TECHNICAL DATA

BULLETIN 1492
Digital/Analog Programmable
Controller Wiring Systems

Bulletin 1492 Digital and Analog Wiring Systems

Table of Contents
Description Page Description Page
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Options and Features Marking System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Digital (IFM/XIM and Cables). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Analog (AIFM and Cables). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Web Site Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Ordering Digital and Analog Wiring Systems. . . . . . . . . . . . . . . . . . . . . . . . . . 28 Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Specifications
Digital IFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Digital Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Analog Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Bulletin 1492
Digital/Analog Programmable Controller Wiring Systems

2
Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 3

Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Description Connecting to Allen-Bradley PLC I/O is fast, convenient, and reliable with the
Allen-Bradley Bul. 1492 wiring system. Unlike conventional terminal blocks,
the Bul. 1492 wiring system connects to digital, analog, and high speed counter
PLC I/O modules through pre-wired and pre-tested cables. The Bulletin 1492
wiring systems are compatible with modular I/O modules for Bulletin 1756
ControlLogix, 1769 CompactLogix, 1746 SLC 500, and 1771 PLC-5. A select
group of wiring system modules are also compatible with the base I/O of the
MicroLogix 1200 (40 I/O base only) and 1500 packaged controllers, plus the
PowerFlex 700H and 700S drives. In addition, wiring system solutions are
available for 1794 Flex I/O through the Flex D-shell type base modules, 1794-
TB37DS and 1794-TB62DS. The interface modules are mounted onto a
standard DIN #3 Rail. Pre-printed adhesive label cards containing field-wiring
information are included for each interface module and I/O module
combination.

Benefits Reduced Wiring Time

PLC I/O module to field device wiring is completed in a fraction of the time
when Bulletin 1492 wiring systems are used as compared with the traditional
method of wiring each point to the PLC I/O swing arm and field-side
terminal blocks. Pre-wired cables are factory-wired to the I/O wiring arm on
one end and a connector for the Interface Module (IFM) on the other. IFMs
enhance the capability of the I/O systems with added terminations, field-side
LED status indicators, isolation circuits, overcurrent protection, and higher
amp outputs. Both standard and specific build to order length cables are
available, providing the correct length for any panel in a neat, space-efficient
wiring solution.

Reduced Wiring Errors

Wiring system cables are pre-tested to ensure 100% accurate connections and
eliminate the need for point-to-point checking of wiring—no more crossed
wires and loose connections between the I/O module and the terminal block.
Even one error in wiring 128 I/O points in a point-to-point system may
require a complete check of the wiring. Wiring errors can take several minutes
or hours to track down and correct before the panel is ready for startup.
When IFMs and cables are snapped in place, they fit every time — no need to
find the wrong or loose connection, resulting in a much higher rate of success
at system startup.

Faster Troubleshooting and Easier Maintenance

Normal terminal blocks can’t offer the benefits of Bulletin 1492 wiring
systems, such as LED indication on each I/O point. Wiring systems improve
system startup and ease troubleshooting and maintenance. Diagnostic
capabilities in the form of fuses, blown fuse indication, and field-side ON-

Publication 1492-TD008D-EN-P - January 2009


4 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

State LEDs — in a reduced space — allow maintenance personnel to quickly


locate faults, reduce downtime, and improve overall productivity.
Benefits, Continued Increased Volume and Productivity

Cable interconnections for a Bulletin 1492 wiring system can be up to 30 times


faster to install than traditional point-to-point wiring, enabling OEMs and
panel builders using wiring systems to build panels faster and produce more
machines.

Reduced Wire Preparation and Routing

Pre-wired Bulletin 1492 wiring system cables eliminate the time and costs
associated with stripping and cutting wires. Routing wires is much easier with
wiring systems, since engineers only have to worry about routing one pre-
wired cable versus the 20 or 40 wires needed in the traditional wiring method.

Labeling and Marking

Pre-printed, PLC I/O-specific adhesive label strips for quick marking of IFM
module terminals save labor compared with point-to-point wiring that requires
labor-intensive wire markers. Pre-wired cables require no wire labels. Pre-
printed I/O-specific labels ensure neat, easy-to-read identification of wires and
I/O points for all users.
The marking of traditional terminal blocks has even caused some OEMs to
move toward a high-tech approach of plotting markers, requiring additional
equipment in the form of a plotter system and a PC to run the plotter
software.

Simplified Design

Design engineers can simplify their panel drawings by calling out an IFM and
pre-wired cable instead of having to detail every single wire and terminal block
on their drawings. Simplified panel drawings aid both the installer and the end
user who receives the panel.

Increased DIN Rail Density

An increasing trend in the industry is to pack more products into the same
DIN Rail space. Wiring systems support this trend, as they require less DIN
Rail space than traditional terminal blocks. For example, if an OEM were to
use a 40-point IFM in place of 40 terminal blocks, DIN Rail space can be
reduced by more than 50%.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 5

Benefits, Continued Increased DIN Rail Density, Continued

All IFMs have terminals for connecting the I/O field wiring. In addition, extra
terminal, sensor, fusible IFMs, and relay IFMs contain common terminals that
are used as power busses for sensors and actuators. No additional terminal
blocks are needed to provide power to the sensors/actuators — saving
valuable panel/DIN Rail space.
To further reduce panel space, narrow IFMs (e.g., Catalog Number
1492-IFM20FN) have been designed. They require 45% less space than the
standard length IFMs, making them well-suited for tightly packed enclosures.
The high-density narrow IFMs have two rows of 10 field-wiring terminals with
an overall length of 60 mm (2.36 in.).

Quality-Looking Panels

The pre-wired cables and IFM wiring system modules organize the wiring in
your panel and provide a consistent look. Pre-printed adhesive labels for the
terminals neatly identify field-wiring connections, which correspond to the
I/O module address. A large marking area is also available for identifying I/O
information on the IFM.

Fewer Parts, Less Inventory and Lower Carrying Cost

A wiring system involves an IFM and the cable, versus the block, barrier,
jumper, markers, wires, and swing arms associated with traditional hardwired
systems. Therefore, it requires fewer components and, in turn, less inventory
and lower carrying costs.

Design Flexibility

To develop a cost-effective system, the hardware components must meet the


needs of the design engineer. Rockwell Automation provides the broadest
range of digital and analog systems in the industry. Allen-Bradley Wiring
Systems deliver a lower life-cycle cost.

Publication 1492-TD008D-EN-P - January 2009


6 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Digital IFM Options and Digital IFMs, similar to groups of terminal blocks, are available with either
20-pin (typically 8 to 16 PLC I/O points) or 40-pin (typically 16 to 32 PLC
Features I/O points) cable connectors. The number of field-side wiring terminals varies
with the type of module — from one to three terminals per I/O point. LEDs
and fuse clips are available on-board the IFMs to customize your wiring
system to your application and provide assistance with troubleshooting your
control panel. The IFMs are compatible with both the pre-wired cables and
the IFM-ready cables.

All of the digital IFMs have the following features:

cULus: Hazardous Locations: Class I Div 2 (all modules, except those with relays); Groups A, B, D, and D.
Temperature Code: T3C @ 60 °C.
UL File No. E10314, Guide No. NRAG
cULus: Ordinary Locations; Module with relays; UL File No. E113724 Guide No. NRAQ
CE Compliant for all applicable directives

Refer to Specifications, page 191.

Pre-printed and blank adhesive marking


Keyed cable connector (20- or 40-pin) with locking strips are provided to identify either
tabs for easy installation and secure connection of Programmable Controller I/O field-side
IFM pre-wired and IFM-ready cables. wiring terminals or your own application
requirements.

High-density field-side wiring terminals


Standard DIN #3 Rail mounting for quick installation. allow more connections in less space
and accommodate #22…12 AWG wire.
Continuous current rating of 2 A per
circuit supports higher-current
programmable controller output modules.
Digital IFM

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 7

Digital IFM Options and Standard Terminal Modules


Features, Continued

Standard terminal IFM modules provide one field-side wiring terminal per
programmable controller input or output point, as well as enough terminals
for the I/O module power connections. The standard terminal modules are
ideal for applications in which the I/O device commons are terminated in the
field or remotely from the I/O module panel.

Extra Terminal Modules

Extra terminal modules provide two or four field-side terminals per input or
output point. IFMs which are not point-to-point isolated have two terminals
per input or output point. Point-to-point isolated IFMs have two or four
terminals per input or output point. Non-isolated IFMs have the lower row of
extra terminals commoned together in groups of 10 ➊, to serve as a power bus
for the field device commons. Isolated IFMs have terminals isolated into 8 or
16 groups, which allows each group of I/O devices to reference a different
power source. The extra terminal modules are beneficial in applications in
which the I/O devices are terminated within the same panel as the I/O
modules — eliminating the need for many additional terminal blocks. These
modules are also available with optional field-side status LEDs for
troubleshooting inputs and outputs.
➊ Except Catalog Numbers 1492-IFM20D24A-2 and -IFM20D120A-2, which are in groups of 20.

Publication 1492-TD008D-EN-P - January 2009


8 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Digital IFM Options and Sensor Modules


Features, Continued

Sensor modules provide three field-side terminals per input point. The middle
and lower rows of terminals, commoned together in groups of 18, serve as
power busses for 3-wire sensor types of devices — eliminating additional
terminal blocks and jumpering systems. The sensor modules provide a
compact method of terminating and powering 24V AC/DC or 120V AC
(Catalog Number IFM20F-3 only) 3-wire devices.

LED Modules

Voltage-indicating LEDs are available on the standard, extra terminal, and


sensor IFMs. The LEDs provide field-side troubleshooting diagnostics: the
on/off status of an input device or the on/off status of the programmable
controller output circuit. When used in conjunction with the logic-side
programmable controller LEDs, the IFM LEDs can help determine whether a
problem resides in the I/O module or field device/wiring. The LED modules
have unique circuitry that allows compatibility with sinking or sourcing input
or output modules.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 9

Digital IFM Options and Fusible Modules


Features, Continued

Fusible modules provide a convenient method of adding overcurrent


protection into your programmable controller field wiring. These modules
have 5 x 20 mm fuse clips on-board and are available with and without blown
fuse indication. The 24V or 120V blown fuse indicators reduce the
troubleshooting time to locate and replace a blown fuse on the IFM. The
fusible modules have an easy-to-remove see-through acrylic cover to prevent
objects from contacting fuse circuitry under normal operation. Standard fuse
holders reside in the IFM, aiding in the removal of a fuse with a fuse puller
(fuses are not included). The fusible modules also have two or four terminals
per I/O point to create a power bus for input or output load connections.
Fusible modules are available in both isolated and non-isolated versions. There
are a select number of fusible IFMs available for input modules.

Relay and Relay Expander Modules

Relay and Relay Expander Interface Modules (XIMs) were developed to


maximize the effectiveness of users’ applications that require output contact
ratings greater than 2 A. Driving large loads up to 10 A for applications such
as motor starters is now possible with Bulletin 1492 Wiring Systems. In
addition, the Relay Modules provide a means to isolate output points.
The Relay and Relay Expander product line consists of a Relay Master module
and Expander Module(s) with expander cable. The 8 or 16 point Relay Master
modules provide the connection for the 20- or 40-pin cable connectors for the
pre-wired Bulletin 1492 cable.

Publication 1492-TD008D-EN-P - January 2009


10 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Digital IFM Options and Relay and Relay Expansion Modules, Continued
Features, Continued
Relay Master Relay Master with Fusing

Relay master XIMs feature field-replaceable relays with 120V or 24V rated
coils. The field-side Form C contacts are rated 240V 10 A (de-rated to 12 A
per adjacent pair on the XIM). The Form C relay output provides isolated
output channels and a different voltage level from one output channel to the
next. Other features include coil-side LED indicating the PLC output module
status, and transient suppression on each coil. In addition, 16-point relay
masters are available with or without 5 x 20 fuse holders so customers can fuse
the output contacts.

Relay Expanders Relay Expander (16) with Fusing

Relay expander XIMs feature eight field-replaceable relays with 120V or 24V
rated coils. The field-side Form C contacts are rated 240V 10 A (de-rated to
12 A per adjacent pair on the XIM). The Form C relay output provides
isolated output channels and a different voltage level from one output channel
to the next. Other features include coil-side LED indicating the PLC output
module status, and transient suppression on each coil. In addition, a relay
expander can have 5 x 20 fuse holders so customers can fuse the output
contacts. An expander cable is provided for connection to the mating module.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 11

Digital IFM Options and Relay and Relay Expansion Modules, Continued
Features, Continued
Fusible Expanders

The fusible expander modules feature eight 5 x 20 mm finger-safe fuse


holders, blown fuse indicators, and extra terminals for landing two wires per
field-side device. They are offered with eight fuse holders for both 24V and
120V applications. An expander cable is provided for connection to the mating
module. Fuses are not provided.

Feed-Through Expanders

The feed-through expander modules feature eight channels with extra


terminals for landing two wires per field-side device. An expander cable is
provided for connection to the mating module.

Publication 1492-TD008D-EN-P - January 2009


12 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Digital IFM Options and Digital IFM Modules with Field Removable Terminal Blocks
Features, Continued (RTBs)

Select groups of standard, fused and relay digital Bulletin 1492 wiring system
modules (refer to Selection Tables) have field terminal blocks that can be
removed (RTB). This RTB feature can provide easier wiring of field devices in
a control cabinet where the IFM is located in a hard to reach area, or where
hand-access is limited. It can also provide easier and faster replacement of a
damaged or defective Bulletin 1492 wiring system module. The removable
plug portion of the RTB assembly has a screw at each end to securely fasten it
to the RTB socket, which is mechanically secured to the module circuit board
hand housing. Modules are shipped with the RTB socket, but without the
removable plug(s). Plugs are available with screw style (e.g., 1492-RTB20N)or
push-in style (e.g., 1492-RTB16P) terminals and must be ordered separately
(two pieces cat. no., refer to page 17 for details). Refer to the selection tables
for the particular PLC I/O system of interest to determine which modules are
offered with field removable terminal blocks.
All of the features available on fixed terminal block products (e.g. labels,
agency certification, etc.) are also provided for the removable terminal block
Bulletin 1492 wiring system modules.

Screw-style RTB plug


(Order separately)

Push-in style RTB plug


(Order separately)

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 13

Digital IFM Options and


Features, Continued Digital Pre-Wired Cables

Pre-Wired Cable and Interface Module

Bulletin 1492 pre-wired cables are designed to minimize control wiring in a


panel. Pre-wired cables, when used with an IFM, replace the point-to-point
wiring between Allen-Bradley programmable controller I/O modules and
individual terminal blocks. The pre-wired cables have a removable terminal
block or wiring arm at the I/O end of the cable and a cable connector on the
other end to connect to the IFM. All of the pre-wired cables use #22 AWG
wire and are 100% tested for continuity to make a perfect connection every
time. The digital pre-wired cables are offered in four standard lengths of 0.5,
1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also
available as build-to-order products. Pre-wired cables are available for many of
the Bulletin 1756 ControlLogix, 1769 Compact I/O used with CompactLogix
and MicroLogix 1500, 1794 Flex, and 1771 I/O modules. Plus availability for
the base I/O of the MicroLogix 1500 and 40 I/O base of the MicroLogix
1200 packaged controllers. A select group of modules are also available for the
PowerFlex 700H and 700S drives.

Ready-to-Wire Digital Cables

Digital I/O Module-Ready Cable and Standard Terminal Block

Digital I/O module-ready cables have an I/O removable terminal block or


wiring arm pre-wired to one end to of the cable and free connectors on the
other end for wiring into standard terminal blocks or other type of connectors.
I/O-ready cables have individual color-coded conductors for quick wire-to-
terminal coordination. Most I/O-ready cables use #18 AWG conductors for
higher current applications or longer cable runs. The I/O-ready cables are
offered in standard lengths of 1.0, 2.5, and 5.0 m to fit a variety of applications.
Other cable lengths are also available as build-to-order products. Digital I/O

Publication 1492-TD008D-EN-P - January 2009


14 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

module ready cables are available for many of the Bulletin 1756 ControlLogix,
1769 Compact I/O used with CompactLogix and MicroLogix 1500, 1794
Flex, and 1771 I/O modules. Plus availability for the base I/O of the
MicroLogix 1500 and 40 I/O base of the MicroLogix 1200 packaged
controllers. A select group of modules are also available for the PowerFlex
700H and 700S drives.

Digital IFM Options and Ready-to-Wire Digital Cables, Continued


Features, Continued

IFM-Ready Cable and Interface Module

IFM-ready cables have a cable connector that attaches to the IFM pre-wired to
one end and free connectors ready to wire to I/O modules or other
components on the other end. IFM-ready cables use #22 AWG wire and have
individual color-coded conductors for quick wire-to-terminal coordination.
The digital IFM-ready cables are offered in standard lengths of 1.0, 2.5, and
5.0 m to fit a variety of applications. Other cable lengths are also available as
build-to-order products.

IFM Catalog Number Important: The following IFM catalog number breakdown is for explanation
purposes only. It is not a product configurator. Not all combinations of fields
Explanation for Digital I/O are valid product catalog numbers. First, select the desired IFM using the steps
Modules in Ordering Digital and Analog Wiring Systems on page 28. Then, use this
breakdown for verification and explanation only.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 15

1492– IFM 20 F– F120– 2


Bulletin No.
No. of Field-Side Wiring Terminals
Digital Interface Modules Blank One per I/O connection
IFM Fixed (non-removable) terminal block 2 Two per I/O connection
RIFM Removable terminal block 3 Three per I/O connection
4 Four per I/O connection

No. of Cable Connector Pins


20 20 pins Fuses and Their Indicators
40 40 pins Blank No fuse clips
F 5 x 20 mm fuse clips
F24 5 x 20 mm fuse clips with 24V blown fuse
Status Indication indicators for output modules
F No LEDs F24A 5 x 20 mm fuse clips with 24V blown fuse
FN Narrow IFM indicators for input modules
D24 24V AC/DC LEDs for input and output modules F120 5 x 20 mm fuse clips with 120V blown fuse
D24N Narrow IFM with 24V AC/DC LEDs indicators for output modules
D24A 24V AC/DC LEDs for input modules F120A 5 x 20 mm fuse clips with 120V blown fuse
indicators for input modules
DS24 Isolated IFM with 24/48V AC/DC LEDs for output
modules F240 5 x 20 mm fuse clips with 240V blown fuse
indicators for output modules
DS24A Isolated IFM with 24V AC/DC LEDs for input modules
F24D-2 5 x 20 mm fuse clips with 24V blown fuse
D120 120V AC LEDs for input and output modules low leakage indicators for the 1756-OB16D
D120N Narrow IFM with 120V AC LEDs diagnostic output module
D120A 120V AC LEDs for input modules F24AD-4 5 x 20 mm fuse clips with 24V blown fuse
DS120 Isolated IFM with 120V AC LEDs for output modules low leakage indicators for the 1756-IB16D
diagnostic input module
DS120A Isolated IFM with 120V AC LEDs for input modules
FS Isolated IFM with 5 x 20 mm fuse clips
D240 240V AC LEDs for output modules
FS24 Isolated IFM with 5 x 20 mm fuse clips with
DS240A Isolated IFM with 240V AC LEDs for input modules
24V blown fuse indicators for output
D240A 240V AC LEDs for input modules modules
FS24A Isolated IFM with 5 x 20 mm fuse clips with
24V blown fuse indicators for input modules
FS120 Isolated IFM with 5 x 20 mm fuse clips with
120V blown fuse indicators for output
modules
FS120A Isolated IFM with 5 x 20 mm fuse clips with
120V blown fuse indication for input
modules
FS240 Isolated IFM with 5 x 20 mm fuse clips with
240V blown fuse indication for output
modules

Publication 1492-TD008D-EN-P - January 2009


16 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Terms for Relay Relay master and expander XIMs are available for Bulletin 1746, 1756, 1769,
and 1771 digital output modules.
Master/Expander IFMs Relay Master XIM — Provides 8 or 16 relay outputs for a digital output
module.
Expander XIM — In addition to the relay master XIM, an expander XIM
provides eight or sixteen additional outputs. There are five types of expander
XIMs: eight-channel relays, eight-channel fusing, and eight-channel feed-
through XIMs.

Relay Master/Expander Important: The following XIM catalog number breakdown is for explanation
purposes only. It is not a product configurator. Not all combinations of fields
XIMs Catalog Number are valid product catalog numbers First, select the desired XIM using the steps
Explanation for Digital I/O in Ordering Digital and Analog Wiring Systems on page 28. Then, use this
Modules breakdown for verification and explanation only.

1492– XIM 20 24– 2

Bulletin No.
No. Relays or Extra Terminals
Relay Master and Expander Interface Modules 2 2 terminals per point
XIM Fixed (non-removable) terminal block 8R 8 relays
RXIM Removable terminal block 16R 16 relays
16RF 16 fused relays

No. Cable Connector Pins Rating of Relay Coil or Blown Fuse Indicator
20 20 pins (master only) 24 24V relay coil
40 40 pins (master only) 120 120V relay coil
Blank Expander module F No relays or fuses
F-F24 5 x 20 mm fuse clips with 24V blown fuse indicators
F-F120 5 x 20 mm fuse clips with 120V blown fuse indicators

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 17

Removable Terminal Block Important: The following RTB plug catalog number breakdown is for
explanation only.
(RTB) Plug Catalog Number
Explanation
1492– RTB 20 – N

Bulletin No.
Connector Style
N Screw Style
Removable Terminal Block Plug Number of
Poles/ P Push-in Style
Terminals
8
12
14
16
17
20

Publication 1492-TD008D-EN-P - January 2009


18 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

IFM and XIM Cable Catalog Important: Use the following tables as a product configurator for pre-wired,
IFM-ready, and I/O module-ready cables for Bulletins 1746, 1756, and 1771
Number Explanation for digital I/O module cables. All combinations of these fields make valid product
Digital I/O Modules catalog numbers. Refer to selection tables for IFM/XIM compatibility and
ordering.

1492– CABLE 010 A

Bulletin No.

Cable Type
A, B, C, D, Pre-wired cables for 8-point isolated and 16-point digital
Digital Interface Cable E, G, N, S Bulletin 1746 I/O modules ➊
CR Pre-wired cable for Catalog Number 1746-OA16 (XIM only)
F, T Pre-wired cable for digital Bulletin 1771 I/O modules ➋
FF Pre-wired cable with fused wiring arm for 16-point digital
Standard or Build-to-Order Length Cable Bulletin 1771 output modules ➋
005 0.5 m (1.64 ft) Standard H Pre-wired cable for 32-point digital Bulletin 1746 I/O modules ➊
010 1.0 m (3.28 ft) Length J, K, L, M, R Pre-wired cables for 16-point isolated and 32-point digital
Bulletin 1771 I/O modules ➋
025 2.5 m (8.20 ft)
U, V, W, X Pre-wired cables for 8- and 16-point digital Bulletin 1756 I/O
050 5.0 m (16.40 ft) modules ➌
001… 0.1…2.0 m (0.328…6.56 ft) Build-to-Order Y, Z Pre-wired cables for 16-point isolated and 32-point digital
020 0.1 m (0.328 ft) increments Length Bulletin 1756 I/O modules ➌
020… 2.0…10.0 m (6.56…32.8 ft)
P Digital IFM-ready cable with 20 conductors
100 0.5 m (1.64 ft) increments
Q Digital IFM-ready cable with 40 conductors
100… 10.0…30.0 m (32.8…98.4 ft)
300 1.0 m (3.28 ft) increments N3 Digital I/O module-ready cable with 40-point Catalog
Number 1746-N3 cable connector
RTBB Digital I/O module-ready cable with 16-point Catalog
Number 1746-RT25B terminal block (blue)
RTBO Digital I/O module-ready cable with 16-point Catalog
Number 1746-RT25C terminal block (orange)
RTBR Digital I/O module-ready cable with 16-point Catalog
Number 1746-RT25R terminal block (red)
TBCH Digital I/O module-ready cable with 36-pin Catalog
Number 1756-TBCH removable terminal block
TBNH Digital I/O module-ready cable with 20-pin Catalog
Number 1756-TBNH removable terminal block
WA Digital I/O module-ready cable with Catalog Number 1771-WA
8-point wiring arm
WD Digital I/O module-ready cable with Catalog Number 1771-WD
6-point wiring arm
WH Digital I/O module-ready cable with Catalog Number 1771-WH
16-point wiring arm
WHF Digital I/O module-ready cable with Catalog Number 1771-WHF
16-point fused wiring arm
WN Digital I/O module-ready cable with Catalog Number 1771-WN
32-point wiring arm
➊ To make sure the Bulletin 1746 SLC 500 digital I/O module is compatible with the
IFM/XIM, refer to pages 29, 31, and 34.
➋ To make sure the Bulletin 1771 PLC digital I/O module is compatible with the
IFM/XIM, refer to pages 59, 60, and 62.
➌ To make sure the Bulletin 1756 ControlLogix digital I/O module is compatible with the
IFM/XIM, refer to pages 36, 38, and 40.

The cables used for Relay Master/Expander XIMs are the same as those used
for Digital I/O Modules (page 28) with the exception of the Catalog
Number 1746-OA16 output module, which uses the 1492-CABLE*CR cable.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 19

IFM and XIM Cable Catalog Important: Use the following tables as a product configurator for pre-wired,
IFM-ready, and I/O module-ready cables for Bulletins 1769 digital I/O
Number Explanation for module cables. All combinations of these fields make valid product catalog
Digital I/O Modules, number. Refer to selection tables for IFM/XIM compatibility and ordering.
Continued
1492– CAB 010 A69

Bulletin No.

Cable Type
Digital Interface Cable A69, B69, C69, Pre-wired cables for 8, 16, and 32-point
D69, E69, F69, Bulletin 1769 digital I/O modules
G69, H69, J69,
Standard or Build-to-Order Length Cable K69, L69, M69
005 0.5 m (1.64 ft) Standard RTN10 I/O-ready cable with Catalog
010 1.0 m (3.28 ft) Length Number 1769-RTBN10 terminal block
025 2.5 m (8.20 ft) RTN18 I/O-ready cable with Catalog Number 1769-
050 5.0 m (16.40 ft) RTBN18 terminal block
001-020 0.1…2.0 m (0.328…6.56 ft) Build-to-Order RTN32I I/O-ready cable for 1769-IQ32 module
0.1 m (0.328 ft increments) Length RTN32O I/O ready cable for 1769-OB32 module
020-100 2.0…10.0 m (6.56…32.8 ft) R71 Pre-wired cables for 16-channel isolated and
0.5 m (1.64 ft) increments 32-channel digital Bulletin 1771 I/O
100-300 10.0…30.0 m (32.8…98.4 ft) modules ➊
1.0 m (3.28 ft) increments ➊ To make sure the Bulletin 1771 PLC analog I/O module is compatible with
the IFM, see pages 59 and 60.

Publication 1492-TD008D-EN-P - January 2009


20 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Cable Catalog Number Important: Use the following tables as a product configurator for pre-wired,
and I/O module-ready cables for Bulletin 1764 MicroLogix 1500 and 1762
Explanation for µ1200 and MicroLogix 1200 40 I/O controller digital I/O cables. All combinations of
µ1500 Base I/O to IFM these fields make valid product catalog numbers. Refer to selection tables for
Modules IFM compatibility and ordering.

