Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

DTM for TZID-C/TZID-C200 HART communication for

positioner TZID-C/TZID-C200

Manual 42/63-24 EN Rev. 01


DTM TZID-C/TZID-C200
HART communication for positioner TZID-C/TZID-C200

Manual
Document number: 42/63-24 EN
Issue date: 01.02
Revision: 01

Vendor:
ABB Automation Products GmbH
Schillerstrasse 72
D-32425 Minden

Phone: +49 (0) 57 18 30 - 0


Fax: +49 (0) 57 18 30 - 18 60

© Copyright 2002 by ABB Automation Products GmbH


Subject to technical changes
These operating instructions are proteced by copyright law. Translating, photocopying and diseminating
it in any form whatsoever - even editings or excerpts thereof - especially as reprint, photomechanical or
electronic reproduction or storage on data processing systems or networks is not allowed without the per-
mission of the copyright owner and non-compliance will lead to both civil and criminal prosecution.
Table of contents

Table of contents

1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 . DTM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

2.2 . Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

2.3 . Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

2.4 . Adding a device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

2.5 . Saving a project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

2.6 . Changing the COM interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

2.7 . Changing the bus address in the project structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.8 . Project manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

2.9 . Changing the bus address of the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 . Connect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

3.2 . Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.3 . Load from device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.4 . Save in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.5 . Load data set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.6 . Save data set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.7 . Select and load data set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

3.8 . Save as data set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

3.9 . Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.10 TZID-C/TZID-C200 main window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.1 . Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 . Positioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.1 . Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6.1.1 Travel counter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6.1.2 Stroke counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6.2 . Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

7 Configure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.1 . General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.1.1 Final control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, (TOC) 3


Table of contents

7.1.2 Additional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.1.3 Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.2 . Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.2.1 Effective variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.2.2 Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

7.3 . Inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7.3.1 Digital input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7.3.2 Alarm messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7.4 . User-specific characteristic curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

7.5 . Control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

7.5.1 KP value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

7.5.2 TV value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

7.5.3 Go pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

7.5.4 Output offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

7.5.5 ADC noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.5.6 I/P module type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.6 . Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.6.1 Deadband time limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.6.2 Travel counter limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.6.3 Stroke counter limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7.6.4 Stroke limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.1 . Reset device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8.2 . Load factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8.3 . Autoadjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8.4 . Start Autoadjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8.5 . Autoadjustment state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8.6 . Signal simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, (TOC) 4


General safety instructions

1 General safety instructions


Safety This chapter contains important instructions for your safety!
instructions Read and observe!
Instructions for These operating instructions are a reference manual for the DTM of the TZID-C or TZID-C200 intelligent
proper use positioner (HART communication).
Loading the factory Prior to commissioning, especially when using ex-stock or old devices, load the factory setting.
setting
National standards The regulations, standards and directives referred to in these operating instructions are applicable in Ger-
and regulations: many. When using the TZID-C or TZID-C 200 positioner outside the German Federal jurisdiction, the rel-
evant standards, regulations and directives applicable in the country where the device is used must be
observed.
Marking important The following symbols are used for marking text sections that contain essential information for your safety
information or for proper use.

WARNING This symbol is printed next to warnings indicating a direct endangerment


of a person's health or life.Observe these instructions. Inform all other us-
ers involved.
Also observe the general safety instructions, and the regulations for the
prevention of accidents.
CAUTION This symbol is printed next to cautions indicating that the relevant
standards, regulations and directives and the respective notes in
this manual must be observed and that the work on the device must be
performed in the described order to prevent damage or destruction of the
device.
• General list

Table 1-1 Symbols and their meaning

2 General
2.1 DTM
The DTM – Device Type Manager – is the basis of the FDT concept. This component is provided by the
vendor of the intelligent field instruments.
The DTM 'knows' all device rules, contains the user dialogs, provides for the device configuration and
diagnostics, and generates the device-specific documentation.
Further field instruments can be added as required and at any time, since the respective DTMs can be
loaded easily.
Note that it is not possible to run several DTMs in parallel under Windows 95/98. If you are using one of
these operating systems and call up several DTMs simultaneously, the operational reliability of your op-
erating system is no longer ensured.

