S4302_OSD_CSF On Selection completed in SOFTSW2 (S43-02)
522001 8F0A061F49 S4303_OSD_CSF On Selection completed in SOFTSW3 (S43-03)
…. …. …..
522001 8F0A401F49 S4361_OSD_CSF On Selection completed in SOFTSW61 (S43-61)
522001 8D0A011F45 CBK_FSD_CSF Off Selection completed in CBK
522001 8D0A021F45 ICB_FSD_CSF Off Selection completed in ICB
522001 8D0A031F45 SCB_FSD_CSF Off Selection completed in SCB
522001 8D0A041F45 S4301_FSD_CSF Off Selection completed in SOFTSW1 (S43-01)
522001 8D0A051F45 S4302_FSD_CSF Off Selection completed in SOFTSW2 (S43-02)
522001 8D0A061F45 S4303_FSD_CSF Off Selection completed in SOFTSW3 (S43-03)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 613 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 614 -
6F2S1927 (0.18)
Operation Failed
Unmatched condition &
detected†
Figure 4.3-13 Cancel logic by the reception of the command from the remote end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.
Cancel command
Command “Local-cancel”
Successes to cancel
&
Unmatched condition
& Operation Failed
detected†
Figure 4.3-14 Cancel logic by the reception of the command at local end
†Note: The criteria “unmatched conditions” are determined when the “Test-bit status” in
the ‘cancel’ command is not identical to the “IED test status”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 615 -
6F2S1927 (0.18)
“S4301_OEC_CHG”
Command “Remote-On-Control” (522001_890A041F5A)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
“S4301_FEC_CHG”
Command “Remote-OFF-Control” (522001_8A0A041F5B)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 616 -
6F2S1927 (0.18)
“S4301_OEC_CHG”
(522001_890A041F5A)
Operate Command
Command “Local-On-Control”
& OFF to ON
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
“S4301_FEC_CHG”
(522001_8A0A041F5B)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL “S4301_EX_SS”
(522001_870A041F62)
0 t
Operate failed
& d
1.0s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 617 -
6F2S1927 (0.18)
†Note: To identify the input and output signals of the other SOFTSW logics, see Table
4.3-12, Table 4.3-13, and Table 4.3-14.
‡Note: “operate condition” signal is provided from operate condition scheme. For more
information, see Figure 4.3-21.
§Note: The ASEQ function can provide sequential signals for automatic control.
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_810A041D03 Operate completed
S4301_ST_ON &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 618 -
6F2S1927 (0.18)
Operate condition‡
ASEQ function§” is in progress
ASEQ_MULTI_SEL
“S4301_EX_SS”
(522001_870A041F62)
522001_830A041D02 Operate completed
S4301_ST_OFF &
“S4301_PLC_CTRL_FAIL”
(522001_870A041F62)
0 t Operate failed
& d
1.0s
[S4301-EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 619 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 620 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 621 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 622 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 623 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 624 -
6F2S1927 (0.18)
Table 4.3-19 shows the required mapping signals in SOFTSW1 function to the IEC 61850
communications. Figure 4.3-25 shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 625 -
6F2S1927 (0.18)
Table 4.3-20 Mapping signals required for SPCSO object in SOFTSW1 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO701$SPCSO$SBOw ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$SBOw T Timestamp CO
Ctrl/GGIO701$SPCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$SBOw Check Check CO
Ctrl/GGIO701$SPCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Oper ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Oper ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Oper T Timestamp CO
Ctrl/GGIO701$SPCSO$Oper Test BOOLEAN CO
522001 700A046D08 S4301_CONTROL_REQ
Ctrl/GGIO701$SPCSO$Oper Check Check CO
Ctrl/GGIO701$SPCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO$Cancel ctlVal BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO701$SPCSO$Cancel T Timestamp CO
Ctrl/GGIO701$SPCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO701$SPCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO701$SPCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO701$SPCSO ctlModel ctlModel CF
Ctrl/GGIO701$SPCSO sboClass sboClass CF
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 626 -
6F2S1927 (0.18)
4.3.6 Setting
SOTFSW(FunctionID:522001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 627 -
6F2S1927 (0.18)
4.3.7 Signal
Signal monitoring points
SOFTSW(Function ID:522001)
Element ID Name Description
000A011001 CBK_STATE CMDBLK status
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 628 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 629 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 630 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 631 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 632 -
6F2S1927 (0.18)
…. …. ….
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 633 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 634 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 635 -
6F2S1927 (0.18)
….. …. …..
860A3FEDE0 S4360_CHG_TO_OFF SOFT 43 switch60 change to off
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the SOFTSW function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “S4301_EC_LCD” point for the
2nd device, use the description of “S4302_EC_LCD” in place of
“S4301_EC_LCD”. The user can obtain the ID value of “S4302_EC_LCD” by
using the following steps:
Step 1 Find the element ID for S4301_EC_LCD (i.e.,
“8C00041F45”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “4”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8C00051F45” of
“S4302_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 636 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.4-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– Number of timers 12 12 NA 12 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 637 -
6F2S1927 (0.18)
864,000,000sec
60sec
Operation time
0sec The TOTALTIM function
checks the state of the
operation signal every
second. If the operation
signal is in the “On” state,
TOTALTIM accumulates
TOTALTIM process the “On” time.
Figure 4.4-2 illustrates that 12 signals can be accommodated from external devices using
BIs. For example, when binary input circuit BI1 receives operating signal1, provided signal-
monitoring point “BI1” is applied for the acquisition of the signal, the user can make the logic
to connect “BI1” with TT01 of the TOTALTIM function using the PLC function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 638 -
6F2S1927 (0.18)
IED TOTALTIM
Device
TOTAL12_PLC_SGNL
TT12
PLC
SAS
Device #12 BI12-NC BI12 BI12-CPL
Photo- Filter CPL
Operating signal #12
coupler
TOTAL02_PLC_SGNL
TT02
PLC
Operating signal #1
Photo- Filter CPL
coupler
Contact-switch Binary IO module (BIO)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 639 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 640 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 641 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
Oper
origin
ctlmodel (choice ”DOes or DOns”)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 642 -
6F2S1927 (0.18)
Note: “Status (ST)” and “Measurement (MX)” are defined in the function constraint (FC)
of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 643 -
6F2S1927 (0.18)
Table 4.4-5 Mapping signals required for GGIO1301 object in TTIM01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO1301$ISCSO1$SBOw ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$SBOw ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$SBOw T Timestamp CO
Ctrl/GGIO1301$ISCSO1$SBOw Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$SBOw Check Check CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Oper ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Oper T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Oper Test BOOLEAN CO
5410017015016D08 TOTAL01_CMM_REQ
Ctrl/GGIO1301$ISCSO1$Oper Check Check CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlVal INT32 CO
Ctrl/GGIO1301$ISCSO1$Cancel ctlNum INT8U CO
Ctrl/GGIO1301$ISCSO1$Cancel T Timestamp CO
Ctrl/GGIO1301$ISCSO1$Cancel Test BOOLEAN CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orCat orCategory CO
Ctrl/GGIO1301$ISCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO1301$ISCSO1 ctlModel ctlModel CF
Ctrl/GGIO1301$ISCSO1 sboClass sboClass CF
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 644 -
6F2S1927 (0.18)
4.4.4 Setting
TOTALTIM(Function ID: 541001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 645 -
6F2S1927 (0.18)
4.4.5 Signal
Signal monitoring points
TOTALTIM(Function ID: 541001)
Element ID Name Description
0015001F41 TTIM00_CCTRL_TIME TTIM00 total time correction summarize
0015011D91 TTIM01_TMP_01 TTIM01 total time change selected signal(stSeld) for SAS
0015021D91 TTIM02_TMP_01 TTIM02 total time change selected signal(stSeld) for SAS
0015031D91 TTIM03_TMP_01 TTIM03 total time change selected signal(stSeld) for SAS
0015041D91 TTIM04_TMP_01 TTIM04 total time change selected signal(stSeld) for SAS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 646 -
6F2S1927 (0.18)
0015051D91 TTIM05_TMP_01 TTIM05 total time change selected signal(stSeld) for SAS
0015061D91 TTIM06_TMP_01 TTIM06 total time change selected signal(stSeld) for SAS
0015071D91 TTIM07_TMP_01 TTIM07 total time change selected signal(stSeld) for SAS
0015081D91 TTIM08_TMP_01 TTIM08 total time change selected signal(stSeld) for SAS
0015091D91 TTIM09_TMP_01 TTIM09 total time change selected signal(stSeld) for SAS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 647 -
6F2S1927 (0.18)
00150A1D91 TTIM10_TMP_01 TTIM10 total time change selected signal(stSeld) for SAS
00150B1D91 TTIM11_TMP_01 TTIM11 total time change selected signal(stSeld) for SAS
00150C1D91 TTIM12_TMP_01 TTIM12 total time change selected signal(stSeld) for SAS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 648 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 649 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.5-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA NA NA NA NA
– Number of controls 2 2 NA NA NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 650 -
6F2S1927 (0.18)
OVr relay (59r) for running line Verification of voltage Permission signal
conditions and issued to DPSY
OVi relay (59i) for incoming line synchronization between logics
Issue CB closing
command
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 651 -
6F2S1927 (0.18)
operating area of OV characteristic. The OVr1 element is used to check for the presence of
voltage on the running-line; similarly, the OVi1 element is used to check for the presence of
voltage on the incoming-line. The user can set pick-up thresholds using the settings [OVR1]
and [OVI1].
Vr†, Vi‡
0 V
Pickup Voltage
Vr†, Vi‡
0 V
Drop-off Voltage
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 652 -
6F2S1927 (0.18)
Settings [OVR1]
and [OVI1]
Setting [SyncRy1-Angle]
Vi
Δ
Vr
V
Setting [SyncRy1-dV]
The provision of a signal for CB closure between two networks may be required subject
to the variance of the two voltages, phase-angles and frequencies being small. Therefore, the
SYNCHK function continuously monitors the Δθ, ΔV and Δf; subsequently the SYNCHK
function issues an operate-permission signal to the DPSY function when the variance is less
than the permissible range. For this purpose, synchronism-relays (SyncRy1-dV, SyncRy1-df,
SyncRy1-dθ) are provided; the user can set them in accordance with their specific requirements.
Figure 4.5-4 shows the angle-variance between Vi and Vr; the increment or decrement of
the angle-variance (Δθ) is shown based upon the running voltage Vr.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 653 -
6F2S1927 (0.18)
Δ increasing
Vi
Vi‡ Δ reducing
Δ near
Vi zero
Δ Vi
Vr†
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 654 -
6F2S1927 (0.18)
Frequency-variance (Δf)
The frequency-variance of Vr and Vi (Δf) is measured by the frequency-variance relay having
the setting [SyncRy1-df]. If the following equations are satisfied, the SyncRy1-df relay
determines that the frequency-variance is inside the permissible range.
where,
fVr Frequency of Vr
fVi Frequency of Vi
Δf Frequency-variance between Vr and Vi
Setting [SyncR1-Angle]
∆f > (4.5-7)
180° × Setting [SYNC01_TSYN]
where,
Δf= Frequency-variance (or cycle-slip in Hertz)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 655 -
6F2S1927 (0.18)
2 × Setting [SyncR1-Angle] 1
Time = × (4.5-9)
360° ∆f[Hz]
2 × Setting [SyncR1-Angle] 1
Setting [SYNC01_TSYN] < × (4.5-10)
360° ∆f[Hz]
Equations rearrangements:
Setting [SyncR1-Angle] 1
Setting [SYNC01_TSYN] < × (4.5-11)
180° ∆f[Hz]
1 𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYNC01_TSYN] 1
> ÷ (4.5-12)
∆𝑓[𝐻𝑧] Setting [SyncR1-Angle] 180°
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SyncR1-Angle] 1
𝑆𝑒𝑡𝑡𝑖𝑛𝑔 [SYNC01_TSYN] < × (4.5-13)
180° ∆𝑓[𝐻𝑧]
Vr :Frequency: f1
Vi :Frequency: f2
time
Δf Δf Δf
Vi
50s SyncR1-Angle
Vr Synchronism zone
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 656 -
6F2S1927 (0.18)
Advance time
The user shall consider the actual device operation time. For an asynchronous network, the
issue of the CB closure command should be initiated such that it is coordinated with the actual
closing. Figure 4.5-6 shows the advancing time; it is introduced with setting [SyncRy1-TCB],
closing time (Tcb) and compensation time:
where,
α: Operation time of the element
β: Compensation (i.e., tolerance) time
Tcb: Closing time of CB
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 657 -
6F2S1927 (0.18)
Vr
Vi
Vr − Vi
Δθ
Start to close CB
End of closing CB
Time
α TCB β
Setting
CB closing command
Tolerance for synchronism
CB contact
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 658 -
6F2S1927 (0.18)
DRLI LRLI
Setting [OVI1]
Setting [UVI1]
DRDI LRDI
Vr on the running line
Setting [UVR1] Setting [OVR1]
For example, “DRLI” zone covers the case when the running-line is out-of-service (DR)
and the incoming-line is in-service (LI). Table 4.5-4 exemplifies the areas in accordance with
the voltage conditions.
Table 4.5-4 Four voltage conditions and zones
Voltage condition 1 2 3 4
Area D○
R L○
I L○
R L○
I D○
R D○
I L○
R D○
I
○
R unning line (Vr) (Dead) (Live) (Dead) (Live)
○
I ncoming line (Vi) (Live) (Live) (Dead) (Dead)
Figure 4.5-8 and Figure 4.5-9 show the voltage-presence (or voltage-absence) check logic
used in the SYNCHK_Ry1 and Ry2 functions.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 659 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 660 -
6F2S1927 (0.18)
511001 8002011E45
Close command (Select)
DPSY01_OSE_RCV
DRLI1
UVi &
DRDI1 LRDI1 SYNCHK1 (Function ID: 560001)
On
SYNC01-LRDIEN
On
SYNC01-DRLIEN
On
SYNC01-DRDIEN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 661 -
6F2S1927 (0.18)
511001 8002021E45
i LRLI1
&
DRLI1 LRLI1
OVi LRDI1
&
DRLI1
UVi &
DRDI1 LRDI1 SYNCHK2 (Function ID: 560001)
On
SYNC02-LRDIEN
On
SYNC02-DRLIEN
On
SYNC02-DRDIEN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 662 -
6F2S1927 (0.18)
For example, if the DPSY01 function is required to operate when the voltage condition
“LRDI” is confirmed (Table 4.5-4.(4)), just set On for the scheme switch [SYNCHK01-LRDIEN].
User programmable pick-up delay timers are available for the conditions “LRDI” and
“DRLI” (Table 4.5-4.(1 and 4)); hence the user can set a desired value for the setting
[SYNC01_TLRDIDRLI]; similarly, a desired value can be applied for the setting
[SYNC01_TDRDI] for the condition “DRDI” (Table 4.5-4.(3)).
†Note:This signal is required for CB closing in the select logic. For more information, see
separate section DPSY: Control logics.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 663 -
6F2S1927 (0.18)
561001 8602001B66
SyncRy2
-df Δf2: Frequency-variance of Running and Incoming
561001 8402001B64
SyncRy2
-dƟ ΔƟ2: Phase-variance of Running and Incoming
Figure 4.5-14 shows the synchronization check logic in the SYNCHK1 function. The user
should note that the logic has been separated for (1) the synchronous condition and (2) the
asynchronous condition; the synchronization check logic is initiated when the
“DPSY01_OEC_RCV” signal is received, which is identical to an operate-command in the On-
direction.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 664 -
6F2S1927 (0.18)
Off SYNC01_SBP
560001 800B01EDE1 SYNC01_SBP_SSP Bypassing condition
SYNC01-SYNCHK1EN Sync bypass
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 665 -
6F2S1927 (0.18)
560001 800B021F54
560001 800B02EDE5 SYNC02_SPS_CL_ECP
Off SYNC02_SBP
SYNC02-SYNCHK2EN Sync bypass
560001 800B02EDE1 SYNC02_SBP_SSP Bypassing condition
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 666 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 667 -
6F2S1927 (0.18)
V3 V4
V1
Relay selection logic programmed by the user
SYNCHK01 function
using the PLC function
✔
Ry2
Ry1 Line
In Figure 4.5-16 , two signals are used for relay selection, but the user should note that
the selection-signals are provided in accordance with the actual line and bus-bar arrangement.
Figure 4.5-17 shows the overall logic used for the selection. The user can program the selection-
signals using the PLC function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 668 -
6F2S1927 (0.18)
&
&
&
&
&
≥
& To DPSY02
& ≥ 560001 850B021F59
SYNCHK2
SYNC02_SYN_CLC
& ≥ (Function ID: 560001) Sync success
&
& ≥
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 669 -
6F2S1927 (0.18)
Signal Setting
names names SYNCHK_ Ry1
V L1 →V-L1
Relays for
incoming voltage
Vs →Vs
Relays for
running voltage
Relays for
incoming voltage
VCT
Figure 4.5-18 illustrates that the signals injected are distributed using scheme switches:
[SyncRy1-VR], [SyncRy1-VI], [SyncRy1-VR], and [SyncRy1-VI]. Examples below show how to
apply a voltage signal for the required relay-element.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 670 -
6F2S1927 (0.18)
Busbar#1
Busbar#2 ✔
DS1 closed
& SYNC01_RY1_USE_STS
DS2 closed
V V2 DS1 DS2
S43P logic programmed Selection of SYNCHK_Ry1
CB1 by the user
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 671 -
6F2S1927 (0.18)
4.5.7 Setting
Synchronism (Function ID: 560001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 672 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 673 -
6F2S1927 (0.18)
4.5.8 Signal
Signal monitoring points
SYNDIF (Function ID: 560001)
Element ID Name Description
880B011F5C SYNC01_DDV_CS SYNC DEV1 27Vr & 27Vi condition signal
800B011F81 SYNC01_RY1_USE_STS SYNC DEV1 Relay Module1 use status from PLC
800B011F82 SYNC01_RY2_USE_STS SYNC DEV1 Relay Module2 use status from PLC
800B011F80 SYNC01_SS_VCS_PLC SYNC DEV1 success voltage condition signal from PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 674 -
6F2S1927 (0.18)
800B021F81 SYNC02_RY1_USE_STS SYNC DEV2 Relay Module1 use status from PLC
800B021F82 SYNC02_RY2_USE_STS SYNC DEV2 Relay Module2 use status from PLC
800B021F80 SYNC02_SS_VCS_PLC SYNC DEV2 success voltage condition signal from PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 675 -
6F2S1927 (0.18)
800B01EDE9 SYNC01_DLV_CL_ECP SYNC DEV1 27Vr & 84Vi close enable condition signal from PLC
800B01EDE8 SYNC01_LDV_CL_ECP SYNC DEV1 84Vr & 27Vi close enable condition signal from PLC
800B01EDE7 SYNC01_LLV_CL_ECP SYNC DEV1 84Vr & 84Vi close enable condition signal from PLC
800B01EDE6 SYNC01_LPS_CL_ECP SYNC DEV1 loop synchronism close enable condition signal from PLC
800B01EDED SYNC01_RY1_USE_STS SYNC DEV1 Relay Module1 use status from PLC
800B01EDEE SYNC01_RY2_USE_STS SYNC DEV1 Relay Module2 use status from PLC
800B01EDEB SYNC01_SBK_CSP SYNC DEV1 synchronism block condition signal from PLC
800B01EDE0 SYNC01_SBP_ECP SYNC DEV1 synchronism bypath enable condition signal from PLC
800B01EDE1 SYNC01_SBP_SSP SYNC DEV1 synchronism bypath success condition signal from PLC
800B01EDE4 SYNC01_SCL_CSP SYNC DEV1 synchronism close condition signal from PLC
800B01EDE2 SYNC01_SCL_F_ECP SYNC DEV1 synchronism close fail condition signal from PLC
800B01EDE3 SYNC01_SCL_SSP SYNC DEV1 synchronism close success condition signal from PLC
800B01EDE5 SYNC01_SPS_CL_ECP SYNC DEV1 split SYNC. close enable condition signal from PLC
800B01EDEC SYNC01_SS_VCS_PLC SYNC DEV1 success voltage condition signal from PLC
800B02EDEA SYNC02_DDV_CL_ECP SYNC DEV2 27Vr & 27Vi close enable condition signal from PLC
800B02EDE9 SYNC02_DLV_CL_ECP SYNC DEV2 27Vr & 84Vi close enable condition signal from PLC
800B02EDE8 SYNC02_LDV_CL_ECP SYNC DEV2 84Vr & 27Vi close enable condition signal from PLC
800B02EDE7 SYNC02_LLV_CL_ECP SYNC DEV2 84Vr & 84Vi close enable condition signal from PLC
800B02EDE6 SYNC02_LPS_CL_ECP SYNC DEV2 loop synchronism close enable condition signal from PLC
800B02EDED SYNC02_RY1_USE_STS SYNC DEV2 Relay Module1 use status from PLC
800B02EDEE SYNC02_RY2_USE_STS SYNC DEV2 Relay Module2 use status from PLC
800B02EDEB SYNC02_SBK_CSP SYNC DEV2 synchronism block condition signal from PLC
800B02EDE0 SYNC02_SBP_ECP SYNC DEV2 synchronism bypath enable condition signal from PLC
800B02EDE1 SYNC02_SBP_SSP SYNC DEV2 synchronism bypath success condition signal from PLC
800B02EDE4 SYNC02_SCL_CSP SYNC DEV2 synchronism close condition signal from PLC
800B02EDE2 SYNC02_SCL_F_ECP SYNC DEV2 synchronism close fail condition signal from PLC
800B02EDE3 SYNC02_SCL_SSP SYNC DEV2 synchronism close success condition signal from PLC
800B02EDE5 SYNC02_SPS_CL_ECP SYNC DEV2 split SYNC. close enable condition signal from PLC
800B02EDEC SYNC02_SS_VCS_PLC SYNC DEV2 success voltage condition signal from PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 676 -
6F2S1927 (0.18)
When using the ILK function, an interlock-check formula is required. The interlock-check
formula examines the operational conditions for all devices, and is stored in the ILK database.
The ILK function provides an output signal “OK/NG decision information”; the “OK/NG
decision information” is transferred to the control functions†, which control the external
devices. Following which, the control functions can commence with the control of the selected
devices in response to the respective “OK/NG decision information”.
†Note:Details of SPOS, DPSY, and TPOS features are discussed separately elsewhere in
the instruction manual under the Chapter Control and monitoring applications.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.6-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 677 -
6F2S1927 (0.18)
Prior to controlling a device, the interlock-check function is used to determine whether the
control of a device is correct or not. If the interlock-check finds that the conditions for device
control have not been satisfied in accordance with the appropriate interlock condition, control
of the device is forbidden. Figure 4.6-1 provides an overview of the interlock-check process.
Formulae for interlock-check are stored in an ILK database; these formulae are used in order
to enable the interlock-check function to output a decision. If the proposed operation of a
particular device is deemed correct then an “OK-decision” is determined by the formulae, and
device control is allowed. However, if the proposed operation of the device is deemed incorrect
then an “NG-decision” is determined by the formulae, and device control is not allowed.
Device IED
Binary
Circuit input Control
breaker Interlock Control
Device status circuits Device status Functions
(CB) Device status Function (ILK)
SPOS
DPOS
Dis- Binary OK/NG decision Interlock
and
connector Output
others
(DS) circuits
Device control Control Database
Other IE Ds
GOOSE GOOSE receiving information
GOOSE subscription
data
transmission
data
PC(GR-TIEMS)
Interlock formulas
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 678 -
6F2S1927 (0.18)
Q0 Q0B
Q53
Q9 Q8
Q69
F52VT
F27L
In accordance with the arrangement of the devices shown in Figure 4.6-2, interlock-check
formulae can be configured from equations (4.6-1) to (4.6-9). The status of respective devices,
(stVal) and interlock operators (“•” and “+”) are placed on the right-hand side of the equations;
and the interlock condition (e.g. Q0(Closing)) is placed on the left-hand side of the equations.
The interlock operators are also shown in Table 4.6-2.
̅̅̅̅ ∙ Q2
Q1 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q15 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.6-1)
+ (Q2 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
̅̅̅̅ ∙ Q1
Q2 = (Q0 ̅̅̅̅̅ ∙ Q52
̅̅̅̅ ∙ Q25 ̅̅̅̅̅ ∙ Q53
̅̅̅̅̅)
(4.6-2)
+ (Q1 ∙ Q0 ∙ Q9 ∙ Q0B ∙ Q1B ∙ Q2B)
Q9 = (Q0 ̅̅̅̅̅ ∙ Q53
̅̅̅̅ ∙ Q52 ̅̅̅̅̅ ∙ Q8
̅̅̅̅) (4.6-3)
Q0(Closing ‡)
= ̅̅̅̅̅̅̅̅̅ ̅̅̅̅̅̅̅̅̅
63QBE ∙ 63GBE
̅̅̅̅ ∙ ̅̅̅̅
∙ ((Q1 Q2 ∙ ̅̅̅̅
Q9) + ((Q1 + Q2) ∙ Q9)) (4.6-4)
∙ Closing Blocking
̅̅̅̅̅̅̅̅̅ ∙ 63GBE
Q0(Opening‡ ) = 63QBF ̅̅̅̅̅̅̅̅̅ (4.6-5)
̅̅̅̅ ∙ Q69 ∙ F27L(No voltage) ∙ F52VT)
Q8 = (Q9 (4.6-6)
̅̅̅̅ ∙ ̅̅̅̅
Q52 = (Q9 Q1 ∙ ̅̅̅̅
Q2) (4.6-7)
̅̅̅̅ ∙ Q1
Q53 = (Q9 ̅̅̅̅ ∙ Q2
̅̅̅̅) (4.6-8)
Q69 = Q8 (4.6-9)
where,
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 679 -
6F2S1927 (0.18)
For example in equation (4.6-12), the interlock condition for DS (Q1) is satisfied when CB
(Q0), DS (Q2), ES for the Bus-bar1-A (Q15), ES (Q52) and ES (Q53) are open. In addition, the
interlock condition for DS (Q1) is also satisfied when DS (Q2), CB (Q0), DS (Q9), CB (Q0), DS
(Q1), and DS (Q2) are closed.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 680 -
6F2S1927 (0.18)
Node
stVal OR (+)
Input(A)
stVal
Quality Output
Quality
Input(B) stVal
Quality
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 681 -
6F2S1927 (0.18)
Node #1
Node #2 Node #7
OR (+) AND(• )
Input A AND(• )
Input B
Output
Input C
Input D Node #4
Node #3
OR (+)
AND(• )
Input E
Input F
Input G
Node #5 Node #6
AND(• )
OR (+)
Input H
Input I
Input J
We can see that equation (4.6-10) is a representation of Figure 4.6-4. This equation is computed
in accordance with the priority order of the interlock-operators: the first is parentheses [()], the
second is AND [•], followed by OR [+].
Output = ((A+B) •C) + (D+E•F) + (G•(H+I) •J) (4.6-10)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 682 -
6F2S1927 (0.18)
Figure 4.6-5 shows the logic symbol for the interlock operator “AND” with input signals
and an output signal. Figure 4.6-5 can be represented by equations (4.6-11) and (4.6-12).
stVal = stVa(A) • stVa(B) (4.6-11)
Quality=(Quality(A)+Quality(B))•(stVa(A)+ Quality(A))
(4.6-12)
•(stVa(B)+Quality(B))
For example, when the interlock operator “AND” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–OK) using the equations (4.6-11) and (4.6-12). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the AND operator; the AND
operator produces zero (0) which is defined as “OK” in ‘Quality’. A note regarding the values
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 683 -
6F2S1927 (0.18)
AND (• )
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B)
Quality
OR interlock operator
When quality information (Quality) is applied to the interlock operator “OR”, the quality
information is affected by device status (stVal). Table 4.6-5 shows two-input-signals (A, B) and
the output signal for “OR”
Table 4.6-5 Output signals (stVal–Quality) of OR
Input B (stVal–Quality)
0–OK 0–NG 1–OK 1–NG
0–OK 0–OK – – –
Input A 0–NG 0–NG 0–NG – –
(stVal–Quality) 1–OK 1–OK 1–OK 1–OK –
1–NG 1–NG 1–NG 1–OK 1–NG
As shown in Table 4.6-5, if ‘0’ represents the status value “stVal” for all input signals, and
if the quality information of “NG” is given for an input signal, then the output signal “Quality”
is represented as “NG”. On the other hand, if all input signals “stVal” are represented by “1”,
and if the quality information for the input signals “stVal(1)” is given, then the representation
“OK” can be weighted for the output signal “Quality” . Note that quality information (OK) for
input signals with “stVal(1)” get priority if there are two or more input signals, which are
represented as “stVal(1)”.
Figure 4.6-6 shows the logic symbol for the interlock operator “OR” with input signals and an
output signal, which can be represented by equations (4.6-13) and (4.6-14).
OR (+)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 684 -
6F2S1927 (0.18)
For example, when the interlock operator “OR” has two input signals (0–NG, 0–OK), it
has to generate a signal (0–NG) using the equations (4.6-13) and (4.6-14). This is because the
quality “NG (i.e., 1)” and the quality “OK (i.e., 0)” are entered into the OR operator; the OR
operator produces one (1) which is defined as “NG” in ‘Quality’. A note regarding the values
used for Quality can be found immediately below Table 4.6-3
Figure 4.6-7 depicts the logic symbol for the interlock operator “NOT” with input signals
and an output signal, which can be represented by equations (4.6-15) and (4.6-16).
NOT(!)
Input(A) stVal
Quality
stVal
Output
Quality
stVal
Input(B) Quality
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 685 -
6F2S1927 (0.18)
Figure 4.6-8 depicts the logic symbol for the interlock operator “COMP” with input signals
and an output signal, which can be represented by equations (4.6-17) and (4.6-18).
stVal=stVa(A) COMP stVa(B) (4.6-17)
Quality=Quality(A) † (4.6-18)
†Note: Input signal (B) does not have quality information because its signal is a
threshold value.
COMP
Input(A) stVal
Quality
stVal
Output
Quality
Input(B) stVal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 686 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 687 -
6F2S1927 (0.18)
4.6.5 Signal
Signal monitoring point
ILK (Function ID: 570001)
Element ID Name Description
3100A11001 ILK_MID_UPDATING ILK condition number during counting
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 688 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 689 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 690 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 691 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 692 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 693 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.7-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– Number of controls 72 72 NA 72 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 694 -
6F2S1927 (0.18)
Cancel logic
Select command Off from the remote-end
Output signal to BO
The DPOS01 function can issue a “Select success” signal at the output point
“DPOS01_OSL_BO_FLG”, when the DPOS01 function determines that the “Remote-ON-
Control” signal is true. If the DPOS01 function determines that the “Remote-ON-Control”
signal is not true, the DPOS01 function returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 695 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 696 -
6F2S1927 (0.18)
Cancel logic
Output signal to BO
The DPOS01 function, in Figure 4.7-4, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_FLG” when the DPOS01 function determines that the received “Select
command Off (Remote-OFF-Control)” signal is true. If the DPOS01 function determines that
the “Remote-OFF-Control” signal is not true, the DPOS01 function returns to the “Wait for a
command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 697 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 698 -
6F2S1927 (0.18)
Cancel logic
Cancel command
Select command On from the remote-end
Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_OSL_BO_CSF”.
Note: The “DPOS01_OSL_BO_CSF” signal is the same as the signal shown in Figure
4.7-2. If the input signal “Local-ON-Control” is not true, the DPOS01 function
returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 699 -
6F2S1927 (0.18)
0.6s
[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 700 -
6F2S1927 (0.18)
Cancel logic
Select command On from the remote-end Cancel command
Cancel logic
Select command On from the local-end
Output signal to BO
When the “select condition” signal is true, the DPOS01 function can issue a “Select success”
signal at the output-point “DPOS01_FSL_BO_FLG”.
1Note: The signal “DPOS01_FSL_BO_FLG” is the same as the signal shown in Figure
4.7-4. If the signal “Local-OFF-Control” is not true, the DPOS01 function returns
to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 701 -
6F2S1927 (0.18)
0.6s
[DPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 702 -
6F2S1927 (0.18)
Cancel logic
Cancel command
Select command On from the remote-end
Operate logic
Select command On by PLC function
Failed Operate command
Output signal to BO
The DPOS01 function, in Figure 4.7-10, can issue a “Select success” signal at the output-point
“DPOS01_OSL_BO_CSF”1.
1Note: The “DPOS01_OSL_BO_CSF” signal is the same signal as that shown in Figure
4.7-2.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 703 -
6F2S1927 (0.18)
1≥ &
ON-control command requiring ILK† checking To “Wait for a next
For DIR operation
(PLC #1 connection point) command”
Operate command
512001 800301EE33 DEV01_CL_INTERLOCK To BO connection
with ILK† condition
& “DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
ILK† condition (“ON”) passed
DPOS01-Close 0 t
Select “success”
0.1s
ON-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point) 0 t
Operate command Select “Failed”
512001 800301EE32 DEV01_CL_COMMAND
without ILK† condition & 0.6s
Select condition‡
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 704 -
6F2S1927 (0.18)
Cancel logic
Cancel command
Select command On from the remote-end
Operate logic
Select command On by the PLC function
Operate command
Output signal to BO
The DPOS01 function, in Figure 4.7-12, can issue a “Select success” signal at the output point
“DPOS01_FSL_BO_CSF”1.
1Note: The output point “DPOS01_FSL_BO_CSF” is the same signal as that shown in
Figure 4.7-4.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 705 -
6F2S1927 (0.18)
1≥ &
OFF-control command requiring ILK† checking For DIR operation
(PLC#1 connection point)
Operate command with To BO connection
512001 800301EE31 DEV01_OP_INTERLOCK
ILK† condition & “DPOS01_FSL_BO_CSF”
ILK† condition (“OFF”) passed (512001_8A03011DC4)
DPOS01-Open 0 t
Select “success”
0.1s
OFF-control command requiring no ILK† checking For DIR operation To “Wait for a command”
(PLC#2 connection point)
0 t
Operate command Select “Failed”
512001 800301EE30 DEV01_OP_COMMAND
without ILK† condition & 0.6s
Select condition‡
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 706 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 707 -
6F2S1927 (0.18)
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 708 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 709 -
6F2S1927 (0.18)
Table 4.7-3 PLC Connection points (Input points for Command ‘Off’)
Signal Number Signal Name Description M/O
512001 800301EE30 DEV01_OP_COMMAND DPOS01 PLC Off-control checking with interlock(PLC#1) O
512001 800302EE30 DEV02_OP_COMMAND DPOS02 PLC Off-control checking with interlock(PLC#1) O
512001 800303EE30 DEV03_OP_COMMAND DPOS03 PLC Off-control checking with interlock(PLC#1) O
…. …. ….
512001 800348EE30 DEV72_OP_COMMAND DPOS72 PLC Off-control checking with interlock(PLC#1) O
512001 800301EE31 DEV01_OP_INTERLOCK DPOS01 PLC Off-control without checking(PLC#2) O
512001 800302EE31 DEV02_OP_INTERLOCK DPOS02 PLC Off-control without checking(PLC#2) O
512001 800303EE31 DEV03_OP_INTERLOCK DPOS03 PLC Off-control without checking(PLC#2) O
…. …. ….
512001 800348EE31 DEV72_OP_INTERLOCK DPOS72 PLC Off-control without checking(PLC#2) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 710 -
6F2S1927 (0.18)
Table 4.7-7 PLC Connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
512001 810301EE62 DPOS01IN_TMP_32 DPOS01 additional failure condition(PLC#1) O
512001 810302EE62 DPOS02IN_TMP_32 DPOS02 additional failure condition(PLC#1) O
512001 810303EE62 DPOS03IN_TMP_32 DPOS03 additional failure condition(PLC#1) O
…. …. ….
5A0101 801016EF40 DPOS72IN_TMP_32 DPOS72 additional failure condition(PLC#1) O
512001 800301EE61 DPOS01IN_TMP_31 DPOS01 user configurable select condition(PLC#2) O
512001 800302EE61 DPOS02IN_TMP_31 DPOS02 user configurable select condition(PLC#2) O
512001 800303EE61 DPOS03IN_TMP_31 DPOS03 user configurable select condition(PLC#2) O
… … …
512001 800348EE61 DPOS72IN_TMP_31 DPOS72 user configurable select condition(PLC#2) O
512001 820301ED50 DPOS01IN_TMP_28 DPOS01 control hierarchy condition(PLC#3) M
512001 820302ED50 DPOS02IN_TMP_28 DPOS02 control hierarchy condition(PLC#3) M
512001 820303ED50 DPOS03IN_TMP_28 DPOS03 control hierarchy condition(PLC#3) M
…. …. ….
512001 820348ED50 DPOS04IN_TMP_28 DPOS20 control hierarchy condition(PLC#3) M
Table 4.7-8 PLC Monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 711 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 712 -
6F2S1927 (0.18)
Operate logic
Output signal to BO
The DPOS01 function can issue a “Success to cancel” signal at the monitoring point
“DPOS01_CC_SS”, when the DPOS01 function has determined that the signal “Remote-cancel”
is true. Another signal “Operation failed” is issued at monitoring point “DPOS01_CC_FS” if
the DPOS01 function is able to determine that the signal “Remote-cancel” is not true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 713 -
6F2S1927 (0.18)
510001 7001016D08
“DPOS01_CC_FS”
(512001_8703011E96)
Operation Failed
Operate logic
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 714 -
6F2S1927 (0.18)
510001 7001016D08
Operation Failed
Output signal to BO
The DPOS01 function, illustrated in Figure 4.7-17, is able to issue a “Success of cancel” signal
at the monitoring point “DPOS01_CC_SS”, when the DPOS01 function determines that the
signal “Local-Cancel” is true.
[DPOS01-LGCNFFCT]
PLC#1
User configurable condition (PLC connection point)
Fixedlogic
512001 800301EE69 DPOS01IN_TMP_44 &
If the original logic does not meet with the requirement of the user, it can be relpced using
the connection point “User configurable condition”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 715 -
6F2S1927 (0.18)
Table 4.7-11 PLC connection points (Input signal for ‘cancel’ condition logic)
Signal Number Signal Name Description M/O
512001 800301EE69 DPOS01IN_TMP_44 DPOS01 user configurable cancel condition O
512001 800302EE69 DPOS02IN_TMP_44 DPOS02 user configurable cancel condition O
512001 800303EE69 DPOS03IN_TMP_44 DPOS03 user configurable cancel condition O
… … … O
512001 800348EE69 DPOS72IN_TMP_44 DPOS72 user configurable cancel condition O
Table 4.7-12 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
512001 8603011E95 DPOS01_CC_SS DPOS01 cancel success
512001 8603021E95 DPOS02_CC_SS DPOS02 cancel success
512001 8603031E95 DPOS03_CC_SS DPOS03 cancel success
… … …
512001 8603481E95 DPOS72_CC_SS DPOS72 cancel success
512001 8703011E96 DPOS01_CC_FS DPOS01 cancel failed
512001 8703021E96 DPOS02_CC_FS DPOS02 cancel failed
512001 8703031E96 DPOS03_CC_FS DPOS03 cancel failed
…. … …
512001 8703481E96 DPOS72_CC_FS DPOS72 cancel failed
DPOSxx-LGCNFFCT Logic selector for cancel condition in DPOSxx Fixedlogic Fixedlogic / PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 716 -
6F2S1927 (0.18)
Failed Do nothing
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.7-20, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the received signal “Remote-
On-Control” is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 717 -
6F2S1927 (0.18)
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
Command “Remote-On-Control” (512001 8103011E82)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 718 -
6F2S1927 (0.18)
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.7-14 for PLC#1, Table 4.7-15 for PLC#2, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [DPOS01-RST] has been reached.
Select command On from the remote-end Operate command On from the remote-end
Failed Do nothing
Select command On from the local-end Operate command On l from the local-end
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.7-22, can issue an “Operate” signal at the output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Remote-
Off-Control” is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 719 -
6F2S1927 (0.18)
“DPOS01_FEC_OK_CSF”
(512001 8003011E7E)
DPOS01 function (Function ID: 512001)
“DPOS01_FEC_OK_CS”
Command “Remote-Off-Control” (512001 8003011E81)
[DPOS01-CPW]
512001_7001016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
“DPOS01_FEC_OK_CSF &
1.0s- 100.0s Operate Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 720 -
6F2S1927 (0.18)
††Note: To identify the input and output signals of the other DPOS logics, see Table
4.7-15 for PLC#2, Table 4.7-16 for PLC#3, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command On from the remote-end Operate command On from the local-end
Select command Off from the remote-end Operate command Off from the local-end
Failed Do nothing
Select command Off from the local-end Operate command Off from the local-end
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.7-24, can issue an “Operate” signal at the output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “Local-On-Control”
is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 721 -
6F2S1927 (0.18)
To BO connection
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS1 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
(512001 8103011E82)
Operate Cmd.
Command “Local-On-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“ON”) passed
DPOS01-Close
S
&
ILK† bypassing 1≥
R
ICB_STATE
[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 722 -
6F2S1927 (0.18)
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.7-14 for PLC#1, Table 4.7-15 for PLC#2, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command Off from the remote-end Operate command Off from remote-end
Select command On from the local-end Operate command On from the local-end
Failed Do nothing
Select command On by the PLC function Operate command On by the PLC function
Select command Off by the PLC function Operate command Off by the PLC function
Output signal to BO
The DPOS01 function, in Figure 4.7-26, can issue an “Operate” signal at the output point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the input signal “Local-Off-
Control” is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 723 -
6F2S1927 (0.18)
“DPOS01_FEC_OK_CSF”
DPOS1 function (Function ID: 512001) (512001 8003011E7E)
“DPOS01_FEC_OK_CS”
Operate Cmd. (512001 8003011E81)
Command “Local-Off-Control” [DPOS01-CPW]
with ILK† condition
& 1≥ & 1≥
& 0.1 – 50.0 s 1≥
Operate Cmd.
without ILK† condition
ILK† condition (“Off”) passed
DPOS01-Open
S
&
ILK† bypassing 1≥
R
ICB_STATE
[DPOS01-LGCFEXOT]
& Assign to BOs
ASEQ function§” is in progress Fixedlogic
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 724 -
6F2S1927 (0.18)
††Note: To identify the input and output signals of the other DPOS logics, see Table
4.7-15 for PLC#2, Table 4.7-16 for PLC#3, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Select command Off by the PLC function Operate command Off by the PLC
Output signal to BO
The DPOS01 function, in Figure 4.7-28, can issue an “Operate” signal at output point
“DPOS01_OEX_BO”, when the DPOS01 function determines that the signal “PLC-On-Control”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 725 -
6F2S1927 (0.18)
is true.
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
DPOS01 function (Function ID: 512001)
“DPOS01_OEC_OK_CS”
Command “PLC-On-Control” requiring ILK† check
(512001 8103011E82)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE33 DEV01_CL_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” not requiring ILK† check 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE32 DEV01_CL_COMMAND Operate Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 726 -
6F2S1927 (0.18)
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is
changed.
††Note: To identify the input and output signal-points in the other DPOS logics, see Table
4.7-14 for PLC#1, Table 4.7-15 for PLC#2, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
following expiration of the setting to timer [DPOS01-RST].
Select command On from the remote-end Operate command On from the remote-end
Select command Off from the remote-end Operate command Off from the remote-end
Select command On from the local-end Operate command On from the local-end
Select command Off from the local-end Operate command Off from the local-end
Failed Do nothing
Output signal to BO
The DPOS01 function, in Figure 4.7-30, can issue an “Operate” signal at output-point
“DPOS01_FEX_BO”, when the DPOS01 function determines that the signal “PLC-Off-Control”
is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 727 -
6F2S1927 (0.18)
“DPOS01_FEC_OK_CSF” “DPOS01_FEC_OK_CS”
Command “PLC-On-Control” with ILK†
(512001 8003011E7E) (512001 8003011E81)
(PLC#3 connection point) [DPOS01-CPW]
512001 800301EE31 DEV01_OP_INTERLOCK Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-On-Control” without ILK† 0.1 – 50.0 s
(PLC#4 connection point)
512001 800301EE30 DEV01_OP_COMMAND Operation Cmd.
without ILK† condition
[DPOS01-LGCFEXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[DPOS01-PLSM]*
Var
Fix To “Wait for a command”
“DPOS01_EX_CMP”
(512001 8003011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 728 -
6F2S1927 (0.18)
changed.
††Note: To identify the input and output signal-points of the other DPOS logics, see Table
4.7-15 for PLC#2, Table 4.7-16 for PLC#3, Table 4.7-18 and Table 4.7-20 for output
signals.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [DPOS01-RST].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 729 -
6F2S1927 (0.18)
1Note: “Command Blocking” disables all operation except for its own; “Command
Blocking” is implemented as “CBK” in a software switch controller (SOTFSW).
The IEC61850 standard defines “Command Blocking” as “CmdBlk”. For more
information on “CBK”, see Chapter Control and monitoring application: Software
switch controller. See the signal ““CBK_STATE” in Table 4.7-6.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.7-6. For more information see Chapter Control and
monitoring application:Common controls.
3Note: Detection of event “device-travelling” signifies that other operators are changing
the status of one or more devices. Thus, device operation by the IED should be
inhibited whilst ever the event is being detected. The detection signal is denoted
as “Travelling OR” in Table 4.7-6.
4Note: If an IED in the process of issuing a trip command, all control operation is blocked
until the trip operation has been completed. If the IED has a relay application, the
trip command is issued at the output point “GEN.TRIP” in Table 4.7-6.
5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 730 -
6F2S1927 (0.18)
Table 4.7-14 PLC connection points (Input point for PLC#1 User configurable condition)
Signal Number Signal Name Description M/O
512001 810301EE57 DPOS01IN_TMP_35 DPOS01 user configurable condition(PLC#1) O
512001 810302EE57 DPOS01IN_TMP_35 DPOS02 user configurable condition(PLC#1) O
512001 810303EE57 DPOS01IN_TMP_35 DPOS03 user configurable condition(PLC#1) O
…. …. …..
512001 810348EE57 DPOS72IN_TMP_35 DPOS72 user configurable condition(PLC#1) O
Table 4.7-15 PLC connection points (Input point for PLC#2 User configurable condition)
Signal Number Signal Name Description M/O
512001 820301EE5E DPOS01IN_TMP_42 DPOS01 user configurable condition(PLC#2) O
512001 820302EE5E DPOS02IN_TMP_42 DPOS02 user configurable condition(PLC#2) O
512001 820303EE5E DPOS03IN_TMP_42 DPOS03 user configurable condition(PLC#2) O
… … …
512001 820348EE5E DPOS72IN_TMP_42 DPOS72 user configurable condition(PLC#2) O
Table 4.7-16 PLC connection points (Input point for PLC#3 User configurable condition)
Signal Number Signal Name Description M/O
512001 800301EE53 DPOS01IN_TMP_34 DPOS01 user configurable condition(PLC#3) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 731 -
6F2S1927 (0.18)
Table 4.7-17 PLC connection points (Input point for PLC#1 and PLC#2 for additional and
operate condition)
Signal Number Signal Name Description M/O
512001 800301EE65 DPOS01IN_TMP_38 DPOS01 user additional condition(PLC#1) O
512001 800302EE65 DPOS02IN_TMP_38 DPOS02 user additional condition(PLC#1) O
512001 800303EE65 DPOS03IN_TMP_38 DPOS03 user additional condition(PLC#1) O
… … …
512001 800348EE65 DPOS72IN_TMP_38 DPOS72 user additional condition(PLC#1) O
512001 810302EE66 DPOS01IN_TMP_39 DPOS01 user configurable operate condition(PLC#2) O
512001 810303EE66 DPOS01IN_TMP_39 DPOS02 user configurable operate condition(PLC#2) O
512001 810304EE66 DPOS01IN_TMP_39 DPOS03 user configurable operate condition(PLC#2) O
…. …. ….
512001 810348EE66 DPOS72IN_TMP_39 DPOS72 user configurable operate condition(PLC#2) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 732 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 733 -
6F2S1927 (0.18)
Off state
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See chapter User interface: Monitoring sub-menu.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 734 -
6F2S1927 (0.18)
“DPOS01_SLD_CSCN”
(512001 8A03031F86)
Command “change value for counter”
512001_7003016D09 DEV01_3PH_REQ Operate Command
&
Operate condition‡
Figure 4.7-34 Changing counter value for three-phase† with operation from the remote-end in
DPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic of
Figure 4.7-36.
†Note: The user can apply other counter change commands for phase-A, -B, and –C as
shown in Table 4.7-23. The resultant signals for the other DPOS02-72 logics are
shown in Table 4.7-24.
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.
Figure 4.7-35 Changing counter value by operation from the front panel in DPOS01
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point “DPOS01_SLD_CSCN”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 735 -
6F2S1927 (0.18)
Figure 4.7-36 Operate condition logic for changing the counter in DPOS01
1Note: “Command Blocking” disables all operation except for its own; the “Command
Blocking” function is initiated by the status of “CBK” in a software switch
controller (SOTFSW). The IEC 61850 standard defines the “Command Blocking”
function as “CmdBlk”. For more information on “CBK”, see Chapter Control and
monitoring application: Software switch controller. See the signal ““CBK_STATE”
of Table 4.7-6.
2Note: “Double Command Blocking” (DCB) is an operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as “DCB
RCV OR” in Table 4.7-6. For more information see Chapter Control and
monitoring application:Common controls.
3Note: If the event “device-travelling” is detected in the CMNCTRL function, it indicates
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted by “Travelling OR” in Table 4.7-6.
4Note: If the issuing of a trip command is executed by the IED, any control operation is
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issues at the output point “GEN.TRIP” in Table
4.7-6.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 736 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 737 -
6F2S1927 (0.18)
Signal “DPOS01_FEX_BO”
Sensing
intermediate state
On Intermediate Off
Signal POS01_FEX_BO”
Sensing
intermediate state
Off Intermediate On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 738 -
6F2S1927 (0.18)
The user can clear the intervals (OT1 to OT4) by key-operation of the “Operation time”
sub-menu Figure 4.7-39 or operation from the remote-end. See chapter User interface:
Monitoring sub-menu.
512001 7003486D0D DEV48_RESET_REQ DPOS72 operation time reset command received (Mapping Data)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 739 -
6F2S1927 (0.18)
Note that the DPOS01 function commences operation when the scheme switch [DPOS01-EN]
is set to On.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 740 -
6F2S1927 (0.18)
DPOS01
To select and operate
condition logics
“DPOS01_3PH_STATE”
(512001 3103011001)
Phase-A signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
&
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Phase-B signals
BI signal selected by & Faulty
N/O contact setting [DPOS01B-NOPSG]
signal &
Phase-C signals
BI signal selected by
N/O contact setting [DPOS01C-NOPSG]
signal & &
Close
BI signal selected by
N/C contact setting [DPOS01C-NCLSG]
signal &
[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
3-Pole
[DPOS01-OPC]
And
&
[DPOS01-CLC]
And
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 741 -
6F2S1927 (0.18)
DPOS01
To select and operate
condition logics
“DPOS01_3PH_STATE”
(512001 3103011001)
Single phase signals BI signal selected by
N/O contact setting [DPOS01A-NOPSG]
Event
signal &
& Suppression
1≥ detector
BI signal selected by Open
N/C contact setting [DPOS01A-NCLSG]
“DPOS01_ F_QLT_SPP”
signal & (512001 8103011F5F)
&
Faulty
&
Intermediate
&
Close
[DPOS01-EN]
On &
[DPOS01-DEVTYPE]
1-Pole
Event suppression
If the status of a device “chatters” for a short time, the DPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPOS function;
hence, event suppression can be required to reduce additional burden created.
