4. Any convention for which type of cycle (1ms/3ms/8ms...) to be used for different
protection/metering block?
All connected signal blocks should have same clock cycle. Measurement blocks should
have clock cycle of 8ms.
5. Outputs from measurement blocks are not taken anywhere, why measured then ?
8. Trip signal option present at L3CPDIF, why LDLPSCH is used to sent trip ?