Sr.

No AS PER GIVEN SPECIFICATION

1 MCCB 10.1-TPN MCCB specified rating along with


cocntrol switch ON/OFF

7.4-MCCB WITH 4P 50KA O/L,S/C,EF

7.7.1- 4P MOTOR DUTY MCCB PROVIDE FOR


MOTOR FEEDER
2 DOL
7.7.1- MCCB IN MOTOR FEEDER SHALL BE AS
PER TYPE -2

3 VFD
7.5.1-MCCB with 50KA ,ACS-560 with I/P and
O/P choke

4 ACB 7.1.1-ACB FIXED TYPE

5 METER 7.1.1-MFM consider for I/C

6 CT 9.3- Consider CT with 10VA


AS PER SLD VELOX REPLY

Up to 400A MCCB ON and OFF shown in SLD and 630A and We have consider ON/OFF upto 400A
above MCCB ON/OFF/TRIP shown in SLD and ON/OFF/TRIP in 630A and 800A
We have consider pole as per SLD
3P and 4P MCCB given with LIG protection

We have consider rating as per TYPE-


2
RATING GIVEN IN SLD

We have consider VFD with ACS560


with I/P and O/P choke Motor
Protection MCCB consider with 4P as
ONLY RATING OF MCCB GIVEN per rating given in SLD

We have consider MDO ACB type-WT


MDO TYPE
with 4P

We have consider EM6400 meter for


I/C

CT with 15VA shown in SLD


we have consider CT with 15VA
COMMENTS VELOX REPLY_13.02.2020

We have consider ON/OFF


INDICATION upto 400A and
ON/OFF/TRIP INDICATION in 630A
OK and 800A AS PER SLD
WE HAVE CONSIDER MCCB WITH
INCOMER LSIG PROTE LSIG ONLY IN I/C

OK CONFIRM

OK CONFIRM

REQUIRED DISPLAY
OF ACS 580 INSTEAD
OF ACS 560 CONFIRM

PLS PROVIDE EDO WE HAVE CONSIDER ACB WITH 3WT


TYPE ACB WITH EDO
MFM HAVING
PROVISION FOR PLEASE FIND ATTCHED DATASHHET
HARMONICS

OK CONFIRM