The DPOS function has an event suppression detector. The user should take into account
of the scheme switches [DPOS-NELD], [DPOS-TELD] and [DPOS-TELR]†. Set On for scheme
switch [DPOS01-SPPEN].
[DPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[DPOS-TELD] [DPOS-TELR]
Time................. A B C D E
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 742 -
6F2S1927 (0.18)
Figure 4.7-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time ‘A’, the setting [DPOS-NELD] is provided so
that the suppression commences at Time ‘B’. The setting [DPOS-TELD] pertains to the
operation of the detection function from Time ‘A’ (e.g., Time ‘A’ to Time ‘C’).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time ‘D’ to Time ‘E’).
To initiate the event suppression the user should set On for scheme switch [DPOS01-
SPPEN].
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select logic for select command On “BO1” Select
Signal captured by command
in DPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
On to the
DRIVER BO1 device
[Input signal 2]
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Select logic for select command check
Off in DPOS01 [Input signal 7]
[Input signal 8]
Terminal and
BO2 circuit at IO#1 (Function ID: 200B01) wire
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) Select
“BO2”
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112) Off to the
device
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Figure 4.7-43 Example of select commands connected with BO1 & BO2 at IO#1
†Note:Table 4.7-9 shows the remaining signals with the exception of
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 743 -
6F2S1927 (0.18)
Terminal and
Operate logic in DPOS01 BO3 and BO4 circuit at IO#1 (Function ID: 200B01) wire
“DPOS01_OEX_BO”
(512001 8203011DD3)
Operate
“BO3” command
Signal captured by
Operate logic for setting [Input signal 1] ≥1 (200B01_8202021112) On to the
device
“Operate command [Input signal 2] DRIVER BO3
On” & ≥1
[Input signal 3]
“BO3-RB”
[Input signal 4] [BO3_CPL] On &
Connected by Off
(200B01_8202021113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
Figure 4.7-44 Example of operate commands connected with BO3 and BO4 at IO#1
†Note:Table 4.7-18 shows the remaining signals with the exception of
“DPOS01_OEX_BO” and “DPOS01_FEX_BO”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 744 -
6F2S1927 (0.18)
“BO1-RB”
(200B01_8002001113)
Signal connected by
setting [DPOS01-OSLBORD]
Figure 4.7-45 Example connection of “Select command On” for the health check feature
“BO2-RB”
(200B01_8102001113)
Signal connected by
setting [DPOS01-FSLBORD]
Figure 4.7-46 Example connection of “Select command Off” for the health check feature
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 745 -
6F2S1927 (0.18)
“BO3-RB”
“200B01_8202021113”
Signal designated by
setting [DPOS01-OEXBORD]
Figure 4.7-47 Example connection of “Operate command On” for the health check feature
“BO4-RB”
“200B01_8302031113”
Signal designated by
setting [DPOS01-FEXBORD]
Figure 4.7-48 Example connection of “Operate command Off” for the health check feature
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 746 -
6F2S1927 (0.18)
Setting for the contact health check (normal setting, example #1)
Figure 4.7-49 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1 to BO4 contacts. To check that the contact health check function is working
correctly, the respective points of the BO-RBs should be connected as shown in Table 4.7-29, to
demonstrate that the settings are physically matched with the BO contacts.
“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK
Figure 4.7-49 Contact health check setting and 43SW scheme for example #1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 747 -
6F2S1927 (0.18)
Settings for erroneous contact health check (improper setting, example #2)
Figure 4.7-50 shows a setting example of an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.7-30, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPOS01-OSLBORD] is
meaningless ; hence, the issue of a select command is blocked.
“DPOS01_OSL_BO_FLG” is connected to “BO1” at IO#1 200B01 8002001112 (BO1) set for [DPOS01-OSLORD] NG
“DPOS01_FSL_BO_FLG” is connected to “BO2” at IO#1 200B01 8102011113 (BO2-RB) set for [DPOS01-FSLBORD] OK
Figure 4.7-50 Contact health check setting and 43SW scheme for example#2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 748 -
6F2S1927 (0.18)
Settings for extra contact health check (special setting, example #3)
Figure 4.7-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point “DPOS01_OSL_BO_FLG” is actually chosen for the
setting [DPOS01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special setting
can issue a select command, which is called “operated by internal select function”. The user
does not need to consider the use of a BO circuit for a select command, when there are no BIO
circuits available.
“DPOS01_FEX_BO_CSF” is connected to “BO4” at IO#1 200B01 8202021113 (BO3-RB) set for [DPOS01-FEXBORD] OK
BIO module
Remote/Local-end Drivers 43SW
Plus (+)
“DPOS01_OSL_BO_FLG”
(512001 8603011DC6)
Select command On SW1 is not driven with any BO
SW 1
On
command
Physical BOs
are virtualized. SW 3
“DPOS01_FSL_BO_FLG”
(512001 8A03011DC4) SW2 is not driven with any BO
Select command Off SW 2
Off
command
SW 4
“DPOS01_OEX_BO”
SW3 is driven with
(512001 8203011DD3)
BO3 at IO#1
Operate command On BO3
Minus (−)
“BO3-RB”
(200B01_8202021113)
“DPOS01_FEX_BO”
(512001 8103011DD0) SW4 is driven with
BO4 BO4 at IO#1
Operate command Off
“BO4-RB”
(200B01_8302031113)
Figure 4.7-51 Contact health check setting and 43SW scheme for example#3
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 749 -
6F2S1927 (0.18)
Table 4.7-32 PLC monitoring points (Output signal for event suppression function in DPOSxx)
Signal Number Signal Name Description
512001 3103011001 DPOS01_3PH_STATE DPOS01 3ph_state
512001 3103021001 DPOS02_3PH_STATE DPOS02 3ph_state
512001 3103031001 DPOS03_3PH_STATE DPOS03 3ph_state
…. …. ….
512001 3103481001 DPOS72_3PH_STATE DPOS72 3ph_state
512001 8103011F5F DPOS01_F_QLT_SPP Event suppression detected (DPOS01)
512001 8103021F5F DPOS02_F_QLT_SPP Event suppression detected (DPOS02)
512001 8103031F5F DPOS03_F_QLT_SPP Event suppression detected (DPOS03)
…. …. ….
512001 8103481F5F DPOS72_F_QLT_SPP Event suppression detected (DPOS72)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 750 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 751 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns”)
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 752 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 753 -
6F2S1927 (0.18)
Table 4.7-36 Mapping signals required for DPC object for CSWI4
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO
Ctrl/CSWI4$Pos$SBOw T Timestamp CO
Ctrl/CSWI4$Pos$SBOw Test BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw Check Check CO
Ctrl/CSWI4$Pos$SBOw$origin orCat orCategory CO
Ctrl/CSWI4$Pos$SBOw$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Oper ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Oper ctlNum INT8U CO
Ctrl/CSWI4$Pos$Oper T Timestamp CO
Ctrl/CSWI4$Pos$Oper Test BOOLEAN CO
512001 7003016D08 DEV01_CONTROL_REQ
Ctrl/CSWI4$Pos$Oper Check Check CO
Ctrl/CSWI4$Pos$Oper$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Oper$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$Cancel ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel ctlNum INT8U CO
Ctrl/CSWI4$Pos$Cancel T Timestamp CO
Ctrl/CSWI4$Pos$Cancel Test BOOLEAN CO
Ctrl/CSWI4$Pos$Cancel$origin orCat orCategory CO
Ctrl/CSWI4$Pos$Cancel$origin orIdent Octet64 CO
Ctrl/CSWI4$Pos$SBOw ctlVal BOOLEAN CO
Ctrl/CSWI4$Pos$SBOw ctlNum INT8U CO
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 754 -
6F2S1927 (0.18)
4.7.8 Setting
DPOS01(Function ID: 512001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 755 -
6F2S1927 (0.18)
FixedLogic /
DPOS01-LGCTRCON - Change logic about control condition FixedLogic
PLC
FixedLogic /
DPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
DPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about off direction execute
DPOS01-LGFEXOT - FixedLogic
PLC output
FixedLogic / Change logic about on direction execute
DPOS01-LGOEXOT - FixedLogic
PLC output
FixedLogic /
DPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
DPOS01-PLSM Fix / Var - pulse mode Fix
DPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
DPOS01-RST 1.0 - 100.0 s response check timer 30.0
NA / C-On / C-
DPOS01-CNTS - count status NA
Off / C-OnOff
DPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
DPOS01-APBD Process / Bay - status change origin Process
DPOS01-CTRDIR Off / On - Capable control direction On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPOS function is available for a 2nd Device and other devices. We have
omitted the other tables because this will be the same as the table for the 1st
device with the exception of the device number.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 756 -
6F2S1927 (0.18)
4.7.9 Signal
Signal monitoring points in DPOS01
DPOS01(Function ID: 512001)
Element ID Name Description
8003011DE0 DEV1PLCCTRLFAIL DEV1PLCCTRLFAIL
3103011001 DPOS01_3PH_STATE DPOS01 3ph_state
3103011FE5 DPOS01_APH_STATE DPOS01 aph_state
3103011FEA DPOS01_BPH_STATE DPOS01 bph_state
8603011F7B DPOS01_CNT_CS07 DPOS01 count change selected fail condition signal
0003011D91 DPOS01_CNT_SEL DPOS01 count change selected signal(stSeld) for SAS
3203011D20 DPOS01_CNT_VAL DPOS01 count value
3103011FEF DPOS01_CPH_STATE DPOS01 cph_state
8B03011F79 DPOS01_CTR_SGU DPOS01 selected signal
8903011F99 DPOS01_CTR_SGUCN DPOS01 count change selected signal
8203011E8B DPOS01_EC_F_CS DPOS01 execute command fail condition signal
8103011E9A DPOS01_ECF_FCT_EIS DPOS01 execute command fail factor signal except interlock/synchronism check
0003011D97 DPOS01_EX_BO_OPOK DPOS01 execute binary output signal for SAS
8003011E93 DPOS01_EX_CMP DPOS01 execute complete signal
8F03011F5E DPOS01_EX_CMP_TMO DPOS01 timeout after execute completion
8903011F9E DPOS01_EX_CMP_TMOCN DPOS01 count change timeout after execute completion
8603011E91 DPOS01_EX_FFL DPOS01 execute fail signal by fixedlogic
8503011E8F DPOS01_EX_SFL DPOS01 execute success signal by fixedlogic
8003011E81 DPOS01_FEC_OK_CS DPOS01 off direction execute command OK condition signal
8103011DD0 DPOS01_FEX_BO DPOS01 off direction execute binary output signal
8403011F45 DPOS01_FLT_DET1 DPOS01 Faulty Detected (3 phase concentration data only)
8A03011DC4 DPOS01_FSL_BO_FLG DPOS01 off direction select binary output signal
8A03011F81 DPOS01_FSL_CS19 DPOS01 select receive open signal check answer
3103011D01 DPOS01_LCD_ST DPOS01 state for LCD
3103011D00 DPOS01_MMC_ST DPOS01 state for MIMIC
8903011DC0 DPOS01_NSL_BO_FLG DPOS01 select binary output signal
8603011F7E DPOS01_NSL_CS07 DPOS01 select receive signal check answer
8103011E82 DPOS01_OEC_OK_CS DPOS01 on direction execute command OK condition signal
8203011DD3 DPOS01_OEX_BO DPOS01 on direction execute binary output signal
8603011DC6 DPOS01_OSL_BO_FLG DPOS01 on direction select binary output signal
8803011F73 DPOS01_OSL_CS41 DPOS01 on direction select condition signal 41
8603011F8B DPOS01_RST_CS07 DPOS01 reset time selected fail condition signal
0003011F57 DPOS01_RST_SIG DPOS01 reset time signal
8503011F87 DPOS01_SE_RCV_RMTCN DPOS01 count change selected fail condition signal check
8503011F8A DPOS01_SE_RCV_RMTRT DPOS01 reset time selected fail condition signal check
8003011E76 DPOS01_SLD_CS DPOS01 selected condition signal
8003011F67 DPOS01_SLD_CS04 DPOS01 selected condition signal 04
8103011F68 DPOS01_SLD_CS05 DPOS01 selected condition signal 05
8203011F69 DPOS01_SLD_CS06 DPOS01 selected condition signal 06
8A03011F86 DPOS01_SLD_CSCN DPOS01 count change selected condition signal
8A03011F89 DPOS01_SLD_CSRT DPOS01 reset time selected condition signal
0003011D90 DPOS01_SLD_RPT DPOS01 selected signal(stSeld) for SAS
8E03011F5D DPOS01_SLD_TMO DPOS01 time out after selected
8A03011F9D DPOS01_SLD_TMOCN DPOS01 count change time out after selected
8103011E7B DPOS01_SLF_CS DPOS01 no direction select fail condition signal
8703011E98 DPOS01_SLF_FCT_EIS DPOS01 select fail factor signal except interlock/synchronism check
8803011F9B DPOS01_SLF_FCT_F03CN DPOS01 count change select fail factor signal by fixedlogic 03
8703011F9C DPOS01_SLF_FCT_F04CN DPOS01 count change select fail factor signal by fixedlogic 04
8303011F9A DPOS01_SLF_FCT_F07CN DPOS01 count change selected timer for a check
8503011F65 DPOS01_SLF_FCT_FLG05 DPOS01 select fail factor signal by fixedlogic 05
8803011F6C DPOS01_SLF_FCT_FLG07 DPOS01 selected timer for a check
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 757 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 758 -
6F2S1927 (0.18)
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the DPOS function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device; hence, the
user can find the same ones for all of the other devices. For example, when the user
wishes to find the “DPOS02A_FLT_DET” point provided for the 2nd device, use the
description of “DPOS01A_FLT_DET”. The user can obtain the ID value of
“DPOS02A_FLT_DET” by using the following steps:
Step 1 Find the element ID for DPOS01A_FLT_DET (i.e., “8303011F49”)
Step 2 Identify the numbers at the fifth and sixth digit from the ID. (i.e.,
“01”)
Step 3 Choose a new device number. (i.e., pick the number “2” for the 2nd
device)
Step 4 Replace the sixth and fifth digit numbers with the new device
number. (i.e., get new ID “8303021F49” of “DPOS02A_FLT_DET”) The
ID is expressed in hexadecimal notation. Thus, the user must change
the device number from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 759 -
6F2S1927 (0.18)
P1 P2 P3
The TPOS function has “Operation counters” and “Operation time measurement”; these
features are used to examine the devices; these features are useful when the user wishes to
assess the operating time of the device; these features are performed by counting the state-
changes for the device. The BO circuits connected with the TPOS function are used for issuing
commands; the BI circuits are used for receiving responses; hence, the user should connect the
BO and BI circuits with the TPOS function†. The TPOS function includes three logic groups:
1. Select logic, 2. Cancel logic, and 3. Operate logic.
EDS devices (43-switches) can be controlled separately; i.e., the function has a number of
separate sets for control (i.e., TPOS01, TPOS02, etc.). For simplicity, only the TPOS01 function
is discussed here; the features in the other TPOS functions are identical to the TPOS01
function.
†Note:A binary IO module has binary input circuits (BIs) and binary output circuits
(BOs); the user makes the connection between the TPOS01 function and the
binary IO module using a signal number (is made of a “Function_ID” and an
“Element_ID”). The signal numbers and names in the TPOS01 function are listed
later.
Tips: If the user wishes to apply the TPOS function quickly, go to sections 4.8.6 and
4.8.5, where settings of the BI and BO circuits and the mapping of signal-points
for IEC61850 communication is described.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 760 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.8-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– Number of controls 24 24 NA 24 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 761 -
6F2S1927 (0.18)
Cancel logic
P2 control from the remote-end
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 762 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The TPOS01 function can issue an signal “Select success” at the output point
“TPOS01_P1SL_BO_FLG”, when the TPOS01 function determines that the input signal
“Remote-P1-Control” received is true. If the TPOS01 function determines that the “Remote-
P1-Control” is not true, the TPOS01 function returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 763 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 764 -
6F2S1927 (0.18)
Output signal to BO
The TPOS01 function, in Figure 4.8-5, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command (Remote-P2-Control)” is true. If the TPOS01 function determines that the
“Remote-P2-Control” signal is not true, the TPOS01 function returns to the “Wait for a
command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 765 -
6F2S1927 (0.18)
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
The TPOS01 function, in Figure 4.8-7, can issue a signal “Select success” at the output point
“TPOS01_P3SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command P3 (Remote-P3-Control)” is true. If the TPOS01 function determines that the
“Remote-P3-Control” is not true, the TPOS01 function returns to the “Wait for a command”
stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 766 -
6F2S1927 (0.18)
Operate logic
P2 control from the local-end
Operate command
P3 control from the local-end
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 767 -
6F2S1927 (0.18)
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Figure 4.8-9 Selection logic for P1-control at the IED locally in TPOS01††
†Note:The ILK function provides the operation criteria for “P1-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-20
§Note:An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.8-6,
Table 4.8-7 and Table 4.8-10.
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P1SL_BO_FL”.
Note: The signal “TPOS01_P1SL_BO_FL” is the same as the signal shown in Figure
4.8-3. If the input signal “Local-P1-Control” is not true, the TPOS01 function
returns to the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 768 -
6F2S1927 (0.18)
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 769 -
6F2S1927 (0.18)
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-20.
††Note: To identify the input/output signals of the other TPOS logics, see Table 4.8-6,
Table 4.8-7, and Table 4.8-10.
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue “Select success”
signal at the output-point “TPOS01_P2SL_BO_FLG”.
1Note: The “TPOS01_P2SL_BO_FLG” signal is the same as the signal shown in Figure
4.8-5. If the “Local-P2-Control” signal is not true, the TPOS01 function returns to
the “Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 770 -
6F2S1927 (0.18)
0.6s
[TPOS01-CTRAHMI]
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*) SBO
Select condition‡
“Automatic sequence control function (AQEQ)§” in progress
ASEQ_MULTI_SEL
Output signal to BO
When the “select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P3SL_BO_FLG”.
1Note: The “TPOS01_P3SL_BO_FLG” signal is the same signal as shown in Figure 4.8-7.
If the “Local-P3-Control” signal is not true, the TPOS01 function returns to the
“Wait for a command” stage.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 771 -
6F2S1927 (0.18)
Operate logic
P1control by the PLC function
Failed Operate command
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 772 -
6F2S1927 (0.18)
510001 7001016D08
1≥ &
P1-control command requiring ILK† check To “Wait for a next
For DIR operation
(PLC connection point #1) command”
Operate command
513001 800401EE31 DEV01_P1_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
ILK† condition (“P1”) passed
TPOS1-P1 0 t Select “success”
0.1s
P1-control command not requiring ILK† checking For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE30 DEV01_P1_COMMAND
without ILK† condition & 0.6s
Select condition‡
Output signal to BO
The TPOS01 function, in Figure 4.8-15, can issue a “Select success” signal at the output-point
“TPOS01_P1SL_BO_FLG”1.
1Note: The “TPOS01_P1SL_BO_FLG” signal is the same as the signal shown in Figure
4.8-13.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 773 -
6F2S1927 (0.18)
Operate logic
P1 control by the PLC function
Operate command
Operate logic
PLC logic programmed Select
Selection logic Signal output
by the user decision Success
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 774 -
6F2S1927 (0.18)
510001 7001016D08
1≥ &
P2-control command requiring ILK †check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE33 DEV01_P2_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
ILK† condition (“P2”) passed
TPOS1-P2 0 t Select “success”
0.1s
P2-control command not requiring ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE32 DEV01_P2_COMMAND
without ILK† condition & 0.6s
Figure 4.8-17 Select logic ‘P2-control’ using the PLC function in TPOS01††
††Note: To identify the input and output points of the other TPOS logics, see Table 4.8-3
for PLC#1 and #2, and Table 4.8-10 for the outputs.
†Note:The ILK function provides the operation criteria for “P2-control”.
‡Note:A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-20.
Output signal to BO
The TPOS01 function, in Figure 4.8-17, can issue a “Select success” signal at the output point
“TPOS01_P2SL_BO_FLG”1.
1Note: The output point “TPOS01_P2SL_BO_FLG” is the same as the signal shown in
Figure 4.8-5.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 775 -
6F2S1927 (0.18)
Operate logic
P1 control by the PLC function
Operate command
P2 control by the PLC function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 776 -
6F2S1927 (0.18)
510001 7001016D08
1≥ &
P3-control command requiring with ILK† check
For DIR operation
(PLC connection point #1)
Operate command
513001 800401EE37 DEV01_P3_INTERLOCK To BO connection
with ILK† condition
& “TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
ILK† condition (“P3”) passed
TPOS1-P3 0 t Select “success”
0.1s
P3-control command not requiring without ILK† check For DIR operation To “Wait for a command”
(PLC connection point #2) 0 t
Operate command Select “Failed”
513001 800401EE36 DEV01_P3_COMMAND
without ILK† condition & 0.6s
Select condition‡
Output signal to BO
The TPOS01 function, in Figure 4.8-19, can issue a “Select success” signal at the output point
“TPOS01_P3SL_BO_FLG”1.
1Note: The output point “TPOS01_P3SL_BO_FLG” is the same as the signal shown in
Figure 4.8-7.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 777 -
6F2S1927 (0.18)
TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3
&
[TPOS01-DEVTYPE]*9
&
EDS
[TPOS01-CTREN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 778 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 779 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 780 -
6F2S1927 (0.18)
Table 4.8-7 PLC connection points Interlock for P1, P2, and P3-control
Signal Number Signal Name Description M/O
570001 3104011DA0 TPOS1-P1 Interlock condition for P1 control in TPOS01. N/A
570001 3104021DA0 TPOS2-P1 Interlock condition for P1 control in TPOS02 N/A
570001 3104031DA0 TPOS3-P1 Interlock condition for P1 control in TPOS03 N/A
… … …
570001 3104181DA0 TPOS24-P1 Interlock condition for P1 control in TPOS24 N/A
570001 3104011DA2 TPOS1-P2 Interlock condition for P2 control in TPOS01. N/A
570001 3104021DA2 TPOS2-P2 Interlock condition for P2 control in TPOS02 N/A
570001 3104031DA2 TPOS3-P2 Interlock condition for P2 control in TPOS03 N/A
Table 4.8-8 PLC connection points (Input signals for select condition logic)
Signal Number Signal Name Description M/O
513001 800401EE61 TPOS01IN_TMP_24 TPOS01 additional failure condition(PLC#1) O
513001 800402EE61 TPOS02IN_TMP_24 TPOS02 additional failure condition(PLC#1) O
513001 800403EE61 TPOS03IN_TMP_24 TPOS03 additional failure condition(PLC#1) O
… … …
513001 800418EE61 TPOS24IN_TMP_24 TPOS03 additional failure condition(PLC#1) O
513001 810401EE62 TPOS01IN_TMP_25 TPOS01 user configurable select condition(PLC#2) O
513001 810402EE62 TPOS02IN_TMP_25 TPOS02 user configurable select condition(PLC#2) O
513001 810403EE62 TPOS03IN_TMP_25 TPOS03 user configurable select condition(PLC#2) O
… … …
513001 810418EE62 TPOS24IN_TMP_25 TPOS24 user configurable select condition(PLC#2) O
513001 820401ED50 TPOS01IN_TMP_21 TPOS01 control hierarchy condition(PLC#3) M
513001 820402ED50 TPOS02IN_TMP_21 TPOS02 control hierarchy condition(PLC#3) M
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 781 -
6F2S1927 (0.18)
Table 4.8-9 PLC monitoring points (Output signal for select condition logic)
Signal Number Signal Name Description
513001 8004011F54 TPOS01_SC_ST_ERR TPOS01 select command mode is invalid.
513001 8004021F54 TPOS02_SC_ST_ERR TPOS02 select command mode is invalid.
513001 8004031F54 TPOS03_SC_ST_ERR TPOS03 select command mode is invalid.
… … …
513001 8004181F54 TPOS24_SC_ST_ERR TPOS24 select command mode is invalid.
513001 8204011F59 TPOS01_QLT_SPP Event suppression detected (TPOS01)
513001 8204021F59 TPOS02_QLT_SPP Event suppression detected (TPOS02)
513001 8204031F59 TPOS03_QLT_SPP Event suppression detected (TPOS03)
… … …
513001 8204181F59 TPOS24_QLT_SPP Event suppression detected (TPOS24)
513001 8604011F5A TPOS01_QLT_BI_ERR BI connection error detected(TPOS01)
513001 8604021F5A TPOS02_QLT_BI_ERR BI connection error detected(TPOS02)
513001 8604031F5A TPOS03_QLT_BI_ERR BI connection error detected(TPOS03)
… … ….
513001 8604181F5A TPOS24_QLT_BI_ERR BI connection error detected(TPOS24)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 782 -
6F2S1927 (0.18)
Operate logic
P3 control by the PLC function
“Do nothing”
“TPOS01_CC_FS”
(513001_8704011E96)
Operation Failed
Output signal to BO
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 783 -
6F2S1927 (0.18)
The TPOS01 function can issue a “Success to cancel” signal at the monitoring, point
“TPOS01_CC_SS”, when the TPOS01 function has determined that the “Remote-cancel” signal
is true. Another “Operate failed” signal is issued at monitoring point “TPOS01_CC_FS” if the
TPOS01 function is able to determine that the “Remote-cancel” signal is not true.
Select stage
Wait for a next command
P1 control from remote-end
Cancel from the remote-end
P2 control from remote-end
Cancel from the local-end
Success
P3 control from remote-end
Operate logic
P3 control by PLC function
Input signal
Figure 4.8-24 depicts the cancel logic when a “Cancel command (Local-cancel)” signal is applied
to the TPOS01 function. The signal is generated when the “Cancel” key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
“Local-cancel” signal, the logic is able to output a result signal, provided that the “cancel
condition” checking is satisfied.
510001 7001016D08
Cancel command
Command “Local-cancel”
& To “Wait for a command”
“TPOS01_ CC_SS”
(513001_8604011E95)
Cancel condition &
Successes to cancel
“Do nothing”
“TPOS01_CC_FS”
(513001_8704011E96)
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 784 -
6F2S1927 (0.18)
at the monitoring point “TPOS01_CC_SS”, when the TPOS01 function determines that the
“Local-Cancel” signal is true.
[TPOS01-LGCNFFCT]
User configurable condition (PLC connection point)
Fixedlogic
513001 800401EE69 TPOS01IN_TMP_40 &
If the original logic does not meet with the requirements of the user, it can be replaced
using the connection point “User Configurable condition”:
Connect the user-customized logic, with the “TPOS01IN_TMP_40”, which is listed
in Table 4.8-12.
Set scheme switch [TPOS01-LGCNFFCT] to PLC.
Table 4.8-12 PLC connection points (Input signal for ‘cancel’ condition)
Signal Number Signal Name Description M/O
513001 800401EE69 TPOS01IN_TMP_40 TPOS1 user configurable cancel condition O
513001 800401EE69 TPOS02IN_TMP_40 TPOS2 user configurable cancel condition O
513001 800401EE69 TPOS03IN_TMP_40 TPOS3 user configurable cancel condition O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 785 -
6F2S1927 (0.18)
Table 4.8-13 PLC monitoring points (Output signal for ‘cancel’ condition)
Signal Number Signal Name Description
513001 8604011E95 TPOS01_CC_SS Cancel succeed in TPOS01
513001 8604021E95 TPOS02_CC_SS Cancel succeed in TPOS02
513001 8604031E95 TPOS03_CC_SS Cancel succeed in TPOS03
… … …
513001 8604181E95 TPOS24_CC_SS Cancel succeed in TPOS24
513001 8704011E96 TPOS01_CC_FS Cancel failed in TPOS01
513001 8704021E96 TPOS02_CC_FS Cancel failed in TPOS02
513001 8704031E96 TPOS03_CC_FS Cancel failed in TPOS03
… … …
513001 8704181E96 TPOS24_CC_FS Cancel failed in TPOS24
TPOSxx-LGCNFFCT Logic selector for cancel condition (TPOS01-24) Fixedlogic Fixedlogic / PLC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 786 -
6F2S1927 (0.18)
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 787 -
6F2S1927 (0.18)
“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command “Remote-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 788 -
6F2S1927 (0.18)
Output signal to BO
The TPOS01 function, in Figure 4.8-27, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the received “Remote-P1-
Control” signal is true.
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 789 -
6F2S1927 (0.18)
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command “Remote-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 790 -
6F2S1927 (0.18)
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.8-16 for PLC#2, Table 4.8-17 for PLC#3 and Table 4.8-20 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.8-29, can issue an “Operate” signal at the output-point
“TPOS01_P2EX_BO”, when the TPOS01 function determine that the input signal “Remote-P2-
Control” is true.
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 791 -
6F2S1927 (0.18)
“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “Remote-P3-Control” (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 792 -
6F2S1927 (0.18)
logic programmed by the user in place of the logic shown in Figure 4.8-26. The
user-programmed logic is connected internally to the “operate completed” signal,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.8-31, can issue an “Operate” signal at the output-point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the input signal “Remote-
P3-Control” is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 793 -
6F2S1927 (0.18)
“TPOS01_P1EC_OK_CSF” “TPOS01_P1EC_OK_CS”
Command Local-P1-Control” (513001 8004011E7E) (5130018004011E81)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
ILK† condition (“P1”) passed
S
TPOS1-P1 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
†Note:The ILK function can provide the operation criteria for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.8-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.8-15 for PLC#1, Table 4.8-16 for PLC#2 and Table 4.8-20 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 794 -
6F2S1927 (0.18)
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the scheme
switch [TPOS01-LGP1EXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.8-26. The user-programmed logic is connected internally to the “operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.8-33, can issue an “Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the “Local-P1-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 795 -
6F2S1927 (0.18)
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P2-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operate Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 796 -
6F2S1927 (0.18)
Output signal to BO
The TPOS01 function, in Figure 4.8-35, can issue an “Operate” signal at the output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “Local-P2-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 797 -
6F2S1927 (0.18)
“TPOS01_P2EC_OK_CSF” “TPOS01_P2EC_OK_CS”
Command Local-P3-Control” (513001 8004011E7F) (513001 8304011E82)
[TPOS01-CPW]
513001_7004016D08 DEV01_CONTROL_REQ Operate Cmd.
with ILK† condition & 1≥ 1≥
& & 1≥
0.1 – 50.0 s
Operation Cmd.
without ILK† condition
ILK† condition (“P2”) passed
S
TPOS1-P2 &
ILK† bypassing R
ICB_STATE
1≥
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(513001 8004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 798 -
6F2S1927 (0.18)
logic programmed by the user in place of the logic shown in Figure 4.8-26. The
user-programmed logic is connected internally to the signal “operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.8-37, can issue an “Operate” signal at the output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the “Local-P3-Control”
signal is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 799 -
6F2S1927 (0.18)
apply the signal at other connection point (PLC#4; i.e., DEV01_P1_COMMAND). We should
assume the PLC#3 and PLC#4 as PLC#1 and PLC#2 in Table 4.8-2. Note that the user should
set PLC for scheme switch [TPOS01-LGP1EXOT].
[TPOS01-LGP1EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operate Completed
1≥
(PLC#2 connection point)
Figure 4.8-39 Operate P1- control using the PLC function in TPOS01††
†Note:The ILK function can provide the criteria for operation for “P1” control.
‡Note:An “operate condition” signal is generated in the operate-condition logic (Figure
4.8-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.8-39 using connection point #1
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note:The ASEQ function can provide sequential signals for automatic control.
*Note:The user can set the type of output signal. When Var is set the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.8-15 for PLC#1, Table 4.8-16 for PLC#2 and Table 4.8-20 for the
outputs.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 800 -
6F2S1927 (0.18)
‡‡Note: The “Operate failed” signal is issued when a state-change remains undetected
failing expiration of the setting applied to timer [TPOS01-RST]
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set the scheme switch
[TPOS01-LGP1EXOT]. If the signal to be issued from the logic programmed by the
user instead of the logic shown in Figure 4.8-26, connect the “operate completed”
signal generated in the user-programmed logic to connection point#2 “User
configurable condition”. That is, set PLC to the scheme switch [TPOS01-
LGP1EXOT] and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.8-39, can issue a “Operate P1-control” signal at output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the signal “PLC-P1-Control”
is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 801 -
6F2S1927 (0.18)
to be treated as PLC#1 and PLC#2 in Table 4.8-3. Note that the user should set PLC for scheme
switch [TPOS01-LGP2EXOT].
[TPOS01-LGP2EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 802 -
6F2S1927 (0.18)
LGP1EXOT]. If the signal is to be issued from the logic programmed by the user
instead of the logic shown in Figure 4.8-26, connect the “operate completed” signal
generated in the user-programmed logic to connection point#2 “User configurable
condition”. That is, set the scheme switch [TPOS01-LGP1EXOT] to PLC and use
“TPOS01IN_TMP_38”.
††Note: To identify the input and output signals of the other TPOS logics, see Table
4.8-16 for PLC#2, Table 4.8-17 for PLC#3 and Table 4.8-20 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.8-41, can issue a signal “Operate P2-control” at output point
“TPOS01_P2EX_BO”, when the TPOS01 function determines that the “PLC-P2-Control” signal
is true.
P3 control from the remote end P3 control from the remote end
Failed Do nothing
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 803 -
6F2S1927 (0.18)
switch [TPOS01-LGP3EXOT].
“TPOS01_P3EC_OK_CSF” “TPOS01_P3EC_OK_CS”
Command “PLC-P3-Control”requiring ILK check (PLC#3
connection point) (5513001 8004011E80) (513001 8404011E83)
[TPOS01-CPW]
Operate Cmd.
513001 800401EE37 DEV01_P3_INTERLOCK
with ILK† condition & 1≥ 1≥
& & 1≥
Command “PLC-P3-Control ”not requiring ILK check 0.1 – 50.0 s
(PLC#4 connection point)
513001 800401EE36 DEV01_P3_COMMAND Operation Cmd.
without ILK† condition
[TPOS01-LGP3EXOT]
& Assign to BOs
Fixedlogic
ASEQ function§” is in progress
ASEQ_MULTI_SEL
[TPOS01-PLSM]*
Var
Fix To “Wait for a command”
“TPOS01_EX_CMP”
(5130018004011E93)
Detection of state-change in a device &
User configurable condition Operation Completed
1≥
(PLC#2 connection point)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 804 -
6F2S1927 (0.18)
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. If the signal is to be issued from the programmed logic by
the user instead of the logic shown in Figure 4.8-26, connect the “operate
completed” signal generated in the user-programmed logic to connection point#2
“User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.8-43, can issue a signal “Operate P3-control” at output point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the signal “PLC-P3-Control”
is true.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 805 -
6F2S1927 (0.18)
TPOS01_ST_P2
“EDS” never permit to control
P3-control command received from “P1 to P3” and “P3 to P1”.
(513001 8504011D04) &
TPOS01_ST_P3
&
[TPOS01-DEVTYPE]*9
&
EDS
[TPOS01-CTREN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 806 -
6F2S1927 (0.18)
4.8-6.
*5Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
*6Note: The Function “Event suppression” can detect chattering in BI circuits. (See
4.8.6(i)-3)
*7Note: A supervision of the Binary IO module can detect connection errors for BI
circuits.
*8Note: The “Common control” (CMNCTRL) function can test or check the operation
– direction of logic. When the user sets off for scheme switch [SCDEN], operation
of the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
*9Note: The user should set scheme switch [TPOS01-DEVTYPE] EDS when the earth-
switch(ES) is applied for the TPOS01 function.
*10Note: The user must program the PLC logic for “Control hierarchy condition” The
user must connect the “Control hierarchy” condition to the select condition logic
using the connection point TPOS01IN_TMP_21” for more information, see chapter
Control and monitoring application: Control hierarchy” see PLC#3 of Table 4.8-8.
*11Note: To identify the input points of the other TPOS, see Table 4.8-8 for PLC#1 to
#3. Note that the logic outputs are generated separately for P1, P2 and P3-
control.
Table 4.8-15 PLC connection points (Input signal PLC#1 user a configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE56 TPOS01IN_TMP_27 TPOS01 operate condition configured by the user (for PLC#1) O
513001 800402EE56 TPOS02IN_TMP_27 TPOS02 operate condition configured by the user (for PLC#1) O
513001 800403EE56 TPOS03IN_TMP_27 TPOS03 operate condition configured by the user (for PLC#1) O
… … …
513001 800418EE56 TPOS24IN_TMP_27 TPOS24 operate condition configured by the user (for PLC#1) O
Table 4.8-16 PLC connection points (Input signal PLC#2 user configurable condition)
Signal Number Signal Name Description M/O
513001 820401EE5E TPOS01IN_TMP_38 TPOS01 operate condition configured by the user (for PLC#2) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 807 -
6F2S1927 (0.18)
Table 4.8-17 PLC connection points (Input signal PLC#3 user configurable condition)
Signal Number Signal Name Description M/O
513001 810401EE57 TPOS01IN_TMP_28 TPOS01 operate condition configured by the user (for PLC#3) O
513001 810402EE57 TPOS02IN_TMP_28 TPOS02 operate condition configured by the user (for PLC#3) O
513001 810403EE57 TPOS03IN_TMP_28 TPOS03 operate condition configured by the user (for PLC#3) O
…. …. …
513001 810418EE57 TPOS24IN_TMP_28 TPOS24 operate condition configured by the user (for PLC#3) O
Table 4.8-18 PLC connection points (Input signal PLC#4 user configurable condition)
Signal Number Signal Name Description M/O
513001 840401EE58 TPOS01IN_TMP_29 TPOS01 operate condition configured by the user (for PLC#4) O
513001 840402EE58 TPOS02IN_TMP_29 TPOS02 operate condition configured by the user (for PLC#4) O
513001 840403EE58 TPOS03IN_TMP_29 TPOS03 operate condition configured by the user (for PLC#4) O
… … …
513001 840418EE58 TPOS24IN_TMP_29 TPOS24 operate condition configured by the user (for PLC#4) O
Table 4.8-19 PLC connection points (Input point additional, user configurable condition)
Signal Number Signal Name Description M/O
513001 800401EE65 TPOS01IN_TMP_33 Condition added by the user in TPOS01 (for PLC#1) O
513001 800402EE65 TPOS02IN_TMP_33 Condition added by the user in TPOS02 (for PLC#1) O
513001 800403EE65 TPOS03IN_TMP_33 Condition added by the user in TPOS03 (for PLC#1) O
… … …
513001 800418EE65 TPOS24IN_TMP_33 Condition added by the user in TPOS24 (for PLC#1) O
513001 810401EE66 TPOS01IN_TMP_34 Condition added by the user in TPOS01 (for PLC#2) O
513001 810402EE66 TPOS02IN_TMP_34 Condition added by the user in TPOS02 (for PLC#2) O
513001 810403EE66 TPOS03IN_TMP_34 Condition added by the user in TPOS03 (for PLC#2) O
… … …
513001 810418EE66 TPOS24IN_TMP_34 Condition added by the user in TPOS24 (for PLC#2) O
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 808 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 809 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 810 -
6F2S1927 (0.18)
Closed
Open
The user can change the value of the operation-counter from either the front panel or
remotely. For example, in the sub-menu for “Operation counter”, the user can set a user-
preferred value for the operation-counter. See Chapter User interface: Monitoring sub-menu
on how to operate the sub-menu.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 811 -
6F2S1927 (0.18)
“TPOS01_SLD_CSCN”
(513001 8A04011F8B)
Command “change value for counter”
513001_7004016D09 DEV01_ALLCNT_REQ Operate Command
&
Operate condition‡
Figure 4.8-47 Change counter value in net counter† by the remote-end in TPOS01
‡Note:The “operate condition” signal is provided from the operate condition logic shown
in Figure 4.8-49.
†Note: The user can apply the other counter change commands for P1-control, P2-control
and P3-control as shown in Table 4.8-24. The resultant signals for the other
TPOS02-24 logics are shown in Table 4.8-23.
Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.
Figure 4.8-48 Changing value by the operation of the front panel in TPOS01
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 812 -
6F2S1927 (0.18)
Output signal to BO
The TPOS01 function can issue a “Result” signal at output point “TPOS01_SLD_CSCN”.
Figure 4.8-49 Operate condition logic for changing the counter in TPOS01
*1Note: “Command Blocking” disables all operation except for its own; the
“Command blocking” function is initiated by the status of “CBK” in a software
switch controller (SOFTSW). The IEC 61850 standard defines the “Command
Blocking” function as “CmdBlk”. For more information on “CBK”, see Chapter
Control and monitoring application: Software switch control function. See the
signal “CBK_STATE” of Table 4.8-6.
*2Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3Note: If the event “device-travelling is detected, it indicates that another operator
is changing the status of a device. Thus, the IED should inhibit the operation of
any device for the duration that the event is detected. The detecting signal is
denoted as “Traveling OR” in Table 4.8-6.
*4Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 813 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 814 -
6F2S1927 (0.18)
to Figure 4.8-53. The user should set scheme switch [TPOS01-OPETMEN] On.
Signal “TPOS01_P2EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P2-control
Signal “TPOS01_PT_P3”
OT1 OT2
a. Switch motion (P1 to P2) b. Operate command and signals with regard to the switch motion (P1 to P2)
Signal “TPOS01_P1EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P1-control
Signal “TPOS01_PT_P3”
OT3 OT4
a. Switch motion (P2 to P1) b. Operate command and signals with regard to the switch motion (P2 to P1)
Signal “TPOS01_P2EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P2-control
Signal “TPOS01_PT_P3”
OT5 OT6
a. Switch motion (P3 to P2) b. Operate command and signals with regard to the switch motion (P3 to P2)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 815 -
Intermediate 6F2S1927 (0.18)
Signal “TPOS01_P3EX_BO”
Intermediate
P3
Signal “TPOS01_PT_P2”
P3-control
Signal “TPOS01_PT_P3”
OT5 OT6
a. Switch motion (P2 to P3) b. Operate command and signals with regard to the switch motion (P2 to P3)
The user can clear the operation-intervals (OT1 to OT8) by key-operation of the
“Operation time” sub-menu or operation from the remote-end. Figure 4.8-54 shows that the
user can clear the eight operation times using this screen. See chapter User interface:
Monitoring sub-menu for the operation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 816 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 817 -
6F2S1927 (0.18)
Note that the TPOS01 function commences operation when the scheme switch [TPOS01-EN]
is set to On.
“TPOS01_STATE”
Event suppression detector (513001_3104011001)
BI1, BI2, and BI3 signals desig
nated by settings
[TPOS01-P1NOPSG], & 1≥
[TPOS01-P2NOPSG],
and [TPOS01-P3NOPSG] S
Status before chattering
R “TPOS01_ QLT_SPP”
(513001_8204011F59)
On
& To select and operate
condition logics
Figure 4.8-55 BI1, BI2 and BI3 signals provided into TPOS01
†Note:The user should set the actual input- points, see Chapter Technical description:
Binary IO module.
‡Note:In Figure 4.8-55 two signals can be issued: “TPOS01_STATE” and
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 818 -
6F2S1927 (0.18)
“TPOS01_QLT_SPP”. The former one is used in the select condition logic and the
operate condition (see Figure 4.8-20 and Figure 4.8-44). The latter is used for an
event suppression detector.
If “On–On–Off” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth switch is still kinetic and is not standstill; thus, the decision is given as
“Intermediate”, the value “3” is given at the connection point ”TPOS01_STATE”.
If “On–On–On” signals are applied to the BI1–BI3 circuits, the decision cannot be made
because the earth-switch may be broken; hence, the value “7” is given.
Table 4.8-30 Decision made by the TPOS01 function
Input signals at IO#1 (200B01) Generated value
Decision by
BI1 BI2 BI3 “TPOS01_STATE”
TPOS01
(8001001110) (8101011110) (8201021110) (513001 3104011001)
Off (0) Off (0) Off (0) Intermediate 0
On (1) Off (0) Off (0) P1 1
Off (0) On (1) Off (0) P2 2
On (1) On (1) Off (0) Intermediate 3
Off (0) Off (0) On (1) P3 4
On (1) Off (0) On (1) Intermediate 5
Off (0) On (1) On (1) Intermediate 6
On (1) On (1) On (1) Faulty 7
Note: When handling the raw information other than the decision, the user can take
respective states of binary input circuits using other monitoring points. That is,
the user can take either state On (1) or state Off (0) corresponding to the BI1
circuit using the monitoring point “TOPS01_PT_P1”. Likewise, the BI2 and BI3
states can be taken using the monitoring points “TOPS01_PT_P2” and
“TOPS01_PT_P3”. (See Table 4.8-35)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 819 -
6F2S1927 (0.18)
[TPOS-NELD]
Signal 2 4 6 8
from device On On On On On On On
1 3 5 7
Suppressed
On On On On
signal
[TPOS-TELD] [TPOS-TELR]
Time................. A B C D E
Figure 4.8-56 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time A, the setting [TPOS-NELD] is provided so
that the suppression commences at Time B. The setting [TPOS-TELD] is pertains to the
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signal stops. The user can adjust the
point at which event suppression stops using the setting [TPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [TPOS01-SPPEN].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 820 -
6F2S1927 (0.18)
Terminal and
Selection logic in TPOS01 BO1 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
Selection logic for select “BO1” Select
Signal captured by command
command P1 in TPOS01 setting [Input signal 1] ≥1 (200B01_8002001112)
P1
[Input signal 2] DRIVER BO1
To contact health & ≥1
check [Input signal 3]
“BO1-RB”
[Input signal 4] [BO1_CPL] On &
(200B01_8002001113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
Selection logic for select check
command P2 in TPOS01 [Input signal 7]
[Input signal 8]
Terminal and
Selection logic for select BO2 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P2SL_BO_FLG”
command P3 in TPOS01
(513001 8A04011DC6)
“BO2” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8102011112)
P2
[Input signal 2] DRIVER BO2
& ≥1
To contact health
[Input signal 3]
check “BO2-RB”
[Input signal 4] [BO2_CPL] On &
(200B01_8102011113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
Terminal and
BO3 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
“BO3” Select
Signal captured by command
setting [Input signal 1] ≥1 (200B01_8202021112)
P3
[Input signal 2] DRIVER BO3
& ≥1
To contact health
[Input signal 3]
check “BO3-RB”
[Input signal 4] [BO3_CPL] On &
(200B01_8102021113)
Off
Connected by [Input signal 5]
“Programming”
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 821 -
6F2S1927 (0.18)
Terminal and
Operate logic in TPOS01 BO4–BO6 circuit at IO#1 (Function ID: 200B01) wire
“TPOS01_P1EX_BO”
(513001_8104011DD0)
“BO4”
Signal designated by Operate
Operate logic for setting [Input signal 1] ≥1 (200B01_8302031112)
command
P1-control P1
[Input signal 2] DRIVER BO4
in TPOS01 & ≥1
[Input signal 3]
“BO4-RB”
[Input signal 4] [BO4_CPL] On &
Connected by Off
(200B01_8302031113)
“Programming” [Input signal 5]
To contact health To contact health
[Input signal 6]
check check
[Input signal 7]
[Input signal 8]
†Note:Table 4.8-21 shows settings for the health check feature in the other TPOS
functions.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 822 -
6F2S1927 (0.18)
the command, the user can connect point “BO1-RB “ with the contact health check function
using the setting [TPOS01-P1SLBORD]. Do not key the point “TPOS01_P1SL_BO”. Likewise,
BO2-RB and BO3-RB are required to be set.
Contact health check
Selection logic in TPOS01 logic in TPOS01
“TPOS01_P1SL_BO” (513001 8A04011DC4)
Figure 4.8-59 Example contact health check feature for P1–P3 select commands
Figure 4.8-60 Contact health check logic for P1–P3 operate commands
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 823 -
6F2S1927 (0.18)
Proper setting for the contact health check (normal setting, example #1)
Figure 4.8-61 shows a setting example for 43S/EDS driving. Select and operate commands
drive the BO1–BO6 contacts. To check that the contact health check function is working
correctly, the respective points of the BO (RBs) should be connected, as shown in Table 4.8-31,
to demonstrate that the settings are physically matched with the BO contacts.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 824 -
6F2S1927 (0.18)
P1-select BO1
command “BO1-RB”
(200B01 8002001113)
“TPOS01_P1EX_BO”
(513001 8104011DD0)
P1-operate BO4
command “BO4-RB”
(200B01 8302031113)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)
P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)
Minus (−)
Figure 4.8-61 Contact health check setting and EDS scheme for example #1
Setting for erroneous in contact health check (improper setting, example #2)
Figure 4.8-62 shows a setting example for an improper setting of the 43S/EDS scheme. The
settings are implemented incorrectly as shown in Table 4.8-32, BO1-RB is not chosen, instead
BO1 is actually chosen, which is incorrect. In this case, the setting [TPOS01-SLBORD] is
meaningless; hence, the issue of a select command is blocked.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 825 -
6F2S1927 (0.18)
“TPOS01_P1SL_BO_FLG” is connected to “BO1” on SLOT1 200B01 8002001112 (BO1) set for [TPOS01-P1SLBORD] NG
P1-select BO1
command
“TPOS01_P1EX_BO”
(513001 8104011DD0)
P1-operate BO4
command “BO4-RB”
(200B01 8302031113)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
P2-select BO2
command “BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
P3-select BO3
command “BO3-RB”
(200B01 8202021113)
“TPOS01_P3EX_BO” EDS
(513001 8204031DD3) Plus (+)
P3-operate BO6
command “BO6-RB” P1-Selection P2-Selection P3-Selection
(200B01 8502051113)
Minus (−)
Figure 4.8-62 Contact health check setting and EDS diagram for example #2
Setting for extra contact health check (special setting, example #3)
Figure 4.8-63 shows an additional setting example for the EDS scheme; one of the settings is
made hypothetically. That is, the point “SPO01_P1*SL_BO_FLG” is actually chosen for the
setting [TPOS01-P1*SLBORD]; i.e. BO1-RB is not chosen for this selection. This special
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 826 -
6F2S1927 (0.18)
example can issue a select command; which is called “operated by internal select function”.
The user does not need to consider the use of a BO circuit for a select command, when there
are no BO circuits available.
Table 4.8-33 Extra setting example for contact health check
Example #3 Setting for example #3
Remote/Local end
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
P1-select
command
“TPOS01_P2SL_BO_FLG” BOs are not connected but virtualized.