1492– CAB 010 A6x

Bulletin No.
Cable Type for Bul. 1492-CAB010A62
A62, B62 Pre-wired cables for Bulletin 1762 40 I/O controllers
X62 I/O-ready cable for 1762-L40AWA, -L40BXB, and
Digital Interface Cable -L40BWA inputs
T62 I/O-ready cable for 1762-L40AWA, -L40BXB and
-L40BWA outputs
Standard or Build-to-Order Length Cable
005 0.5 m (1.64 ft) Standard Cable Type for Bul. 1492-CAB010A64
010 1.0 m (3.28 ft) Length
A64, B64, C64, F64 Pre-wired cables for Bulletin 1764 I/O base units
025 2.5 m (8.20 ft) W64 I/O-ready cable for 1764-24AWA, -24BWA base unit
050 5.0 m (16.40 ft) inputs
001… 0.1…2.0 m (0.328…6.56 ft) Build-to-Order X64 I/O-ready cable 1764-28BXB base unit inputs
020 0.1 m (0.328 ft) increments Length T64 I/O-ready cable for1764-24AWA, -24BWA base unit
020… 2.0…10.0 m (6.56…32.8 ft) outputs
100 0.5 m (1.64 ft) increments U64 I/O-ready cable for 1764-28BXB base unit outputs
100… 10.0…30.0 m (32.8…98.4 ft)
300 1.0 m (3.28 ft) increments

Cable Catalog Number Important: Use the following tables as a product configurator for pre-wired,
and I/O module-ready cables for Bulletin 1794 Flex I/O, Cat. Nos. 1794-
Explanation for 1794 Flex TB37DS, and 1794-TB62DS base units. All combinations of these fields
I/O to IFM Modules make valid product catalog number. Refer to selection tables for IFM
compatibility and ordering.

1492– CAB 010 A94

Bulletin No.

Digital Interface Cable Cable Type


A94 Pre-wired cables for Bulletin 1794 Flex digital I/O
using the Bulletin 1794-TB37DS base
Standard or Build-to-Order Length Cable B94 Pre-wired cables for Bulletin 1794 Flex digital I/O
005 0.5 m (1.64 ft) Standard using the Bulletin 1794-TB62DS base
Length G94 Digital I/O ready cable for digital I/O using the
010 1.0 m (3.28 ft) Bulletin 1794 TB37DS base
025 2.5 m (8.20 ft) H94 Digital I/O ready cable for digital I/O using the
050 5.0 m (16.40 ft) Bulletin 1794 TB62DS base
001-020 0.1…2.0 m (0.328…6.56 ft) Build-to-Order
0.1 m (0.328 ft increments) Length
020-100 2.0…10.0 m (6.56…32.8 ft)
0.5 m (1.64 ft) increments
100-300 10.0…30.0 m (32.8…98.4 ft)
1.0 m (3.28 ft) increments

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 21

Analog IFM Options and Analog IFMs (AIFMs), similar to groups of terminal blocks, are available with
either 15- or 25-pin D-shell connectors. The number of field-side wiring
Features terminals varies with the type of module — from three to five terminals per
analog I/O channel. AIFMs are available as feed-through or fusible to
customize the wiring system to your application.

All of the AIFMs have the following features:


cULus: Hazardous Locations: Class I Div 2;
Groups A, B, D, and D.
Temperature Code: T3C @ 60 °C.
UL File No. E10314, Guide No. NRAG
Factory Mutual (FM): Hazardous Locations; Metal polarized D-shell connector (15- or
Class I Div 2: Groups A, B, C, and D. 25-pin) for easy installation. Pre-wired cable
Temperature Rating: T3C @ 60 °C. FM file has mating D-shell connector with slide-
Pre-printed and blank adhesive marking
J.I.3000590 locking mechanism for secure connection.
strips are provided to identify either
CE Compliant for all applicable directives Provides the facility for continuous shield.
Programmable Controller I/O field-side
wiring terminals or your own application
Refer to Specifications, page 191. requirements.

High-density field-side wiring terminals


allow more connections in less space
and accommodate #22…12 AWG wire.

Continuous current rating of 2 A per


Standard DIN #3 Rail mounting for quick installation. circuit supports higher-current
programmable controller output modules.
Analog IFM

Analog Feed-Through Modules

Feed-through AIFMs have three terminals per analog I/O channel to wire the
analog I/O device connections and shield. The shield terminals are internally
bussed together and also tied to the D-shell housing to connect with the
Bulletin 1492 cable shield and back to the PLC module. Some feed-through
AIFMs also have special features (refer to page 26).
The Catalog Number 1492-AIFM4-3 AIFM, when used with Catalog
Numbers 1771-OFE2 and -OFE3 analog input modules, provides selectable
current limiting resistors. Simply flip a DIP switch to add the 250 Ω series
impedance into the output circuit. As a troubleshooting aid, test point loops
access the circuit on either side of the series resistor and can be used to

Publication 1492-TD008D-EN-P - January 2009


22 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

measure output circuit voltage/current. The limiting resistors are configured


on a per channel basis.
The Catalog Number 1492-AIFM6TC-3 AIFM for the Cat. Nos. 1756-IT6I
and 1756-IT6I2 controllers provide on- or off-board cold junction
compensation to allow thermocouples to be connected “remotely” while still
correcting for temperature at the termination point. The combination
thermistor and isothermal bar acquires temperature data at the AIFM for the
Bul. 1756 thermocouple module to adjust the input value.
The Catalog Number 1492-AIFM8-3 AIFM has eight extra terminals
commoned together in a power bus that can be used for Module Common
connections or power supply connections. The extra terminals and internal
jumpering eliminate the need for some terminal blocks for power connections
and jumper accessories.
Below are examples of the field-side connections available on the feed-through
AIFMs.
4-Wire Transmitter Input
AIFM Analog Input Module
1+ Pre-wired Cable
Channel 1+
Power Supply Transmitter 1-
Channel 1-

SHIELD = AIFM Field Terminal

Output
AIFM Analog Output Module

0 Pre-wired Cable
OUT 0
LOAD C
ANL COM

SH

Analog Fusible Modules

Fusible AIFMs are available for analog input modules. These AIFMs enable
you to fuse the input device power source on the field-side. The field-side
power source is distributed through individual on-board 5 x 20 mm fuse clips.
The fused AIFMs have 24V DC blown fuse indicators to reduce the
troubleshooting time needed to locate and replace a blown fuse. The fuse
holder has an integrated fuse puller to simplify fuse removal. Isolation switch

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 23

plugs or “dummy fuses” (refer to Accessories, page 184) are also available to
isolate an input circuit after power is removed. In addition, once the circuit has
been isolated and power restored, the input loop current can be measured in
2-wire transmitter applications.
The fusible AIFMs have five terminals per input channel (except Catalog
Number AIFM16-F-3, which has three terminals per channel) to wire the
input-device connections, device shield, and power connections for 2-, 3-, and
4-wire transmitters. The shield terminals are internally bussed together and
also tied to the D-shell housing to connect with the Bulletin 1492 cable shield
and back to the PLC module. There are two separate power busses
(4…16 terminals, depending on the AIFM) that can be used for +V and DC
COM connections and/or device Common. The extra terminals and internal
connections eliminate additional terminal blocks and jumpers — reducing
spare parts inventory, saving panel space, and simplifying installation.
Several of the fusible AIFMs have on-board DIP switches to easily connect
unused inputs to module common — reducing wiring on the field-side. You
no longer need extra jumper wires or comb-style jumpers to properly
terminate unused inputs, as recommended on many Bulletin 1746, 1756, and
1771 analog input modules. Inputs are jumpered via DIP switch on a per-
channel basis.
The Catalog Numbers 1492-AIFM4I-F-5 and 1492-AIFM4C-F-5 AIFMs
both have test point loops on either side of the fuse clips for easier access and
connection of metering equipment. Metering equipment can also be attached
to the fuse clips on other AIFMs for measuring input loop current.
Below are several examples of the field-side connections for 2- and 4-wire
transmitters available on the fusible AIFMs.

2-Wire Analog Input Transmitter

AIFM
+V

Power Supply V1
Analog Input Module
Transmitter Pre-wired Cable
1+
Channel 1+

SHIELD

1-
Channel 1-

VCOM = Fuse
= AIFM Field Side Terminal

Publication 1492-TD008D-EN-P - January 2009


24 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

4-Wire Analog Input Transmitter

AIFM
+V

Power Supply V1
Analog Input Module
1+ Pre-wired Cable
Channel 1+
Transmitter
1-
Channel 1-
SHIELD

VCOM

Note: Bulletin 1492 module wiring diagrams are available at www.ab.com.


Refer to page 186.

Analog AIFM Modules with Field Removable Terminal Blocks


(RTBs)

Select groups of analog Bulletin 1492 wiring system modules (refer to


Selection Tables) have field terminal blocks that can be removed (RTB). This
RTB feature can provide easier wiring of field devices in a control cabinet
where the IFM is located in a hard to reach area, or where hand-access is
limited. It can also provide easier and faster replacement of a damaged or
defective Bulletin 1492 wiring system module. The removable plug portion of
the RTB assembly has a screw at each end to securely fasten it to the RTB
socket, which is mechanically secured to the module circuit board and housing.
Modules hare shipped with the RTB socket, but without the removable
plug(s). Plugs are available with screw style or push-in style terminals and must
be ordered separately. Refer to the Selection Tables for the particular PLC I/O
system of interest to determine which modules are offered with field
Removable Terminals Blocks.
All of the features available on analog fixed terminal block products (e.g. labels,
agency certification, etc.) are also provided for the removable terminal block
Bulletin 1492 wiring system modules.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 25

RTB Socket

Screw style RTB Plug Push-in style RTB Plug


(Order Separately) (Order Separately)
2 per cat. no. 2 per cat. no.

Publication 1492-TD008D-EN-P - January 2009


26 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

AIFM Catalog Number Important: The following AIFM catalog number breakdown is for
explanation purposes only. It is not a product configurator. Not all
Explanation for Analog I/O combinations of fields are valid product catalog numbers First, select the
Modules desired AIFM using the steps in Ordering Digital and Analog Wiring Systems
on page 28. Then, use this breakdown for verification and explanation only.

1492– AIFM 16– F– 5

Bulletin No.
No. Field-Side Wiring Terminals
3 3 per I/O channel
Analog Interface Modules 5 5 per input channel
AIFM Fixed (non-removable) terminal block
RAIMF Removable terminal block
Input Fuse Clips and Blown Fuse
Indicators
Blank No fuse clips
No. Analog I/O Channels F 5 x 20 mm fuse clips with
24V DC blown fuse
4 4 channels: input, output, indicators for output
or 2 input/output modules
combination
4C 4 channels:
2 input/2 output
combination
4I 4 input channels
6S 6 isolated input or output
channels
6TC 6 thermocouple input
channels
8 8 input or output channels
16 16 input channels
PI 8 input/2 output channels
CE4 2-channel counter input/4
outputs

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 27

Pre-Wired Cable Catalog Important: The following analog cable catalog number breakdown is for
explanation purposes only. It is not a product configurator. All combinations
Number Explanation for of fields are not valid product catalog numbers. First, select the desired AIFM
Bulletins 1746, 1756, and using the steps in Ordering Digital and Analog Wiring Systems on page 28.
1771 Analog I/O Modules Then, use this breakdown for verification and explanation only.

1492– ACABLE 050 A

Bulletin No.

A-Cable Type
A, B, C, D, Pre-wired cables for Bulletin 1746 analog I/O and
Analog Interface Cables K, L, P, Q, R RTD input modules.
E, F, G, H, J Pre-wired cables for Bulletin 1771 analog I/O and
RTD input modules.
Standard or Build-to-Order Length Cable TA, TB, TC, Pre-wired cables for Bulletin 1756 analog I/O, RTD,
005 0.5 m (1.64 ft) Standard TD, UA, UB, and -IT6I thermocouple input modules.
010 1.0 m (3.28 ft) Length UC, UD, VA,
VB, WA, WB,
025 2.5 m (8.20 ft) X, Y, Z, ZA,
050 5.0 m (16.40 ft) ZB, ZC
001-020 0.1…2.0 m (0.328…6.56 ft) Build-to-Order YT Pre-wired cable for bulletin 1756-IT6I2 thermocouple
0.1 m (0.328 ft increments) Length input Module.
020-100 2.0…10.0 m (6.56…32.8 ft) M Pre-wired cables for Bulletin 1757 pulse input
0.5 m (1.64 ft) increments module.
100-300 10.0…30.0 m (32.8…98.4 ft)
1.0 m (3.28 ft) increments

Pre-Wired Cable Catalog Important: The following analog cable catalog number breakdown is for
explanation purposes only. It is not a product configurator. All combinations
Number Explanation for of fields are not valid product catalog numbers. First, select the desired AIFM
Bulletin 1746, 1769, 1794, using the steps in Ordering Digital and Analog Wiring Systems on page 28.
and PowerFlex Analog I/O Then, use this breakdown for verification and explanation only.

Modules
1492– ACAB 005 A46

Bulletin No.

Cable Type
Analog Interface Cables
A46 Pre-wired cables for Bulletin 1746-NI16I and
-NI16V analog modules.
Standard or Build-to-Order Length Cable AA69, AB69, Pre-wired cables for Bulletin 1769 analog I/O
005 0.5 m (1.64 ft) Standard BA69, BB69, modules and RTD input module.
Length BC69, BD69,
010 1.0 m (3.28 ft) CA69, CB69,
025 2.5 m (8.20 ft) CC69, EA69,
050 5.0 m (16.40 ft) EB69, EC69,
ED69, C69, D69,
001-020 0.1…2.0 m (0.328…6.56 ft) Build-to-Order HA69
0.1 m (0.328 ft increments) Length
Z7H Pre-wired cable for PowerFlex 700H
020-100 2.0…10.0 m (6.56…32.8 ft)
0.5 m (1.64 ft) increments X7S, Z7S Pre-wired cables for PowerFlex 700S
100-300 10.0…30.0 m (30.0…98.4 ft) Z94 Pre-wired cables for Bulletin 1794 analog I/O
1.0 m (3.28 ft) increments modules

Publication 1492-TD008D-EN-P - January 2009


28 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Ordering Digital and To order the proper IFM/XIM/AIFM pre-wired cable:


Analog Wiring Systems 1. Determine the PLC or PowerFlex I/O platform (e.g., Bulletin 1746,
1756, 1769, 1771, 1794, 700H,700S) you are using and the catalog
number of the I/O module being specified (e.g., 1746-IB16).
2. Determine whether you require field-side LEDs, fusing for over-current
protection, or relays (check voltage ratings for LEDs, fuse blown
indication, relay, and coil voltage).
3. Determine your field-side wiring requirements. Are extra terminals
needed?
4. Determine your desired PLC I/O module to IFM/XIM/AIFM cable
length (0.5 m, 1.0 m, 2.5 m, 5.0 m, or build-to-order) based on wiring
needs.
5. Refer to selection tables as follows:

Selection Table Quick Reference

Platform Page No.


Bulletin 1746 Digital (IFM/XIM) 29
Bulletin 1746 Analog (AIFM) 35
Bulletin 1756 Digital (IFM/XIM) 36
Bulletin 1756 Analog (AIFM) 41
Bulletin 1762/1764 43
Bulletin 1769 Digital (IFM/XIM) 45
Bulletin 1769 Analog (AIFM) 52
Bulletin 1794 (IFM/XIM) 53
Bulletin 1794 (AIFM) 58
Bulletin 1771 Digital (IFM/XIM) 59
Bulletin 1771 Analog (AIFM) 63
Bulletin 700 PowerFlex 66

Ordering Digital IFM-Ready Cables for IFMs/XIMs


(Refer to page 14 for definition of IFM-ready)
For pinout and wiring information, refer to IFM-Ready Cable Specifications
on page 138 and the selection table on page 65.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 29

Ordering Digital I/O Module-Ready Cables


(Refer to page 13 for the definition of I/O module-ready cables) To order the
proper digital I/O module-ready cable, the following information is required:
• Type of connector needed for the I/O module(s) (catalog number of the
wiring arm or removable terminal block).
• Code for the desired cable length:
– 010 = 1.0 m
– 025 = 2.5 m
– 050 = 5.0 m
– Build-to-order length

Selection Tables Using Bulletin 1746 Selection Tables to Make Valid Bulletin 1492
Wiring System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
1. Find the appropriate table based on the catalog numbers of the 1746
I/O module.
2. Find the column for the 1746 I/O module.
3. Follow the column down to determine which Wiring Systems Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the Bulletin 1492 Wiring System Module is not
compatible with the I/O module. NOTE: The letter codes designate
the compatible Bulletin 1492 cable for that 1746 I/O and Bulletin 1492
Wiring System Module combination.
4. Select the desired Bulletin 1492 Wiring System Module.
5. Configure the cable catalog number using 1492-CABLE➊ (for digital
cables) or 1492-ACABLE➊ (for analog cables). See footnote ➊ on
pages 34 and 35.

Bulletin 1746 SLC 500 IFMs and Cables


Bulletin 1746 Digital 16-Point and 8-Point Isolated I/O Modules ➋
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring System I/O Module Catalog Number 1746-…
System Module with Module with Removable
scOAP81➌

Fixed Terminal Terminal Block Socket


sc-IA8I➌
sc-IB8I➌
scIC8I➌

Block Assembly (order plugs


OBP16

OVP16
OB16E

OW16
ITB16
ITV16

OA16
OB16

OG16
OV16
IM16

separately)
IN16
IA16
IB16

IG16
IH16
IC16

IV16

OX8

Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F➐ A B B E B A B B B B C E E E E E E D D A B B A
Narrow standard 1492-IFM20FN 1492-RIFM20FN➑ A B B E B — B B B B G E E E E E E N N A B B A
132V AC/DC Max.
Extra terminals (2 per I/O) 1492-IFM20F-2 1492-RIFM20F-2➐ A B B E B A B B B B C E E E E E E D — — — — —
264V AC/DC Max.
3-wire sensor type input 1492-IFM20F-3 — A B B E B — B B B B — — — — — — — — — — — — —
devices 132V AC/DC Max.
LED Indicating
Standard with 1492-IFM20D24 — — B — — — — B B B B — E E E — E E D — — — — —
24V AC/DC LEDs
Narrow standard with 1492-IFM20D24N — — B — — — — B B B B — E E E — — — N — — — — —
24V AC/DC LEDs
Note: Footnotes are on page 31.

Publication 1492-TD008D-EN-P - January 2009


30 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1746 Digital 16-Point and 8-Point Isolated I/O Modules (Continued)➋
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring System I/O Module Catalog Number 1746-…
System Module with Module with Removable

scOAP81➌
Fixed Terminal Terminal Block Socket

sc-IA8I➌
sc-IB8I➌
scIC8I➌
Block Assembly (order plugs

OBP16
OB16E

OVP16
OW16
ITB16
ITV16

OA16
OB16

OG16
OV16
IM16
separately)

IN16
IA16
IB16

IG16
IH16
IC16

IV16

OX8
Standard with 1492-IFM20D120 ➍ — A — — — B — — — — — C — — — — — — D — — — — —
120V AC/DC LEDs
Narrow standard with 1492-IFM20D120N — A — — — — — — — — — G — — — — — — N — — — — —
120V AC LEDs
24V AC/DC LEDs and extra 1492-IFM20D24-2 — — — — — — — — — — — — E E E — E E D — — — — —
terminals for outputs
24V AC/DC LEDs and extra 1492-IFM20D24A-2 — — B — — — — B B B B — — — — — — — — — — — — —
terminals for inputs
120V AC LEDs and extra 1492-IFM20D120-2 — — — — — — — — — — — C — — — — — — D — — — — —
terminals for outputs
120V AC LEDs and extra 1492-IFM20D120A-2 — A — — — — — — — — — — — — — — — — — — — — —
terminals for inputs
3-wire sensor with 24V 1492-IFM20D24-3 — — B — — — — B B B B — — — — — — — — — — — —
AC/DC LEDs
8 Individually isolated with 1492-IFM20DS24-4 — — — — — — — — — — — — — — — — — — — S — — — —
24/48V AC/DC LEDs and
4 terminals/output
8 Individually isolated with 1492-IFM20DS120-4 — — — — — — — — — — — — — — — — — — — S — — — —
120V AC LEDs and
4 terminals/output
240V AC LEDs and extra 1492-IFM20D240-2 — — — — — — — — — — — C — — — — — — D — — — — —
terminals for outputs
240V AC LEDs and extra 1492-IFM20D240A-2 — — — — — — A — — — — — — — — — — — — — — — — —
terminals for inputs
Fusible
120V AC/DC with Extra 1492-IFM20F-F-2 1492-RIFM20F-F-2➐ — — — — — — — — — — C E E E — E E D — — — — —
terminals for outputs
Extra terminals with 24V 1492-IFM20F-F24-2 1492-RIFM20F-F24-2➐ — — — — — — — — — — — E E E — E E D — — — — —
AC/DC blown fuse LED
indicators
Extra terminals with 120V 1492-IFM20F-F120-2 1492-RIFM20F-F120-2➐ — — — — — — — — — — C — — — — — — D — — — — —
AC/DC blown fuse LED
indicators
Extra terminals with 240V 1492-IFM20F-F240-2 — — — — — — — — — — — C — — — — — — D — — — — —
AC/DC blown fuse LED
indicators
Extra terminals with 24V 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2➐ — B — — — — B B — — — — — — — E E — — — — — —
AC/DC blown fuse LED
indicators for inputs
Extra terminals with 120V 1492-IFM20F-F120A-2 1492-RIFM20F-F120A-2➐ A — — — B — — — — — — — — — — — — — — — — — —
AC/DC blown fuse LED
indicators for inputs
8 Individually isolated 120V 1492-IFM20F-FS-2 — — — — — — — — — — — — — — — — — — — S — — — —
AC/DC with extra terminals
for outputs
8 Individually isolated with 1492-IFM20F-FS24-2 — — — — — — — — — — — — — — — — — — — S — — — —
extra terminals output, and
24V AC/DC blown fuse
indicators
Two 4-point isolated groups 1492-IFM20F-FS24A-4 — — — — — — — — — — — — — — — — — — — — — — — —
with four terminals/input and
24V AC/DC blown fuse LED
indicators
8 Individually isolated with 1492-IFM20F-FS120-2 — — — — — — — — — — — — — — — — — — — S — — — A
extra terminals output, and
120V AC/DC blown fuse LED
indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — — — — — — — — — — — — — — S — — — —
four terminals/output and
120V AC/DC blown fuse LED
indicators
Two 4-point isolated groups 1492-IFM20F-FS120A-4 — — — — — — — — — — — — — — — — — — — — — — — —
with four terminals/input and
120V AC/DC blown fuse
indicators
8 Individually isolated with 1492-IFM20F-FS240-4 — — — — — — — — — — — — — — — — — — — S — — — A
four terminals/output and
240V AC/DC blown fuse LED
indicators
Note: Footnotes are on page 31.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 31

Bulletin 1746 Digital 16-Point and 8-Point Isolated I/O Modules (Continued)➋
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring System I/O Module Catalog Number 1746-…
System Module with Module with Removable

scOAP81➌
Fixed Terminal Terminal Block Socket

sc-IA8I➌
sc-IB8I➌
scIC8I➌
Block Assembly (order plugs

OBP16
OB16E

OVP16
OW16
ITB16
ITV16

OA16
OB16

OG16
OV16
IM16
separately)

IN16
IA16
IB16

IG16
IH16
IC16

IV16

OX8
Relay Master (LED Indicating)➎➏
20-pin master with eight (8) 1492-XIM2024-8R➒ — — — — — — — — — — — — E E E — — — — — — — — —
24V DC relays
20-pin master with eight (8) 1492-XIM20120-8R➓ — — — — — — — — — — — CR — — — — — — — — — — — —
120V AC relays
20-pin master with sixteen 1492-XIM2024-16R — — — — — — — — — — — — E E E — — — — — — — — —
(16) 24V DC relays
20-pin master with sixteen 1492-XIM2024-16RF — — — — — — — — — — — — E E E — — — — — — — — —
(16) 24V DC relays with
fusing
20-pin master with sixteen 1492-XIM20120-16R — — — — — — — — — — — CR — — — — — — — — — — — —
(16) 120V AC relays
20-pin master with sixteen 1492-XIM20120-16RF — — — — — — — — — — — CR — — — — — — — — — — — —
(16) 120V AC relays with
fusing
Relay Expander (LED Indicating) ➎➏
Expander with eight (8) 24V 1492-XIM24-8R 1492-RXIM24-8R✱ — — — — — — — — — — — ➊ ➊ ➊ — — — — — — — — —
DC relays
Expander with eight (8)120V 1492-XIM120-8R — — — — — — — — — — — ➊ — — — — — — — — — — — —
AC relays
Fusible Expander
8-ch. expander with 24V DC 1492-XIMF-F24-2 — — — — — — — — — — — — ➊ ➊ ➊ — — — — — — — — —
blown fuse indicators
8-ch. expander with 120V AC 1492-XIMF-F120-2 — — — — — — — — — — — ➊ — — — — — — — — — — — —
blown fuse indicators
Feed-through Expander
Expander with eight feed- 1492-XIMF-2 — — — — — — — — — — — ➊ ➊ ➊ ➊ — — — — — — — — A
through channels

➊ Can have up to 1 expandable module depending upon master used (total 16 pts or less), extender cable is provided.
➋ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050A is for a 5.0 m cable, and the letter A.
➌ For information concerning this I/O module, contact Spectrum Controls (Phone: 425-641-9473) or at www.spectrumcontrols.com.
➍ This IFM is not recommended for use with PLC I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 for
inputs. Use 1492-IFM20D120-2 for outputs.
➎ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➏ The LED indicates the PLC output status.
➐ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB10N (screw style terminals) or 1492-RTB10P (push-in style terminals). ORDER PLUGS SEPARATELY.
➒ Expandable to 16 using XIM24-8R or XIMF-24-2.
➓ Expandable to 16 using XIM120-8R or XIMF-24-2.
✱ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.

Bulletin 1746 SLC 500 IFMs and Cables, Continued

Bulletin 1746 Digital 32-Point I/O Modules ➋


Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog
System Module with System Module with Number 1746-…
Fixed Terminal Block Removable Terminal
OB32E

Block Socket Assembly


OB32

OV32
IB32

IV32

(order plugs separately


Feed-through
Standard 132V AC/DC Max. 1492-IFM40F 1492-RIFM40F➏ H H H H H
Extra terminals132V AC/DC Max. 1492-IFM40F-2 1492-RIFM40F-2➏ H H H H H
3-wire sensor type input devices 60V AC/DC Max. 1492-IFM40F-3 — H H — — —
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM40D24 1490-RIFM40D24➏ H H H H H
24V AC/DC LEDs and extra terminals for outputs 1492-IFM40D24-2 — — — H H H
24V AC/DC LEDs and extra terminals for inputs 1492-IFM40D24A-2 1492-RIFM40D24A-2➏ H H — — —

Note: Footnotes are on the following page.


