DETAILED DESIGN FOR BLACK POWDER FILTRATION UNIT FOR


GTP
SKID FOUNDATION CALCULATION NOTE
CONTRACTOR Document N°: COMPANY Document N°: Rev: 000
55367-OMV-CV-CA-001 NAWGTP-AEI-PF02-220-CV-CLN-00001 Page : 19 of 20

8.2. REINFORCEMENT
8.2.1. Bottom Spread
 Inferior bed reinforcement:

Figure 7 : Inferior Reinforcement


For 3.98 cm2/m section  70 HA16, Spacing = 15cm will be adapted.

 Superior bed reinforcement:

Figure 8 : Superior Reinforcement

For 3.91 cm2/m section  36 HA14, Spacing = 15cm will be adapted

ALPHA ENGINEERING Intl.


Sahloul III - 4054 Sousse – Tunisia
Code TVA : 950448R/A/M/000. R.C : B279902006
Tél : +216 73 821 245 / 246 / 247 Fax : +216 73 821 249
This document is the property of Alpha Engineering International who will safeguard its rights according to the civil and penal provisions of the Law.