2.2 Installation
Insert the CD ROM disk into your CD-ROM drive.
Close all Windows95/98/2000/NT applications and click on the Windows Start button.
Choose the <Run> command from the Start pull-down menu. Type the CD-ROM drive indicator and a
colon (e.g. “D:“) and then "setup".
Click on the OK button or press the <ENTER> key to confirm your entries and start the installation.
The DTM will be installed automatically. Upon successful installation your computer has to be restarted.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 1 5


General

2.3 Communication

Fig. 2-1 Setting up communication

Select “Project” -> “New” to call up the appropriate window and select the communication interface.
Choose "HART 5.1, FSK Modem, LKS-Adapter“ for a connection via LKS adapter and FSK modem.
Confirm with OK or <ENTER>.

2.4 Adding a device

Fig. 2-2 Adding a device

Call up the device list via “Project” -> “Edit”. You can add any of the displayed devices to your project
structure. Click with the left mouse button on the respective device(s), hold the mouse button down, drag
the mouse cursor to the COM2: HART 5.1. field in the left window, and then release the mouse button
(drag & drop operation). The device(s) will be inserted.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 2 6


General

2.5 Saving a project


Select "Project” -> "Save” to save the current project structure.

2.6 Changing the COM interface


Click with the left mouse button on the serial PC interface (COM interface) that you want to change. Select
“Edit” -> “Change address/name”. A selection window with the available interfaces pops up. Select the
wanted COM interface and confirm with "Done".

2.7 Changing the bus address in the project structure


Click with the left mouse button on the respective device in the project structure. Select “Edit” -> “Change
address/name” to call up the bus address selection window. Mark the respective bus address and confirm
with "Done".
Note that this will only change the bus address in the project structure, not in the device! See “Changing
the bus address of the device” on page 7.

2.8 Project manager

Fig. 2-3 Project manager

Select "Project” -> "Back to project mananager” to return to the window from where you can establish a
connection to the devices.

2.9 Changing the bus address of the device


Click with the left mouse button to select the respective interface from the project manager. Select "Find
device” -> "Bus device.” SMART VISION will search for connected devices. Click with the right mouse
button to select the respective device from the displayed list. Select "Change slave address” to call up
the appropriate window from where you can write the new bus address into the device.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 2 7


Device

3 Device
3.1 Connect
Open the project manager and click with the left mouse button on the respective device in the project
manager to establish a connection with this device. Then click with the right mouse button and select
"Connect“ -> "More“.
Once the connection has been established, the COM LED in the bottom right corner of the SMART
VISION main window starts flashing, and the device name in the project manager is indicated in bold
characters.

Note If the device name is displayed in red, this means that connection setup to the device has failed. In this
case check the cables for proper connection, and if the proper serial interface and communication proto-
col has been selected. It is also possible that the device bus address is not identical with the address in
the project tree.
You can call up the context menu by actuating the right mouse button. From this window you can return
to the main window by selecting the appropriate menu item.

3.2 Disconnect
Select "Device" -> "Disconnect" to interrupt the connection to a device. You can also click with the left
mouse button on the respective device in the project tree, click with the right mouse button to open the
appropriate pull-down menu, and then select menu item "Disconnect".

3.3 Load from device


Call up the information window from the TZID-C or TZID-C200 main window. All device data indicated in
blue are different from the loaded data set.
Select "Device" -> "Load from device" to read out the current device data.
Windows highlighted yellow cannot be edited. Windows with white background can be edited upon click-
ing with the left mouse button.

Note The "Load from device" function must be repeated for every window. The respective device must have
been selected under "View" and "Source".
Comments are not loaded from the device, but from the data set.

3.4 Save in the device


All device data indicated in blue are different from the loaded data set.
Select "Device" -> "Save in device" to save the device data in the device.
Note You can save comments for each data set.

3.5 Load data set


Select "Device" -> "Load data set" to load the data from the device data set. These are the data last
saved. When calling up the data set for the first time, the default data set is loaded.

3.6 Save data set


Select "Device" -> "Save data set" to save the current data in the device data set.

3.7 Select and load data set


With "Select and load data set" you can define the file from which the saved data of the device shall be
loaded.

3.8 Save as data set


Here you can create a new file in which the device data will be saved.

3.9 Print
This menu item calls up the print preview. Select "Edit" -> "Create print file with default template" to dis-
play all data of the device data set. The data can then be output via "File" -> "Print".

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 3 8


Display

3.10 TZID-C/TZID-C200 main window

Fig. 3-1 TZID-C/TZID-C200 main window

From the main window you can call up all windows for operating/configuring the program.
A message in the status line at the bottom of the window indicates whether or not the device is connected,
which data source is being used (data set or device ), and the user access level.

