PV Array (N) Junction Boxes (N) Inverters (N) SOLAR - ONLY Subpanel (N) AC Disconnect (N) Main Service

Inverters (N) SOLAR - ONLY Subpanel (N) AC Disconnect (N) Main Service Panel (E)
7 Strings of 4 x 16 and 3 x 12 Panels in Parallel Weather proof Bell box Solar Edge 200 Amp Rated Square D - DU324NRB 600 Amp Service
(100) Panasonic VBHN325SA16 Panels 10.0KW (Model SE10K) 3P200A - Fused 600 Amp Main Breaker
(100) P400 Power Optimizers under Panels (240V) 175 Amp Fuses
Rated output power: 240 V LOAD SIDE CONNECTION
Output: 32,500 Watts STC
10,000 Watts NEMA 3R
Integrated AC/DC Disconnect Located next to
12 Located next to Main Electrical Panel
Main Electrical Panel

12
DC
Main Breaker:
AC (E) 2P600Amp
Utility Meter
12

- 3.96 kWh

16
DC
Utility Grid
AC 120/240V
Single Phase

16 (N) 3 x Solar Breakers


2P60Amp

DC
AC
16
Ioperating @ 125% = 52.5 A (42 A x 125%) (2) # 2/0 THHN/THWN-2 (2) # 2/0 THHN/THWN-2
(2) # 6 THHN/THWN-2 (1) # 2/0 THHN/THWN-2 Neutral (1) # 2/0 THHN/THWN-2 Neutral
(1) # 6 THHN/THWN-2 Neutral (1) # 6 THHN/THWN-2 AC - EGC (1) # 6 THHN/THWN-2 AC - EGC
(1) # 8 THHN/THWN-2 AC-EGC 2" EMT Conduit 2" Rigid Conduit
16 3/4" EMT conduit
Max string current: 15A (6) #10 THWN-2
Max system current: 45A (1) #10 THWN-2 EGC SUM OF INVERTER OUTPUT:
Panel Specs: Max system Voltage: 500V Wire Sizing: 42 Amp x 3 x 125% = 157.5 Amp
Pmax: 325 W (2) #10 AWG PV wire / string # 10 THWN-2 - 40A
Imp: 5.65 A (1) #10 solid copper EGC 10A x 80% (conduit fill) x 0.58 (temp. correction) = 18.56 A
Vmp: 57.6 V Max string current: 15A (4) #10 THWN-2 Legend:
Voc: 69.6 V Max system current: 30A (1) #10 THWN-2 EGC
Isc: 6.03 A Max system Voltage: 500V Wire Sizing:
(2) #10 AWG PV wire / string # 10 THWN-2 - 40A
(E) Existing
(1) #10 solid copper EGC 10A x 80% (conduit fill) x 0.58 (temp. correction) = 18.56 A (N) New

Single Line Notes:

1. The Inverter is transformerless. It does not connect one of the DC circuit conductors in the PV array to
Approved by:
ground and has no internal bonding jumper. GEC is not required.
2. All wire sizes are as indicated or larger.
3.
4.
Wire sizes meet the criteria of 125% continuous use factor.
All equipment is bonded by mechanical means or by a grounding conductor.
1 - Line
5. All modules and rails are grounded mechanically using Prosolar Grounding Mid-Clamps. Jokeland, CA 94600
6.
7.
The system is grounded at the neutral buss in the main electrical panel.
The system is grid - intertie only, has no batteries or UPS.
Contractor: Sun Solar 510-282-0840
CA Lic#888888

25 Milky Way
DISCLAIMER: If any Errors, Discrepancies or Omissions appear in these drawings, specifications or other contract documents; The Owner or General Contractor shall notify the Designer, in writing,
Customer: Dear Customer Jokeland, CA 94600
of such error or omission. In the event that the Owner or General Contractor falls to give such notice, before construction and/or fabrication of the work, the Owner or General Contractor will be 510-000-0000
held responsible to the result of any errors, discrepancies or omissions and the cost of rectifying them. Drawing Number:
16-022
REV: # Scale: Sheet 4 of 5