Publication 1492-TD008D-EN-P - January 2009
32 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1746 Digital 32-Point I/O Modules (Continued)➋


Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog
System Module with System Module with Number 1746-…
Fixed Terminal Block Removable Terminal

OB32E
Block Socket Assembly

OB32

OV32
IB32

IV32
(order plugs separately
120V AC LEDs and extra terminals for outputs 1492-IFM40D120-2 — — — — — —
120V AC LEDs and extra terminals for inputs 1492-IFM40D120A-2 — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM40D24-3 — H H — — —
16 Individually isolated with 24/48V AC/DC LEDs and 1492-IFM40DS24-4 — — — — — —
four terminals/output
16 Individually isolated with 24V AC/DC LEDs and 1492-IFM40DS24A-4 — — — — — —
four terminals/input
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120-4 — — — — — —
four terminals/output
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120A-4 — — — — — —
four terminals/input
16 Individually isolated with 240V AC LEDs and 1492-IFM40DS240A-4 — — — — — —
four terminals/input
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM40F-F-2 — — — H H H
Extra terminals with 24V AC/DC blown fuse LED 1492-IFM40F-F24-2 1492-RIFM40F-F24-2➏ — — H H H
indicators for outputs
Extra terminals with 120V AC/DC blown fuse LED 1492-IFM40F-F120-2 — — — — — —
indicators for outputs
16 Individually isolated with extra terminals for 120V 1492-IFM40F-FS-2 — — — — — —
AC/DC outputs
16 Individually isolated with extra terminals and 24V 1492-IFM40F-FS24-2 — — — — — —
AC/DC blown fuse indicators
16 Individually isolated with 24V AC/DC blown fuse 1492-IFM40F-FS24-4 — — — — — —
indicators and four terminals/output
16 Individually isolated 240V AC/DC with 4 1492-IFM40F-FS-4 — — — — — —
terminals/output
16 Individually isolated with extra terminals and 120V 1492-IFM40F-FS120-2 1492-RIFM40F-FS120-2➏ — — — — —
AC/DC blown fuse LED indicators
16 Individually isolated with 120V AC/DC blown fuse 1492-IFM40F-FS120-4 1492-RIFM40F-FS120-4❼ — — — — —
LED indicators and four terminals/output
16 Individually isolated with 240V AC/DC blown fuse 1492-IFM40F-FS240-4 — — — — — —
LED indicators and four terminals/output
16 Individually isolated with 24V AC/DC blown fuse LED 1492-IFM40F-FS24A-4 — — — — — —
indicators and four terminals/input
16 Individually isolated 120V AC/DC with 4 1492-IFM40F-FSA-4 — — — — — —
terminals/input
16 Individually isolated with 120V AC/DC blown fuse 1492-IFM40F-FS120A-4 1492-RIFM40F-FS120A-4❼ — — — — —
LED indicators and four terminals/input
16 Individually isolated with 240V AC/DC blown fuse 1492-IFM40F-FS240A-4 — — — — — —
LED indicators and 4 terminals/input
Relay Master ➍➎ —
40-pin master with eight (8) 24V DC relays 1492-XIM4024-8R — — — H H —
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16R 1492-RXIM4024-16R➑ — — H H —
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16RF — — — H H —
with fusing
Relay Expander (LED Indicating) ➍➎ —
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R➒ — — ➊ ➊ —
Expander with sixteen (16) 24V DC relays with fusing 1492-XIM24-16RF — — — ➌ ➌ —
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — —
Fusible Expander (LED Indicating) —
8-channel expander with 24V DC blown fuse indicators 1492-XIMF-F24-2 — — — ➊ ➊ —
8-channel expander with 120V AC blown fuse indicators 1492-XIMF-F120-2 — — — — — —
Feed through Expander —
Expander with eight feed-through channels 1492-XIMF-2 — — — ➊ ➊ —

Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 33

➊ Can have up to two or three expandable modules depending upon master used (total 32 pts or less), extender cable is provided.
➋ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050Yis for a 5.0 m cable, and the letter Y.
➌ 1492-XIM24-16RF is to be used with 1492-XIM4024-16R and 1492-XIM4024-16RF 32 PT. Only.
➍ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➎ The LED indicates the PLC output status.
➏ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
❼ Compatible Removable Terminal Block (RTB) plug; 1492-RTB17N (screw style terminals) or 1492-RTB17P (push-in style terminals). ORDER PLUGS SEPARATELY.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB14N (screw style terminals) or 1492-RTB14P (push-in style terminals). ORDER PLUGS SEPARATELY.
➒ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.

Publication 1492-TD008D-EN-P - January 2009


34 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Bulletin 1746 SLC 500 IFMs and Cables, Continued
Continued
These pre-wired cables have a pre-wired removable terminal block (RTB) on
one end to connect to the front of a Bulletin 1746 digital I/O module and a
connector on the other end to plug into a 20- or 40-terminal IFM/XIM. You
must first select the IFM/XIM from one of the preceding selection tables.

Pre-Wired Cables for Bulletin 1746 Digital I/O Modules


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1746
Lengths Available Conductors I/O Module Catalog Number
1492-CABLE➊A 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-IA16, -IM16
1492-CABLE➊B 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-IB16, -IH16, -IN16, -ITB16, -ITV16
1492-CABLE➊C 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OA16
1492-CABLE➊CR 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OA16
1492-CABLE➊D 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OW16, -OX8
1492-CABLE➊E 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-IG16, -OB16, -OB16E, -OBP16, -OG16, -OV16, -OVP16
1492-CABLE➊G 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OA16
1492-CABLE➊H 0.5, 1.0, 2.5, 5.0 m Yes 40 1746-IB32, -IV32, -OB32, -OB32E, -OV32
1492-CABLE➊N 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OW16, -OX8
1492-CABLE➊S 0.5, 1.0, 2.5, 5.0 m Yes 20 1746-OX8

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CABLE005N is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM20D24N IFM to a Catalog Number 1746-OW16 I/O module. Build-to-order lengths are also available.

The I/O module-ready cables have a pre-wired RTB on one end to plug
onto the front of a Bulletin 1746 I/O module and 20 or 40 individually
colored #18 AWG conductors on the other end. These cables provide the
convenience of pre-wired connections at the I/O module end, while still
allowing the flexibility to field-wire to standard terminal blocks of your choice.

I/O Module-Ready Cables for Bulletin 1746 Digital I/O Modules ➌


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1746
Lengths Available Conductors I/O Module Catalog Number
1492-CABLE➋N3 1.0, 2.5, 5.0 m Yes 40 1746-IB32, -IV32, -OB32, -OV32, -OB32E
1492-CABLE➋RTBB 1.0, 2.5, 5.0 m Yes 20 1746-IB16, -IC16, -IG16, -IH16, -IN16, -ITB16, -ITV16,
-IV16, -OB16, -OB16E, -OBP8, -OBP16, -OG16, -OV16,
-OVP16
1492-CABLE➋RTBO 1.0, 2.5, 5.0 m Yes 20 1746-OW16, -OX8
1492-CABLE➋RTBR 1.0, 2.5, 5.0 m Yes 20 1746-IA16, -OA16, -OAP12, -IM16

➋ Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m,
and 050 = 5.0 m). Example: Catalog Number 1492-CABLE050RTBR is for a 5.0 m cable with a pre-wired Catalog Number 1746-RT25R RTB on one end.
➌ Digital I/O module-ready cables should not be used with analog module as a cable shield and drain wire is not provided.

Note: The following I/O Modules do not have RTBs: 1746-IA4, 1746-IA8,
1746-IB8, 1746-IM4, 1746-IM8, 1746-IV8, 1746-OA8, 1746-OB8.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 35

Selection Tables, Bulletin 1746 SLC 500 AIFMs and Cables


Continued
Bulletin 1746 Analog I/O Modules ➊
Description of AIFM Cat. No. for Wiring Cat. No. for Wiring System I/O Module Catalog Number 1746-…
System Module Module with Removable

HSCE2 (Diff.)
with Fixed Terminal Block Socket Assembly

HSCE (Diff.)
Terminal Block (order plugs separately

NIO4V

NI16V
FIO4V

NO4V
NO8V
NIO4I

NI16I
FIO4I

NO4I
NO8I

NR4
NI4
NI8

QS
Feed-through
4-channel input, output or 2-in/2-out 1492-AIFM4-3 1492-RAIFM4-3➌ — — L L A — L L B — B — — — — —
combination with 3 terminals/channel
6-channel isolated with 1492-AIFM6S-3 1492-RAIFM6S-3➍ — — — — — — — — — — — — D — — —
3…4 terminals/channel
8- or 16-channel input or output with 1492-AIFM8-3 1492-RAIFM8-3➎ — — — — — C — — — R — R — — A46 A46
3 terminals/channel
Thermocouple
6-channel with 3 terminals/channel➋ 1492-AIFM6TC-3 — — — — — — — — — — — — — — — — —
High-Speed Counter/Encoder
2-channel center input/2 outputs 1492-AIFMCE4 — K P — — — — — — — — — — — — — —
Fusible High Speed Counter/Encoder
2-channel fused counter input/4 fused outputs 1492-AIFMCE4-F — K P — — — — — — — — — — — — — —
Fusible Analog
2-channel input, 2-channel output with 24V DC 1492-AIFM4C-F-5 — — — L L — — L L — — — — — — — —
blown fuse indicators, test points,
5 terminals/input, 3 terminals/output
4-channel input with 24V DC blown fuse 1492-AIFM4I-F-5 — — — — — A — — — — — — — — — — —
indicators, test points, 5 terminals/input
8-channel input with 24V DC blown fuse 1492-AIFM8-F-5 — — — — — — C — — — — — — — — — —
indicators, 5 terminals/channel
16-channel input with 24V DC blown fuse 1492-AIFM16-F-3 — — — — — — — — — — — — — — — A46 A46
indicators, 3 terminals/channel
16-channel input with 24V DC blown fuse 1492-AIFM16-F-5 — — — — — — — — — — — — — — — — —
indicators, 5 terminals/channel
4-input/4-output channel with 8 fuses and 24V 1492-AIFMQS — — — — — — — — — — — — — — Q — —
DC blown fuse indicators
➊ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-ACABLE025A is for a 2.5 m cable, and the letter A.
➋ Cannot be used with SLC I/O.
➌ Compatible Removable Terminal Block (RTB) plug; 1492-RTB8N (screw style terminals) or 1492-RTB8P (push-in style terminals). ORDER PLUGS SEPARATELY.
➍ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.
➎ Compatible Removable Terminal Block (RTB) plug; 1492-RTB16N (screw style terminals) or 1492-RTB16P (push-in style terminals). ORDER PLUGS SEPARATELY.
These pre-wired cables have a pre-wired RTB on one end to connect to the
front of a Bulletin 1746 analog I/O module and a connector on the other end
to plug into a 15- or 25-pin D-shell terminal AIFM. To use this table, you must
first have selected an AIFM from the preceding table.
Pre-Wired Cables for Bulletin 1746 Analog I/O Modules
Cable Catalog Number Standard Cable Lengths (m) Build-to-Order Available AIFM Connector Mating 1746 I/O Module Catalog Number
1492-ACABLE➊A 0.5, 1.0, 2.5, 5.0 Yes 15-pin D-shell 1746-NI4
1492-ACABLE➊B 0.5, 1.0, 2.5, 5.0 Yes 15-pin D-shell 1746-NO4I, -NO4V
1492-ACABLE➊C 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-NI8
1492-ACABLE➊D 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-NR4
1492-ACABLE➊K 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-HSCE
1492-ACABLE➊L 0.5, 1.0, 2.5, 5.0 Yes 15-pin D-shell 1746-NIO4I, -NIO4V, -FIO4I, -FIO4V
1492-ACABLE➊P 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-HSCE2
1492-ACABLE➊Q 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-QS
1492-ACABLE➊R 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-N08I, N08V
1492-ACAB➊A46 0.5, 1.0, 2.5, 5.0 Yes 25-pin D-shell 1746-NI16I, -NI16V
➊ To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-ACABLE005A is for a 0.5 m cable that
could be used to connect a Catalog Number 1492-AIFM4I-F-5 IFM to a Catalog Number 1746-NI4 I/O module.

Publication 1492-TD008D-EN-P - January 2009


36 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Using Bulletin 1756 Selection Tables to Make Valid 1492 Wiring
Continued System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers.:
1. Find the appropriate table based on the catalog number of the 1756 I/O
module.
2. Find the column in the selected table for the 1756 I/O module.
3. Follow the column down to determine which Wiring System Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the 1492 Wiring System Module is not compatible with
the I/O module. NOTE: The letter codes designate the compatible
1492 cable for that 1756 I/O and 1492 Wiring System Module
combination.
4. Select the desired 1492 Wiring System Module.
5. Configure the cable catalog number using 1492-CABLE➊ (for digital
cables) or 1492-ACABLE➊ (for analog cables). See footnote ➊ on
pages 40 and 42.

Bulletin 1756 ControlLogix IFMs and Cables


Bulletin 1756 Digital 8-Point and 16-Point I/O Modules ➋
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring System Module I/O Module Catalog Number 1756-…
System Module with with Removable Terminal Block

OB16E

OV16E
Fixed Terminal Block Socket Assembly (order plugs

OA8D
OA8E

OA16
IA8D

IN16
IA16
IB16
IC16

IV16

ON8
OA8

OB8

OC8
separately

Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F➏ U X X X X X U U U X U X U U X
Narrow standard 132V AC/DC Max. 1492-IFM20FN 1492-RIFM20FN➐ U X X X X X U U U X U X U U X
Extra terminals (2 per I/O) 264V AC/DC Max. 1492-IFM20F-2 1492-RIFM20F-2➏ U X X X X X U U U X U X U U X
3-wire sensor type input devices 1492-IFM20F-3 — — X X X X X — — — — — — — — —
132V AC/DC Max.
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM20D24 — — — X — X X — — — — — X — — X
Narrow standard with 24V AC/DC LEDs 1492-IFM20D24N — — — X — X X — — — — — X — — —
Standard with 120V AC/DC LEDs 1492-IFM20D120 ➌ — U X — — — — — — — — — — — — —
Narrow standard with 120V AC LEDs 1492-IFM20D120N — U X — — — — — — — X — — — — —
24V AC/DC LEDs and extra terminals 1492-IFM20D24-2 — — — — — — — — — — — — X — — X
for outputs
24V AC/DC LEDs and extra terminals 1492-IFM20D24A-2 — — — X — X X — — — — — — — — —
for inputs
120V AC LEDs and extra terminals 1492-IFM20D120-2 — — — — — — — — — — X — — — — —
for outputs
120V AC LEDs and extra terminals for inputs 1492-IFM20D120A-2 — U X — — — — — — — — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM20D24-3 — — — X — X X — — — — — — — — —
8 Individually isolated with 24/48V AC/DC 1492-IFM20DS24-4 — — — — — — — — — — — W — W W —
LEDs and 4 terminals/output
8 Individually isolated with 120V AC LEDs 1492-IFM20DS120-4 — — — — — — — W V V — — — — — —
and 4 terminals/output
240V AC LEDs with extra terminals 1492-IFM20D240-2 — — — — — — — — — — — — — — — —
for outputs
240V AC LEDs with extra terminals for inputs 1492-IFM20D240A-2 — — — — — — — — — — — — — — — —
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM20F-F-2 1492-RIFM20F-F-2➏ — — — — — — — — — X — X — — X
Extra terminals with 24V AC/DC blown fuse 1492-IFM20F-F24-2 1492-RIFM20F-F24-2➏ — — — — — — — — — — — X — — X
LED indicators
Extra terminals with 120V AC/DC blown fuse 1492-IFM20F-F120-2 1492-RIFM20F-F120-2➏ — — — — — — — — — X — — — — —
LED indicators

Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 37

Bulletin 1756 Digital 8-Point and 16-Point I/O Modules (Continued)➋


Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring System Module I/O Module Catalog Number 1756-…
System Module with with Removable Terminal Block

OB16E

OV16E
Fixed Terminal Block Socket Assembly (order plugs

OA8D
OA8E

OA16
IA8D

IN16
IA16
IB16
IC16

IV16

ON8
OA8

OB8

OC8
separately

Extra terminals with 240V AC/DC blown fuse 1492-IFM20F-F240-2 — — — — — — — — — — X — — — — —


LED indicators
Extra terminals with 24V AC/DC blown fuse 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2➏ — — X — X — — — — — — — — — —
LED indicators
Extra terminals with 120V AC/DC blown fuse 1492-IFM20F-F120A-2 1492-RIFM20F-F120A-2➏ — X — — — — — — — — — — — — —
LED indicators
8 Individually isolated 120V AC/DC with 1492-IFM20F-FS-2 — — — — — — — W V V — W — W W —
extra terminals for outputs
8 Individually isolated with extra 1492-IFM20F-FS24-2 — — — — — — — — — — — W — W W —
terminals/output and 24V AC/DC blown fuse
LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS24A-4 — — — — — — — — — — — — — — — —
four terminals/input and 24V AC/DC blown
fuse LED indicators
8 Individually isolated with extra terminals 1492-IFM20F-FS120-2 — — — — — — — W V V — — — — — —
output, and 120V AC/DC blown fuse LED
indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — — W V V — — — — — —
4 terminals/output and 120V AC/DC blown
fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS120A-4 — U — — — — — — — — — — — — — —
four terminals/input and 120V AC/DC blown
fuse indicators
8 Individually isolated with 1492-IFM20F-FS240-4 — — — — — — — W — — — — — — — —
4 terminals/output and 240V AC/DC blown
fuse LED indicators
Relay Master (LED Indicating) ➍➎
20-pin master with eight (8) 24V DC relays 1492-XIM2024-8R➑ — — — — — — — — — — — — X — — —
20-pin master with eight (8) 120V AC relays 1492-XIM20120-8R➒ — — — — — — — — — — X — — — — —
20-pin master with sixteen (16) 24V CD 1492-XIM2024-16R — — — — — — — — — — — — X — — —
relays
20-pin master with sixteen (16) 24V DC 1492-XIM2024-16RF — — — — — — — — — — — — X — — —
relays with fusing
20-pin master with sixteen (16) 120V AC 1492-XIM20120-16R — — — — — — — — — — X — — — — —
relays
20-pin master with sixteen (16) 120V AC 1492-XIM20120-16RF — — — — — — — — — — X — — — — —
relays with fusing
Relay Expander (LED Indicating) ➍➎
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R✱ — — — — — — — — — — — ➊ — — —
Expander with eight (8) 120V AC Relays 1492-XIM120-8R — — — — — — — — — — ➊ — — — — —
Fusible Expander
Expander with eight (8) 24V channels with 1492-XIMF-F24-2 — — — — — — — — — — — — ➊ — — —
blown fuse indicators
Expander with eight (8) 120V channels with 1492-XIMF-F120-2 — — — — — — — — — — ➊ — — — — —
blown fuse indicators
Feed-through Expander
Expander with eight (8) feed-through 1492-XIMF-2 — — — — — — — — — — ➊ — ➊ — — —
channels
➊ Can have up to 1 expandable module depending upon master used (total 16 pts or less) extender cable is provided.
➋ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050W is for a 5.0 m cable, and the letter W.
➌ This IFM is not recommended for use with PLC I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 for
inputs. Use 1492-IFM20D120-2 for outputs.
➍ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➎ The LED indicates the PLC output status.
➏ Compatible Removable Terminal Block (RTB) plug 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
➐ Compatible Removable Terminal Block (RTB) plug; 1492-RTB10N (screw style terminals) or 1492-RTB10P (push-in style terminals). ORDER PLUGS SEPARATELY.
➑ Expandable to 16 using XIM24-8R or XIMF-24-2.
➒ Expandable to 16 using XIM120-8R or XIMF-24-2.
✱ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.

Publication 1492-TD008D-EN-P - January 2009


38 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Bulletin 1756 ControlLogix IFMs and Cables, Continued


Continued
Bulletin 1756 Digital 16-Point Isolated and 32-Point I/O Modules ➋
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1756-…
System Module with System Module with

OB16IS
Fixed Terminal Block Removable Terminal

OB16D

OW16I
OV32E
OB8EI
IB16D

OA16I

OB16I
IM16I

OB32
IA16I

IB16I

IH16I

OH8I

OX8I
IA32
IB32
Block Socket Assembly

IV32
(order plugs separately
Feed-through
Standard 132V AC/DC Max. 1492-IFM40F 1492-RIFM40F➑ Y Y Y Z Z Z Y — Y Y Y Y Y Z Z Y Y Y
Extra terminals (2 per I/O) 132V 1492-IFM40F-2 1492-RIFM40F-2➑ — Y — Z Z Z — — — — Y — — Z Z — — —
AC/DC Max.
3-wire sensor type input devices 1492-IFM40F-3 — — — — — Z Z — — — — — — — — — — — —
60V AC/DC Max.
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM40D24 1492-RIFM40D24➑ — — — — Z Z — — — — — — — Z Z — — —
24V AC/DC LEDs and extra 1492-IFM40D24-2 — — — — — — — — — — — — — — Z Z — — —
terminals for outputs
24V AC/DC LEDs and extra 1492-IFM40D24A-2 1492-RIFM40D24A-2➑ — — — — Z Z — — — — — — — — — — — —
terminals for inputs
120V AC LEDs and extra terminals 1492-IFM40D120-2 — — — — — — — — — — — — — — — — — — —
for outputs
120V AC LEDs and extra terminals 1492-IFM40D120A-2 — — — — Z — — — — — — — — — — — — — —
for inputs
3-wire sensor with 24V AC/DC LEDs 1492-IFM40D24-3 — — — — — Z Z — — — — — — — — — — — —
16 Individually isolated with 24/48V 1492-IFM40DS24-4 — — — — — — — — — — Y Y Y Y — — — Y Y
AC/DC LEDs and 4 terminals/output ♣
16 Individually isolated with 24V 1492-IFM40DS24A-4 — — Y Y — — — — — — — — — — — — — — —
AC/DC LEDs and 4 terminals/input
16 Individually isolated with 120V 1492-IFM40DS120-4 — — — — — — — — — Y — — — — — — — Y Y
AC LEDs and 4 terminals/output
16 Individually isolated with 120V 1492-IFM40DS120A-4 — Y — — — — — — — — — — — — — — — — —
AC LEDs and 4 terminals/input
16 Individually isolated with 240V 1492-IFM40DS240A-4 — — — — — — — — Y — — — — — — — — — —
AC LEDs and 4 terminals/input
Fusible
120V AC/DC with extra terminals 1492-IFM40F-F-2 — — — — — — — — — — — — — — Z Z — — —
for outputs
Extra terminals with 24V AC/DC 1492-IFM40F-F24-2 1492-RIFM40F-F24-2➑ — — — — — — — — — — — — — Z Z — — —
blown fuse indicators for outputs
16 Individually fused with 24V DC 1492-IFM40F-F24D-2 — — — — — — — — — — — Y — — — — — — —
blown fuse low leakage (0.05 mA)
LED circuit, 4 isolated groups, 2
terminals/output
Individually Fused w/24V DC blown 1492-IFM40F-F24AD-4 — — Y — — — — — — — — — — — — — — — —
fuse low leakage (0.05 mA) LED
circuit, 4 isolated groups, 4
terminals/input
Extra terminals with 120V AC/DC 1492-IFM40F-F120-2 — — — — — — — — — — — — — — — — — — —
blown fuse indicators for outputs
16 Individually isolated with extra 1492-IFM40F-FS-2 — — — — — — — — — Y Y YY Y — — Y Y Y
terminals for 120V AC/DC outputs ➤ ➤
16 Individually isolated with extra 1492-IFM40F-FS24-2 — — — — — — — — — — Y ➐ Y Y — — — Y Y
terminals and 24V AC/DC blown ➤ ➤
fuse indicators for outputs
16 Individually isolated with 24V 1492-IFM40F-FS24-4 — — — — — — — — — — Y ➐ Y Y — — — Y Y
AC/DC blown fuse indicators and ➤ ➤
4 terminals/output
16 Individually isolated 240V AC/DC 1492-IFM40F-FS-4 — — — — — — — — — Y Y Y — — — Y Y Y Y
with 4 terminals/output ➤ ➤
16 Individually isolated with extra 1492-IFM40F-FS120-2 1492-RIFM40F-FS120-2➑ — — — — — — — — Y — — — — — — Y Y Y
terminals and 120V AC/DC blown
fuse LED indicators
16 Individually isolated with 120V 1492-IFM40F-FS120-4 1492-RIFM40F-FS120-4➒ — — — — — — — — Y — — — — — — — Y Y
AC/DC blown fuse indicators and
4 terminals/output

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 39

Bulletin 1756 Digital 16-Point Isolated and 32-Point I/O Modules (Continued)➋
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1756-…
System Module with System Module with

OB16IS
Fixed Terminal Block Removable Terminal

OB16D

OW16I
OV32E
OB8EI
OA16I

OB16I
IB16D

IM16I

OB32
IA16I

IB16I

IH16I

OH8I

OX8I
IA32
IB32
Block Socket Assembly

IV32
(order plugs separately
16 Individually isolated with 240V 1492-IFM40F-FS240-4 — — — — — — — — — Y — — — — — — — Y Y
AC/DC blown fuse indicators and
4 terminals/output
16 Individually isolated with 24V 1492-IFM40F-FS24A-4 — — ➏ Y — — — — — — — — — — — — — — —
AC/DC blown fuse indicators and
4 terminals/input
16 Individually isolated 120V AC/DC 1492-IFM40F-FSA-4 — Y Y Y — — — Y — — — — — — — — — — —
with 4 terminals/input
16 Individually Isolated with 120V 1492-IFM40F-FS120A-4 1492-RIFM40F-FS120A-4➒ Y — — — — — Y — — — — — — — — — — —
AC/DC blown fuse indicators and
4 terminals/input
16 Individually isolated with 240V 1492-IFM40F-FS240A-4 — — — — — — — — Y — — — — — — — — — —
AC/DC blown fuse indicators and 4
terminals/input
Relay Master (LED Indicating) ➍➎
40-pin master with eight (8) 24V DC 1492-XIM4024-8R — — — — — — — — — — — — — — Z — — — —
relays
40-pin master with sixteen (16) 24V 1492-XIM4024-16R 1492-RXIM4024-16R➓ — — — — — — — — — — — — — Z — — — —
DC relays
40-pin master with sixteen (16) 24V 1492-XIM4024-16RF — — — — — — — — — — — — — — Z — — — —
DC relays with fusing
Relay Expander (LED Indicating) ➍➎
Expander with eight (8) 24V DC 1492-XIM24-8R 1492-RXIM24-8R✪ — — — — — — — — — — — — — ➊ — — — —
relays
Expander with eight (8) 120V AC 1492-XIM120-8R — — — — — — — — — — — — — — — — — — —
relays
Fusible Expander
8-channel expander with 24V DC 1492-XIMF-F24-2 — — — — — — — — — — — — — — ➊ — — — —
blown fuse indicators
8-channel expander with 120V AC 1492-XIMF-F120-2 — — — — — — — — — — — — — — — — — — —
blown fuse indicators
Expander with sixteen (16) 24V DC 1492-XIM24-16RF — — — — — — — — — — — — — — ➌ — — — —
relays with fusing
Feed-through Expander
Expander with eight (8) feed- 1492-XIMF-2 — — — — — — — — — — — — — — ➊ — — — —
through channels

➊ Can have up to two or three expandable modules depending upon master used (total 32 pts or less), extender cable is provided.
➋ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050Y is for a 5.0 m cable, and the letter Y.
➌ One 1492-XIM24-16RF is to be used with one 1492-XIM4024-16R or 1492-XIM4024-16RF master (32 PT. Only).
➍ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➎ The LED indicates the PLC output status.
➏ The 1492-IFM40F-FS24A-4 module and 1492-CABLE➋Y cable can be used with the 1756-IB16D module. However, due to the 1492-IFM40F-FS24A-4 module’s blown fuse
leakage current rating, the “wire off” diagnostic function of the 1756-IB16D will not indicate a blown or removed fuse as a wire off condition. If you require this diagnostic
to function for a blown or removed fuse, you must use a 1492-IFM40F-F24AD-4.
➐ The 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 module and 1492-CABLE➋Y cable can be used with the 1756-OB16D module. However, due to the 1492-IFM40F-FS24-
2 and 1492-IFM40F-FS24-4 module’s blown fuse leakage current rating, the “no load” diagnostic function of the 1756-OB16D will not indicate a blown or removed fuse as
a no load condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24D-2.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
➒ Compatible Removable Terminal Block (RTB) plug; 1492-RTB17N (screw style terminals) or 1492-RTB17P (push-in style terminals). ORDER PLUGS SEPARATELY.
➓ Compatible Removable Terminal Block (RTB) plug; 1492-RTB14N (screw style terminals) or 1492-RTB14P (push-in style terminals). ORDER PLUGS SEPARATELY.
✪ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.
➤ Do not use this module in output sinking mode with fused IFM modules as the IFM module fuses will not properly protect the circuit.
♣ IFMs LED provides PLC output ON/OFF indication. Due to the magnitude of current through the LED, the 1756-0B16D PLC module “No Load” diagnostic function will not
work. If this function is required, use the 1492-IFM40F-2.