(513001 8A04011DC6)
P2-select
command “TPOS01_P3SL_BO_FLG”
EDS
(513001 8A04011DC8)
P3-select
command
Plus (+)
SAS/Local IED
BIO module P1-Operate P2-Operate P3-Operate
“TPOS01_P1EX_BO”
(513001 8104011DD0) Drivers
P1-operate BO4
command “BO4-RB”
(200B01 8302031113) Minus (−)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
P2-operate BO5
command “BO5-RB”
(200B01 8402041113)
“TPOS01_P3EX_BO”
(513001 8204031DD3
P3-operate BO6
command “BO6-RB”
(200B01 8502051113)
Figure 4.8-63 Contact health check setting and EDS diagram for example #3
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 827 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 828 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 829 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 830 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 831 -
6F2S1927 (0.18)
Table 4.8-39 Mapping signals required for ISCSO object for GIGO2701
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GGIO2701$ISCSO$SBOw ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$SBOw ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$SBOw T Timestamp CO
Ctrl/GGIO2701$ISCSO$SBOw Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$SBOw Check Check CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$SBOw$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Oper ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Oper ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Oper T Timestamp CO
Ctrl/GGIO2701$ISCSO$Oper Test BOOLEAN CO
5130017 004016D08 DEV01_CONTROL_REQ
Ctrl/GGIO2701$ISCSO$Oper Check Check CO
Ctrl/GGIO2701$ISCSO$Oper$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Oper$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlVal INT32 CO
Ctrl/GGIO2701$ISCSO$Cancel ctlNum INT8U CO
Ctrl/GGIO2701$ISCSO$Cancel T Timestamp CO
Ctrl/GGIO2701$ISCSO$Cancel Test BOOLEAN CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orCat orCategory CO
Ctrl/GGIO2701$ISCSO$Cancel$origin orIdent Octet64 CO
Ctrl/GGIO2701$ISCSO ctlModel ctlModel CF
Ctrl/GGIO2701$ISCSO sboClass sboClass CF
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 832 -
6F2S1927 (0.18)
4.8.8 Setting
TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 833 -
6F2S1927 (0.18)
TPOS01(FunctionID:513001)
Setting items Range Unit Contents Default Note
FixedLogic /
TPOS01-LGSLFFCT - Change logic about select fail factor FixedLogic
PLC
FixedLogic / Change logic about execute command fail
TPOS01-LGEXFFCT - FixedLogic
PLC factor
FixedLogic / Change logic about P1 direction execute
TPOS01-LGP1EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P2 direction execute
TPOS01-LGP2EXOT - FixedLogic
PLC output
FixedLogic / Change logic about P3 direction execute
TPOS01-LGP3EXOT - FixedLogic
PLC output
FixedLogic /
TPOS01-LGCNFFCT - Change logic about cancel command fail factor FixedLogic
PLC
TPOS01-PLSM Fix / Var - pulse mode Fix
TPOS01-CPW 0.1 - 50.0 s control pulse width 1.0
TPOS01-RST 1.0 - 100.0 s response check timer 30.0
TPOS01-CTRDIR P1 / P2 / P3 - Capable control direction P2
TPOS01-P1CNTS Off / On - P1 count status Off
TPOS01-P2CNTS Off / On - P2 count status Off
TPOS01-P3CNTS Off / On - P3 count status Off
TPOS01-OPETMEN Off / On - Operation Time Measurement enable Off
TPOS01-APBD Process / Bay - status change origin Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The TPOS function is available for a 2nd Device and other devices. We have
omitted the others because this will be the same as the 1st device with the
exception of the device number.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 834 -
6F2S1927 (0.18)
4.8.9 Signal
Signal monitoring points in TPOS01
TPOS(FunctionID:513001)
Element ID Name Description
8004001FA3 TPOS00_CH_EC_LCD TPOS00 count change execute command by LCD
8004001D5E TPOS00_CH_EC_OWS TPOS00 count change execute command by OWS(HMI)
8004001D5F TPOS00_CH_EC_RCC TPOS00 count change execute command by RCC
8004001D60 TPOS00_CH_EC_RMT TPOS00 count change execute command by Remote
8004001FA2 TPOS00_CH_SC_LCD TPOS00 count change select command by LCD
8004001D5B TPOS00_CH_SC_OWS TPOS00 count change select command by OWS(HMI)
8004001D5C TPOS00_CH_SC_RCC TPOS00 count change select command by RCC
8004001D5D TPOS00_CH_SC_RMT TPOS00 count change select command by Remote
3204011D20 TPOS01_ALL_CNT_VAL TPOS01 all count value
0004011F7C TPOS01_AUTO_SIG TPOS01 Auto sequence signal
8304011E9C TPOS01_CCF_FCT_CS TEMP21
8704011E96 TPOS01_CC_FS TEMP19
8604011E95 TPOS01_CC_SS TEMP18
8804011E9B TPOS01_CC_ST_ERR TEMP39
0004011F7D TPOS01_CMNCTRL_SIG TPOS01 control receive signal
8604011F8D TPOS01_CNT_CS07 TPOS01 count change selected fail condition signal
0004011D91 TPOS01_CNT_SEL TPOS01 count change selected signal(stSeld) for SAS
0004011F7A TPOS01_CNT_SIG TPOS01 Count correction signal
8004011E9E TPOS01_CTR_SGC TPOS01 control logic stage(select command check)
8004011EA0 TPOS01_CTR_SGE TPOS01 control logic stage(execute command check)
8304011E9D TPOS01_CTR_SGN TPOS01 control logic stage(unselected)
8004011E9F TPOS01_CTR_SGS TPOS01 control logic stage(selected)
8B04011EA2 TPOS01_CTR_SGU TPOS01 control logic stage(under selection)
8904011FAB TPOS01_CTR_SGUCN TPOS01 count change selected signal
8904011FB1 TPOS01_CTR_SGURS TPOS01 reset time selected signal
8004011EA1 TPOS01_CTR_SGW TPOS01 control logic stage(wait for change)
8104011E9A TPOS01_ECF_FCT_EIS TPOS01 execute command fail factor signal except interlock/synchronism check
8004011D58 TPOS01_EC_LCD TPOS01 execute command by LCD
8004011D55 TPOS01_EC_OWS TPOS01 execute command by OWS(HMI)
8004011D59 TPOS01_EC_PLC TPOS01 execute command by PLC
8004011D56 TPOS01_EC_RCC TPOS01 execute command by RCC
8004011D57 TPOS01_EC_RMT TPOS01 execute command by Remote
8004011F55 TPOS01_EC_ST_ERR TPOS01 execute command mode err
0004011D97 TPOS01_EX_BO_OPOK TPOS01 execute binary output signal for SAS
8004011E93 TPOS01_EX_CMP TPOS01 execute complete signal
8F04011F58 TPOS01_EX_CMP_TMO TPOS01 timeout after execute completion
8904011FB0 TPOS01_EX_CMP_TMOCN TPOS01 count change timeout after execute completion
8904011FB6 TPOS01_EX_CMP_TMORS TPOS01 reset time timeout after execute completion
8904011F6F TPOS01_EX_CS01 TPOS01 response supervisory timer for P1
8A04011F70 TPOS01_EX_CS02 TPOS01 response supervisory timer for P2
8B04011F72 TPOS01_EX_CS03 TPOS01 P1 timer for under execution
8C04011F73 TPOS01_EX_CS04 TPOS01 P2 timer for under execution
8A04011F71 TPOS01_EX_CS05 TPOS01 response supervisory timer for P3
8C04011F74 TPOS01_EX_CS06 TPOS01 P3 timer for under execution
8604011E91 TPOS01_EX_FFL TPOS01 execute fail signal by fixedlogic
8504011E8F TPOS01_EX_SFL TPOS01 execute success signal by fixedlogic
8404011F43 TPOS01_FLT_DET1 TPOS01 Faulty Detected (3 phase concentration data only)
8104011F42 TPOS01_FLT_STA TPOS01 Faulty Start
8204011E8B TPOS01_F_CS TPOS01 execute command fail condition signal
3104011D01 TPOS01_LCD_ST TPOS01 state for LCD
3104011D00 TPOS01_MMC_ST TPOS01 state for MIMIC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 835 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 836 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 837 -
6F2S1927 (0.18)
Note: In the table above, the user will only find Element IDs and their names for the 1st
device, but a 2nd and other devices are also provided in the TPOS function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 838 -
6F2S1927 (0.18)
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “TPOS01_SC_OWS” point for
the 2nd device, use the description of “TPOS01_SC_OWS” in place of
“TPOS02_SC_OWS”. The user can obtain the ID value of
“TPOS02_SC_OWS” by using the following steps:
Step 1 Find the element ID for TPOS01_SC_OWS (i.e.,
“8001011D51”)
Step 2 identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “8001021D51” of
“TPOS02_SC_OWS”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 839 -
6F2S1927 (0.18)
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.9-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
– Number of controls 15 15 NA 15 NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 840 -
6F2S1927 (0.18)
IED
ASEQ01_
OUT2 Binary Output
EXEC_STOP circuit4
IED front panel
operation Xxxxxx 8xxxxxxxxx IN2
“Reply Signal” Driver
Open
EMERSTOP_
EXEC_STOP
“Emergency stop”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 841 -
6F2S1927 (0.18)
Table 4.9-4 PLC connection points (Inputs for stopping ASEQ operation)
Signal Number Signal Name Description M/O
The scheme switch [ASEQ01-CTRMENU] is used for a local operation (e.g., the front panel
operation on the IED). When On is set for the scheme switch [ASEQ01-CTRMENU], the PLC
sequence #1 can be instructed locally. The scheme switch [ASEQ01-CTRAHMI] is used to select
either a select-before-operation command (SBO) or a direct command (DIR) when the local
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 842 -
6F2S1927 (0.18)
instruction is applied.
t 0 4ASEQ01 in execution
1Start command for ASEQ01 S Q
1s R 5s
S Q t 0 &
Closing Command for Device #2
End of execution of ASEQ01 1s R
≧1 2s 1
Termination of ASEQ01 on Level_1
≥1
Temporary signal 001
5Reset of ASEQ01 execution
Temporary signal 002
& t 0
S Q &
Closing Command for Device #3
Termination of ASEQ01 on Level_2 1s R 2s
1
In selecting device #1 &
In selecting device #2 1
In selecting device #3
In selecting device #2 1
In selecting device #3
1DEV1PLCCTRLFAIL ≥1
6Control failure
1DEV2PLCCTRLFAIL
UTOSEQ01)
1DEV3PLCCTRLFAIL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 843 -
6F2S1927 (0.18)
When a stop command is generated during the selection of Device #3, the control logic
will clear the operation if the control logic can determine that the operation of Device #3 is
complete. Figure 4.9-3 shows that Device #3 unable to operate following reception of the stop
command.
ON
*3The operating state turns to OFF, when the operation of Device#3 finishes
following the reception of a stop command from the ASEQ01 function.
*2The ASEQ01 function generates an operate signal for stopping the control logic.
*1The ASEQ01 function generates a select signal for stopping the control logic.
Figure 4.9-3 Timing chart for an automatic sequence when a stop command is injected during
the operation of Device#3
Figure 4.9-4 depicts the operating sequence when an emergency command is input; the
control logic will cancel the operation in accordance with the execution state given from a
device. If the operation signal is not controlling the device, the control logic will clear the
operation promptly. If the operation signal is controlling the device, the control logic will clear
the operation when the control logic function can determine that the operation of the device is
complete, in this case Device#1.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 844 -
6F2S1927 (0.18)
ON
OFF
Operating state
*4The operation state turns to OFF, when the control logic cancels the
selection of Device#1 following the reception of a stop command from
the ASEQ01 function.
Selection signal for Device #2
Figure 4.9-4 Time chart of automatic sequence when emergency stop command is applied
during the operation of Device#1
Table 4.9-10 PLC monitoring points (Outputs for ASEQ emergency status)
Signal Number Signal Name Description
523001 000D0D1001 EMERSTOP_ACC_EXEC Reception of an emergency signal
523001 800D0D1D58 EMERSTOP_EC_LCD Emergency signal generated on the LCD scream
523001 800D0D1D55 EMERSTOP_EC_OWS Emergency signal generated from OWS(HMI)
523001 800D0D1D56 EMERSTOP_EC_RCC Emergency signal generated from RCC
523001 800D0D1D57 EMERSTOP_EC_RMT Emergency signal generated at Remote
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 845 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 846 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 847 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down
Oper
Origin
ctlmodel (choice ”DOes or DOns”)
Table 4.9-11 shows the signals in the ASEQ01 function that require mapping to the IEC
61850 communications. Figure 4.9-8 shows how to map a signal.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 848 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 849 -
6F2S1927 (0.18)
Table 4.9-12 Mapping signals required for SPCSO1 object in ASEQ01 function
Object_reference Attribute Type FC Signal Number Signal Name
Ctrl/GAPC1$SPCSO1$SBOw ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$SBOw T Timestamp CO
Ctrl/GAPC1$SPCSO1$SBOw Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$SBOw Check Check CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$SBOw$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Oper ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Oper ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Oper T Timestamp CO
Ctrl/GAPC1$SPCSO1$Oper Test BOOLEAN CO
523001 700D016D08 ASEQ01_CONTROL_REQ
Ctrl/GAPC1$SPCSO1$Oper Check Check CO
Ctrl/GAPC1$SPCSO1$Oper$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Oper$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1$Cancel ctlVal BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel ctlNum INT8U CO
Ctrl/GAPC1$SPCSO1$Cancel T Timestamp CO
Ctrl/GAPC1$SPCSO1$Cancel Test BOOLEAN CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orCat orCategory CO
Ctrl/GAPC1$SPCSO1$Cancel$origin orIdent Octet64 CO
Ctrl/GAPC1$SPCSO1 ctlModel ctlModel CF
Ctrl/GAPC1$SPCSO1 sboClass sboClass CF
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 850 -
6F2S1927 (0.18)
4.9.7 Setting
Auto Sequence(Function ID: 523001)
Setting items Range Unit Contents Default Note
! Note: The user can enter a preferred setting name using GR-TIEMS.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 851 -
6F2S1927 (0.18)
4.9.8 Signal
Signal monitoring points in ASEQ01
ASEQ(Function ID: 523001)
Element ID Name Description
000D001F40 ASEQ_MULTI_SEL Status flag to not be selected for multiple operations
Note: In the table above, the user will only find Element IDs and their names for the 1st
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 852 -
6F2S1927 (0.18)
device, but a 2nd and other devices are also provided in the ASEQ function. We
have omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every device;
hence, the user can find the same ones for all of the other devices. For
example, when the user wishes to find the “ASEQ01_EC_LCD” point for
the 2nd device, use the description of “ASEQ02_EC_LCD” in place of
“ASEQ01_EC_LCD”. The user can obtain the ID value of
“ASEQ02_EC_LCD” by using the following steps:
Step 1 Find the element ID for ASEQ01_EC_LCD (i.e.,
“800D011D58”)
Step 2 Identify the number at the fifth digit from the ID. (i.e., “1”)
Step 3 Choose a new device number. (i.e., pick the number “2” for
the 2nd device)
Step 4 Replace the number that occurs at the fifth digit with the
new device number. (i.e., get new ID “800D021D58” of
“ASEQ02_EC_LCD”) The ID is expressed in hexadecimal
notation. Thus, the user must change the device number
from decimal notation to hexadecimal notation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 853 -
6F2S1927 (0.18)
TPOS01 function
Clearing measured time-intervals
“OT1”, “OT2”, “OT3” and “OT4”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 854 -
6F2S1927 (0.18)
‡Note:The measurements in the DPOS and the DPSY functions are grouped into four
intervals in each respective device. Measurement is possible by sensing the device
events. The measured intervals are accumulated; they are grouped into four
intervals (OT1–OT4), which the user can monitor from the IED screen. Figure
4.10-2 and Figure 4.10-3 exemplify the four intervals upon occurrence of On
(Closing)-control event and Off (Open)-control event, provided that the DPOS
function operates.
Sensing
intermediate state On Intermediate Off
Figure 4.10-2 Two intervals (OT1 and OT2) for Off-control event
Issuing On control
Sensing
intermediate state Off Intermediate On
Figure 4.10-3 Two intervals (OT3 and OT4) for On-control event
Tips: If the user wishes to implement the OPTIM function quickly, go to section 4.10.4,
which discusses how to map signal-points for the IEC 61850 communication.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.10-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 855 -
6F2S1927 (0.18)
Operate logic
0 t
Failed
0.3s
Select condition‡
“Automatic sequence control function
(AQEQ)§” in progress
ASEQ_MULTI_SEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 856 -
6F2S1927 (0.18)
*Note:The OPTIM function can run on either “the SBO mode” or “the DIR mode” using a
signal “ctlmodel” when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
[OPTR1_EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 857 -
6F2S1927 (0.18)
Table 4.10-3 PLC connection point (Input point on select condition logic)
Signal Number Signal Name Description M/O
529001 820C01ED50 OPTR01_CTRL_RIGHT OPTIM control hierarchy M
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 858 -
6F2S1927 (0.18)
Operate logic
Operate command
Operate logic
“Do nothing”
Operation Failed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 859 -
6F2S1927 (0.18)
Failed Do nothing
Failed Do nothing
Cancel logic
Cancel command
Cancel logic
Figure 4.10-9 Outline of operate command for resetting intervals OT1 to OT4
OPTR01_RST_CMD
Command “Operating reset”
529001 310C011EA1
529001 700C016D08 OPTR01_CONTROL_REQ Operate command
& Reset all OTs
≥
Operate condition‡
“Automatic sequence control function (AQEQ)§”
in progress
ASEQ_MULTI_SEL
Reset All
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 860 -
6F2S1927 (0.18)
[OPTR1_EN]
On
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 861 -
6F2S1927 (0.18)
SBO defined in LN
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 862 -
6F2S1927 (0.18)
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice ”operate-once”)
ctlmodel (choice ”SBOes or SBOns” )
†”sboClass” can be found by scrolling down.
Oper
origin
ctlmodel (choice ”DOes or DOns” )
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 863 -
6F2S1927 (0.18)
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 864 -
6F2S1927 (0.18)
map the input-point to the Object references having attributes CO and CF†. Figure 4.10-16 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; “CO” stands for “Control” and “CF”
stands for “Configuration” in the functional constraint (FC).
Check “Input”
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 865 -
6F2S1927 (0.18)
4.10.5 Setting
OPTIMRSTCTRL (Function ID: 529001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 866 -
6F2S1927 (0.18)
4.10.6 Signal
Signal monitoring points
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
8B0C011F44 OPTR01_CTR_SGU OPTR01 signal before KC_OPTR_SC001
000C011D90 OPTR01_STSELD OPTR01 the controllable data is in the status selected (StSeld)
Mapping point
OPTIMRSTCTRL (Function ID: 529001)
Element ID Name Description
700C016D08 OPTR01_CTRL_RIGHT Control command
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 867 -
6F2S1927 (0.18)
Respective
BIO module output signals
Output from BI1 to BIn†
(at IO#n‡) GENBI for slot #n‡
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 4.11-1 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
– Main features ✓ ✓ NA ✓ NA NA NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
868
6F2S1927 (0.18)
SLOT1 GBI01_STATE
Device #1 BI1-NC BI1 BI1-CPL GBI01 Status detection about the BI1 at IO#1 slot
Pulse train1 Photo-
Filter
coupler
Signal
from
On On On On On On On On
device
Event No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
[GBI-TELD] [GBI-TELR]
Event suppression
Time................. A B C D E
Figure 4.11-3 illustrates the case where a device produces repetitive signals. From this
figure, it can be seen that the start of event suppression occurs at the tenth state-change (point
B) because the GENBI function counts the number of state-changes. The GENBI function
detects the commencement of the signal repeated from the signal initiation point ‘A’. Scheme
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 869 -
6F2S1927 (0.18)
switch [GBI-NELD] is provided to set the number of state-changes so that this function will
start to suppress the signal from this point. The user can set [GBI-TELD] pertaining to the
detection period of the repetitive signals (point A to point C). For example, the user can set the
value “10” for the scheme switch [GBI-NELD]; period A–C is set for the setting [GBI-TELD].
The GENBI function should remove event suppressed operation when the repetitive
signals disappear, (that is, the operation of the device is steady); event suppression operation
is cleared when no repetitive signal is found for a set period. The user can set the period using
scheme switch [GBI-TELR]; this reset operation clears the event suppression function at point
E when the last state change is confirmed at point D. Here, the period D–E is set for the Scheme
switch [GBI-TELR].
The event suppression function is provided for every device; the user should set On for
the scheme switch [SLOT1 GBI01-SPPEN], for example.
Table 4.11-2 shows the event list screen. This event list is in response to the signals shown
in Figure 4.11-3. Table 4.11-3 lists the common settings for event suppression. Table 4.11-4
shows the settings for a particular slot.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 870 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 871 -
6F2S1927 (0.18)
Table 4.11-5 shows the mapping signals that are required within the GENBI function for
IEC 61850 communications. Figure 4.11-5 shows how to map a signal.
Note: “Status (ST)” is defined in the function constraint (FC) of the IEC 61850 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 872 -
6F2S1927 (0.18)
Figure 4.11-5 Quality signal being mapped into Ind1 object of GGIO101
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 873 -
6F2S1927 (0.18)
4.11.3 Setting
General BI (Function ID: 580001)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 874 -
6F2S1927 (0.18)
4.11.4 Signal
Signal monitoring points in BI module at IO#1 slot
GENBI (Function ID: 580001)
Element ID Name Description
0010001001 SLOT1 GBI01_STATE Status of binary input circuit BI1 at IO#1 slot
0010011001 SLOT1 GBI02_STATE Status of binary input circuit BI2 at IO#1 slot
0010021001 SLOT1 GBI03_STATE Status of binary input circuit BI3 at IO#1 slot
…. …. ….
00101F1001 SLOT1 GBI32_STATE Status of binary input circuit BI32 at IO#1 slot
… … …
… … ….
…. …. ….
Note: In the table above, the user will only find Element IDs and their names for the 1st
slot, but a 2nd and other slots are also provided in the GENBI function. We have
omitted the Element IDs and their names for the other devices to improve
readability. Use the rule described below when the user wishes to obtain the
Element IDs and their names for the other devices.
Rule: The same types of signal monitoring points are provided in every circuit;
hence, the user can find the same ones for all of the other circuits. For
example, when the user wishes to find the “SLOT2 GBI02_STATE” point
for the 2nd circuit, use the description of SLOT1 GBI01_STATE in place of
“SLOT2 GBI02_STATE”. The user can obtain the ID value of “SLOT2
GBI02_STATE” by using the following steps:
Step 1 Find the element ID for SLOT1 GBI01_STATE (i.e.,
“0010001001”)
Step 2 Identify the number at the fifth and sixth digits from the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 875 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 876 -
6F2S1927 (0.18)
5 Technical Description
Contents Pages Pages
Case structure and slot layout 880 CPU 908
Type using compression terminals 881 -Configuration switch 909
-1/1 size case 881 Date and time 966
-1/2 size case 885 -Time synchronization 967
-1/3 size case 887 -DST(Summer time) 972
-3/4 size case 883 -Time zone 971
Type using ring terminals 889
-1/1 size case 889 Function keys with LEDs 958
-1/2 size case 893
-3/4 size case 891 Group setting for relays 975
Binary IO modules (BI, BO, and BIO) 916 LED indicators 953
-Input circuits 918
-Input features 917 Monitoring jacks 963
-Output circuits 929
-Output features 927 Operation keys 965
-BI1A module 934
-BI2A module 934 Power supply module (PWS) 949
-BI3A module 934 -FAIL contacts 949
-BO1A module 934 -Alarm threshold 949
-BO2A module 934
-BIO1A module 934 Transformer modules for AC (VCT) 895
-BIO2A module 934 -VCT31B module 896
-BIO3A module 934 -VCT32B module 898
-VCT33B module 899
Communication modules 910 -VCT36B module 900
-100Base-TX/1000Base-T 910 -Ratio setting 902
-100Base-FX 910 -Changing rated current 903
-1000Base-LX 910 -Residual voltage setting 906
-RS485 910 -VT connection setting 906
-Fiber optic 910 -CT connection setting 907
-IRIG-B000 910 -Polarity setting 907
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 877 -
6F2S1927 (0.18)
The IED hardware consists of a case, modules, and a human machine interface (HMI). For
instance, Figure 5-1 shows the structure of the GR-series IED which is mounted in 3/4×19”
rack. The user can find that the IED consists of a transformer module (VCT), a signal
processing and communication module (CPU), binary input and output modules (BI, BI, and
BIO, and a power supply module (PWS), which can be mounted in an order from left to right.
The IED case, which is designed for rack mount as shown in Figure 5-1, has two flanges
attached on the IED sides. Figure 5-2 shows hardware block diagram. The module structure
depends on the GR-series models, IED cases, and the customer specification. Therefore, the
user should check and confirm the actual modules with the ordering number in advance.
(The description of IED case helps to understand the IED structure and its functions.
Based on slot reference, terminal block, slot reference, GR-Series selects different cases. VCT,
CPU, BI, BO and BIO, PWS modules and HMI are described sequentially in this chapter. The
user is required to understand information provided in this chapter when wiring between the
IED and external devices and setting of the IED are performed. Hence, the user is required to
read this chapter thoroughly.)
Figure 5-1 Modules in 3/4 19” rack’s chassis (Front view, removed the front panel)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 878 -
6F2S1927 (0.18)
VCT CPU
CPM2 LAN I/F
I Filter Tele-
A/D
communication
AC analogue input
CT×n
LAN I/F system
V
VT×m
BO
Binary output
circuits ×16 Binary output
BI
HMI Binary input Binary input
circuits ×18
LCD/MIMIC
BIO
LE Ds
Binary output
circuits ×8 Binary output
Operation keys
Binary input
Monitoring jacks circuits ×6 Binary input
Function Key
USB
Maintenance I/F
PC
Power supply
PW S
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 879 -
6F2S1927 (0.18)
Figure 5.1-1 Terminal type and case structure (1/2 size case, back view)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 880 -
6F2S1927 (0.18)
PWS terminal block is placed on the far left side; hence, the user finds it with alpha-
numeric reference “T9”, and that is discussed later (see section 5.5).
Communication modules, which are placed between VCT and BIOs, are labeled with “C11”
to “C15”. Those are provided for LAN, IEC61850 communication, etc.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 881 -
6F2S1927 (0.18)
T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1
1 1 1 1 1 1 1 1 1
C11
2 2 2 2 2 2 2 2 2
3 3 3 3 3 3 3 3 3
4 4 4 4 4 4 4 4 4
5 5 5 5 5 5 5 5 5
6 6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8 8
9 9 9 9 9 9 9 9 9
10 10 10 10 10 10 10 10 10 C12
11 11 11 11 11 11 11 11 11
12 12 12 12 12 12 12 12 12
13 13 13 13 13 13 13 13 13
14 14 14 14 14 14 14 14 14
15 15 15 15 15 15 15 15 15
16 16 16 16 16 16 16 16 16
17 17 17 17 17 17 17 17 17
18 18 18 18 18 18 18 18 18
19 19 19 19 19 19 19 19 19
C13
20 20 20 20 20 20 20 20 20
21 21 21 21 21 21 21 21 21
22 22 22 22 22 22 22 22 22
23 23 23 23 23 23 23 23 23
24 24 24 24 24 24 24 24 24
25 25 25 25 25 25 25 25 25 C14
26 26 26 26 26 26 26 26 26
27 27 27 27 27 27 27 27 27
28 28 28 28 28 28 28 28 28
29 29 29 29 29 29 29 29 29
30 30 30 30 30 30 30 30 30
31 31 31 31 31 31 31 31 31
32 32 32 32 32 32 32 32 32
33 33 33 33 33 33 33 33 33
34 34 34 34 34 34 34 34 34 C15 FG1
35 35 35 35 35 35 35 35 35
36 36 36 36 36 36 36 36 36
37 37 37 37 37 37 37 37 37
38 38 38 38 38 38 38 38 38
E
39 39 39 39 39 39 39 39 39
40 40 40 40 40 40 40 40 40
T9 T8 T7 T6 T5 T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 882 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 883 -
6F2S1927 (0.18)
T7 T6 T5 T4 T3 T2 T1 VC1
C11
1 1 1 1 1 1 1
2 2 2 2 2 2 2
3 3 3 3 3 3 3
4 4 4 4 4 4 4
5 5 5 5 5 5 5
6 6 6 6 6 6 6
7 7 7 7 7 7 7
8 8 8 8 8 8 8
9 9 9 9 9 9 9
10 10 10 10 10 10 10
11 11 11 11 11 11 11 C12
12 12 12 12 12 12 12
13 13 13 13 13 13 13
14 14 14 14 14 14 14
15 15 15 15 15 15 15
16 16 16 16 16 16 16
17 17 17 17 17 17 17
18 18 18 18 18 18 18
19
20
19
20
19
20
19
20
19
20
19
20
19
20
C13
21 21 21 21 21 21 21
22 22 22 22 22 22 22
23 23 23 23 23 23 23
24 24 24 24 24 24 24
25
26
25
26
25
26
25
26
25
26
25
26
25
26
C14
27 27 27 27 27 27 27
28 28 28 28 28 28 28
29 29 29 29 29 29 29
30 30 30 30 30 30 30
31 31 31 31 31 31 31
32 32 32 32 32 32 32
33 33 33 33 33 33 33
34 34 34 34 34 34 34 FG1
35 35 35 35 35 35 35 C15
36 36 36 36 36 36 36
37 37 37 37 37 37 37
38 38 38 38 38 38 38
E
39 39 39 39 39 39 39
40 40 40 40 40 40 40
T7 T6 T5 T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic figure
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 884 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 885 -
6F2S1927 (0.18)
1 1 1 1
2 2 2 2 C11
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
9 9 9 9
10 10 10 10
11 11 11 11 C12
12 12 12 12
13 13 13 13
14 14 14 14
15 15 15 15
16 16 16 16
17 17 17 17
18 18 18 18
C13
19 19 19 19
20 20 20 20
21 21 21 21
22 22 22 22
23 23 23 23
24 24 24 24
C14
25 25 25 25
26 26 26 26
27 27 27 27
28 28 28 28
29 29 29 29
30 30 30 30
31 31 31 31
32 32 32 32
33 33 33 33
34 34 34 34 FG1
35 35 35 35 C15
E
36 36 36 36
37 37 37 37
38 38 38 38
39 39 39 39
40 40 40 40
FG FGB FGA
T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 886 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 887 -
6F2S1927 (0.18)
21 21
22 22
23 23
24 24
25
26
25
26
C14
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
C15 FG1
35 35
36 36
37 37
38 38
E
39 39
40 40
FG FGA
T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 888 -
6F2S1927 (0.18)
PWS terminal block is placed on the far left side; hence, the user finds it with alpha-
numeric reference “T8”. That circuit is discussed later (see section 5.5)
Communication modules, which are between VCT and BIOs, are labeled with “C11” to
“C15”. Those are used for LAN, IEC61850 communication, etc.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 889 -
6F2S1927 (0.18)
T8 T7 T6 T5 T4 T3 T2 T1 VC1
C11
1 2 1 2 1 2 1 2 1 2 1 2 1 2
1 2
3 4 3 4 3 4 3 4 3 4 3 4 3 4
3 4
5 6 5 6 5 6 5 6 5 6 5 6 5 6
C12
5 6
7 8 7 8 7 8 7 8 7 8 7 8 7 8
7 8
9 10 9 10 9 10 9 10 9 10 9 10 9 10
9 10
11 12 11 12 11 12 11 12 11 12 11 12 11 12
11 12
13 14 13 14 13 14 13 14 13 14 13 14 13 14
13 14
15 16 15 16 15 16 15 16 15 16 15 16 15 16
C13
15 16
17 18 17 18 17 18 17 18 17 18 17 18 17 18
17 18
21 22 21 22 21 22 21 22 21 22 21 22 21 22
21 22
23 24 23 24 23 24 23 24 23 24 23 24 23 24
23 24
25 25 25 26 25 25 25 25
C14
26 26 26 26 26 26
25 26
27 28 27 28 27 28 27 28 27 28 27 28 27 28
27 28
29 30 29 30 29 30 29 30 29 30 29 30 29 30
29 30
31 32 31 32 31 32 31 32 31 32 31 32 31 32
31 32
33 34 33 34 33 34 33 34 33 34 33 34 33 34
FG1
C15
33 34
35 36 35 36 35 36 35 36 35 36 35 36 35 36
E
35 36
37 38 37 38 37 38 37 38 37 38 37 38 37 38
38
FG
T8 T7 T6 T5 T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 890 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 891 -
6F2S1927 (0.18)
T5 T4 T3 T2 T1 VC1
C11
1
2
3
4
1 2 1 2 1 2 1 2
5
2 6
1
3 4 3 4 3 4 3 4
7
4 8
C12
3
5 6 5 6 5 6 5 6
9
6 10
5
7 8 7 8 7 8 7 8
11
8 12
7
9 10 9 10 9 10 9 13 10
10 14
9
11 12 11 12 11 12 11 15 12
12 16
11
13 14 13 14 13 14 13 17 14
13
14
15 16 15 16 15 16 15
18
19 16 C13
16 20
15
17 18 17 18 17 18 17 18
18
17
21 22 21 22 21 22 21 22
22
21
23 24 23 24 23 24 23 24
24
23
25 26 25 26 25 26 25 26
26
C14
25
27 28 27 28 27 28 27 28
28
27
29 30 29 30 29 30 29 30
30
29
31 32 31 32 31 32 31 32
32
31
33 34 33 34 33 34 33 34
33
34
35 36 35 36 35 36 35 36 C15 FG1
36
35
37 38 37 38 37 38 37 38
E
38
FG
FG FGB FGA
T5 T4 T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic figure
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 892 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 893 -
6F2S1927 (0.18)
T3 T2 T1 VC1
C11
1 2 1 2
1 2
3 4 3 4
3
4
5 6 5 6
C12
5
6
7 8 7 8
7 8
9 10 9 10
9
10
11 12 11 12
11
12
13 14 13 14
13 14
15 16 15 16 C13
15
16
17 18 17 18
17
18
21 22 21 22
21 22
23 24 23 24
23
24
25 26 25 26
25
26 C14
27 28 27 28
27 28
29 30 29 30
29
30
31 32 31 32
31
32
33 34 33 34
33 34 FG1
C15
35 36 35 36
35 36
37 38 37 38
E
38
FG
FG FGB FGA
T3 T2 T1 VC1
C11
C12
C13
C14
C15
c. Schematic diagram
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 894 -
6F2S1927 (0.18)
The blow figures exemplify the ratio settings for respective channels on the VCT. For more
information about the operation of LCD screen, see chapter User interface. The user can also
set them using GR-TIMES (see chapter Engineering tool).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 895 -
6F2S1927 (0.18)
5.2.1 VCT31B
The VCT31B can be used for ‘voltage & current relay’ or ‘reclosing relay’, which is designed for
1/2 size case or larger.
VCT31B
Three-phase voltages
Va VL1
Jumper
Vb VL2
Termina Input Type of AC analog
l Screw position input
Vc VL3 Number signal(7) input channel(4)
(5)
Reference voltage on busbar
Vs Vs 1 2 VL1 Voltage NA Ch1
3 4 VL2 Voltage NA Ch2
Residual voltage Ve Ve / Vs2
5 6 VL3 Voltage NA Ch3
(9)
Three-phase currents 7 8 Vs Voltage NA Ch4
Ia (6)
Ia 9 10 Ve / Voltage NA Ch5
Ib (9)
Vs2
Ib
Ic 11 12 – – – –
Ic
13 14 – – – –
Ie
15 16 – – – –
(8)
Ie
17 18 Ia Current W9(1) Ch9
Residual current
19 20 Ib Current W10 (1) Ch10
3I0
21 22 Ic Current W11 (1) Ch11
Ie for SEF
23 24 Ie Current W12(1) Ch12
25 26 Ie Current W13(2) Ch13
Figure 5.2-3 Transformer module 27 28 Ie for SEF Current NA(3) Ch14
(VCT31B)
(1)Note: The scale is defined with the rated current multiplied by 65.536 (amperes).
(2)Note: The scale is defined with the rated current multiplied by 4.096 (amperes).
(3)Note: The scale is fixed to be 1.024 (amperes) used in the SEF function.
(4)Note: The channel number is used to represent the terminal location when the user
sets the ratio of the CT or the VT. See later section Setting VCT ratio.
(5)Note: In 5A rated operation, jumpers are inserted on all CTs, whereas no jumper is
inserted for 1A rated. To change it, see section Changing VCT rated current.
(6)Note: The residual quantities can be derived by the means to the calculation when
the signal is not given straightforward. The user should set the input signal
for the VCT using APPL setting, which is discussed later.
(7)Note: For the destination of input signals, see Appendix: Matrix between VCT
terminals and relay applications.
(8)Note: Residual Ie numerical data is obtained with a large scale CT and a small one,
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 896 -
6F2S1927 (0.18)
VCT31B
Three-phase voltages
Va VL1
Jumper
Vb VL2
Termina Input Type of AC analog
l Screw position input
Vc VL3 Number signal(7) input channel(4)
(5)
Reference voltages on busbar
Vs Vs 1 2 VL1 Voltage NA Ch1
3 4 VL2 Voltage NA Ch2
Vs2 Vs2
5 6 VL3 Voltage NA Ch3
Three-phase currents 7 8 Vs Voltage NA Ch4
Ia
Ia 9 10 Vs2 Voltage NA Ch5
Ib
Ib
11 12 – – – –
Ic 13 14 – – – –
Ic
15 16 – – – –
(Not used)
17 18 Ia Current W9(1) Ch9
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 897 -
6F2S1927 (0.18)
5.2.2 VCT32B
The VCT32B can be used for ‘current relay’ designed for 1/3 size case.
(i) Use in Software ‘30’ (current relay)
The VCT32B is designed to obtain three-phase current and zero-sequence current. The
VCT32B is used in in the current relay named Software ‘30’. Note that the VCT32B herein can
get zero-sequence current (3I0). If the VCT32B can get the zero-sequence current from the
tertiary CT directly and residual current will not be derived here at, switch Off the zero-
sequence supervision function (i.e., setting [CHK_IZ]=Off).
AC
VCT32B
Termina Input Type of Jumper analog
l Screw
Three-phase currents Number Signal(6) input position(5) input
Ia
Ia channel(4)
Ib
Ib
1 2 – – – –
Ic 3 4 – – – –
Ic
5 6 – – – –
Ie 7 8 Ia Current W5(1) Ch7
(7) 9 10 Ib Current W6(1) Ch9
Ie
Residual current 11 12 Ic Current W7(1) Ch11
13 14 Ie Current W8(1) Ch13
3I0 15 16 Ie Current W13(2) Ch15
Ie for SEF
17 18 Ie for SEF Current N.A(3) Ch17
19 20 – – – –
Figure 5.2-5 Transformer module (VCT32B)
(1)Note: The scale is defined with the rated current multiplied by 65.536 (amperes).
(2)Note: The scale is defined with the rated current multiplied by 4.096 (amperes).
(3)Note: The scale is fixed to be 1.024 (amperes), which is used only for sensitive
earth fault protection function (SEF).
(4)Note: The channel number about the AC analog input is used to represent the
terminal location when the user sets the ratio about the CT or the VT. We
shall discuss later in section Setting VCT ratio.
(5)Note: Inserting a jumper on the board is carried out to operate for 5A rated
current. We shall discuss the rated current in later section Check of rated
current.
(7)Note: Terminals regarding to the residual current (Ie) is required to connect in
series, if it should be derived.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 898 -
6F2S1927 (0.18)
5.2.3 VCT33B
The VCT33B is designed for reclosing relay named Software ‘39’, which is designed for 1/3 size
case
VL2
1 2 VL1 Voltage NA Ch1
Vb
3 4 VL2 Voltage NA Ch2
Vc VL3
Reference voltage#1
5 6 VL3 Voltage NA Ch3
(4)
Vs Vs 7 8 Vs Voltage NA Ch5
(4)
Reference voltage#2 9 10 Vs2 Voltage NA Ch6
Vs2 Vs2 11 12 – – – –
13 14 – – – –
15 16 – – – –
17 18 – – – –
19 20 – – – –
Figure 5.2-6 Transformer module (VCT33B)
(1)Note: The channel number about the AC analog input is used to represent the
terminal location when the user sets the ratio about the VT. We shall discuss
later in section Setting VCT ratio.
(4)Note: Reference voltages are used in Voltage check (VCHK) function; see Chapter
Relay applications.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 899 -
6F2S1927 (0.18)
5.2.4 VCT36B
The VCT36B can be used for ‘voltage & current relay’ named Software ‘3E’ or ‘3F’, which is
designed for 1/3 size case.
(i) Use in current and voltage relay (Software ‘3E’)
VCT36B
Three-phase voltages
Va VL1
Terminal Input Type of AC analog
Vb VL2 Screw Jumper(4) input
Vc VL3 Number signal(5) input channel(3)
Residual voltage
1 2 VL1 Voltage NA Ch1
Ve Ve / Vs
3 4 VL2 Voltage NA Ch2
Three-phase currents 5 6 VL3 Voltage NA Ch3
(6) (9)
Ia
Ia
7 8 Ve /Vs Voltage NA Ch5
Ib 9 10 Ia Current W6(1) Ch6
Ib
11 12 Ib Current W7(1) Ch7
Ic
Ic 13 14 Ic Current W8(1) Ch8
Ie 15 16 Ie Current W13(1) Ch13
(6) 17 18 Ise Current W14(2) Ch14
Residual current Ise 19 20 – – – –
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 900 -
6F2S1927 (0.18)
VCT Alpha-
numeric VC1
VC1 VC1
reference
Module type
1
2
3
4
5
6
7
8
9
10
Short-bar1 11
12
13
14
15
16
FG1
17
Short-bar1 18
19
20
21
22
23
FG1
24
Frame ground 25
terminal on the case
26
27
28
29
30
1
Short-bar
FG1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 901 -
6F2S1927 (0.18)
†Note: For more information, see Chapter User interface: AC analog input.
‡Note:The number of AC analog input channels depends on the configuration of the VCT
type and the VCT slot. Thereby, the user has to set the value of the VCT ratio
corresponding to a specific auxiliary VT/CT.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 902 -
6F2S1927 (0.18)
W1
W2
Connector
W3 Tr.3 Tr.4
Rating jumpers
W4
W5
Tr.5 Tr.6
W6
W7
W8
W9 Tr.7 Tr.8
W10
W11
W12 Tr.9
W13 Tr.10
W14
Tr.11
Tr.12 Tr.13 Tr.14
header header
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 903 -
6F2S1927 (0.18)
Note: Channel numbers for rated settings are dependent on VCT type.
1A and 5A are shown above, but neglect them. They are invalid here. Confirm
that all have DEP setting from LCD menu or GR-TIEMS screen.
VCT jumper: Close or open the circuits named W* numbers corresponding to the
currents. The hatched areas are required to close or open.
For changing to 5A rated, insert jumpers at W9, 10, 11, 12, 13.
For changing to 1A rated, remove jumper at W9, 10, 11, 12, 13.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 904 -
6F2S1927 (0.18)
LCD screen
AC
Terminal I/O setting sub-menu
Input Type of Jumper analog
Screw AI#1
signal input position input
Number 10:48 1/2
channel
AI1_Ch13Ratio +
1 2 VL1 Voltage NA Ch1 2000
3 4 VL2 Voltage NA Ch2 AI1_Ch13_Rating +
DEP
5 6 VL3 Voltage NA Ch3
7 8 Vs Voltage NA Ch4
9 10 Ve Voltage NA Ch5
11 12 – – – – VCT circuit board Rear
Front
13 14 – – – –
15 16 – – – – W1
Connector
Ib Ch10 W4 Tr.3 Tr.4
21 22 Ic Current W11 Ch11 W5
W6
23 24 Ie Current W12 Ch12 W7 Tr.5
W8
25 26 Ie Current W13 Ch13 W9
Tr.11
Tr.12 Tr.13 Tr.14
Configuration switch: Change the CPU to constrained mode (see section Signal
processing and communication module).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 905 -
6F2S1927 (0.18)
VL2 Vb
VL3 Vc
Computation
Residual
voltage
Ve
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 906 -
6F2S1927 (0.18)
VL2 Vb
VL3 Vc
Ve Residual voltage
VL2 Vb
VL3 Vc
Computation
Residual
voltage
Busbar1
VT
Vs Vs(V3)
Busbar2 Voltages for
VT
synchronism
check
Vs2 Vs2(V4)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 907 -
6F2S1927 (0.18)
CPU
CPM2
COM#1
CPU COM#2
COM#3
COM#4
COM#5
BIO#2 COM#3
BIO#3
BIO#4
BIO#5
BIO#6 COM#4
BIO#7
BIO#8
COM#5 IRIG-B
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
908
6F2S1927 (0.18)
CPU
W5
COM#1
2-1
4-3
COM#2
CPM2
W6
2-1
4-3 COM#3
W7 CPU
2-1
4-3
COM#4
W8
2-1 COM#5
4-3
W6 W6
Jumper Configuration mode
(1-2) (3-4)
2-1 Default (normal) mode(i.e.,
Open Open
4-3 manufacture setting mode )
2-1
Closed Open Constrained mode (1A rated)
4-3
2-1
Open Closed Constrained mode (5A rated)
4-3
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 909 -
6F2S1927 (0.18)
Symbol
TX
RX
Symbol
RX
B2 B2(Disuse)
COM-B
A3 A3
B3 B3
COMM TX GND
C11
C12
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 910 -
6F2S1927 (0.18)
C11 C11
C12 C12
Figure 5.3-5 100Base-FX module (left for single port; right for dual ports)
C12
4. RS485 module
RS485 module has a PCB connector. The module should be connected with a shielded-twisted-
pair cable; it is used for communication in the IEC60870-5-103, Modbus, and DNP. The
terminal arrangement and references are shown below. The cable sheath should be connected
with the frame ground (FG) in the IED case. For the use of the a shielded-twisted-pair cable,
the user should note that the total length should be less than 1200 meter (0.75 miles); the
terminal resistor (150 ohms) should be connected when any connector is not connected. For
setting the parameters, see Chapter Communication protocol: RS485 communication.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 911 -
6F2S1927 (0.18)
Sheath
Top
PCB connector A1 A cable for
A1 B1 B1 an IED
COM-A(+)
A2
A2 B2 Sheath
COM-B(−) B2
A cable for
A3 B3 A3
another
Bottom
COMM(GND) B3
IED
0V
C11
C12
6. IRIG-B000 module
IRIG-B000 module is used to receive the digital signal generated with an external clock; the
signal is in conformity to serial IRIG-B000 format. Note that the IRIG-B000 module is able to
receive digital signal (TTL) only (i.e., the reception of AM signal is not applicable). This module
is isolated using a photo coupler; the user should note A2 and B2 connectors are not used. The
peak value of IRIG-B000 signal should be greater than 3.5 volts; the IRIG-B000 module has
the input register (about 3k ohm). Thus, the terminal register can be required when the IRIG-
B000 signal is delivered for several devices; the value of the terminal register depends on the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 912 -
6F2S1927 (0.18)
number of deliveries and the performance of the external clocks. For setting of time
synchronization, see Chapter Technical Description: Clock function.
Top
PCB connector A1
A1 B1 B1 SIG
A2 (Disuse)
A2 B2
B2 (Disuse)
A3 B3 A3
Bottom B3 GND
a. View from connector edge b. Port circuit
C11
C12
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 913 -
6F2S1927 (0.18)
Figure 5.3-10 exemplifies IED has a LAN module (1000BASE-FX) at C11. RS485 and IRIG-B
modules are located at C13 and C15.
C12
RS485
C12 Blank
Blank C13
C13 •A1
485
•B1• COM-A
•A2
•B2• COM-B
•A3
• •
B3
COMM
C14
C14 Blank
IRIG-B000
FG1
E C15
C15
FGE
FG1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
914
6F2S1927 (0.18)
Figure 5.3-11 illustrates a structure, which has 100BASE-FX, RS385, and IRIG-B000 modules.
C12
RS485
C12 100BASE
-FX
Blank C13
C13 •A1
485
•B1• COM-A
•A2
•B2• COM-B
•A3
• •
B3
COMM
C14
C14 Blank
IRIG-B000
FG1
E C15
C15
FGE
FG1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
915
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 916 -
6F2S1927 (0.18)
-Polarity dependent
1
(+)
-Independent circuit 2
BI1
(−)
2 BI2A -Isolated using photo Circuit
number
coupler
Screw on terminal block
-Polarity dependent
- Independent circuit
-Variable threshold
3 BI3A -Isolated using photo
Polarity
coupler Terminal screw
number
-Polarity dependent (+)
1
BI1 BI1
-Sharing common
Circuit number
connections (+)
2
BI2
Circuit
number
Terminal screw
number
34
(+)
BI32
35
(−) Photo coupler
36
(−)
37
(−)
38
(−)
4 BIO1A
5 BIO2A Same as BI1A Same as BI1A and BI2A
6 BIO3A
The user can find the connector of binary IO modules, the terminal number and
arrangement of the binary input circuits in section 5.4.5.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 917 -
6F2S1927 (0.18)
Table 5.4-3 Setting items for binary input circuits in the standard type
Units
Setting item1 Range Contents Default
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 918 -
6F2S1927 (0.18)
Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A module)
Units
Setting devices Range Contents Default
As an example, Figure 5.4-1 shows the binary input circuit of the BI1A in order to help
understand the settings. The BI1A consists of 18 binary input circuits and each circuit has
three settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches (“Delayed pick-up and delayed drop-off signal” and “Logic level
inversion”), used as basis of input signal characteristics.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 919 -
6F2S1927 (0.18)
Normal On &
[INVERSE-SW]
Inverse [BI1-CPL] Off
8101011111 8101011110
On Delay Timer Off Delay Timer 8101011172
BI2-NC BI2
t 0 0 t & ≥1
BI2 BI2-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BI2-CPL] Off
8201021110 8201021110
On Delay Timer Off Delay Timer
BI3-NC BI3 8201021172
t 0 0 t & ≥1
BI3 BI3-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BI3-CPL] Off
8********** BIn
BIn-NC BIn
On Delay Timer Off Delay Timer 8**********
t 0 0 t & ≥1
BIn BIn-CPL
0.000-300.000s 0.000-300.000s & ≥1
1
&
Normal On &
[INVERSE-SW]
Inverse [BIn-CPL] Off
Low
[THRES_Lvl]
High
R1
R1
Respective element IDs (i.e., 8001001172 and others) designate respective signal
monitoring points of the binary input circuits (i.e., BI1-CPL and others). Thus, the user can
handle the signals on the binary input circuit using element ID together with function ID.
When we assume that the BI1A module is at IO#1 slot in the IED case, and if the user wishes
to see the first circuit signal of this BI1A module, the user can identify its signal† using the
element ID (8001001172) and the function ID of IO#1 slot‡.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 920 -
6F2S1927 (0.18)
†Note:The user can see the signals of the binary input circuits on the IED screen.
Chapter User interface: Monitoring-sub menu discusses how to see the state of the
binary input circuits.
‡Note:Function IDs identify every IO slots. For example, IO#1 slot has been identified by
the function ID “200B001”. Therefore, when the user wishes to program the signal
“BI1-CPL” on the BI1A at IO#1, the user should designate its signal using the
function ID “200B001” and Element ID “8001001172”. On the other hand, when
the signal “BI2-CPL” on the BI1A at IO#2 is required to program, the user should
designate that signal using the function ID “200B002” and Element ID
“8001001172”. For more information with regard to the function ID and the Data
ID at IO#1, see sections 5.4.6(i), 5.4.7(i), and others.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 921 -
6F2S1927 (0.18)
Binary input circuits #1 to #3 follow the setting [BI1-3_PICKUP] and the user should set
the value between 18 to 222V DC2 for this setting. For the setting [BI4-6_PICKUP], the above
mentioned value holds true for #4 to #6 binary input circuits; similarly the setting [BI7-
9_PICKUP] is used for #7 to #9 binary input circuits; and finally the setting [BI10-12_PICKUP]
is used for #10 to #12 binary input circuits.
1Note: The threshold value is fixed for all types of BIO modules except the BI2A. The
user should notice that “binary IO module voltage type” influences these values
(see the 1st note in Table 5.4-1). These particular values are found when 220V dc
type is used.
2Note: In the variable type, the user can set the threshold arbitrarily between 18 to 222V
in DC, and can regulate its threshold voltage in a voltage step. Table 5.4-5 shows
the corresponding values with regard to guaranteed and typical thresholds in
response to the setting values. Note that the operation in the variable type is
segmented into ‘Operate’, ‘Intermediate’, ‘and ‘Non-operate’ areas, which are
decided by the guaranteed-pick-up, typical-pick-up, and guaranteed-drop-off
levels, as illustrated in Figure 5.4-2.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 922 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 923 -
6F2S1927 (0.18)
Input voltage
Operating area
Non-operating area
Imported signal by
binary input circuit
t
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 924 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 925 -
6F2S1927 (0.18)
IO#n
IO#1
IO#2
IO#3
IO#4
IO_SLOT1 IO_SLOT3
Setting table (input) Setting table (in & out)
Figure 5.4-4 BO and BIO setting tables related to IO_slot1 and IO_slot3
The setting table of section 5.4.6 is available for all binary IO modules except for the BI2A
module; thus, the user should understand and select the setting points that are relevant to the
BI1A module. That is, for the BI1A, the user should choose the setting items of reference (i.e.,
binary input circuits #1 to #18) from IO_SLOT1 setting table. On the other hand, for the BIO1A
module, the user should choose the setting items of reference (i.e., binary input circuits #1 to
#7) from IO_SLOT3 setting table. The IO_SLOT3 setting table for the binary input circuits are
shown in sec. 5.4.6. The setting operation via the IED screen is discussed later. (See chapter
User interface: I/O setting sub-menu)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 926 -
6F2S1927 (0.18)
The arrangement of the BO types is determined for every binary IO module, as shown in
Table 5.4-1 and Table 5.4-6. The difference in the types and number of BOs are also found in
section 5.4.5.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 927 -
6F2S1927 (0.18)
Table 5.4-6 Output circuits and features associated with binary IO module
No Type Binary output feature Example Symbol Applied
sign module
1 Fast -Normally open (N/O) Terminal screw BIO3A
-Dry contact BO1(F) number
operating
-Closure is the fastest 1
(F) amongst all of the BO types. 2
Type
-Make & Carry: 5A cont.