4 Display
4.1 Log
In this window you can start logging of four positioner parameters in parallel at selectable intervals.
Under "Options" you can select the parameters that are to be logged. Additionally, the time interval
(1…3600 seconds) can be defined.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 4 9


Operation

5 Operation
5.1 Positioner

Fig. 5-1 Positioner

The valve range, stroke range, setpoint and control deviation of are represented in graphical form in this
window.
Additionally, it can seen whether or not the stroke range is smaller than the actual valve range, and the
instantaneous input current and device temperature are indicated.
The “Direct value” button can be used to enter a manual setpoint, to which the final control element can
be moved independently of the input signal.
Note With “Direct value“ the device ignores the 4...20 mA setpoint signal.

6 Diagnostics
6.1 Load

6.1.1 Travel counter


In this window the instantaneous value of the travel counter can be displayed and, if required, can be re-
set.

6.1.2 Stroke counter


In this window the instantaneous value of the stroke counter can be displayed and, if required, can be
reset.

6.2 Messages
In this window messages are indicated, e.g. when the limits are exceeded.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 5 10


Configure

7 Configure
7.1 General

7.1.1 Final control elements


The following information is indicated in this window:
– FSK bus address
– Device manufacturer
– Device type
– Device ID
– Serial number
– Device version
– Software version
– Hardware version
– Device state

The following data can be edited in this window


– Communication name
– Plant tag of the final control element
– Device date
– General plant description
– Additional plant description

7.1.2 Additional data


This window provides the following information:
– I/P module type
– I/P module serial number
– Sensor type
– Sensor number

7.1.3 Comments
In this window you can enter comments or special information e.g. date and scope of the last valve main-
tenance. This information will be saved in the data set.

7.2 Operation

7.2.1 Effective variables

7.2.1.1 Setpoint range


With this function you can define the setpoint range between 4.0 and 20mA. The setpoint range is always
scaled to the configured stroke range (0...100%) of the device.
The setpoint range factory setting is 4.0...20.0mA.
Example: Split-Range
It is possible to run two series-connected positioners on a single setpoint source by configuring the first
device for a range of 4.0...12.0mA and the second one for 12.0...20mA. Overlaps or gaps between the
setpoint ranges can be configured as required.

Note The setpoint range must not be smaller than 10% (1.6mA).

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 11


Configure

7.2.1.2 Characteristic curve


With this function you can configure the characteristic curve for the setpoint channel. The following op-
tions can be selected:
– Linear
– Equal percentage 1:25
– Equal percentage 1:50
– Equal percentage 25:1
– Equal percentage 50:1
– User-configurable

Note Selecting a user-configurable characteristic curve is only possible if such a curve has been defined before
under "Extension“ -> "Special data“.
In factory the device is set to a linear characteristic curve.

7.2.1.3 Valve action


With this function you can define the valve action for the setpoint channel ("Direct" or "Reverse").
The factory setting is "Direct".

7.2.1.4 Tolerance band


With this function you can define the tolerance band for control.
Enter the tolerance band within the range of 0.30...10.00% in steps of 0.05 %. The tolerance band defines
a +/- range around the setpoint. When the valve position is within this range, the controlled system is
considered as balanced. If the valve is not controlled smoothly by the positioner, the tolerance band
should be increased. If the positioner does not reach the set position exactly enough, the tolerance band
should be decreased.
The tolerance band factory setting is 0.30%.

7.2.1.5 Shut-off value


With this function you can define the shut-off value.
When the setpoint reaches the shut-off value, the valve is immediately driven to the 0% stroke limit.
Enter a value between 0.0 and 20.0%.

7.2.1.6 Setpoint ramp


With this function you can define a setpoint ramp for control.
A setpoint change is not directly transferred to the controller, but with the defined time function.

Note The setpoint ramp is only active during control. The set values should always be greater than the actual
stroke times. The setpoint ramp is disabled in manual mode and when the device is moving to the safe
position.
Enter the setpoint ramps separately for each moving direction (up and down) for the entire valve stroke
within a range of 0...200 seconds. A value of 0 seconds will switch off this function. “Down” refers to a
moving direction towards the 0% stroke limit, "up" refers to a moving direction towards the 100% stroke
limit.
The setpoint ramp factory setting is 0 seconds (OFF).

