SECONDARY C

S.No Description Pipe Size in (Inch) length(m) Length (ft)


Section
PIPE 5 20.12 66
GATE VALVE 5 0.00 0
BUTTERFLY VALVE 5 0.00 0
A-I STRAINER 5 0.00 0
ELBOW 5 0.00 0
NRV 5 0.00 0
DRV 5 0.00 0
I-J PIPE 5 3.66 12
J-K PIPE 4 4.27 14
REDUCER 4 0.00 0
NO REDUCTION TEE 4 0.00 0
K-L PIPE 3 4.88 16
GATE VALVE 3 0.00 0
STRAINER 3 0.00 0
REDUCER 3 0.00 0

BHP = (GPM*Head(ft)*sp

BHP
HP
KW

PRIMARY CH
S.No Description Pipe Size in (Inch) length(m) Length (ft)
Section
PIPE 3 4.88 16

L'-K'
GATE VALVE 3 0.00 0
L'-K' DRV 3 0.00 0
2 Way valve 3 0.00 0
ELBOW 3 0.00 0
REDUCER 4 0.00 0
K'-J'
PIPE 4 4.27 14
PIPE 5 3.66 12
J'-I'
REDUCER 5 0.00 0
PIPE 5 25.91 85
ELBOW 5 0.00 0
GATE VALVE 5 0.00 0
I'-A' BUTTERFLY VALVE 5 0.00 0
STRAINER 5 0.00 0
DRV 5 0.00 0
NRV (Swing Check Valve) 5 0.00 0

BHP = (GPM*Head(ft)*sp

BHP
HP
KW
SECONDARY CHILLED WATER PUMP HEAD CALCULATION
L/S Flow (GPM) Friction (Ft/100Ft) Equivalent length(Ft) No of fittings

30.28 480 3.895 0 0


30.28 480 3.895 6 1
30.28 480 3.895 6 2
30.28 480 3.895 80 1
30.28 480 3.895 8.2 5
30.28 480 3.895 50 1
30.28 480 3.895 58 1
22.71 360 2.261 0 0
15.14 240 3.255 0 0
15.14 240 3.255 3.8 1
15.14 240 3.255 6.7 1
7.57 120 3.433 0 0
7.57 120 3.433 3.2 1
7.57 120 3.433 42 1
7.57 120 3.433 2.6 1

PUMP HEAD(FT)
PUMP HEAD(M)
S.F(15%)
S.F(15%)
TOTAL HEAD LOSS(M)
TOTAL HEAD LOSS(FT)

= (GPM*Head(ft)*specific heat of water)/(3960*ƞ of Pump)

2.53
2.91
2.17

PRIMARY CHILLED WATER PUMP HEAD CALCULATION


L/S Flow (GPM) Friction (Ft/100Ft) Equivalent length(Ft) No of fittings

7.57 120 3.433 0 0


7.57 120 3.433 3.2 1
7.57 120 3.433 35 1
7.57 120 3.433 25 1
7.57 120 3.433 7.5 1
15.14 240 3.255 3.8 1
15.14 240 3.255 0 0
22.71 360 2.261 0 0
22.71 360 2.261 5 1
30.28 480 3.895 0 0
30.28 480 3.895 13 7
30.28 480 3.895 6 2
30.28 480 3.895 6 2
30.28 480 3.895 80 1
30.28 480 3.895 58 2
30.28 480 3.895 50 1
PUMP HEAD(FT)
PUMP HEAD(M)
S.F(15%)
S.F(15%)
TOTAL HEAD LOSS(M)
TOTAL HEAD LOSS(FT)

= (GPM*Head(ft)*specific heat of water)/(3960*ƞ of Pump)

3.49
4.02
3.00
Total equivalent length in straight pipe (ft) Head Loss(Ft)

66 2.57
6 0.23
12 0.47
80 3.12
41 1.60
50 1.95
58 2.26
12 0.27
14 0.46
3.8 0.12
6.7 0.22
16 0.55
3.2 0.11
42 1.44
2.6 0.09

15.45
4.71
0.71
2.32
5.42
17.77

Total equivalent length in straight pipe (ft) Head Loss(Ft)

16 0.55
3.2 0.11
35 1.20
25 0.86
7.5 0.26
3.8 0.12
14 0.46
12 0.27
5 0.11
85 3.31
91 3.54
12 0.47
12 0.47
80 3.12
116 4.52
50 1.95
21.31
6.50
0.97
3.20
7.47
24.51