A + -
VA = 8314?0° V VAS = 480?0° V VBS = 480?-120° V
- - - +
In = 20.96?59.5° A VB = 8314 ?-120° V IBS = 363?-180.5° A
n B
.

The real and reactive powers supplied by each transformer are calculated below:
PA  VAS I A cos    480 V  363 A  cos 0   60.5    85.8 kW
QA  VAS I A cos    480 V  363 A  sin 0   60.5    151.7 kvar
PB  VBS I B cos    480 V  363 A  cos 120   120.5    174.2 kW
QB  VBS I B sin    480 V  363 A  sin 120   120.5    1.5 kvar

Notice that the real and reactive powers supplied by the two transformers are radically different, put the
apparent power supplied by each transformer is the same. Also, notice that the total power PA  PB
supplied by the transformers is equal to the power consumed by the loads (within roundoff error), while
the total reactive power Q A  QB supplied by the transformers is equal to the reactive power consumed by
the loads.
2-20. A 50-kVA 20,000/480-V 60-Hz single-phase distribution transformer is tested with the following results:
Open-circuit test Short-circuit test
(measured from secondary side) (measured from primary side)
VOC = 480 V VSC = 1130 V
IOC = 4.1 A ISC = 1.30 A
POC = 620 W PSC = 550 W
(a) Find the per-unit equivalent circuit for this transformer at 60 Hz.
(b) What is the efficiency of the transformer at rated conditions and unity power factor? What is the
voltage regulation at those conditions?
(c) What would the ratings of this transformer be if it were operated on a 50-Hz power system?
(d) Sketch the equivalent circuit of this transformer referred to the primary side if it is operating at 50
Hz.
(e) What is the efficiency of the transformer at rated conditions on a 50 Hz power system, with unity
power factor? What is the voltage regulation at those conditions?
(f) How does the efficiency of a transformer at rated conditions and 60 Hz compare to the same
physical device running a 50 Hz?
SOLUTION
(a) The base impedance of this transformer referred to the primary side is

60
V   20,000 V 
2 2

Z base,P  P   8 k
S 50 kVA
The base impedance of this transformer referred to the secondary side is

VS   480 V 
2 2

Z base,S    4.608 
S 50 kVA
The open circuit test yields the values for the excitation branch (referred to the secondary side):
I ,OC 4.10 A
YEX    0.00854 S
V ,OC 480 V
 POC   620 W 
   cos 1  1
   cos    71.6
 VOC I OC    480 V  4.1 A  
YEX  GC  jBM  0.00854  71.6  0.00270  j 0.00810
RC  1 / GC  370 
X M  1/ BM  123 
The excitation branch elements can be expressed in per-unit as
370  123 
RC   80.3 pu XM   26.7 pu
4.608  4.608 
The short circuit test yields the values for the series impedances (referred to the primary side):
VSC 1130 V
Z EQ    869 
I SC 1.30 A
 PSC   550 W 
  cos 1  1
  cos    68.0
 VSC I SC   1130 V 1.30 A  
Z EQ  REQ  jX EQ  86968  326  j806 

The resulting per-unit impedances are


326  806 
REQ   0.041 pu X EQ   0.101 pu
8,000  8,000 
The per-unit equivalent circuit is
IP IS
REQ jXEQ

+ 0.041 j0.101 +

VP RC jXM VS

80.3 j26.7

- -
61
(b) The per-unit primary voltage at rated conditions and unity power factor is
VP  VS  I S Z EQ
VP  10 V  10  0.041  j 0.101    1.0465.54 pu

The per-unit power consumed by REQ is

PEQ  I 2 R  1 pu   0.041 pu   0.041 pu


2

The per-unit power consumed by RC is

V 2 1.046 
2

PC  P   0.0136 pu
RC 80.3
Therefore the efficiency of this transformer at rated load and unity power factor is
Pout Pout 1.00
 100%  100%  100%  94.8%
Pin Pout  PEQ  PC 1.00  0.041  0.0136
and the voltage regulation is
1.046  1.00
VR   100%  4.6%
1.00
(c) The voltage and apparent power ratings of this transformer must be reduced in direct proportion to
the decrease in frequency in order to avoid flux saturation effects in the core. At 50 Hz, the ratings are
50 Hz
S rated   50 kVA   41.7 kVA
60 Hz
50 Hz
VP ,rated   20, 000 V   16, 667 kV
60 Hz
50 Hz
VS ,rated   480 V   400 V
60 Hz
(d) The transformer parameters referred to the primary side at 60 Hz are:
RC  Z base RC ,pu   8 k  80.3  642 k
X M  Z base X M ,pu   8 k  26.7   214 k
REQ  Z base REQ ,pu   8 k  0.041  328 
X EQ  Z base X EQ ,pu   8 k  0.101  808 

At 50 Hz, the resistance will be unaffected but the reactances are reduced in direct proportion to the
decrease in frequency. At 50 Hz, the reactances are
 50 Hz 
XM     214 k   178 k
 60 Hz 
 50 Hz 
X EQ     808    673 
 60 Hz 

62
The resulting equivalent circuit referred to the primary at 50 Hz is shown below:
IP IS
REQ jXEQ

+ 328 ? j673 ? +

VP RC jXM VS

642 k? j178 k?

- -
(e) The base impedance of this transformer at 50 Hz referred to the primary side is

V  16,667 V 
2 2

Z base,P  P   6.66 k
S 41.7 kVA
The base impedance of this transformer at 50 Hz referred to the secondary side is

VS   400 V 
2 2

Z base,S    3.837 
S 41.7 kVA
The excitation branch elements can be expressed in per-unit as
642 k 178 k
RC   96.4 pu XM   26.7 pu
6.66 k 6.66 k
The series impedances can be expressed in per-unit as
328  673 
REQ   0.0492 pu X EQ   0.101 pu
6.66 k 6.66 k
The per-unit primary voltage at rated conditions and unity power factor is
VP  VS  I S Z EQ
VP  10 V  10  0.0492  j 0.101    1.0545.49 pu

The per-unit power consumed by REQ is

PEQ  I 2 R  1 pu   0.0492 pu   0.0492 pu


2

The per-unit power consumed by RC is

VP 2 1.054 
2

PC    0.0115 pu
RC 96.4
Therefore the efficiency of this transformer at rated load and unity power factor is
Pout Pout 1.00
 100%  100%  100%  94.3%
Pin Pout  PEQ  PC 1.00  0.0492  0.0115

63
and the voltage regulation is
1.054  1.00
VR   100%  5.4%
1.00
(f) The efficiency of the transformer at 50 Hz is almost the same as the efficiency at 60 Hz (just slightly
less), but the total apparent power rating of the transformer at 50 Hz must be less than the apparent power
rating at 60 Hz by the ratio 50/60. In other words, the efficiencies are similar, but the power handling
capability is reduced.
2-21. Prove that the three-phase system of voltages on the secondary of the Y- transformer shown in Figure 2-
37b lags the three-phase system of voltages on the primary of the transformer by 30°.
SOLUTION The figure is reproduced below:

-
VB'
+ +
VA + +
VB - - VC'
-
-
-
VC VA'
+
+

+ +
VA VA'

- -

+ +
VB VB'

- -

+ +
VC VC'

- -

Assume that the phase voltages on the primary side are given by
VA  VP 0 VB  VP   120 VC  VP 120
Then the phase voltages on the secondary side are given by
  
VA  VS 0 VB  VS   120 VC  VS 120