External Static Pressure Calculation Sheet

Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

DISCHARGE SIDE
SUPPLY AIR
250*200 2.9 5.1 136.88 42.40
GRILLE

Straight Duct 350*150. 0.65 2.9 5.1 136.88 0.492 0.32

VCD 350*150. 2.9 5.1 0.52 1 136.88 0.492 2.65


1-2.
ELBOW 350*150. 2.9 5.1 0.16 1 136.88 0.492 0.82

Straight Duct 350*150. 4.25 2.9 5.1 1 136.88 0.492 2.09

Reducer 350*150/350*275 2.9 5.1 0.05 1 136.88 0.492 0.26

TEE 350*275X 300*225 4 9.7982 0.11 1 363.44 0.61 1.08

Straight Duct 2-3. 350*275 8.05 4 9.7982 1 363.44 0.61 4.91

Reducer 500*350/350*275 4 9.7982 0.05 1 363.44 0.61 0.49


External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

TEE 500*350X 400*300 5 14.82 0.02 1 809.48 0.625 0.30

Straight Duct 500*350 3.4 5 14.82 1 809.48 0.625 2.13


3-4.
TEE 500*349 X 250*150 5.4 17.4 0.02 1 877.92 0.729 0.35

Straight Duct 500*350 3.4 5.4 17.4 1 877.92 0.729 2.48

Reducer 4-5. 500*375/500*350 5.4 17.4 0.05 1 877.92 0.729 0.87

TEE 500*375 X 150*150 5.3 16.94 0.02 1 929.84 0.679 0.34

Straight Duct 4-5. 500*375 3.4 5.3 16.94 1 929.84 0.679 2.31

Reducer 500*400/500*375 5.3 16.94 0.05 1 929.84 0.679 0.85

TEE 500*400 X 150*150 5.25 16.54 0.02 1 981.76 0.637 0.33


5-6.
Straight Duct 500*400 3.4 5.25 16.54 981.76 0.637 2.17
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

TEE 6-7. 500*400 X 150*150 5.53 18.34 0.02 1 1033.68 0.702 0.37

Straight Duct 6-7. 500*400 3.4 5.53 18.34 1033.68 0.702 2.39 ###

Reducer 6-7. 500*425/500*400 5.53 18.34 0.05 1 1033.68 0.702 0.92

TEE 500*425 X 150*150 5.45 17.86 0.02 1 1085.6 0.66 0.36

Straight Duct 7-8. 500*425 3.4 5.45 17.86 1085.6 0.66 2.24

Reducer 500*450/500*425 5.45 17.86 0.05 1 1085.6 0.66 0.89

500*450.X
TEE 5.4 17.46 0.02 1 1137.52 0.623 0.35
150X150
8-9.
Straight Duct 500*450. 3.4 5.4 17.46 1137.52 0.623 2.12

TEE 500*450.X 150*150 5.64 19.1 0.02 1 1189.44 0.678 0.38

Straight Duct 9-10. 500*450. 3.4 5.64 19.1 1189.44 0.678 2.31
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
9-10. (m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

Reducer 500*475/500*450 5.64 19.1 0.05 1 1189.44 0.678 0.96

TEE 500*475.X 150*150 5.6 18.64 0.02 1 1241.36 0.641 0.37


10-11.
Straight Duct 500*475. 3.4 5.6 18.64 1241.36 0.641 2.18

TEE 500*475.X 150*150 5.8 20.22 0.02 1 1293.28 0.693 0.40

Straight Duct 11-12. 500*475. 3.4 5.8 20.22 1293.28 0.693 2.36

REDUCER 500*500 /500*475. 5.8 20.22 0.05 1 1293.28 0.693 1.01

TEE 500*500.X 150*150 5.734 19.76 0.02 1 1345.2 0.656 0.40


12-13.
Straight Duct 500*500. 3.4 5.734 19.76 1345.2 0.656 2.23

TEE 500*500.X 150*150 5.955 21.31 0.02 1 1397.12 0.705 0.43

Straight Duct 13-14. 500*500. 3.4 5.955 21.31 1397.12 0.705 2.40
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
13-14. (m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