BO number
-Break: 0.15A at 290Vdc
-OP Time: 3ms (typical) N/O contact
connections 37
-Make and carry: 8A cont. BO number
36
-Break: 0.1A at 250Vdc N/O
0.2A at 125Vdc 38
-OP Time: 8ms (typical) N/C
Contact
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 928 -
6F2S1927 (0.18)
Unit
Setting items Contents Default
Data_ID
BO1_CPL Off / On – Switch On for programmable operation Off
BO1 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO1. Not assigned1
Input signal2 (Preferred Data ID) – Set a Data ID at the second input on BO1. Not assigned1
Input signal3 (Preferred Data ID) – Set a Data ID at the third input on BO1. Not assigned1
Input signal4 (Preferred Data ID) – Set a Data ID at the forth input on BO1. Not assigned1
Input signal5 (Preferred Data ID) – Set a Data ID at the fifth input on BO1. Not assigned1
Input signal6 (Preferred Data ID) – Set a Data ID at the sixth input on BO1. Not assigned1
Input signal7 (Preferred Data ID) – Set a Data ID at the seventh input on BO1. Not assigned1
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO1. Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO1 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO1 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO1 0.000
INVERSE-SW Normal / Inverse s Inversion operation of BO1 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO1 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
BO2_CPL Off / On – Switch On for programmable operation Off
BO2 Input signal1 (Preferred Data ID) – Set a Data ID at the first input on BO2. Not assigned1
….. ….. ….. …..
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BO2 Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BO2 AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BO2 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BO2 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BO2 signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BO2 OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
…..
Input signal8 (Preferred Data ID) – Set a Data ID at the eighth input on BOn Not assigned1
LOGIC-SW AND/OR/XOR – Switch for logic-gate operation on BOn AND
On Delay Timer 0.000 to 300.000 s Set a value for an on-delay-timer on BOn 0.000
Off Delay Timer 0.000 to 300.000 s Set a value for an off-delay-timer on BOn 0.000
INVERSE-SW Normal / Inverse – Inversion operation of BOn signal Normal
TIMER-SW OFF/Delay/Dwell/Latch – Selection of a type in the delay timer on BOn OFF
Logic Timer 0.000 to 300.000 s Setting Off Delay Timer for Delay and Dwell 0.000
Reset signal (Preferred Data ID) – Setting Data ID for Latch Not assigned1
1Note: The user can set a reset signal and eight input signals with Data IDs. Data IDs
are listed as a signal monitoring point for each function. Setting items are
summarized in each slot. (See sections 5.4.8(i) and 5.4.8(ii))
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 929 -
6F2S1927 (0.18)
Figure 5.4-5 shows the binary output circuits on the BO1A module in order to help
understand the settings. The BO1A consists of 18 binary output circuits and every circuit has
timers and switches. The features of the CPLs are divided into the five components as listed
below:
CPL switch
Selection of input signals
Logic gate switch
Delayed pick-up/delayed drop-off
Logic level inversion
Logic timer switch
From relay
application and To external
control functions devices
8002001112 Contact
On Delay Timer Off Delay Timer
[LOGIC-SW] & ≥1
t 0 0 t BO1
Input signal 1 DRIVER BO1
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8002001113
≥1 [INVERSE-SW]
Normal
Off
Inverse On &
XOR Delay &
0.000-300.000s [BO1_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310200E11D BO1-SOURCE
810201112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO2
Input signal 1 t 0 0 t DRIVER BO2
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
810201113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO2 RB
XOR Delay &
0.000-300.000s [BO2_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310201E11D BO2-SOURCE
820202112 Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BO3
Input signal 1 t 0 0 t DRIVER BO3
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR & 8202021113
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BO3 RB
XOR Delay &
0.000-300.000s [BO3_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
310202E11D BO3-SOURCE
8********* Contact
[LOGIC-SW] On Delay Timer Off Delay Timer
& ≥1 BOn
Input signal 1 t 0 0 t DRIVER BOn
&
AND
1 & Logic Timer ≥1 & ≥1
Input signal 2 0.000-300.000s 0.000-300.000s & 0 t
Input signal 3 OR &
8*********
≥1 [INVERSE-SW]
Normal
Off
Inverse On & BOn RB
XOR Delay &
0.000-300.000s [BOn_CPL] Off
≥1 Dwell
Input signal 8
[TIMER-SW] Latch &
F/F
Reset signal
3102E**11D BOn-SOURCE
Figure 5.4-5 Binary Output Circuit for the BO1A (#1 to #n=18)
In Figure 5.4-5 respective element IDs (i.e., 8002001112 and others) designate respective
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 930 -
6F2S1927 (0.18)
signal monitoring points of the binary output circuits. The user can monitor the operations of
the binary output circuit using element ID together with function ID. When we assume that a
BO1A module is at IO#2 slot in the IED case, and if the user wishes to monitor the first-circuit
in the BO1A module, the user can see the operation using the element ID (8002001112) and
the function ID† of IO#2 slot.
†Note: A function ID identifies every IO slots. For example, with regard to the function
ID and the Data ID at IO#1 slot, see section 5.4.9(i). On the other hand, for IO#2
slot see section 5.4.9(ii).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 931 -
6F2S1927 (0.18)
Instant type
When the user uses a binary output signal without the following characteristics, the user
should set Off for the scheme switch [TIMER-SW].
Delay type
If the user requires a binary output signal with a delayed characteristic, the user should set
Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting [Logic
timer].
Dwell type
For instance, if the user requires a binary output signal as a one shot pulse, the user should
set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer]. If the input signals received have a shorter duration than the set value in the
setting [Logic timer], the pulse width will be equal to the setting value. On the other hand, if
the duration of the input signals are longer than that of the set value, the pulse width will be
equal to the width of the input signals.
Latch type
If the user requires a binary output signal to be removed by a reset signal, the user should set
Latch for scheme switch [TIMER-SW] and key the Data ID of the reset signal for setting [Reset
signal]. Since the binary output signal is removed with the Data ID, the user should determine
the Data ID from other functions. The Data ID is designated by the signal monitoring point for
each function and the user should set the [Reset signal] setting.
Note: When Latch is set, the state of BO circuit will be sustained during power turn-
on/off.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 932 -
6F2S1927 (0.18)
IO#2
IO#n
IO#3
IO#1
IO#4
BO1A BIO1A
IO_SLOT2 IO_SLOT3
Setting table (output) Setting table (in & out)
Figure 5.4-6 BO and BIO modules and setting tables related to IO_SLOT2 and IO_SLOT3
Figure 5.4-6 illustrates an example of a binary IO module arrangement and the binary
output circuit printed circuit boards (PCBs). If the user wishes to set the binary output circuits,
the setting targets are on BO1A and BIO1A at locations IO#2 and IO#3. The user should key
the CPL settings from the setting tables for the IO2_SLOT and IO3_SLOT.
The setting table is available for all binary IO modules; thus, the user should understand
and select setting points that are relevant to the BO1A and BIO1A. That is, for the BO1A the
user should choose the setting terms of reference (i.e., binary output circuits #1 to #18) from
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 933 -
6F2S1927 (0.18)
IO_SLOT2. On the other hand, for the BIO1A, the setting terms of reference (i.e., binary output
circuits #1 to #10) are from IO_SLOT3. These setting tables are shown in section 5.4.8(ii).
Figure 5.4-10 shows a diagram of how an actual terminal block connects with circuits of the
module. The use can identify the correspondence using the left side block figure and the right
side schematic figure. If the user takes account of wiring works on the BI1A, their targets are
designated with terminal screw numbers (1 to 40) that are shown next to the terminal block.
Slot number labeled by alpha-numeric reference “T*” is used to identify the location of the slot,
and the asterisk(*) is substituted for any one of the slot numbers. For the actual
implementation of a binary IO module, the user should examine the arrangement of binary IO
modules from External connection figures, which are shown separately. (See Appendix: Typical
external connection)
Polarity is shown on some input-and-output circuits, hence, the user should check the polarity
sign (+) or (−), respectively.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 934 -
6F2S1927 (0.18)
FG
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 935 -
6F2S1927 (0.18)
BO1A BO2A
1 1
(+)
BO1(SF) 2 BO1(H) 2
(−)
3 3
(+)
BO2(SF) 4 BO2(H) 4
(−)
5 5
(+)
BO3(SF) 6 BO3(H) 6
(−)
7 7
(+)
BO4(SF) 8 BO4(H) 8
(−)
9 9
(+)
BO5(SF) 10 BO5(H) 10
(−)
11 11
(+)
BO6(SF) 12 BO6(H) 12
(−)
13 13
(+)
BO7 14 BO7(H) 14
(−)
15 15
(+)
BO8 16 BO8(H) 16
(−)
17 17
(+)
BO9 18 BO9(H) 18
(−)
21 21 (+)
BO10 22 BO10(H) 22 (−)
23 23 (+)
BO11 24 BO11(H) 24 (−)
25 25 (+)
BO12 26 BO12(H) 26 (−)
27 27 (+)
BO13 28 BO13(H) 28 (−)
29 29 (+)
BO14 30 BO14(H) 30 (−)
31 31 (+)
BO15 32 BO15(H) 32 (−)
33 33 (+)
BO16 34 BO16(H) 34 (−)
35
BO17 36
37
BO18 38
Schematic figures
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 936 -
6F2S1927 (0.18)
(+) 1 1 (+) 1
BI1 (+) BI1 BI1
(−) 2 2 (−) 2
(−)
(+) 3 3 (+) 3
BI2 (+) BI2 BI2
(−) 4 4 (−) 4
(−)
(+) 5 5 (+) 5
BI3 (+) BI3 BI3
(−) 6 6 (−) 6
(−)
(+) 7 7 (+) 7
BI4 (+) BI4 BI4
(−) 8 8 (−) 8
(−)
(+) 9 9 (+) 9
BI5 (+) BI5 BI5
(−) 10 10 (−) 10
(−)
(+) 11 11 (+) 11
BI6 (+) BI6 BI6
(−) 12 12 (−) 12
(−)
(+) 13 13 (+) 13
BI7 (+) BI7 BI7
(−) 14 14 (−) 14
(−)
15 15 15
BO1(SF) (+) (+)
16 16 BI8 16 BI8
(−) (−)
17 17
BO2(SF) (+) BI9
18 18
(−)
21 21 21
BO3(SF) 22 (+) 22 BI10 BO1(F) 22
23 (−) 23 23
BO4(SF) 24 (+) 24 BI11 BO2(F) 24
25 (−) 25 25
BO5(SF) 26 (+) 26 BI12 BO3(F) 26
27 (−) 27 27
BO6(SF) 28 BO1(SF) 28 BO4(F) 28
29 29 29
BO7 30 BO2(SF) 30 BO5(F) 30
31 31 31
BO8 32 BO3(SF) 32 BO6(F) 32
33 33 33
BO9 34 BO4 34 BO7 34
35 35 35
37 37 37
BO10 36 BO5 36 BO8 36
38 38 38
Schematic figures
Figure 5.4-9 Input and output arrangements in BIO1A, BIO2A and BIO3A
Note: For more detailed circuit information, refer to Table 5.4-2 or Table 5.4-6.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 937 -
6F2S1927 (0.18)
BIO3A
T* T*
(+) 1
1 BI1
(−) 2
2
(+) 3
3 1 2 BI2
(−) 4
4
3 4 (+) 5
5 BI3
(−) 6
6
5 6 (+) 7
7 BI4
(−) 8
8 7 8
(+) 9
9 BI5
(−) 10
10 9 10
(+) 11
11 BI6
12 11 12 (−) 12
13 (+) 13
13 14 14 BI7
14 (−)
15 (+) 15
15 16 16 BI8
16 (−)
17 17 18
18
19 21 22
20
23 24
25 26
21 21
27 28 BO1(F)
22 22
23 29 30 23
BO2(F) 24
24
25 31 32 25
BO3(F) 26
26 33 34
27 27
BO4(F) 28
28 35 36
29 29
30 37 38 BO5(F) 30
31 31
32 BO6(F) 32
33 Ring type terminal 33
34 BO7 34
35
36 35
37 Terminal screw numbers 37
38 are denoted with the BO8 36
39 same one.
40 38
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 938 -
6F2S1927 (0.18)
FG FG
Figure 5.4-11 The BI2A module and its frame ground screw
Note: The BI2A is earthed to the frame’s ground screw (FG) using a short wire.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 939 -
6F2S1927 (0.18)
…… …… …… …… ……
…… …… …… …… ……
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 940 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 941 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 942 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 943 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 944 -
6F2S1927 (0.18)
Units
Setting item Range Contents Notes
value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 945 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 946 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 947 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 948 -
6F2S1927 (0.18)
T* T*
PWS PWS
T
1* Ring plug type
2
3 terminal block
4
5 T*
6 2
2
7
8 1 2 4
4
9
10 FAIL15 3 4
FAIL15
3 3
11
12 5 6 1
13 1
14 7 8
15 9 10
16
17 8 11 12 8
18 10
19 10 13 14
20 FAIL25
FAIL25 9 15 16 9
17 18
7 7
21 22
21
22 23 24
23
24 25 26
25 29 29
26 Positive(+) DC 27 28 Positive(+) DC
30
27
30
/ 29 30 /
28
31 DC 31 DC
29 Negative(−) 31 32 Negative(−)
30 32 32
33 34
31
35 Short-wire1 35
32
33 35 36
36 36
34 Short-wire1 37 38
35 37 37
FG
36
37 Short-bar2(B) 38
38
38 Short-wire2(A)
39
40
E E
FG FG
FG
E3 E3
Figure 5.5-1 shows the difference between ‘Compression plug type terminal’ and ‘Ring type
terminal’. Alpha-numeric reference “T*” identifies slot locations, and an asterisk “*” shows its
slot number. An external connection figure illustrates the PSW location (see Appendix: Typical
External connection).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 949 -
6F2S1927 (0.18)
CAUTION
1Note: The connection (triplet lines) between terminal screw No. 35 and terminal screw
No. 37 is made with a short-wire, which is installed by the manufacturer. Read
Appendix: Notes for the dielectric voltage test carefully and follow the instructions
during testing.
2ANote: The connection–for Type using compression terminals–between terminal screw
38 and screw labeled “FG” is made with a short-wire by the manufacturer.
2BNote: The connection–for Type using ring terminals–between terminal screw 37 and
screw labeled “FG” is made with a short-bar by the manufacturer.
3Note: For installation, the user should connect the case earth screw labeled “E” to the
protective earth of the panel or others using earthing wire, such that its cross-
section is AWG9 or larger.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 950 -
6F2S1927 (0.18)
JP4 JP4
3 3
2 2
1 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 951 -
6F2S1927 (0.18)
LED indicators
(#1–#26) Screen
Indicator label
Operation keys
Function keys
(F1–F7)
Monitoring jacks
(Term A/B/C) USB port
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 952 -
6F2S1927 (0.18)
The LED indicators‡ (#3 to #26) are also provided as user-programmable indicators.
Figure 5.6-2 shows the schematic diagrams. Each LED indicator can be lit and controlled using
a logic-gate-switch setting and others. For simplicity, we discuss setting the LED indicator #3
only, but the user can take account that setting the other LED indicators (#4 to #26) is the
same as the #3. Table 5.6-1 shows the LED indicator settings; Table 5.6-2 shows the signal
monitoring points on all LED indicator logics.
‡Note:Setting menus of the LED indicator are also discussed in Chapter User interface:
I/O setting sub-menu.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 953 -
6F2S1927 (0.18)
LED-03
3100031001
[On Delay Timer] [Off Delay Timer] LED indicator #3
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
[LOGIC-SW] Dwell & Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
LED-04
3100041001 LED indicator #4
[On Delay Timer] [Off Delay Timer]
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2]
0.000-300.000s 0.000-300.000s 1
[Input signal 3] & 0 t
&
≥1 OR 0.000-300.000s
[INVERSE-SW] Normal
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
LED-26
31001A100
[On Delay Timer] [Off Delay Timer] LED indicator #26
& ≥1
[Input signal 1] t 0 0 t DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s 1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 954 -
6F2S1927 (0.18)
Instant type
When required not to have the below characteristics (v)-2, (v)-3, and (v)-4, the user should set
Off for the scheme switch [TIMER-SW].
Delay type
If the user requires lighting the LED indicator with a delayed characteristic, the user should
set Delay for scheme switch [TIMER-SW] and set the value of the pulse width using setting
[Logic timer].
Dwell type
For instance, if the user requires lighting the LED indicator as a one shot pulse, the user
should set Dwell for scheme switch [TIMER-SW] and set the value of the pulse width using
setting [Logic timer]. If the input signals received have a shorter duration than the set value
in the setting [Logic timer], the pulse width will be equal to the setting value. On the other
hand, if the duration of the input signals are longer than that of the set value, the pulse width
will be equal to the width of the input signals.
Latch type
If the user requires lighting the LED indicator to be removed by a reset signal, the user should
set Latch for scheme switch [TIMER-SW]; the user should set the Data ID of the reset signal
for setting [Reset signal]. Since lighting the LED indicator is cleared with the Data ID, the
user should determine the Data ID from other functions. The Data ID is designated by the
signal monitoring point for each function and the user should set the [Reset signal] setting.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 955 -
6F2S1927 (0.18)
Default setting
Setting items Range Units Contents
value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 956 -
6F2S1927 (0.18)
Table 5.6-2 Signal monitoring points on all LED indicator (Function ID: 201B01)
Element ID Name Description
3100021001 ERROR Error LED
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 957 -
6F2S1927 (0.18)
For testing, the user can also program to generate binary signals when the user presses
the F1 to F7 keys. The F1 to F7 circuits have LEDs; accordingly, the user can also program to
light the LEDs using the settings.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 958 -
6F2S1927 (0.18)
“BO1”
Setting Data ID “F1 Signal designated by
setting [Input signal 1] ≥1 (200B01_8002001112)
SIGNAL” for the Signal to the
device
“FUNC-KEY1” [Input signal 1] [Input signal 2] DRIVER BO1
& ≥1
Pressing the F1 key (240001_ 3100001730)
[Input signal 3]
& “BO1-RB”
F1 [Input signal 4] [BO1_CPL] On
Off
&
(200B01_8002001113)
[Input signal 5]
To contact health
[Input signal 6]
check
[Input signal 7]
[Input signal 8]
“F1 SIGNAL”
Setting Data ID (240001_ 3100001737) PLC connection point in BO1
“BO1_SOURCE”
&
for the [Signal]† 200B01 310200E11D BO1_SOURCE
[Logic] Instant
Toggle
The user can select either Toggle or Instant modes for the signal generation using scheme
switch [LOGIC], as shown in Table 5.6-4. Thus, the user can substitute “F1-SIGNAL (240001
310001737)” for the “FUNC-KEY1 SIGNAL (240001 310001730)”, provided the Toggle mode
is preferred. In the Table 5.6-7 the other FUNC-KEY2 to FUNC-KEY7 are shown.
Table 5.6-4 Signal mode selection using setting [LOGIC]
Setting Generated signal corresponding to pressing the function key
Pressing Key
Toggle
Binary signal
Pressing Key
Instant
Binary signal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 959 -
6F2S1927 (0.18)
31001B1001
[On Delay Timer] [Off Delay Timer] F1 LED logic
& ≥1
t 0 0 t LED-F1
[Input signal 1] DRIVER
& AND & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s
1
& 0 t
[Input signal 3]
&
≥1 OR [INVERSE-SW] Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
[On Delay Timer] [Off Delay Timer] 31001C1001 F2 LED logic
& ≥1
[Input signal 1] t 0 0 t LED-F2
DRIVER
& AND 1 & [Logic Timer] ≥1
[Input signal 2] 0.000-300.000s 0.000-300.000s & 0 t
[Input signal 3]
[INVERSE-SW]
&
≥1 OR Normal 0.000-300.000s
Inverse
Off &
=1 XOR
Delay
[Input signal 8]
Dwell &
[LOGIC-SW] Blink
Blink
[TIMER-SW]
Latch &
F/F
[Reset signal]
……….
Screen Jump / Assign Signal /
Function - Operation mode for the F7 key Screen Jump
No Assign
F7
Signal (Preferred Data ID) - Set a Data ID at the input on F7 key (No Assigned)
Logic Instant / Toggle - Switch for logic-gate operation on F7 Instant
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 960 -
6F2S1927 (0.18)
Table 5.6-6 Settings of LEDs on the Function keys (Function ID: 240001)
Default setting
Setting items Range Units Contents
value
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F1 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F1. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F1. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F1. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F1. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F1. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F1. (No Assigned)
F1 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F1. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F1 AND
INVERSE-SW Normal / Inverse - Inversion operation of F1 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F1 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F1 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F1 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F2 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F2. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F2. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F2. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F2. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F2. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F2. (No Assigned)
F2 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F2. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F2 AND
INVERSE-SW Normal / Inverse - Inversion operation of F2 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F2 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F2 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F2 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
……….
Input signal1 (Preferred Data ID) - Set a Data ID at the first input on F7 (No Assigned)
Input signal2 (Preferred Data ID) - Set a Data ID at the second input on F7. (No Assigned)
Input signal3 (Preferred Data ID) - Set a Data ID at the third input on F7. (No Assigned)
Input signal4 (Preferred Data ID) - Set a Data ID at the forth input on F7. (No Assigned)
Input signal5 (Preferred Data ID) - Set a Data ID at the fifth input on F7. (No Assigned)
Input signal6 (Preferred Data ID) - Set a Data ID at the sixth input on F7. (No Assigned)
Input signal7 (Preferred Data ID) - Set a Data ID at the seventh input on F7. (No Assigned)
F7 Input signal8 (Preferred Data ID) - Set a Data ID at the eighth input on F7. (No Assigned)
Reset signal (Preferred Data ID) - Setting Data ID for "Latch" circuit (No Assigned)
LOGIC-SW AND / OR / XOR - Switch for logic-gate operation on F7 AND
INVERSE-SW Normal / Inverse - Inversion operation of F7 signal Normal
TIMER-SW Off/Delay/Dwell/Latch/Blink - Selection of a type in the delay timer on F7 Off
On Delay Timer 0.00 – 300.00 s Set a value for an on-delay-timer on F7 0.00
Off Delay Timer 0.00 – 300.00 s Set a value for an off-delay-timer on F7 0.00
Logic Timer 0.00 – 300.00 s Off delay timer value for "Delay" and "Dwell" circuit 0.00
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 961 -
6F2S1927 (0.18)
Table 5.6-7 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100001737 F1 SIGNAL Signal generated when pressing F1 referring the setting [LOGIC]
3100011737 F2 SIGNAL Signal generated when pressing F2 referring the setting [LOGIC]
3100021737 F3 SIGNAL Signal generated when pressing F3 referring the setting [LOGIC]
3100031737 F4 SIGNAL Signal generated when pressing F4 referring the setting [LOGIC]
3100041737 F5 SIGNAL Signal generated when pressing F5 referring the setting [LOGIC]
3100051737 F6 SIGNAL Signal generated when pressing F6 referring the setting [LOGIC]
3100061737 F7 SIGNAL Signal generated when pressing F7 referring the setting [LOGIC]
Table 5.6-8 Signal monitoring points for function LEDs (Function ID: 201B01)
Element ID Name Description
31001B1001 LED-F1 Signal generated during pressing the F1 key
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 962 -
6F2S1927 (0.18)
When the user wishes to test the phase-A element the OC1 relay using an oscilloscope,
for example, set the phase-A monitoring point (44001 8000011C20†) for the setting [Term A],
as shown in Figure 5.6-5. Consequently, the OC1 operating signal is outputted to the jack at
the Term A. The LED at the Term A is also lit in step with the output signal. The user can use
to monitor the phase-B and phase-C signals using by settings respective Data IDs for the [Term
B] and [Term C]. We shall see the menus for the Term A to Term C in Chapter User interface:
Test sub-menu: Signal monitoring screen.
OC function
(Function ID: 440001) Monitoring jack (Function ID: 201301) Jacks and LEDs
Signal designated by
setting [Term A] DRIVER Term Signal to the
440001 8000011C20
A oscilloscope
A
OC1 440001 8100011C21
B “TEST-A”
440001 8200011C22 (201B01_3100221001)
C
Term A LED
Signal designated by
setting [Term B] DRIVER Term Signal to the
B oscilloscope
“TEST-B”
(201B01_3100231001)
Term B LED
Signal designated by
setting [Term C] DRIVER Term Signal to the
C oscilloscope
“TEST-C”
(201B01_3100241001)
Term C LED
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 963 -
6F2S1927 (0.18)
Table 5.6-11 Signal monitoring points for monitoring jack LEDs (Function ID: 201B01)
Element ID Name Description
3100221001 TEST-A TEST-A
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 964 -
6F2S1927 (0.18)
Table 5.6-12 Signal monitoring points for L/R LEDs (Function ID: 201B01)
Element ID Name Description
3100251001 LOC LED Local
Table 5.6-13 Signal monitoring points for KEYINPUT (Function ID: 240001)
Element ID Name Description
3100081730 CANCEL Key situation of CANCEL
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 965 -
6F2S1927 (0.18)
Clock function
Clock function (or time function) provides the time information for recording upon occurrence
of the fault; it includes a synchronization function when the reference clock is available out of
the IED. The clock is operated referring the Coordinated Universal Time (UTC‡) when the
UTC is selected; the clock can run in accordance with the user’s time zone and summer
time(DST)† by referring the UTC when the time zone and the DST are set. The explanation is
also found in Chapter User interface: Time sub-menu.
†Note:In other words, it is called “daylight saving time (DST)”. For setting, see section
5.7.5.
‡Note:For example, the Internet and World Wide Web standards run in the UTC. For
more information, see section 5.7.4.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 966 -
6F2S1927 (0.18)
LAN
………….
IED_1 IED_2 IED_n
Setting procedure
The user should make the following steps in respective IEDs.
1) Set SNTP for the setting [Time Sync Src]; then set On for the setting [SNTP].
2) Set the address of a time server using settings [Server1]. The settings [Server2],
[Server3], and [Server4] are provided for other time-servers.
3) Check that the SNTP is shown under the ActivSyncSrc, as shown in Figure 5.7-4.
4) Check to see that the time zone and the DST are set correctly (see 5.7.4 and 5.7.5).
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] > Check “SNTP” being shown under ActiveSyncSrc.
SNTP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 967 -
6F2S1927 (0.18)
IED
IRIG-B000†
Clock
10:00 1/2
Signal [Time] +
A1 2012-11-21 10:00:05
IRIG-B signal
[Format]
generator Unit GND
A3 YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
IRIG-B
Figure 5.7-5 IED connected with the signal generator unit using IRIG-B000 module
†Note:See Chapter Technical description: Signal processing and communication module .
Setting procedure
The user should make the following steps in respective IEDs.
1) Set IRIG-B for the setting [Time Sync Src]; then set On for the setting [IRIG-SYNC].
2) Check that the IRIG-B is shown under the ActivSyncSrc, as shown in Figure 5.7-6.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
Check “IRIG-B” being shown under ActiveSyncSrc.
IRIG-B
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 968 -
6F2S1927 (0.18)
IED
BI1
BI1A (200B01 8001001111)
1
2 BI1
3
4 BI2
5
6 BI3
7
8 BI4
9
10 BI5 Setting [BI_ID]
11
12 BI6
13
14 BI7
15
16 BI8
17
18 BI9 Clock
21
22 BI10
23
24 BI11
25
26 BI12
27
Signal generator 28 BI13
29
30 BI14
31
32 BI15
1Hz squire wave 33
34 BI16
35
36 BI17
37
38 BI18
IO#1
Figure 5.7-7 IED connected with the signal generator via BI module
†Note:The BI1 circuit is just used for the explanation; hence, an actual BI circuit should
be selected in accordance with wiring cables. For more information of the BI
circuit, see Chapter Technical description: Binary IO module.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 969 -
6F2S1927 (0.18)
Setting procedure
The user should make the following steps in respective IEDs.
1) Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2) Check BI is shown under the ActivSyncSrc, as shown in Figure 5.7-8.
3) Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.7-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
BI1(200B01 8001001111) for the setting [BI_ID].
4) Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., −0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 970 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 971 -
6F2S1927 (0.18)
Beginning of the DST at 01:00 a.m. in Mar. 29 E nding of the DST at 02:00 a.m. in Oct. 25
March October
Mon Tue Wed Thu Fri Sat Sun Mon Tue Wed Thu Fri Sat Sun
1 1 2 3 4
2 3 4 5 6 7 8 5 6 7 8 9 10 11
9 10 11 12 13 14 15 12 13 14 15 16 17 18
16 17 18 19 20 21 22 19 20 21 22 23 24 25
23 24 25 26 27 28 29 26 27 28 29 30
30 31
Transposed Transposed
March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 972 -
6F2S1927 (0.18)
March October
Week Sun Mon Tue Wed Thu Fri Sat Week Thu Fri Sat Sun Mon Tue Wed
1 1 2 3 4 5 6 7 1 1 2 3 4 5 6 7
2 8 9 10 11 12 13 14 2 8 9 10 11 12 13 14
3 15 16 17 18 19 20 21 3 15 16 17 18 19 20 21
4 22 23 24 25 26 27 28 4 22 23 24 25 26 27 28
5 29 30 31 5 29 30
Figure 5.7-11 DST setting examples by the day (1st or 15th) of month
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 973 -
6F2S1927 (0.18)
5.7.6 Setting
Setting of CLOCK (Function ID: 200301)
Unit Default setting
Setting item Range Contents Notes
s value
Timezone -14.00 - 14.00 hour Time zone 0.00
--- / SNTP / BI /
TimeSyncSrc - Time sync source SNTP
MODBUS / IRIG-B
YYYYMMDD /
Date_fmt MMDDYYYY / - YMD/MDY/DMY YYYYMMDD
DDMMYYYY
Date_delimiter -///. - - or / or . -
Time_delimiter :/. - : or period :
Sec_delimiter ./, - . or , .
SummerTime Off / On - Summer time enable Off
IS_UTC_base Off / On - Is setting value base on UTC? On
Start_Month 1 - 12 - Start month 3
Start_Week 1-5 - Start week 5
--- / Sun. / Mon. / Tue.
Start_Wday / Wed. / Thr. / Fri. / - Start day of week Sun.
Sat.
Start_Hour 0 - 23 - Start hour 1
End_Month 1 - 12 - End month 10
End_Week 1-5 - End week 5
--- / Sun. / Mon. / Tue.
End_Wday / Wed. / Thr. / Fri. / - End day of week Sun.
Sat.
End_Hour 0 - 23 - End hour 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 974 -
6F2S1927 (0.18)
Settings
Protection (Relay)
Group1 setting
OC
EF
OV
UV
THM
TRC
Group2 setting
OC
EF
OV
UV
THM
TRC
Group8 setting
OC
EF
OV
UV
THM
TRC
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 975 -
6F2S1927 (0.18)
consists of a binary input circuit (BI1), a number generation function (‘Binary selection’
provided in basic functions of the PLC editor), and the signal reception point. That is, when
the B1 switch is closed, a signal enters the BI1 circuit and is carried to the Binary selection;
accordingly the Binary selection, which is programmed to generate a group number ‘2’ in UNIT
when signal ‘1’ is injected in BOOL(BIT), can generates and inject the group number ‘2’ at the
‘PLC_Group_ENUM’. Consequently, the Setting function (201400) starts change the group
from number ‘1’ to ‘2’. Note that changing is only performed during the BI1 is closed in the
example logic; hence, the setting number goes back to ‘1’ when the BI1 is open.
GR200 IED
Binary selection
(+) (–)
IO_SLOT1 (200B01)
BI1 8001001110 Entering → Leaving 201400 314000E1A0 PLC_Group_ENUM Operation of
BI1 changing
‘1’ in BOOL ‘2’ in UNIT
‘0’ in BOOL ‘1’ in UNIT
BI2 8101011110
BI2
1
DIN_BOOL
FID DO
DTYPE ST
DID
Figure 5.8-3 exemplifies that selecting a group among eight groups is required by the
usage of three BI circuits (i.e., Group 1→Group2, Group3,… Group8).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 976 -
6F2S1927 (0.18)
BI3_2
DIN_BOOL TON DOUT_UNIT_1
UDINT#16#200B03 FID DO IN Q BOOL_TO_UNIT MUL
DOUT_UNIT
UDINT#16#80 DTYPE ST Unit#16#201400 FID ST
Delay time# PT ET
UDINT#16#01011111 DID UDINT#16#2 Unit#16#31 DTYPE
XX ms
Unit#16#4000E1A0 DID
DI
BI3_3
DIN_BOOL TON
UDINT#16#200B03 ADD ADD
FID DO IN Q BOOL_TO_UNIT
MUL
UDINT#16#80 DTYPE ST
UDINT#16#01021111 DID Delay time# PT ET
XX ms UDINT#16#4
UDINT#16#1
(iii) Setting
Setting_PF (Function ID: 201400)
Default setting
Setting item Range Units Contents Notes
value
3010011001 COM_CHG
3010031001 CTRL_CHG
3010021001 PRO_CHG
3010001001 SYS_CHG
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 977 -
6F2S1927 (0.18)
6 Engineering tool
Contents Pages Pages
Common tools 981 Settings for Relay and control functions 982
Configuration tools 982 Settings for Input and output signals 982
Comparison of settings 981 Settings for Event recorder 983
Configuration in IEC 61850 983 Setting of Interlock (ILK) 983
Configuration in IEC 60870-5-103 983 Signal monitor 981
Connection with PC 980 Status monitor 981
Double command blocking (DCB) 981 Tool for Fault recorder 982
Tool for Disturbance recorder 982
Tool for Event recorder 982
Label creator 981
Logging management 981
MIMIC configuration 983
Project management 981
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 978 -
6F2S1927 (0.18)
Overview of GR-TIEMS
When engineering, monitoring, record viewing, and test support functions are required in the
IED, the user can handle these advanced and integrated functions using GR-Series Toshiba
IED Engineering and Monitoring Software (GR-TIEMS). The GR-TIEMS should be installed
into a PC prior to engineering. After that, the user can view the IED states (Table 6.1-1) on a
PC screen connected with the IED. The user can also program the IED using the GR-TIEMS.
The GR-TIEMS is software to retrieve and analyze power system quantities, fault and
event records. The user can change the settings in the respective IEDs when the PC is
connected with the IED via a USB or a LAN. For more information in the GR-TIEMS
operations, see separate manual “Operation manual GR-TIEMS (6F2M1082)”.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 979 -
6F2S1927 (0.18)
Connection
Figure 6.2-1 illustrates that the user can connect the local PC with the IED (type B receptacle)
using a USB cable. Alternatively, the user can connect the local PC with the IED by connecting
a RJ45 cable to the LAN port (if available in the IED). In Figure 6.2-2, when using the LAN
port, the user has to select the communications option, which can be found from the Main menu
in GR-TIEMS (go to “Tool” ->“Option…”; “Option” dialog will be displayed; change
communications option with the second tab – ‘Communication’).
Tip: See Chapter Communication protocol.
IED
LAN
USB Cable
Personal Computer
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 980 -
6F2S1927 (0.18)
Common tools
(i) Project management
Project files are required to engage sub-engineering tools. The user can manage to read/write
the project file of the IED using the project management function. The user can also see the
contents of the project files.
(ii) Comparison
When the user wishes to get the comparison between respective IEDs, using the compare
function the user can get the comparison data about Settings, Disturbance record binary
signals, PLCs, Interlock, Large LCD (MIMIC)†, IEC61850, and IEC60870-5-103 data†.
(iv) Logging
The user can view the recorded data with regard to the logging date/time. As the user can also
find operation recorded when an operator/engineer logs into the IED, analyzing a problem is
possible when an error is detected during the IED operations.
Monitoring tools
The user can monitor status and measurement value obtained in the IED using the monitoring
tools. All signals monitored are tabulated in the monitoring list dialog. When the user wishes
to monitor a signal, select a signal in the monitoring list dialog after the operation of the drag-
drop on the monitoring window. The monitoring tools can generate an exporting layout file in
the CSV; it also can obtain the layout file in the CSV.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 981 -
6F2S1927 (0.18)
Record tools
(i) Fault record
Fault records are including measuring information before and after the occurrence of the faults.
Accordingly, the user can see information before the fault so that the user can analyze the fault
more precisely. The user can select a fault from the recorded lists; the user can save it into the
fault information file in the CSV. The user can also view the fault records when the exported
data file in the CSV are retrieved into the IED.
Note: In the IED the date and time is clocked in the coordinated universal time (UTC)
when the clock is selected to operate in UTC. In the record tools within the PC the
date and time is treated in the UTC. Notice that the time in the UTC is converted
for the local time when the recording time is displayed on the PC. For the clock
operation if the user selects neither the UTC, the time zone or the daylight saving
time (the summer time), displaying incorrect time may result in between the IED
and the PC. For more information about the clock and time, see Chapter Technical
description: Clock function.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 982 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 983 -
6F2S1927 (0.18)
7 PLC function
Contents Pages
About PLC function 985 PLC driver 986
BIT (Boolean) type 986
Error check 985 USINT (Unsigned short integer) type 988
IED screen information 985 UNIT (Unsigned integer) type 988
UDINT (Unsigned double integer) type 989
SINT (Short integer) type 989
INT (Integer) type 989
DINT (Double integer) type 989
Timer variable setting 990
Setting [UTM1] ~ [UTM24] 992
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 984 -
6F2S1927 (0.18)
[00000006] [00000000]
[00000000] [00000000]
[00000000] [00000000]
Figure 7.2-1 Error code at 1st row and 1st column on Monitoring sub-menu
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 985 -
6F2S1927 (0.18)
PLC driver
The PLC driver is provided for the user-programmed logic.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 986 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 987 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 988 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 989 -
6F2S1927 (0.18)
Figure 7.4-1 shows that a delay timer “TON1” has been set 500ms in the PLC logic, but the
user can set new value using the setting [UTM1] (e.g., the user can change 500ms to 200ms on
the LCD). Since an internal IED memory is able to access the [UTM1], the IED can operate
with new value of the [UTM1] when new one is set.
PLC editor
Timer FB
Constant value set
Fixed PLC = 500ms
Input Output
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 990 -
6F2S1927 (0.18)
On
FB output Off
On
FB input Off
Run
Counter Stop
0 15 30 45 60
Timer counter
(millisecond)
[UTM1] = 30 ms [UTM1] = 10 ms
Figure 7.4-2 Input and output time chart on TON1 delay timer
Note: Entering new value for the setting [UTM1] does not make the timer counter reset,
if the timer counter is running.
FB output Off
On
FB input Off
Run
[UTM2] = 30 ms [UTM2] = 60 ms
Figure 7.4-3 Input and output time chart onTON2 delay timer
Note: If the FB output has be yielded already, when new value is set for the timer and
that new value is longer input signal duration, the timer counter is not reset.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 991 -
6F2S1927 (0.18)
UTM24 +
0 ms
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 992 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 993 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 994 -
6F2S1927 (0.18)
8 Recording function
Contents Pages Pages
Disturbance recorder 1036 Event recorder 1010
-Maximum number of recording 1037 -Setup 1034
-Recording signals 1036 -Trigger signals 1010
-Recording time and capacities 1036 -Trigger modes 1033
-Relays within disturbance recorder 1036 Fault recorder 996
-Trigger settings for PLC 1046 -Screen information 998
-Types of recording information 1046 -Setup 999
Transferring recording information 1050
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 995 -
6F2S1927 (0.18)
The recording function consists of three recording features: (1) Fault recorder, (2) Event
recorder, and (3) Disturbance recorder. The fault recorder collects the information about the
power system quantities when a fault occurs. The event recorder groups state information
when the changes are detected. The disturbance recorder is designed to memory the various
quantities—numerical analog data and logic data (binary data)—from the monitoring function
and the BIO modules; it is possible to analyze the disturbance using the engineering tool (GR-
TIMES), which can draw several chronological waves.
Fault recorder
During the fault, the fault recorder can memorize reasons by equipment failures/operation
states, system information etc. It commences by injecting a signal coming from the TRC alarm-
signal generation logic, but is also started by a trigger provided by PLC function. The fault
recorder captures the following items for each fault:
Date and time at the fault
Tripped phase information
Operating mode information
FL calculation result (if the FL function operates)
Evolving faults (if the ARC function operates)
Fault and pre-fault quantities
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 996 -
6F2S1927 (0.18)
†Note:A number of the operation identifiers are provided by the protection functions. For
example, the ‘OC1-OPT-A’ operation identifier is used to identify the pickup in the
first element of the overcurrent function (OC1) in phase-A. See respective
protection functions in Chapter Relay application.
‡Note:64 logical signals are selectable for recording. For example in this purpose, the
user may choose an operation signal on the circuits of the BIO modules (BIOs).
Ie (2)
Va, Vb, Vc
Voltage in phase, phase-to-phase, and symmetrical Vab, Vbc, Vca – – –
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 997 -
6F2S1927 (0.18)
Software model3
Recording quantities Abbreviations 3D 3E 3F 30 32 36 39
Reference voltage Vs – – – – –
Second reference voltage Vs2 – – – – –
1Note: Terms ‘I0 (i.e., 3I0)’ and ‘V0 (i.e., 3V0)’ are calculated using three-phase quantities.
2Note: The ‘Ie’ is obtained usually with corresponding ‘Ie’ circuit in the VCT.
3Note: A software model is choices when the ordering. See the ‘Software selection’ in
Appendix: Ordering.
have the information about evolving faults, which is able to memory up to 32 developing faults.
Quantitates when the fault occurred are shown below messages○ h .
g ○
Figure 8.1-1 Information of the fault recorder displayed on the IED screen
†Note:For more screen information, see Chapter User interface: Record sub-menu. For
more information about the FL calculation, see Chapter Relay application: Single-
end fault locator.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 998 -
6F2S1927 (0.18)
PreFault values ○
h Pre-fault quantities
Ia
1234.56kVa 123.4deg
Ib
1234.56kVa 123.4deg
Ic
1234.56kVa 123.4deg
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 999 -
6F2S1927 (0.18)
logical signal using settings the [OP Mode ID265] etc. For example, the user wishes to record
the output level of the binary output circuit#1 (BO1) at the IO#1 slot, set its PLC monitoring
point ‘200B01 8002001112’ for the setting [OP Mode ID265]; set the displaying name using the
[OP Mode Name265].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1000 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1001 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1002 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1003 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1004 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1005 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1006 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1007 -
6F2S1927 (0.18)
GEN.TRIP_ALARM OP.MODE-GET
From ARC 0 t
ARC INPROG F.RECORD_TRIG_SPRED
0. 1s
8020001001 1 Drop Off
802000E001 ADD_F.RECORD_TRIG1
8120011001 0.01s
812001E001 ADD_F.RECORD_TRIG2
≥1 ≥1
1 ≥1
8220021001
Drop Off
822002E001 ADD_F.RECORD_TRIG3
8320031001 1s
832003E001 ADD_F.RECORD_TRIG4 Pick Up
1
≥1
Drop Off
0.01s
From protection function #1(FC1)
FC1_OPT_AR Identifier signals &
FC1_OPT_BR (FC*_OPT_*) coming Setting [OP Mode ID1] Operation mode information recorded
FC1_OPT_CR from protection functions when GEN.TRIP_ALARM signal is
(FC*) are detected & generated in the TRC function
FC1_OPT_ABR changing the logic level Setting [OP Mode ID2]
FC1_OPT_BCR “0(Un-operated)” to
FC1_OPT_CAR “1(Operated)”. &
Setting [OP Mode ID3]
From protection function #2(FC2)
FC1_OPT_AR
FC1_OPT_BR
FC1_OPT_CR Signals about the
FC1_OPT_ABR operation modes in the
FC1_OPT_BCR protection functions are &
FC1_OPT_CAR set. Setting [OP Mode ID128]
Setting [OP Mode ID1]
&
Setting [OP Mode ID2] Setting [OP Mode ID201]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1008 -
6F2S1927 (0.18)
8.1.5 Setting
FAULT_RECORD(Function ID: 200602)
Setting items Range Unit Contents Default Note
8.1.6 Signal
Signal monitoring point
FAULT_RECORD (Function ID: 200602)
Name Element ID Description
ADD_F.RECORD_TRIG1 8020001001 Receiving Trigger1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1009 -
6F2S1927 (0.18)
Event recorder
Signals are generated in the logics of BIO modules etc. in the IED. The event recorder can
memory the generated signals as events. To operate the event recorder, the user should pick a
preferred signal as a trigger of the event recorder; the event recorder can have 768 triggers,
some of which have been set as a default. The user can group the triggers into three categories;
consequently, it is possible that a number of the events are divided depending on the degree of
the errors, the meaning of the operations, and the signals of relay elements, etc. The user can
also program how an event is to be detected. An event is recorded with millisecond accuracy.
The information are memorized until the number of the events reaching 1024; the oldest event
will be deleted when a new event appears.
Pulse train
3000001001
FR_CLR List of ‘Event record1’
FAULT RECORD (200602)
Event #3
On 2012-07-25 10:31:12
Event #3 F.Record clear ‘On’
Event #2
3010001001
Active group Active group
2012-07-25 10:56:12
SYS_CHG Set group change
‘3’ Changed to ‘4’
Setting_PF (201400)
Event #2
Figure 8.2-1 Relation between function signals and triggers for Event record1
Figure 8.2-1 illustrates signals connected with triggers in the event recorder. For example,
‘SYS_CHG’ is connected with trigger#7 using the [Trigger ID7] and ‘FR_CLR’ is connected with
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1010 -
6F2S1927 (0.18)
trigger#14 using the [Trigger ID14]. Note that the both triggers (#7 and #14) are smaller than
the setting [End of E.Record-1]=256; hence, the both are listed in the ‘Event recored1’ list.
Keep in mind that the event names are set by the [Event Name7] and [Event Name14].Table
8.2-1 and the others tabulate the ones.
