Specification
1.1 Voltage AC220V ±10%
1.2 Cycles 50/60㎐
1.3 Consumption 29.3mA
1.4 Operation temperature -10℃ ~ 60℃
1.5 humidity Under 85% RH
1.6 Temperature for keep -20℃ ~ 70℃
1.7 Weight 202g ( With base:273g )
1.8 Measurement 65.8×87.7×86.8
2. Input, Output
2.1 Motor(BM) AC250V 10A
2.2 Ignitor(IT) AC250V 10A
2.3 Valve1.2(EV1,EV2) AC250V 10A
2.4 Alarm(AL) AC250V 10A
2.5 Limit controller HI/LOW(Contact), OP503ET(Temp.sensor:Option)
2.6 Flame detector CDS(OPA1060-11)
3. Main parts of model
Model PO2A-S,(W) PO2B-T,(X) PO2A-U,(Y) PO2B-V,(Z) PO2A-R Remarks
Function ( )Model auto
Normal 2Valve type Normal & No response 2Valvw, No response Incinerator Type return
3.1 Pre purge time 12Sec
3.2 Pre ignition time 2Sec
3.3 Post ignition time 7Sec
3.4 Post purge time 10Sec 4min ∞
3.5 2Valve opening time No 10Sec No 10Sec No
3.6 Limit time of flame sensor 7Sec
3.7 Inital alarm time Within 2Sec No No Initial alarm
3.8 Response time of fire off Within 1Sec
3.9 Re-Ignition 3 Times ∞
3.10 Flame method CDS
3.11 Response range after ignition Max 115㏀(More 6.0Lux)
3.12 Valve q'ty 1 2 1 2 1
3.13 Warm water temp. sensor OP503ET OPTION
3.14 Buzzor BZ OPTION
Start
Operate
Reset
Pre purge time
IT ON
EV ON
Combustion
lamp Flame detection? Limit time of flame
detection
Alarm lamp,
Sense of dark Midway no Alarm
light? flame output(Memory)
EP OFF
END
RY1
RY2
RY3
RY4
SS
LS
1 2 3 4 5 6 7 8 9
<< Caution: For change between OP-200H(old type) and PO2A-S(New type) >>
** No.2(Flame detector wire) and No.7(Burner motor wire) of 2 wires, you must remove
to No.6 according to wiring circuit.(If not change, goods will be damaged.)
** When you use other company : Be careful wiring circuit....
M10 BOLT(Cu)
M10
Ring
4.Caution :
A.Check voltage and electricity power
B.Check wiring circuit
C.Do not push continuously 3 times reset button and
consult with engineer
D.Check feul leakage after get rid of cause when you
use reset button
E.Check shot circuit when you change.
F.When you use humidity area, installaton humidity
protection instrument
G.Do not dissolve and repair when controller out of order
H.Do not use for other use
<< Caution: For change between OP-200H(old type) and PO2 -S(New type) >>
** No.2(Flame detector wire) and No.7(Limit controller wire) of 2 wires, you must remove
to No.6 according to wiring circuit.(If not change, goods will be damaged.)
** When you use other company : Be careful wiring circuit....