Reducer 525*500/500*500. 5.955 21.31 0.05 1 1397.12 0.705 1.07

TEE 525*500.X 150*150 5.88 20.8 0.02 1 1449.04 0.669 0.42

Straight Duct 14-15. 525*500. 3.4 5.88 20.8 1449.04 0.669 2.27

Reducer 550*500/525*500. 5.88 20.8 0.05 1 1449.04 0.669 1.04

TEE 550*500.X 150*150 5.82 20.34 0.02 1 1500.96 0.637 0.41


15-16.
Straight Duct 550*500. 3.4 5.82 20.34 1500.96 0.637 2.17

TEE 550*500.X 150*150 6 21.77 0.02 1 1552.88 0.679 0.44

Straight Duct 16-17. 550*500. 3.4 6 21.77 1552.88 0.679 2.31

Reducer 575*500/550*500. 5.88 20.8 0.05 1 1449.04 0.669 1.04

TEE 575*500.X 150*150 5.955 21.31 0.02 1 1604.8 0.648 0.43


17-18.
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C
17-18.
Straight Duct 575*500. 3.4 5.955 21.31 1604.8 0.648 2.20

TEE 575*500.X 150*150 6.15 22.7 0.02 1 1656.72 0.688 0.45

Straight Duct 18-19. 575*500. 3.4 6.15 22.7 1656.72 0.688 2.34

Reducer 600*500/575*500. 6.15 22.7 0.05 1 1656.72 0.688 1.14

TEE 600*500 X 150*150 6.1 22.21 0.02 1 1708.64 0.657 0.44


19-20.
Straight Duct 600*500 3.4 6.1 22.21 1708.64 0.657 2.23

TEE 600*500 X 150*150 6.27 23.59 0.02 1 1760.56 0.696 0.47

Straight Duct 20-21. 600*500. 3.4 6.27 23.59 1760.56 0.696 2.37

Reducer 625*500/600*500. 6.27 23.59 0.05 1 1760.56 0.696 1.18

TEE 625*500./ 150*150 6.2 23.1 0.02 1 1812.48 0.665 0.46


21-22.
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C
21-22.
Straight Duct 625*500. 3.4 6.2 23.1 1812.48 0.665 2.26

TEE 625*500.X 150*150 6.4 24.43 0.02 1 1864.4 0.702 0.49

Straight Duct 22-23. 625*500. 3.4 6.4 24.43 1864.4 0.702 2.39

Reducer 650*500/625*500 6.4 24.43 0.05 1 1864.4 0.702 1.22

TEE 650*500./150*150 6.3 23.92 0.02 1 1916.32 0.673 0.48


23-24.
Straight Duct 650*500. 3.4 6.3 23.92 1916.32 0.673 2.29

TEE 650*500.X 150*150 6.48 25.24 0.02 1 1968.24 0.708 0.50

Straight Duct 24-25. 650*500. 3.4 6.48 25.24 1968.24 0.708 2.41

Reducer 675*500/650*500. 6.48 25.24 0.05 1 1968.24 0.708 1.26

TEE 675*500.X 150*150 6.413 24.71 0.02 1 2020.16 0.679 0.49

25-26.
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

Straight Duct 25-26. 675*500. 3.4 6.413 24.71 2020.16 0.679 2.31

Reducer 700*500/675*500. 6.413 24.71 0.05 1 2020.16 0.679 1.24

TEE 700*500.X 150*150 6.35 24.24 0.02 1 2072.08 0.652 0.48


26-27.
Straight Duct 700*500. 3.55 6.35 24.24 2072.08 0.652 2.31

TEE 700*500./ 150*150 6.511 25.47 0.02 1 2124 0.684 0.51

Straight Duct 700*500. 3.4 6.511 25.47 1 2124 0.684 2.33

ELBOW 27-28. 700*500. 6.511 25.47 0.4 1 2124 0.684 10.19

Straight Duct 700*500 6 6.511 25.47 2124 0.684 4.10

Mouth Connection 700*500 3.50

SUCTION SIDE
Mouth Connection 700*500 6.511 25.47 2 2124 0.684 3.50

28-29.
External Static Pressure Calculation Sheet
Project : WSTOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-02

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure drop
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) (pa)
Vp(Pa) C

Straight tDuct 700*500 2 6.511 25.47 0 0.684 1.37


28-29.

