2.8 Explanation On FB IO - LINK - 3RS1x (FB5130) : 2.8.1 Interface and Parameters
2.8 Explanation On FB IO - LINK - 3RS1x (FB5130) : 2.8.1 Interface and Parameters
Interface
Figure 2-6
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-17 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-18 Input/Output parameters
Parameter Data type Description
Data UDT 3RS1x Data structure for IO-Link devices 3RS1x.
Interface
Figure 2-7
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-19 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-20 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link devices 3UG481x.
3UG481x
Interface
Figure 2-8
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-21 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-22 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link device 3UG4822.
3UG4822
Interface
Figure 2-9
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-23 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
SystemCommands BOOL Write system commands.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
SerialNumber BOOL Read access to serial number.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-24 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link device 3UG4825.
3UG4825
Interface
Figure 2-10
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-25 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-26 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link device 3UG4832.
3UG4832
Interface
Figure 2-11
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-27 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-28 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link device 3UG4841.
3UG4841
Interface
Figure 2-12
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-29 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
HWRevision BOOL Read access to hardware version.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Measurements BOOL Read access for measured values
Parameters BOOL Read/write access for parameter
ParameterPage0 BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-30 Input/Output parameters
Parameter Data type Description
Data UDT Data structure for IO-Link device 3UG4851.
3UG4851
Interface
Figure 2-13
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-31 Input parameters
Parameter Data type Description
DirectParameterPage BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
ErrorCount BOOL Read access to error counter
EventHistory BOOL Read access to event history
ReaderStatus BOOL Read access to state of the reader
TagStatus BOOL Read access to tag status
UIDHistory BOOL Read access to UID history
DirectParameterPage BOOL Read access to ParameterPage 0.
VendorName BOOL Read access to manufacturer name.
Siemens AG 2015 All rights reserved
Input/output parameters
Table 2-32 Input/Output parameters
Parameter Data type Description
Data UDT RFID Data structure for RFID
Note More information on the parameters that are processed with this function block
can be found in \6\.
Interface
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-33 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
System Command BOOL Write access to the system commands.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Del_Key-ID BOOL Write access to the key ID to be deleted.
KeyList1-30 BOOL Write access to the individual encodable
key IDs (1-30)
KeyList31-50 BOOL Read access to the memory of the individual
encodable key IDs (31-50)
Diagnostics BOOL Read access to diagnostics data.
Siemens AG 2015 All rights reserved
Input/output parameters
Interface
Siemens AG 2015 All rights reserved
Note The parameters valid for all blocks from Chapter 2.3 onward are described in
Chapter 2.2.
Input parameters
Table 2-35 Input parameters
Parameter Data type Description
ParameterPage0 BOOL Read access to ParameterPage 0.
System Command BOOL Write access to the system commands.
VendorName BOOL Read access to manufacturer name.
VendorText BOOL Read access to the specific text of the
manufacturer.
ProductName BOOL Read access to product name.
ProductID BOOL Read access to product ID.
FWRevision BOOL Read access to firmware version.
ApplicationSpecificName BOOL Read/write access to application-specific name.
Diagnostics BOOL Read access to diagnostics data.
Statistics BOOL Read access to the statistic input/output data.
Parameters BOOL Read/write access to the parameters.
Input/output parameters
Siemens AG 2015 All rights reserved
Table 3-1
Step Instruction
1. The library is available on the HTML page from which you downloaded this
document. Save the “90529409_IOLink_Devices_LIB_V55.zip” library to your hard
drive.
2. Open the SIMATIC MANAGER and retrieve STEP 7 library
“90529409_IOLink_Devices_LIB_V55.zip”.
“File > Retrieve...”
The library is now available in “Libraries”.
Siemens AG 2015 All rights reserved
3.
Table 3-2
Step Instruction
1. Open an already existing STEP 7 V5.5 project.
2. Open the “SIEMENS_Devices_IO_Link” library.
General:
Move FB5001, the FB that corresponds to your device, as well as the
respective UDTs and UDT5000 into your user program. Then add the required
system functions.
Example:
Siemens AG 2015 All rights reserved
Step Instruction
4. Check the consistency of your user program via right mouse click on the block
folder and select “Check Block Consistency”.
5. Create organization block 1 (OB1) and open it. Use drag & drop to move the
function block into any network for your IO-Link device.
Note
You can also use the blocks in other, cyclic organization blocks.
6. Enter the data block with the number of the instance data block that you would
like to use. Generate the instance data block if it does not exist.
Step Instruction
7. Assign values of your choice to all formal parameters. The values can be, for
example, stored in any data block.
Table 4-1
Step Instruction
1. The library is available on the HTML page from which you downloaded this
document. Store the “90529409_IOLink_Devices_LIB_V13_SP1.zip” library on
your hard disk and extract it.
2. Open the TIA Portal and retrieve the STEP 7 library “Siemens_IO-
Link_Devices_Library_V13_SP1.zal13”.
Siemens AG 2015 All rights reserved
The following table describes the procedure for adding the “IO_LINK_3RAxy”
function block.
Table 4-2
Step Instruction
1. Open an already existing STEP 7 V13 SP1 project.
2. Open the library “Siemens_IO-LINK_Devices_Library_V13_SP1”.
Siemens AG 2015 All rights reserved
Step Instruction
5. Open the OB “Main”. Use drag & drop to move the function block into any
network for your IO-Link device.
Note
You can also use the blocks in other, cyclic organization blocks.
6. Enter the data block with the number of the instance data block that you would
like to use.
Siemens AG 2015 All rights reserved
7. Assign values of your choice to all formal parameters. The values can be, for
example, stored in any data block.
Save the OB1 organization block and load the STEP 7 project into your
S7-CPU.
Shift-F1
Siemens AG 2015 All rights reserved
Note The direct call of the documentation only works after the library name has been
selected. When using <Shift-F1> to call a different item in this library, you will be
forwarded to the HTML page in the Siemens Industry Online Support from which
you downloaded this entry.
command and
Signaling devices
3SU1
6 History
Table 6-1
Version Date Modifications
V1.0 07/2014 First version
V2.0 05/2015 Upgrade to TIA Portal V13 SP1
V2.1 09/2015 Expanded by SIRIUS ACT devices