7.2.1.7 Stroke time


This parameter is determined by the Autoadjust function and is then indicated as the shortest possible
stroke time over the entire valve range.

7.2.1.8 Deadband time limit


With this function you can monitor the valve stroke time in control mode.
As soon as the valve position is outside the tolerance band, it is monitored if the setpoint is reached within
the set time. Otherwise, an alarm is signalled. The respective alarm message is indicated in the "Mes-
sages" window.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 12


Configure

Enter the deadband time limit to be monitored within the range of 0...200 seconds. A value of 0 seconds
will switch off this function.
If the optional module for "Digital position feedback" is present, the alarm output is enabled. The alarm
will be reset when the set position is reached.

Note Make sure that the deadband time limit is always greater than the actual stroke time.
The factory setting of the deadband time limit is 0 seconds (OFF).

7.2.2 Adjustment

7.2.2.1 Lever zero position


With this function you can assign an end position to the lever range zero positions.
This parameter defines whether the zero position of the actuator is assigned to the stops reached when
the lever shaft is turning counterclockwise or clockwise (seen from the device front).
The lever zero position is not determined by the Autoajdust function. It has to be derived from the lever
link and from the intended zero position of the valve.

7.2.2.2 Actuator spring action


With this function you can define the end position to which a single-action actuator is set by the spring.
Note Usually, this parameter is determined by the Autoadjust function with valve stops. When using the Auto-
adjust function without stops, this parameter must be set properly.
This parameter defines whether the spring moves the feedback shaft with depressurized valve chamber
to the end position when turning counterclockwise or clockwise (seen from the device front).In the case
of a double-acting actuator the spring action corresponds to pressurizing the pneumatic output Y2.
Changing the spring action may cause a sudden movement of the actuator upon data transfer to the de-
vice.
When using the Autoadjust function with control data, only, the "Actuator spring action" parameter must
be set properly.

7.2.2.3 Actuator type


With this parameter you can define the positioner for operation on a linear or rotary actuator.

7.2.2.4 Valve range limits


This parameter indicates whether the valve range was limited as compared to the actual stroke range,
such that the mechanical limit stops of the valve are no longer reached. In this case the actuator is not
fully pressurized/depressurized when reaching the high or low end position. This may be useful, espe-
cially if the valve has a tendency to swing through.

7.2.2.5 Stroke range limits


With this function you can limit the stroke range as compared to the actual valve stroke.
Enter the range between 0.0 and 100%. If the stroke range is limited, only a part of the actual mechanical
valve stroke is covered by the set point range.
The setpoint range always refers to the stroke range.
Not that any change of the stroke range changes the absolute positions of the switching points as com-
pared to the valve position.
If the stroke range is limited, (<100%) the mechanical stops of the valve are nor longer reached by fully
depressurizing or pressurizing.
The stroke range limitation is only active in control mode. In manual mode it is still possible to use the full
mechanical valve stroke. In case of a power failure and fail-safe positioning through the I/P module, the
valve is set to the mechanical end positions.
The stroke range factory setting is 0.0...100.0%.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 13


Configure

Example 1:
The valve shall not close fully with minimum setpoint, to ensure a minimum flow. In this case the low
stroke range limit has to be set to the wanted minimum stroke.
Example 2:
The valve must not exceed a maximum flow, even with maximum setpoint. In this case the high stroke
range limit has to be set to the wanted maximum stroke.

7.2.2.6 Switching points


With this function you can define the switching points. When the valve position is below the low switching
point or above the high switching point, the respective message is shown in the "Display measured value"
window.
If the option module for "Digital position feedback" is present, the "Min." switching output (terminals 41,42)
is activated when the value is below the low switching point. If the high switching point is exceeded, the
"Max." switching output (terminals 51 and 52) is activated.
Enter the high or low switching point in the range between 0.0 and 100.0%. The percentage values refer
to the configured stroke range.

Note Not that any change of the stroke range changes the absolute positions of the switching points as com-
pared to the valve position. The defined deadband is used as the hysteresis range for resetting the active
switching points.
The switching point factory setting is 0% and 100%.

7.3 Inputs/outputs

7.3.1 Digital input


With this parameter you can define the function/reaction if no external 12 V DC voltage is applied.
– no function (in this case, the TZID-C or TZID-C200 positioner does not require an external 12 V DC
voltage across its digital input for proper operation).
– move to 0% position
– move to 100% position
– hold current position
– local configuration locked; local operation is still possible
– local operation is locked
– both local operation and external configuration are locked

7.3.2 Alarm messages


Here you can define which alarm messages are to be signalled and output via the digital output as a cur-
rent signal (Namur).