SAND TRAP
1000*700 3.26 6.38 1 2124 16.90
LOUVRE

CALCULATED PRESSURE DROP IN Pa 179.567

SAFETY FACTOR 30% 53.870

TOTAL PRESSURE DROP IN Pa 233.437

TOTAL PRESSURE DROP IN inches of Water 0.919

DESIGN PRESSURE DROP IN inches of Water 1.500


External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

DISCHARGE SIDE

SUPPLY AIR GRILL 400*250 5.36 299.657 14.50

Straight Duct 325*250. 0.65 3.953 9.387 299.657 0.651 0.42

VCD 325*250. 3.953 9.387 0.52 1 299.657 0.651 4.88


1-2.
ELBOW 325*250. 3.953 9.387 0.42 1 299.657 0.651 3.94

Straight Duct 325*250. 4.25 3.953 9.387 1 299.657 0.651 2.77

Reducer 550*250/325*250 3.953 0.05 1 299.657 0.614 0.00


External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

TEE 550*250X 325*250 4.82 13.95 0.02 1 599.313 0.697 0.28

Straight Duct 2-3. 550*250 8.05 4.82 13.95 0 1 599.313 0.697 5.61

Reducer 550*350/550*250 4.82 13.95 0.05 1 599.313 0.697 0.70

TEE 550*350X 325*250 5.04 15.26 0.01 1 898.97 0.608 0.15

Straight Duct 3-4. 550*350 3.4 5.04 15.26 898.97 0.608 2.07

Reducer 550*425/550*350 5.04 15.26 0.05 1 898.97 0.608 0.76

TEE 550*425X 325*250 5.49 18.08 0.01 1 1198.63 0.63 0.18

Straight Duct 4-5. 550*425 3.4 5.49 18.08 0 1 1198.63 0.63 2.14

Reducer 550*500/550*425 5.49 18.08 0.05 1 1198.63 0.63 0.90

TEE 550*500X 325*250 5.81 20.26 0.01 1 1498.28 0.635 0.20

5-6.
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Straight Duct 5-6. 550*500 3.4 5.81 20.26 1 1498.28 0.635 2.16

Reducer 550*550/550*500 5.81 20.26 0.05 1 1498.28 0.635 1.01

TEE 550*550X325*250 6.33 24.1 0.01 1 1797.94 0.706 0.24

Straight Duct 6-7. 550*550 3.4 6.33 24.1 1 1797.94 0.706 2.40

Reducer 625*550/550*550 6.33 24.1 0.05 1 1797.94 0.706 1.21

TEE 625*550X325*250 6.51 25.45 0.01 1 2097.6 0.688 0.25

Straight Duct 7-8. 625*550 3.4 6.51 25.45 2097.6 0.688 2.34

Reducer 700*550/625*550 6.51 25.45 0.05 1 2097.6 0.688 1.27

TEE 700*550X325*250 6.66 26.644 0.01 1 2397.25 0.672 0.27

Straight Duct 8-9. 700*550 3.4 6.66 26.644 2397.25 0.672 2.28
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
8-9. (m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Reducer 775*550/700*550 6.66 26.644 0.05 1 2397.25 0.672 1.33

TEE 775*550X325*250 6.79 27.71 0.01 1 2696.91 0.66 0.28

Straight Duct 9-10. 775*550 3.4 6.79 27.71 2696.91 0.66 2.24

Reducer 825*550/775*550 6.79 27.71 0.05 1 2696.91 0.66 1.39

TEE 825*550X 325*250 7.11 30.37 0.01 1 2996.57 0.692 0.30

Straight Duct 10-11. 825*550 3.4 7.11 30.37 2996.57 0.692 2.35

Reducer 900*550/825*550 7.11 30.37 0.05 1 2996.57 0.692 1.52

TEE 900*550X325*250 7.2 31.16 0.01 1 3296.22 0.675 0.31

Straight Duct 11-12. 900*550 3.4 7.2 31.16 3296.22 0.675 2.30

Reducer 950*550/900*550 7.2 31.16 0.05 1 3296.22 0.675 1.56


External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

TEE 950*550X325*250 7.47 33.53 0.01 1 3595.88 0.702 0.34

Straight Duct 12-13. 950*550 3.4 7.47 33.53 3595.88 0.702 2.39

1025*550/ 950*550 7.47 33.53 0.05 1 3595.88 0.702 1.68

1025*550X
TEE 7.54 34.17 0.01 1 3895.53 0.684 0.34
325*250

Straight Duct 13-14. 1025*550 3.4 7.54 34.17 3895.53 0.684 2.33

1075*550/
REDUCER 7.54 34.17 0.05 1 3895.53 0.684 1.71
1025*550
1075*550X
TEE 7.77 36.29 0.01 1 4195.19 0.706 0.36
325*250

Straight Duct 14-15. 1075*550 3.4 7.77 36.29 4195.19 0.706 2.40

1150*550/
Reducer 7.77 36.29 0.05 1 4195.19 0.706 1.81
1075*550
1150*550X
TEE 7.828 36.818 0.01 1 4494.85 0.69 0.37
325*250

15-16.
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Straight Duct 15-16. 1150*550 3.4 7.828 36.818 4494.85 0.69 2.35