Publication 1492-TD008D-EN-P - January 2009


40 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Bulletin 1756 ControlLogix IFMs and Cables, Continued


Continued
These pre-wired cables have a pre-wired RTB on one end to connect to the
front of a Bulletin 1756 digital I/O module and a connector on the other end
to plug into a 20- or 40-terminal IFM/XIM. You must first select the
IFM/XIM from one of the preceding selection tables.

Pre-Wired Cables for Bulletin 1756 Digital I/O Modules

Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1756


Lengths Available Conductors I/O Module Catalog Number
1492-CABLE➊U 0.5, 1.0, 2.5, 5.0 m Yes 20 1756-IA8D, -OA8, -OA8D, -OA8E, -OB8, -OC8, -ON8
1492-CABLE➊V 0.5, 1.0, 2.5, 5.0 m Yes 20 1756-OA8D, -OA8E
1492-CABLE➊W 0.5, 1.0, 2.5, 5.0 m Yes 20 1756-OA8, -OB8, -OC8, -ON8
1492-CABLE➊X 0.5, 1.0, 2.5, 5.0 m Yes 20 1756-IA16, -IB16, -IC16, -IN16, -IV16, -OA16, -OB16E,
-OV16E
1492-CABLE➊Y 0.5, 1.0, 2.5, 5.0 m Yes 40 1756-IA16I, -IB16D, -IB16I, -IH16, -IM16I, -OA16I, -OB8EI,
-OB16D, -OB16I, -OB16IS, -OH8I, -OW16I, -OX8I
1492-CABLE➊Z 0.5, 1.0, 2.5, 5.0 m Yes 40 1756-IB32, -OB32, -IV32, -OV32E

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CABLE005Y is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM40F IFM to a Catalog Number 1756-IA16I I/O module.

The I/O module-ready cables have a pre-wired RTB on one end to plug
onto the front of a Bulletin 1756 I/O module and 20 or 40 individually
colored #18 AWG conductors on the other end. These cables provide the
convenience of pre-wired connections at the I/O module end, while still
allowing the flexibility to field-wire to standard terminal blocks of your choice.

I/O Module-Ready Cables for Bulletin 1756 Digital I/O Modules ➌


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1756
Lengths Available Conductors I/O Module Catalog Number
1492-CABLE➋TBNH 1.0, 2.5, 5.0 m Yes 20 1756-IA8D, -IA16, -IB16, -IC16, -IN16, -IV16, -OA8, -OA8D,
-OA8E, -OA16, -OB8, -OB16E, -OC8, -ON8, -OV16E
1492-CABLE➋TBCH 1.0, 2.5, 5.0 m Yes 40 1756-IA16I, -IA32, -IB16D, -IB16I, -IB32, -IV32, -IH16I,
-IM16I, -OA16I, -OB8EI, -OB16D, -OB16I, -OB16IS, -OB32,
-OV32E, -OH8I, -OW16I, -OX8I

➋ Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m,
and 050 = 5.0 m). Example: Catalog Number 1492-CABLE050TBNH is for a 5.0 m cable with a pre-wired Catalog Number 1756-TBNH RTB on one end.
➌ Discrete I/O ready cables should not be used with PLC analog I/O modules as cable shield and drain wires are not provided.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 41

Selection Tables, Bulletin 1756 ControlLogix AIFMs and Cables


Continued
Bulletin 1756 Analog I/O Module ➊ ➋
Description of AIFM Catalog Number Catalog Number I/O Module
for Wiring for Wiring Catalog Number

Cat. No. 1757


System Module System Module 1756
with Fixed with Removable
Terminal Block Terminal Block
Socket Assembly
(order plugs
separately

IF4FXOF2F (Cur In & Volt Out


IF4FXOF2F (Volt In & Out
IF4FXOF2F (Cur In & Out

IF16 (Sgl-End Current)


IF8 (Sgl-End Current)

OF8H (Current/Hart)
IF8H (Current/Hart)

IF16 (Sgl-End Volt)

IF16 (Diff Voltage)

IF16 (Diff Current)


IF8 (Sgl-End Volt)

IF8 (Diff Voltage)


IF8 (Diff Current)

OH8H (Voltage)
HSC (24V Diff.)

IF8H (Voltage)
HCS (5V Diff.)

OF4 (Voltage)

OF8 (Voltage)
IF6I (Voltage)

OF4 (Current)

OF8 (Current)
IF6I (Current)

IF6CIS

OF6CI
OF6VI
IT6I2

PIM
IR6I
IT6I
Feed-through
4-channel input, output or 2- 1492-AIFM4-3 1492-RAIFM4-3➌ — — — — — — — — — — — — — — — — — — — — — VA VB — — — — — — —
in/2-out combination with
3 terminals/channel
6-channel isolated with 1492-AIFM6S-3 1492-RAIFM6S-3➍ — — ZA ZB ZC X Y Z — — — — — — — — — — Z — — — — Y Y — — — —
3…4 terminals/channel
8- or 16-channel input or 1492-AIFM8-3 1492-RAIFM8-3➎ — — — — — — — — TA TB TC TD UC UD UA UB UC UD — — — — — — — WA WB WA WB —
output with
3 terminals/channel
Thermocouple
6-channel with 1492-AIFM6TC-3 — — — — — — — — — — — — — — — — — — — — Y YT — — — — — — — — —
3 terminals/channel
High Speed Counter/Encoder
2-channel counter input/4 1492-AIFMCE4 — XA XB — — — — — — — — — — — — — — — — — — — — — — — — — — — —
outputs
Fusible High-Speed Counter/Encoder
2-channel fused counter 1492-AIFMCE4-F — XA XB — — — — — — — — — — — — — — — — — — — — — — — — — — — —
input/4 fused outputs
Fusible Analog
8-channel input with 24V DC 1492-AIFM8-F-5 — — — ZA ZB ZC — — — TA TB TC TD UC UD — — UC UD — — — — — — — — — — — —
blown fuse indicators,
5 terminals/channel
16-channel input with 24V DC 1492-AIFM16-F-3 — — — — — — — — — — — — — — — UA UB UC UD — — — — — — — — — — — —
blown fuse indicators,
3 terminals/channel
16-channel input with 24V DC 1492-AIFM16-F-5 — — — — — — — — — — — — — — — UA UB UC UD — — — — — — — — — — — —
blown fuse indicators,
5 terminals/channel
8 input/ 1492-AIFMPI — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — M
2 output channels

➊ Some analog I/O modules can be operated in up to four modes (current/voltage, single-ended/differential) based on connections. In all cases, each channel is factory-
configured for the same mode. However, you can field configure any channel for another mode. You made need to alter the terminal block wiring to match the application.
Refer to the PLC installation manual
➋ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-ACABLE025TB is for a 2.5 m cable, and the letters TB.
➌ Compatible Removable Terminal Block (RTB) plug; 1492-RTB8N (screw style terminals) or 1492-RTB8P (push-in style terminals). ORDER PLUGS SEPARATELY.
➍ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.
➎ Compatible Removable Terminal Block (RTB) plug; 1492-RTB16N (screw style terminals) or 1492-RTB16P (push-in style terminals). ORDER PLUGS SEPARATELY.

Publication 1492-TD008D-EN-P - January 2009


42 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Bulletin 1756 ControlLogix AIFMs and Cables, Continued


Continued
These pre-wired cables have a pre-wired RTB on one end to connect to the
front of a Bulletin 1756 analog I/O module and a D-shell connector on the
other end to plug into a 15- or 25-pin D-shell terminal AIFM. You must first
select the AIFM from the preceding selection table.

Pre-Wired Cables for 1756 Analog I/O Modules

Cable Standard Cable Build-to-Order AIFM Mating 1756


Catalog Number Lengths Available Connector I/O Module Catalog Number
1492-ACABLE➊M 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1757-PIM
1492-ACABLE➊X 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Current
1492-ACABLE➊Y 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Voltage, -IT6I, -OF6CI, -OF6VI
1492-ACABLE➊YT 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IT6I2
1492-ACABLE➊Z 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IR6I, -IF6CIS
1492-ACABLE➊TA 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF8 Single-Ended Voltage
1492-ACABLE➊TB 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF8 Single-Ended Current
1492-ACABLE➊TC 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF8 Diff. Voltage
1492-ACABLE➊TD 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF8 Diff. Current
1492-ACABLE➊UA 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Single-Ended Voltage
1492-ACABLE➊UB 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Single-Ended Current
1492-ACABLE➊UC 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Diff. Voltage, -IF8H (Voltage)
1492-ACABLE➊UD 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF16 Diff. Current, IF8H (Current/Hart)
1492-ACABLE➊VA 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1756-OF4 Voltage
1492-ACABLE➊VB 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1756-OF4 Current
1492-ACABLE➊WA 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-OF8 Voltage, -OF8H (Voltage)
1492-ACABLE➊WB 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-OF8 Current, -OF8H (Current/Hart)
1492-ACABLE➊XA 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-HSC (24V DC Diff.)
1492-ACABLE➊XB 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-HSC (5V DC Diff.)
1492-ACABLE➊ZA 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF4FXOF2F (Cur In & Out)
1492-ACABLE➊ZB 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF4FXOF2F (Volt In & Out)
1492-ACABLE➊ZC 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1756-IF4FXOF2F (Cur In & Volt Out)

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-ACABLE005Y is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-AIFM6TC-3 analog IFM to a Catalog Number 1756-IT6I I/O module.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 43

Selection Tables, Using Bulletin 1762/1764 Selection Tables to Make Valid 1492
Continued Wiring System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
1. Find the appropriate table based on the catalog numbers of the
1762/1764 controller.
2. Find the column for the 1762/1764 I/O.
3. Follow the column down to determine which Wiring System Modules
are compatible with the I/O as indicated by letter and number (e.g. A62)
code. If there is no letter/number code, the Wiring System Module is
not compatible with the I/O module. NOTE: The letter/number
codes designate the compatible 1492 cable for that 1762/1764 I/O and
Wiring System Module combination.
4. Select the desired Wiring System Module.
5. Configure the cable catalog number using 1492-CAB➊. See footnote ➊
on pages 43 and 44.

MicroLogix 1200 Embedded 40 I/O Controllers to IFM Selection


Tables
Bulletin 1762-L40x Compatible 40-Terminal 1492-IFMs
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring 1762 Embedded I/O Controller
System Module System Module

-L40BWA Outputs
-L40AWA Outputs

-L40BXB Outputs
with Fixed with Removable

-L40BWA Inputs
-L40AWA Inputs

-L40BXB Inputs
Terminal Block Terminal Block
Socket Assembly
(order plugs
separately

Feed-through
Standard 132V AC/DC Max. 1492-IFM40F❶ 1492-RIFM40F❶➋ A62 A62 A62 B62 B62 B62
Extra terminals 132V AC/DC Max. 1492-IFM40F-2❶ 1492-RIFM40F-2❶➋ A62 A62 A62 B62 B62 B62
❶ When using this IFM module with the base I/O of the 1762 controller, the current rating of the ouputs must be considered.
➋ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminlas) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
These pre-wired cables have a pre-wired removable terminal block (RTB) on
one end to connect to the front of the Bulletin 1762 controller embedded
digital I/O and a connector on the other end to plug into a 40-terminal IFM.
You must first select the IFM from the preceding selection table.
Pre-Wired Cables for 1762-L40x Embedded I/O Controllers
Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1762-L40x Embedded I/O Controller
Lengths Available Conductors
1492-CAB➊A62 0.5, 1.0, 2.5, 5.0 Yes 40 -L40AWA Inputs, -L40BWA Inputs, -L40BXB Inputs
1492-CAB➊B62 0.5, 1.0, 2.5, 5.0 Yes 40 -L40AWA Outputs, -L40BWA Outputs, -L40BXB Outputs

➊ Pre-wired cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number
(005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CAB005A62 is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM40F to a Cat. No. 1762-L40AWA Input.

Publication 1492-TD008D-EN-P - January 2009


44 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, The I/O module-ready cables have a pre-wired RTB on one end to plug
onto the front of the Bulletin 1762 controller embedded I/O and 25 or 40
Continued individually colored conductors on the other end. These cables provide the
convenience of pre-wired connections at the controller embedded I/O end,
while still allowing the flexibility to field-wire to standard terminal blocks of
your choice.
I/O Ready Cables for 1762-L40x Embedded I/O Controllers
Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1762-L40x Embedded I/O Controller
Lengths Available Conductors❸
1492-CAB➋T62 1.0, 2.5, 5.0 m Yes 25 -L40AWA Outputs, -L40BWA Outputs, -L40BXB Outputs
1492-CAB➋X62 1.0, 2.5, 5.0 m Yes 40 -L40AWA Inputs, -L40BWA Inputs, -L40BXB Inputs

❷ I/O ready cables are available in standard lengths or 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025
= 2.5 m, and 050 = 5.0 m) Example: Catalog Number 1492-CABLE050RTBR is for a 5.0 m cable with a pre-wired Catalog Number 1746-RT25R RTB on one end.
❸ 1492-CAB➊T62 uses 18AWG wire and 1492-CAB➊X62 uses 22AWG wire.

MicroLogix 1500 Base Unit I/O to IFM Selection Tables

Bulletin 1764, Base Units I/O and Compatible 20-Terminal 1492-IFMs


Description of 20-PIN IFM Catalog Number for Catalog Number for 1764 Base Unit I/O
Wiring System Module Wiring System Module

BWA Outputs
AWA Outputs
with Fixed Terminal with Removable

BXB Outputs
BWA Inputs
AWA Inputs

BXB Inputs
Block Terminal Block Socket
Assembly (order plugs
separately

Feed-through
Standard 264Vac/dc Max. 1492-IFM20F❶ 1492-RIFM20F❶➋ A64 A64 B64 C64 C64 F64
Narrow standard 132Vac/dc Max. ❶ ❶➌ A64 A64 B64 C64 C64 F64
1492-IFM20FN 1492-RIFM20FN
With Extra terminals (2 per I/O) 264Vac/dc Max. 1492-IFM20F-2❶ 1492-RIFM20F02❶➋ A64 A64 B64 C64 C64 F64
❶ When using this IFM module with the base I/O of the 1762 controller, the current rating of the ouputs must be considered. Refer to appendix A
➋ Compatible Removablae Terminal Block (RTB) 1492-RTB20N (screw style terminal) or 1492-RTB20P (push-in style terminal, available March 2006). ORDER PLUGS
SEPARATELY.
➌ Compatible Removable Terminal Block (RTB) plug; 1492-RTB10N (screw style terminals) or 1492-RTB10P (push-in style terminals, available March 2006. ORDER PLUGS
SEPARATELY.
These pre-wired cables have a pre-wired removable terminal block (RTB) on
one end to connect to the front of the Bulletin 1764 base unit digital I/O and
a connector on the other end to plug into a 20-terminal IFM. You must first
select the IFM from the preceding selection table.
Pre-Wired Cables for 1764 Base I/O
I/O Ready Cable Standard Cable Build-to-Order No. of Mating 1764 Base Unit I/O
Cat. No. Lengths Available Conductors

1492-CAB➊A64 0.5, 1.0, 2.5, 5.0 Yes 20 AWA Inputs, BWA Inputs

1492-CAB➊B64 0.5, 1.0, 2.5, 5.0 Yes 20 BXB Inputs

1492-CAB➊C64 0.5, 1.0, 2.5, 5.0 Yes 20 AWA Outputs, BWA Outputs

1492-CAB➊F64 0.5, 1.0, 2.5, 5.0 Yes 20 BXB Output

➊ Pre-wired cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number
(005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CAB005A64 is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM20F to a Cat. No. 1764-AWA Input.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 45

Selection Tables, The I/O module-ready cables have a pre-wired RTB on one end to plug onto
Continued the front of the Bulletin 1764 base unit I/O and 20 individually colored
conductors on the other end. These cables provide the convenience of pre-
wired connections at the base unit I/O end, while still allowing the flexibility
to field-wire to standard terminal blocks of your choice.
I/O Ready Cables for 1764 Base I/O
Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1764 Base Unit I/O
Lengths Available Conductors

1492-CAB➋T64 1.0, 2.5, 5.0 m Yes 20❸ AWA Outputs, BWA Outputs

1492-CAB➋U64 1.0, 2.5, 5.0 m Yes 20❸ BXB Outputs

1492-CAB➋W64 1.0, 2.5, 5.0 Yes 20❹ AWA Inputs, BWA Inputs

1492-CAB➋X64 1.0, 2.5, 5.0 Yes 20❹ BXB Inputs

➋ I/O ready cables are available in standard lengths or 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025
= 2.5 m, and 050 = 5.0 m) Example: Catalog Number 1492-CABLE050RTBR is for a 5.0 m cable with a pre-wired Catalog Number 1746-RT25R RTB on one end.
➌ Uses #18 AWG wire.
➍ Uses #22 AWG wire.

Using Bulletin 1769 Selection Tables to Make Valid 1492 Wiring


System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
1. Find the appropriate table based on the catalog number of the 1769 I/O
module.
2. Find the column in the selected table for the 1769 I/O module.
3. Follow the column down to determine which Wiring System Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the Wiring System Module is not compatible with the
I/O module. NOTE: The letter codes designate the compatible 1492
cable for that 1769 I/O and Wiring System Module combination.
4. Select the desired Wiring System Module.
5. Configure the cable catalog number using 1492-CAB➊ (for digital
cables) or 1492-ACAB➊ (for analog cables). See footnote ➊ on
pages 50 and 53.

Bulletin 1769 Compact I/O for CompactLogix and MicroLogix 1500


IFMs and Cables
Bulletin 1769 Digital 8 and 16-Point I/O Modules ➌
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal
OW16
OW8I
IQ16F

OA16

OB16

OV16
IM12

OW8
IA16

IQ16

OA8

OB8

Block Socket Assembly


IA8I

(order plugs separately


Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F➐ F69 A69 B69 B69 G69 C69 M69 L69 E69 E69 C69 D69 M69
Narrow standard 132V AC/DC Max. 1492-IFM20FN 1492-RIFM20FN➑ F69 A69 B69 B69 — C69 M69 L69 E69 E69 C69 — M69
Extra terminals (2 per I/O) 264V AC/DC 1492-IFM20F-2 1492-RIFM20F-2➐ — A69 B69 B69 G69 C69 M69 L69 E69 E69 C69 — M69
Max.
3-wire sensor type input devices 132V 1492-IFM20F-3 — — A69 B69 B69 — — — — — — — — —
AC/DC Max.
Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


46 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1769 Digital 8 and 16-Point I/O Modules (Continued)➌


Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal

OW16
OW8I
IQ16F

OA16

OB16

OV16
IM12

OW8
IA16

IQ16

OA8

OB8
Block Socket Assembly

IA8I
(order plugs separately
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM20D24 — — — B69 B69 — — — — E69 E69 — — M69
Narrow standard with 24V AC/DC 1492-IFM20D24N — — — B69 B69 — — — — E69 — — — H69
LEDs
Standard with 120V AC/DC LEDs 1492-IFM20D120 ➍ — — A69 — — — — M69 — — — — — M69
Narrow standard with 120V AC LEDs 1492-IFM20D120N — — A69 — — — — H69 — — — — — H69
24V AC/DC LEDs and extra terminals 1492-IFM20D24-2 — — — — — — — — — E69 E69 — — M69
for outputs
24V AC/DC LEDs and extra terminals 1492-IFM20D24A-2 — — — B69 B69 — — — — — — — — —
for inputs
120V AC LEDs and extra terminals for 1492-IFM20D120-2 — — — — — — — M69 — — — — — M69
outputs
120V AC LEDs and extra terminals for 1492-IFM20D120A-2 — — A69 — — — — — — — — — — —
inputs
3-wire sensor with 24V AC/DC LEDs 1492-IFM20D24-3 — — — B69 B69 — — — — — — — — —
8 Individually isolated with 24/48V 1492-IFM20DS24-4 — — — — — — — — — — — C69 D69 —
AC/DC LEDs and 4 terminals/output
8 Individually isolated with 120V AC 1492-IFM20DS120-4 — — — — — — C69 — — — — C69 D69 —
LEDs and 4 terminals/output
240V AC LEDs and extra terminals for 1492-IFM20D240-2 — — — — — — — M69 — — — — — M69
outputs
240V AC LEDs and extra terminals for 1492-IFM20D240A-2 — — — — — G69 — — — — — — — —
inputs
Fusible
120V AC/DC with extra terminals for 1492-IFM20F-F-2 14792-RIFM20F-F-2➐ — — — — — — M69 — E69 E69 — — M69
outputs
Extra terminals with 24V AC/DC blown 1492-IFM20F-F24-2 1492-IFM20F-F24-2➐ — — — — — — — — E69 E69 — — M69
fuse LED indicators
Extra terminals with 120V AC/DC 1492-IFM20F-F120-2 1492-RIFM20F-F120-2➐ — — — — — — M69 — — — — — M69
blown fuse LED indicators
Extra terminals with 240V AC/DC 1492-IFM20F-F240-2 — — — — — — — — — — — — — —
blown fuse LED indicators
Extra terminals with 24V AC/DC blown 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2➐ — — B69 B69 — — — — — E69 — — —
fuse LED indicators ➊ ➊
Extra terminals with 120V AC/DC 1492-IFM20F-F120A-2 1492-RIFM20F-F120A02➐ — A69 — — — — — — — — — — —
blown fuse LED indicators
8 Individually isolated 120V AC/DC 1492-IFM20F-FS-2 — — — — — — C69 — — — — C69 D69 —
with extra terminals for outputs
8 Individually isolated with extra 1492-IFM20F-FS24-2 — — — — — — — — — — — C69 D69 —
terminals output, and 24V AC/DC
blown fuse indicators
Two 4-point isolated groups with 1492-IFM20F-FS24A-4 — — — — — — — — — — — — — —
four terminals/input and 24V AC/DC
blown fuse LED indicators
8 Individually isolated with extra 1492-IFM20F-FS120-2 — — — — — — C69 — — — — C69 D69 —
terminals output, and 120V AC/DC
blown fuse LED indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — C69 — — — — C69 D69 —
four terminals/output and 120V
AC/DC blown fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS120A-4 — — — — — — — — — — — — — —
four terminals/input and 120V AC/DC
blown fuse indicators
8 Individually isolated with 1492-IFM20F-FS240-4 — — — — — — — — — — — — D69 —
four terminals/output and 240V
AC/DC blown fuse LED indicators
Relay Master (LED Indicating) ➎➏
20-pin master with eight (8) 24V DC 1492-XIM2024-8R➒ — — — — — — — — — E69 — — — —
relays
20-pin master with eight (8) 120V AC 1492-XIM20120-8R➓ — — — — — — — H69 — — — — — —
relays
20-pin master with sixteen (16) 24V 1492-XIM2024-16R — — — — — — — — — E69 — — — —
DC relays with fusing
20-pin master with sixteen (16) 24V 1492-XIM2024-16RF — — — — — — — — — E69 — — — —
DC relays with fusing
20-pin master with sixteen (16) 120V 1492-XIM20120-16R — — — — — — — H69 — — — — — —
AC relays
20-pin master with sixteen (16) 120V 1492-XIM20120-16RF — — — — — — — H69 — — — — — —
AC relays with fusing

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 47

Bulletin 1769 Digital 8 and 16-Point I/O Modules (Continued)➌


Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal

OW16
OW8I
IQ16F

OA16

OB16

OV16
IM12

OW8
IA16

IQ16

OA8

OB8
Block Socket Assembly

IA8I
(order plugs separately
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM20D24 — — — B69 B69 — — — — E69 E69 — — M69
Narrow standard with 24V AC/DC 1492-IFM20D24N — — — B69 B69 — — — — E69 — — — H69
LEDs
Standard with 120V AC/DC LEDs 1492-IFM20D120 ➍ — — A69 — — — — M69 — — — — — M69
Narrow standard with 120V AC LEDs 1492-IFM20D120N — — A69 — — — — H69 — — — — — H69
24V AC/DC LEDs and extra terminals 1492-IFM20D24-2 — — — — — — — — — E69 E69 — — M69
for outputs
24V AC/DC LEDs and extra terminals 1492-IFM20D24A-2 — — — B69 B69 — — — — — — — — —
for inputs
120V AC LEDs and extra terminals for 1492-IFM20D120-2 — — — — — — — M69 — — — — — M69
outputs
120V AC LEDs and extra terminals for 1492-IFM20D120A-2 — — A69 — — — — — — — — — — —
inputs
3-wire sensor with 24V AC/DC LEDs 1492-IFM20D24-3 — — — B69 B69 — — — — — — — — —
8 Individually isolated with 24/48V 1492-IFM20DS24-4 — — — — — — — — — — — C69 D69 —
AC/DC LEDs and 4 terminals/output
8 Individually isolated with 120V AC 1492-IFM20DS120-4 — — — — — — C69 — — — — C69 D69 —
LEDs and 4 terminals/output
240V AC LEDs and extra terminals for 1492-IFM20D240-2 — — — — — — — M69 — — — — — M69
outputs
240V AC LEDs and extra terminals for 1492-IFM20D240A-2 — — — — — G69 — — — — — — — —
inputs
Fusible
120V AC/DC with extra terminals for 1492-IFM20F-F-2 14792-RIFM20F-F-2➐ — — — — — — M69 — E69 E69 — — M69
outputs
Extra terminals with 24V AC/DC blown 1492-IFM20F-F24-2 1492-IFM20F-F24-2➐ — — — — — — — — E69 E69 — — M69
fuse LED indicators
Extra terminals with 120V AC/DC 1492-IFM20F-F120-2 1492-RIFM20F-F120-2➐ — — — — — — M69 — — — — — M69
blown fuse LED indicators
Extra terminals with 240V AC/DC 1492-IFM20F-F240-2 — — — — — — — — — — — — — —
blown fuse LED indicators
Extra terminals with 24V AC/DC blown 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2➐ — — B69 B69 — — — — — E69 — — —
fuse LED indicators ➊ ➊
Extra terminals with 120V AC/DC 1492-IFM20F-F120A-2 1492-RIFM20F-F120A02➐ — A69 — — — — — — — — — — —
blown fuse LED indicators
8 Individually isolated 120V AC/DC 1492-IFM20F-FS-2 — — — — — — C69 — — — — C69 D69 —
with extra terminals for outputs
8 Individually isolated with extra 1492-IFM20F-FS24-2 — — — — — — — — — — — C69 D69 —
terminals output, and 24V AC/DC
blown fuse indicators
Two 4-point isolated groups with 1492-IFM20F-FS24A-4 — — — — — — — — — — — — — —
four terminals/input and 24V AC/DC
blown fuse LED indicators
8 Individually isolated with extra 1492-IFM20F-FS120-2 — — — — — — C69 — — — — C69 D69 —
terminals output, and 120V AC/DC
blown fuse LED indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — C69 — — — — C69 D69 —
four terminals/output and 120V
AC/DC blown fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS120A-4 — — — — — — — — — — — — — —
four terminals/input and 120V AC/DC
blown fuse indicators
8 Individually isolated with 1492-IFM20F-FS240-4 — — — — — — — — — — — — D69 —
four terminals/output and 240V
AC/DC blown fuse LED indicators
Relay Master (LED Indicating) ➎➏
20-pin master with eight (8) 24V DC 1492-XIM2024-8R➒ — — — — — — — — — E69 — — — —
relays
20-pin master with eight (8) 120V AC 1492-XIM20120-8R➓ — — — — — — — H69 — — — — — —
relays
20-pin master with sixteen (16) 24V 1492-XIM2024-16R — — — — — — — — — E69 — — — —
DC relays with fusing
20-pin master with sixteen (16) 24V 1492-XIM2024-16RF — — — — — — — — — E69 — — — —
DC relays with fusing
20-pin master with sixteen (16) 120V 1492-XIM20120-16R — — — — — — — H69 — — — — — —
AC relays
20-pin master with sixteen (16) 120V 1492-XIM20120-16RF — — — — — — — H69 — — — — — —
AC relays with fusing

Note: Footnotes are on the following page.