†Note:The GR-TIEMS uses terms ‘Level1’, ‘Level2’, and ‘Level3’ to represent the ‘Event
Record1’, ‘Event Record2’, and ‘Event Record3’. The scope of each level is the same
as the scope of each group. The GR-TIEMS does not show unused triggers and
Trigger ID numbers automatically when the triggers are displayed on the screen.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1011 -
6F2S1927 (0.18)
[Trigger ID1] 220001 3110201001 On-Off Serious error [Trigger ID91] 4A70018000001B63 On-Off ARC READY [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 220001 3110211001 On-Off ErrorLevel2 [Trigger ID92] 4A70018000001BBE On-Off ARC_BLOCK [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 220001 3110221001 On-Off Minor error [Trigger ID93] 4A70018000001BB3 On-Off ARC NO ACT [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 220001 3110231001 On-Off ErrorLevel4 [Trigger ID94] 4A70018000001BB2 On-Off EXT.ARC_START [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 220001 3110241001 On-Off ErrorLevel5 [Trigger ID95] 4A70018000001B6A On-Off ARC CLOSE COMMAND [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not Assigned) Off - [Trigger ID96] (Not Assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 201400 3200001001 Change Set. group change [Trigger ID97] (Not Assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 201400 3010001001 On System set. change [Trigger ID98] (Not Assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 201400 3010011001 On Comm. set. change [Trigger ID99] (Not Assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 201400 3010021001 On Prot. set. change [Trigger ID100] (Not Assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 201400 3010031001 On Ctrl. set. change [Trigger ID101] (Not Assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not Assigned) Off - [Trigger ID102] (Not Assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not Assigned) Off - [Trigger ID103] (Not Assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 200602 3000001001 On F.Record clear [Trigger ID104] (Not Assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 200710 3001001001 On E.Record1 clear [Trigger ID105] (Not Assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 200710 3002001001 On E.Record2 clear [Trigger ID106] (Not Assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 200710 3003001001 On E.Record3 clear [Trigger ID107] (Not Assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not Assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not Assigned) Off - [Trigger ID109] (Not Assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not Assigned) Off - [Trigger ID110] (Not Assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not Assigned) Off - [Trigger ID111] 4900018000001B61 On-Off VTF DETECT [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not Assigned) Off - [Trigger ID112] 4900018100001BB1 On-Off EXTERNAL VTF [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not Assigned) Off - [Trigger ID113] (Not Assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not Assigned) Off - [Trigger ID114] 4910018000001B62 On-Off CTF DETECT [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not Assigned) Off - [Trigger ID115] 4910018100001BB1 On-Off EXTERNAL CTF [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not Assigned) Off - [Trigger ID116] (Not Assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not Assigned) Off - [Trigger ID117] (Not Assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not Assigned) Off - [Trigger ID118] (Not Assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not Assigned) Off - [Trigger ID119] (Not Assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not Assigned) Off - [Trigger ID120] (Not Assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not Assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not Assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not Assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not Assigned) Off - [Trigger ID124] (Not Assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not Assigned) Off - [Trigger ID125] (Not Assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not Assigned) Off - [Trigger ID126] (Not Assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not Assigned) Off - [Trigger ID127] (Not Assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not Assigned) Off - [Trigger ID128] (Not Assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not Assigned) Off - [Trigger ID129] (Not Assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not Assigned) Off - [Trigger ID130] (Not Assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not Assigned) Off - [Trigger ID131] (Not Assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not Assigned) Off - [Trigger ID132] (Not Assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not Assigned) Off - [Trigger ID133] (Not Assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not Assigned) Off - [Trigger ID134] (Not Assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not Assigned) Off - [Trigger ID135] (Not Assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not Assigned) Off - [Trigger ID136] (Not Assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not Assigned) Off - [Trigger ID137] (Not Assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not Assigned) Off - [Trigger ID138] (Not Assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not Assigned) Off - [Trigger ID139] (Not Assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not Assigned) Off - [Trigger ID140] (Not Assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not Assigned) Off - [Trigger ID141] (Not Assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not Assigned) Off - [Trigger ID142] (Not Assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not Assigned) Off - [Trigger ID143] (Not Assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB_CLOSE [Trigger ID144] (Not Assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not Assigned) Off - [Trigger ID145] (Not Assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not Assigned) Off - [Trigger ID146] (Not Assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not Assigned) Off - [Trigger ID147] (Not Assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not Assigned) Off - [Trigger ID148] (Not Assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] 48A0018E00001B85 On-Off DS_CLOSE [Trigger ID149] (Not Assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not Assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not Assigned) Off - [Trigger ID151] (Not Assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not Assigned) Off - [Trigger ID152] (Not Assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not Assigned) Off - [Trigger ID153] (Not Assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not Assigned) Off - [Trigger ID154] (Not Assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not Assigned) Off - [Trigger ID155] (Not Assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not Assigned) Off - [Trigger ID156] (Not Assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not Assigned) Off - [Trigger ID157] (Not Assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not Assigned) Off - [Trigger ID158] (Not Assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not Assigned) Off - [Trigger ID159] (Not Assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not Assigned) Off - [Trigger ID160] (Not Assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A10018300001B6F On-Off GEN.TRIP [Trigger ID161] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A10018400001B64 On-Off GEN.ALARM [Trigger ID162] (Not Assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A10018000001B71 On-Off OPT.PHASE-A [Trigger ID163] (Not Assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A10018100001B72 On-Off OPT.PHASE-B [Trigger ID164] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A10018200001B73 On-Off OPT.PHASE-C [Trigger ID165] (Not Assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not Assigned) Off - [Trigger ID166] (Not Assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not Assigned) Off - [Trigger ID167] (Not Assigned) Off -
[Trigger ID78] (Not Assigned) Off - [Trigger ID168] (Not Assigned) Off -
[Trigger ID79] (Not Assigned) Off - [Trigger ID169] (Not Assigned) Off -
[Trigger ID80] (Not Assigned) Off - [Trigger ID170] (Not Assigned) Off -
[Trigger ID81] (Not Assigned) Off - [Trigger ID171] (Not Assigned) Off -
[Trigger ID82] (Not Assigned) Off - [Trigger ID172] (Not Assigned) Off -
[Trigger ID83] (Not Assigned) Off - [Trigger ID173] (Not Assigned) Off -
[Trigger ID84] (Not Assigned) Off - [Trigger ID174] (Not Assigned) Off -
[Trigger ID85] (Not Assigned) Off - [Trigger ID175] (Not Assigned) Off -
[Trigger ID86] (Not Assigned) Off - [Trigger ID176] (Not Assigned) Off -
[Trigger ID87] (Not Assigned) Off - [Trigger ID177] (Not Assigned) Off -
[Trigger ID88] (Not Assigned) Off - [Trigger ID178] (Not Assigned) Off -
[Trigger ID89] (Not Assigned) Off - [Trigger ID179] (Not Assigned) Off -
[Trigger ID90] (Not Assigned) Off - [Trigger ID180] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1012 -
6F2S1927 (0.18)
[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1013 -
6F2S1927 (0.18)
[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1014 -
6F2S1927 (0.18)
[Trigger ID1] 220001 3110201001 On-Off Serious error [Trigger ID91] 4A70018000001B63 On-Off ARC READY [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 220001 3110211001 On-Off ErrorLevel2 [Trigger ID92] 4A70018000001BBE On-Off ARC_BLOCK [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 220001 3110221001 On-Off Minor error [Trigger ID93] 4A70018000001BB3 On-Off ARC NO ACT [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 220001 3110231001 On-Off ErrorLevel4 [Trigger ID94] 4A70018000001BB2 On-Off EXT.ARC_START [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 220001 3110241001 On-Off ErrorLevel5 [Trigger ID95] 4A70018000001B6A On-Off ARC CLOSE COMMAND [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not Assigned) Off - [Trigger ID96] (Not Assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 201400 3200001001 Change Set. group change [Trigger ID97] (Not Assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 201400 3010001001 On System set. change [Trigger ID98] (Not Assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 201400 3010011001 On Comm. set. change [Trigger ID99] (Not Assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 201400 3010021001 On Prot. set. change [Trigger ID100] (Not Assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 201400 3010031001 On Ctrl. set. change [Trigger ID101] (Not Assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not Assigned) Off - [Trigger ID102] (Not Assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not Assigned) Off - [Trigger ID103] (Not Assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 200602 3000001001 On F.Record clear [Trigger ID104] (Not Assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 200710 3001001001 On E.Record1 clear [Trigger ID105] (Not Assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 200710 3002001001 On E.Record2 clear [Trigger ID106] (Not Assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 200710 3003001001 On E.Record3 clear [Trigger ID107] (Not Assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not Assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not Assigned) Off - [Trigger ID109] (Not Assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not Assigned) Off - [Trigger ID110] (Not Assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not Assigned) Off - [Trigger ID111] 4900018000001B61 On-Off VTF DETECT [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not Assigned) Off - [Trigger ID112] 4900018100001BB1 On-Off EXTERNAL VTF [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not Assigned) Off - [Trigger ID113] (Not Assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not Assigned) Off - [Trigger ID114] 4910018000001B62 On-Off CTF DETECT [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not Assigned) Off - [Trigger ID115] 4910018100001BB1 On-Off EXTERNAL CTF [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not Assigned) Off - [Trigger ID116] (Not Assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not Assigned) Off - [Trigger ID117] (Not Assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not Assigned) Off - [Trigger ID118] (Not Assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not Assigned) Off - [Trigger ID119] (Not Assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not Assigned) Off - [Trigger ID120] (Not Assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not Assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not Assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not Assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not Assigned) Off - [Trigger ID124] (Not Assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not Assigned) Off - [Trigger ID125] (Not Assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not Assigned) Off - [Trigger ID126] (Not Assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not Assigned) Off - [Trigger ID127] (Not Assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not Assigned) Off - [Trigger ID128] (Not Assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not Assigned) Off - [Trigger ID129] (Not Assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not Assigned) Off - [Trigger ID130] (Not Assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not Assigned) Off - [Trigger ID131] 4370018000001B60 On-Off EXT.DEFCAR-R1 [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not Assigned) Off - [Trigger ID132] 4370018100001B62 On-Off EXT.DEFCAR-R2 [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not Assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not Assigned) Off - [Trigger ID134] 4380018000001BB0 On-Off CAR_BLOCK [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not Assigned) Off - [Trigger ID135] (Not Assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not Assigned) Off - [Trigger ID136] (Not Assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not Assigned) Off - [Trigger ID137] (Not Assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not Assigned) Off - [Trigger ID138] (Not Assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not Assigned) Off - [Trigger ID139] (Not Assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not Assigned) Off - [Trigger ID140] (Not Assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not Assigned) Off - [Trigger ID141] (Not Assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not Assigned) Off - [Trigger ID142] (Not Assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not Assigned) Off - [Trigger ID143] (Not Assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB_CLOSE [Trigger ID144] (Not Assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not Assigned) Off - [Trigger ID145] (Not Assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not Assigned) Off - [Trigger ID146] (Not Assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not Assigned) Off - [Trigger ID147] (Not Assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not Assigned) Off - [Trigger ID148] (Not Assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] 48A0018E00001B85 On-Off DS_CLOSE [Trigger ID149] (Not Assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not Assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not Assigned) Off - [Trigger ID151] (Not Assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not Assigned) Off - [Trigger ID152] (Not Assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not Assigned) Off - [Trigger ID153] (Not Assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not Assigned) Off - [Trigger ID154] (Not Assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not Assigned) Off - [Trigger ID155] (Not Assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not Assigned) Off - [Trigger ID156] (Not Assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not Assigned) Off - [Trigger ID157] (Not Assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not Assigned) Off - [Trigger ID158] (Not Assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not Assigned) Off - [Trigger ID159] (Not Assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not Assigned) Off - [Trigger ID160] (Not Assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A10018300001B6F On-Off GEN.TRIP [Trigger ID161] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A10018400001B64 On-Off GEN.ALARM [Trigger ID162] (Not Assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A10018000001B71 On-Off OPT.PHASE-A [Trigger ID163] (Not Assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A10018100001B72 On-Off OPT.PHASE-B [Trigger ID164] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A10018200001B73 On-Off OPT.PHASE-C [Trigger ID165] (Not Assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not Assigned) Off - [Trigger ID166] (Not Assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not Assigned) Off - [Trigger ID167] (Not Assigned) Off -
[Trigger ID78] (Not Assigned) Off - [Trigger ID168] (Not Assigned) Off -
[Trigger ID79] (Not Assigned) Off - [Trigger ID169] (Not Assigned) Off -
[Trigger ID80] (Not Assigned) Off - [Trigger ID170] (Not Assigned) Off -
[Trigger ID81] (Not Assigned) Off - [Trigger ID171] (Not Assigned) Off -
[Trigger ID82] (Not Assigned) Off - [Trigger ID172] (Not Assigned) Off -
[Trigger ID83] (Not Assigned) Off - [Trigger ID173] (Not Assigned) Off -
[Trigger ID84] (Not Assigned) Off - [Trigger ID174] (Not Assigned) Off -
[Trigger ID85] (Not Assigned) Off - [Trigger ID175] (Not Assigned) Off -
[Trigger ID86] (Not Assigned) Off - [Trigger ID176] (Not Assigned) Off -
[Trigger ID87] (Not Assigned) Off - [Trigger ID177] (Not Assigned) Off -
[Trigger ID88] (Not Assigned) Off - [Trigger ID178] (Not Assigned) Off -
[Trigger ID89] (Not Assigned) Off - [Trigger ID179] (Not Assigned) Off -
[Trigger ID90] (Not Assigned) Off - [Trigger ID180] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1015 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1016 -
6F2S1927 (0.18)
[Trigger ID513] 5120018203291F43 On DPOS41 Undefined [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] 5120018403291F45 On DPOS41 Faulty [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] 51200182032A1F43 On DPOS42 Undefined [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] 51200184032A1F45 On DPOS42 Faulty [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] 51200182032B1F43 On DPOS43 Undefined [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] 51200184032B1F45 On DPOS43 Faulty [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] 51200182032C1F43 On DPOS44 Undefined [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] 51200184032C1F45 On DPOS44 Faulty [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] 51200182032D1F43 On DPOS45 Undefined [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] 51200184032D1F45 On DPOS45 Faulty [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] 51200182032E1F43 On DPOS46 Undefined [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] 51200184032E1F45 On DPOS46 Faulty [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] 51200182032F1F43 On DPOS47 Undefined [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] 51200184032F1F45 On DPOS47 Faulty [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] 5120018203301F43 On DPOS48 Undefined [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] 5120018403301F45 On DPOS48 Faulty [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] 5120018203311F43 On DPOS49 Undefined [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] 5120018403311F45 On DPOS49 Faulty [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] 5120018203321F43 On DPOS50 Undefined [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] 5120018403321F45 On DPOS50 Faulty [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] 5120018203331F43 On DPOS51 Undefined [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] 5120018403331F45 On DPOS51 Faulty [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] 5120018203341F43 On DPOS52 Undefined [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] 5120018403341F45 On DPOS52 Faulty [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] 5120018203351F43 On DPOS53 Undefined [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] 5120018403351F45 On DPOS53 Faulty [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] 5120018203361F43 On DPOS54 Undefined [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] 5120018403361F45 On DPOS54 Faulty [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] 5120018203371F43 On DPOS55 Undefined [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] 5120018403371F45 On DPOS55 Faulty [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] 5120018203381F43 On DPOS56 Undefined [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] 5120018403381F45 On DPOS56 Faulty [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] 5120018203391F43 On DPOS57 Undefined [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] 5120018403391F45 On DPOS57 Faulty [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] 51200182033A1F43 On DPOS58 Undefined [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] 51200184033A1F45 On DPOS58 Faulty [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] 51200182033B1F43 On DPOS59 Undefined [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] 51200184033B1F45 On DPOS59 Faulty [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] 51200182033C1F43 On DPOS60 Undefined [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] 51200184033C1F45 On DPOS60 Faulty [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] 51200182033D1F43 On DPOS61 Undefined [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] 51200184033D1F45 On DPOS61 Faulty [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] 51200182033E1F43 On DPOS62 Undefined [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] 51200184033E1F45 On DPOS62 Faulty [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] 51200182033F1F43 On DPOS63 Undefined [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] 51200184033F1F45 On DPOS63 Faulty [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] 5120018203401F43 On DPOS64 Undefined [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] 5120018403401F45 On DPOS64 Faulty [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] 5120018203411F43 On DPOS65 Undefined [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] 5120018403411F45 On DPOS65 Faulty [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] 5120018203421F43 On DPOS66 Undefined [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] 5120018403421F45 On DPOS66 Faulty [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] 5120018203431F43 On DPOS67 Undefined [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] 5120018403431F45 On DPOS67 Faulty [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] 5120018203441F43 On DPOS68 Undefined [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] 5120018403441F45 On DPOS68 Faulty [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] 5120018203451F43 On DPOS69 Undefined [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] 5120018403451F45 On DPOS69 Faulty [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] 5120018203461F43 On DPOS70 Undefined [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] 5120018403461F45 On DPOS70 Faulty [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] 5120018203471F43 On DPOS71 Undefined [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] 5120018403471F45 On DPOS71 Faulty [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] 5120018203481F43 On DPOS72 Undefined [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] 5120018403481F45 On DPOS72 Faulty [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] 522001000A011001 On-Off Command Blocking [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] 523001000D011001 On ASEQ1 Start [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] 523001000D101001 On EMERGENCY Stop [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] 560001810B011F85 On-Off SYNC1 Release [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] 560001810B011F55 On-Off SYNC1 Progress [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] 560001840B011F58 On-Off SYNC1 Vol. check [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] 560001850B011F59 On-Off SYNC1 Diff. check [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] 560001800B011F54 On-Off SYNC1 Bypass [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] 560001840B011F5F On-Off SYNC1 Failed [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] 560001860B011F5A On RSYN1 84Vr & 84Vi [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] 560001890B011F5D On RSYN1 84Vr & 27Vi [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] 560001870B011F5B On RSYN1 27Vr & 84Vi [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] 560001880B011F5C On RSYN1 27Vr & 27Vi [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] 560001810B021F85 On-Off SYNC2 Release [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] 560001810B021F55 On-Off SYNC2 Progress [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] 560001840B021F58 On-Off SYNC2 Vol. check [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] 560001850B021F59 On-Off SYNC2 Diff. check [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] 560001800B021F54 On-Off SYNC2 Bypass [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] 560001840B021F5F On-Off SYNC2 Failed [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] 560001860B021F5A On RSYN2 84Vr & 84Vi [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] 560001890B021F5D On RSYN2 84Vr & 27Vi [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] 560001870B021F5B On RSYN2 27Vr & 84Vi [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] 560001880B021F5C On RSYN2 27Vr & 27Vi [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1017 -
6F2S1927 (0.18)
[Trigger ID1] 220001 3110201001 On-Off Serious error [Trigger ID91] 4A70018000001B63 On-Off ARC READY [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 220001 3110211001 On-Off ErrorLevel2 [Trigger ID92] 4A70018000001BBE On-Off ARC_BLOCK [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 220001 3110221001 On-Off Minor error [Trigger ID93] 4A70018000001BB3 On-Off ARC NO ACT [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 220001 3110231001 On-Off ErrorLevel4 [Trigger ID94] 4A70018000001BB2 On-Off EXT.ARC_START [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 220001 3110241001 On-Off ErrorLevel5 [Trigger ID95] 4A70018000001B6A On-Off ARC CLOSE COMMAND [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not Assigned) Off - [Trigger ID96] (Not Assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 201400 3200001001 Change Set. group change [Trigger ID97] (Not Assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 201400 3010001001 On System set. change [Trigger ID98] (Not Assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 201400 3010011001 On Comm. set. change [Trigger ID99] (Not Assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 201400 3010021001 On Prot. set. change [Trigger ID100] (Not Assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 201400 3010031001 On Ctrl. set. change [Trigger ID101] (Not Assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not Assigned) Off - [Trigger ID102] (Not Assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not Assigned) Off - [Trigger ID103] (Not Assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 200602 3000001001 On F.Record clear [Trigger ID104] (Not Assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 200710 3001001001 On E.Record1 clear [Trigger ID105] (Not Assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 200710 3002001001 On E.Record2 clear [Trigger ID106] (Not Assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 200710 3003001001 On E.Record3 clear [Trigger ID107] (Not Assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not Assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not Assigned) Off - [Trigger ID109] (Not Assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not Assigned) Off - [Trigger ID110] (Not Assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not Assigned) Off - [Trigger ID111] 4900018000001B61 On-Off VTF DETECT [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not Assigned) Off - [Trigger ID112] 4900018100001BB1 On-Off EXTERNAL VTF [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not Assigned) Off - [Trigger ID113] (Not Assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not Assigned) Off - [Trigger ID114] 4910018000001B62 On-Off CTF DETECT [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not Assigned) Off - [Trigger ID115] 4910018100001BB1 On-Off EXTERNAL CTF [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not Assigned) Off - [Trigger ID116] (Not Assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not Assigned) Off - [Trigger ID117] (Not Assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not Assigned) Off - [Trigger ID118] (Not Assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not Assigned) Off - [Trigger ID119] (Not Assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not Assigned) Off - [Trigger ID120] (Not Assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not Assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not Assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not Assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not Assigned) Off - [Trigger ID124] (Not Assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not Assigned) Off - [Trigger ID125] (Not Assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not Assigned) Off - [Trigger ID126] (Not Assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not Assigned) Off - [Trigger ID127] (Not Assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not Assigned) Off - [Trigger ID128] (Not Assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not Assigned) Off - [Trigger ID129] (Not Assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not Assigned) Off - [Trigger ID130] (Not Assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not Assigned) Off - [Trigger ID131] 4370018000001B60 On-Off EXT.DEFCAR-R1 [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not Assigned) Off - [Trigger ID132] 4370018100001B62 On-Off EXT.DEFCAR-R2 [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not Assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not Assigned) Off - [Trigger ID134] 4380018000001BB0 On-Off CAR_BLOCK [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not Assigned) Off - [Trigger ID135] (Not Assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not Assigned) Off - [Trigger ID136] (Not Assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not Assigned) Off - [Trigger ID137] (Not Assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not Assigned) Off - [Trigger ID138] (Not Assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not Assigned) Off - [Trigger ID139] (Not Assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not Assigned) Off - [Trigger ID140] (Not Assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not Assigned) Off - [Trigger ID141] (Not Assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not Assigned) Off - [Trigger ID142] (Not Assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not Assigned) Off - [Trigger ID143] (Not Assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB_CLOSE [Trigger ID144] (Not Assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not Assigned) Off - [Trigger ID145] (Not Assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not Assigned) Off - [Trigger ID146] (Not Assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not Assigned) Off - [Trigger ID147] (Not Assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not Assigned) Off - [Trigger ID148] (Not Assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] 48A0018E00001B85 On-Off DS_CLOSE [Trigger ID149] (Not Assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not Assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not Assigned) Off - [Trigger ID151] (Not Assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not Assigned) Off - [Trigger ID152] (Not Assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not Assigned) Off - [Trigger ID153] (Not Assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not Assigned) Off - [Trigger ID154] (Not Assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not Assigned) Off - [Trigger ID155] (Not Assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not Assigned) Off - [Trigger ID156] (Not Assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not Assigned) Off - [Trigger ID157] (Not Assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not Assigned) Off - [Trigger ID158] (Not Assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not Assigned) Off - [Trigger ID159] (Not Assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not Assigned) Off - [Trigger ID160] (Not Assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A10018300001B6F On-Off GEN.TRIP [Trigger ID161] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A10018400001B64 On-Off GEN.ALARM [Trigger ID162] (Not Assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A10018000001B71 On-Off OPT.PHASE-A [Trigger ID163] (Not Assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A10018100001B72 On-Off OPT.PHASE-B [Trigger ID164] (Not Assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A10018200001B73 On-Off OPT.PHASE-C [Trigger ID165] (Not Assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not Assigned) Off - [Trigger ID166] (Not Assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not Assigned) Off - [Trigger ID167] (Not Assigned) Off -
[Trigger ID78] (Not Assigned) Off - [Trigger ID168] (Not Assigned) Off -
[Trigger ID79] (Not Assigned) Off - [Trigger ID169] (Not Assigned) Off -
[Trigger ID80] (Not Assigned) Off - [Trigger ID170] (Not Assigned) Off -
[Trigger ID81] (Not Assigned) Off - [Trigger ID171] (Not Assigned) Off -
[Trigger ID82] (Not Assigned) Off - [Trigger ID172] (Not Assigned) Off -
[Trigger ID83] (Not Assigned) Off - [Trigger ID173] (Not Assigned) Off -
[Trigger ID84] (Not Assigned) Off - [Trigger ID174] (Not Assigned) Off -
[Trigger ID85] (Not Assigned) Off - [Trigger ID175] (Not Assigned) Off -
[Trigger ID86] (Not Assigned) Off - [Trigger ID176] (Not Assigned) Off -
[Trigger ID87] (Not Assigned) Off - [Trigger ID177] (Not Assigned) Off -
[Trigger ID88] (Not Assigned) Off - [Trigger ID178] (Not Assigned) Off -
[Trigger ID89] (Not Assigned) Off - [Trigger ID179] (Not Assigned) Off -
[Trigger ID90] (Not Assigned) Off - [Trigger ID180] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1018 -
6F2S1927 (0.18)
[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1019 -
6F2S1927 (0.18)
[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1020 -
6F2S1927 (0.18)
[Trigger ID1] 2200013110201001 On-Off Serious error [Trigger ID91] 4A70018000001B63 On-Off ARC READY [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 2200013110211001 On-Off ErrorLevel2 [Trigger ID92] 4A70018000001BBE On-Off ARC_BLOCK [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 2200013110221001 On-Off Minor error [Trigger ID93] 4A70018000001BB3 On-Off ARC NO ACT [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 2200013110231001 On-Off ErrorLevel4 [Trigger ID94] 4A70018000001BB2 On-Off EXT.ARC_START [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 2200013110241001 On-Off ErrorLevel5 [Trigger ID95] 4A70018000001B6A Default ARC CLOSE COMMAND [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not assigned) Off - [Trigger ID96] (Not assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 2014003200001001 Change Set. group change [Trigger ID97] (Not assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 2014003010001001 On System set. change [Trigger ID98] (Not assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 2014003010011001 On Comm. set. change [Trigger ID99] (Not assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 2014003010021001 On Prot. set. change [Trigger ID100] (Not assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 2014003010031001 On Ctrl. set. change [Trigger ID101] (Not assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not assigned) Off - [Trigger ID102] (Not assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not assigned) Off - [Trigger ID103] (Not assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 2006023000001001 On F.Record clear [Trigger ID104] (Not assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 2007103001001001 On E.Record1 clear [Trigger ID105] (Not assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 2007103002001001 On E.Record2 clear [Trigger ID106] (Not assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 2007103003001001 On E.Record3 clear [Trigger ID107] (Not assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not assigned) Off - [Trigger ID109] (Not assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not assigned) Off - [Trigger ID110] (Not assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not assigned) Off - [Trigger ID111] (Not assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not assigned) Off - [Trigger ID112] (Not assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not assigned) Off - [Trigger ID113] (Not assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not assigned) Off - [Trigger ID114] (Not assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not assigned) Off - [Trigger ID115] (Not assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not assigned) Off - [Trigger ID116] (Not assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not assigned) Off - [Trigger ID117] (Not assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not assigned) Off - [Trigger ID118] (Not assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not assigned) Off - [Trigger ID119] (Not assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not assigned) Off - [Trigger ID120] (Not assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not assigned) Off - [Trigger ID124] (Not assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not assigned) Off - [Trigger ID125] (Not assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not assigned) Off - [Trigger ID126] (Not assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not assigned) Off - [Trigger ID127] (Not assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not assigned) Off - [Trigger ID128] (Not assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not assigned) Off - [Trigger ID129] (Not assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not assigned) Off - [Trigger ID130] (Not assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not assigned) Off - [Trigger ID131] (Not assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not assigned) Off - [Trigger ID132] (Not assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not assigned) Off - [Trigger ID134] (Not assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not assigned) Off - [Trigger ID135] (Not assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not assigned) Off - [Trigger ID136] (Not assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not assigned) Off - [Trigger ID137] (Not assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not assigned) Off - [Trigger ID138] (Not assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not assigned) Off - [Trigger ID139] (Not assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not assigned) Off - [Trigger ID140] (Not assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not assigned) Off - [Trigger ID141] (Not assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not assigned) Off - [Trigger ID142] (Not assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not assigned) Off - [Trigger ID143] (Not assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB_CLOSE [Trigger ID144] (Not assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not assigned) Off - [Trigger ID145] (Not assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not assigned) Off - [Trigger ID146] (Not assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not assigned) Off - [Trigger ID147] (Not assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not assigned) Off - [Trigger ID148] (Not assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] 48A0018E00001B85 On-Off DS_CLOSE [Trigger ID149] (Not assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not assigned) Off - [Trigger ID151] (Not assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not assigned) Off - [Trigger ID152] (Not assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not assigned) Off - [Trigger ID153] (Not assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not assigned) Off - [Trigger ID154] (Not assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not assigned) Off - [Trigger ID155] (Not assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not assigned) Off - [Trigger ID156] (Not assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not assigned) Off - [Trigger ID157] (Not assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not assigned) Off - [Trigger ID158] (Not assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not assigned) Off - [Trigger ID159] (Not assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not assigned) Off - [Trigger ID160] (Not assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A10018300001B6F On-Off GEN.TRIP [Trigger ID161] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A10018400001B64 On-Off GEN.ALARM [Trigger ID162] (Not assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A10018000001B71 On-Off OPT.PHASE-A [Trigger ID163] (Not assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A10018100001B72 On-Off OPT.PHASE-B [Trigger ID164] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A10018200001B73 On-Off OPT.PHASE-C [Trigger ID165] (Not assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] 4A10018300001B74 On-Off OPT.PHASE-N [Trigger ID166] (Not assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not assigned) Off - [Trigger ID167] (Not assigned) Off -
[Trigger ID78] (Not assigned) Off - [Trigger ID168] (Not assigned) Off -
[Trigger ID79] (Not assigned) Off - [Trigger ID169] (Not assigned) Off -
[Trigger ID80] (Not assigned) Off - [Trigger ID170] (Not assigned) Off -
[Trigger ID81] (Not assigned) Off - [Trigger ID171] (Not assigned) Off -
[Trigger ID82] (Not assigned) Off - [Trigger ID172] (Not assigned) Off -
[Trigger ID83] (Not assigned) Off - [Trigger ID173] (Not assigned) Off -
[Trigger ID84] (Not assigned) Off - [Trigger ID174] (Not assigned) Off -
[Trigger ID85] (Not assigned) Off - [Trigger ID175] (Not assigned) Off -
[Trigger ID86] (Not assigned) Off - [Trigger ID176] (Not assigned) Off -
[Trigger ID87] (Not assigned) Off - [Trigger ID177] (Not assigned) Off -
[Trigger ID88] (Not assigned) Off - [Trigger ID178] (Not assigned) Off -
[Trigger ID89] (Not assigned) Off - [Trigger ID179] (Not assigned) Off -
[Trigger ID90] (Not assigned) Off - [Trigger ID180] (Not assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1021 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1022 -
6F2S1927 (0.18)
[Trigger ID513] 5120018203291F43 On DPOS41 Undefined [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] 5120018403291F45 On DPOS41 Faulty [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] 51200182032A1F43 On DPOS42 Undefined [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] 51200184032A1F45 On DPOS42 Faulty [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] 51200182032B1F43 On DPOS43 Undefined [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] 51200184032B1F45 On DPOS43 Faulty [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] 51200182032C1F43 On DPOS44 Undefined [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] 51200184032C1F45 On DPOS44 Faulty [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] 51200182032D1F43 On DPOS45 Undefined [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] 51200184032D1F45 On DPOS45 Faulty [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] 51200182032E1F43 On DPOS46 Undefined [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] 51200184032E1F45 On DPOS46 Faulty [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] 51200182032F1F43 On DPOS47 Undefined [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] 51200184032F1F45 On DPOS47 Faulty [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] 5120018203301F43 On DPOS48 Undefined [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] 5120018403301F45 On DPOS48 Faulty [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] 5120018203311F43 On DPOS49 Undefined [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] 5120018403311F45 On DPOS49 Faulty [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] 5120018203321F43 On DPOS50 Undefined [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] 5120018403321F45 On DPOS50 Faulty [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] 5120018203331F43 On DPOS51 Undefined [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] 5120018403331F45 On DPOS51 Faulty [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] 5120018203341F43 On DPOS52 Undefined [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] 5120018403341F45 On DPOS52 Faulty [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] 5120018203351F43 On DPOS53 Undefined [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] 5120018403351F45 On DPOS53 Faulty [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] 5120018203361F43 On DPOS54 Undefined [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] 5120018403361F45 On DPOS54 Faulty [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] 5120018203371F43 On DPOS55 Undefined [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] 5120018403371F45 On DPOS55 Faulty [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] 5120018203381F43 On DPOS56 Undefined [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] 5120018403381F45 On DPOS56 Faulty [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] 5120018203391F43 On DPOS57 Undefined [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] 5120018403391F45 On DPOS57 Faulty [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] 51200182033A1F43 On DPOS58 Undefined [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] 51200184033A1F45 On DPOS58 Faulty [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] 51200182033B1F43 On DPOS59 Undefined [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] 51200184033B1F45 On DPOS59 Faulty [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] 51200182033C1F43 On DPOS60 Undefined [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] 51200184033C1F45 On DPOS60 Faulty [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] 51200182033D1F43 On DPOS61 Undefined [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] 51200184033D1F45 On DPOS61 Faulty [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] 51200182033E1F43 On DPOS62 Undefined [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] 51200184033E1F45 On DPOS62 Faulty [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] 51200182033F1F43 On DPOS63 Undefined [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] 51200184033F1F45 On DPOS63 Faulty [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] 5120018203401F43 On DPOS64 Undefined [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] 5120018403401F45 On DPOS64 Faulty [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] 5120018203411F43 On DPOS65 Undefined [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] 5120018403411F45 On DPOS65 Faulty [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] 5120018203421F43 On DPOS66 Undefined [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] 5120018403421F45 On DPOS66 Faulty [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] 5120018203431F43 On DPOS67 Undefined [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] 5120018403431F45 On DPOS67 Faulty [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] 5120018203441F43 On DPOS68 Undefined [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] 5120018403441F45 On DPOS68 Faulty [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] 5120018203451F43 On DPOS69 Undefined [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] 5120018403451F45 On DPOS69 Faulty [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] 5120018203461F43 On DPOS70 Undefined [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] 5120018403461F45 On DPOS70 Faulty [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] 5120018203471F43 On DPOS71 Undefined [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] 5120018403471F45 On DPOS71 Faulty [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] 5120018203481F43 On DPOS72 Undefined [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] 5120018403481F45 On DPOS72 Faulty [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] 522001000A011001 On-Off Command Blocking [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] 523001000D011001 On ASEQ1 Start [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] 523001000D101001 On EMERGENCY Stop [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1023 -
6F2S1927 (0.18)
[Trigger ID1] 2200013110201001 On-Off Serious error [Trigger ID91] 4A70018000001B63 On-Off ARC READY [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 2200013110211001 On-Off ErrorLevel2 [Trigger ID92] 4A70018000001BBE On-Off ARC_BLOCK [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 2200013110221001 On-Off Minor error [Trigger ID93] 4A70018000001BB3 On-Off ARC NO ACT [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 2200013110231001 On-Off ErrorLevel4 [Trigger ID94] 4A70018000001BB2 On-Off EXT.ARC_START [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 2200013110241001 On-Off ErrorLevel5 [Trigger ID95] 4A70018000001B6A Default ARC CLOSE COMMAND [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not assigned) Off - [Trigger ID96] (Not assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 2014003200001001 Change Set. group change [Trigger ID97] (Not assigned) Off - [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 2014003010001001 On System set. change [Trigger ID98] (Not assigned) Off - [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 2014003010011001 On Comm. set. change [Trigger ID99] (Not assigned) Off - [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 2014003010021001 On Prot. set. change [Trigger ID100] (Not assigned) Off - [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] 2014003010031001 On Ctrl. set. change [Trigger ID101] (Not assigned) Off - [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not assigned) Off - [Trigger ID102] (Not assigned) Off - [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not assigned) Off - [Trigger ID103] (Not assigned) Off - [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 2006023000001001 On F.Record clear [Trigger ID104] (Not assigned) Off - [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 2007103001001001 On E.Record1 clear [Trigger ID105] (Not assigned) Off - [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 2007103002001001 On E.Record2 clear [Trigger ID106] (Not assigned) Off - [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 2007103003001001 On E.Record3 clear [Trigger ID107] (Not assigned) Off - [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] (Not assigned) Off - [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not assigned) Off - [Trigger ID109] (Not assigned) Off - [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not assigned) Off - [Trigger ID110] (Not assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not assigned) Off - [Trigger ID111] (Not assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not assigned) Off - [Trigger ID112] (Not assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not assigned) Off - [Trigger ID113] (Not assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not assigned) Off - [Trigger ID114] (Not assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not assigned) Off - [Trigger ID115] (Not assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not assigned) Off - [Trigger ID116] (Not assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not assigned) Off - [Trigger ID117] (Not assigned) Off - [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not assigned) Off - [Trigger ID118] (Not assigned) Off - [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not assigned) Off - [Trigger ID119] (Not assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not assigned) Off - [Trigger ID120] (Not assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not assigned) Off - [Trigger ID124] (Not assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not assigned) Off - [Trigger ID125] (Not assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not assigned) Off - [Trigger ID126] (Not assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not assigned) Off - [Trigger ID127] (Not assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not assigned) Off - [Trigger ID128] (Not assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not assigned) Off - [Trigger ID129] (Not assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not assigned) Off - [Trigger ID130] (Not assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not assigned) Off - [Trigger ID131] (Not assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not assigned) Off - [Trigger ID132] (Not assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not assigned) Off - [Trigger ID134] (Not assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not assigned) Off - [Trigger ID135] (Not assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not assigned) Off - [Trigger ID136] (Not assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not assigned) Off - [Trigger ID137] (Not assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not assigned) Off - [Trigger ID138] (Not assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not assigned) Off - [Trigger ID139] (Not assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not assigned) Off - [Trigger ID140] (Not assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not assigned) Off - [Trigger ID141] (Not assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not assigned) Off - [Trigger ID142] (Not assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not assigned) Off - [Trigger ID143] (Not assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB_CLOSE [Trigger ID144] (Not assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not assigned) Off - [Trigger ID145] (Not assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not assigned) Off - [Trigger ID146] (Not assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not assigned) Off - [Trigger ID147] (Not assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not assigned) Off - [Trigger ID148] (Not assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] 48A0018E00001B85 On-Off DS_CLOSE [Trigger ID149] (Not assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not assigned) Off - [Trigger ID151] (Not assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not assigned) Off - [Trigger ID152] (Not assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not assigned) Off - [Trigger ID153] (Not assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not assigned) Off - [Trigger ID154] (Not assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not assigned) Off - [Trigger ID155] (Not assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not assigned) Off - [Trigger ID156] (Not assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not assigned) Off - [Trigger ID157] (Not assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not assigned) Off - [Trigger ID158] (Not assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not assigned) Off - [Trigger ID159] (Not assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not assigned) Off - [Trigger ID160] (Not assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] 4A10018300001B6F On-Off GEN.TRIP [Trigger ID161] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] 4A10018400001B64 On-Off GEN.ALARM [Trigger ID162] (Not assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] 4A10018000001B71 On-Off OPT.PHASE-A [Trigger ID163] (Not assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] 4A10018100001B72 On-Off OPT.PHASE-B [Trigger ID164] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] 4A10018200001B73 On-Off OPT.PHASE-C [Trigger ID165] (Not assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] 4A10018300001B74 On-Off OPT.PHASE-N [Trigger ID166] (Not assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not assigned) Off - [Trigger ID167] (Not assigned) Off -
[Trigger ID78] (Not assigned) Off - [Trigger ID168] (Not assigned) Off -
[Trigger ID79] (Not assigned) Off - [Trigger ID169] (Not assigned) Off -
[Trigger ID80] (Not assigned) Off - [Trigger ID170] (Not assigned) Off -
[Trigger ID81] (Not assigned) Off - [Trigger ID171] (Not assigned) Off -
[Trigger ID82] (Not assigned) Off - [Trigger ID172] (Not assigned) Off -
[Trigger ID83] (Not assigned) Off - [Trigger ID173] (Not assigned) Off -
[Trigger ID84] (Not assigned) Off - [Trigger ID174] (Not assigned) Off -
[Trigger ID85] (Not assigned) Off - [Trigger ID175] (Not assigned) Off -
[Trigger ID86] (Not assigned) Off - [Trigger ID176] (Not assigned) Off -
[Trigger ID87] (Not assigned) Off - [Trigger ID177] (Not assigned) Off -
[Trigger ID88] (Not assigned) Off - [Trigger ID178] (Not assigned) Off -
[Trigger ID89] (Not assigned) Off - [Trigger ID179] (Not assigned) Off -
[Trigger ID90] (Not assigned) Off - [Trigger ID180] (Not assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1024 -
6F2S1927 (0.18)
[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1025 -
6F2S1927 (0.18)
[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1026 -
6F2S1927 (0.18)