1250*550/
Reducer 7.828 36.818 0.05 1 4494.85 0.69 1.84
1150*550
1250*550
TEE 7.742 36 0.01 1 4794.5 0.645 0.36
X325*250

Straight Duct 16-17. 1250*550 3.4 7.742 36 4794.5 0.645 2.19

1250*575/
Reducer 7.742 36 0.05 1 4794.5 0.645 1.80
1250*550
1250*575X
TEE 7.834 36.88 0.01 1 5094.16 0.641 0.37
325*250

Straight Duct 17-18. 1250*575 3.4 7.834 36.88 5094.16 0.641 2.18

1250*600/
Reducer 7.834 36.88 0.05 1 5094.16 0.641 1.84
1250*575
1250*600 X
TEE 7.92 37.68 0.01 1 5393.82 0.636 0.38
325*250
18-19.
Straight Duct 1250*600 3.4 7.92 37.68 5393.82 0.636 2.16
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

1250*600
TEE 8.36 41.99 0.01 1 5693.47 0.706 0.42
X325*250

Straight Duct 19-20. 1250*600 3.4 8.36 41.99 5693.47 0.706 2.40

1250*625/
Reducer 8.36 41.99 0.05 1 5693.47 0.706 2.10
1250*600
1250*625 X
TEE 8.42 42.57 0.01 1 5993.13 0.696 0.43
325*250

Straight Duct 20-21. 1250*625 3.4 8.42 42.57 5993.13 0.696 2.37

1250*650/
Reducer 8.42 42.57 0.05 1 5993.13 0.696 2.13
1250*625
1250*650X
TEE 8.472 43.12 0.01 1 6292.79 0.687 0.43
325*250

Straight Duct 21-22. 1250*650 3.4 8.472 43.12 6292.79 0.687 2.34

1250*675/
Reducer 8.472 43.12 0.05 1 6292.79 0.687 2.16
1250*650
1250*675X
TEE 8.522 43.63 0.01 1 6592.44 0.678 0.44
325*250

22-23.
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Straight Duct 22-23. 1250*675 3.4 8.522 43.63 6592.44 0.678 2.31

1250*700/
Reducer 8.522 43.63 0.05 1 6592.44 0.678 2.18
1250*675
1250*700X
TEE 8.57 44.11 0.01 1 6892.1 0.669 0.44
325*250

Straight Duct 23-24. 1250*700 3.4 8.57 44.11 6892.1 0.669 2.27

1250*725/
Reducer 8.57 44.11 0.05 1 6892.1 0.669 2.21
1250*700
1250*725 *
TEE 8.6 44.56 0.01 1 7191.76 0.661 0.45
325*250

Straight Duct 24-25. 1250*725 3.4 8.6 44.56 7191.76 0.661 2.25

1250*750/
Reducer 8.6 44.56 0.05 1 7191.76 0.661
1250*725
1250*750 X
TEE 8.653 44.98 0.01 1 7491.41 0.652 0.45
325*250
25-26.
Straight Duct 1250*750 3.4 8.653 44.98 7491.41 0.652 2.22
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

1250*750 X
TEE 9 48.65 0.01 1 7791.07 0.703 0.49
325*250

Straight Duct 26-27. 1250*750 3.4 9 48.65 7791.07 0.703 2.39

1250*775/
Reducer 9 48.65 0.05 1 7791.07 0.703 2.43
1250*750

TEE 1250*775/ 325*250 9 48.937 0.01 1 8090.73 0.693 0.49

Straight Duct 27-28. 1250*775 3.55 9 48.937 8090.73 0.693 2.46

1250*800
Reducer 9 48.937 0.05 1 8390.38 0.693 2.45
/1250*775

1250*800 X
TEE 9.05 49.22 0.01 1 8390.38 0.683 0.49
325*250

Straight Duct 28-29. 1250*800 3.4 9.05 49.22 1 8390.38 0.683 2.32

1250*825/
Reducer 9.05 49.22 0.05 1 8390.38 0.683 2.46
1250*800

1250*825 X
TEE 9.075 49.48 0.01 1 8690 0.673 0.49
325*250

29-30.
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Straight Duct 29-30. 1250*825 3.4 9.075 49.48 8690 0.673 2.29