Publication 1492-TD008D-EN-P - January 2009
48 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1769 Digital 8 and 16-Point I/O Modules (Continued)➌


Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal

OW16
OW8I
IQ16F

OA16

OB16

OV16
IM12

OW8
IA16

IQ16

OA8

OB8
Block Socket Assembly

IA8I
(order plugs separately
Relay Expander (LED Indicating) ➎➏
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R✱ — — — — — — — — ➋ — — — —
Expander with eight (8) 120V AC 1492-XIM120-8R — — — — — — — — — — — — — —
relays
Fusible Expander — — — — — — — — — — — — — —
8-channel expander with 24V DC 1492-XIMF-F24-2 — — — — — — — — — ➋ — — — —
blown fuse indicators
8-channel expander with 120V AC 1492-XIMF-F120-2 — — — — — — — ➋ — — — — — —
blown fuse indicators
Feed-through Expander
Expander with eight (8) feed-through 1492-XIMF-2 — — — — — — — ➋ ➋ ➋ — — — —
channels 132V AC/DC max.
➊ In the input module’s sink mode only.
➋ One expander module is connected to a master to provide a total of 16 outputs. An extender cable is included with each expander to connect it to the master.
➌ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050A is for a 5.0 m cable, and the letter A.
➍ This IFM is not recommended for use with PLC I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 for
inputs. Use 1492-IFM20D120-2 for outputs.
➎ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➏ The LED indicates the PLC output status.
➐ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB10N (screw style terminals) or 1492-RTB10P (push-in style terminals). ORDER PLUGS SEPARATELY.
➒ Expandable to 16 using XIM24-8R or XIMF-24-2.
➓ Expandable to 16 using XIM120-8R or XIMF-24-2.
✱ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 49

Bulletin 1769 Compact I/O for CompactLogix and MicroLogix 1500


IFMs and Cables, Continued

Bulletin 1769 Digital 32-Point I/O Modules ➊


Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal
Block Socket Assembly IQ32 IQ32T OB32 OB32T OV32T
(order plugs separately
Feed-through
Standard 132V AC/DC Max. 1492-IFM40F 1492-RIFM40F➏ J69 H K69 H H
Extra terminals (2 per I/O) 132V AC/DC Max. 1492-IFM40F-2 1492-RIFM40F-2➏ J69 H K69 H H
3-wire sensor type input devices 60V AC/DC Max. 1492-IFM40F-3 — J69 H — — —
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM40D24 1492-RIFM40D24➏ J69 H K69 H H
24V AC/DC LEDs and extra terminals for outputs 1492-IFM40D24-2 — — — K69 H H
24V AC/DC LEDs and extra terminals for inputs 1492-IFM40D24A-2 1492-RIFM40D24A-2➏ J69 H — — —
120V AC LEDs and extra terminals for outputs 1492-IFM40D120-2 — — — — — —
120V AC LEDs and extra terminals for inputs 1492-IFM40D120A-2 — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM40D24-3 — J69 H — — —
16 Individually isolated with 24/48V AC/DC LEDs 1492-IFM40DS24-4 — — — — — —
and 4 terminals/output
16 Individually isolated with 24V AC/DC LEDs and 1492-IFM40DS24A-4 — — — — — —
4 terminals/input
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120-4 — — — — — —
4 terminals/output
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120A-4 — — — — — —
4 terminals/input
16 Individually isolated with 240V AC LEDs and 1492-IFM40DS240A-4 — — — — — —
4 terminals/input
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM40F-F-2 — — — K69 H H
Extra terminals with 24V AC/DC blown fuse 1492-IFM40F-F24-2 1492-RIFM40F-F24-2➏ — — K69 H H
indicators for outputs
Extra terminals with 120V AC/DC blown fuse 1492-IFM40F-F120-2 — — — — — —
indicators
16 Individually isolated with extra terminals for 1492-IFM40F-FS-2 — — — — — —
120V AC/DC outputs
16 Individually isolated with extra terminals and 1492-IFM40F-FS24-2 — — — — — —
24V AC/DC blown fuse indicators
16 Individually isolated with 24V AC/DC blown 1492-IFM40F-FS24-4 — — — — — —
fuse indicators and 4 terminals/output
16 Individually isolated 240V AC/DC with 4 1492-IFM40F-FS-4 — — — — — —
terminals/output
16 Individually isolated with extra terminals and 1492-IFM40F-FS120-2 1492-RIFM40F-FS120-2➏ — — — — —
120V blown fuse indicators
16 Individually isolated with 120V AC/DC blown 1492-IFM40F-FS120-4 1492-RIFM-FS120-4❼ — — — — —
fuse indicators and 4 terminals/output
16 Individually isolated with 240V AC/DC blown 1492-IFM40F-FS240-4 — — — — — —
fuse indicators and 4 terminals/output
16 Individually isolated with 24V AC/DC blown 1492-IFM40F-FS24A-4 — — — — — —
fuse indicators and 4 terminals/input
16 Individually isolated 120V AC/DC with 4 1492-IFM40F-FSA-4 — — — — — —
terminals/input
16 Individually isolated with 120V AC/DC blown 1492-IFM40F-FS120A-4 1492-RIFM40F-FS120A- — — — — —
fuse indicators and 4 terminals/input 4❼
16 Individually isolated with 240V AC/DC blown 1492-IFM40F-FS240A-4 — — — — — —
fuse indicator and 4 terminals/input
Relay Master (LED Indicating) ➍➎
40-pin master with eight (8) 24V DC relays 1492-XIM4024-8R — — — K69 H —
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16R 1492-RXIM4024-16R➑ — — K69 H —
Note: Footnotes are on the following page.
Publication 1492-TD008D-EN-P - January 2009
50 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1769 Digital 32-Point I/O Modules (Continued)➊


Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1769-…
System Module with System Module with
Fixed Terminal Block Removable Terminal
Block Socket Assembly IQ32 IQ32T OB32 OB32T OV32T
(order plugs separately
40-pin master with sixteen (16) 24V DC relays with 1492-XIM4024-16RF — — — K69 H —
fusing
Relay Expander (LED Indicating) ➍➎
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R➒ — — ➋ ➋ —
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — —
Fusible Expander
8-channel expander with 24V DC blown fuse 1492-XIMF-F24-2 — — — ➋ ➋
indicators
8-channel expander with 120V AC blown fuse 1492-XIMF-F120-2 — — — — — —
indicators
Expander with sixteen (16) 24V DC relays with 1492-XIM24-16RF — — — ➌ ➋ —
fusing
Feed-through Expander
Expander with eight (8) feed-through channels 1492-XIMF-2 — — — ➋ ➋ —
➊ Cables are available in standard lengths of 0.5, 1.0, 2.5, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m (010 = 1.0 m,
025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050A is for a 5.0 m cable, and the letter A.
➋ Can have 2 or 3 expander modules depending on master used (32 pts. or less). Extender cable is provided.
➌ One 1492-XIM24-16RF is to be used with one 1492-XIM4024-16R or 1492-XIM4024-16RF master (32 pts. max.).
➍ The voltage rating is relay control/coil voltage. For relay contact ratings, refer to page 192.
➎ The LED indicates the PLC output status.
➏ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P (push-in style terminals). ORDER PLUGS SEPARATELY.
❼ Compatible Removable Terminal Block (RTB) plug; 1492-RTB17N (screw style terminals) or 1492-RTB17P (push-in style terminals). ORDER PLUGS SEPARATELY.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB14N (screw style terminals) or 1492-RTB14P (push-in style terminals). ORDER PLUGS SEPARATELY.
➒ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-in style terminals). ORDER PLUGS SEPARATELY.

Bulletin 1769 Compact I/O for CompactLogix and MicroLogix 1500


IFMs and Cables, Continued

These pre-wired cables have a pre-wired RTB on one end to connect to the
front of a Bulletin 1769 digital I/O module and a connector on the other end
to plug into a 20- or 40-terminal IFM/XIM. You must first select the
IFM/XIM from the preceding selection table.

Pre-Wired Cables for Bulletin 1769 Digital I/O Modules


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1769
Lengths Available Conductors I/O Module Catalog Number
1492-CAB➊A69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-IA16
1492-CAB➊B69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-IQ16
1492-CAB➊C69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OA8, -OW8
1492-CAB➊D69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OW8I
1492-CAB➊E69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OB16, -OV16
1492-CAB➊F69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-IA8I
1492-CAB➊G69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-IM12
1492-CAB➊H69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OA16, -OW16 (IFM modules with single common)
1492-CAB➊J69 0.5, 1.0, 2.5, 5.0 m Yes 40 1769-IQ32
1492-CAB➊K69 0.5, 1.0, 2.5, 5.0 m Yes 40 1769-OB32

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 51

Pre-Wired Cables for Bulletin 1769 Digital I/O Modules (Continued)


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1769
Lengths Available Conductors I/O Module Catalog Number
1492-CAB➊L69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OB8
1492-CAB➊M69 0.5, 1.0, 2.5, 5.0 m Yes 20 1769-OA16, -OW16 (IFM modules with multiple commons)
1492-CABLE➊H 0.5, 1.0, 2.5, 5.0 m Yes 40 1769-IQ32T, -OB32T, -OV32T

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CAB005E69 is for a 0.5 m cable that can be used to connect a Catalog
Number 1492-IFM20D24N IFM to a Catalog Number 1769-OB16 I/O module.

The I/O module-ready cables have a pre-wired RTB on one end to plug
onto the front of a Bulletin 1769 I/O module and 20 individually colored
#18 AWG conductors on the other end. These cables provide the convenience
of pre-wired connections at the I/O module end, while still allowing the
flexibility to field-wire to standard terminal blocks of your choice.

I/O Module-Ready Cables for Bulletin 1769 Digital I/O Modules ➍


Cable Standard Cable Build-to-Order No. of Mating 1769
Catalog Number Lengths Available Conductors I/O Module Catalog Number
1492-CAB➌RTN10 1.0, 2.5, 5.0 m Yes 12 1769-OA8, -OW8
1492-CAB➌RTN18 1.0, 2.5, 5.0 m Yes 20 1769-IA8I, -IA16, -IQ16, -IQ16F, -OA16, -OB16, -OV16,
-OW16, -OW8I, -IM12, -OB8
1492-CAB➌RTN32I 1.0, 2.5, 5.0 m Yes 40 ➋ 1769-IQ32
1492-CAB➌RTN32O 1.0, 2.5, 5.0 m Yes 40 ➋ 1769-OB32
1492-CABLE➌N3 1.0, 2.5, 5.0 m Yes 40 ➋ 1769-IQ32T, -OB32T, -OV32T

➋ 1492-CAB➌ RTN32I and 1492-CAB➌ RTN320 cables use 22 AWG wire.


➌ Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m,
and 050 = 5.0 m). Example: Catalog Number 1492-CAB050RTN10 is for a 5.0 m cable with a wired Catalog Number 1746-RTBN10 on one end.
➍ Discrete I/O ready cables should not be used with PLC analog I/O modules as a cable shield and drain wires are not provided.

Publication 1492-TD008D-EN-P - January 2009


52 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Bulletin 1769 Compact I/O for CompactLogix and MicroLogix 1500


AIFMs and Cables

IFMs for Bulletin 1769 Analog I/O Modules➊


Description of AIFM Catalog Number for Catalog Number for I/O Module Catalog Number 1769-…
Wiring System Wiring System Module

(Single-Ended Voltage)

(Single-Ended Voltage)

(Single-Ended Current)

(Single-Ended Current)
Module with Fixed with Removable

IF4XOF2 or IF4FXOF2F

IF4XOF2 or IF4FXOF2F

IF4XOF2 or IF4FXOF2F
(Differential Voltage)

(Differential Voltage)

(Differential Current)

(Differential Current)
Terminal Block Terminal Block Socket

(Cur In & Volt Out)


HSC (Differential)
Assembly (order plugs

(Volt In & Out)


separately

(Cur In & Out)

(Voltage)

(Voltage)

(Current)

(Current)
OF8V

OF8C
OF2
OF2
IR6
IF4

IF8

IF4

IF8

IF4

IF8

IF4

IF8
Feed-through
4-channel input, output or 2-in/2- 1492-AIFM4-3 1492-RAIFM4-3➋ — BA69 — BB69 — BC69 — BD69 — — — — — AA69 — AB69 —
out combination with
3 terminals/channel
6-channel isolated with 1492-AIFM6S-3 1492-RAIFM6S-3➌ — — — — — — — — — CA69 CB69 CC69 C69 — — — —
3…4 terminals/channel
8- or 16-channel input or output 1492-AIFM8-3 1492-RAIFM8-3➍ — — EA69 — EB69 — EC69 — ED69 — — — — — D69 — D69
with 3 terminals/channel
Thermocouple
6-channel with 1492-AIFM6TC-3 — — — — — — — — — — — — — — — — — —
3 terminals/channel
High-Speed Counter/Encoder
2-channel counter input/4 1492-AIFMCE4 — HA69 — — — — — — — — — — — — — — — —
outputs
Fusible High-Speed Counter/Encoder
2-channel fused counter input/4 1492-AIFMCE4-F — HA69 — — — — — — — — — — — — — — — —
fused outputs
Fusible Analog
4-channel with 24V DC blown 1492-AIFM4I-F-5 — — BA69 — BB69 — BC69 — BD69 — — — — — — — — —
fuse indicators, test points,
5 terminals/input
3 terminals/output
2-channel input, 2-channel 1492-AIFM4C-F-5 — — — — — — — — — — — — — — — — — —
output with 24V DC blown fuse
indicators, test points,
5 terminals/input,
3 terminals/output
8-channel input with 24V DC 1492-AIFM8-F-5 — — — EA69 — EB69 — EC69 — ED69 CA69 CB69 CC69 — — — — —
blown fuse indicators,
5 terminals/channel
16-channel input with 24V DC 1492-AIFM16-F-3 — — — — — — — — — — — — — — — — — —
blown fuse indicators,
3 terminals/channel
16-channel input with 24V DC 1492-AIFM16-F-5 — — — — — — — — — — — — — — — — — —
blown fuse indicators,
5 terminals/channel
4-input/4-output channel with 1492-AIFMQS — — — — — — — — — — — — — — — — — —
8 fuses and 24V DC blown fuse
indicators
➊ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-ACAB025BA69 is for a 2.5 m cable, and the letters BA.
➋ Compatible Removable Terminal Block (RTB) plug; 1492-RTB8N (screw style terminals) or 1492-RTB8P. ORDER PLUGS SEPARATELY.
➌ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P. ORDER PLUGS SEPARATELY.
➍ Compatible Removable Terminal Block (RTB) plug; 1492-RTB16N (screw style terminals) or 1492-RTB16P. ORDER PLUGS SEPARATELY.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 53

These pre-wired cables have a pre-wired RTB on one end to connect to the
front of a Bulletin 1769 analog I/O module and a connector on the other end
to plug into a 15- or 25-pin D-shell terminal AIFM. You must first select the
AIFM from the preceding selection table.

Pre-Wired Cables for Bulletin 1769 Analog I/O Modules


Cable Standard Cable Build-to-Order AIFM Mating 1769
Catalog Number Lengths Available Connector I/O Module Catalog Number
1492-ACAB➊AA69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-OF2 Voltage
1492-ACAB➊AB69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-OF2 Current
1492-ACAB➊BA69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-IF4 Single-Ended Voltage
1492-ACAB➊BB69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-IF4 Single-Ended Current
1492-ACAB➊BC69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-IF4 Differential Voltage
1492-ACAB➊BD69 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1769-IF4 Differential Current
1492-ACAB➊C69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IR6 Resist. Temperature Detector
1492-ACAB➊CA69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF4XOF2 or -IF4FXOF2F (Cur In & Out)
1492-ACAB➊CB69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF4XOF2 or -IF4FXOF2F (Volt In & Out)
1492-ACAB➊CC69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF4XOF2 or -IF4FXOF2F (Cur In & Volt Out)
1492-ACAB➊D69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-OF8C, 1769-OF8V
1492-ACAB➊EA69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF8 Single-Ended Voltage
1492-ACAB➊EB69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF8 Single-Ended Current
1492-ACAB➊EC69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF8 Differential Voltage
1492-ACAB➊ED69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-IF8 Differential Current
1492-ACAB➊HA69 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1769-HSC Counter/Encoder (Differential)
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-ACAB005➋ is for a 0.5 m cable.

Selection Tables Using Bulletin 1794 Selection Tables to Make Valid 1492 Wiring
System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
Note: I/O modules must use Flex D-shell base cat. nos. 1794-TB37DS or
1794-TB62DS.
1. Find the appropriate table based on the catalog numbers of the 1794
I/O module.
2. Find the column for the 1794 I/O module.
3. Follow the column down to determine which Wiring Systems Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the 1492 Wiring System Module is not compatible with
the I/O module. NOTE: The letter codes designate the compatible
1492 cable for that 1794 I/O and 1492 Wiring System Module
combination.
4. Select the desired 1492 Wiring System Module.
5. Configure the cable catalog number using 1492-CAB➊ (for digital
cables) or 1492-ACAB➊ (for analog cables). See footnote ➊ on page 57.

Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


54 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Pre-Wired Cable and IFMs for Bulletin 1794 Digital 8-Point and 16-Point I/O Modules ➌
Description of 20-PIN IFM and Flex Cat. No. for Wiring Cat. No. for Wiring Cat. No. for Flex Digital I/O Module — Uses D-Shell Base 1794-TB37DS
Distributed I/O System Module with System Module with Compatible

IB10XOB6
Fixed Terminal Block Removable Terminal Screw Style (N)
Block Socket and Push-in

OB8EP
OB16P

OV16P
OB16

OV16
Assembly (order plugs Style (P) RTB

OW8
IB16

IV16

OB8
IB8
separately Plugs ➊
Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F 1492-RTB20✪ A94 A94 A94 A94 A94 A94 A94 A94 A94 A94 A94
Narrow standard 132V AC/DC Max. 1492-IFM20FN 1492-RIFM20FN 1492-RTB10✪ A94 A94 A94 A94 A94 A94 A94 A94 A94 A94 A94
Extra terminals (2 per I/O) 1492-IFM20F-2 1492-RIFM20F-2 1492-RTB20✪ A94 A94 A94 A94 A94 A94 A94 A94 A94 A94 A94
264V AC/DC Max.
3-wire sensor type input devices 1492-IFM20F-3 — — A94 A94 — A94 — — — — — — —
132V AC/DC Max.
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM20D24 — — — — — — A94 A94 A94 A94 A94 A94 —
Narrow standard with 24V AC/DC LEDs 1492-IFM20D24N — — A94 A94 — — A94 A94 A94 A94 — — —
Standard with 120V AC/DC LEDs 1492-IFM20D120 — — — — — — — — — — — — —
Narrow standard with 120V AC LEDs 1492-IFM20D120N — — — — — — — — — — — — —
24V AC/DC LEDs and extra terminals 1492-IFM20D24-2 — — — — — — A94 A94 A94 A94 A94 A94 —
for outputs
24V AC/DC LEDs and extra terminals 1492-IFM20D24A-2 — — A94 A94 — A94 — — — — — — —
for inputs
120V AC LEDs and extra terminals 1492-IFM20D120-2 — — — — — — — — — — — — —
for outputs
120V AC LEDs and extra terminals 1492-IFM20D120A-2 — — — — — — — — — — — — —
for inputs
3-wire sensor with 24V AC/DC LEDs 1492-IFM20D24-3 — — — — — — — — — — — — —
8 Individually isolated with 24/48V AC/DC 1492-IFM20DS24-4 — — — — — — — — — — — — A94
LEDs and 4 terminals/output
8 Individually isolated with 120V AC LEDs 1492-IFM20DS120-4 — — — — — — — — — — — — A94
and 4 terminals/output
240V AC LEDs and extra terminals 1492-IFM20D240-2 — — — — — — — — — — — — —
for outputs
240V AC LEDs and extra terminals 1492-IFM20D240A-2 — — — — — — — — — — — — —
for inputs
Fusible
120V AC/DC with extra terminals 1492-IFM20F-F-2 1492-RIFM20F-F-2 1492-RTB20✪ — — — — A94 A94 A94 A94 A94 A94 —
for outputs
Extra terminals with 24V AC/DC blown fuse 1492-IFM20F-F24-2 1492-RIFM20F-F24-2 1492-RTB20✪ — — — — A94 A94 A94 A94 A94 A94 —
LED indicators
Extra terminals with 120V AC/DC blown 1492-IFM20F-F120-2 1492-RIFM20F-F120-2 1492-RTB20✪ — — — — — — — — — — —
fuse LED indicators
Extra terminals with 240V AC/DC blown 1492-IFM20F-F240-2 — — — — — — — — — — — — —
fuse LED indicators
Extra terminals with 24V AC/DC blown fuse 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2 1492-RTB20✪ A94 A94 — — — — — — — — —
LED indicators
Extra terminals with 120V AC/DC blown 1492-IFM20F-F120A-2 1492-RIFM20F-F120A-2 1492-RTB20✪ — — — — — — — — — — —
fuse LED indicators
8 Individually isolated 120V AC/DC with 1492-IFM20F-FS-2 — — — — — — — — — — — — A94
extra terminals for outputs
8 Individually isolated with extra terminals 1492-IFM20F-FS24-2 — — — — — — — — — — — — A94
and 24V AC/DC blown fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS24A-4 — — — — — — — — — — — — —
four terminals/input and 24V AC/DC blown
fuse LED indicators
8 Individually isolated with extra terminals 1492-IFM20F-FS120-2 — — — — — — — — — — — — A94
output, and 120V AC/DC blown fuse LED
indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — — — — — — — —
four terminals/output and 120V AC/DC
blown fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS120A-4 — — — — — — — — — — — — —
four terminals/input and 120V AC/DC
blown fuse indicators
8 Individually isolated with 1492-IFM20F-FS240-4 — — — — — — — — — — — — —
4 terminals/output and 240V AC/DC blown
fuse indicators

Note: Footnotes are on the following page.


Publication 1492-TD008D-EN-P - January 2009
Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 55

Pre-Wired Cable and IFMs for Bulletin 1794 Digital 8-Point and 16-Point I/O Modules ➌ (Continued)
Description of 20-PIN IFM and Flex Cat. No. for Wiring Cat. No. for Wiring Cat. No. for Flex Digital I/O Module — Uses D-Shell Base 1794-TB37DS
Distributed I/O System Module with System Module with Compatible

IB10XOB6
Fixed Terminal Block Removable Terminal Screw Style (N)
Block Socket and Push-in

OB8EP
OB16P

OV16P
OB16

OV16
Assembly (order plugs Style (P) RTB

OW8
IB16

IV16

OB8
IB8
separately Plugs ➊
Relay Master (LED Indicating) ➎➏
20-pin master with eight (8) 24V DC relays 1492-XIM2024-8R — — — — — — A94 A94 A94 — — — —
20-pin master with eight (8) 120V AC relays 1492-XIM20120-8R — — — — — — — — — — — — —
20-pin master with sixteen (16) 120V AC 1492-XIM20120-16R — — — — — — — — — — — — —
relays
20-pin master with sixteen (16) 120V AC 1492-XIM20120-16RF — — — — — — — — — — — — —
relays with fusing
20-pin master relay with sixteen (16) 24V 1492-XIM2024-16R — — — — — — A94 A94 — — — — —
DC relays
20-pin master with sixteen (16) 24V DC 1492-XIM2024-16RF — — — — — — A94 A94 — — — — —
relays with fusing
Relay Expander (LED Indicating) ➎➏
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R 1492-RTB12✪ — — — — ➋ ➋ — — — — —
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — — — — — — — — —
Fusible Expander
8-channel expander with 24V DC blown 1492-XIMF-F24-2 — — — — — — ➋ ➋ — — — — —
fuse indicators
8-channel expander with 120V AC blown 1492-XIMF-F120-2 — — — — — — — — — — — — —
fuse indicators
Feed-through Expander
Expander with eight (8) feed-through 1492-XIMF-2 — — — — — — ➋ ➋ — — — — —
channels

➊ Order plugs separately (two plugs per catalog number). Plugs are available in screw style and push in style terminal types. To order, replace the ✪ in the catalog number
with the code for the desired terminal style. The code for screw style is N and the code for push in style is P. The number (i.e, 20) in the cat. no. indicates the number of
connections/pole.
➋ Can have up to one relay expansion module depending upon relay master used (total 16 points or less). Extender cable is provided.
➌ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CAB010A94 is for a 1.0 m cable, and the suffix A94.
➍ This IFM is not recommended for use with PLC I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 for
inputs. Use 1492-IFM20D120-2 for outputs.
➎ The voltage rating is relay control/coil voltage. For Relay Contact Ratings, refer to page 192.
➏ The LED indicates the PLC output status.