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 14


Configure

7.4 User-specific characteristic curve

Fig. 7-7 User-specific characteristic curve

Here you can either edit the 20 reference points of a user-defined characteristic curve or load/save a char-
acteristic curve.

7.5 Control parameters

7.5.1 KP value
With this function you can define the KP value.
Note Note that all control parameters are determined in an optimum way for most of the actuators by the Au-
toadjust function. Changes should only be made when Autoadjust cannot be executed or control stability
cannot be achieved.
To compensate for existing dissymmetries in the controlled system, the KP value is to be set separately
for both directions (up/down).
Enter a KP value in the range between 1.0 and 400,0.

Definition The KP value is a gain of the PD controller and results in a positioning signal of 100% for KP=1 and a
control deviation of 100%.
The KP value influences the controlling speed and stability. With higher KP values the controlling speed
increases.
Note that the control accuracy is not affected by the KP value!

Hints for setting For most actuators sufficient control action can be achieved with a KP value between 2.0 and 10.0.
Choosing a KP value smaller than 5.0 can, despite the go pulse, result in starting times longer than 400
milliseconds. In such a case you can shorten the starting time without impairing the stability of the control
loop by proportionally increasing the KP and TV values.
If the control loop continues to show instable behavior, even if the KP value has been decreased, a too
high offset has been chosen for the output value or other parameters are highly unbalanced.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 15


Configure

7.5.2 TV value
With this function you can define the TV value.
The TV value is usually determined by the Autoadjust function and defines the derivative time of the PD
controller.
The TV value factory setting is 0.04 seconds.
Note Note that all control parameters are determined in an optimum way for most of the actuators by the Au-
toadjust function. Changes should only be made when Autoadjust cannot be executed or control stability
cannot be achieved.
To compensate for existing dissymmetries in the controlled system, the TV value is to be set separately
for both directions (up/down).
Enter the TV value within the range of 10...800 milliseconds.

Definition The TV value is the derivative time of the PD controller and results, for example, in an output signal of
100% for TV=100 ms in balanced condition, together with KP=1 for a dynamic control deviation of 100%/
100 ms.
Speed and stability are affected by the TV value in such a way that it counteracts dynamically to the KP
value. With higher TV values the controlling speed decreases.

Hints for setting For most actuators satisfactory control action is achieved with a TV value between 20 and 200 ms.
In manual configuration choose a TV value of approximately 8...10 * KP value [msec].

7.5.3 Go pulse
With this function you can define the go pulse.
Note Note that all control parameters are determined in an optimum way for most of the actuators by the Au-
toadjust function. Changes should only be made when Autoadjust cannot be executed or control stability
cannot be achieved.
To compensate for existing dissymmetries in the controlled system, the go pulse is to be set separately
for both directions (up/down).
Enter a go pulse between 0 and 200 milliseconds in steps of 20 milliseconds.

Definition The controller issues an amplified positioning signal for the defined pulse length and with the actuator not
moving, in order to achieve accelerated starting of the actuator.
In this way the time required to build the pressure needed to begin moving the actuator is reduced.
Hints for setting The value determined by Autoadjust should NOT be increased, as this may result in overshooting! If the
actuator consistently overshoots the setpoint, decrease the go pulse.
For small and fast actuators it may be necessary to set the go pulse to 0, even if Autoadjust has deter-
mined a higher value.

7.5.4 Output offset


With this function you can define the output offset.
Note Note that all control parameters are determined in an optimum way for most of the actuators by the Au-
toadjust function. Changes should only be made when Autoadjust cannot be executed or control stability
cannot be achieved.
To compensate for existing dissymmetries in the controlled system, the output offset is to be set sepa-
rately for both directions (up/down).
Enter an offset value between [minOffset] and 100%.

Definition The "offset for the output signal" linearizes the behavior of the I/P module used and enables fast control
even for small control deviations. The value is limited a the low end by a minimum value (neutral zone).
The offset substantially affects the controlling speed for control deviations smaller than 5%. In manual
mode the offset values are issued for fine adjustment to the I/P module.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 16


Configure

Hints for setting For most actuators satisfactory control is achieved with offset values between 40 and 80%.
If the valve overshoots, both offset values should be decreased.
Both offset values should be increased if the actuator stops outside the tolerance band. For larger, slower
actuators Autoadjust may determine values higher than 80%. In these cases there will be no noticeable
difference between fine and coarse adjustment while in manual mode.