1250*850/
Reducer 9.075 49.48 0.05 1 8690 0.673 2.47
1250*825

TEE 1250*850/ 325*250 8.89 47.5 0.01 1 8784.42 0.635 0.48

Straight Duct 1250*850 6 8.89 47.5 8784.42 0.635 3.81


30-31.
ELBOW 1250*850 8.89 47.5 0.75 1 8784.42 0.635 35.63

MOUTH
8.89 47.5 0 2 8784.42 0.635 3.20
CONNECTION

SUCTION SIDE

Straight Duct 1250*850 2 8.89 47.5 8878.8 0.635 1.27

VCD 1250*850 8.89 47.5 0.52 1 8784.42 0.635 24.70


31-32.
MOUTH
8.89 47.5 0 2 8784.42 0.635 3.20
CONNECTION
SAND TRAP
1800X1600 3.25 1 8784.42 0.635 15.80
LOUVRE
External Static Pressure Calculation Sheet
Project :
Consultant :
Main contractor :
Unit Ref. :STPRF-01 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

CALCULATED PRESSURE DROP IN Pa 235.00

SAFETY FACTOR(30%) 70.50

TOTAL PRESSURE DROP IN Pa 305.51

TOTAL PRESSURE DROP IN INCHES OF WATER 1.20

PRESSURE DROP AS PER DESIGN(INCHES OF WATER) 2.50


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

DISCHARGE SIDE
SUPPLY AIR
1 500X350 2 236 6.2
GRILLE

2 STRAIGHT DUCT 350X200 0.3 3.665 8.1 236 0.626 0.1878

3 VCD 350X200 3.665 8.1 0.52 1 236 4.21


1-2.
4 ELBOW 350X200 3.665 8.1 0.185 1 236 0.626 1.50

5 STRAIGHT DUCT 350X200 3.4 3.665 8.1 236 0.626 2.1284

6 REDUCER 350*325/350*200 4.424 8.1 0.29 1 236 2.35

7 TEE 350X325 * 350X200 4.424 11.76 0.02 1 472 0.24

8 STRAIGHT DUCT 2-3. 350X325 3.4 11.76 472 0.652 2.22

9 REDUCER 450X350/350X325 11.76 0.05 1 472 0.652 0.59

10 TEE 450X350 * 350X200 4.8 13.9 0.01 1 708 0.626 0.14

11 STRAIGHT DUCT 3-4. 450*350 3.4 708 0.626 2.13 ###

12 Reducer 450X425/450X350 4.8 13.9 0.05 1 708 0.626 0.70

13 TEE 5.26 16.61 0.01 1 944 0.17

14 STRAIGHT DUCT 4-5. 450*425 3.4 944 0.656 2.23

15 REDUCER 450*425/450*350 5.26 16.61 0.05 1 944 0.83

16 TEE 5.592 18.79 0.01 1 1180 0.668 0.19


5-6.
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C
5-6.
17 STRAIGHT DUCT 500*450 3.4 5.592 18.79 1180 0.668 2.27