Pre-Wired Cables and IFMs for Bulletin 1794 Digital 16-Point Isolated and 32-Point I/O Modules ➌
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring Cat. No. for Compatible Flex Digital I/O Module — Uses D-Shell
System Module with System Module with Screw Style (N) and Base 1794-TB62DS…
Fixed Terminal Block Removable Terminal Push-in Style (P) RTB
Plug ➏
IB16XOB16P

Block Socket
Assembly (order plugs
separately)

OB32P
IB16D

IB32

Feed-through
Standard 132V AC/DC Max. 1492-IFM40F 1492-RIFM40F 1492-RTB20✪ B94 B94 B94 B94
Extra terminals (2 per I/O) 132V AC/DC Max. 1492-IFM40F-2 1492-RIFM40F-2 1492-RTB20✪ B94 B94 B94 B94
3-wire sensor type input devices 60V AC/DC Max. 1492-IFM40F-3 — — — — — —
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM40D24 1492-RIFM40D24 1492-RTB20✪ — — B94 B94
24V AC/DC LEDs and extra terminals for outputs 1492-IFM40D24-2 — — — — — B94
24V AC/DC LEDs and extra terminals for inputs 1492-IFM40D24A-2 1492-RIFM40D24A-2 1492-RTB20✪ — — — —
120V AC LEDs and extra terminals for outputs 1492-IFM40D120-2 — — — — — —
120V AC LEDs and extra terminals for inputs 1492-IFM40D120A-2 — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM40D24-3 — — — — — —
16 Individually isolated with 24/48V AC/DC LEDs and 1492-IFM40DS24-4 — — — — — —
4 terminals/output
16 Individually isolated with 24V AC/DC LEDs and 1492-IFM40DS24A-4 — — — — — —
4 terminals/input
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120-4 — — — — — —
4 terminals/output
16 Individually isolated with 120V AC LEDs and 1492-IFM40DS120A-4 — — — — — —
4 terminals/input

Publication 1492-TD008D-EN-P - January 2009


56 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Pre-Wired Cables and IFMs for Bulletin 1794 Digital 16-Point Isolated and 32-Point I/O Modules (Continued)➌
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring Cat. No. for Compatible Flex Digital I/O Module — Uses D-Shell
System Module with System Module with Screw Style (N) and Base 1794-TB62DS…
Fixed Terminal Block Removable Terminal Push-in Style (P) RTB
Plug ➏

IB16XOB16P
Block Socket
Assembly (order plugs
separately)

OB32P
IB16D

IB32
16 Individually isolated with 240V AC LEDs and 1492-IFM40DS240A-4 — — — — — —
4 terminals/input
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM40F-F-2 — — — — — B94
Extra terminals with 24V AC/DC blown fuse indicators for 1492-IFM40F-F24-2 1492-RIFM40F-F24-2 1492-RTB20✪ — — — B94
outputs
Extra terminals with 120V AC/DC blown fuse indicators for 1492-IFM40F-F120-2 — — — — — —
outputs
16 Individually isolated with extra terminals for 120V AC 1492-IFM40F-FS-2 — — — — — —
DC outputs
Individually isolated with extra terminals and 24V AC/DC 1492-IFM40F-FS24-2 — — — — — —
blown fuse indicators for outputs
16 Individually isolated with 24V AC/DC blown fuse 1492-IFM40F-FS24-4 — — — — — —
indicators and 4 terminals/output
16 Individually isolated 240V AC/DC with 4 1492-IFM40F-FS-4 — — — — — —
terminals/output
16 Individually isolated with extra terminals and 120V 1492-IFM40F-FS120-2 1492-RIFM40F-FS120-2 1492-RTB20✪ — — — —
AC/DC blown fuse indicators for outputs
16 Individually isolated with 120V AC/DC blown fuse 1492-IFM40F-FS120-4 1492-RIFM40F-FS120-4 1492-RTB17✪ — — — —
indicators and 4 terminals/output
16 Individually isolated with 240V AC/DC blown fuse 1492-IFM40F-FS240-4 — — — — — —
indicators and 4 terminals/output
16 Individually isolated with 24V AC/DC blown fuse 1492-IFM40F-FS24A-4 — — — — — —
indicators and 4 terminals/input
16 Individually isolated with 120V AC/DC 1492-IFM40F-FSA-4 — — — — — —
4 terminals/input
16 Individually isolated with 120V AC/DC blown fuse 1492-IFM40F-FS120A-4 1492-RIFM40F-FS120A-4 1492-RTB17✪ — — — —
indicators and 4 terminals/input
16 Individually isolated with 240 VAC/DC blown fuse 1492-IFM40F-FS240A-4 — — — — — —
indicators and 4 terminals/input
Relay Master (LED Indicating) ➍➎
40-pin master with eight (8) 24V DC relays 1492-XIM4024-8R — — — — — B94
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16R 1492-RXIM4024-16R 1492-RTB14✪ — — — B94
40-pin master with sixteen (16) 24V DC relays with fusing 1492-XIM4024-16RF — — — — — B94
Relay Expander (LED Indicating) ➍➎
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R 1492-RTB12✪ — — — ➊
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — —
Fusible Expander
8-channel expander with 24V DC blown fuse indicators 1492-XIMF-F24-2 — — — — — ➊
8-channel expander with 120V AC blown fuse indicators 1492-XIMF-F120-2 — — — — — —
Expander with sixteen (16) 24V DC relays with fusing 1492-XIM24-16RF — — — — — ➋
Feed through Expander
Expander with eight (8) feed-through channels 1492-XIMF-2 — — — — — ➊

➊ Two or three expanders are connected to a master to provide a total of 32 outputs max (depends on PLC module). An extender cable is included with each expander to
connect it to the master.
➋ One 1492-XIM24-16RF is to be used with one 1492-XIM4024-16R AND 1492-XIM4024-16RF master (32 PT. only).
➌ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CAB010A94 is for a 1.0 m cable, and the suffix A94
➍ The voltage rating is relay control/coil voltage. For Relay Contact Ratings, refer to page 192.
➎ The LED indicates the PLC output status.
➏ Order plugs separately (two plugs per catalog number). Plugs are available in screw style and push in style terminal types. To order, replace the ✪ in the catalog number
with the code for the desired terminal style. The code for screw style is N and the code for push in style is P. The number (i.e, 20) in the cat. no. indicates the number of
connections/pole.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 57

Bulletin 1794 Pre-wired Cables

These pre-wired cables have a 37- or 62-pin D-shell connector on one end to
mate with the Flex base (Cat. No. 1492-TB37DS or -TB62DS) and a 20- or
40–pin AMP connector at the other end to mate with the IFM/XIM module.
You must first select the IFM/XIM from one of the preceding selection tables.

Pre-Wired Cables for Bulletin 1794 Flex Digital I/O Modules Using Flex Base 1794-TB37DS or -TB62DS
Cable Cat. No. Standard Cable Build-to-Order No. of Uses Flex Mating 1794
Lengths Available Conductors Base I/O Modules Catalog Number
1492-CAB➊A94 0.5, 1.0, 2.5, Yes 20 1794-TB37DS 1794-IB16, -IB8, -IV16, -OB16, -OB16P, -
5.0 m OB8, -OB8EP, -OV16, -OV16P,-OW8,
-IB10XOB8
1492-CAB➊B94 0.5, 1.0, 2.5, Yes 40 1794-TB62DS 1794-IB16D, -IB32, -OB32P, -IB16XOB16P
5.0 m
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CAB050A94 is for a 5.0 m cable that could be used to connect a Catalog
Number 1492-IFM40F IFM to a Catalog Number 1794-IB16 I/O module.

The I/O module-ready cables have a 37- or 62-pin D-shell connector on


one end to mate with the Cat. No. 1794-TB37DS or 1794-TB62DS Flex I/O
base and 20 or 40 individually colored #22 AWG conductors (flying leads) at
the other end. These cables provide the convenience of pre-wired connectors
at the I/O module end, while allowing the flexibility to field-wire to standard
terminal blocks of your choice.

I/O Module-Ready Cables for 1794 Flex Digital I/O modules Using Flex Base 1794-TB37DS or -TB62DS
Cable Cat. No. Standard Build-to-Order No. of Uses Flex Mating 1794
Cable Lengths Available Conductors Base I/O Modules Catalog Number
1492-CAB➊G94 1.0, 2.5, 5.0 m Yes 20 1794-TB37DS 1794-IB16, -IB8, -IV16, -OB16, -OB16P, -OB8, –
OB8EP, -OV16, -OV16P,-OW8, -IB10XOB8
1492-CAB➊H94 1.0, 2.5, 5.0 m Yes 40 1794-TB62DS 1794-IB16D, -IB32, -OB32P, -IB16XOB16P
➊ Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m,
and 050 = 5.0 m). Example: Catalog Number 1492-CAB050G94 is for a 5.0 m cable.

Publication 1492-TD008D-EN-P - January 2009


58 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Pre-Wired Cable, Analog, and Specialty IFMs for Bulletin 1794 Analog I/O Modules
Description of AIFM Cat. No. for Wiring Cat. No. for Wiring System Cat. No. for Compatible I/O Module Catalog
System Module with Module with Removable Screw Style (N) and Push- Number 1794-… ➊
Fixed Terminal Block Terminal Block Socket in Style (P) RTB Plug ➌

IF2X0F2I
Assembly (order plugs

IE4X0E2
separately

0F4I
IF4I

0E4
IE8
Feed-through
4-channel input, output or 2 in/2 out combination with 3 1492-AIFM4-3 1492-RAIFM4-3 1492-RTB8✪ — — — — — —
terminal/channel
6-channel isolated with 3...4 terminals/channel 1492-AIFM6S-3 1492-RAIFM6S-3 1492-RTB12✪ — — — — — —

8-channel differential 16-channel single-ended with 3 1492-AIFM8-3 1492-RAIFM8-3 1492-RTB16✪ Z94 Z94 Z94 Z94 Z94 Z94
terminals/channel
Thermocouple
6-channel with 3 terminals/channel ➋ 1492-AIFM6TC-3 — — — — — — — —
Fusible
4-channel with 24V DC blown fuse indicators, test 1492-AIFM4I-F-5 — — — — — — — —
points, 5 terminals/input
2-channel with 24V DC blown fuse indicators, test 1492-AIFM4C-F-5 — — — — — — — —
points, 5 terminals/input, 3 terminals/output
8-channel input with 24V DC blown fuse indicators, 5 1492-AIFM8-F-5 — — Z94 Z94 Z94 Z94 — —
terminals/channel
16-channel input with 24V DC blown fuse indicators, 3 1492-AIFM16-F-3 — — — — — — — —
terminals/channel
16-channel input with 24V DC blown fuse indicators, 5 1492-AIFM16-F-5 — — — — — — — —
terminals/channel
4-input/4-output channel with 8 fuses and 24V blown 1492-AIFMMQS — — — — — — — —
fuse indicators
➊ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-ACAB010Z94 is for a 1.0 m cable, and the suffix Z94.
➋ Cannot be used with 1794 I/0.
➌ Order plugs separately (two plugs per catalog number). Plugs are available in screw style and push in style terminal types. To order, replace the ✪ in the catalog number
with the code for the desired terminal style. The code for screw style is N and the code for push in style is P. The number (i.e, 20) in the cat. no. indicates the number of
connections/pole.

These pre-wired cables have a wiring arm on one end to connect to the front
of a Bulletin 1794 analog I/O module and a connector on the other end to
plug into a 15- or 25-pin D-shell terminal AIFM. You must first select the
AIFM from the preceding selection table

Pre-Wired Cables for 1794 Flex Analog I/O modules Using Flex Base 1794-TB37DS or -TB62DS

Cable Cat. No. Standard Cable Build-to-Order No. of Uses Flex Mating 1794
Lengths Available Conductors Base I/O Modules Catalog Number
1492-ACAB➊Z94 0.5, 1.0, 2.5, 5.0 m Yes 20 1794-TB37DS 1794-IE8, -IF4I, -OE4, -IE4XOE2, -IF2XOF2I

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-ACAB050Z94 is for a 5.0 m cable, and the suffix Z94.

Note: Footnotes are on the following page.


Publication 1492-TD008D-EN-P - January 2009
Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 59

Using Bulletin 1771 Selection Tables to Make Valid 1492 Wiring


System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
1. Find the appropriate table based on the catalog number of the 1771
I/O module.
2. Find the column in the selected table for the 1771 I/O module.
3. Follow the column down to determine which Wiring System Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the Wiring System Module is not compatible with the
I/O module. NOTE: The letter codes designate the compatible 1492
cable for that 1771 I/O and Wiring System Module combination.
4. Select the desired Wiring System Module.
5. Configure the cable catalog number using 1492-CABLE➊ (for digital
cables) or 1492-ACABLE➊ (for analog cables). See footnote ➊ on
pages 62 and 64.

Bulletin 1771 PLC-5 IFMs and Cables

IFMs for Bulletin 1771 Digital 8-Point and 16-Point I/O Modules
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1771-…
System Module with System Module with
Fixed Terminal Block Removable Terminal
Block Socket

OND➊
OAD➊

OBD➊

OMD
OGD
Assembly (order plugs

IMD

IND
IAD

IBD

IGD
ICD
IA2

IN
IA

IB

IH
separately

IT
Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F➐ — — F — F F F F — — F — F,FF F,FF F F F,FF
Narrow standard 132V AC/DC Max. 1492-IFM20FN 1492-RIFM20FN➑ — — F — F F F — — — F — F,FF F,FF F — F,FF
Extra terminals (2 per I/O) 264V AC/DC Max. 1492-IFM20F-2 1492-RIFM20F-2➐ — — F — F F F F — — F — F,FF F,FF F F F,FF
3-wire sensor type input devices 132V AC/DC 1492-IFM20F-3 — — — F — F F F — — — F — — — — — —
Max.
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM20D24 — — — — — F F — — — — F — F,FF F,FF — — F,FF
Narrow standard with 24V AC/DC LEDs 1492-IFM20D24N — — — — — F F — — — — F — F,FF F,FF — — F,FF
Standard with 120V AC/DC LEDs 1492-IFM20D120➍ — — — F — — — — — — — — — — — — — —
Narrow standard with 120V AC LEDs 1492-IFM20D120N — — — F — — — — — — — — — F,FF — — — —
24V AC/DC LEDs and extra terminals for outputs 1492-IFM20D24-2 — — — — — — — — — — — — — F,FF F,FF — — F,FF
24V AC/DC LEDs and extra terminals for inputs 1492-IFM20D24A-2 — — — — — F F — — — — F — — — — — —
120V AC LEDs and extra terminals for outputs 1492-IFM20D120-2 — — — — — — — — — — — — — F,FF — — — —
120V AC LEDs and extra terminals for inputs 1492-IFM20D120A-2 — — — F — — — — — — — — — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM20D24-3 — — — — — F F — — — — — — — — — — —
8 Individually isolated with 24/48V AC/DC LEDs 1492-IFM20DS24-4 — — — — — — — — — — — — — — — — — —
and 4 terminals/output
8 Individually isolated with 120V AC LEDs and 1492-IFM20DS120-4 — — — — — — — — — — — — — — — — — —
4 terminals/output
240V AC LEDs and extra terminals for outputs 1492-IFM20D240-2 — — — — — — — — — — — — — — — — F —
240V AC LEDs and extra terminals for inputs 1492-IFM20D240A-2 — — — — — — — — F — — — — — — — — —
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM20F-F-2 1492-RIFM20F-F-2➐ — — — — — — — — — — — — F F — — F
Extra terminals with 24V AC/DC blown fuse LED 1492-IFM20F-F24-2 1492-RIFM20F-F24-2➐ — — — — — — — — — — — — F F — — F
indicators
Extra terminals with 120V AC/DC blown fuse 1492-IFM20F-F120-2 1492-RIFM20F-F120-2➐ — — — — — — — — — — — — F — — — —
LED indicators
Extra terminals with 240V AC/DC blown fuse 1492-IFM20F-F240-2 — — — — — — — — — — — — — — — — F —
LED indicators
Extra terminals with 24V AC/DC blown fuse LED 1492-IFM20F-F24A-2 1492-RIFM20F-F24A-2➐ — — — — F F — — — — F — — — — — —
indicators
Extra terminals with 120V AC/DC blown fuse 1492-IFM20F-F120A-2 1492-RIFM20F-F120A-2➐ — — F — — — — — — — — — — — — — —
LED indicators

Publication 1492-TD008D-EN-P - January 2009


60 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

IFMs for Bulletin 1771 Digital 8-Point and 16-Point I/O Modules (Continued)
Description of 20-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1771-…
System Module with System Module with
Fixed Terminal Block Removable Terminal
Block Socket

OND➊
OAD➊

OBD➊

OMD
OGD
Assembly (order plugs

IMD

IND
IAD

IBD

IGD
ICD
IA2

IN
IA

IB

IH
separately

IT
8 Individually isolated 120V AC/DC with extra 1492-IFM20F-FS-2 — — — — — — — — — — — — — — — — — —
terminals for outputs
8 Individually isolated with extra terminals and 1492-IFM20F-FS24-2 — — — — — — — — — — — — — — — — — —
24V AC/DC blown fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS24A-4 — — — — T — — — — T T — T — — — — —
four terminals/input and 24V AC/DC blown fuse
LED indicators
8 Individually isolated with extra terminals 1492-IFM20F-FS120-2 — — — — — — — — — — — — — — — — — —
output, and 120V AC/DC blown fuse LED
indicators
8 Individually isolated with 1492-IFM20F-FS120-4 — — — — — — — — — — — — — — — — — —
four terminals/output and 120V AC/DC blown
fuse LED indicators
Two 4-point isolated groups with 1492-IFM20F-FS120A-4 — T T — — — — — — — — — — — — — — —
four terminals/input and 120V AC/DC blown
fuse indicators
8 Individually isolated with 4 terminals/output 1492-IFM20F-FS240-4 — — — — — — — — — — — — — — — — — —
and 240V AC/DC blown fuse indicators
Relay Master (LED Indicating) ➎➏
20-pin master with eight (8) 24V DC relays 1492-XIM2024-8R — — — — — — — — — — — — — — F,FF — — —
20-pin master with eight (8) 120V AC relays 1492-XIM20120-8R — — — — — — — — — — — — — F,FF — — — —
20-pin master with sixteen (16) 120V AC relays 1492-XIM20120-16R — — — — — — — — — — — — — F,FF — — — —
20-pin master with sixteen (16) 120V AC relays 1492-XIM20120-16RF — — — — — — — — — — — — — F,FF — — — —
with fusing
20-pin master relay with sixteen (16) 24V DC 1492-XIM2024-16R — — — — — — — — — — — — — — F,F — — —
relays
20-pin master with sixteen (16) 24V DC relays 1492-XIM2024-16RF — — — — — — — — — — — — — — F,F — — —
with fusing
Relay Expander (LED Indicating) ➎➏
Expander with eight (8) 24V DC relays 1492-XIM24-8R — — — — — — — — — — — — — — ➋ — — —
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — — — — — — — — — ➋ — — — —
Fusible Expander
8-channel expander with 24V DC blown fuse 1492-XIMF-F24-2 — — — — — — — — — — — — — — ➋ — — —
indicators
8-channel expander with 120V AC blown fuse 1492-XIMF-F120-2 — — — — — — — — — — — — — ➋ — — — —
indicators
Feed-through Expander
Expander with eight (8) feed-through channels 1492-XIMF-2 — — — — — — — — — — — — — ➋ ➋ — — —
➊ Either F or FF.
➋ One expander is connected to a master to provide a total of 16 outputs. An extender cable is included with each expander to connect it to the master.
➌ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050A is for a 5.0 m cable, and the letter A.
➍ This IFM is not recommended for use with PLC I/O modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-IFM20D120A-2 for
inputs. Use 1492-IFM20D120-2 for outputs.
➎ The voltage rating is relay control/coil voltage. For Relay Contact Ratings, refer to page 192.
➏ The LED indicates the PLC output status.
➐ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P. ORDER PLUGS SEPARATELY.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB10N (screw style terminals) or 1492-RTB10P. ORDER PLUGS SEPARATELY.

Bulletin 1771 PLC-5 IFMs and Cables, Continued

IFMs for Bulletin 1771 Digital 16-Point Isolated and 32-Point I/O Modules ➌
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1771-…
System Module with System Module with
scOM16➍

Fixed Terminal Block Removable Terminal


scIM16➍

Block Socket Assembly


OWNA
OW16

OWN
OD16

OQ16

(order plugs separately


OAN

OBN

OVN
ODD
ID16

IQ16
IAN

IBN

IVN

Feed-through
Standard 132V AC/DC Max. 1492-IFM40F 1492-RIFM40F➑ J J M M K L L M M M L R L L — M
Extra terminals (2 per I/O) 132V AC/DC Max. 1492-IFM40F-2 1492-RIFM40F-2➑ J J — — K L L — — — L R L L — —

Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 61

IFMs for Bulletin 1771 Digital 16-Point Isolated and 32-Point I/O Modules (Continued)➌
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1771-…
System Module with System Module with

scOM16➍
Fixed Terminal Block Removable Terminal

scIM16➍
Block Socket Assembly

OWNA
OW16

OWN
OD16

OQ16
(order plugs separately

OAN

OBN

OVN
ODD
ID16

IQ16
IAN

IBN

IVN
3-wire sensor type input devices 60V AC/DC 1492-IFM40F-3 — — J — — K — — — — — — — — — — —
Max.
LED Indicating
Standard with 24V AC/DC LEDs 1492-IFM40D24 1492-RIFM40D24➑ — J — — K — L — — — L — L L — —
24V AC/DC LEDs and extra terminals for 1492-IFM40D24-2 — — — — — — — L — — — L — L L — —
outputs
24V AC/DC LEDs and extra terminals for 1492-IFM40D24A-2 1492-RIFM40D24A-2➑ — J — — K — — — — — — — — — — —
inputs
120V AC LEDs and extra terminals for outputs 1492-IFM40D120-2 — — — — — — L — — — — — — L L — —
120V AC LEDs and extra terminals for inputs 1492-IFM40D120A-2 — J — — — — — — — — — — — — — — —
3-wire sensor with 24V AC/DC LEDs 1492-IFM40D24-3 — — J — — K — — — — — — — — — — —
16 Individually isolated with 24/48V AC/DC 1492-IFM40DS24-4 — — — — — — — — — — M — — — — — —
LEDs and 4 terminals/output
16 Individually isolated with 24V AC/DC LEDs 1492-IFM40DS24A-4 — — — — M — — — — — — — — — — — —
and 4 terminals/input
16 Individually isolated with 120V AC LEDs 1492-IFM40DS120-4 — — — — — — — — M M — — — — — — M
and 4 terminals/output
16 Individually isolated with 120V AC LEDs 1492-IFM40DS120A-4 — — — M — — — — — — — — — — — — —
and 4 terminals/input
16 Individually isolated with 240V AC LEDs 1492-IFM40DS240A-4 — — — — — — — — — — — — — — — M —
and 4 terminals/input
Fusible
120V AC/DC with extra terminals for outputs 1492-IFM40F-F-2 — — — — — — L L — — — L — L L — —
Extra terminals with 24V AC/DC blown fuse 1492-IFM40F-F24-2 1492-RIFM40F-F24-2➑ — — — — — — L — — — L — L L — —
indicators for outputs
Extra terminals with 120V AC/DC blown fuse 1492-IFM40F-F120-2 — — — — — — L — — — — — — L L — —
indicators for outputs
16 Individually isolated with extra terminals 1492-IFM40F-FS-2 — — — — — — — — M M M — R71 — — M
for 120V AC DC outputs ➎
Individually isolated with extra terminals and 1492-IFM40F-FS24-2 — — — — — — — — — — M — R71 — — — —
24V AC/DC blown fuse indicators for outputs ➎
16 Individually isolated with 24V AC/DC 1492-IFM40F-FS24-4 — — — — — — — — — — M — — — — — —
blown fuse indicators and 4 terminals/output
16 Individually isolated 240V AC/DC with 4 1492-IFM40F-FS-4 — — — — — — — — — — M — — — — — —
terminals/output
16 Individually isolated with extra terminals 1492-IFM40F-FS120-2 1492-RIFM40F-FS120-2➑ — — — — — — — M M — — R71 — — — M
and 120V AC/DC blown fuse indicators for ➎
outputs
16 Individually isolated with 120V AC/DC 1492-IFM40F-FS120-4 1492-RIFM40F-FS120-4➒ — — — — — — — M M — — — — — — M
blown fuse indicators and 4 terminals/output
16 Individually isolated with 240V AC/DC 1492-IFM40F-FS240-4 — — — — — — — — — — — — — — — — M
blown fuse indicators and 4 terminals/output
16 Individually isolated with 24V AC/DC 1492-IFM40F-FS24A-4 — — — — M — — — — — — — — — — — —
blown fuse indicators and 4 terminals/input
16 Individually isolated with 120V AC/DC 1492-IFM40F-FSA-4 — — — M M — — — — — — — — — — — —
4 terminals/input
16 Individually isolated with 120V AC/DC 1492-IFM40F-FS120A-4 1492-RIFM40F-FS120A- — — M — — — — — — — — — — — — —
blown fuse indicators and 4 terminals/input 4➒
16 Individually isolated with 240 VAC/DC 1492-IFM40F-FS240A-4 — — — — — — — — — — — — — — — — —
blown fuse indicators and 4 terminals/input
Relay Master (LED Indicating) ➏➐
40-pin master with eight (8) 24V DC relays 1492-XIM4024-8R — — — — — — — L — — — — — — — — —
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16R 1492-RXIM4024-16R➓ — — — — — — L — — — — — — — — —
40-pin master with sixteen (16) 24V DC relays 1492-XIM4024-16RF — — — — — — — L — — — — — — — — —
with fusing
Relay Expander (LED Indicating) ➏➐
Expander with eight (8) 24V DC relays 1492-XIM24-8R 1492-RXIM24-8R✪ — — — — — — ➊ — — — — — — — — —
Expander with eight (8) 120V AC relays 1492-XIM120-8R — — — — — — — — — — — — — — — — —
Fusible Expander
8-channel expander with 24V DC blown fuse 1492-XIMF-F24-2 — — — — — — — ➊ — — — — — — — — —
indicators

Publication 1492-TD008D-EN-P - January 2009


62 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

IFMs for Bulletin 1771 Digital 16-Point Isolated and 32-Point I/O Modules (Continued)➌
Description of 40-PIN IFM Cat. No. for Wiring Cat. No. for Wiring I/O Module Catalog Number 1771-…
System Module with System Module with

scOM16➍
Fixed Terminal Block Removable Terminal

scIM16➍
Block Socket Assembly

OWNA
OW16

OWN
OD16

OQ16
(order plugs separately

OAN

OBN

OVN
ODD
ID16

IQ16
IAN

IBN

IVN
8-channel expander with 120V AC blown fuse 1492-XIMF-F120-2 — — — — — — — — — — — — — — — — —
indicators
Expander with sixteen (16) 24V DC relays with 1492-XIM24-16RF — — — — — — — ➋ — — — — — — — — —
fusing
Feed through Expander
Expander with eight (8) feed-through 1492-XIMF-2 — — — — — — — ➊ — — — — — — — — —
channels

➊ Two or three expanders are connected to a master to provide a total of 32 outputs max (depends on PLC module). An extender cable is included with each expander to
connect it to the master.
➋ One 1492-XIM24-16RF is to be used with one 1492-XIM4024-16R AND 1492-XIM4024-16RF master (32 PT. only).
➌ Cables are available in standard lengths of 0.5 m 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE025J is for a 2.5 m cable, and the letter J.
➍ For information concerning this I/O module contact Spectrum Controls (phone: 425-641-9473 or www.spectrumcontrols.com).
➎ Cable Catalog Number 1492-CAB➌ has the N.O. contacts only connected.
➏ The voltage rating is relay control/coil voltage. For Relay Contact Ratings, refer to page 192.
➐ The LED indicates the PLC output status.
➑ Compatible Removable Terminal Block (RTB) plug; 1492-RTB20N (screw style terminals) or 1492-RTB20P. ORDER PLUGS SEPARATELY.
➒ Compatible Removable Terminal Block (RTB) plug; 1492-RTB17N (screw style terminals) or 1492-RTB17P. ORDER PLUGS SEPARATELY.
➓ Compatible Removable Terminal Block (RTB) plug; 1492-RTB14N (screw style terminals) or 1492-RTB14P. ORDER PLUGS SEPARATELY.
✪ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P. ORDER PLUGS SEPARATELY.