[Trigger ID1] 2200013110201001 On-Off Serious error [Trigger ID91] (Not assigned) Off - [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 2200013110211001 On-Off ErrorLevel2 [Trigger ID92] (Not assigned) Off - [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 2200013110221001 On-Off Minor error [Trigger ID93] (Not assigned) Off - [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 2200013110231001 On-Off ErrorLevel4 [Trigger ID94] (Not assigned) Off - [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 2200013110241001 On-Off ErrorLevel5 [Trigger ID95] (Not assigned) Off - [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not assigned) Off - [Trigger ID96] (Not assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 2014003200001001 Change Set. group change [Trigger ID97] 4A60018500011B6F On-Off CB1_94TT [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 2014003010001001 On System set. change [Trigger ID98] 4A60018500021B6B On-Off CB2_94TT [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 2014003010011001 On Comm. set. change [Trigger ID99] 4A60018800011B62 On-Off CB1_BRIDGE [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 2014003010021001 On Prot. set. change [Trigger ID100] 4A60018800021B62 On-Off CB2_BRIDGE [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] (Not assigned) Off - [Trigger ID101] 4A60018000011B60 On-Off ARC1 READY [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not assigned) Off - [Trigger ID102] 4A60018000021B60 On-Off ARC2 READY [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not assigned) Off - [Trigger ID103] 4A60018200001BB4 On-Off ARC_BLOCK [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 2006023000001001 On F.Record clear [Trigger ID104] 4A60018000001BB3 On-Off ARC NO ACT [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 2007103001001001 On E.Record1 clear [Trigger ID105] 4A60018000001BB0 On-Off START-A [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 2007103002001001 On E.Record2 clear [Trigger ID106] 4A60018100001BB1 On-Off START-B [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 2007103003001001 On E.Record3 clear [Trigger ID107] 4A60018200001BB2 On-Off START-C [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] 4A60018000011B6C On-Off ARC1 CLOSE COMMAND [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not assigned) Off - [Trigger ID109] 4A60018100021B68 On-Off ARC2 CLOSE COMMAND [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not assigned) Off - [Trigger ID110] (Not assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not assigned) Off - [Trigger ID111] (Not assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not assigned) Off - [Trigger ID112] (Not assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not assigned) Off - [Trigger ID113] (Not assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not assigned) Off - [Trigger ID114] (Not assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not assigned) Off - [Trigger ID115] (Not assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not assigned) Off - [Trigger ID116] (Not assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not assigned) Off - [Trigger ID117] 4A60018200011B61 On-Off ARC1 IN-PROG [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not assigned) Off - [Trigger ID118] 4A60018200021B61 On-Off ARC2 IN-PROG [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not assigned) Off - [Trigger ID119] (Not assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not assigned) Off - [Trigger ID120] (Not assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not assigned) Off - [Trigger ID121] 4530018000011BB0 On-Off EXT.CBF_START-A [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not assigned) Off - [Trigger ID122] 4530018100011BB1 On-Off EXT.CBF_START-B [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not assigned) Off - [Trigger ID123] 4530018200011BB2 On-Off EXT.CBF_START-C [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not assigned) Off - [Trigger ID124] (Not assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not assigned) Off - [Trigger ID125] (Not assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not assigned) Off - [Trigger ID126] (Not assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not assigned) Off - [Trigger ID127] (Not assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not assigned) Off - [Trigger ID128] (Not assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not assigned) Off - [Trigger ID129] (Not assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not assigned) Off - [Trigger ID130] (Not assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not assigned) Off - [Trigger ID131] (Not assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not assigned) Off - [Trigger ID132] (Not assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not assigned) Off - [Trigger ID134] (Not assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not assigned) Off - [Trigger ID135] (Not assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not assigned) Off - [Trigger ID136] (Not assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not assigned) Off - [Trigger ID137] (Not assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not assigned) Off - [Trigger ID138] (Not assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not assigned) Off - [Trigger ID139] (Not assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not assigned) Off - [Trigger ID140] (Not assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not assigned) Off - [Trigger ID141] (Not assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not assigned) Off - [Trigger ID142] (Not assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not assigned) Off - [Trigger ID143] (Not assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] 48A0018300001B76 On-Off CB1_CLOSE [Trigger ID144] (Not assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not assigned) Off - [Trigger ID145] (Not assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not assigned) Off - [Trigger ID146] (Not assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not assigned) Off - [Trigger ID147] (Not assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] 48A0018300001B7F On-Off CB2_CLOSE [Trigger ID148] (Not assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] (Not assigned) Off - [Trigger ID149] (Not assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] 48A0018000001B9C On-Off DEAD_LINE_DETECT [Trigger ID150] (Not assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not assigned) Off - [Trigger ID151] (Not assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not assigned) Off - [Trigger ID152] (Not assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not assigned) Off - [Trigger ID153] (Not assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not assigned) Off - [Trigger ID154] (Not assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not assigned) Off - [Trigger ID155] (Not assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not assigned) Off - [Trigger ID156] (Not assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not assigned) Off - [Trigger ID157] (Not assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not assigned) Off - [Trigger ID158] (Not assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not assigned) Off - [Trigger ID159] (Not assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not assigned) Off - [Trigger ID160] (Not assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] (Not assigned) Off - [Trigger ID161] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] (Not assigned) Off - [Trigger ID162] (Not assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] (Not assigned) Off - [Trigger ID163] (Not assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] (Not assigned) Off - [Trigger ID164] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] (Not assigned) Off - [Trigger ID165] (Not assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not assigned) Off - [Trigger ID166] (Not assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not assigned) Off - [Trigger ID167] (Not assigned) Off -
[Trigger ID78] (Not assigned) Off - [Trigger ID168] (Not assigned) Off -
[Trigger ID79] (Not assigned) Off - [Trigger ID169] (Not assigned) Off -
[Trigger ID80] (Not assigned) Off - [Trigger ID170] (Not assigned) Off -
[Trigger ID81] 4A00018000001B6C On-Off GEN.TRIP-A [Trigger ID171] (Not assigned) Off -
[Trigger ID82] 4A00018100001B6D On-Off GEN.TRIP-B [Trigger ID172] (Not assigned) Off -
[Trigger ID83] 4A00018200001B6E On-Off GEN.TRIP-C [Trigger ID173] (Not assigned) Off -
[Trigger ID84] 4A00018300001B6F On-Off GEN.TRIP [Trigger ID174] (Not assigned) Off -
[Trigger ID85] 4A00018400001B64 On-Off GEN.ALARM [Trigger ID175] (Not assigned) Off -
[Trigger ID86] 4A00018000001B71 On-Off OPT.PHASE-A [Trigger ID176] (Not assigned) Off -
[Trigger ID87] 4A00018100001B72 On-Off OPT.PHASE-B [Trigger ID177] (Not assigned) Off -
[Trigger ID88] 4A00018200001B73 On-Off OPT.PHASE-C [Trigger ID178] (Not assigned) Off -
[Trigger ID89] 4A00018300001B74 On-Off OPT.PHASE-N [Trigger ID179] (Not assigned) Off -
[Trigger ID90] (Not assigned) Off - [Trigger ID180] (Not assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1027 -
6F2S1927 (0.18)
[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1028 -
6F2S1927 (0.18)
[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1029 -
6F2S1927 (0.18)
[Trigger ID1] 2200013110201001 On-Off Serious error [Trigger ID91] (Not assigned) Off - [Trigger ID181] (Not Assigned) Off -
[Trigger ID2] 2200013110211001 On-Off ErrorLevel2 [Trigger ID92] (Not assigned) Off - [Trigger ID182] (Not Assigned) Off -
[Trigger ID3] 2200013110221001 On-Off Minor error [Trigger ID93] (Not assigned) Off - [Trigger ID183] (Not Assigned) Off -
[Trigger ID4] 2200013110231001 On-Off ErrorLevel4 [Trigger ID94] (Not assigned) Off - [Trigger ID184] (Not Assigned) Off -
[Trigger ID5] 2200013110241001 On-Off ErrorLevel5 [Trigger ID95] (Not assigned) Off - [Trigger ID185] (Not Assigned) Off -
[Trigger ID6] (Not assigned) Off - [Trigger ID96] (Not assigned) Off - [Trigger ID186] (Not Assigned) Off -
[Trigger ID7] 2014003200001001 Change Set. group change [Trigger ID97] 4A60018500011B6F On-Off CB1_94TT [Trigger ID187] (Not Assigned) Off -
[Trigger ID8] 2014003010001001 On System set. change [Trigger ID98] 4A60018500021B6B On-Off CB2_94TT [Trigger ID188] (Not Assigned) Off -
[Trigger ID9] 2014003010011001 On Comm. set. change [Trigger ID99] 4A60018800011B62 On-Off CB1_BRIDGE [Trigger ID189] (Not Assigned) Off -
[Trigger ID10] 2014003010021001 On Prot. set. change [Trigger ID100] 4A60018800021B62 On-Off CB2_BRIDGE [Trigger ID190] (Not Assigned) Off -
[Trigger ID11] (Not assigned) Off - [Trigger ID101] 4A60018000011B60 On-Off ARC1 READY [Trigger ID191] (Not Assigned) Off -
[Trigger ID12] (Not assigned) Off - [Trigger ID102] 4A60018000021B60 On-Off ARC2 READY [Trigger ID192] (Not Assigned) Off -
[Trigger ID13] (Not assigned) Off - [Trigger ID103] 4A60018200001BB4 On-Off ARC_BLOCK [Trigger ID193] (Not Assigned) Off -
[Trigger ID14] 2006023000001001 On F.Record clear [Trigger ID104] 4A60018000001BB3 On-Off ARC NO ACT [Trigger ID194] (Not Assigned) Off -
[Trigger ID15] 2007103001001001 On E.Record1 clear [Trigger ID105] 4A60018000001BB0 On-Off START-A [Trigger ID195] (Not Assigned) Off -
[Trigger ID16] 2007103002001001 On E.Record2 clear [Trigger ID106] 4A60018100001BB1 On-Off START-B [Trigger ID196] (Not Assigned) Off -
[Trigger ID17] 2007103003001001 On E.Record3 clear [Trigger ID107] 4A60018200001BB2 On-Off START-C [Trigger ID197] (Not Assigned) Off -
[Trigger ID18] 20040130A0001001 On D.Record clear [Trigger ID108] 4A60018000011B6C On-Off ARC1 CLOSE COMMAND [Trigger ID198] (Not Assigned) Off -
[Trigger ID19] (Not assigned) Off - [Trigger ID109] 4A60018100021B68 On-Off ARC2 CLOSE COMMAND [Trigger ID199] (Not Assigned) Off -
[Trigger ID20] (Not assigned) Off - [Trigger ID110] (Not assigned) Off - [Trigger ID200] (Not Assigned) Off -
[Trigger ID21] (Not assigned) Off - [Trigger ID111] (Not assigned) Off - [Trigger ID201] (Not Assigned) Off -
[Trigger ID22] (Not assigned) Off - [Trigger ID112] (Not assigned) Off - [Trigger ID202] (Not Assigned) Off -
[Trigger ID23] (Not assigned) Off - [Trigger ID113] (Not assigned) Off - [Trigger ID203] (Not Assigned) Off -
[Trigger ID24] (Not assigned) Off - [Trigger ID114] (Not assigned) Off - [Trigger ID204] (Not Assigned) Off -
[Trigger ID25] (Not assigned) Off - [Trigger ID115] (Not assigned) Off - [Trigger ID205] (Not Assigned) Off -
[Trigger ID26] (Not assigned) Off - [Trigger ID116] (Not assigned) Off - [Trigger ID206] (Not Assigned) Off -
[Trigger ID27] (Not assigned) Off - [Trigger ID117] 4A60018200011B61 On-Off ARC1 IN-PROG [Trigger ID207] (Not Assigned) Off -
[Trigger ID28] (Not assigned) Off - [Trigger ID118] 4A60018200021B61 On-Off ARC2 IN-PROG [Trigger ID208] (Not Assigned) Off -
[Trigger ID29] (Not assigned) Off - [Trigger ID119] (Not assigned) Off - [Trigger ID209] (Not Assigned) Off -
[Trigger ID30] (Not assigned) Off - [Trigger ID120] (Not assigned) Off - [Trigger ID210] (Not Assigned) Off -
[Trigger ID31] (Not assigned) Off - [Trigger ID121] (Not assigned) Off - [Trigger ID211] (Not Assigned) Off -
[Trigger ID32] (Not assigned) Off - [Trigger ID122] (Not assigned) Off - [Trigger ID212] (Not Assigned) Off -
[Trigger ID33] (Not assigned) Off - [Trigger ID123] (Not assigned) Off - [Trigger ID213] (Not Assigned) Off -
[Trigger ID34] (Not assigned) Off - [Trigger ID124] (Not assigned) Off - [Trigger ID214] (Not Assigned) Off -
[Trigger ID35] (Not assigned) Off - [Trigger ID125] (Not assigned) Off - [Trigger ID215] (Not Assigned) Off -
[Trigger ID36] (Not assigned) Off - [Trigger ID126] (Not assigned) Off - [Trigger ID216] (Not Assigned) Off -
[Trigger ID37] (Not assigned) Off - [Trigger ID127] (Not assigned) Off - [Trigger ID217] (Not Assigned) Off -
[Trigger ID38] (Not assigned) Off - [Trigger ID128] (Not assigned) Off - [Trigger ID218] (Not Assigned) Off -
[Trigger ID39] (Not assigned) Off - [Trigger ID129] (Not assigned) Off - [Trigger ID219] (Not Assigned) Off -
[Trigger ID40] (Not assigned) Off - [Trigger ID130] (Not assigned) Off - [Trigger ID220] (Not Assigned) Off -
[Trigger ID41] (Not assigned) Off - [Trigger ID131] (Not assigned) Off - [Trigger ID221] (Not Assigned) Off -
[Trigger ID42] (Not assigned) Off - [Trigger ID132] (Not assigned) Off - [Trigger ID222] (Not Assigned) Off -
[Trigger ID43] (Not assigned) Off - [Trigger ID133] (Not assigned) Off - [Trigger ID223] (Not Assigned) Off -
[Trigger ID44] (Not assigned) Off - [Trigger ID134] (Not assigned) Off - [Trigger ID224] (Not Assigned) Off -
[Trigger ID45] (Not assigned) Off - [Trigger ID135] (Not assigned) Off - [Trigger ID225] (Not Assigned) Off -
[Trigger ID46] (Not assigned) Off - [Trigger ID136] (Not assigned) Off - [Trigger ID226] (Not Assigned) Off -
[Trigger ID47] (Not assigned) Off - [Trigger ID137] (Not assigned) Off - [Trigger ID227] (Not Assigned) Off -
[Trigger ID48] (Not assigned) Off - [Trigger ID138] (Not assigned) Off - [Trigger ID228] (Not Assigned) Off -
[Trigger ID49] (Not assigned) Off - [Trigger ID139] (Not assigned) Off - [Trigger ID229] (Not Assigned) Off -
[Trigger ID50] (Not assigned) Off - [Trigger ID140] (Not assigned) Off - [Trigger ID230] (Not Assigned) Off -
[Trigger ID51] (Not assigned) Off - [Trigger ID141] (Not assigned) Off - [Trigger ID231] (Not Assigned) Off -
[Trigger ID52] (Not assigned) Off - [Trigger ID142] (Not assigned) Off - [Trigger ID232] (Not Assigned) Off -
[Trigger ID53] (Not assigned) Off - [Trigger ID143] (Not assigned) Off - [Trigger ID233] (Not Assigned) Off -
[Trigger ID54] (Not assigned) Off - [Trigger ID144] (Not assigned) Off - [Trigger ID234] (Not Assigned) Off -
[Trigger ID55] (Not assigned) Off - [Trigger ID145] (Not assigned) Off - [Trigger ID235] (Not Assigned) Off -
[Trigger ID56] (Not assigned) Off - [Trigger ID146] (Not assigned) Off - [Trigger ID236] (Not Assigned) Off -
[Trigger ID57] (Not assigned) Off - [Trigger ID147] (Not assigned) Off - [Trigger ID237] (Not Assigned) Off -
[Trigger ID58] (Not assigned) Off - [Trigger ID148] (Not assigned) Off - [Trigger ID238] (Not Assigned) Off -
[Trigger ID59] (Not assigned) Off - [Trigger ID149] (Not assigned) Off - [Trigger ID239] (Not Assigned) Off -
[Trigger ID60] (Not assigned) Off - [Trigger ID150] (Not assigned) Off - [Trigger ID240] (Not Assigned) Off -
[Trigger ID61] (Not assigned) Off - [Trigger ID151] (Not assigned) Off - [Trigger ID241] (Not Assigned) Off -
[Trigger ID62] (Not assigned) Off - [Trigger ID152] (Not assigned) Off - [Trigger ID242] (Not Assigned) Off -
[Trigger ID63] (Not assigned) Off - [Trigger ID153] (Not assigned) Off - [Trigger ID243] (Not Assigned) Off -
[Trigger ID64] (Not assigned) Off - [Trigger ID154] (Not assigned) Off - [Trigger ID244] (Not Assigned) Off -
[Trigger ID65] (Not assigned) Off - [Trigger ID155] (Not assigned) Off - [Trigger ID245] (Not Assigned) Off -
[Trigger ID66] (Not assigned) Off - [Trigger ID156] (Not assigned) Off - [Trigger ID246] (Not Assigned) Off -
[Trigger ID67] (Not assigned) Off - [Trigger ID157] (Not assigned) Off - [Trigger ID247] (Not Assigned) Off -
[Trigger ID68] (Not assigned) Off - [Trigger ID158] (Not assigned) Off - [Trigger ID248] (Not Assigned) Off -
[Trigger ID69] (Not assigned) Off - [Trigger ID159] (Not assigned) Off - [Trigger ID249] (Not Assigned) Off -
[Trigger ID70] (Not assigned) Off - [Trigger ID160] (Not assigned) Off - [Trigger ID250] (Not Assigned) Off -
[Trigger ID71] (Not assigned) Off - [Trigger ID161] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID72] (Not assigned) Off - [Trigger ID162] (Not assigned) Off - [Trigger ID252] (Not Assigned) Off -
[Trigger ID73] (Not assigned) Off - [Trigger ID163] (Not assigned) Off - [Trigger ID253] (Not Assigned) Off -
[Trigger ID74] (Not assigned) Off - [Trigger ID164] (Not assigned) Off - [Trigger ID254] (Not Assigned) Off -
[Trigger ID75] (Not assigned) Off - [Trigger ID165] (Not assigned) Off - [Trigger ID255] (Not Assigned) Off -
[Trigger ID76] (Not assigned) Off - [Trigger ID166] (Not assigned) Off - [Trigger ID256] (Not Assigned) Off -
[Trigger ID77] (Not assigned) Off - [Trigger ID167] (Not assigned) Off -
[Trigger ID78] (Not assigned) Off - [Trigger ID168] (Not assigned) Off -
[Trigger ID79] (Not assigned) Off - [Trigger ID169] (Not assigned) Off -
[Trigger ID80] (Not assigned) Off - [Trigger ID170] (Not assigned) Off -
[Trigger ID81] (Not assigned) Off - [Trigger ID171] (Not assigned) Off -
[Trigger ID82] (Not assigned) Off - [Trigger ID172] (Not assigned) Off -
[Trigger ID83] (Not assigned) Off - [Trigger ID173] (Not assigned) Off -
[Trigger ID84] (Not assigned) Off - [Trigger ID174] (Not assigned) Off -
[Trigger ID85] (Not assigned) Off - [Trigger ID175] (Not assigned) Off -
[Trigger ID86] (Not assigned) Off - [Trigger ID176] (Not assigned) Off -
[Trigger ID87] (Not assigned) Off - [Trigger ID177] (Not assigned) Off -
[Trigger ID88] (Not assigned) Off - [Trigger ID178] (Not assigned) Off -
[Trigger ID89] (Not assigned) Off - [Trigger ID179] (Not assigned) Off -
[Trigger ID90] (Not assigned) Off - [Trigger ID180] (Not assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1030 -
6F2S1927 (0.18)
[Trigger ID257] (Not Assigned) Off - [Trigger ID347] (Not Assigned) Off - [Trigger ID437] (Not Assigned) Off -
[Trigger ID258] (Not Assigned) Off - [Trigger ID348] (Not Assigned) Off - [Trigger ID438] (Not Assigned) Off -
[Trigger ID259] (Not Assigned) Off - [Trigger ID349] (Not Assigned) Off - [Trigger ID439] (Not Assigned) Off -
[Trigger ID260] (Not Assigned) Off - [Trigger ID350] (Not Assigned) Off - [Trigger ID440] (Not Assigned) Off -
[Trigger ID261] (Not Assigned) Off - [Trigger ID351] (Not Assigned) Off - [Trigger ID441] (Not Assigned) Off -
[Trigger ID262] (Not Assigned) Off - [Trigger ID352] (Not Assigned) Off - [Trigger ID442] (Not Assigned) Off -
[Trigger ID263] (Not Assigned) Off - [Trigger ID353] (Not Assigned) Off - [Trigger ID443] (Not Assigned) Off -
[Trigger ID264] (Not Assigned) Off - [Trigger ID354] (Not Assigned) Off - [Trigger ID444] (Not Assigned) Off -
[Trigger ID265] (Not Assigned) Off - [Trigger ID355] (Not Assigned) Off - [Trigger ID445] (Not Assigned) Off -
[Trigger ID266] (Not Assigned) Off - [Trigger ID356] (Not Assigned) Off - [Trigger ID446] (Not Assigned) Off -
[Trigger ID267] (Not Assigned) Off - [Trigger ID357] (Not Assigned) Off - [Trigger ID447] (Not Assigned) Off -
[Trigger ID268] (Not Assigned) Off - [Trigger ID358] (Not Assigned) Off - [Trigger ID448] (Not Assigned) Off -
[Trigger ID269] (Not Assigned) Off - [Trigger ID359] (Not Assigned) Off - [Trigger ID449] (Not Assigned) Off -
[Trigger ID270] (Not Assigned) Off - [Trigger ID360] (Not Assigned) Off - [Trigger ID450] (Not Assigned) Off -
[Trigger ID271] (Not Assigned) Off - [Trigger ID361] (Not Assigned) Off - [Trigger ID451] (Not Assigned) Off -
[Trigger ID272] (Not Assigned) Off - [Trigger ID362] (Not Assigned) Off - [Trigger ID452] (Not Assigned) Off -
[Trigger ID273] (Not Assigned) Off - [Trigger ID363] (Not Assigned) Off - [Trigger ID453] (Not Assigned) Off -
[Trigger ID274] (Not Assigned) Off - [Trigger ID364] (Not Assigned) Off - [Trigger ID454] (Not Assigned) Off -
[Trigger ID275] (Not Assigned) Off - [Trigger ID365] (Not Assigned) Off - [Trigger ID455] (Not Assigned) Off -
[Trigger ID276] (Not Assigned) Off - [Trigger ID366] (Not Assigned) Off - [Trigger ID456] (Not Assigned) Off -
[Trigger ID277] (Not Assigned) Off - [Trigger ID367] (Not Assigned) Off - [Trigger ID457] (Not Assigned) Off -
[Trigger ID278] (Not Assigned) Off - [Trigger ID368] (Not Assigned) Off - [Trigger ID458] (Not Assigned) Off -
[Trigger ID279] (Not Assigned) Off - [Trigger ID369] (Not Assigned) Off - [Trigger ID459] (Not Assigned) Off -
[Trigger ID280] (Not Assigned) Off - [Trigger ID370] (Not Assigned) Off - [Trigger ID460] (Not Assigned) Off -
[Trigger ID281] (Not Assigned) Off - [Trigger ID371] (Not Assigned) Off - [Trigger ID461] (Not Assigned) Off -
[Trigger ID282] (Not Assigned) Off - [Trigger ID372] (Not Assigned) Off - [Trigger ID462] (Not Assigned) Off -
[Trigger ID283] (Not Assigned) Off - [Trigger ID373] (Not Assigned) Off - [Trigger ID463] (Not Assigned) Off -
[Trigger ID284] (Not Assigned) Off - [Trigger ID374] (Not Assigned) Off - [Trigger ID464] (Not Assigned) Off -
[Trigger ID285] (Not Assigned) Off - [Trigger ID375] (Not Assigned) Off - [Trigger ID465] (Not Assigned) Off -
[Trigger ID286] (Not Assigned) Off - [Trigger ID376] (Not Assigned) Off - [Trigger ID466] (Not Assigned) Off -
[Trigger ID287] (Not Assigned) Off - [Trigger ID377] (Not Assigned) Off - [Trigger ID467] (Not Assigned) Off -
[Trigger ID288] (Not Assigned) Off - [Trigger ID378] (Not Assigned) Off - [Trigger ID468] (Not Assigned) Off -
[Trigger ID289] (Not Assigned) Off - [Trigger ID379] (Not Assigned) Off - [Trigger ID469] (Not Assigned) Off -
[Trigger ID290] (Not Assigned) Off - [Trigger ID380] (Not Assigned) Off - [Trigger ID470] (Not Assigned) Off -
[Trigger ID291] (Not Assigned) Off - [Trigger ID381] (Not Assigned) Off - [Trigger ID471] (Not Assigned) Off -
[Trigger ID292] (Not Assigned) Off - [Trigger ID382] (Not Assigned) Off - [Trigger ID472] (Not Assigned) Off -
[Trigger ID293] (Not Assigned) Off - [Trigger ID383] (Not Assigned) Off - [Trigger ID473] (Not Assigned) Off -
[Trigger ID294] (Not Assigned) Off - [Trigger ID384] (Not Assigned) Off - [Trigger ID474] (Not Assigned) Off -
[Trigger ID295] (Not Assigned) Off - [Trigger ID385] (Not Assigned) Off - [Trigger ID475] (Not Assigned) Off -
[Trigger ID296] (Not Assigned) Off - [Trigger ID386] (Not Assigned) Off - [Trigger ID476] (Not Assigned) Off -
[Trigger ID297] (Not Assigned) Off - [Trigger ID387] (Not Assigned) Off - [Trigger ID477] (Not Assigned) Off -
[Trigger ID298] (Not Assigned) Off - [Trigger ID388] (Not Assigned) Off - [Trigger ID478] (Not Assigned) Off -
[Trigger ID299] (Not Assigned) Off - [Trigger ID389] (Not Assigned) Off - [Trigger ID479] (Not Assigned) Off -
[Trigger ID300] (Not Assigned) Off - [Trigger ID390] (Not Assigned) Off - [Trigger ID480] (Not Assigned) Off -
[Trigger ID301] (Not Assigned) Off - [Trigger ID391] (Not Assigned) Off - [Trigger ID481] (Not Assigned) Off -
[Trigger ID302] (Not Assigned) Off - [Trigger ID392] (Not Assigned) Off - [Trigger ID482] (Not Assigned) Off -
[Trigger ID303] (Not Assigned) Off - [Trigger ID393] (Not Assigned) Off - [Trigger ID483] (Not Assigned) Off -
[Trigger ID304] (Not Assigned) Off - [Trigger ID394] (Not Assigned) Off - [Trigger ID484] (Not Assigned) Off -
[Trigger ID305] (Not Assigned) Off - [Trigger ID395] (Not Assigned) Off - [Trigger ID485] (Not Assigned) Off -
[Trigger ID306] (Not Assigned) Off - [Trigger ID396] (Not Assigned) Off - [Trigger ID486] (Not Assigned) Off -
[Trigger ID307] (Not Assigned) Off - [Trigger ID397] (Not Assigned) Off - [Trigger ID487] (Not Assigned) Off -
[Trigger ID308] (Not Assigned) Off - [Trigger ID398] (Not Assigned) Off - [Trigger ID488] (Not Assigned) Off -
[Trigger ID309] (Not Assigned) Off - [Trigger ID399] (Not Assigned) Off - [Trigger ID489] (Not Assigned) Off -
[Trigger ID310] (Not Assigned) Off - [Trigger ID400] (Not Assigned) Off - [Trigger ID490] (Not Assigned) Off -
[Trigger ID311] (Not Assigned) Off - [Trigger ID401] (Not Assigned) Off - [Trigger ID491] (Not Assigned) Off -
[Trigger ID312] (Not Assigned) Off - [Trigger ID402] (Not Assigned) Off - [Trigger ID492] (Not Assigned) Off -
[Trigger ID313] (Not Assigned) Off - [Trigger ID403] (Not Assigned) Off - [Trigger ID493] (Not Assigned) Off -
[Trigger ID314] (Not Assigned) Off - [Trigger ID404] (Not Assigned) Off - [Trigger ID494] (Not Assigned) Off -
[Trigger ID315] (Not Assigned) Off - [Trigger ID405] (Not Assigned) Off - [Trigger ID495] (Not Assigned) Off -
[Trigger ID316] (Not Assigned) Off - [Trigger ID406] (Not Assigned) Off - [Trigger ID496] (Not Assigned) Off -
[Trigger ID317] (Not Assigned) Off - [Trigger ID407] (Not Assigned) Off - [Trigger ID497] (Not Assigned) Off -
[Trigger ID318] (Not Assigned) Off - [Trigger ID408] (Not Assigned) Off - [Trigger ID498] (Not Assigned) Off -
[Trigger ID319] (Not Assigned) Off - [Trigger ID409] (Not Assigned) Off - [Trigger ID499] (Not Assigned) Off -
[Trigger ID320] (Not Assigned) Off - [Trigger ID410] (Not Assigned) Off - [Trigger ID500] (Not Assigned) Off -
[Trigger ID321] (Not Assigned) Off - [Trigger ID411] (Not Assigned) Off - [Trigger ID501] (Not Assigned) Off -
[Trigger ID322] (Not Assigned) Off - [Trigger ID412] (Not Assigned) Off - [Trigger ID502] (Not Assigned) Off -
[Trigger ID323] (Not Assigned) Off - [Trigger ID413] (Not Assigned) Off - [Trigger ID503] (Not Assigned) Off -
[Trigger ID324] (Not Assigned) Off - [Trigger ID414] (Not Assigned) Off - [Trigger ID504] (Not Assigned) Off -
[Trigger ID325] (Not Assigned) Off - [Trigger ID415] (Not Assigned) Off - [Trigger ID505] (Not Assigned) Off -
[Trigger ID326] (Not Assigned) Off - [Trigger ID416] (Not Assigned) Off - [Trigger ID506] (Not Assigned) Off -
[Trigger ID327] (Not Assigned) Off - [Trigger ID417] (Not Assigned) Off - [Trigger ID507] (Not Assigned) Off -
[Trigger ID328] (Not Assigned) Off - [Trigger ID418] (Not Assigned) Off - [Trigger ID508] (Not Assigned) Off -
[Trigger ID329] (Not Assigned) Off - [Trigger ID419] (Not Assigned) Off - [Trigger ID509] (Not Assigned) Off -
[Trigger ID330] (Not Assigned) Off - [Trigger ID420] (Not Assigned) Off - [Trigger ID510] (Not Assigned) Off -
[Trigger ID331] (Not Assigned) Off - [Trigger ID421] (Not Assigned) Off - [Trigger ID511] (Not Assigned) Off -
[Trigger ID332] (Not Assigned) Off - [Trigger ID422] (Not Assigned) Off - [Trigger ID512] (Not Assigned) Off -
[Trigger ID333] (Not Assigned) Off - [Trigger ID423] (Not Assigned) Off -
[Trigger ID334] (Not Assigned) Off - [Trigger ID424] (Not Assigned) Off -
[Trigger ID335] (Not Assigned) Off - [Trigger ID425] (Not Assigned) Off -
[Trigger ID336] (Not Assigned) Off - [Trigger ID426] (Not Assigned) Off -
[Trigger ID337] (Not Assigned) Off - [Trigger ID427] (Not Assigned) Off -
[Trigger ID338] (Not Assigned) Off - [Trigger ID428] (Not Assigned) Off -
[Trigger ID339] (Not Assigned) Off - [Trigger ID429] (Not Assigned) Off -
[Trigger ID340] (Not Assigned) Off - [Trigger ID430] (Not Assigned) Off -
[Trigger ID341] (Not Assigned) Off - [Trigger ID431] (Not Assigned) Off -
[Trigger ID342] (Not Assigned) Off - [Trigger ID432] (Not Assigned) Off -
[Trigger ID343] (Not Assigned) Off - [Trigger ID433] (Not Assigned) Off -
[Trigger ID344] (Not Assigned) Off - [Trigger ID434] (Not Assigned) Off -
[Trigger ID345] (Not Assigned) Off - [Trigger ID435] (Not Assigned) Off -
[Trigger ID346] (Not Assigned) Off - [Trigger ID436] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1031 -
6F2S1927 (0.18)
[Trigger ID513] (Not Assigned) Off - [Trigger ID603] (Not Assigned) Off - [Trigger ID693] (Not Assigned) Off -
[Trigger ID514] (Not Assigned) Off - [Trigger ID604] (Not Assigned) Off - [Trigger ID694] (Not Assigned) Off -
[Trigger ID515] (Not Assigned) Off - [Trigger ID605] (Not Assigned) Off - [Trigger ID695] (Not Assigned) Off -
[Trigger ID516] (Not Assigned) Off - [Trigger ID606] (Not Assigned) Off - [Trigger ID696] (Not Assigned) Off -
[Trigger ID517] (Not Assigned) Off - [Trigger ID607] (Not Assigned) Off - [Trigger ID697] (Not Assigned) Off -
[Trigger ID518] (Not Assigned) Off - [Trigger ID608] (Not Assigned) Off - [Trigger ID698] (Not Assigned) Off -
[Trigger ID519] (Not Assigned) Off - [Trigger ID609] (Not Assigned) Off - [Trigger ID699] (Not Assigned) Off -
[Trigger ID520] (Not Assigned) Off - [Trigger ID610] (Not Assigned) Off - [Trigger ID700] (Not Assigned) Off -
[Trigger ID521] (Not Assigned) Off - [Trigger ID611] (Not Assigned) Off - [Trigger ID701] (Not Assigned) Off -
[Trigger ID522] (Not Assigned) Off - [Trigger ID612] (Not Assigned) Off - [Trigger ID702] (Not Assigned) Off -
[Trigger ID523] (Not Assigned) Off - [Trigger ID613] (Not Assigned) Off - [Trigger ID703] (Not Assigned) Off -
[Trigger ID524] (Not Assigned) Off - [Trigger ID614] (Not Assigned) Off - [Trigger ID704] (Not Assigned) Off -
[Trigger ID525] (Not Assigned) Off - [Trigger ID615] (Not Assigned) Off - [Trigger ID705] (Not Assigned) Off -
[Trigger ID526] (Not Assigned) Off - [Trigger ID616] (Not Assigned) Off - [Trigger ID706] (Not Assigned) Off -
[Trigger ID527] (Not Assigned) Off - [Trigger ID617] (Not Assigned) Off - [Trigger ID707] (Not Assigned) Off -
[Trigger ID528] (Not Assigned) Off - [Trigger ID618] (Not Assigned) Off - [Trigger ID708] (Not Assigned) Off -
[Trigger ID529] (Not Assigned) Off - [Trigger ID619] (Not Assigned) Off - [Trigger ID709] (Not Assigned) Off -
[Trigger ID530] (Not Assigned) Off - [Trigger ID620] (Not Assigned) Off - [Trigger ID710] (Not Assigned) Off -
[Trigger ID531] (Not Assigned) Off - [Trigger ID621] (Not Assigned) Off - [Trigger ID711] (Not Assigned) Off -
[Trigger ID532] (Not Assigned) Off - [Trigger ID622] (Not Assigned) Off - [Trigger ID712] (Not Assigned) Off -
[Trigger ID533] (Not Assigned) Off - [Trigger ID623] (Not Assigned) Off - [Trigger ID713] (Not Assigned) Off -
[Trigger ID534] (Not Assigned) Off - [Trigger ID624] (Not Assigned) Off - [Trigger ID714] (Not Assigned) Off -
[Trigger ID535] (Not Assigned) Off - [Trigger ID625] (Not Assigned) Off - [Trigger ID715] (Not Assigned) Off -
[Trigger ID536] (Not Assigned) Off - [Trigger ID626] (Not Assigned) Off - [Trigger ID716] (Not Assigned) Off -
[Trigger ID537] (Not Assigned) Off - [Trigger ID627] (Not Assigned) Off - [Trigger ID717] (Not Assigned) Off -
[Trigger ID538] (Not Assigned) Off - [Trigger ID628] (Not Assigned) Off - [Trigger ID718] (Not Assigned) Off -
[Trigger ID539] (Not Assigned) Off - [Trigger ID629] (Not Assigned) Off - [Trigger ID719] (Not Assigned) Off -
[Trigger ID540] (Not Assigned) Off - [Trigger ID630] (Not Assigned) Off - [Trigger ID720] (Not Assigned) Off -
[Trigger ID541] (Not Assigned) Off - [Trigger ID631] (Not Assigned) Off - [Trigger ID721] (Not Assigned) Off -
[Trigger ID542] (Not Assigned) Off - [Trigger ID632] (Not Assigned) Off - [Trigger ID722] (Not Assigned) Off -
[Trigger ID543] (Not Assigned) Off - [Trigger ID633] (Not Assigned) Off - [Trigger ID723] (Not Assigned) Off -
[Trigger ID544] (Not Assigned) Off - [Trigger ID634] (Not Assigned) Off - [Trigger ID724] (Not Assigned) Off -
[Trigger ID545] (Not Assigned) Off - [Trigger ID635] (Not Assigned) Off - [Trigger ID725] (Not Assigned) Off -
[Trigger ID546] (Not Assigned) Off - [Trigger ID636] (Not Assigned) Off - [Trigger ID726] (Not Assigned) Off -
[Trigger ID547] (Not Assigned) Off - [Trigger ID637] (Not Assigned) Off - [Trigger ID727] (Not Assigned) Off -
[Trigger ID548] (Not Assigned) Off - [Trigger ID638] (Not Assigned) Off - [Trigger ID728] (Not Assigned) Off -
[Trigger ID549] (Not Assigned) Off - [Trigger ID639] (Not Assigned) Off - [Trigger ID729] (Not Assigned) Off -
[Trigger ID550] (Not Assigned) Off - [Trigger ID640] (Not Assigned) Off - [Trigger ID730] (Not Assigned) Off -
[Trigger ID551] (Not Assigned) Off - [Trigger ID641] (Not Assigned) Off - [Trigger ID731] (Not Assigned) Off -
[Trigger ID552] (Not Assigned) Off - [Trigger ID642] (Not Assigned) Off - [Trigger ID732] (Not Assigned) Off -
[Trigger ID553] (Not Assigned) Off - [Trigger ID643] (Not Assigned) Off - [Trigger ID733] (Not Assigned) Off -
[Trigger ID554] (Not Assigned) Off - [Trigger ID644] (Not Assigned) Off - [Trigger ID734] (Not Assigned) Off -
[Trigger ID555] (Not Assigned) Off - [Trigger ID645] (Not Assigned) Off - [Trigger ID735] (Not Assigned) Off -
[Trigger ID556] (Not Assigned) Off - [Trigger ID646] (Not Assigned) Off - [Trigger ID736] (Not Assigned) Off -
[Trigger ID557] (Not Assigned) Off - [Trigger ID647] (Not Assigned) Off - [Trigger ID737] (Not Assigned) Off -
[Trigger ID558] (Not Assigned) Off - [Trigger ID648] (Not Assigned) Off - [Trigger ID738] (Not Assigned) Off -
[Trigger ID559] (Not Assigned) Off - [Trigger ID649] (Not Assigned) Off - [Trigger ID739] (Not Assigned) Off -
[Trigger ID560] (Not Assigned) Off - [Trigger ID650] (Not Assigned) Off - [Trigger ID740] (Not Assigned) Off -
[Trigger ID561] (Not Assigned) Off - [Trigger ID651] (Not Assigned) Off - [Trigger ID741] (Not Assigned) Off -
[Trigger ID562] (Not Assigned) Off - [Trigger ID652] (Not Assigned) Off - [Trigger ID742] (Not Assigned) Off -
[Trigger ID563] (Not Assigned) Off - [Trigger ID653] (Not Assigned) Off - [Trigger ID743] (Not Assigned) Off -
[Trigger ID564] (Not Assigned) Off - [Trigger ID654] (Not Assigned) Off - [Trigger ID744] (Not Assigned) Off -
[Trigger ID565] (Not Assigned) Off - [Trigger ID655] (Not Assigned) Off - [Trigger ID745] (Not Assigned) Off -
[Trigger ID566] (Not Assigned) Off - [Trigger ID656] (Not Assigned) Off - [Trigger ID746] (Not Assigned) Off -
[Trigger ID567] (Not Assigned) Off - [Trigger ID657] (Not Assigned) Off - [Trigger ID747] (Not Assigned) Off -
[Trigger ID568] (Not Assigned) Off - [Trigger ID658] (Not Assigned) Off - [Trigger ID748] (Not Assigned) Off -
[Trigger ID569] (Not Assigned) Off - [Trigger ID659] (Not Assigned) Off - [Trigger ID749] (Not Assigned) Off -
[Trigger ID570] (Not Assigned) Off - [Trigger ID660] (Not Assigned) Off - [Trigger ID760] (Not Assigned) Off -
[Trigger ID571] (Not Assigned) Off - [Trigger ID661] (Not Assigned) Off - [Trigger ID761] (Not Assigned) Off -
[Trigger ID572] (Not Assigned) Off - [Trigger ID662] (Not Assigned) Off - [Trigger ID762] (Not Assigned) Off -
[Trigger ID573] (Not Assigned) Off - [Trigger ID663] (Not Assigned) Off - [Trigger ID763] (Not Assigned) Off -
[Trigger ID574] (Not Assigned) Off - [Trigger ID664] (Not Assigned) Off - [Trigger ID764] (Not Assigned) Off -
[Trigger ID575] (Not Assigned) Off - [Trigger ID665] (Not Assigned) Off - [Trigger ID765] (Not Assigned) Off -
[Trigger ID576] (Not Assigned) Off - [Trigger ID666] (Not Assigned) Off - [Trigger ID766] (Not Assigned) Off -
[Trigger ID577] (Not Assigned) Off - [Trigger ID667] (Not Assigned) Off - [Trigger ID767] (Not Assigned) Off -
[Trigger ID578] (Not Assigned) Off - [Trigger ID668] (Not Assigned) Off - [Trigger ID768] (Not Assigned) Off -
[Trigger ID579] (Not Assigned) Off - [Trigger ID669] (Not Assigned) Off -
[Trigger ID580] (Not Assigned) Off - [Trigger ID670] (Not Assigned) Off -
[Trigger ID581] (Not Assigned) Off - [Trigger ID671] (Not Assigned) Off -
[Trigger ID582] (Not Assigned) Off - [Trigger ID672] (Not Assigned) Off -
[Trigger ID583] (Not Assigned) Off - [Trigger ID673] (Not Assigned) Off -
[Trigger ID584] (Not Assigned) Off - [Trigger ID674] (Not Assigned) Off -
[Trigger ID585] (Not Assigned) Off - [Trigger ID675] (Not Assigned) Off -
[Trigger ID586] (Not Assigned) Off - [Trigger ID676] (Not Assigned) Off -
[Trigger ID587] (Not Assigned) Off - [Trigger ID677] (Not Assigned) Off -
[Trigger ID588] (Not Assigned) Off - [Trigger ID678] (Not Assigned) Off -
[Trigger ID589] (Not Assigned) Off - [Trigger ID679] (Not Assigned) Off -
[Trigger ID590] (Not Assigned) Off - [Trigger ID680] (Not Assigned) Off -
[Trigger ID591] (Not Assigned) Off - [Trigger ID681] (Not Assigned) Off -
[Trigger ID592] (Not Assigned) Off - [Trigger ID682] (Not Assigned) Off -
[Trigger ID593] (Not Assigned) Off - [Trigger ID683] (Not Assigned) Off -
[Trigger ID594] (Not Assigned) Off - [Trigger ID684] (Not Assigned) Off -
[Trigger ID595] (Not Assigned) Off - [Trigger ID685] (Not Assigned) Off -
[Trigger ID596] (Not Assigned) Off - [Trigger ID686] (Not Assigned) Off -
[Trigger ID597] (Not Assigned) Off - [Trigger ID687] (Not Assigned) Off -
[Trigger ID598] (Not Assigned) Off - [Trigger ID688] (Not Assigned) Off -
[Trigger ID599] (Not Assigned) Off - [Trigger ID689] (Not Assigned) Off -
[Trigger ID600] (Not Assigned) Off - [Trigger ID690] (Not Assigned) Off -
[Trigger ID601] (Not Assigned) Off - [Trigger ID691] (Not Assigned) Off -
[Trigger ID602] (Not Assigned) Off - [Trigger ID692] (Not Assigned) Off -
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1032 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1033 -
6F2S1927 (0.18)
(e.g., the ‘SYS_CHG’ signal; which has been connected with the trigger#9 using the setting
[Trigger ID9], as default; we have been discussed in Chapter Technical description: Group
setting for protection functions.)
occurred for the event#1. Preceding event#2, event#3, etc. are shown below the event#1.
Similarly, the information about the ‘Event Record2’ and ‘Event Record3’ groups are displayed
on the IED screen.
†Note:For more information about the screen operation, see Chapter User interface:
Record sub-menu.
Event Record1 ○
a Event record1 list
10:48 1/4
#1 2012-07-26 ○
b The latest event#1
12:34:51.223
F.Record clear ○
c Trigger inform ation
On ○
d Trigger m ode inform ation
#2 2012-07-25
Screen scroll down 10:56:12.021
○
e Event#2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1034 -
6F2S1927 (0.18)
8.2.5 Setting
EVENTRECORD(Function ID: 200710)
Setting items Range Unit Contents Default Note
End of E.Record-1 0 to 768 – The last position of the event group1 (Level1) 256
End of E.Record-2 0 to 768 – The last position of the event group2 (Level2) 512
Trigger ID1 (Preferred DataID) – Trigger signal1 for the operation
On / Off / On-Off /
Tigger Mode1 – Mode setting for the detection
Change
Event name1 (Preferred name) – Name of the trigger signal1
Trigger ID2 (Preferred DataID) – Trigger signal2 for the operation
On / Off / On-Off /
Tigger Mode2 – Mode setting for the detection
Change
See tables in this
Event name2 (Preferred name) – Name of the trigger signal2
section
…… …… – ……
…… …… – ……
…… …… – ……
Trigger ID768 (Preferred DataID) – Trigger signal768 for the operation
On / Off / On-Off /
Tigger Mode768 – Mode setting for the detection
Change
Event name768 (Preferred name) – Name of the trigger signal768
8.2.6 Signal
Signal monitoring point
EVENTRECORD (Function ID: 200710)
Name Element ID Description
ER1_CLR 3001001001 Clearing the data in Event group1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1035 -
6F2S1927 (0.18)
Disturbance recorder
Disturbance recorder is to record the phenomenon about the occurrences of the fault with 1ms
accuracy; the disturbance recorder is operated with the reception of the TRC trip command.
The disturbance recorder has exclusive overcurrent and other relays; thus, they can also start
the disturbance recorder when the exclusive relays detects abnormal phenomenon.
Additionally, the disturbance recorder can accept the instruction of the PLC function using
settings. The recording time and the sampling time are programmable; thus, the measuring
values about currents, voltage, frequency, and logic signals are collected in accordance with
the recording and the sampling times. The logic signals are also memorized during the
disturbance phenomenon; the disturbance recorder can hold up to 256 signals. The recording
number of the disturbance phenomena is limited by the recording and sampling times.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1036 -
6F2S1927 (0.18)
also check the maximum number on the IED screen (See Figure 8.3-2).
Table 8.3-1 Max number depending on time settings
Recording Max. recording number for Disturbance phenomena
period set with Setting [Sampling Rate] in 60Hz sys. Setting [Sampling Rate] in 50Hz sys.
[Record Time] 7.5º 15º 7.5º 15º
A 170, ○
○ B 170 A 255, ○
○ B 255 A 204, ○
○ B 204 A 255, ○
○ B 255
1 sec C 204, ○
○ D 204 C 255, ○
○ D 255 C 204, ○
○ D 255 C 255, ○
○ D 255
E 170
○ E 255
○ E 204
○ E 255
○
A 60, ○
○ B 64 A 113, ○
○ B 128 A 73, ○
○ B 78 A 113, ○
○ B 128
3 sec C 73, ○
○ D 73 C 128, ○
○ D 146 C 85, ○
○ D 85 C 128, ○
○ D 146
E 64
○ E 128
○ E 78
○ E 128
○
A 37, ○
○ B 39 A 73, ○
○ B 78 A 73, ○
○ B 78 A 85, ○
○ B 93
5 sec C 42, ○
○ D 44 C 85, ○
○ D 85 C 85, ○
○ D 85 C 102, ○
○ D 102
E 40
○ E 78
○ E 78
○ E 93
○
Note: The maximum number is dependent on the VCT type and the model selected in
the ‘Software selection’, which is shown in ○
A to ○
E of Table 8.3-2.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1037 -
6F2S1927 (0.18)
8.3.4 Number of analog quantities and logical signals for disturbance recorder
Ten analog quantities and 256 logical signals are record in a disturbance phenomenon.
(i) Number of analog quantities
For example, when VCT31B is used in the IED, the currents (Ia, Ib, Ic, Ie) and the voltages
(VL1, VL2, VL3, Ve, Vs) are recorded. For more information about the VCT, see Chapter
Technical description: Transformer module for AC analog input.
Table 8.3-2 Recording number of logic signals depending on time settings
VCT type 31B 36B 32B 33B 31B
(Soft model) ○
A (3D) ○
B (3E/3F) ○
C (30/32) ○
D (39) ○
E (36)
VL1 VL1 – VL1 VL1
VL2 VL2 – VL2 VL2
Voltages VL3 VL3 – VL3 VL3
Vs Vs – Vs Vs
Ve – – Vs2 Vs2
Ia Ia Ia – Ia
Ib Ib Ib – Ib
Currents Ic Ic Ic – Ic
Ie Ie Ie – –
Ie for SEF Ie for SEF Ie for SEF – Ie for SEF
Number of records 10 9 6 5 8
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1038 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1039 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1040 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1041 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1042 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1043 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1044 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1045 -
6F2S1927 (0.18)
Disturbance Record
10:48 1/2
_Record List >
Number of items
5/77
Clear Records +
Max. recording number for Disturbance phenomena
Operating counter
Figure 8.3-2 Running counter and Max number in the disturbance recorder
Disturbance Record
10:48 1/5
#1 2012-07-25 ○
a Disturbance record#1
10:48:21.223
#2 2012-07-21 ○
b Disturbance record#2
01:15:55.018
#3 2012/07/21 ○
c Disturbance record#3
Screen scroll down 13:11:29.621
#4 2012-07-02 ○
d Disturbance record#4
23:32:09.015
#5 2012-06-20 ○
e Disturbance record#5
09:37:48.915
The information in the disturbance recorder are managed in the COMTRADE format,
hence, the user can transferor the disturbance recording file to the PC using the engineering
tool ‘GR-TIEMS’. Figure 8.3-4 shows the example of the GR-TIMES screen. For more
information, see Chapter Engineering tool.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1046 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1047 -
6F2S1927 (0.18)
8.3.7 Setting
DISTURB_REC(Function ID: 200401)
Setting items Range Unit Contents Default Note
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1048 -
6F2S1927 (0.18)
8.3.8 Signal
Signal monitoring point
DRT_LP (Function ID: 4B0001)
Element ID Name Description
8000001C20 DRT-LP DRT-LP protection operated
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1049 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1050 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1051 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1052 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1053 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1054 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1055 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1056 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1057 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1058 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1059 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1060 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1061 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1062 -
6F2S1927 (0.18)
9 Monitoring function
Contents Pages Pages
Accumulated time 1077 Metering features –
Counter features – -Information 1066
-Information in GCNT 1077 -Diminishing small value 1067
Demand features – -Flow settings for P, Q, S 1067
-Information 1074 -Measurement settings 1066
-Demand cycle 1074 -Information on the screen 1066
-Resetting data in demand features 1075 -Polarity setting for PF 1068
-Max/Min/Ave information 1074 Peak Demand features –
Dead band features – -Max/Min/Ave. information 1076
-V, I, P, Q, S, PF, Frequency. 1070 -Reset of peak-demand data 1076
-Wh, Varh, Phase, Voltage difference 1070 Power settings –
-GCNT 1077 -Information on the screen 1072
-TOTALTIM 1079 -Regulating power values 1072
-Power values settings 1072
Total time measurements –
-Information in TOTALTIM 1079
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1063 -
6F2S1927 (0.18)
Outline
The monitoring function is provided to measure the number of power quantities and statistics
data obtained on the VCT or BI circuits†. When the measuring instruments start measures
quantities, mathematical means is applied to the quantities from the circuits so that the actual
data (i.e., primary value or secondary value etc.) is shown accurately on the IED screen.
†Note:The VCT/BIO structures and their features are discussed in Chapter Technical
description.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1064 -
6F2S1927 (0.18)
Va, Vb, Vc
Voltage in phase, phase-to-phase, and
Vab, Vbc, Vca – – –
symmetrical
V1, V2, V0(1)
Residual voltage Ve – – – –
Frequency f(3) – – –
Active(real) power in phase-a,-b,-c /
Pa, Pb, Pc / P – – – –
three-phase
Reactive power in phase-a,-b,-c / three-
Qa, Qb, Qc / Q – – – –
phase
Complex (apparent) power in phase-a,-b,-
Sa, Sb, Sc / S – – – –
c / three-phase
Power factors in phase-a,-b,-c / three-
PFa, PFb, PFc / PF – – – –
phase
Voltage differences between VB and VL /
dV-SYN1, dV-SYN2 – – – – – –
VB and VL2 by the VCHK function
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1065 -
6F2S1927 (0.18)
Metering
10:48 1/59
Ia
12.345kA 123.45deg
Ib
12.345kA 123.45deg
Ic
12.345kA 123.45deg
Metering
10:48 1/2
Display Value +
Primary
I-Display Unit +
kA
V-Display Unit +
kV
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1066 -
6F2S1927 (0.18)
II
(P<0)
I
(P>0)
II
(P>0)
I
(P<0)
V V (+)
III I
IV
(P>0)
III
(P>0)
I
IV
(P<0) (P<0)
a. Metering (P) for supplying power b. Metering (P) for absorbing power
[Power]=Send [Power]=Receive
Figure 9.2-3 Sign of the active power (P) ruled by setting [Power]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1067 -
6F2S1927 (0.18)
II
(Q>0)
I
(Q>0)
II
(Q<0)
I
(Q<0)
V
V
III
(Q<0)
I
IV
(Q<0)
III I
IV
(Q>0)
(Q>0)
a. Q (shown in quadrant IV) has a minus sign b. Q (shown in quadrant IV) has a plus sign because
because the Q is supplied by the outside source. the Q is absorbed by the outside source. The
The decision is made with the P (shown in the decision is based on the P (shown in the
quadrant IV, defined with [Power]=Send) having quadrant I, defined with [Power]=Receive)
“a plus sign” when the current lags the voltage. having “a minus sign” when the current leads
the voltage.
[Current]=Lag [Current]=Lead
Figure 9.2-4 Sign of the reactive power (Q) ruled by setting [Current]
(i) AP setting
When the sign of the PF value is required to match with the sign of the P value, set AP for the
setting [PF_sign].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1068 -
6F2S1927 (0.18)
II I II I
(PF <0) (PF>0) (PF <0) (PF <0)
[Power]=
V [Current
III
(PF <0)
I
IV III I
IV
(PF >0)
(PF>0) (PF >0) a. Q has a minus sign be
the outside. The deci
[Power]=Send [Power]=Send sending P having “a
[Current]=Lag [Current]=Lead lags the voltage.
[Current]=Lag
II I II I
(PF >0) (PF<0) (PF >0) (PF <0)
V
V
III
(PF >0)
I
IV III I
IV
(PF<0) (PF >0) (PF <0)
Figure 9.2-5 PF sign matched with the sign of the P value (i.e., [PF sign]=AP)
II I II I
(PF <0) (PF>0) (PF >0) (PF <0)
[Powe
V [Curr
III
(PF >0)
I
IV III I
IV
(PF >0)
(PF<0) (PF <0) a. Q has a minus sign
the outside. The d
[Power]=Send [Power]=Send sending P having
[Current]=Lag [Current]=Lead lags the voltage.
[Current]=Lag
II I II I
(PF >0) (PF<0) (PF <0) (PF >0)
V
V
III
(PF <0)
I
IV III I
IV
(PF>0) (PF >0) (PF <0)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1069 -
6F2S1927 (0.18)
Lower limit
Repeat number
4
3
2
1
0 Time
a b c d e f g h i j k
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1070 -
6F2S1927 (0.18)
Metering
10:48 1/8
ISD +
5.00 %
VSD +
0.60 %
dVSD +
0.60 %
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1071 -
6F2S1927 (0.18)
Power Value
10:48 1/4
Wh+ +
0.0MWh
Wh- +
0.0MWh
varh+ +
0.0Mvarh
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1072 -
6F2S1927 (0.18)
Voltage applied between phases-a-to-b Vab MaX, Vab Min, Vab Ave
Demand
value – – –
(MaX., Min., and Averaged data)
Voltage applied between phases-b-to-b Vbc MaX, Vbc Min, Vbc Ave
– – –
(MaX., Min., and Averaged data)
Voltage applied between phases-c-to-a Vca MaX, Vca Min, Vca Ave
– – –
(MaX., Min., and Averaged data)
Second reference voltages (MaX., Min., Vs2 MaX, Vs2 Min, Vs2 Ave
– – – – –
and Averaged data)
Sensitive residual current (MaX., Min., Ise MaX, Ise Min, Ise Ave(1)
– –
and Averaged data)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1073 -
6F2S1927 (0.18)
Demand Value
10:48 1/42
Ia Max
0.00kA
Ia Min
0.00kA
Ia Ave
0.00kA
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1074 -
6F2S1927 (0.18)
Metering
10:48 21/23
PhaseSD +
0.50 deg
PeriodSD +
0
Demand_period +
10 min
Demand Value
10:48 1/2
Demand Value >
Reset All Values +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1075 -
6F2S1927 (0.18)
Peak Demand
10:48 1/2
Peak Demand Value >
Reset All Values +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1076 -
6F2S1927 (0.18)
…. …. ….
†Note:See Chapter General control function: Counter function for the general (GCNT).
‡Note:See Chapter Relay application: Autoreclose for more information.
Counter
10:48 1/32
ARC1 CLOSE COMMAND +
0
ARC1_SPAR +
0
ARC1_TPAR +
0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1077 -
6F2S1927 (0.18)
Accumulated Time
10:48 1/1
ACT_TIME +
***d **h **m
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1078 -
6F2S1927 (0.18)
…. …. ….
Total Time
10:48 1/12
TOTAL TIME 1 +
****d **h **m
TOTAL TIME 2 +
****d **h **m
TOTAL TIME 3 +
****d **h **m
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1079 -
6F2S1927 (0.18)
(ii) Communication
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Communication. The communication features about the LAN port is discussed in
Chapter Communication protocol: LAN communication. The hardware information is
discussed in Chapter Technical description: Signal processing and communication module).
(iii) Binary IO
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Binary I/O. The structure and its operation is discussed in Chapter Technical
description: Binary IO module).
(v) Diagnostics
(For more information about the menu operation, see Chapter User interface: Monitoring sub-
menu: Diagnostics sub-menu. The information about the diagnostics is discussed in Chapter
Automatic supervision).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1080 -
6F2S1927 (0.18)
Setting
Metering settings in MES (Function ID: 710001)
Unit Default
Setting item Range Contents Notes
s setting value
Display Value Primary/Secondary – Display selection of primary or secondary Primary
Power Send/Receive – Power flow definition (Supply or absorb) Send
Current Lead/Lag – The angle compared with the voltage Lead
PF Sign AP/AP+RP – Denison of the sign of the power factor AP+RP
I-Valid Level 0.10 to 5.00 % Cutting off small entering current 4.00
V-Valid Level 0.10 to 5.00 % Cutting off small applied voltage 0.30
I-Display Unit A/kA – Current shown in Ampere or Kilo-Ampere kA
V-Display Unit V/kV – Voltage shown in Volt or Kilo-Volt kV
P-Display Unit kW/MW – Active power shown in Kilo- or Mega-watt MW
Q-Display Unit kvar/Mvar – Reactive power shown in Kilo- or Mega-var Mvar
S-Display Unit kVA/MVA – Apparent power shown in Kilo- or Mega-
MVA
VA
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1081 -
6F2S1927 (0.18)
Signal
Signal monitoring point
MES_MANAGEMENT (Function ID: 711001)
Element ID Name Description
3100901060 CT-ERR CT Monitoring Result
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1082 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1083 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1084 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1085 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1086 -
6F2S1927 (0.18)
10 Automatic supervision
Contents Pages Pages
61850 irregular data 1130 Interruption 1101
A/D accuracy error on VCT 1105 LAN pinging error 1128
Abnormal currents flowing on CTs 1106 LRE error 1129
Aux. contacts monitoring 1133 MRAM memory error 1097
BIO module#1 error 1111 PLC Data error 1121
BIO module#2 error 1112 Power supply failure 1120
BIO module#3 error 1113 Program code error 1099
BIO module#4 error 1114 RAM error 1095
BIO module#5 error 1115 ROM and RAM mismatch 1093
BIO module#6 error 1116 Sampling error 1102
BIO module#7 error 1117 Setting error 1103
BIO module#8 error 1118 Sigma Iy error 1156
CB failure 1124 Trip circuit error 1152
CB interruption capability error 1156 Trip circuit supervision task 1148
Check-sum error 1094 Voltage error in negative-sequence 1109
Clock error 1104 Voltage error in zero-sequence 1110
CT open circuit 1107 VT error 1123
Current error in zero-sequence 1110
DS failure 1126
ECC memory error 1096
FPGA problem 1098
GOOSE publishing error 1132
HMI malfunction 1119
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1087 -
6F2S1927 (0.18)
Tips: The alarms can be blocked when Off is set for the switch [A.M.F]. The switch can
be used to remove alarms during testing. See Chapter User interface: Test sub-
menu for more information.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1088 -
6F2S1927 (0.18)
The user can see a current error information in Monitoring sub-menu† on the LCD screen†
(see Figure 10.1-1); Table 10.1-3 shows the six detail information, which the user can examine
carefully using the hexadecimal number. When two or more errors occur at the same time, an
error code is given by the summation of the error codes. That is, when X and Y errors (e.g., X-
error-code ‘00000002’ and Y-error-code ‘00000004’) occur, the sum value ‘00000006’ is screened.
CP1M(ROM/RAM) error 1/1 C u r r e n t e r r o r i n d i c a te d b y S u p e r v i s i o n
10:48 C u r r e n t l o c a l ti m e ( N o t E r r o r o c c u r r i n g ti m e )
[Serious error] E rro r d e g re e (le ve l) d is p la ye d
D e ta i l e d i n f o r m a ti o n i n H e x a d e c i m a l d u m p
[00000011] [01234567] 7 6 5 4 3 2 1 0
[01234567]
[01234567]
[01234567]
[00000000] [ “Top left” ][ “Top right” ]
[ “Middle left” ][ “Middle right” ]
[ “Bottom left” ][ “Bottom right” ]
Figure 10.1-1 Example error codes and detailed information on Diagnostics sub-menu
†Note:See Chapter User interface: Monitoring sub-menu: Diagnostics. It will not be
updated automatically. If new information is required, refresh LED screen again.
Table 10.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display Meaning of the detailed information
area Left column Right column
00000001: ROM read error
Top row ROM address
00000002: ROM RAM mismatch
Middle row RAM address ROM value
Bottom row RAM value (No information displayed)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1089 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1090 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1091 -
6F2S1927 (0.18)
Detailed Error
Sec. No. Supervision items (Screen message) Info. Lvl. LED
10.2.32 Supervision of second circuit breaker contacts (CB2 fail) N/A 3 On
10.2.33 Supervision of disconnector contacts (DS fail) N/A 3 On
10.2.34 Supervision of LAN status (LAN error) Displayed 3 On
10.2.35 Supervision of response for pinging (Ping error) Displayed 3 On
10.2.36 Supervision of link redundant entity (LRE error) Displayed 1 On
10.2.37 Supervision of communication setting (Commslv error) Displayed 3 On
10.2.38 Supervision of GOOSE publishing (LAN(GOOSE)error) Displayed 3 On
10.2.39 Aux. contacts monitoring (DPSY/DOPS/TOPS faulty or undefined) Displayed 3 On
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Check the order number for the “G&T position”
whilst referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.2-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
10.2.14 CHK_CT ✓ ✓ ✓ ✓ ✓ ✓ NA
10.2.15 CHK_CTF ✓ ✓ ✓ NA NA NA NA
10.2.16 CHK_IZ ✓ ✓ ✓ ✓ ✓ NA NA
10.2.17 CHK_V2 ✓ ✓ ✓ NA NA ✓ ✓
10.2.18 CHK_VZ ✓ ✓ ✓ NA NA ✓ ✓
10.2.30 CHK_VTF ✓ ✓ ✓ NA NA NA NA
10.2.31 CHK_CB ✓ ✓ ✓ ✓ ✓ ✓ NA
10.2.32 CHK_CB2 NA NA NA NA NA ✓ NA
10.2.33 CHK_DS ✓ ✓ ✓ ✓ ✓ NA NA
CHK_DPOSSYN ✓ ✓ NA NA NA NA NA
10.2.39 CHK_DPOS ✓ ✓ NA ✓ NA NA NA
CHK_TPOS ✓ ✓ NA ✓ NA NA NA
– Except the above ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓: Applicable NA: Not applicable
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1092 -
6F2S1927 (0.18)
Middle
RAM address ROM value
row
Bottom
RAM value (No information displayed)
row
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1093 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1094 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1095 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1096 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1097 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1098 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1099 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1100 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1101 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1102 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1103 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1104 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1105 -
6F2S1927 (0.18)
where,
Max (|Ia|, |Ib|, |Ic|): The largest amplitude among Ia, Ib, and Ic
Min (|Ia|, |Ib|, |Ic|): The smallest amplitude among Ia, Ib, and Ic
k0: 20% of the rated current†
†Note:When the VCT has two or more three-phase-CT circuits, the CT supervision may
be required to operate for respective CT circuits. The rated current above the
equation is defined with VCT setting. For more information regarding the VCT,
see Chapter Technical description: Transformer module for AC analog input.