18 REDUCER 5-6. 5.592 18.79 0.05 1 1180 0.668 0.94

19 TEE 5.854 20.59 0.01 1 1415 0.67 0.21

20 STRAIGHT DUCT 6-7. 575*450 3.4 5.854 20.59 1416 0.67 2.28

21 REDUCER 5.854 20.59 0.05 1 1416 0.67 1.03

22 TEE 6.07 22.13 0.01 1 1652 0.22

23 STRAIGHT DUCT 7-8. 650*450 3.4 6.07 22.13 1652 0.668 2.27

24 REDUCER 6.07 22.13 0.05 1 1652 1.11

25 TEE 6.254 23.5 0.01 1 1888 0.24

26 STRAIGHT DUCT 8-9. 725*450 3.4 6.254 1888 0.664 2.26

27 REDUCER 6.254 23.5 0.05 1 1888 1.18

28 TEE 6.42 24.73 0.01 1 2124 0.25

29 STRAIGHT DUCT 9-10. 800*450 3.4 2124 0.659 2.24

30 REDUCER 6.42 24.73 0.05 1 2124 1.24

31 TEE 6.729 27.21 0.01 1 2360 0.27

32 STRAIGHT DUCT 10-11. 800*475 3.4 2360 0.697 2.37

33 REDUCER 6.729 27.21 0.05 1 2360 1.36


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

34 TEE 6.658 26.636 0.01 1 2596 0.27


11-12.
35 STRAIGHT DUCT 800*525 3.4 2596 0.64 2.18

36 REDUCER 11-12. 6.658 26.636 0.05 1 2596 1.33

37 TEE 6.9 28.75 0.01 1 2832 0.29

38 STRAIGHT DUCT 12-13. 800*550 3.4 2832 0.668 2.27

39 REDUCER 6.9 28.75 0.05 1 2832 1.44

40 TEE 7.22 31.33 0.01 1 3068 0.31

41 STRAIGHT DUCT 13-14. 800*570 3.4 3068 0.71 2.41

42 REDUCER 7.22 31.33 0.05 1 3068 1.57

43 TEE 7.1 30 0.01 1 3304 0.30

44 STRAIGHT DUCT 14-15 800*625 3.4 3304 0.642 2.18

45 REDUCER 7.1 30 0.05 3304 0.00

46 TEE 7.273 31.787 0.01 1 3540 0.32

47 STRAIGHT DUCT 15-16. 800*650 3.4 3540 0.662 2.25

48 REDUCER 7.273 31.787 0.05 1 3540 1.59

49 TEE 7.464 33.47 0.01 1 3776 0.33

50 STRAIGHT DUCT 16-17 800*675 3.4 3776 0.68 2.31


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
16-17 Vp(Pa) C

51 REDUCER 7.464 33.47 0.05 1 3776 1.67

52 TEE 7.642 35.1 0.01 1 4012 0.35


17-18
53 STRAIGHT DUCT 800*700 3.4 4012 0.695 2.36

54 REDUCER 17-18 7.642 35.1 0.05 1 4012 1.76

55 TEE 7.625 34.94 0.01 1 4248 0.35

56 STRAIGHT DUCT 18-19 850*700 3.4 4248 0.668 2.27

57 REDUCER 7.625 34.94 0.05 1 4248 1.75

58 TEE 7.824 36.78 0.01 1 4484 0.37

59 STRAIGHT DUCT 19-20 875*700 3.4 4484 0.69 2.35

60 REDUCER 7.824 36.78 0.05 1 4484 1.84

61 TEE 8 38.59 0.01 1 4720 0.39

62 STRAIGHT DUCT 20-21 900*700 3.4 4720 0.71 2.41

63 REDUCER 8 38.59 0.05 1 4720 1.93

64 TEE 7.99 38.33 0.01 1 4956 0.38

65 STRAIGHT DUCT 21-22 950*700 3.4 4956 0.684 2.33

66 REDUCER 7.99 38.33 0.05 1 4956 1.92

67 TEE 8 38.12 0.01 1 5192 0.38

22-23
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

68 STRAIGHT DUCT 22-23 1000*700 3.4 5192 0.661 2.25

69 REDUCER 8 38.12 0.05 1 5192 1.91

70 TEE 8 38.7 0.01 1 0.39


5428
71 STRAIGHT DUCT 23-24 1000*725 3.4 0.656 2.23
5428
72 REDUCER 8 38.7 0.05 1 1.94
5428
73 TEE 8 39.3 0.01 1 0.39
5664
74 STRAIGHT DUCT 1000*750 13.695 8 39.3 1 0.65 8.90
5664
75 TEE 8 39.3 0.01 1 0.65 0.39
5664

76 STRAIGHT DUCT 24-25. 1000*750 4.8 8 39.3 0.65 3.12


5664

77 ELBOW 1000X750 8 39.3 1.1 2 5664 0.65 86.46

MOUTH
78 2 5664 3.50
CONNECTION

SUCTION SIDE

MOUUTH
79 1000X750 2 5664 3.50
CONNECTION

80 STRAIGHT DUCT 1000*750 5.4 8 39.3 5664 0.65 3.51


25-26.

81 VCD 1000X750 8 39.3 0.52 1 5664 0.65 20.44


SAND TRAP
82 1500*1200 3.363 16.00
LOUVER

CALCULATED PRESSURE DROP IN Pa 242.58


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : CPRF-1

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
SL# Description NODE Size(mm) Length(m)
(m/s)
pressure- coefficient-
fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

SAFETY FACTOR(30%) 72.77


TOTAL PRESSURE DROP IN Pa 315.35
TOTAL PRESSURE DROP IN INCHES OF WATER 1.242
DESIGN PRESSURE DROP 2.5
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