Bulletin 1771 PLC-5 IFMs and Cables, Continued

These pre-wired cables have a wiring arm on one end to connect to the front
of a Bulletin 1771 digital I/O module and a connector on the other end to
plug into a 20- or 40-terminal IFM/XIM. You must first select the IFM/XIM
from one of the preceding selection tables

Pre-Wired Cables for Bulletin 1771 Digital I/O Modules


Cable Cat. No. Standard Cable Build-to-Order No. of Mating 1771
Lengths Available Conductors I/O Modules Catalog Number
1492-CABLE➊F 0.5, 1.0, 2.5, 5.0 m Yes 20 1771-IAD, -IBD, -ICD, -IGD, -IND, -OAD, -OBD,
-OGD, -OMD, -OND, -IMD
1492-CABLE➊FF 0.5, 1.0, 2.5, 5.0 m Yes 20 1771-OAD, -OBD, -OND
1492-CABLE➊J 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-IAN, -IBN
1492-CABLE➊K 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-IVN
1492-CABLE➊L 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-OAN, -OBN, -OVN, -OWN, -OWNA
1492-CABLE➊M 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-ID16, -IQ16, -OD16, -ODD, -OQ16,
-SCIM16, -SCOM16
1492-CABLE➊R 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-OW16
1492-CAB➊R71➋ 0.5, 1.0, 2.5, 5.0 m Yes 40 1771-OW16
1492-CABLE➊T 0.5, 1.0, 2.5, 5.0 m Yes 20 1771-IA, -IA2, -IB, -IH, -IN, -IT
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CABLE005M is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM40F IFM to a Catalog Number 1771-ODD I/O module.
➋ Cable Catalog Number 1492-CAB➊R71 has only the N.O. contacts connected.

Note: Footnotes are on the following page.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 63

The I/O module-ready cables have a wiring arm on one end to plug onto
the front of a Bulletin 1771 I/O module and 20 or 40 individually colored
#18 AWG conductors on the other end. These cables provide the convenience
of pre-wired connections at the I/O module end, while still allowing the
flexibility to field-wire to standard terminal blocks of your choice.

I/O Module-Ready Cables for 1771 Digital I/O Modules ➎

Cable Cat. No. Standard Build-to-Order No. of Mating 1771


Cable Lengths Available Conductors I/O Modules Catalog Number
1492-CABLE➌WA 1.0, 2.5, 5.0 m Yes 12 1771-IA, -IA2, -IB, -IC, -IH, -IM, -IN, -IT, -IV, -OA, -OB, -OC, -OM,
-ON, -OP
1492-CABLE➌WD 1.0, 2.5, 5.0 m Yes 12 1771-ID, -ID01, -OD, -ODZ, -OR, -OW, -OYL, -OZL
1492-CABLE➌WH 1.0, 2.5, 5.0 m Yes 20 1771-IAD, -IBD, -ICD, -IGD, -IMD, -IND, -OAD, -OBD, -OGD,
-OMD, -OND
1492-CABLE➌WHF 1.0, 2.5, 5.0 m Yes 20 1771-IBD ➍, -OAD ➍, -OBD ➍, -OMD ➍, -OND ➍
1492-CABLE➌WN 1.0, 2.5, 5.0 m Yes 40 1771-IAN, -IBN, -ID16, -IQ16, -IVN, -OAN, -OBN, -OD16, -ODD,
-OQ16, -OVN, -OW16, -OWN, -OWNA
➌ Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m,
and 050 = 5.0 m). Example: Catalog Number 1492-CABLE050WN is for a 5.0 m cable with a pre-wired Catalog Number 1771-WN wiring arm on one end.
➍ Includes an optional 3 A fuse in the Wiring Arm for 1771 PLC mating I/O Modules.
➎ Discrete I/O ready cables should not be used with PLC analog I/O modules as a cable shield and drain wires are not provided.

Bulletin 1771 PLC-5 AIFMs and Cables

IFMs for Bulletin 1771 Analog I/O Modules


Description of AIFM Catalog Number Catalog Number I/O Module Catalog Number 1771-…
for Wiring for Wiring
IFE (Single-Ended)

System Module System Module IFF (Single-Ended)


IFE (Differential)

IFF (Differential)

with Fixed with Removable


Terminal Block Terminal Block
Socket Assembly
(order plugs
separately
OFE1

OFE2

OFE3
IR
IL

Feed-through
4-channel input, output or 2 in/2 out combination with 1492-AIFM4-3 1492-RAIFM4-3➌ — — — — — — G G G
3 terminals/channel
6-channel isolated with 3…4 terminals/channel 1492-AIFM6S-3 1492-RAIFM6S-3➍ — — — — — J — — —
8-channel differential 16-channel single-ended with 1492-AIFM8-3 1492-RAIFM8-3➎ E F E F H — — — —
3 terminals/channel
Thermocouple
6-channel with 3 terminals/channel➋ 1492-AIFM6TC-3 — — — — — — — — — —
Fusible
4-channel with 24V DC blown fuse indicators, test 1492-AIFM4I-F-5 — — — — — — — — — —
points, 5 terminals/input
2-channel/input, 2-channel/output with 24V DC blown 1492-AIFM4C-F-5 — — — — — — — — — —
fuse indicators, test points, 5 terminals/input,
3 terminals/
output
8-channel Input with 24V DC blown fuse indicators, 1492-AIFM8-F-5 — E — E — — — — — —
5 terminals/channel

Publication 1492-TD008D-EN-P - January 2009


64 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

IFMs for Bulletin 1771 Analog I/O Modules (Continued)


Description of AIFM Catalog Number Catalog Number I/O Module Catalog Number 1771-…
for Wiring for Wiring

IFE (Single-Ended)

IFF (Single-Ended)
System Module System Module

IFE (Differential)

IFF (Differential)
with Fixed with Removable
Terminal Block Terminal Block
Socket Assembly
(order plugs
separately

OFE1

OFE2

OFE3
IR
IL
16-channel Input with 24V DC blown fuse indicators, 1492-AIFM16-F-3 — — F — F — — — — —
3 terminals/channel
16-channel Input with 24V DC blown fuse indicators, 1492-AIFM16-F-5 — — F — F — — — — —
5 terminals/channel
4-input /4-output channel with 8 fuses and 24V blown 1492-AIFMQS — — — — — — — — — —
fuse indicators

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number 005 = 0.5 m
(010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-ACABLE025H is for a 2.5 m cable, and the letter H.
➋ Cannot be used with 1771 I/O.
➌ Compatible Removable Terminal Block (RTB) plug; 1492-RTB8N (screw style terminals) or 1492-RTB8P. ORDER PLUGS SEPARATELY.
➍ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P. ORDER PLUGS SEPARATELY.
➎ Compatible Removable Terminal Block (RTB) plug; 1492-RTB16N (screw style terminals) or 1492-RTB16P. ORDER PLUGS SEPARATELY.

These pre-wired cables have a wiring arm on one end to connect to the front
of a Bulletin 1771 analog I/O module and a connector on the other end to
plug into a 15- or 25-pin D-shell terminal AIFM. You must first select the
AIFM from the preceding selection table
.
Pre-Wired Cables for Bulletin 1771 Analog I/O Modules
Cable Catalog Standard Cable Lengths Build-to-Order Available AIFM Connector Mating 1771 I/O Modules
Number
1492-ACABLE➊E 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1771-IFE, -IFF Differential
1492-ACABLE➊F 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1771-IFE, -IFF Single-Ended
1492-ACABLE➊G 0.5, 1.0, 2.5, 5.0 m Yes 15-pin D-shell 1771-OFE1, -OFE2, -OFE3
1492-ACABLE➊H 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1771-IL
1492-ACABLE➊J 0.5, 1.0, 2.5, 5.0 m Yes 25-pin D-shell 1771-IR
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (005 = 0.5 m,
010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-ACABLE005E is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-AIFM8-3 IFM to a Catalog Number 1771-IFE I/O module. Build-to-order lengths are also available.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 65

Selection Tables, IFM-Ready I/O Cables


Continued
IFM-ready cables have a cable connector on one end to attach to the IFM and
either 20 or 40 individually colored conductors on the other end (CABLE➊P
and CABLE➊Q, respectively). These cables allow the IFM to be used in
specialty applications that require a custom connection.

IFM-Ready I/O Cable

Cable Standard Cable Insulation No. Conductor Nominal Outer Current/ Compatible
Catalog Lengths Rating Conductors Size Diameter Conductor IFM Catalog
Number Numbers
1492-CABLE➊P 1.0, 2.5, 5.0 m 300V, 80°C 20 22 AWG 9 mm (0.36 in.) 2A 1492-IFM20…,
1492-XIM20…
1492-CABLE➊Q 1.0, 2.5, 5.0 m 300V, 80°C 40 22 AWG 11.7 mm (0.46 in.) 2A 1492-IFM40…,
1492-XIM40…

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m).
Example: Catalog Number 1492-CABLE025P is for a 2.5 m, 20 conductor IFM-ready cable. Also refer to Build-to-Order Length Cables on page 65.

Build-to-Order Length Cables

Build-to-Order Length Cables

Cable Lengths Increment Size Cable Length Codes Example Catalog Number
0.1…2.0 m 0.1 m 001…020 1492-CABLE015A (1.5 m cable)
2.0…10.0 m 0.5 m 020…100 1492-CABLE075P (7.5 m cable)
10.0…99.0 m 1.0 m 100…990 1492-CABLE150RTBB (15.0 m cable)

All Bulletin 1492 cables are available in build-to-order lengths. Consult your
distributor for availability.

Publication 1492-TD008D-EN-P - January 2009


66 Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems

Selection Tables, Using PowerFlex 700H & 700S Drive Selection Tables to Make
Continued Valid 1492 Wiring System Module Catalog Numbers

Follow these steps when using the selection tables to make valid catalog
numbers:
1. Find the appropriate table based on the PowerFlex 700H or 700 S
control I/O module.
2. Find the column in the selected table for the I/O module.
3. Follow the column down to determine which Wiring System Modules
are compatible with the I/O module as indicated by letter code. If there
is no letter code, the Wiring System Module is not compatible with the
I/O module. NOTE: The letter codes designate the compatible 1492
cable for that PowerFlex 700H or 700S control I/O and Wiring System
Module combination.
4. Select the desired Wiring System Module.
5. Configure the cable catalog number using 1492-CAB➊ (for digital
cables) or 1492-ACAB➊ (for analog cables). See footnote ➊ on
pages 50 and 53.

PowerFlex 700H and 700S Drive IFMs, AIFMs and Cables

PowerFlex 700H and 700S drive Digital Control I/O


Description of 20-PIN IFM Catalog Number Catalog Number for 700H Drive 700S Drive I/O
for Wiring System Wiring System Module I/O Module Module
Module with with Removable Terminal

20C-DO1 & 20CDA1-A

20C-DO1 & 20CDA1-B


Fixed Terminal Block Socket Assembly
Block (order plugs separately)

TB2
Feed-through
Standard 264V AC/DC Max. 1492-IFM20F 1492-RIFM20F➊ A7H B7H A7S
Narrow standard 132V AC/DC Max. 1492-IFM20FN 1492-RIFM20FN➋ A7H B7H A7S
Extra terminals (2 per I/O) 264V AC/DC Max. 1492-IFM20F-2 1492-RIFM20F-2➊ A7H B7H A7S
➊ Compatible Removable Terminal Block (RTB plug; 1492-RTB20N (screwstyle terminals) or 1492-RTB20P. ORDER
PLUGS SEPARATELY.
➋ Compatible Removable Terminal Block (RTB plug; 1492-RTB10N (screwstyle terminals) or 1492-RTB10P. ORDER
PLUGS SEPARATELY.

These pre-wired cables have a pre-wired removable terminal block (RTB) on


one end to connect to the PowerFlex 700H or PowerFlex 700S drive digital
control I/O board terminal. There is a second connector on the other end to
plug into a 20-pin IFM. You must first select the IFM from the table below.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller and PowerFlex® Drive Wiring Systems 67

Pre-Wired cables for PowerFlex 700H and 700S Drive Digital I/O
Cable Catalog Standard Cable Length Build-to-Order Number of Mating PowerFlex Control
Number Available Conductors Board Cat. No or Terminal
1492-CAB➊A7H 0.5, 1.0, 2.5, 5.0 m Yes 20 20C-DA1-A and 20C-DO1
1492-CAB➊B7H 0.5, 1.0, 2.5, 5.0 m Yes 20 20C-DA1-B and 20C-DO1
1492-CAB➊A7S 0.5, 1.0, 2.5, 5.0 m Yes 20 Terminal TB2
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the
desired cable length into the catalog number (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m).
Example: Catalog Number 1492-CAB005A7H is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-IFM20F IFM to a PowerFlex 700H drive 20C-DO1 and 20C-DA1-A module.

PowerFlex 700H and 700S Drive Analog Control I/O


Description of Analog IFM Catalog Number for Catalog Number for 700H 700S Drive I/O
Wiring System Wiring System Module Drive I/O Module
Module with Fixed with Removable Module
Terminal Block Terminal Block Socket

20C-DA1-A or 20C-DA1-B
Assembly (order plugs
separately)

TB1 (Pins 13…24)


TB1 (Pins 1…12)
Feed-through
6-channel isolated with 3…4 terminals/channel 1492-AIFM6S-3 1492-RIFM6S-3➊ Z7H Z7S
2-channel counter inputs with 4 output points 1492-AIFMCE4 — — — X7S
2-channel fused counter inputs with 4 fused 1492-AIFMCE4-F — — — X7S
output points
➊ Compatible Removable Terminal Block (RTB) plug; 1492-RTB12N (screw style terminals) or 1492-RTB12P (push-
in style terminals, available August 2007). ORDER PLUGS SEPARATELY.These pre-wired cables have a pre-
wired removable terminal block (RTB) on one end to connect to the PowerFlex 700H or PowerFlex 700S drive
analog control I/O board terminal. There is a 25-pin D-shell connector on the other end to plug into the mating
AIFM module terminal. You must first select the AIFM from the table below.

Pre-Wired Cables for PowerFlex 700H and 700S Drive Analog I/O
Cable Catalog Standard Cable Length Build-to-Order Number of Mating PowerFlex Control
Number Available Conductors Board Cat. No or Terminal
1492-ACAB➊Z7H 0.5, 1.0, 2.5, 5.0 m Yes 25-Pin D-Shell 20C-DA1-A or 20C-DA1-B I/O board
1492-ACAB➊Z7S 0.5, 1.0, 2.5, 5.0 m Yes 25-Pin D-Shell Terminal TB1 (DINS 1…12)
1492ACAB➊Z7S 0.5, 1.0, 2.5, 5.0 m Yes 25-Pin D-Shell Terminal TB2 (DINS 13…24)
➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the
desired cable length into the catalog number (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m).
Example: Catalog Number 1492-ACAB005Z7S is for a 0.5 m cable that could be used to connect a Catalog
Number 1492-AIFM6S-3 analog IFM to a PowerFlex 700S drive analog terminal I/O.

Publication 1492-TD008D-EN-P - January 2009


68 Digital/Analog Programmable Controller Wiring Systems

Digital IFM Specifications


Digital/Analog Programmable Controller Wiring Systems

IFM Page No. for Page No. for IFM Page No. for Page No. for IFM Page No. for Page No. for
Catalog Number Application Specifications Catalog Number Application Specifications Catalog Number Application Specifications
Notes and Notes and Notes and
Pinout Pinout Pinout
1492-IFM20F, -RIFM20F 70 187 1492-IFM20D240A-2 76 188 1492-IFM40DS120A-4 100 186
1492-IFM20F-2, -RIFM20F-2 71 187 1492-IFM20F-F240-2 82 188 1492-IFM40F-F120-2 106 187
1492-IFM20F-3 71 187 1492-IFM20F-FS240-4 88 188 1492-IFM40F-FS120-2, 110 187
-RIFM40F-FS120-2
1492-IFM20FN, -RIFM20FN 70 187 1492-IFM20DS24-4 78 188 1492-IFM40F-FS120-4, 111 187
-RIFM40F-FS120-4
— — — 1492-IFM20F-F-2, 80 188 1492-IFM40F-FS120A-4, 114 187
-RIFM20F-F-2 -RIFM40F-FS120A-4
1492-IFM20D24N 72 187 1492-IFM20F-FS-2 83 188 1492-IFM40DS240A-4 101 186
1492-IFM20D24-2 74 187 1492-IFM40F, -RIFM40F 89 188 1492-IFM40F-FS240-4 112 187
1492-IFM20D24A-2 74 187 1492-IFM40F-2, - 89 188 1492-XIM4024-16R, 123 188
RIFM40F-2 -RXIM4024-16R
1492-IFM20D24-3 77 187 1492-IFM40F-F-2 102 188 1492-XIM4024-16RF 126 188
1492-IFM20F-F24-2, 80 187 1492-IFM40F-FS-2 107 188 1492-XIM4024-8R 122 188
-RIFM20F-F24-2
1492-IFM20F-F24A-2, 81 187 1492-IFM40F-FSA-4 114 188 1492-XIM2024-8R 115 188
-RIFM20F-F24A-2
1492-IFM20F-FS24-2 83 187 1492-IFM40F-FS-4 108 189 1492-XIM2024-16R 118 188
1492-IFM20F-FS24A-4 84 187 1492-IFM40F-3 90 189 1492-XIM2024-16RF 119 188
1492-IFM20D120 73 187 1492-IFM40DS24-4 97 189 1492-XIM24-8R, 127 188
-RXIM24-8R
1492-IFM20D120N 73 187 1492-IFM40D24, 91 189 1492-XIM24-16RF 131 188
-RIFM40D24
1492-IFM20D120-2 75 187 1492-IFM40D24-2 92 189 1492-XIMF-F24-2 132 188
1492-IFM20D120A-2 75 187 1492-IFM40D24A-2, 93 189 1492-XIM20120-16R 120 188
-RIFM40D24A-2
1492-IFM20DS120-4 79 187 1492-IFM40D24-3 96 189 1492-XIM20120-16RF 121 188
1492-IFM20F-F120-2, 81 187 1492-IFM40DS24A-4 98 189 1492-XIM20120-8R 117 188
-RIFM20F-F120-2
1492-IFM20F-F120A-2, 82 187 1492-IFM40F-F24-2, 103 189 1492-XIM120-8R 129 188
-RIFM20F-F120A-2 -RIFM40F-F24-2
1492-IFM20F-FS120-2, 85 187 1492-IFM40F-FS24-2 107 189 1492-XIMF-F120-2 134 188
1492-IFM20F-FS120-4 86 187 1492-IFM40D120A-2 95 189 1492-XIMF-2 136 188
1492-IFM20F-FS120A-4 87 187 1492-IFM40D120-2 94 189 — — —
1492-IFM20D240-2 76 187 1492-IFM40DS120-4 99 189 — — —

For all IFM dimensions, refer to page 180.


For general Adhesive Label Card information, refer to page 181.
For Field-Side Wiring Diagrams, refer to the Wiring System web page at
http://www.ab.com/catalogs/RAISE. Refer to page 186 for specific
platform web site information. Refer to the online documentation for new
product information.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 69

Symbols and Terminal Identification Conventions Used


Throughout the Pinout Section

Fuse and Blown Fuse


Indicator (where applicable)
LED Circuit

LED Indicator

Connector Pin

Field-Side Terminal

N.C./N.O. Relay Contact

~~
Relay Coil Circuit

Publication 1492-TD008D-EN-P - January 2009


70 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F 1492-IFM20FN
1492-RIFM20F 1492-RIFM20FN

Feed-Through Standard 264V AC/DC Max. Feed-Through Narrow Standard 132V AC/DC Max.

Application Notes Application Notes

1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. and current ratings of the IFM.
2. Wiring — Refer to the Label Section on page 181. 2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. Wiring System web site information on page 186.
3. Dimensions — Refer to page 187. 3. Dimensions — Refer to page 187.

Pinout Pinout

1 A1 2 B1
2 A2
3 A3 11 B2

18 A18
18 B9
19 A19
20 A20 20 B10

1 A1

3 A2

10 A9

19 A10

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 71

1492-IFM20F-2 1492-IFM20F-3
1492-RIFM20F-2 Feed-Through 3-Wire Sensor Type Input Devices 132V
Feed-Through Extra Terminals (2 per I/O) 264V AC/DC AC/DC Max.
Max.

Application Notes Application Notes

1. Compatibility — To ensure proper operation


1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage
and current ratings of the IFM.
and current ratings of the IFM.
2. Wiring — Refer to the Label Section on page 181.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
Wiring System web site information on page 186.
3. Isolation — The power busses are connected to
3. Isolation — The power bus is isolated into two
one common (one bus has 17 terminals, and one
groups of 10 terminals. This allows each group of
bus has 18 terminals). All of the input devices used
the I/O devices to reference a different power
must reference the same power source.
source.
4. Dimensions — Refer to page 187.
4. Dimensions — Refer to page 187.

Pinout Pinout
3 C1

1 B1
2 B2
18 C16
3 B3

B1
B2
18 B18
20
19 B19
20 B20

B17
A1 A11
B18
A2 A12

A1
A2
A9 A19
A10 A20

A16
A17
1 A18

Publication 1492-TD008D-EN-P - January 2009


72 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20D24 1492-IFM20D24N
LED Indicating Standard with 24V AC/DC LEDs LED Indicating Narrow Standard with 24V AC/DC LEDs

Application Notes Application Notes


1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across be used (e.g., a 1N4004 diode reverse-wired across
a DC load). a DC load).
2. Wiring — The LEDs are powered from the 2. Wiring — Refer to the Label Section on page 181.
two-position terminal block. Make only one For Field-Side Wiring Diagrams, refer to the
connection to the power source for normal Wiring System web site information on page 186.
operation. Refer to the Label Section on page 181. 3. Isolation — The LEDs are connected to one
For Field-Side Wiring Diagrams, refer to the common. All of the I/O devices must reference
Wiring System web site information on page 186. the same power source.
3. Isolation — The LEDs are broke into two 4. Dimensions — Refer to page 187.
separate groups. Group 1 is commoned at terminal Pinout
“Test 0-7” and Group 2 is commoned at terminal 2 B1
“Test 8-15.”
11 B2
4. Dimensions — Refer to page 187.

Pinout 18 B9

20 B10
1 A1
2 A2
3 A3
1 A1

3 A2
18 A 18
19 A 19
20 A 20
10 A9

19 A10

~~ ~~

LED Circuit
L E D 8 -1 5
L E D 0 -7

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 73

1492-IFM20D120 1492-IFM20D120N
LED Indicating Standard with 120V AC/DC LEDs LED Indicating Narrow Standard with 120V AC LEDs

Application Notes
Application Notes
1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage
and current ratings of the IFM. This IFM is not
and current ratings of the IFM. When this IFM is
recommended for use with input devices or
used with a hard contact (relay) output circuit that
programmable controller output circuits having an
switches an inductive load, surge suppression must
off-state leakage current exceeding 0.5 mA. Use
be used (e.g., a 1N4004 diode reverse-wired across
Cat. No. 1492-IFM20D120N instead, or use Cat.
a DC load).
No. 1492-IFM20D120A-2 for input modules and
Cat. No. 1492-IFM20D120-2 for output modules. 2. Wiring — Refer to the Label Section on page 181.
When this IFM is used with a hard contact (relay) For Field-Side Wiring Diagrams, refer to the
output circuit that switches an inductive load, Wiring System web site information on page 186.
surge suppression must be used (e.g., a 1N4004 3. Isolation — The LEDs are connected to one
diode reverse-wired across a DC load). common. All of the I/O devices must reference
2. Wiring — Refer to the Label Section on page 181. the same power source.
For Field-Side Wiring Diagrams, refer to the 4. Dimensions — Refer to page 187.
Wiring System web site information on page 186. Pinout
3. Isolation — The LEDs are isolated into two 2 B1
groups of eight terminals. This allows each group
11 B2
of the I/O devices to reference a different power
source.
4. Dimensions — Refer to page 187. 18 B9

Pinout 20 B10
1 A1
2 A2
3 A3
1 A1

10 A10 3 A2

11 A11

10 A9

18 A18
19 A10
19 A19
20 A20

LED Circuit
L2 (-)

L2 (-)

Publication 1492-TD008D-EN-P - January 2009


74 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20D24-2 1492-IFM20D24A-2
LED Indicating 24V AC/DC LEDs & Extra Terminals for LED Indicating 24V AC/DC LEDs & Extra Terminals for
Outputs Inputs

Application Notes Application Notes


1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across
be used (e.g., a 1N4004 diode reverse-wired across
a DC load).
a DC load).
2. Wiring — Refer to the Label Section on page 181.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
Wiring System web site information on page 186.
3. Isolation — The power bus and LEDs are
3. Isolation — The power bus comprises
isolated into two groups of 10 terminals (eight
20 terminals connected together. The LEDs are
LEDs). This allows each group of output devices
connected to one common. All of the I/O devices
to reference a different power source.
must reference the same power source.
4. Dimensions — Refer to page 187.
4. Dimensions — Refer to page 187.
Pinout
1 B1
2 B2 Pinout
3 B3
1 B1

10 B10 2 B2

11 B11
3 B3

18 B18
19 B19
20 B20 18 B18

19 B19

20 B20
A1 A11

A2 A12

A1
A9 A19

A10 A20 A2
LED Circuit

LED Circuit A19

A20

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 75

1492-IFM20D120-2 1492-IFM20D120A-2
LED Indicating 120V AC LEDs & Extra Terminals for LED Indicating 120V AC LEDs & Extra Terminals for
Outputs Inputs

Application Notes Application Notes


1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load). be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181. 2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. Wiring System web site information on page 186.
3. Isolation — The power bus and LEDs are 3. Isolation — The power bus comprises
isolated into two groups of 10 terminals (8 LEDs). 20 terminals connected together. The LEDs are
This allows each group of output devices to connected to one common. All of the I/O devices
reference a different power supply. must reference the same power source.
4. Dimensions — Refer to page 187. 4. Dimensions — Refer to page 187.
Pinout Pinout
1 B1
1 B1
2 B2
3 B3
2 B2

10 B10
3 B3
11 B11

18 B18
18 B18
19 B19
20 B20
19 B19

20 B20

A1 A11

A2 A12
A1

A9 A19

LED Circuit A2
A10 A20

A19
LED Circuit

A20

Publication 1492-TD008D-EN-P - January 2009


76 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20D240-2 1492-IFM20D240A-2
LED Indicating 240V AC LEDs & Extra Terminals for LED Indicating 120V AC LEDs & Extra Terminals for
Outputs Inputs

Application Notes Application Notes


1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load). be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181. 2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. Wiring System web site information on page 186.
3. Isolation — The power bus and LEDs are 3. Isolation — The power bus comprises
isolated into two groups of 10 terminals (8 LEDs). 20 terminals connected together. The LEDs are
This allows each group of output devices to connected to one common. All of the I/O devices
reference a different power supply. must reference the same power source.
4. Dimensions — Refer to page 187. 4. Dimensions — Refer to page 187.
Pinout Pinout
1 B1 B1
1
2 B2
3 B3 B2
2

3 B3
10 B10

11 B11
18 B18

18 B18 19 B19
19 B19
20 B20 20 B20

A1

A2

A1 A11
A19
LED Circuit A2 A12 LED Circuit
A20

A9 A19

A10 A20

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 77

1492-IFM20D24-3 Pinout
LED Indicating 3-Wire Sensor with 24V AC/DC LEDs 3 C1

18 C16

B1
B2
1
2
19
20
Application Notes B17
B18
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage A1
and current ratings of the IFM. When this IFM is A2
used with a hard contact (relay) output circuit that
LED Circuit
switches an inductive load, surge suppression must
be used.
A17
2. Wiring — Refer to the Label Section on page 181. A18
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — The LEDs are connected to one
common. All of the field input devices must
reference the same power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


78 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20DS24-4 Pinout
LED Indicating 8 Individually Isolated with 24/48V
10 B1
AC/DC LEDs & 4 Terminals/Output B2
2 B3

(even)

8 B6
12 B7

(even)

18 B10
3 B11

(odd)

9 B14
Application Notes 11 B15

1. Compatibility — To ensure proper operation (odd)


with the I/O module, do not exceed the voltage
17 B18
and current ratings of the IFM. When this IFM is 20 B19
used with a hard contact (relay) output circuit that B20
switches an inductive load, surge suppression must
be used. 1 A1
A2
2. Wiring — Refer to the Label Section on page 181. A3
For Field-Side Wiring Diagrams, refer to the A4

Wiring System web site information on page 186.