7.5.5 ADC noise


With this function you can define the noise band of the AD converter.
Note Note that all control parameters are determined in an optimum way for most of the actuators by the Au-
toadjust function. Changes should only be made when Autoadjust cannot be executed or control stability
cannot be achieved.
Enter a noise band between 0.03 and 0.1% referred to the lever range.
Definition The noise band defines the smallest measurable stroke change in the lever range. This value depends
on the quality of the ADC and on external disturbances.
The possible control accuracy is given by the triple noise band. This means the noise band defines the
smallest strokes which can still be recognized by the PD controller.
Hints for setting The noise band only has to be set manually of the Autoadjust function cannot be executed. Usually, it
noise band of up to 0.03% is sufficient.

7.5.6 I/P module type


In this field the installed I/P module type and its safe position are indicated.

7.6 Monitoring

7.6.1 Deadband time limit


With this function you can monitor the valve stroke time in control mode.
As soon as the valve position is outside the tolerance band, it is monitored if the setpoint is reached within
the set time. Otherwise, an alarm is signalled. The alarm message is displayed in the "Display measured
value" window.
Enter the deadband time limit to be monitored within the range of 0...200 seconds. A value of 0 seconds
will switch off this function.
If the optional module for "Digital position feedback" is present, the alarm output is enabled. The alarm
will be reset when the set position is reached.

Note Make sure that the deadband time limit is always greater than the actual stroke time.
The factory setting of the deadband time limit is 0 seconds (OFF).

7.6.2 Travel counter limit


With this function you can configure the travel counter in the device.
The totalizes the total travel of the valve stem in %.
Limits in the range of 0...4.294.967.295 can be configured for the travel counter. When the counter reach-
es the limit value, an alarm is signalled if this has been configured before under "Inputs/outputs".
In the factory setting the counter is reset, and a limit value of 1,000,000 is set.

7.6.3 Stroke counter limit


With this function you can configure the stroke counter in the device.
Every stroke that is greater than the stroke hysteresis (measured from the most distant position of the last
direction change) is counted in the positioner.
Limits in the range of 0...4.294.967.295 can be configured for the stroke counter. When the counter
reaches the limit value, an alarm is signalled, provided that this has been configured before under "Inputs/
outputs" and then saved in the device.
In the factory setting the counter is reset, and a limit value of 100,000 is set.

42/63-24 EN DTM for TZID-C/TZID-C200, HART communication, Section 7 17


Service

7.6.4 Stroke limit


Here you can define the stroke hysteresis that the stroke counter shall interpret as a stroke.
The stroke hysteresis can be configured in the range of 1...100%.
In the factory setting the stroke hysteresis is reset to 50%.

8 Service
8.1 Reset device
This function is used to re-initialize the device. All data that have not been stored in the non-volatile mem-
ory will be erased.

8.2 Load factory setting


This function is used to re-initialize the device. All data saved in the non-volatile memory will be erased,
and the factory setting will be restored.

8.3 Autoadjust
With this parameter you can define the type and scope of the autoadjustment function.
The following options can be selected:
– Full autoadjustment
– Stops only
– Control parameters only
– Zero only (requires parameterized stops)

8.4 Start Autoadjust


With this function you can externally start the autoadjustment, provided that the lock is
disabled.
The autoadjustment can be terminated at any time by using the <Cancel> button in the information win-
dow. All parameter data determined up to this moment will be rejected, and the previous data will be re-
stored.
If you choose the reduced autoadjustment function where only the control parameters are determined,
make sure that the “Valve range“ and “Actuator spring action“ parameters were set properly.

8.5 Autoadjustment state


With this function you can display the type and scope of autoadjustment.

8.6 Signal simulation


With this parameter you can simulate an actuator position in order to activate the software contacts and
check the analog position feedback. This is especially useful in the commissioning phase when checking
the cables.

ABB Automation Products GmbH Subject to technical changes


Schillerstrasse 72 Printed in the Fed. R. of Germany
42/63-24 EN Rev. 01
D-32425 Minden Issue 01.02
Phone +49 (0) 57 18 30 - 0
Fax +49 (0) 57 18 30 - 18 60
http://www.abb.com

You might also like