DISCHARGE SIDE

SUPPLY AIR GRILL 350*125 169.92 24.60

Straight Duct 300*200 0.65 3.05 5.59 169.92 0.487 0.32

VCD 300*200 3.05 5.59 0.52 1 169.92 0.487 2.91


1-2.
ELBOW 300*200 3.05 5.59 0.16 1 169.92 0.487 0.89

Straight Duct 300*200 4.25 3.05 5.59 1 169.92 0.487 2.07

Reducer 350*300/300*200 3.05 5.59 0.05 1 169.92 0.487 0.28


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

350*300X
TEE 4.17 10.46 0.04 1 410.64 0.614 0.42
300*225

Straight Duct 2-3. 350*300 8.05 4.17 10.46 1 410.64 0.614 4.94

Reducer 400*350/350*300 4.17 10.46 0.05 1 410.64 0.614 0.52

TEE 400*350 X 350*200 4.78 13.73 0.01 1 627.76 0.664 0.14

Straight Duct 3-4. 400*350 3.4 4.78 13.73 1 627.76 0.664 2.26

Reducer 450*400/400*350 4.78 13.73 0.05 1 627.76 0.664 0.69

TEE 450*400X300*225 5.2 16.25 0.01 1 877.92 0.667 0.16


4-5.
Straight Duct 450*400 3.4 5.2 16.25 1 877.92 0.667 2.27

Reducer 450*400/500*400 5.2 16.25 0.05 1 877.92 0.667 0.81


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

TEE 500*400X250*150 5.2 16.227 0.01 1 972.32 0.626 0.16

Straight Duct 5-6. 500*400 3.4 5.2 16.227 1 972.32 0.626 2.13

Reducer 500*425/500*400 5.2 16.227 0.05 1 972.32 0.626 0.81

TEE 500*425X250*150 5.36 17.25 0.01 1 1066.72 0.64 0.17

Straight Duct 6-7. 500*425 3.4 5.36 17.25 1066.72 0.64 2.18

Reducer 500*450/500*425 5.36 17.25 0.05 1 1066.72 0.64 0.86

TEE 500*450X 250*150 5.502 18.19 0.01 1 1161.12 0.648 0.18

Straight Duct 7-8. 500*450 3.4 5.502 18.19 1161.12 0.648 2.20 ###

Reducer 525*450/ 500*450 5.502 18.19 0.05 1 1161.12 0.648 0.91

TEE 525*450 X 250*150 5.67 19.32 0.01 1 1255.52 0.67 0.19

8-9.
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Straight Duct 8-9. 525*450 3.4 5.67 19.32 1255.52 0.67 2.28

Reducer 550*450/ 525*450 5.67 19.32 0.05 1 1255.52 0.67 0.97

TEE 550*450X 250*150 5.8 20.37 0.01 1 1349.92 0.68 0.20

Straight Duct 9-10. 550*450 3.4 5.8 20.37 1349.92 0.68 2.31

Reducer 575*450/550*450 5.8 20.37 0.05 1 1349.92 0.68 1.02

TEE 575*450X 250*150 5.97 21.38 0.01 1 1444.32 0.694 0.21

Straight Duct 10-11. 575*450 3.4 5.97 21.38 1444.32 0.694 2.36

Reducer 600*450/575*450 5.97 21.38 0.05 1 1444.32 0.694 1.07

TEE 600*450 X 250*150 6.1 22.38 0.01 1 1538.72 0.707 0.22

Straight Duct 11-12. 600*450 3.4 6.1 22.38 1538.72 0.707 2.40
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
11-12. (m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Reducer 650*450/600*450 6.1 22.38 0.05 1 1633.12 0.707 1.12

TEE 650*450 X 250*150 6 21.62 0.01 1 1633.12 0.653 0.22

Straight Duct 12-13. 650*450 3.4 6 21.62 1633.12 0.653 2.22

REDUCER 675*450/650*450 6 21.62 0.05 1 1633.12 0.653 1.08

TEE 675*450 X 250*150 6.12 22.5 0.01 1 1727.52 0.664 0.23

Straight Duct 13-14. 675*450 3.4 6.12 22.5 1727.52 0.664 2.26

Reducer 700*450/675*450 6.12 22.5 0.05 1 1727.52 0.664 1.13

TEE 700*450 X 250*150 6.2 23.38 0.01 1 1821.92 0.673 0.23

Straight Duct 14-15. 700*450 3.4 6.2 23.38 1821.92 0.673 2.29

Reducer 725*450/700*450 6.2 23.38 0.05 1 1821.92 0.673 1.17


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

TEE 725*450 X 250*150 6.35 24.2 0.01 1 1916.32 0.683 0.24

Straight Duct 15-16. 725*450 3.4 6.35 24.2 1916.32 0.683 2.32

Reducer 750*450/725*450 6.35 24.2 0.05 1 1916.32 0.683 1.21

TEE 750*450 X 250*150 6.45 25 0.01 1 2010.72 0.69 0.25

Straight Duct 16-17. 750*450 3.4 6.45 25 2010.72 0.69 2.35

Reducer 800*450/750*450 6.45 25 0.05 1 2010.72 0.69 1.25

TEE 800*450 X 250*150 6.36 24.29 0.01 1 2105.12 0.647 0.24


17-18.
Straight Duct 800*450 3.4 6.36 24.29 2105.12 0.647 2.20

TEE 800*450 X 250*150 6.641 26.5 0.01 1 2199.52 0.704 0.27

Straight Duct 18-19. 800*450 3.4 6.641 26.5 0.77 2199.52 0.704 2.39
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
18-19. (m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Reducer 800*475/800*450 6.541 26.5 0.77 1 2199.52 0.704 20.41