Settings are required to respective groups of the three-phase currents.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1106 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1107 -
6F2S1927 (0.18)
|Ia + Ib + Ic − Ie |
1. ≥ 0.1 × Max(|Ia |, |Ib |, |Ic |) + k 0 (10.2-2)
3
where,
Ie Residual current
Max(|Ia|, |Ib|, |Ic|) The largest amplitude among Ia, Ib and Ic
k0: 5% of the rated current†
†Note:The rated current above the equation is defined with the setting of the VCT. For
more information regarding the VCT, see Chapter Technical description:
Transformer module for AC analog input.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1108 -
6F2S1927 (0.18)
The voltage in negative sequence can be used to detect a failure within the voltage input
circuit in high sensitivity. It facilitates the detection of the incorrect phase sequence if cables
are connected irregularly.
|Va + 𝑎2 Vb + aVc |
1. ≥ 6.35 (V) (10.2-3)
3
where,
a = Phase shift operator of 120
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1109 -
6F2S1927 (0.18)
|Va + Vb + Vc |
1. ≥ 6.35 (V) (10.2-4)
3
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1110 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1111 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1112 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1113 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1114 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1115 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1116 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1117 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1118 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1119 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1120 -
6F2S1927 (0.18)
1For more information about the task and its kind, see Chapter PLC editing in PLC editor
(6F2S1904) separately.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1121 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1122 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1123 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1124 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1125 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1126 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1127 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1128 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1129 -
6F2S1927 (0.18)
Data(cmmslv) error
10:48 1/1
[Minor error]
[00010004] [51200131]
[03011001] [4747494F]
[32245354] [7456616C]
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1130 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1131 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1132 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1133 -
6F2S1927 (0.18)
Middle
(No information is displayed) (No information is displayed)
row
Bottom
(No information is displayed) (No information is displayed)
row
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1134 -
6F2S1927 (0.18)
10.2.40 Setting
Setting of CHK_SAMPLING (Function ID: 220701)
Setting item Range Contents Default setting value Notes
… … … …
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1135 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1136 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1137 -
6F2S1927 (0.18)
PING_IP_ADRS4 0 - 255 1
PING_IP_ADRS4 0 - 255 1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1138 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1139 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1140 -
6F2S1927 (0.18)
10.2.41 Signal
Signal monitoring point
MNT_LOGIC (Function ID: 220001)
Element ID Name Description
3211001001 ACT_TIME System active time in minutes
3210111001 CHECKSUMC
32E0001001 CHK_POINT
3210201001 LOADERSUM
3210121001 PROG_SIZE
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1141 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1142 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1143 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1144 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1145 -
6F2S1927 (0.18)
… … …
… … …
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1146 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1147 -
6F2S1927 (0.18)
Displaying error message founded by the TCS function is shown in Table 10.3-1; the error
is cleared when recovered
Table 10.3-1 Supervision items and error levels for Trip supervision
Detailed Error
Sec.No. Supervision items(Screen message) Info. Lvl LED
10.3.1 Trip circuit error (TC error) N/A 3 On
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.3-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 39 39
10.3.1 CHK_TCS ✓ ✓ ✓ ✓ ✓ ✓ NA
✓: Applicable NA: Not applicable TBD: To be developed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1148 -
6F2S1927 (0.18)
8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s
8000011BB2
800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
TCS1-EN
On
8100021B60
8200031B60
8300041B60
8400051B60
8500061B60
≥1
8F00001B60
TC_FAIL
(ii) Applications
Example1
Figure 10.3-2 provides an application example of the TCS function. Two binary-input signals
are assigned to PLC connection points “TC1_FAIL_SIGNAL1” and “TC1_FAIL_SIGNAL2”.
When the trip circuit is healthy, a small current will flow in the BI circuits, the CB auxiliary
contacts, and the trip coil. This small current can be observed to flow in both the CB-open
condition and the CB-closed condition. If the small current supplied to the trip circuit is lost,
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1149 -
6F2S1927 (0.18)
or if the connections between the trip circuit and the BI circuits become open circuit, a signal
"TC1_FAIL" is generated; then, the TCS1 logic will issue a Trip Circuit Fail alarm.
Note: A threshold setting voltage is required for the BI circuits. The user should set the
threshold to one-half of the value of the trip supply voltage. This is because in this
scheme there are two BI circuits connected in series. The supply voltage across the
BI circuit will be divided by two when the 52 contact is closed and the 52b contact
is open. Thus, the BI circuit may fail to operate if the BI sensitivity is only set in
response to the supply voltage. For example, the BI threshold voltage should be
set below 55V when a trip supply voltage of 110V is applied. For the TCS function,
the user should select two BI circuits from the BI2A module, because the BI
circuits of both of these modules can have lower threshold voltages than the BI
circuits that are available in other modules.
Trip circuit
()
Protection
8000011BB0
relay R
BI1 Binary input 800001EBB0 TC1_FAIL_SIGNAL1 1
circuit &
8000011B60
R 8000011BB1 t 0 0 t TC1_FAIL
Trip coil
()
LCP & GIS
Example2
In Example2 a binary input signal is assigned to PLC connection point “TC1_FAIL_SIGNAL1”.
With this arrangement if the CB is open, the small monitoring current will not be able to flow
in the BI circuit. Therefore, it is recommended that setting OPT-On is selected for the scheme
switch [TCS1-EN] and that a CB-closed-status signal is applied to PLC connection point
“TC1_FAIL_COND”. Monitoring is only enabled while the CB is in the closed position when
using this setting. This setting avoids unnecessary monitoring when the circuit breaker is open
when using this scheme.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1150 -
6F2S1927 (0.18)
Trip circuit
()
Protection
8000011BB0
relay R
8000011BB1 t 0 0 t TC1_FAIL
800001EBB1 TC1_FAIL_SIGNAL2 1 0.4s 0.4s
52a
8000011BB2
800001EBB2 TC1_FAIL_COND
OPT-On &
≥1
CB closed TCS1-EN On
Trip coil status signal
()
LCP & GIS
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1151 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1152 -
6F2S1927 (0.18)
10.3.3 Setting
Setting of TCS(Function ID: 482001)
Note
Setting item Range Units Contents Default setting value
s
TCS1(Trip Circuit Supervision 1)
TCS1-EN Off / On / OPT-On — Off
enable
TCS2(Trip Circuit Supervision 2)
TCS2-EN Off / On / OPT-On — Off
enable
TCS3(Trip Circuit Supervision 3)
TCS3-EN Off / On / OPT-On — Off
enable
TCS4(Trip Circuit Supervision 4)
TCS4-EN Off / On / OPT-On — Off
enable
TCS5(Trip Circuit Supervision 5)
TCS5-EN Off / On / OPT-On — Off
enable
TCS6(Trip Circuit Supervision 6)
TCS6-EN Off / On / OPT-On — Off
enable
…. …. …. ….
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1153 -
6F2S1927 (0.18)
10.3.4 Signal
Signal monitoring point
TCS(Function ID: 482001)
Element ID Name Description
8000011B60 TC1_FAIL Trip circuit1 fail
8000011BB0 TC1_FAIL_SIGNAL1 Trip circuit1 fail signal1
8000011BB1 TC1_FAIL_SIGNAL2 Trip circuit1 fail signal2
8000011BB2 TC1_FAIL_COND TC1 fail condition
8100021B60 TC2_FAIL Trip circuit2 fail
8100021BB0 TC2_FAIL_SIGNAL1 Trip circuit2 fail signal1
8100021BB1 TC2_FAIL_SIGNAL2 Trip circuit2 fail signal2
8100021BB2 TC2_FAIL_COND TC2 fail condition
8200031B60 TC3_FAIL Trip circuit3 fail
8200031BB0 TC3_FAIL_SIGNAL1 Trip circuit3 fail signal1
8200031BB1 TC3_FAIL_SIGNAL2 Trip circuit3 fail signal2
8200031BB2 TC3_FAIL_COND TC3 fail condition
8300041B60 TC4_FAIL Trip circuit4 fail
8300041BB0 TC4_FAIL_SIGNAL1 Trip circuit4 fail signal1
8300041BB1 TC4_FAIL_SIGNAL2 Trip circuit4 fail signal2
8300041BB2 TC4_FAIL_COND TC4 fail condition
8400051B60 TC5_FAIL Trip circuit5 fail
8400051BB0 TC5_FAIL_SIGNAL1 Trip circuit5 fail signal1
8400051BB1 TC5_FAIL_SIGNAL2 Trip circuit5 fail signal2
8400051BB2 TC5_FAIL_COND TC5 fail condition
8500061B60 TC6_FAIL Trip circuit6 fail
8500061BB0 TC6_FAIL_SIGNAL1 Trip circuit6 fail signal1
8500061BB1 TC6_FAIL_SIGNAL2 Trip circuit6 fail signal2
8500061BB2 TC6_FAIL_COND TC6 fail condition
8F00001B60 TC_FAIL Trip circuit fail
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1154 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1155 -
6F2S1927 (0.18)
Displaying error message founded by the sigma_Iy function is shown in Table 10.4-1.
─────────────────────────────────────────────────────────────────
Note: The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.4-2 Comparative table in respective ordering numbers
Ordering No. at “G&T”
Sec. Feature
3D 3E 3F 30 32 36 39
10.4.1 CHK_SGMIY ✓ ✓ ✓ ✓ ✓ ✓ NA
✓: Applicable NA: Not applicable
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1156 -
6F2S1927 (0.18)
y y y y
∑ IY =I1 +I2 +I3 +⋯+In (10.4-1)
As setting for a conventional CB with regard to the parameter ‘y’, the user can set a value
‘2.0’ for the [SIGMA_IY-Y]; that is, the accumulation is performed with the fault currents
squared (I 2). On the other hand, the user can be required to set a less value (say ‘1.0’) for the
[SIGMA_IY-Y] when a special CB is required (that is, for the high voltage system).
Tripping CB
Command issuing #1
Command issuing #2 Tripping CB
Command issuing #n
y y y y
∑ IY =I1 +I2 +I3 +⋯+In
The sigma_Iy function can designed to issue an alarm when the synthesized broken
current value reaches an alarm level set by [SIGMA_IY-Alarm]; issuing an alarm is ready when
the user sets On for scheme switch [SIGMA_IY-AEN].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1157 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1158 -
6F2S1927 (0.18)
10.4.3 Setting
Setting of SIGMA_IY (Function ID: 713001)
Note
Setting item Range Units Contents Default setting value
s
SIGMA_IY-EN Off / On — Enabling Sigma Iy function operation Off
SIGMA_IY-AEN Off / On — Enabling Sigma Iy alarming Off
SIGMA_IY-Alarm 1.0 to 100000000.0 — Alarm level in Sigma Iy function 10000.0
SIGMA_IY-Y 1.0 to 2.0 — Y parameter for in Sigma Iy 1.0
10.4.4 Signal
Signal monitoring point
SIGMA_IY (Function ID: 713001)
Element ID Name Description
8000001C20 SGMIY-A Monitoring SIGMA_IY relay element output (phase-A)
8100001C21 SGMIY-B Monitoring SIGMA_IY relay element output (phase-B)
8200001C22 SGMIY-C Monitoring SIGMA_IY relay element output (phase-C)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1159 -
6F2S1927 (0.18)
11 Communication protocol
Contents Pages Pages
IEC 60870-5-103 operation – LAN operation –
-Interface 1232 -IP address 1162
-Interoperability 1235 -Hot standby operation 1163
-Operation 1256 -PRP/HSR operation 1170
IEC 61850 operation 1182 -RSTP operation 1174
-About protocol 1182 -Monitoring (Hot standby) 1165
-Communication service 1185 -Monitoring (PRP/HSR) 1172
-Engineering work 1188 Protocol selection 1161
-Goose monitoring status 1212 RS485operation 1261
-Protocol selection 1209 USB operation 1260
-Quality signal 1210
-Setting 1207
-Supervise 1209
-61850 Editon1 option 1184
-61850 Editon2 1184
─────────────────────────────────────────────────────────────────
Note: The implementation of such protocols depends on the selection of protocols. Several
IED models do not have the protocols. To determine whether the protocols are implemented in
the IED, locate the IED ordering number; and check the order number at the “U position”
referring to the comparison table below. For more information, see Appendix: Ordering.
Table 10.4-1 Comparative table in respective ordering numbers
Ordering No. at “U”
Sec. Feature
1 2
11.2.1 TCP/IP ✓ ✓
11.2.2 Hot-standby ✓ ✓
11.2.3 PRP/HSR NA ✓1
11.2.4 RSTP NA ✓1
11.3 IEC 61850 ✓2 ✓
11.4 IEC 60870-5-103 ✓2 NA
✓: Applicable NA: Not applicable
1 LAN modules, designed for PRP/HSR/RSTP marked with “L or N” code at position “E”, shall
be mounted in IED, if network operation in PRP/HSR/RSTP is required.
2 Either 61850 or 103 shall be selected during the operation.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1160 -
6F2S1927 (0.18)
Figure 11.1-1 illustrates the LAN and USBCOM sub-menus are provided for the
connection to the LAN, whereas the SLAVE PROTOCOL sub-menu is for the selection of either
the IEC61850 or the IEC103 protocols. The IEC61850 sub-menu has its own settings, so does
the IEC103 menu. The RS485 sub-menu is screened when the IED has the one used for the
IEC103 in the serial communication.
Communication
10:48 1/6
LAN >
USBCOM >
RS485 >
SLAVE PROTOCOL >
IEC61850 >
IEC103 SLV >
Figure 11.1-1 Example of Setting menu ‘IEC61850, IEC103, RS485 and USB’
†Note:Selection and operation is dependent on the IED configurations, which the
customer has determined with the ordering code. Accordingly, the selection and
operation can be unavailable if the protocol is not provided in the IED. To examine
the IED configuration, check your ordering code referring Appendix: Ordering.
‡Note:We have discussed the specifications regarding the communication interface. See
Technical description: Signal processing and communication module.
§Note:The setting function is provided with the function ‘CNN_SLAVE’. The setting list
and Signal monitoring point (in Data ID) are shown below:
CNN_SLAVE (Function ID: 300001)
Setting item Range Contents Default setting value
Slave Protocol IEC61850 / IEC103 Protocol selection IEC61850
S-TestFlagCancel Off / On Canceling Test-flag in the slave communication Off
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1161 -
6F2S1927 (0.18)
LAN operation
11.2.1 LAN address (IP address)
The IED can have the communication with “Transmission Control Protocol/Internet Protocol
(TCP/IP)”. The user can set IP addresses and other TCP/IP information. Table 11.2-1 shows
the setting items provided for the LAN†.
When wishing to change addresses, enter the new address at LAN setting sub-menu.
Figure 11.2-1 shows the setting menu provided to change the addresses‡.
LAN
10:48 1/6
IPADDRESS1 +
192.168.1.11
SUBNETMASK1 +
255.255.255.1
GATEWAY1 +
192.168.1.1
†Note:For the location of the LAN communication modules, see Chapter Technical
description: Signal processing and communication module.
‡Note:IP address setting is dependent on the selection of the communication protocols.
For setting [RedundantMode]=Hot-standby, an IP address should be assigned for
the both A and B pots (i.e., a single one is set for the both; see Table 11.2-4).
Similarly, for [RedundantMode]=PRP/HSR/RSTP, an IP address will be assigned
for the both (see Table 11.2-5).
When setting [RedundantMode]=Fixed, two IP addresses can be assigned for the
respective ports, provided two ports are sited (see Table 11.2-5).
‡Note:Chapter User interface: Setting sub-menu describes how to set the address on the
IED screen.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1162 -
6F2S1927 (0.18)
†Note: When the user wishes not to operate Hot-standby, or the network is not ready for
the redundant, set Fixed for the [RedundantMode]. Port B (located at C12 if
provided) can only operate for the connection with the engineering tool (GR-
TIEMS®) or the PLC editor (MULTIPLOG®).
‡Note: See Chapter Technical description: Signal processing and communication
module.
(i) Overview
For the Hot-standby communication, the first communication module for Network is used as
the primary port, (i.e. Port A at C11) while a second communication module for Network, (i.e.
Port B at C12) is used as the secondary port; the IED will communicate using Port A for normal
operation. If a communications failure occurs at Port A, the IED can automatically switch
communication from Port A to Port B.
When the IED detects the occurrence of a communications failure, for which the LAN
module is unable to respond to the IED (i.e. a communications link is down), the IED starts a
timer. When the timer exceeds a setting [DownTime], the IED will switch ports. Thus, Port B
is then used for communications. (Note that Port A can be determined to be the secondary port
on the occurrence of the failure. If Port B is unable to continue to operate, then Port A will be
re-switched to run after a predetermined setting [UpTime]. Then, Port B will be discriminated
as the secondary port.)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1163 -
6F2S1927 (0.18)
The user should be aware of the following three facts prior to the Hot-standby operation:
1 The IED uses the IP/MAC address of Port A for the Hot-standby operation. The
IP/MAC address of Port B is not used even if communication is carried out on Port
B.
2 The user should ensure that an optical fiber is correctly connected when a 100Base-
FX module is used, otherwise a repeat communication failure (link-down) will be
experienced continuously. If the period for which the link-down is shorter than the
setting [DownTime], another port cannot be switched as the primary port. Thus,
the user should determine the setting value to be applied for [DownTime] on the
basis of the system requirement. It is allowable for the user to apply a setting of
zero for [DownTime] so that the switching of the ports will be performed
immediately; conversely, the user can set any value less than 3000ms in order that
the system need not experience chattering failures if the optical fiber were not
connected securely. Switching between the primary and the secondary ports is not
carried out during a value is setting for the [DownTime]. The user should consider
the setting approach for [UpTime] in the same manner as when setting [DownTime].
3 The auto-negotiation function is executed when the 100Base-TX modules establish
communication over the communications network. The auto-negotiation function
selects a mode for communication; the auto-negotiation function adjusts the
communication speed. In the case of a link-down condition, the auto-negotiation
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1164 -
6F2S1927 (0.18)
function will run again immediately. The link-down condition continues until auto-
negotiation has been completed (it may continue for 1 or 2 seconds). The user can
apply a setting for [DownTime] for any value of time less than that required by the
auto-negotiation function in response to the system requirement (i.e. the user can
set [DownTime] to be zero milliseconds). In this case, switching between the
primary and secondary ports is performed immediately i.e. prior to the auto-
negotiation function running. If switching between ports is not required before the
completion of the auto-negotiation function, the user can set the setting
[DownTime] longer than the time required by the auto-negotiation function. The
user can consider the setting for [UpTime] in the same manner as when setting
[DownTime].
(vi) Monitor
LCD screen: The user can examine the statuses about the communion modules by
the monitoring function. Figure 11.2-2 shows the port status about the modules; terms
‘Up’ and ‘Down’ mean running and stopping, respectively. For menus operations, see
Chapter User interface: Monitoring sub-menu.
PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP
Port 1 (i.e., Port A) is connected. Ports 1&2 (i.e., Port A&B) are connected.
Port 2 (i.e., Port B) is not connected.
Status signals for Port A and Port B: The user can also examine the LAN status
using PLC signal monitoring points ‘Port1_Link (3100061001)’ and ‘Port2_Link
(3100061001)’ of the HOTST function. For example, when the user wishes to monitor
the status of the Prot1_Link, use the ‘Port1_Link’. Consequently, the user can get the
physical information about the Port A: the value ‘1’ is issued when the communication
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1165 -
6F2S1927 (0.18)
is made (Linkup), whereas value ‘0’ is issued when the communication is not made
(Linkdown).
When Hot_Standby is set for the [RedundantMode], the user can find a running port
using the PLC signal monitoring point ‘Using_CH (3100081001)’ of the HOTST
function. Value ‘1’ is provided when the Port A is running, whereas value ‘2’ is
provided when the Port B is running.
Monitor setting: The Hot-standby (HOTST) function can send PING packets to
remote devices thus enabling the Hot-standby function to monitor the state of the
network. The Hot-standby function checks for a response signal from the remote
device. If the Hot-standby function does not receive a response signal, the Hot-
standby function will switch to the other port. The operation is performed when
the user sets the [RedundantMode]= Hot_Standby and [NetMonitor_EN] = On.
Settings [Ping_IP1] to [Ping_IP12] are provided in the Hot-standby function for the
monitoring of remote devices on the network. When the user sets plural remote IP
addresses for the settings [Ping_IP*], and if the Hot-standby function does not receive
a response from any one of these remote devices, the Hot-standby function determines
that a communication failure has occurred. Table 11.2-3 shows the network
monitoring settings for Hot-standby operation.
The user should note that the use of network monitoring could increase the burden
on the network. This is because a number of PING packets are repeatedly transmitted
over the network. Thus, the user should choose the setting values carefully in
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1166 -
6F2S1927 (0.18)
accordance with the network capacity, the burden, and the required time. Examples
1 and 2 below show the respective results using the network monitoring function with
for different settings.
Example1: There is a remote device on the network with the address Ping_IP1.
The Hot-standby function sends ping packets to the remote device every five
seconds; then the Hot-standby function waits for one second until the Hot-
standby function receives a response signal from the remote device. The Hot-
standby function will determine that a communication failure has occurred if two
sequential response signals are not received from the remote device. Subsequently,
the Hot-Standby function will switch from one port to the other port (See Figure
11.2-3). The following settings are required in this example 1:
・ The IP address of the remote device1 is set for setting [Ping_IP1]. (the setting of
IP addresses in the other remote devices is not required.)
・ One second is set for setting [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “2” is set for [Check_Count].
Local IED Remote device with
Ping_IP1 address
Ping_Interval Ping_Wait
: 5sec : 1sec Sending Ping Packet for Ping_IP1.
5sec
NG: due to no response
Switching LAN ports is
performed if a response signal is
Sending Ping Packet for Ping_IP1.
not received for setting
[Chk_Count]. 1sec
5sec
Example2: It is assumed that there are three remote devices on the network:
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1167 -
6F2S1927 (0.18)
Ping_IP1, Ping_IP2, and Ping_IP3. The Hot-standby function sends a Ping packet to
every remote device every 10 second (i.e., the IED sends a ping packet to a remote
device every 30 second). Suppose that “1” is set for [Check_Count]. The Hot-standby
function can determine a communication failure after 30 seconds if one of the remote
devices is unable to send a response. Figure 11.2-4 shows the operation. Switching is
not executed, because the IED cannot confirm all no-responses from the remote
addresses in the milled of the figure. Switching is performed after no-response is
confirmed from all remote devices.
・ The IP addresses of the remote devices are set for [Ping_IP1] to [Ping_IP3].
(Setting IP addresses for other remote devices is not required.)
・ 10seconds is set for [Ping_Wait].
・ Number “5” is set for [Ping_Interval].
・ Number “1” is set for [Check_Count].
5sec
5sec
10sec
NG: due to no response
LAN switching is not performed because the IED has not confirmed a response from the IP3.
Sending Ping Packet for Ping_IP1.
LAN switching is performed because the IED has not confirmed all response.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1168 -
6F2S1927 (0.18)
IP address at
Not applicable 192.168.1.12‡ 192.168.1.12§
Port B
†Note:Port A ‘192.168.1.11 (default)’ is ready for IEC61850 (GOOSE), but Port B is not
ready for IEC61850.
‡Note: Single IP address is generally set in SNTP. The user is not recommended to have
Time synchronization using different IP addresses with ‘Port A’ and ‘Port B’.
§Note: For the local PC engineering, the use of Port B (192.168.1.12, default) is
recommended, but the user can also use Port A (192.168.1.11, default) for that.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1169 -
6F2S1927 (0.18)
(i) Overview
‘Parallel redundancy protocol (PRP)’ is designed for double LAN networks in order to construct
high availability automation networks. Figure 11.2-5 shows an IED (i.e., Source, IED1 with
Port A and Port B†) and a server (i.e., Destination, Substation computer with Port A and Port
B). They are connected through LAN_A and LAN_B. For duplicating data, the IED have Link
redundancy entity (LRE) so that the IED can transfer data with A-Frame packet and B-Frame
packet at the same time. At the destination, either frames being arrived later is removed.
Substation computer
CPU
Operator
workstation
Data
Port A Port B
Rx Tx Rx Tx
Destination RedBox‡
A-Frame
LAN_A
B-Frame
LAN_B
TOSHIBA
IN SER VICE
ER R OR
Tx Rx Tx Rx
RedBox‡
Port A Port B TOSHIBA
IN SER VICE
LAN module LAN module Rx Rx
ER R OR
(C11) (C12) Tx Tx
Port A Port B
TOSHIBA
LAN module LAN module IN SER VICE
Data (C11) (C12) Rx
ER R OR
Tx
I Port A
R Data LAN module
L (C11)
CPU I
O Help Cancel ENTER
R
IED1 F1 F2 F3 F4 F5 F6 F7 L Data
CPU
Source O Help Cancel ENTER
I
IED2 F1 F2 F3 F4 F5 F6 F7
R
L
CPU
O Help Cancel ENTER
F3
IED3 F1 F2 F4 F5 F6 F7
Figure 11.2-5 PRP example for redundant LAN_A and LAN_B with DANP
†Note:For the locations about the LAN module, see Chapter Technical description:
Signal processing and communication modules.
‡Note: IED3 and Operator workstation (connected with singly attached node) can join
the network with Redundancy boxes (RedBox).
‘High-availability Seamless redundancy (HSR)’, for the ring topology, is designed to achieve
high reliability communication. Figure 11.2-6 illustrates IEDs connected over the ring LAN.
As doubly ports (Port A and Port B) are embedded in an IED, the IED can transfer the data
packet (A-Frame and B-Frame) for the destination over the ring LAN.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1170 -
6F2S1927 (0.18)
Source Destination
TOSHIBA
IED1 IN SE R VICE
E R R OR Substation Computer Operator Workstation
CPU CPU
CPU
Data Data
Data
I Port B Port A Port B Port A
R
L Rx Tx Rx Tx Rx Tx Rx Tx
Port B Port A
O Help Cancel ENTER
Rx Tx Rx Tx
F1 F2 F3 F4 F5 F6 F7
B-Frame B-Frame
A-Frame A-Frame A-Frame
Ring LAN1
A-Frame A-Frame
B-Frame B-Frame B-Frame
TOSHIBA TOSHIBA
IN SE R VICE
IN SE R VICE
E R R OR
E R R OR
Tx Rx Tx Rx Tx
Rx
Tx
Rx
Port A Port B QuadBox QuadBox Port A Port B
LAN module LAN module LAN module LAN module
(C11) (C12) (C11) (C12)
Data Data
I I
R R
L Ring LAN2 L
CPU CPU
O Help Cancel ENTER
O Help Cancel ENTER
IED2 F1 F2 F3 F4 F5 F6 F7 IED4 F1 F2 F3 F4 F5 F6 F7
A-Frame
B-Frame
TOSHIBA
IN SE R VICE
E R R OR
Tx Rx Tx Rx
Port A Port B
LAN module LAN module
(C11) (C12)
Data
R
L
CPU
O Help Cancel ENTER
IED3 F1 F2 F3 F4 F5 F6 F7
For Figure 11.2-5 example, the IED1 (Source) duplicates data by the LRE. The duplicated
data (in A and B-Frames) are transferred simultaneously over the LAN_A and LAN_B. In the
meantime, both frames cannot arrive at Substation computer (Destination). If the duplicated
frame is older than the setting [EntryForgetTime], the duplicated frame will be removed.
The [EntryForgetTime] has default 400ms setting, but the user can change it for an
appropriate value among 100 to 10,000ms. The setting value should be taken account of the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1171 -
6F2S1927 (0.18)
time after the entry removed from the duplicate table. The setting value also should be taken
account of the differences of the communication speeds between LANs.
(iv) Supervision
The communication supervisor function is available in PRP and HSR. The user can have
following settings:
Setting [LineCheckInterval]: is the setting of the interval time to send supervision frames
cyclically. The user is able to choice the time among 100ms to 100,000ms, but the
setting has default 2000ms values.
Setting [SV_Dst_MACAddr]: is for a reserved multicast address ’01-15-4E-00-01-xx’. By
default, ‘00’ is set for the ‘xx’. However, if conflict arises, the use can configure to
set any value between 0x00 and 0xFF for the ‘xx’.
Setting [SV_VLAN_EN]: can have On setting when the supervision frame is used in VLAN.
Additionally, the user can set identification specifying the VLAN to which the
supervision frame belongs and the priority of the supervision frame. Use the
settings [SV_VLAN_ID] and [SV_VLAN_Priority]. By default, Off is set for the
[SV_LAN_EN].
(v) Monitor
It is possible for the user to watch the communion statuses about Port A and Port B. Figure
11.2-7 shows the numbers of transferred packets via ports.
RedundantPacketNum
10:48 1/6
PortA_Send 12345
PortA_Recv 12345
PortA_ErrLANID 12345
PortB_Send 12345
PortB_Recv 12345
PortB_ErrLANID 12345
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1172 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1173 -
6F2S1927 (0.18)
(i) Overview
‘Rapid Spanning Tree Protocol (RSTP)’ is designed to achieve LAN bridge connections in stable.
The RSTP choose one of bridges as the root and BPDU data (called ‘Bridge Protocol Data Unit)
is exchanged periodically over RPST network. Each bridge can listen and learn the BPDU data
so that all bridges in the network can find the shortest path for the root location (we call it
“Path-cost”). Consequently, the RTSP operation clear and recover the network failure if
occurred; no temporary loop will not occur in the network (that is, all terminals can have loop-
free LAN).
(ii) Parameters
When RSTP is set for the [RedundantMode], the user should enter several PSTP parameters
so that the IED is able to enjoy the Spanning Tree topology by the RSTP:
Setting [BridgeHelloTime]: is used to set a BPDU transferring cycle for other terminals
(i.e., BPDU sending interval; they are sent for IEDs, Network bridges, etc.)
Setting [BridgeMaxAge]: instructs the terminal (IED) to listen to a BPDU cyclically. When
a terminal (IED) cannot listen to BPDUs within the setting, the terminal (IED) starts the
computation to make new spanning tree.
Setting [BridgePrioriy]: is allowed for the user to make priority tables in the IEDs. When
a terminal has the smallest number, the terminal can become the root bridge with high
possibility Note that a number can be set in 4096 steps.
Note: the user shall take the above settings based on the IEEE 802.1w equations below:
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1174 -
6F2S1927 (0.18)
Setting [PortA_PathCost]: is used to set the distance for the root bridge (path cost), when
the port is used in the LAN network, actually. As a rule, the setting value depends on the
communication bandwidth.
Setting [PortA_Priority]: is set a priority value for the port. Similar to the setting
[BridgePrioriy], a port having the smallest number can have the highest priority. Note
that a number can be set in 16 steps
†Note: Port A (connection for LAN_A) is located at C11 of IED. The second Port B
(connection for Port B) is located at C12 and has similar settings. See Table 11.2-6
for the IP addresses examples. The user can find the contents about LAN
communication module in Chapter Technical description: Signal processing and
communication module.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1175 -
6F2S1927 (0.18)
11.2.5 Settings
Setting of TCPIP_DRV (Function ID: 230201)
Setting item Range Units Contents Default setting value Notes
IPADDRESS1 0 – 255 – First IP address in the local IED 192.168.1.11
Port A SUBNETMASK1 0 – 255 – Subnet mask 255.255.255.1
GATEWAY1 0 – 255 – Gateway 192.168.1.1
IPADDRESS1 0 – 255 – Second IP address in the local IED 192.168.1.11
Port B SUBNETMASK1 0 – 255 – Subnet mask 255.255.255.1
GATEWAY1 0 – 255 – Gateway 192.168.1.1
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1176 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1177 -
6F2S1927 (0.18)
3111101001 RX2_CNT
3111111001 RX2ER_CNT
3111201001 TX2_CNT
3111211001 TX2ER_CNT
3211021001 PortB_Send frames sent over B(only HSR tagged or with PRP RCT)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1178 -
6F2S1927 (0.18)
3211071001 PortB_Recv frames received over Port B(only HSR tagged or with PRP RCT)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1179 -
6F2S1927 (0.18)
Remote
Monitoring
GPS
Communication Substation
Operator Network
Workstation Computer
Engineering
Workstation Printer Router/
Modem
GBU GRT GRG GBU GRL GRB GBU GRG GRZ GBU GRT GRL
GOOSE
†Note:When applying IEC 61850 communications, the user should map application
signals with the required logical-nodes (LNs) within the IED. In this manual, we
show the application signals as Data IDs; hence, the user is able to connect the
Data IDs with the required LNs using the engineering tool (GR-TIEMS) provided
by Toshiba. For the GR-TIEMS, see Chapter Engineering tool.
‡Note:Before using the IEC 61850 communications feature provided within the IED, the
user should verify its IEC 61850 capability by reviewing both the protocol-
implementation-conformance-statement (PICS) and the model-implementation-
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1180 -
6F2S1927 (0.18)
conformance-statement (MICS). The MICS provides the user with information for
the LNs provided within the IED; the PICS provides the user with information to
enable the IED to communicate with both SAS and other devices. See
Appendix:IEC61850 MICS, PICS, PIXIT and TICS. It explains how the user can
obtain this information.
When TCP/IP operates, the IEDs can communicate with SAS computer, operator
workstation (OWS), engineering workstation (EWS), remote monitoring system, SNTP server.
In the SAS, the communication is served with the method of data transfer:
Report method of sending event messages like measurement, status, alarm and so on
GOOSE (Generic Object Oriented Substation Event) method of communication
between IEDs like interlock
Control method like controlling the circuit breaker (CB), the disconnector (DS), the
selector device (43), the transformer tap (TAP) and so on
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1181 -
6F2S1927 (0.18)
For the IEC 61850 communication, the IED consists of multiple logical devices and logical
nodes. The user should configure the 61850 Data Model to perform a required function for the
protection and control.
Modular approach achieves data transfer between devices in the IEC 61850 standard. All
function in the IEC 61850 network are grouped into smaller objects called Logical Nodes (LNs),
which contains process objects related data and attributes of a logical device protection and
control function. Logical Node Zero (LLN0) represents specific information of the logical device.
Logical Node Physical Device (LPHD) represents specific information of a physical device. A
generic device is called Physical device (PD). The LPHD contains the properties of the PD. A
specific function in the IED is represented as domain specific LN. The domain specific LN
contains the essential function for target devices in the IEC 61850 network.
LN data model defines the abstract syntax and semantics of the information exchanged
between PDs. The relation between data object classes, data types, data attributes and
abstract data objects are provided in the LN data model. The LN data model is mapped to
Manufacturing Message Specification (MMS) and Generic Object Oriented Substation Event
(GOOSE) functions. Table 11.3-1shows the description of LNs.
All LN classes (LLN0 and domain specific LN) receive the mandatory data of the common LN
except LPHD. Table 11.3-2 exemplifies Function, Logical node and Communication service
used in the IEC 61850 communication.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1182 -
6F2S1927 (0.18)
Harmonics
measurement
Measuring
Control / Monitoring Protection function
Physical Model
“Logical Node” “Communication Service”
IEC 61850 Model Physical Device
LN Physical Device
LN LPHD LN
GOOSE
CB XCBR CALH
LN Enhanced-security Control
LN
CSWI
IHMI
LN Buffered Report
LN
CT PTOC
LN IARC
GOOSE
PTRC
LN
Buffered Report
VT PTUV
LN Unbuffered Report
MHAI
LN GOOSE
Binary
SIMG
Input
Figure 11.3-2 Example of Physical model and its equivalent IEC 61850 model
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1183 -
6F2S1927 (0.18)
The user can handle LGOS with signals shown in Table 11.3-3. The signals are provided for
mapping in the 61850 Editon2. Figure 11.3-3 shows an example that they are mapped for the
LGOS.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1184 -
6F2S1927 (0.18)
The LN contains data list with their attributes based on their functionality in SAS. A
data has a well-defined structure and information of SAS. The data and attributes of the LN
in a logical device are exchanged by the communication services according to IEC 61850
protocol. The communication services are implemented by SCSM using Ethernet TCP/IP
protocol.
The data structures of the GOOSE are illustrated in Table 11.3-4; they are grouped for
the system (say, SAS) and other logical devices (say, a relay); they are used in the applications
in the SAS and the IED.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1185 -
6F2S1927 (0.18)
(iii) System
The data model in the LN named “System” is not allowed to modify (that is, a data model is
fixed; other LN data models are configurable to meet the system requirement). Mapping
signals to the GGIO1 is required when the GOOSE should send data faster.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1186 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1187 -
6F2S1927 (0.18)
IED
*IEC 61850-7-4
Logical device1 CONTROL
Logical Node
Current
Application
Data Logical device2
BIO ・・・ GOOSE GOOSE
DataSet
Binary
Control Block (outgoing)
Logical Node
Input
Binary
Input
2. Mapping 1. icd(cid)
data
GOOSE
GOOSE subscribe function
(incoming)
3. GOOSE subscribe
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1188 -
6F2S1927 (0.18)
Add Substation, Voltage level, Bay and IED to the project tree
(→cf. sec. 11.3.3(i))
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1189 -
6F2S1927 (0.18)
Selection of IED
When user’s project has been created or is opened, the user can add new IEDs.
Figure 11.3-7 illustrates new IED has been added on the project tree.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1190 -
6F2S1927 (0.18)
Edition list
Edition 1
Edition1 display
Edition 1-Opetion
Edition1_Option display
Edition 2
Edition2 display
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1191 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1192 -
6F2S1927 (0.18)
Import CID/ICD
Export CID
Export ICD
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1193 -
6F2S1927 (0.18)
should check whether the required signals are mapped in the default
configuration.
To verify the signals configured for the IEC 61850 protocol, the user should check
the mapped data, Dataset or Report Control list. If they have existed, the signals
in the signal list should be matched with the attributes of LNs.
Figure 11.3-11 shows an example to check if the signals are mapped in default
configuration. For example, to check for mapping of the primary element signal
in earth fault protection (EF1), follow the steps below:
1. To check if the EF1 signal is already mapped in the LN, key ‘EF1’ under Signal
Name in the Signal List screen.
Mapped data
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1194 -
6F2S1927 (0.18)
3. To check, if the DataSet is already assigned to RCB, Right click on “LLN0” and
select Edit Report Control, then Report Control List screen appears as shown in
Figure 11.3-13.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1195 -
6F2S1927 (0.18)
Mapped data
Drop
Drag
Signals
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1196 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1197 -
6F2S1927 (0.18)
Edit DataSet
Dataset can be edited or a new dataset can be added for the LNs as shown in
Figure 11.3-17. For editing the DataSet, follow the steps below:
1. Right click LLNO and select Edit DataSet, DataSet List window appears as
shown in Figure 11.3-17.
2. Choose the variables to be added to the DataSet and click OK.
*Note: 100 DataSets can be added in the DataSet List and each DataSet can have
maximum of 32 elements.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1198 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1199 -
6F2S1927 (0.18)
If the user wishes to assign the DataID for GOOSE operation, follow the steps
below:
1. Click GGIO1 and select Ind1 as shown in Figure 11.3-19.
2. Drag and Drop the required signals to be sent by GOOSE.
Note: The user can assign any signal to GGIO1->Ind1~16 for high-speed GOOSE, as
required.
Drop
Drag
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1200 -
6F2S1927 (0.18)
Figure 11.3-20 shows the GOOSE Publish screen, where “System” is fixed and is
not configurable for GGIO1, whereas “Ctrl” (Control) and “Prot” (Protection) are
configurable. The user can add new variables from the “Logical Node” screen to
the GOOSE Publish screen using drag & drop* method. Figure 11.3-20 shows an
example for GOOSE Publish, where “System/GGIO2$Ind1$stVal” is added to the
GOOSE Publish screen.
*Note: Only “stVal” and “q” variables can be added to GOOSE Publish screen.
Drag
Fixed
Drop
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1201 -
6F2S1927 (0.18)
In the example shown below, select the required variable and click Add. Similarly,
the user can delete the variables.
When the user adds a signal to the GOOSE subscribe list from the other IED,
then the same signal is automatically added in the Signal List of the current
IED.
List 2
List 1 List 2
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1202 -
6F2S1927 (0.18)
For example, to let a device execute “Select”, “Operate” and “Cancel” commands
from the sever through “CSWI4” and transmit the information to an IED, the user
should map an input point (Data ID) to several variables of “CSWI4” (See Figure
11.3-22). Mapping period for Control shall be 100.
*Note: For more information of the input points, see chapter General control function or
Control and monitoring application, if available.
SBOW
Oper
DE V01_ CONTROL_ RE Q
Cancel
†Note:For more information for the BI, BO, see Chapter Technical description: Binary IO
module.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1203 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1204 -
6F2S1927 (0.18)
Note: The user can check the edition number through on the LCD screen. Therefore, the
user should confirm the edition number written in the IED too. See sec. 11.3.3(vi)
to show the LCD screen.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1205 -
6F2S1927 (0.18)
Scroll downward
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1206 -
6F2S1927 (0.18)
†Note:For example, Figure 11.3-27 shows the signal flow between a substation computer
(SC), an IED and a target device (e.g. CB). If the requirement is to close the CB on
request of the SC, the SC will send the operation command “Operate” to the IED;
the time information (T) is also sent along with the operation command. When
receiving the operation command and observing that the CB has closed, the IED
will send a response signal “CommTerm” to the SC along with the time
information. However, this time information is not the actual operation time of the
CB, but the same time information originally sent with the operation command.
The IEC 61850 standard defines this rule; hence, general operations in the IEC
61850 standard are subject to this rule. However, the server communication
provided by Toshiba is able to accept the actual operation time; hence, the setting
‘CommTerm’ is required in the Toshiba communication. The user should also note
that Off is set for the scheme switch [TCMD] as the default setting.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1207 -
6F2S1927 (0.18)
Command Open
Response
Process Closed
CommTerm+(T) Response
†Note:The user may wish to perform bad reception tests from a remote terminal using
the GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid the influence, we recommend the user to test bad receptions for a particular
IED using the GOSUBBLK function. As a result, testing will only affect the
particular IED under test i.e. all other terminals will not be influenced by the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1208 -
6F2S1927 (0.18)
tests.
SLAVE PROTOCOL
10:48 1/1
Slave protocol +
IEC61850
Figure 11.3-28 Slave protection for the IEC61850 protocol (LCD setting menu)
†Note:The menu is just screened when the IED has IEC61850 and another (e.g.,
IEC60870-5-103). The above one will not be screened when the IED has only the
IEC61850.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1209 -
6F2S1927 (0.18)
Qual_Validity
M/ Default
Attribute Name Attribute value O/
C1 value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1210 -
6F2S1927 (0.18)
(i) Qual_validity
Qual_validity (61850: Signal No. 301001 3110041005) is a signal provided for a common quality
information. It can be useful if some ‘q’ attributes (it’s defined in Quality type) should belong
to a common quality. Both severe and non-severe errors are included; therefore, that signal
value will be changed whenever errors (including alarm and warning incidents) are detected.
In this quality signal, the Detail quality information—defined in the standard—is not set at
all.
Detail quality
operatorblocked
badReference
questionable
outOfRange
inconsistent
inaccurate
oscillatory
overflow
oldData
source
invalid
failure
test
301001 3110041005
0 0 0 0 0 0 0 0 0 0 0 Qual_Validity
220001 3110111001
SERI_ERR
≥1
220001 3110121001
MINR_ERR
201301 3100001190
Test Mode
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1211 -
6F2S1927 (0.18)
On the LCD screen, the user can find either OK or NG message regarding other IEDs. The
OK/NG message is generated with the information of the GOOSE packet received. Table 11.3-7
illustrates the messages displayed on LCD screen and GR-TIEMS screen.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1212 -
6F2S1927 (0.18)
When the user wishes to see GOOSE outputs†, the user can see them by user’s PLC logic, but
the user should build its logic using the PLC function. Table 11.3-8 shows the GOOSE signals,
which the user can select. For example, in order to get the GRL200_Bay1_4 information, the
user should take the GOOSE content using SUB_QUAL#3 output.
Note: The option1 is designed to transfer the metering values during the fault on the
IEC61850 Edition1.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1213 -
6F2S1927 (0.18)
11.3.10 Setting
Setting of 61850(Function ID: 301001)
Unit Default setting
Setting item Range Contents Notes
s value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1214 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1215 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1216 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1217 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1218 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1219 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1220 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1221 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1222 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1223 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1224 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1225 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1226 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1227 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1228 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1229 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1230 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1231 -
6F2S1927 (0.18)
11.4.1 Overview
For the communication in the IEC 60870-5-103 standard, the user should create the data with
regard the protocol, which is grouped into a slave and a master. The user can edit the slave
Data or the master Data using the GR-TIEMS.
(i) Management
As cited earlier, the IEC 60870-5-103 standard is grouped into the slave and the master. In an
IED the user should select either the master mode or the slave mode; the user should edit
either the master data or the slave Data. The both modes can provide the same functions
equally. The GR-TIEMS can provide the user the management means for the following data.
Data management
Import data are provided in the CSV file. The data are categorized as “adding items”,
“editing items”, “deleting items”, and “arranging items”.
Process management
Creation of the new data
Registration, clear, and change name of a slave IED
Registration and clear of signals
Edition of the dialog prototype
External Interfaces
Logging and Access Security
(ii) Configuration†
Table 11.4-1 and Table 11.4-2 show that the items should be programmed using the GR-TIEMS.
We shall see how to set and edit data of the IEC 60870-5-103 configuration in section 11.4.5
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1232 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1233 -
6F2S1927 (0.18)
Data request
Data request
Response frame
Figure 11.4-1 Ping cycles between the master station and the IED
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1234 -
6F2S1927 (0.18)
11.4.3 Interoperability
The IEC 60870-5-103 protocol provides a physical layer and an application layer for the
communication to secure the interoperability.
Optic interface
Several optic communication modules are available
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1235 -
6F2S1927 (0.18)
(iv) Commands2
The user can customize the supported commands. The IED can replay for unsupported
commands using the cause of transmission (COT) negative acknowledgement of a command.
1Note: With regard to the GI list, see Appendix IEC 60870-5-103 interoperability. When
the user wishes to understand the details, refer to the section 7.4.3 of the IEC
60870-5-103 standard.
2Note: For details, refer to the section 7.4.4 of the IEC 60870-5-103 standard.
3Note: For details, refer to the section 7.4.5 of the IEC 60870-5-103 standard.
4Note: For details, refer to the section 7.4.6 of the IEC 60870-5-103 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1236 -
6F2S1927 (0.18)
Measurand period
This setting is used to set the transmission cycle (s) of Measurand frame. The setting range
is 0 to 60s. If no Measurand frame is provided by measurand setting, this setting is disabled.
GRD200 software:
- 1237 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
The test mode in the IEC 60870-5-103 standard is enabled by the operation on the IED
screen or the GR-TIEMS. When the set signal changes “ON” and Time-tagged message or
Time-tagged measured of spontaneous cause (COT=1) or measurand frame or cyclic
transmission (Type ID=3 or 9) occurs, its COT shifts COT=7 (Test mode).
The time (ms), which is from the establishment of a set signal to the detection of a
status change, is added the set frame as RET value. FAN (Fault number), attached the
frame of Type ID=2 or 4, has the same number during the set signal ON. (Whenever the set
signal is ON, the FAN increases.) When setting to “0”, RET value is always “0” (RET=0).
The default setting is set to the OR signal of elements operation. When Type ID=2 frame is
provided with OC trip as send condition, for example, the time from OC element operation
to OC tripping is attached to the frame as RET. Though, the RET of GI frame is always “0”
in spite of this setting.
T1
T2
T3 t
Signal “ON” Type ID=2 Type ID=4 Signal “OFF” Type ID=2
i occurs ii occurs iii occurs
Figure 11.4-4 Occurrences after the signal “ON”
GRD200 software:
- 1238 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
When the “Time-tagged message” tab is selected, the “Time-tagged message” setting
screen is displayed on the start screen.
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative
time) can be set in this screen. In one frame of Time-tagged message, the Type ID, INF,
FUN, DPI and COT must be set and the maximum 256 frames of Time-tagged message can
be set. The information number of the frame is determined by the INF setting. The most
left item “No.” is only serial number and can be skipped.
Common address is linked with the address setting† in the IEC 60870-5-103 standard.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.
In the transmission format of Type ID=1 (Time-tagged message) and Type ID=2 (Time-
tagged message with relative time), customized items are shown in Table 11.4-3 and Table
11.4-4.
Table 11.4-3 Time-tagged message (Type ID=1)
Oct. Item Value Remarks
1 Start 68H
2 Length 14
3 Length 14
4 Start 68H
5 Control field 08H+ACD+D
FC
6 Address 1-254 Setting from the relay
7 Type identification (Type ID) 1 Customized by GR-TIEMS
8 Variable structure qualifier 81H
9 Cause of transmission (COT) 1/9/11/12 Customized by GR-TIEMS
GRD200 software:
- 1239 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of IEC 60870-5-103 communication.
GRD200 software:
- 1240 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
relay. If the setting value (signal No.) is “0”, all setting items related events are disable and
the frame is not provided.
†Note:A relevant Data ID is required to select; the description is obtained
automatically.
Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-5 and the
Appendix†.
Table 11.4-5 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 Status
32 to 47 Supervision
48 to 63 earth fault
64 to 127 short circuit
128 to 143 auto-reclosure
144 to 159 Measurands
160 to 239 not used
240 to 255 generic functions
†Note:See Appendix: IEC 60870-5-103 interoperability: Semantics of Information
number.
FUN
Function type (FUN) is set referring to Table 11.4-6. The FUN can be set to 0 to 255. When
clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 11.4-6 Semantics of Function type
0 - 127 private range
128 distance protection
129 not used
144 not used
145 not used
160 overcurrent protection
161 not used
176 transformer differential protection
177 not used
192 Line differential protection
GRD200 software:
- 1241 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
DPI/Off, DPI/On
Double-point information (DPI) is set using the menu as follows:
DPI/Off: The frame is transmitted when the DPI/Sig.No. signal is OFF.
DPI/On: The frame is transmitted when the DPI/Sig.No. signal is ON.
Note: If selecting “-”(=don’t care), the frame is not transmitted even though the
DPI/Sig.No. signal set change to the set status. In general, the frames related
to tripping such as “Time-tagged message” and Time-tagged measurand”, etc.,
which are not an object of GI (General Interrogation), are not transmitted
when the DPI changes “On” to “Off”. In this case, set the “DPI/Off” to “-”(=don’t
care).
Note: When selecting “DP” for both “DPI/Off” and “DPI/On”, the DPI number is
transmitted as the number (=0/1/2/3) using the same information number
(INF). Regarding the frame related to a device control, the “undefined/failed”
status may be required in addition to the “close/open” status for the extension.
When selecting “DP”, “undefined(00)/close(01)/open(10)/failed(11)” status is
applied in the same information number (INF).
COT
Cause of Transmission (COT) of the frame is set. Not only one COT but also two or more
COT can be selected each No. (frame). COT setting pattern and COT supplemented the
frame are as follows:
(1) If two or all of COT=1, 11 and 12 are checked per No., each frame of the No. become
the following conditions.
Table 11.4-7 COT
COT Conditions
COT=12
TR[ms] after receiving any command of the IEC 60870-5-1031
(remote operation)
COT=11
TL[ms] after Key operation on the relay front panel1
(local operation)
(2) If one of COT is specified per No., the frame is always supplemented with the
GRD200 software:
- 1242 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Table 11.4-8 shows the summary of (1), (2) and (3) above.
