Calculation of Operating Currents For RET521 Testing: Transformer Details
Calculation of Operating Currents For RET521 Testing: Transformer Details
Transformer Details
Winding 1 Winding 2 Winding 3 Reference
Rating (MVA) 75 60 20 75
Rated Volts(kV) 132 34.5 6.9 132
Rated Current (Ir) 328.04 1004.09 1673.48 328.040
Vector Group Star Star Delta
CT Primary (Amps) 500 1600 2500
CT Secondary(Amps) 1 1 1
No of Windings 3
Minimum Pickup
W1 W2 W3
Primary Pickup (A) 98.412 376.533 1882.664
Three Phase Values Secondary Pickup (A) 0.197 0.235 0.753
Primary Pickup (A) 170.455 652.174 1882.664
Single Phase Values Secondary Pickup (A) 0.341 0.408 0.753
Idiff Primary (A) 98.412 w.r.t. reference side
Unrestrained Operation
Primary Pickup (A) 3280.399 12551.093 62755.464
Three Phase Values
Secondary Pickup (A) 6.561 7.844 25.102
Primary Pickup (A) 5681.818 21739.130 62755.464
Single Phase Values
Secondary Pickup (A) 11.364 13.587 25.102
Idiff Primary (A) 3280.399 w.r.t. reference side
.
While doing Bias tests, the delta side should be injected with currents in two
phases. For example R & N from the test kit should be connected to R & Y phases
on the relay
Terminal Settings
Idmin 30
Characteristics 3
ZSC Sub OFF
Id Unrestrain 1000%
1.60
1.40
1.20
1.00
Id(pu)
Operating point
0.80 Characteristic
0.60
0.40
0.20
0.00
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00
Ibias(pu)
char 3.00 0.30
idmin 0.30
ibias id
0.00 0.30
1.25 0.30
3.58 1.00
4.36 1.39