TEE 800*475 X 250*150 6.541 25.7 0.01 1 2293.92 0.66 0.26

Straight Duct 19-20. 800*475 3.4 6.541 25.7 2293.92 0.66 2.24

Reducer 800*500/800*475 6.541 25.7 0.05 1 2293.92 0.66 1.29

TEE 800*500 X 250*150 6.45 24.994 0.01 1 2388.32 0.622 0.25


20-21.
Straight Duct 800*500 3.4 6.45 2388.32 0.622 2.11

TEE 800*500 X 250*150 6.705 27.01 0.01 1 2482.72 0.669 0.27

Straight Duct 21-22. 800*500 3.4 6.705 27.01 0.8 2482.72 0.669 2.27

Reducer 800*525/800*500 6.609 27.01 0.8 1 2482.72 0.669 21.61

TEE 800*525 X 250*150 6.609 26.24 0.01 1 2577.12 0.631 0.26


22-23.
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C
22-23.
Straight Duct 800*525 3.4 2577.12 0.631 2.15

TEE 800*525 X 250*150 6.852 28.21 0.01 1 2671.52 0.676 0.28

Straight Duct 23-24. 800*525 3.4 6.852 28.21 2671.52 0.676 2.30

Reducer 800*550/800*525 6.852 28.21 0.05 1 2671.52 0.676 1.41

TEE 800*550 X 250*150 6.76 27.42 0.01 1 2765.92 0.639 0.27


24-25.
Straight Duct 800*550 3.4 6.76 2765.92 0.639 2.17

TEE 800*550 X 250*150 6.99 29.33 0.01 1 2860.3 0.681 0.29

Straight Duct 25-26. 800*550 3.4 6.99 29.33 2860.32 0.681 2.32

Reducer 800*575/800*550 6.99 29.33 0.05 1 2860.32 0.681 1.47

TEE 800*575 X 250*150 6.891 28.53 0.01 1 2954.72 0.645 0.29


26-27.
External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C
26-27.
Straight Duct 800*575 3.4 6.891 2954.72 0.645 2.19

TEE 800*575 X 250*150 7.11 30.38 0.01 1 3049.12 0.685 0.30

Straight Duct 23-24 800*575 3.55 7.11 30.38 3049.12 0.685 2.43

Reducer 800*600/800*575 7.11 30.38 0.05 1 3049.12 0.685 1.52

TEE 800*600 X 250*150 7.01 29.56 0.01 1 3143.52 0.30


24-25
Straight Duct 800*600 3.4 7.01 29.56 1 3143.52 0.65 2.21

TEE 800*600 X 250*150 7.224 31.36 0.01 1 3237.92 0.687 0.31

Straight Duct 800*600 3.4 7.224 31.36 3237.92 0.687 2.34

REDUCER 825*600/800*600 31.36 0.05 1 3237.92 0.687 1.57

TEE 25-26 7.2 31.3 0.01 1 3332.32 0.674 0.31

Straight Duct 825*600 6 7.2 31.3 3332.32 0.674 4.04

ELBOW 825*600 31.3 1.1 1 3332.32 34.43


External Static Pressure Calculation Sheet
Project : WS TOWER
Consultant :
Main contractor :
25-26
Unit Ref. : LPRF-03 Basement-02 to Machine floor

Velocity Loss
Velocity Qty of Airflow Frictional Total Pressure
Description NODE Size(mm) Length(m) pressure- coefficient-
(m/s) fittings (lps) loss (Pa/m) drop (pa)
Vp(Pa) C

Mouth Connection 825*600 3332.32 3.20

SUCTION SIDE
Mouth Connection 825*600 2 3332.32 3.20

Straight Duct 26-27 825*600 2 7.2 31.3 3332.32 0.674 1.35

LOUVRE 1800*1200 3.52 1 3332.32 15.95

TOTAL PRESSURE DROP CALCULATED(Pa) 230.35

SAFETY FACTOR (30%) 69.11

TOTAL PRESSURE DROP (Pa) 299.46

PREESSURE DROP IN INCHES OF WATER 1.18

PRESSURE DROP AS PER DESIGN(INCHES OF WATER) 1.5