Ambient Conditions and Protection Data: Cm1 N c1, c2 ASC9.3 Double Auxiliary A, B, C ASZ7.3 Potentiometer Y1 Y2 21 N

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Ambient conditions and protection data

Classification to Automatic action: Type 1AA / Type 1AC / Modulation Action


IEC/EN 60730 Pollution degree: 2
Housing protection as per IP54
IEC/EN 60529
Environmental conditions
Transportation Class 2K3
(in transport packaging) Temperature -30...65 °C
to IEC/EN 60721-3-2 Humidity 5...95 % (no condensation)
Operation Class 3K5
to IEC/EN 60721-3-3 Temperature -15...50 °C
Humidity 5...95 % (no condensation)
Storage Class 1K3
to IEC/EN 60721-3-1 Temperature -15...50 °C
Humidity 5...95 % (no condensation)

Internal diagrams

SKD32.51, SKD32.21 Cm1 end switch

4567G01
21 Y1 Y2 3 3 a b c
n solenoid valve for spring-
AC 230 V, 3-Position 100 % 100 %
0% 0% return
c1 c2 c1, c2 ASC9.3 double auxiliary
switch
n Cm1
N 4 5 4 5 a, b, c ASZ7.3 potentiometer
ASC9.3 ASZ7.3... Y1 Positioning signal «open»
SKD32.50 Y2 Positioning signal «close»
4567G02

Y1 Y2 3 3 a b c

AC 230 V, 3-Position 100 % 100 % 21 spring-return function


0% 0%
N neutral conductor
c1 c2

Cm1
N 4 5 4 5

ASC9.3 ASZ7.3...

SKD82.51 Cm1 end switch


4569G01

21 Y1 Y2 3 3 a b c
n solenoid valve for spring-
AC 24 V, 3-Position 100 % 100 %
0% 0% return
c1 c2 c1, c2 ASC9.3 double auxiliary
switch
n Cm1
G 4 5 4 5 a, b, c ASZ7.3 potentiometer
ASC9.3 ASZ7.3... Y1 Positioning signal «open»
SKD82.50 Y2 Positioning signal «close»
4569G02

Y1 Y2 3 3 a b c

AC 24 V, 3-Position 100 % 100 % 21 spring-return function


0% 0%
G System potential
c1 c2

Cm1
G 4 5 4 5

ASC9.3 ASZ7.3...

SKD60, SKD60U, DC 0 ...10 V


U position indication
U oder Ausgang
SKD62, 4 ... 20 mA Z override control
SKD62U, SKD62UA
voll offen
Eingang Y positioning signal
Zwangsteuerung

AC 24 V, DC 0…10 V, 0 ...100 %
(Signalpriorität) M measuring neutral
G0 operating voltage AC 24 V:
4…20 mA, 0…1000 Ω Y
DC 0 ...10 V
oder 0 ...100 %
Eingang
Valve Seat
Detection
4 ... 20 mA Hub system neutral (SN)
M Valve Jam G operating voltage AC 24 V:
Detection
system potential (SP)
G0 Switching without power as
a spring return function
MMI
G

Ventil

15/20

Siemens Electrohydraulic actuators for valves CM1N4561en


Smart Infrastructure 2019-12-17

You might also like