Table 11.4-8 COT setting pattern and COT supplemented frame
COT setting
pattern COT supplemented frame when status changes GI
1 9 11 12
Always “1” No
Events don’t occur. Yes
Always “11” No
Always “12” No
Always “1” Yes
“11” (cause at local) or “1” (other causes) No
“12” (cause at remote) or “1” (other causes) No
Always “11” Yes
Always “12” Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) No
“11” (cause at local) or “1” (other causes) Yes
“12” (cause at remote) or “1” (other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) No
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) Yes
“11” (cause at local) or “12” (cause at remote) or “1”
(other causes) Yes
Always “1” in spite of cause of event occurrence No
Note: When being in the test mode, the COT=1(Spontaneous) is shifted to 7(Test
mode)
GRD200 software:
- 1243 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
When the “Time-tagged measurand” item is selected on the GR-TIEMS, the setting
screen is displayed.
Type ID=4 (Time-tagged measurand with relative time) can be set in this screen. In
one frame of Time-tagged measurand, the INF, FUN, Sig No., Rev, COT and SCL must be
set and the maximum eight frames of Time-tagged measurand can be set. The information
number of the frame is determined by the INF setting. The most left item “No.” is only serial
number and can be skipped.
In the transmission format of Type ID=4 (Time-tagged measurand with relative time),
customized items are shown in Table 11.4-9.
GRD200 software:
- 1244 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
The frame cannot be set to the object of GI and cannot be transmitted even though the
status of set signal changes from ON to OFF. If the metering values at the newest fault
record are transmitted as the status change frame, select the Data ID of “F.Record_DONE”
or “FAULT RECORD DONE” in the signal list of the relay.
†Note:A relevant Data ID is required to select in the signal list. The description of the
Data ID is obtained automatically on the setting.
Inverse
This setting is used to invert the logic of the signal assigned to the Data ID above. If the
frame is transmitted when the signal assigned to the Data ID is ON, leave the Inverse check
box blank. If the frame is transmitted when the signal is OFF, click the inverse check box
to be marked with “”.
Type ID
Type ID=4 (Time-tagged measurand with Relative time) is fixed. In Type ID=4, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the fame
out of the standard is provided, the INF should be set referring Table 11.4-3 and the
Appendix†.
†Note:For more information, see Appendix: IEC 60870-5-103 interoperability.
GRD200 software:
- 1245 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
FUN
Function type (FUN) is set referring to the Table 11.4-4. The FUN can be set to 0 to 255.
When clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed
to the setting values at Common setting.
COT
Cause of Transmission (COT) of the frame is set. Not only one COT but two or more COT
can be selected each No. (frame). COT setting pattern and COT supplemented the frame
are according to Table 11.4-6. Though, the COT=9 (General Interrogation) cannot be
selected.
Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The SCL is a value which the power system quantity specified as above is
multiplied by this setting value.
GRD200 software:
- 1246 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
When the “General command” item is selected on the GR-TIEMS, the setting screen
is displayed.
The frame of Type ID=20 (General command) and Command ACK/NACK can be set
in this screen. In one command of General command, the INF, FUN and DCO must be set.
The Command ACK/NACK is for detail setting and must not be set usually. (If do not check
the Ext check box, the setting of Command ACK/NACK is disabled and the Command ACK
and Command NACK respond according to the default response.)
The maximum 32 frames of General command and Command ACK/NACK can be set.
The information number of the frame is determined by the INF setting. The most left item
“No.” is only serial number and can be skipped.
In this setting screen, if a Data ID except “0” is set to “Sig Off” and “Sig On”, the
command at INF setting value is provided and Command ACK or Command NACK is sent
back when receiving the command from upper station. If both “Sig Off” and “Sig On” have
“0”, the fixed length NACK is always sent back then and the command is not provided.
Though the command is provided, however, Command NACK is always sent back and
no control is performed in the following cases:
(1): When receiving any General command from the upper station before Command
ACK/NACK is sending back from the relay.
(2): Under Monitor direction block condition (“IECBLK” setting is “blocked”.) when
receiving General command.
(3): When receiving an incorrect value of DCO of General command, that is DCO is neither
“1” nor “2”.
GRD200 software:
- 1247 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Primary Secondary
station station
General
Command
ACK
Class 1
Command
ACK/NACK
In the transmission format of General command (Type ID=20), customized items are
shown in Table 11.4-10.
GRD200 software:
- 1248 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Any comment with maximum 16 characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Type ID
Type ID=20 (General command) is fixed.
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided†, the INF according to the standard is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-12 and the
appendix†.
Table 11.4-12 INF category of Monitor direction
INF Category
0 to 15 system functions
16 to 31 status
32 to 239 not used
240 to 255 generic functions
GRD200 software:
- 1249 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
FUN
Function type (FUN) applied to a command response frame is set referring to Table 11.4-13.
The FUN can be set to 0 to 255. When clicking the “Change all FUNs” on the Common
setting screen, all FUNs are changed to the setting values at Common setting.
DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc.,
Inverse
“Sig off” and “Sig On” are used to set the Data ID of control object in General command.
(Hereafter, these are described as “command output signal”.) “Inverse” is used to reverse
the logic when controlling the command output signal.
When the command output signal is treated as two signals (Sig Off Sig On), the
control scheme is shown as the following table by the combination of the receiving command
DCO and Inverse setting.
For example, when the DCO=Off command is received under “Inverse” no-checked,
the command output signal of “Sig Off” is controlled to “1”. “Sig On” is not controlled.
Table 11.4-13 Control Scheme of Command Output Signal (Sig Off Sig On)
“Inverse” checked Checked No-checked
Control object
Signal specified Signal specified Signal specified Signal specified to
Receiving
to Sig.off to Sig.on to Sig.off Sig.on
command DCO
When the command output signal is treated as one signal (Sig Off Sig On), the
control scheme is shown in Table 11.4-14. For example, when the DCO=On command is
received under “Inverse” checked, the command output signals of “Sig On” and “Sig Off” are
controlled to “0”. “Sig On” is not controlled.
Table 11.4-14 Control Scheme of Command Output Signal (Sig Off = Sig On)
“Inverse” checked Checked No-checked
Control object
Signal specified Signal specified Signal specified Signal specified
Receiving
to Sig.off to Sig.on to Sig.off to Sig.on
command DCO
When setting the “Sig Off”, “Sig On” and “Inverse”, check the specifications of the
command output signals of communication and others, and then set them.
Valid time
GRD200 software:
- 1250 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Valid time is used to set the time (ms) to control the command output signal. The command
output signal is controlled based on the control scheme described in section 11.4.5(iv)-5 for
the setting time after receiving General command, and is reset by communication side after
the set time. However, if the time is set to “0”, the control is not reset and is continued. Set
the time with a margin for interface of other applications.
ACK/NACK / Ext
This setting is used to enable the extension setting of Command ACK/NACK response
scheme or not. If “Ext” is not specified (Ext check box is not checked.), Command NACK (in
cases of (1)–(3) of the section 11.4.5(iii) and Command ACK (in case of others) respond
according to the default response. If “Ext” is specified, the setting of Command ACK/NACK
described later is enabled and the response scheme can be customized. When required the
stricter handshake by using Command ACK/NACK, it is better to specify the “Ext”. This
setting is not influenced by the control scheme of the command output signal.
When the command response signal is treated as two signals (ACK Sig NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is when (1), (2), (3) or (4) in Table
11.4-15 is established. If the neither (1), (2), (3) nor (4) is established (that is ACK sig =
NACK Sig = 1 or ACK sig = NACK Sig = 0) for the period from the command receiving to
the timeout setting time, Command NACK responds at that time.
For example, when the DCO=On command is received under “Inverse” no-checked,
Command ACK responds in case of “ACK Sig = 0” and NACK Sig = 1”.
Table 11.4-15 Judgment Scheme of Command Response (ACK Sig NACK Sig)
“Inverse” checked No-checked Checked
When the command response signal is treated as one signal (ACK Sig = NACK Sig),
the judgment scheme is shown as the following table by the combination of the receiving
command DCO and Inverse setting. The judgment timing is after the timeout setting time
GRD200 software:
- 1251 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
For example, when the DCO=On command is received under “Inverse” checked,
Command ACK responds in case of “ACK Sig = NACK Sig = 1” after the timeout setting
time.
Table 11.4-16 Judgment Scheme of Command Response (ACK Sig = NACK Sig)
“Inverse” checked No-checked Checked
GRD200 software:
- 1252 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
When the “Measurands” item is selected on the start screen of the GR-TIEMS, the
setting screen is displayed.
In one frame of Measurand, the Type ID, INF, FUN settings, and its position setting
(Measurement Name/Measurement Description/Lower Limit/Upper Limit/Coefficient)
must be set. “No.” shows the position of power system quantity. (For details, describe later.)
The maximum 16 items of Measurands and the maximum 32 power system quantities per
one frame can be set.
GRD200 software:
- 1253 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
In the transmission format of Measurand I (Type ID=3) and Measurand II (Type ID=9),
customized items are shown in Table 11.4-17.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function of the IEC 60870-5-103 communication.
Type ID
Type ID=3 (Measurands I) or Type ID=9 (Measurands II) can be selected to set the frame
type of Measurand frame. In general, the maximum MEA number of Type ID=3 uses 1 or 2
or 4 and that of Type ID=9 uses 9. (However, the maximum MEA number of both types can
extend up to 32 in the GR-TIEMS. In this case, there are no difference between the
transmission format of Type ID=3 and that of Type ID=9.)
INF
Information number (INF) of the Measurand frame is set. The INF can be set to 0 to 255.
When the standard frame† is provided, the INF according to the standard is recommended.
If the fame out of standard is provided, the INF should be set referring Table 11.4-3
and the appendix†.
FUN
Function type (FUN) of the Measurand frame is set referring to the Table 11.4-4. The FUN
can be set to 0 to 255. If click the “Change all FUNs” on the Common setting screen, all
FUNs are changed to the setting values at Common setting.
GRD200 software:
- 1254 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
Name
Any comment with maximum eight characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
If MEA value exceeds the full scale (if the value expressed as B1 to B12 is less than
4096 or more than 4095), the MEA is clamped at 4096 or 4095 and OV flag is established.
However, if IV flag is established, OV flag is not established.
Coefficient
Set the conversion coefficient, multiplied the power system quantities by, using floating-
point number. The MEA is a value which the power system quantity specified as above is
multiplied by this setting value.
GRD200 software:
- 1255 - 03D, 03E, 03F, 030, 032, 036, and 039
6F2S1927 (0.18)
SLAVE PROTOCOL
10:48 1/1
Slave protocol +
IEC103
Figure 11.4-11 Slave protection for the IEC103 protocol (on IED setting menu)
Note: The menu is just screened when a couple of communication protocols are
embedded in the IED.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1256 -
6F2S1927 (0.18)
Figure 11.4-12 shows the editing screen of the GR-TIEMS; the screen has a remark field
concerning to the IEC 60870-5-103 communication. Note the available length of the remark
field is up to 12 in the one-byte character. The remark field is utilized for the control of the
setting data.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1257 -
6F2S1927 (0.18)
11.4.8 Setting
Setting of 103_SLAVE (Function ID: 304001)
Unit Default setting
Setting item Range Contents Notes
s value
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1258 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1259 -
6F2S1927 (0.18)
USB communication
The IED front panel has an USB receptacle in a B-type to connect with a local PC for
engineering. The user can select a transmission speed, which is shown below, by the operation
of the setting menu, as shown in Figure 11.5-1.
USBCOM
10:48 1/1
USBCOM_BRATE_SW +
921.6kbps
USBCOM_BRATE_SW 115.2 / 921.6 kbps Baud rate Switch for USB Com port 921.6
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1260 -
6F2S1927 (0.18)
RS485 communication
When the IED has an RS485 module for the communication, the user can select and set its
transmission and error check parity codes. Figure 11.6-1 shows the setting screen when the
RS485 module (#1) operates.
RS485
10:48 1/2
RS485_1_BRATE_SW +
19.2kbps
RS485_1_BRATE_SW +
NONE
Module RS485_1_BRATE_SW 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbps Transmission speed 19.2
#1 RS485_1_PAR_SW NONE / ODD /EVEN – Parity check code NONE
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1261 -
6F2S1927 (0.18)
12 User interface
Contents Pages Pages
Outline 1263 Time sub-menu 1305
-Front panel 1263 -Clock 1305
-LCD screen 1263 -Time zone 1306
-LEDs 1263 -Time synchronization 1307
-Function Keys 1264 -Display format 1309
-Operation Keys 1265 -Summer time(DST) 1311
HMI operation 1266 Test sub-menu 1313
-General operation 1266 -Test screen 1313
-Main-menu and sub-menu 1266 -Test mode screen 1313
Record sub-menu 1269 -Test flag enabling screen 1317
-Fault record 1269 -Mode change screen 1318
-Event record 1272 -Signal monitoring screen 1318
-Disturbance record 1274 Information sub-menu 1319
Monitoring sub-menu 1276 Security setting sub-menu 1320
-Metering 1276 Control sub-menu 1321
-Binary I/O 1276 -CB operation 1322
-Communication 1277
-Relay elements 1279
-Statistics 1280
-Goose monitoring 1282
-Diagnostics 1283
Setting sub-menu 1284
-Setting method 1284
-Confirmation dialog 1288
-On/Off 1291
- Group setting 1291
-Function key 1293
I/O setting 1297
-AC analog input 1297
-Binary input 1299
-Binary output 1301
-LED 1303
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1262 -
6F2S1927 (0.18)
Outline
Users can perform maintenance on the IED from the front panel. Monitoring is also possible
locally by using a PC connected through the USB cable. This section discusses the
configuration of the front panel and the basic configuration of the screen-menu hierarchy of
the Human Machine Interface (HMI).
LEDs
LCD screen
Operation keys
Function keys
with LEDs
(iii) LEDs
As shown in Table 12.1-1, 26 LEDs, each having signal labels and colors, are defined:
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1263 -
6F2S1927 (0.18)
. N/A N/A ✔ .
. . . . .
. . . . .
. . . . .
26 N/A N/A ✔
1Note: LED3 to LED26 are user-configurable. Users can use them with or without latch
function.
2Note: For setting LEDs, see section 12.6(iv).
3Note: For Reclosing relay, LED4 is named “OPERATE”. When the ARC function runs,
the LED comes on; the LED will not turn off until CLEAR key is pressed.
†Note: The user can program to light the LEDs by itself. Setting are similar to the ones
of the Table 12.1-1 (For setting, see section 12.6(iv)). Note the manufacture
programs to light the respective LEDs in default prior to shipping.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1264 -
6F2S1927 (0.18)
ENTER Enter edit mode, if item is active / Executive operation / Accept alarm
message.
CLEAR Clear all latched LEDs (Except [In service] and [Error] LEDs).
HELP Display the help message, for cases where the active item has a help
function.
L
R
Switch between Local mode and Remote mode.
MENU Switch for using MIMIC2 mode or for returning back to the menu screen.
MIMIC
This key is not provided for standard LCD screen2.
1Note: To scroll up or scroll down quickly, press keys ▲ or ▼ respectively along with key
►.
2Note: The MIMIC key is only available when Large LCD screen is mounted on the front
panel. The pixel resolution (dot) is 240(W) × 320(H). Note that this mode is only
provided when the user programmed the feature using GR-TIEMS engineering
tool. See chapter Engineering tool: MIMIC configuration tool.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1265 -
6F2S1927 (0.18)
HMI operation
By using the LCD screen, the operation keys and the function keys, the user can access
functions such as recording, monitoring, relay setting and testing.
Note: The operation of the LCD screen is more or less common in all IED models.
However, the contents of the LCD screen depend upon the IED model.
Sub-menu
An example of setting the sub-menu screen is shown in the right of Figure 12.2-1. By
using the key ▼ and the key ▲, the user can move the cursor downward or upward
to view all of the items. By using the keys ◄ ►, the user can return to a previous
level of hierarchy or go to the next level of hierarchy.
Screen structure
The screen is composed of a title area and a data area. The title area is fixed on the
top two lines. The first line displays the screen title. The second line on the left-hand
side displays local time, whereas the right-hand side displays either the current line
number, cursor position number and the maximum page number, or the item number.
For example, the display “2/4” means the current cursor position, which is at the
second item of a maximum of four items.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1266 -
6F2S1927 (0.18)
Main Menu OC
10:48 1/8 10:48 2/4
_Record > OC1EN +>
Monitoring > On
Setting > _OC2EN +>
I/O Setting > On
Time > OC3EN +
Test > Off
a. Main Menu b. Sub Menu
Figure 12.2-2 shows the menu hierarchy. The menu consists of a Main-Menu and several
Sub-menus. Table 12.2-1 shows the configuration of Main-Menu.
Common
Security Setting Change Password
PLC-TIMER
Active Group
Copy Group(A->B)
Security
Group1
Group2
Group3
Group4
Login / Logout
Group5
Group6
Group7
Group8
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1267 -
6F2S1927 (0.18)
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1268 -
6F2S1927 (0.18)
Record sub-menu
The Record sub-menu is composed of several sub-menus: fault record, event record,
disturbance record, and clearance of all records. In each sub-menu, the user can clear records
separately.
Record
10:48 1/6
_Fault Record >
Event Record1 >
Event Record2 >
Event Record3 >
Disturbance Record >
Clear All Records +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1269 -
6F2S1927 (0.18)
Record
1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Fault Record
2). Fault Record screen is displayed. Press ► at the Record List sub
10:48 1/2 menu.
_Record List >
Clear Records +
Fault Record
3). Fault record list in the Fault Record screen is displayed. Move
10:48 1/6 cursor to a desired item by ▲ or ▼ and press ►.
#1 2012-07-25 >
10:48:21.223
#2 2012-07-21 >
01:15:55.018
#3 2012/07/20 >
13:11:29.621
Fault Record#2
4). Press ▲ or ▼ to move display items.
10:48 1/222
2012-07-21
01:15:55.018
DIFZA
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1270 -
6F2S1927 (0.18)
Record
1). Move cursor to the Fault Record menu and press ►.
10:48 1/6
_Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Record
1). Move cursor to the Clear all Records sub menu and press ENTER.
10:48 1/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
_Clear all Records +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1271 -
6F2S1927 (0.18)
Event record1
10:48 1/3
#1 2012-07-25
10:48:21.223
Set.Group change
2
#2 2012-07-25
10:20:21.021
Record
1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
10:48 2/6
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
Event Record1
2). Event Record screen is displayed. Press ► at the Record List sub
10:48 1/2 menu.
_Record List >
Clear Records +
Event Record1
3). Press ▲ or ▼ to move display items.
10:48 1/3
#1 2012-07-25
10:48:21.223
Set. Group change
2
#2 2012-07-25
10:20:11.021
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1272 -
6F2S1927 (0.18)
Record
1). Move cursor to Event Record 1, 2, or 3 sub menu and press ►.
10:48 2/6
Fault Record >
_Event Record 1 >
Event Record 2 >
Event Record 3 >
Disturbance Record >
Clear all Records +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1273 -
6F2S1927 (0.18)
Disturbance record
10:48 1/6
#1 2012-07-25
10:48:04.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621
Record
1). Move cursor to Disturbance Record sub menu and press ►.
10:48 2/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +
Disturbance Record
2). Disturbance Record screen is displayed. Press ► at the Record List
10:48 1/2 sub menu.
_Record List >
Clear Records +
Disturbance Record
3). Press ▲ or ▼ to move display items.
10:48 1/6
#1 2012-07-25
10:48:21.223
#2 2012-07-21
01:15:55.018
#3 2012-07-20
13:11:29.621
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1274 -
6F2S1927 (0.18)
Record
1). Move cursor to Disturbance Record sub menu and press ►.
10:48 2/6
Fault Record >
Event Record 1 >
Event Record 2 >
Event Record 3 >
_Disturbance Record >
Clear all Records +
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1275 -
6F2S1927 (0.18)
Monitoring sub-menu
“Monitoring” sub-menu is used to display the current status of the IED. The data is updated
every second on the LCD screen. The user can view the following functions from the Monitoring
sub-menu:
i. Metering sub-menu
ii. Binary I/O sub-menu
iii. Communication sub-menu
iv. Relay Elements sub-menu
v. Statistics sub-menu
vi. GOOSE Monitoring sub-menu
vii. Diagnostics sub-menu
(i) Metering
The value and direction of current, voltage etc. can be displayed. The user can change the units
as required by using the appropriate setting. Figure 12.4-1 shows an example of the Metering
sub-menu.
Metering
10:48 1/25
Va
23.231kV 121.34deg
Vb
23.200kV 120.14deg
Vc
22.713kV 121.50deg
Slot#1
10:48 1/12
BI1 0 CB1 contact
BI2 0 DC power sup.
BI3 0 Trans-T Comm1
BI3 0 Trans-T Comm2
BI4 0 ARC-Block1
BI5 0 Indi. Reset
Figure 12.4-3 shows the steps required to display the status of the binary inputs and outputs.
► ◄
Slot#1 Slot#1
10:48 2/12 10:48 1/12
BI1 0 CB1 contact ▲ BI1 0 CB1 contact
BI2 0 DC power sup. BI2 0 DC power sup.
BI3 0 Trans-T Comm1 BI3 0 Trans-T Comm1
▼
BI3 0 Trans-T Comm2 BI3 0 Trans-T Comm2
BI4 0 ARC-Block1 BI4 0 ARC-Block1
BI5 0 Indi. Reset BI5 0 Indi. Reset
(iii) Communication
The “Communication” sub-menu provides several sub-menus as shown in Figure 12.4-4.
61580STAT
LAN sub-menu: the communication port name and status are shown in a line.
When the IED has single communication module, or when the IED has
communication modules but a communication module is allowed to operate in
the IED, an operation status of the communication ports is shown, as shown
in Figure 12.4-5.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1277 -
6F2S1927 (0.18)
LAN
10:48 1/2
PortStatus >
NetMonitor Inactive
The following two sub-menus are displayed to show the communication status
when the IED has dual LAN communication modules.
PortStatus PortStatus
10:48 1/2 10:48 1/2
*Port1_Link UP *Port1_Link UP
Port2_Link DOWN Port2_Link UP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1278 -
6F2S1927 (0.18)
61850STAT
10:48 1/6
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
255.255.255.255:0
0/ 0
OC
10:48 1/25
OC1-A 0
OC1-B 0
OC1-C 0
OC2-A 0
OC2-B 0
OC2-C 0
► ◄
OC
10:48 1/25
OC1-A 0
OC1-B 0
OC1-C 0
OC2-A 0
OC2-B 0
OC2-C 0
(v) Statistics
“Statistics” sub-menu has several sub-menus.
Counter
Accumulated Time
Operation Time
Operation Counter
Total Time
Power Value sub-menu: With regard to statistics item, the name and its value
are shown below. The user can also change the unit of each value by the
setting1. It is allowed to reset or revise the statistics value2.
Power Value
10:48 1/4
Wh+ +
0.0MWh
Wh- +
0.0MWh
varh+ +
0.0Mvarh
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1280 -
6F2S1927 (0.18)
and it is not "78,456kW" or "123,456kW". Note that the compensated value will be
affected when there is a change in CT ratio setting. That is, when the user key in a
value of "78MW" for the CT ratio of "2000:1" and later when the CT ratio is changed
from "2000:1" to "4000:1", then the value is displayed as "156MW" on the IED screen.
Therefore when the CT ratio setting is changed, the user should key in the value of
"78MW" again to display the compensated value.
Counter sub-menu: the name and number of statistical items are shown in
two lines. When an item is revised, a [+] mark is shown at the end of the first
line.
Counter
10:48 1/32
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1281 -
6F2S1927 (0.18)
► ◄
CANCEL Counter
ENTER 10:48 1/32
Count1(No Assign) +
0
COUNT2 (No Assign) +
The data has been revised. 1
COUNT3 (No Assign) +
0
Accumulated Time sub-menu: Total time for which the IED has been running
is shown in “d (date) h (hour) m (minute)” format. The user can clear the total
time value by clear operation (reset), which is shown in Figure 12.4-14.
ENTER
GOOSE Monitoring
10:48 1/3
GRx200-11-603 OK
GRx200-21-603 OK
GRx200-31-603 NG
(vii) Diagnostics
Error message will be published in Automatic supervision. If there are no errors, an error
message is not displayed.
Diagnostics
10:48 1/2
PLC data error
>
Data(commslv) error >
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1283 -
6F2S1927 (0.18)
Setting sub-menu
"Setting" sub-menu is used to view and change settings for the following functions: Recording,
Metering, Communication interface, Relay application, and Monitoring. In this section, we
show the “Setting method for elements, switches, and list selection”, “Protection setting”, and
others. Furthermore, this section describes the confirmation of setting, and the “On/Off”
function that is used to hide some unnecessary settings.
Note: The meaning of settings and their setting process are beyond the scope of this
section. The figures in this chapter are examples only. The user should confirm
setting values after their values are changed.
Element Setting Mode: The “Element Setting Mode” is used for setting
numerical values. For each setting, the setting name, setting value and the
unit are displayed in two lines. Figure 12.5-1 provides an example of the
element setting mode.
OC1 OC1
10:48 2/8 10:48 2/8
_OC1-b + *OC1-b +
123.00000 124.00000
OC1-c + OC1-c +
1.00000 1.00000
OC1-angle + OC1-angle +
45 deg 45 deg
To begin the setting process, press the key ENTER. Once the setting has been
changed, the [*] mark will appear alongside the name of the setting. Once the
change is canceled or confirmed, the [*] mark will disappear automatically. For
the setting of a value, follow the steps as shown in Figure 12.5-21:
[▲] [▼]
[CANCEL] [CANCEL]
OC1 OC1
OC1
10:48 2/8 10:48 2/8
10:48 2/8
*OC1-b + [▼] *OC1-b + [ENTER] *OC1-b +
124.00000 124.00000
124.00000
_OC1-c + [▲] OC1-c +
OC1-c +
1.00000 1.00000 [ENTER] 1.00000
OC1-angle + OC1-angle +
OC1-angle +
45 deg 45 deg
45 deg
Table 12.5-1 Operation example when the operation keys are pressed.
Before Key After
1 2 6 7 9
1 2 6 8 0
[▲]
9 1 7 1 0 1 7
9 1 7 [▼] 1 0 9 1 7
9 . 1 1 0 9 . 1
6 7 5 6 7 5
[◄]
1 . 7 5 1 . 7 5
2 1 : 2 3 [►] 2 1 : 2 3
Switch Setting Mode: The “Switch Setting Mode” is a setting used for the
selection of two modes. Figure 12.5-3 provides an example of the switch
setting mode. For each setting, the setting name and the selected item are
OC1 OC1
10:48 24/56 10:48 24/56
_OC1-VTFBlk + *OC1-VTFBlk +
Non Block
OC1-UseFor + OC1-UseFor +
Trip Trip
OC1-OPMD + OC1-OPMD +
3POR 3POR
To begin the setting process, press the key ENTER. Once the setting is changed,
the [*] mark will appear alongside the name of the setting. When the change is
canceled or confirmed, the [*] mark will disappear automatically. Figure 12.5-4
shows the operation of the switch setting mode.
[CANCEL]
[ENTER] [ENTER]
OC1 OC1
10:48 24/56 10:48 24/56
*OC1-2fBlk + *OC1-2fBlk +
[▼] Block
Block
_OC1-UseFor + OC1-UseFor +
Trip [▲] Trip
OC1-OPMD + OC1-OPMD +
3POR 3POR
setting-screen, the setting name and the selected item are displayed. Press
the key ENTER to begin the setting process; the screen for selection list will
appear. Once a setting has been changed, the [*] mark will appear alongside
the name of the setting. When the change is canceled or confirmed, the [*]
mark will disappear automatically.
[CANCEL] [ENTER]
OC1 OC1
10:48 23/56 10:48 23/56
*OC1-2fBlk + [▼] *OC1-2fBlk +
Block-3P Block-3P
_OC1-VTFBlk + OC1-VTFBlk +
Non [▲] Non
OC1-UseFor + OC1-UseFor +
Trip Trip
Signal Selection Mode: Figure 12.5-6 shows the steps to select a signal.
[CANCEL] [ENTER]
F1 Key
10:48 1/2
*Signal +
423100 AF00001001
Logic +
Toggle
[►] [◄]
OC OC Trip
10:48 1/4 10:48 1/4 10:48 1/12
*OC1EN +> [ENTER] *OC1EN + [►] *OC >
On On UV >
OC2EN + OC2EN + ZS >
Off [CANCEL] Off [◄] ZG >
OC3EN + OC3EN + EF >
Off Off DIFF >
OC [CANCEL] OC Group1
10:48 1/4 10:48 1/4 10:48 2/3
*OC1EN +> *OC1EN +> [◄] x 2 Telecommunication >
Off Off *Trip >
OC2EN + [ENTER] OC2EN + Autoreclose >
Off Off
[►] x 2
OC3EN + OC3EN +
Off Off
[◄]
Protection Protection
[ENTER]
10:48 3/10 The changed Setting
Active group > Change setting?
is confirmed. ENTER=Yes CANCEL=No
Copy gr.(A->B) >
_Group 1 >
Group 2 > The changed Setting
Group 3 > [CANCEL]
Group 4 >
is canceled.
[►] [◄]
[ENTER] [CANCEL]
IEC61850 Setting
Communication
10:48 1/6 10:48 2/5
*850BLK + [◄] [◄] Change setting?
LAN >
Block ENTER=Yes CANCEL=No
*IEC61850 >
GSECHK + IEC103 >
ON
[►] Modbus >
SI1-1 + DNP >
254
Setting [ENTER]
The changed setting is
10:48 3/7
Record > confirmed.
Metering >
_Communication >
Protection > The changed setting is
Counter >
[CANCEL]
canceled.
Function key >
“On” indicates that the setting is enabled; the mark [>] will appear. More detail of the
settings provided within the hierarchy are described later.
“Off” indicates that the setting is disabled; the detailed settings are hidden, the mark [>]
is not indicated. The following figure shows the usage of On/Off function.
OC OC OC
10:48 1/4 10:48 1/4
[►] / [◄] /
10:48 1/4
*OC1EN +>
[ENTER] *OC1EN +> [▲] / [▼]
*OC1EN +
On On Off
OC2EN + OC2EN + OC2EN +
Off [CANCEL] Off [►] / [◄] / Off
OC3EN + OC3EN + [▲] / [▼] OC3EN +
Off Off Off
[ENTER]
Protection OC
10:48 1/4
[ENTER] Change setting? *OC1EN +
The changed ENTER=Yes CANCEL=No Off
setting is confirmed. [◄] x 3
OC2EN +
Off
OC3EN +
Off
Protection OC
10:48 3/10 10:48 1/4
Active group > *OC1EN +
Copy gr.(A->B) >
Return to the “OC” Off
_Group 1 > setting screen. OC2EN +
Group 2 > Off
Group 3 > OC3EN +
Group 4 > Off
operation of the power system. In the “Protection” sub-menu, the user can change the active
group and can copy the group settings. Jump to the “Element Setting Menu” if a relay setting
is required.
Change active group: An example for changing the active group is shown in
the following figure.
[▲] x 2 [▼] x 2
Protection
Protection
10:48 5/11
Common
Change Setting? [ENTER]
ENTER=Yes CANCEL=No Active Group +
1
Copy Group (A->B) >
Group 1 >
Group 2 >
[ENTER]
Protection
10:48 1/10
Common
The changed [►]
Active Group >
setting is confirmed. Copy Group(A->B) >
Group 1 >
Group 2 >
Group 3 >
Copy group setting: The user can copy an active setting from one group to
another group. As an example, in the following figure “Group3” will be copied
to “Group2”, as shown in Figure 12.5-12.
Note: In the “Copy Group (A->B)” screen, the number displayed at A is the current active
group number.
[ENTER]
[◄]
Protection
Protection
10:48 1/11
Common
Active Group >
1
Copy Group(A->B) >
Group 1 >
Group 2 >
Change group settings: Upon shipment from the factory, the default settings
are set. Therefore, in each group, the user can change the settings of the
protection functions and other features. To change the settings in each group,
refer to the setting method discussed in section 12.5(i).
programmed using settings. Six screens are configured for six of the function keys (F1 to F6),
respectively, as the default settings shown in Table 5.6-3.
Screen jump function: To configure the screen jump function, follow the steps
as shown in the figure below.
Function Key F1 Key F1 Key Function
10:48 1/7 10:48 1/3 10:48 3/3
F1 Key > [►] *Function + [ENTER] Screen Jump
F2 Key > No Assign Assign Signal
F3 Key > Signal + _No Assign
[◄] [CANCEL]
F4 Key > No Assign
F5 Key > Logic
F6 Key > Instant +
[ ]x2 [▼] x 2
[ENTER]
[An Example]
OC F1 Key
The “Screen Jump”
10:48 1/4 Push [F1]
setting is _OC1EN +> for 3s. Register this screen
On to F1 Key?
confirmed. Do the
OC2EN +> ENTER=Yes CANCEL=No
next step to select On
OC3EN +
a screen.
Off
[ENTER]
The selected screen is assigned to [F1].
On any screen, press the screen-jump function key to display a screen, refer to the
following figure:
Main Menu OC
10:48 2/8 10:48 1/4
Record > [F1] _OC1EN +>
_Monitoring > On
Setting > OC2EN +>
[F1]
IO setting > On
Time > OC3EN +
Test > Off
To cancel the screen-jump function, follow the procedure provided in Figure 12.5-15.
Note: 1) Once a screen is configured to a function key, it will not be deleted until a new
screen is configured for the same function key.
2) If a configured screen is disabled by “On/Off Function” setting (refer to section
12.5(iii)), the screen jump function is also disabled for the function key.
[▼] x 2 [▲] x 2
[ENTER]
The “Screen Jump” function is
canceled on F1 key.
Signal control function: To assign a test signal to a function key, follow the
steps as shown in Figure 12.5-16.
[▲] [▼]
[ENTER]
[ENTER]
Setting F1 Key
[ENTER] [◄] x 2 10:48 1/3
The changed Change Setting? *Signal +
ENTER=Yes CANCEL=No
setting is confirmed. 123101AF00003001
Logic +
Instant
Selection of ratio: For example, Figure 5.2-1 shows how the channel selection
is made for the AC analog input on a VCT module (AI#1 = VCT#1). Move the
cursor by pressing keys ▲ and ▼. Then, press key ►to go to the next level in
the hierarchy.
[►]
AI#1
10:48 1/2
AI1_Ch1_Ratio +
2000
AI1_Ch1_Rating +
DEP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1297 -
6F2S1927 (0.18)
Rating check: Figure 12.6-2 is a check example for channel#1. Using this
screen, the user should confirmed DEP being set in each CT channel.
AI#1 AI1_Ch1_Rating
10:48 1/2 10:48 1/3
AI1_Ch1_Ratio + DEP
2000 [►] 1A
AI1_Ch1_Rating + 5A
DEP
Selection of CT polarity: For example, Figure 12.6-3 shows how change the
CT polarity on a VCT module (AI#1 = VCT#1). Using the cursor by pressing
keys ▲ and ▼ and pressing key ►, go for required setting items.
[►]
Polarity Change
10:48 1/3
Pol–1CT +
Positive
Pol–1CT-Ie +
Positive
Pol–1CT-Iem +
Positive
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1298 -
6F2S1927 (0.18)
[►]
APPL-VCT
10:48 1/3
Off
Ve
Vs2
The user can activate or turn off the above timers and switches using the setting function.
To configure the binary input circuits, the user should follow the procedure in steps ((ii)-1 and
(ii)-2)
Selection of binary input circuit: For example, Figure 12.6-5 illustrates the
selection of a binary input circuit on a binary IO module. Move the cursor by
pressing keys ▲ and ▼. Then, press key ►to go to the next hierarchy.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1299 -
6F2S1927 (0.18)
Common
10:48 1/2
Thres_Level +
Low
Cmp_Num +
4
For example, Figure 12.6-7 shows the CPL setting for binary input circuit (BI1).
The timer and the inverse switch can be activated when On is set for setting
[BI1_CPL]. Press key ENTER to commence the setting of a switch or parameter.
BI1
10:48 1/2
BI1_CPL +
Off
On Delay Timer +
0.000 s
Off Delay Timer +
0.000 s
SW
Inverse-SW +
Normal
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1300 -
6F2S1927 (0.18)
Selection of binary output circuit: For example, Figure 12.6-8 illustrates the
selection of a binary output circuit on a binary IO module. Move the cursor by
pressing keys ▲ and ▼. Press key ► to go to the next level in the hierarchy.
CPL Setting: For example, Figure 12.6-9 illustrates the setting of a binary
output circuit (BO1). Using setting [BI1_CPL] On, the CPL logic in BO1 is
available. Similarly, assigned signals, timers and switches can be set in this
menu. Note that detailed setting items are shown when On is keyed into
setting [BI*_CPL].
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1301 -
6F2S1927 (0.18)
BO1
10:48 1/17
BO1_CPL +
Off
Input signal1 +
No Assign
Input Signal2 +
No Assign
Input Signal3 +
No Assign
Signal8 +
No Assign
LOGIC-SW
AND
On Delay Timer +
0.000 s
Off Delay Timer +
0.000 s
INVERSE-SW +
Normal
TIMER-SW +
Off
Logic Timer +
0.000 s
FF-SW +
Off
Reset Signal +
No Assign
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1302 -
6F2S1927 (0.18)
[►] [CANCEL]
Select Element
10:48 2/155
No Assign
_CO-OC-A 8000001B60
CO-OC-B 8100001B61
CO-OC-C 8200001B62
CO-EF 8300001B63
EXT.ARC_S 8300001B64
Selection of LED: Figure 12.6-11 shows the LED selection screen; the user
can select a setting item by pressing keys ▲ and ▼. Press key ► to go to the
next level in the hierarchy.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1303 -
6F2S1927 (0.18)
LED
10:48 1/31
_LED3 >
LED4 >
LED5 >
LED6 >
LED7 >
LED8 >
LED26 >
F1 Key >
F2 Key >
:
Figure 12.6-11 LED selecting screen
LED Setting: As shown in Figure 12.6-12, the user can set the logical gate,
timer, color of LED and assign signals in this screen.
LED3
10:48 1/16
Color >
RED
Input signal1 +
No assign
Input signal 2 +
No assign
Input signal 8 +
No assign
Reset signal +
No assign
LOGIC-SW +
AND
INVERSE-SW +
Normal
TIMER-SW +
Off
On Delay Timer +
0.00 s
Off Delay Timer +
0.00 s
Logic Timer +
0.00 s
Color +
Figure 12.6-12 LED setting screen
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1304 -
6F2S1927 (0.18)
Time sub-menu
In Time sub-menu, the user can change settings of Clock function, such as time zone, time
synchronizing source, format of time displaying and so on. Figure below shows the Time sub-
menu. (For more information, see Chapter Technical description: Clock function)
Time
10:48 1/5
Clock >
Time Zone >
Time Sync >
Display Format >
Summer Time >
Time menu
(1) Move cursor to the Time menu and press ENTER.
Clock
10:00 1/2
_[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc] >
SNTP
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1305 -
6F2S1927 (0.18)
ActiveSyncSrc menu
ActiveSyncSrc can be shown by the following procedure.
(1) Move cursor to the [ActiveSyncSrc] menu and press ►.
Clock
10:00 1/2 *Note: When the active synchronizing source is not SNTP, the > is
[Time] +
2012-11-21 10:00:05 not shown in the screen.
[Format]
YYYY-MM-DD HH:mm:ss
_[ActiveSyncSrc] >
SNTP
Time Zone
10:48 1/1
Time zone +
0.00hour
(1) Move cursor to the Time zone menu and press ENTER.
Time Zone
10:48 1/1 Time zone can be set by 0.25 hour. The user has to fill the Time zone
_Time zone +
0.00hour in accordance with UTC (Coordinate Universal Time).
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1306 -
6F2S1927 (0.18)
Time Sync
10:48 1/4
TimeSyncSrc +
SNTP
SNTP +>
On
BI SYNC +>
On
TimeSyncSrc menu
Time SyncSrc (Time Synchronization Source) can be changed by the following procedure.
(1) Move cursor to the TimeSyncSrc menu and press ENTER.
Time Sync
10:48 1/4
_TimeSyncSrc +
SNTP
SNTP +>
On
BI SYNC +>
On
By using time synchronization via Ethernet with a SNTP server, the user can connect up
to a maximum of four SNTP servers. If more than one SNTP is used, the priority of the servers
can be decided in ascending order of synchronized stratum value (in order of higher-accuracy)
and select the server with the smallest value.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1307 -
6F2S1927 (0.18)
SNTP menu
IP address of SNTP server can be set by the following procedure.
(1) To confirm that the SNTP synchronization function has been set
Time Sync
10:48 1/4 for On. Subsequently move cursor to the SNTP menu and press ►.
TimeSyncSrc +
SNTP
_SNTP +>
On
BI SYNC +>
On
SNTP (2) Move cursor to desired server number and press ENTER.
10:48 1/4
_Server1 +
0. 0. 0. 0
Server2 +
0. 0. 0. 0
Server3 +
0. 0. 0. 0
SNTP (3) The user can set IP address using ▲ or ▼ by each digit.
10:48 1/4 When the user has finished setting IP address of the server, press
Server1 +
0. 0. 0.176 ENTER.
Server2 +
0. 0. 0. 0
Server3 +
0. 0. 0. 0
BI SYNC menu
When the “BI SYNC” is set to On in Time Sync menu, the user can choose a binary input circuit
(BI) as a synchronization standard. Adjustment setting ‘SYNC_ADJ’ is provided.
Binary synchronization function can be set by the following procedure.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1308 -
6F2S1927 (0.18)
Display Format
10:48 1/4
Date_fmt +
YYYYMMDD
Date_delimiter +
-
Time_delimiter +
:
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1309 -
6F2S1927 (0.18)
Date_delimiter
10:48 1/3 (2) Date delimiter can be selected by moving cursor to the desired
_-
/ format type.
.
Display Format
10:48 3/4 (2) The time delimiter mark is switched.
Date_fmt +
YYYYMMDD
Date_delimiter +
-
_Time_delimiter +
.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1310 -
6F2S1927 (0.18)
Summer Time
10:48 1/13
Summer time +
Off
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1311 -
6F2S1927 (0.18)
Summer Time
(1) Move cursor to the [Summer time] menu and press ENTER.
10:48 1/13 Summer time mode can be switched On/Off by pressing ► or ◄.
_Summer time +
Off After Summer time mode is set to On, the user can set summer time
in detail.
Summer Time (2) In this screen, details of summer time setting can be set.
10:48 1/9
IS_UTC_base +
On
Start_Month +
3
Start_Week +
5
The user can set the starting date and ending of summer time. The following procedure is a
case of starting weekday setting.
Summer Time
(1) Move cursor to the [Start_Wday] menu and press ►.
10:48 4/9
Start_Month +
3
Start_Week +
5
_Start_Wday +
Sun
Start_SM(Wday)
(2) Move cursor to the desired weekday and press ENTER.
10:48
1/8
---
_Sun
Mon
Tue
Wed
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1312 -
6F2S1927 (0.18)
Test sub-menu
Test functions can be operated from the test screen available on the front panel of the IED.
(i) Test screen
The Test screen has functions such as Test Mode, Test Flag, Mode Change and Signal
Monitoring. The user can select any of these test functions using the following test screen.
Test
10:48 1/4
Test Mode +
Off
TestFlag-EN +
On
Mode Change >
Single Monitoring >
Test Mode
10:48 1/4
Test Option >
Function Test >
Binary Input >
Binary Output >
Test Option
10:48 1/65
S-TestFlagCancel +
Off
GOSNDBLK +
Off
GOSUBBLK +
Off
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1313 -
6F2S1927 (0.18)
Note: The user may perform bad reception tests from a remote terminal using the
GOSNDBLK function. However, carrying out the GOSNDBLK function at a
remote terminal may influence the overall operation of other IEDs, because
communication packets will not be received from the remote terminal. In order to
avoid that the user can simulate bad reception tests for a particular IED using the
GOSUBBLK function. As a result, testing will only affect the particular IED
under test i.e. all other terminals will not be influenced by the tests.
Function test screen: Function test screen is provided for testing; the use can
program test operations, which can be implemented in protection and control
functions. Figure 12.8-4 exemplifies the Test screen. Automatic supervision
will stop when the user sets Off for A.M.F (for more information about the
automatic supervision, see Chapter Automatic supervision).
Function Test
10:48 1/65
A.M.F. +
On
BU1_Exclusion +
Off
BU2_Exclusion +
Off
Binary input test screen: The user can have a virtual signal to a binary input
circuit using the binary input test screen. Figure 12.8-5 shows an example;
the user can select IO#1 or IO#3. (Actually, the content displayed will differ
depending upon the binary IO module inserted. Refer to Chapter Technical
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1314 -
6F2S1927 (0.18)
Binary Input
10:48 1/2
Slot#1 >
Slot#3 >
Slot#3
10:48 1/19
BIF OP +
Slot3-BIO1-SET +
Normal
Slot3-BIO2-SET +
Normal
Slot3-BI03-SET +
Slot3-BIO1-SET
10:48 1/3
Normal
Off
On
The user can then make the following selections on the screen and configure the
items required for simulation.
ON: BI1 output is set forcibly to ON(Logic level=high(1)) regardless of
the actual input signal.
OFF: BI1 output is set forcibly to OFF(Logic level=low(0)) regardless of
the actual input signal.
Normal: Actual inputs are applied.
Use the screen shown in Figure 12.8-7 only to configure the BI signals for the
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1315 -
6F2S1927 (0.18)
The setting menu is shown in the manner of the screen illustrated in Figure 12.8-7,
if the user needs to configure an Input Circuit other than BI01 (BI02 to BI18 in the
screen shown in Figure 12.8-6); the user can configure each BI signal in a manner
similar to that described for BI01.
After selecting OP in Figure 12.8-6, use the following screen to start the simulation
test.
Slot#3
10:48
Press and hold ENTER
to operate
Press <- to return
To previous page
Slot#3
10:48
Press and hold ENTER
to operate
Operating..
Binary output test screen: The user is able to test a binary output circuit.
Figure 12.8-10 is an example of how to select a binary output from the Test
Mode screen.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1316 -
6F2S1927 (0.18)
Binary Output
10:48 1/2
Slot#2 >
Slot#3 >
Slot#2
10:48 1/19
BO2F OP +
SLOT2-BO01-SET +
Normal
SLOT2-BO02-SET +
Normal
SLOT2-BO02-SET +
Figure 12.8-12 shows the Output Circuit configuration of BO01 at IO#2 (Slot#2).
The procedure for operation is similar to the operation of the binary input circuit.
(Refer to Figure 12.8-7 to Figure 12.8-9)
SLOT2-BO01-SET
10:48 1/3
Normal
Off
On
The user can configure the required settings for the simulation test of the binary
output circuit.
ON: Output signal for simulation test is ON
OFF: Output signal for simulation test is OFF
Normal: Actual inputs are applied.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1317 -
6F2S1927 (0.18)
Mode Change
10:48 1/3
MDCTRL-EN +
Off
MDCTRL-SELRST +
30 s
MDCTRL-EXERST +
30 s
Signal Monitoring
10:48 1/3
Term A +
No Assign
Term B +
No Assign
Term C +
No Assign
When the user wishes to use monitoring jack A to monitor a signal-monitoring point,
select “Term A” in the signal monitoring sub-menu (Figure 12.8-15). The user can then assign
the signal monitoring point for Term A.
10:48 1/3
Input signal +
No Assign
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1318 -
6F2S1927 (0.18)
Information sub-menu
In the information sub-menu, the user can see the information about the IED. Those of the
information are set in a factory. Figure 12.9-1 shows the Information sub-menu. Table 12.9-1
shows detail of information that is displayed in this screen.
Information
10:48 1/9
[IED TYPE]
GRD200 __-11-111-22-33-
44-555
__-6666-777-88
[Serial No.]
View ✔ ✔ ✔ ✔ ✔
to operate F2 ✔ ✔ ✔ ✔ ✔
F3 ✔ ✔ ✔ ✔ ✔
F4 ✔ ✔ ✔ ✔ ✔
F5 ✔ ✔ ✔ ✔ ✔
F6 ✔ ✔ ✔ ✔ ✔
F7 ✔ ✔ ✔ ✔ ✔
Note: Sign “✔” shows that the user can operate the function. Sign “N.A” shows that the user
cannot operate the function. Password can be changed in Change-Password sub-menu in
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1320 -
6F2S1927 (0.18)
Control sub-menu
The user can control external devices using the IED front panel. Control sub-menus are
provided to operate; the user can operate the devices by pressing Operation keys. Note that
Control sub-menus are only available when the IED is in “LOCAL” mode†. When the IED is in
“REMOTE” mode, an error message will be shown on the screen. Remember that the IED will
change to “REMOTE” mode if there is no operation for a while; then the IED can be monitored
remotely. Figure 12.11-1 shows “Control” sub-menu.
Control
10:48 1/6
_Circuit Breaker >
SPOS >
DPOS >
TPOS >
Software Switch >
Auto Sequence >
Table 12.11-1 shows how to operate by the IED front panel. The IED can have several
control functions, which are dependent on the ordering code. For more information, see
Chapter Control and monitoring application or Appendix: Ordering for more information).
(i) CB operation
Figure 12.11-2 shows how to open CB (Off position).
Control
10:48 1/6
_Circuit Breaker >
Double DIR mode
SPOS >
DPOS >
responses?
TPOS >
Software Switch > SBO mode
Executing screen
Auto Sequence >
Output the command DPOS_SYN_Dev1
[ENTER]
10:48
Control Control execution
10:48 1/6 Push O button [CANCEL]
Waiting for the Select control POS:
_DPOS_SYN_Dev1 >
On
second response On
[ ] [ ] [ ] [ ] [ ]
─────────────────────────────────────────────────────────────────
For rack mounting, cable and electrical wiring, see a separate service manual entitled
Installation handbook for rack mounting, cable work, etc. (Document No. 6F2S1954).
See a service manual entitled Guide for replacement of inner modules depending on the
situation. (Document No. 6F2S1955 or 6F2S1956).
Handling precautions
Modules of the IED should be handled in the electro static charge free environment. That is,
the user shall use an anti-electrostatic-wrist-band; and it is grounded.
CAUTION
Before removing a module, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
Handle the module by its front plate, frame or edges of the printed circuit board. Avoid
touching the electronic components, printed circuit board or connectors.
Place the module on an anti-static surface, or on a conducting surface connected to
the earth.
You have to check carefully the electronic circuitry for your handling area, which is defined in
the IEC 60747 standard.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1324 -
6F2S1927 (0.18)
Ordering positions
7 8 9 A B C D E F G H J K L
- 4 1 - 3 5 E - 0 0 - 6 6 - 3 0 - 22 0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1325 -
6F2S1927 (0.18)
Ordering positions
7 8 9 A B C D E F G H J K L
- 4 1 - 3 5 E - 0 0 - 6 6 - 3 0 - 2 2 0
VCT31B
System
frequency (fn) = 60Hz
AC rating (In) = 5A
The user can check the layout of the binary input and output modules (BI, BO, or BIO)
using the ordering codes. For example, the user can find BI3A, and BO1A modules in IED
depending the ordering cords “5E” at Positions A&B. The user can also read the configuration
with IO configuration label. Additionally, the user can check terminal block types by seeing a
code at Positon ‘H’.
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1326 -
6F2S1927 (0.18)
Ordering positions
7 8 9 A B C D E F G H J K L
- 4 1 - 3 5 E - 0 0 - 6 6 - 3 0 - 2 2 0
Figure 13.3-3 IO configuration label example (viewing from the back in 3/4 size case)
Note: See Section IED case and module slot in Chapter Technical description to find the
structure of IED cases and terminals. For more information about the BI, BO, and
BIO circuits, see Section Binary IO module in the same chapter.
- 4 1 - 3 5 E - 0 0 - 6 6 - 3 0 - 2 2 0
GRD200 software:
03D, 03E, 03F, 030, 032, 036, and 039
- 1327 -
6F2S1927 (0.18)