3. Isolation — There are eight individually isolated A9
channels. LED returns are individually isolated. A10

4. Extra Terminals — Two field-side terminals are A11


A12
internally connected on the IFM for each channel,
and are available for power source common
connections. A17

5. Dimensions — Refer to page 187. A18


19 A19
A20

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 79

1492-IFM20DS120-4 Pinout
LED Indicating 8 Individually Isolated with 120V AC LEDs 10 B1

& 4 Terminals/Output 2
B2
B3

(even)

8 B6
12 B7

(even)

18 B10
3 B11

(odd)

9 B14
11 B15

(odd)

Application Notes 17 B18


20 B19

1. Compatibility — To ensure proper operation B20

with the I/O module, do not exceed the voltage


1 A1
and current ratings of the IFM. When this IFM is A2
used with a hard contact (relay) output circuit that A3

switches an inductive load, surge suppression must A4

be used (e.g., an MOV wired across an AC load).


2. Wiring — Refer to the Label Section on page 181. A9
For Field-Side Wiring Diagrams, refer to the A10

Wiring System web site information on page 186. A11

A12
3. Isolation — There are eight individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are A17

internally connected on the IFM for each channel, A18


19 A19
and are available for power source common A20
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


80 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F-F-2 1492-IFM20F-F24-2
1492-RIFM20F-F-2 1492-RIFM20F-F24-2
Fusible Extra Terminals for Outputs Fusible Extra Terminals with 24V AC/DC Blown Fuse
Indicators

Application Notes Application Notes


1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. and current ratings of the IFM. When this IFM is
2. Wiring — Refer to the Label Section on page 181. used with a hard contact (relay) output circuit that
For Field-Side Wiring Diagrams, refer to the switches an inductive load, surge suppression must
Wiring System web site information on page 186. be used.
3. Fusing — Fuse holders are included with the 2. Wiring — Refer to the Label Section on page 181.
IFM. Fuses (5 x 20 mm) are not included. For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
4. Isolation — The power bus and fuse clips are
isolated into two groups of 10 terminals (eight fuse 3. Fusing — Fuse holders are included with the
clips). This allows each group of output devices to IFM. Fuses (5 x 20 mm) are not included.
reference a different power source. 4. Isolation — The power bus, fuse clips, and blown
5. Dimensions — Refer to page 187. fuse indicators are isolated into two groups of
10 terminals (eight fuse clips and blown fuse
Pinout indicators). This allows each group of output
1 B1 devices to reference a different power source.
2 B2
3 B3
5. Dimensions — Refer to page 187.
Pinout
1 B1
18 B18 2 B2
19 B19 3 B3

20 B20

18 B18
A1 A11
19 B19
A2 A12
20 B20

A1 A11
A2 A12
A9 A19
A10 A20
A9 A19
A10 A20

Blown Fuse
Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 81

1492-IFM20F-F24A-2 1492-IFM20F-F120-2
1492-RIFM20F-F24A-2 1492-RIFM20F-F120-2
Fusible Extra Terminals with 24V AC/DC Blown Fuse Fusible Extra Terminals with 120V AC/DC Blown Fuse
Indicators Indicators

Application Notes
1. Compatibility — To ensure proper operation
Application Notes with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
1. Compatibility — To ensure proper operation
used with a hard contact (relay) output circuit that
with the I/O module, do not exceed the voltage
switches an inductive load, surge suppression must
and current ratings of the IFM.
be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The power bus, fuse clips, and blown
4. Isolation — The power bus, fuse clips, and blown
fuse indicators are isolated into two groups of
fuse indicators are isolated into two groups of
10 terminals (eight fuse clips and blown fuse
10 terminals (eight fuse clips and blown fuse
indicators). This allows each group of input
indicators). This allows each group of output
devices to reference a different power source.
devices to reference a different power source.
5. Dimensions — Refer to page 187.
5. Dimensions — Refer to page 187.
Pinout Pinout
1 B1 1 B1
2 B2
2 B2
3 B3
3 B3

18 B18
19 B19 18 B18
20 B20 19 B19
20 B20

A1
A1 A11
A2
A2 A12

A3

A9 A19
A10 A10 A20

A11

A18 Blown Fuse


Blown Fuse Indicator Circuit Indicator Circuit
A19
A20

Publication 1492-TD008D-EN-P - January 2009


82 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F-F120A-2 1492-IFM20F-F240-2
1492-RIFM20F-F120A-2 Fusible Extra Terminals with 240V AC/DC Blown Fuse
Indicators
Fusible Extra Terminals with 120V AC/DC Blown Fuse
Indicators

Application Notes
1. Compatibility — To ensure proper operation
Application Notes
with the I/O module, do not exceed the voltage
1. Compatibility — To ensure proper operation and current ratings of the IFM.
with the I/O module, do not exceed the voltage
2. Wiring — Refer to the Label Section on page 181.
and current ratings of the IFM.
For Field-Side Wiring Diagrams, refer to the
2. Wiring — Refer to the Label Section on page 181. Wiring System web site information on page 186.
For Field-Side Wiring Diagrams, refer to the
3. Fusing — Fuse holders are included with the
Wiring System web site information on page 186.
IFM. Fuses (5 x 20 mm) are not included.
3. Fusing — Fuse holders are included with the
4. Isolation — The power bus, fuse clips, and blown
IFM. Fuses (5 x 20 mm) are not included.
fuse indicators are isolated into two groups of
4. Isolation — The power bus, fuse clips, and blown 10 terminals (eight fuse clips and blown fuse
fuse indicators are isolated into two groups of indicators). This allows each group of output
10 terminals (eight fuse clips and blown fuse devices to reference a different power source.
indicators). This allows each group of input
5. Dimensions — Refer to page 187.
devices to reference a different power source.
Pinout
5. Dimensions — Refer to page 187.
Pinout 1 B1
1 B1
2 B2
2 B2
3 B3
3 B3

18 B18 18 B18
19 B19
19 B19
20 B20
20 B20

A1
A1 A11
A2
A2 A12

A3

A9 A19
A10 A10 A20

A11

A18
Blown Fuse Indicator Circuit
A19 Blown Fuse
A20 Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 83

1492-IFM20F-FS-2 1492-IFM20F-FS24-2
Fusible 8 Individually Isolated 120V AC/DC with Extra Fusible 8 Individually Isolated with Extra Terminals and
Terminals for Outputs 24V AC/DC Blown Fuse Indicators

Application Notes
Application Notes
1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage and current ratings of the IFM. When this IFM is
and current ratings of the IFM. used with a hard contact (relay) output circuit that
2. Wiring — Refer to the Label Section on page 181. switches an inductive load, surge suppression must
For Field-Side Wiring Diagrams, refer to the be used (e.g., a 1N4004 diode reverse-wired across
Wiring System web site information on page 186. a DC load).
3. Fusing — Fuse holders are included with the 2. Wiring — Refer to the Label Section on page 181.
IFM. Fuses (5 x 20 mm) are not included. For Field-Side Wiring Diagrams, refer to the
4. Isolation — The fuse clips are isolated into eight Wiring System web site information on page 186.
groups of terminals. This allows each output 3. Fusing — Fuse holders are included with the
device to reference a different power source. IFM. Fuses (5 x 20 mm) are not included.
5. Dimensions — Refer to page 187. 4. Isolation — The fuse clips and blown fuse
indicators are isolated into eight groups of
Pinout terminals. This allows each output device to
10 B1 reference a different power source.
3 B2
5. Dimensions — Refer to page 187.
5 B3
Pinout
(odd)
10 B1
15 B8 3 B2

17 B9 5 B3

20 B10 (odd)

15 B8
17 B9
1 A1 20 B10

2 A2
1 A1
4 A3 2 A2
6 A4 4 A3

8 A5 6 A4
8 A5
12 A6
12 A6
14 A7
14 A7
16 A8
16 A8
18 A9 18 A9

19 A10 19 A10

Blown Fuse
Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


84 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F-FS24A-4 Pinout
Fusible Two 4-Point Isolated Groups with 4 3 B6

Terminals/Input and 24V AC/DC Blown Fuse LED 4 B7


Indicators 5 B8
6 B9
15 B10
16 B11
17 B12
18 B13

B1

B2

B3

B4
7 B5

Application Notes
A1

1. Compatibility — To ensure proper operation A2

with the I/O module, do not exceed the voltage A3

and current ratings of the IFM. When this IFM is A4


used with a hard contact (relay) output circuit that 11 A5
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across 2 B14

a DC load).
2. Wiring — Refer to the Label Section on page 181. A6

For Field-Side Wiring Diagrams, refer to the A7


Wiring System web site information on page 186.
A8
3. Fusing — Fuse holders are included with the
A9
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The fuse clips and blown fuse A10
indicators are isolated into two groups of A11
terminals. This allows each group of output
devices to reference a different power source. A12

5. Dimensions — Refer to page 187. A13

19 A14

Blown Fuse
Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 85

1492-IFM20F-FS120-2 Pinout
Fusible 8 Individually Isolated with Extra Terminals and 10 B1
3 B2
120V AC/DC Blown Fuse LED Indicators 5 B3

(odd)

15 B8
17 B9
20 B10

1 A1
2 A2
4 A3
6 A4
8 A5
12 A6
14 A7
Application Notes 16 A8

1. Compatibility — To ensure proper operation 18 A9

with the I/O module, do not exceed the voltage 19 A10

and current ratings of the IFM. When this IFM is


Blown Fuse
used with a hard contact (relay) output circuit that Indicator Circuit
switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The fuse clips and blown fuse
indicators are isolated into eight groups of
terminals. This allows each output device to
reference a different power source.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


86 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F-FS120-4 Pinout
2 A11
Fusible 8 Individually Isolated with 4 Terminals/Output 3 B11
and 120V AC/DC Blown Fuse LED Indicators 1
A3

B3
4 A12

5 B12
A4

B4
6 A13

7 B13
A5

B5
8 A14

9 B14
A6
Application Notes
B6
1. Compatibility — To ensure proper operation 12 A15
with the I/O module, do not exceed the voltage 11 B15
and current ratings of the IFM. When this IFM is A7
used with a hard contact (relay) output circuit that 19
switches an inductive load, surge suppression must B7

be used (e.g., an MOV wired across an AC load). 14 A16

2. Wiring — Refer to the Label Section on page 181. 13 B16


For Field-Side Wiring Diagrams, refer to the A8
Wiring System web site information on page 186. B8
3. Fusing — Ten fuse holders are included with the 16 A17
IFM. Fuses (5 x 20 mm) are not included. 15 B17
4. Isolation — The fuse clips and blown fuse A9
indicators are isolated into eight groups of B9
terminals. This allows each output device to 18 A18
reference a different power source.
17 B18
5. Dimensions — Refer to page 187.
A10

B10

Blown Fuse
Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 87

1492-IFM20F-FS120A-4 Pinout
3 B6
4 B7
Fusible Two 4-Point Isolated Groups with 4 5 B8
Terminals/Input and 120V AC/DC Blown Fuse LED 6 B9

Indicators 15 B10
16 B11
17 B12
18 B13

B1

B2

B3

B4
7 B5

A1

A2

Application Notes A3

A4

1. Compatibility — To ensure proper operation 11 A5


with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is 2 B14

used with a hard contact (relay) output circuit that


switches an inductive load, surge suppression must A6

be used (e.g., a 1N4004 diode reverse-wired across A7


a DC load or an MOV across an AC load).
A8
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the A9

Wiring System web site information on page 186.


A10
3. Fusing — Ten fuse holders are included with the
A11
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The fuse clips and blown fuse A12

indicators are isolated into two groups of A13


terminals. This allows each group of input devices
19 A14
to reference a different power source.
Blown Fuse
5. Dimensions — Refer to page 187. Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


88 Digital/Analog Programmable Controller Wiring Systems

1492-IFM20F-FS240-4 Pinout
2 A11

3
Fusible 8 Individually Isolated with 4 Terminals/Output A3
B11

and 240V AC/DC Blown Fuse LED Indicators 1


B3
4 A12

5 B12
A4

B4
6 A13

7 B13
A5

B5
8 A14

9 B14
A6

B6
Application Notes 12 A15

11 B15
1. Compatibility — To ensure proper operation A7
19
with the I/O module, do not exceed the voltage B7
and current ratings of the IFM. When this IFM is 14 A16
used with a hard contact (relay) output circuit that 13 B16
switches an inductive load, surge suppression must A8
be used (e.g., a 1N4004 diode reverse-wired across B8
a DC load or an MOV across an AC load). 16 A17

2. Wiring — Refer to the Label Section on page 181. 15 B17


For Field-Side Wiring Diagrams, refer to the A9

Wiring System web site information on page 186. B9


18 A18
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included. 17 B18

4. Isolation — The fuse clips and blown fuse A10

indicators are isolated into eight groups of B10

terminals. This allows each output device to


reference a different power source.
Blown Fuse
5. Dimensions — Refer to page 187.
Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 89

1492-IFM40F 1492-IFM40F-2
1492-RIFM40F 1492-RIFM40F-2
Feed-Through Standard 132V AC/DC Feed-Through Extra Terminals (2 per I/O) 132V AC/DC

Application Notes Application Notes


1. Compatibility — To ensure proper operation 1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage with the I/O module, do not exceed the voltage
and current ratings of the IFM. and current ratings of the IFM.
2. Wiring — Refer to the Label Section on page 181. 2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. Wiring System web site information on page 186.
3. Dimensions — Refer to page 187. 3. Isolation — The power bus is isolated into four
groups of 10 terminals. This allows each group of
Pinout the I/O devices to reference a different power
source.
4. Dimensions — Refer to page 187.
1 A1 Pinout
3 A2
1 B1
5 A3
3 B2

(odd) 5 B3

(odd)
35 A18
37 A19 35 B18

39 A20 37 B19
39 B20

2 B1
2 B21
4 B2
4 B22
6 B3
6 B23
(even)
(even)

36 B18 36 B38
38 B19 38 B39
40 B20 40 B40

A1 A11 A21 A31

A2 A12 A22 A32

A9 A19 A29 A39

A10 A20 A30 A40

Publication 1492-TD008D-EN-P - January 2009


90 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-3 Pinout
TB1
Feed-Through 3-Wire Sensor Type Input Devices 60V 5 C1
AC/DC (odd) 
35 C16

B1
TB2
1 B2
3
37
B17
39
B18

A1
A2

TB1
A17
A18

Application Notes
TB2
1. Compatibility — To ensure proper operation
6 C1
with the I/O module, do not exceed the voltage
(even) 
and current ratings of the IFM.
36 C16
2. Wiring — Refer to the Label Section on page 181.
B1
For Field-Side Wiring Diagrams, refer to the 2 B2
Wiring System web site information on page 186. 4

3. Isolation — The power busses are isolated into 38

two groups of 18 terminals. This allows the input 40 B17


B18
devices connected to the left field-side terminal
block to reference a different power source than A1
A2
the input devices connected to the right field-side
 Even  Odd
terminal block.
4. Dimensions — Refer to page 187. A17
A18

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 91

1492-IFM40D24 Pinout
1 A1
1492-RIFM40D24 3 A2

LED Indicating Standard with 24V AC/DC LEDs 5 A3

(odd)

35 A18
37 A19
39 A20

LED 0-15
LED 16-31

Application Notes
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that 2 B1
4 B2
switches an inductive load, surge suppression must
6 B3
be used (e.g., a 1N4004 diode reverse-wired across
a DC load). (even)

2. Wiring — The LEDs are powered off the 36 B18


B19
two-position terminal block. Make only one 38
40 B20
connection to the power source for normal
operation. Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — The LEDs are connected to one
common. All of the I/O devices used must
reference the same power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


92 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40D24-2 Pinout
1 B1
3 B2
LED Indicating24V AC/DC LEDs and Extra Terminals for 5
(odd)
B3

Outputs 19 B10

21 B11
(odd)
35 B18
37 B19
39 B20

A1 A11

A2 A12

A9 A19

A10 A20
2 B21
4 B22
6 B23
(even)

20 B30

22 B31
Application Notes (even)
36 B38

1. Compatibility — To ensure proper operation 38


40
B39
B40

with the I/O module, do not exceed the voltage


and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that A21 A31

switches an inductive load, surge suppression must LED


A22 A32

be used (e.g., a 1N4004 diode reverse-wired across Circuit A29 A39


a DC load). A30 A40

2. Wiring — Refer to the Label Section on page 181.


For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — The power bus and LEDs are
isolated into four groups of 10 terminals (eight
LEDs). This allows each group of output devices
to reference a different power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 93

1492-IFM40D24A-2 Pinout
1492-RIFM40D24A-2 1 B1
3 B2
5 B3
LED Indicating24V AC/DC LEDs and Extra Terminals for (odd)

Inputs 19 B10

21 B11

(odd)
35 B18
37 B19
39 B20
A1 A11

A2 A12

A9 A19

A10 A20
2 B21
4 B22
6 B23
(even)

20 B30
Application Notes
22 B31

1. Compatibility — To ensure proper operation (even)

with the I/O module, do not exceed the voltage 36 B38

and current ratings of the IFM. When this IFM is 38 B39


40 B40
used with a hard contact (relay) output circuit that
A21 A31
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across LED A22 A32

a DC load). Circuit
A29 A39

2. Wiring — Refer to the Label Section on page 181. A30 A40


For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — The power bus and LEDs are
isolated into four groups of 10 terminals (eight
LEDs). This allows each group of input devices to
reference a different power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


94 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40D120-2 Pinout
1 B1
1
3 B1
B2
3
5 B2
B3
5 B3
LED Indicating 120V AC LEDs and Extra Terminals for (odd)
(odd)
Outputs 19
19
B10
B10
21 B11
21 B11
(odd)
(odd)
35 B18
35 B18
37 B19
37 B19
B20
39
39 B20

A1 A11
A1 A11
A2 A12
A2 A12

A9 A19
A9 A19
A10 A20
A10 A20
2 B21
2 B21
4 B22
4 B22
6 B23
6 B23
(even)
(even)
20 B30
Application Notes 20 B30
22 B31
22 B31
(even)
1. Compatibility — To ensure proper operation (even)
36 B38
with the I/O module, do not exceed the voltage 36
38
38
B38
B39
B39
and current ratings of the IFM. When this IFM is 40
40
B40
B40

used with a hard contact (relay) output circuit that


switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load). A21
A21
A31
A31

2. Wiring — Refer to the Label Section on page 181. A22


A22
A32
A32
For Field-Side Wiring Diagrams, refer to the LED A29 A39
Wiring System web site information on page 186. Circuit A29 A39
A30 A40
3. Isolation — The power bus and LEDs are A30 A40

isolated into four groups of 10 terminals (eight


LEDs). This allows each group of output devices
to reference a different power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 95

1492-IFM40D120A-2 Pinout
1 1 B1 B1
3 B2
3 B2
LED Indicating 120V AC LEDs and Extra Terminals for 5
5 B3
B3
(odd)
Inputs (odd)
19 B10
19 B10
21 B11

21 (odd) B11
35 B18
(odd)
37 B19
35 B18
39 B20
37 A1 A11 B19
39 B20
A2 A12
A1 A11
A9 A19
A2 A12
A10 A20
2 B21
A9 A19
4 B22
6 A10 A20B23
2 (even) B21
4 20 B30 B22
6 22 B31 B23
(even)
(even)
Application Notes 20 36 B38 B30
38 B39
22 40
1. Compatibility — To ensure proper operation B40 B31

(even) A21 A31


with the I/O module, do not exceed the voltage
36 A22 A32 B38
and current ratings of the IFM. When this IFM is 38 B39
used with a hard contact (relay) output circuit that 40
A29 A39
B40
switches an inductive load, surge suppression must A30
A21
A40
A31
be used (e.g., an MOV wired across an AC load).
A22 A32
2. Wiring — Refer to the Label Section on page 181. LED
For Field-Side Wiring Diagrams, refer to the Circuit
A29 A39

Wiring System web site information on page 186. A30 A40

3. Isolation — The power bus and LEDs are


isolated into four groups of 10 terminals (eight
LEDs). This allows each group of input devices to
reference a different power source.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


96 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40D24-3 Pinout
TB1
5 C1

LED Indicating 3-Wire Sensor with 24V AC/DC LEDs (odd)

35 C16

TB2
B1
1 B2
3
37
39 B17
B18

A1
A2

TB1 A17
A18

TB2
6 C1
(even)

36 C16

Application Notes

1. Compatibility — To ensure proper operation B1


with the I/O module, do not exceed the voltage 2 B2

and current ratings of the IFM. When this IFM is 4

used with a hard contact (relay) output circuit that 38


B17
40
switches an inductive load, surge suppression must B18

be used (e.g., a 1N4004 diode reverse-wired across A1


a DC load). A2

2. Wiring — Refer to the Label Section on page 181. LED Circuit


For Field-Side Wiring Diagrams, refer to the A17
A18
Wiring System web site information on page 186.
3. Isolation — The power busses and LEDs are
isolated into two groups of 18 terminals
(16 LEDs). This allows the input devices
connected to the left field-side terminal block to
reference a different power source than the input
devices connected to the right field-side terminal
block.
4. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 97

1492-IFM40DS24-4 Pinout

5 B1
LED Indicating 16 Individually Isolated with
24/48V AC/DC LEDs and 4 Terminals/Output (odd)

19 B8
21 B25

(odd)

35 B32
6 B9

(even)

20 B16
22 B17

(even)

36 B24

A1
A2
Application Notes

1. Compatibility — To ensure proper operation A15

with the I/O module, do not exceed the voltage A16


A17
and current ratings of the IFM. When this IFM is A18
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across A31

a DC load). A32

2. Wiring — Refer to the Label Section on page 181.


For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — There are 16 individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


98 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40DS24A-4 Pinout

6 B9
LED Indicating 16 Individually Isolated with 24V AC/DC 6 B9

LEDs and 4 Terminals/Input (even)


(even)

20 B16
20 B16

5 B1
B1
5
(odd)
(odd)

19 B8
B8
19

22 B17
B17
22

(even)
(even)

36 B24
B24
36

Application Notes
21 B25
B25
21

1. Compatibility — To ensure proper operation (odd)


(odd)

with the I/O module, do not exceed the voltage 35


35
B32
B32
and current ratings of the IFM. When this IFM is A1
A1
used with a hard contact (relay) output circuit that A2
A2
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across
a DC load). A31
A31
A32
A32
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — There are 16 individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 99

1492-IFM40DS120-4 Pinout

5 B1
LED Indicating 16 Individually Isolated with 120V AC and
(odd)
4 Terminals/Output
19 B8
21 B25

(odd)

35 B32
6 B9

(even)

20 B16
22 B17

(even)

36 B24

A1
A2
Application Notes

1. Compatibility — To ensure proper operation A15

with the I/O module, do not exceed the voltage A16


A17
and current ratings of the IFM. When this IFM is
A18
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load). A31
A32
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — There are 16 individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


100 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40DS120A-4 Pinout

LED Indicating 16 Individually Isolated with 120V AC 6 B9

LEDs and 4 Terminals/Input (even)

20 B16

5 B1

(odd)

19 B8

22 B17

(even)

36 B24

Application Notes
21 B25

1. Compatibility — To ensure proper operation (odd)

with the I/O module, do not exceed the voltage 35 B32


and current ratings of the IFM. When this IFM is
A1
used with a hard contact (relay) output circuit that A2
switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181. A31
A32
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — There are 16 individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 101

1492-IFM40DS240A-4 Pinout

6 B17
LED Indicating 16 Individually Isolated with 240V AC
LEDs and 4 Terminals/Input (even)

36 B32

5 A17

(odd)

35 A32

A1

B1

Application Notes A16

B16
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Isolation — There are 16 individually isolated
channels. LED returns are individually isolated.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


102 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-F-2 Pinout
Fusible 120V AC/DC with Extra Terminals for Outputs 1 B1
3 B2
5 B3

(odd)

35 B18
37 B19
39 B20

2 B21
4 B22
6 B23

(even)

36 B38
Application Notes
38 B39
1. Compatibility — To ensure proper operation 40 B40

with the I/O module, do not exceed the voltage


and current ratings of the IFM. A1 A11 A21 A31
A2 A12 A22 A32
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. A9 A19 A29 A39
A10 A20 A30 A40
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The power bus and fuse clips are
isolated into four groups of 10 terminals (eight
fuse clips). This allows each group of output
devices to reference a different power source.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 103

1492-IFM40F-F24-2 Pinout
1492-RIFM40F-F24-2 1 B1
3 B2
Fusible Extra Terminals with 24V AC/DC Blown Fuse LED 5 B3
Indicators for Outputs (odd)

35 B18
37 B19
39 B20

2 B21
4 B22
6 B23

(even)

36 B38
38 B39
40 B40

A1 A11 A21 A31

Application Notes A2 A12 A22 A32

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage A9 A19 A29 A39
and current ratings of the IFM. When this IFM is A10 A20 A30 A40
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must Blown Fuse
be used (e.g., a 1N4004 diode reverse-wired across Indicator Circuit
a DC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The power bus, fuse clips, and blown
fuse indicators are isolated into four groups of
10 terminals (eight fuse clips and blown fuse
indicators). This allows each group of output
devices to reference a different power source.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


104 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-F24D-2 Pinout
16 Individually fused with 24V DC blown fuse low 6 B3
leakage (0.05 mA) LED circuit, 4 isolated groups, 2
(even)
terminals/output
36 B18

5 B1 21 B19

7 B2 23 B20

9 25

11 27

13 29

15 31

17 33

Application Notes
1. Compatibility — To ensure proper operation A1 A11

with the I/O module, do not exceed the voltage A2 A12


and current ratings of the IFM. When this IFM is
A3 A13
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must A4 A14

be used (e.g., a 1N4004 diode reverse-wired across


A5 A15
a DC load).
A6 A16
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the A7 A17
Wiring System web site information on page 186.
A8 A18
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included. A9 A19
4. Isolation — Each point is individually fused. The 19 A10 35 A20
fuse clips and blown fuse indicators are isolated
into 4 groups of terminals. This allows use with 4 Blown Fuse Indicator Circuit
separate power supplies.
5. Dimensions — Refer to page 187.

COM +V

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 105

1492-IFM40F-F24AD-4 Pinout
Individually Fused w/24V DC blown fuse low leakage A2

(0.05 mA) LED circuit, 4 isolated groups, 4 B2

terminals/input 5
(even)
A3

6 B3

A8
(odd)
B8

11 A9

12 B9

A10

B10

13 A11
(even)
14 B11

A16
(odd)
B16

Application Notes 19 A17

1. Compatibility — To ensure proper operation 20 B17

with the I/O module, do not exceed the voltage


and current ratings of the IFM.
A18

B18
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the 21
(even)
A19

Wiring System web site information on page 186. 22 B19

3. Fusing — Fuse holders are included with the A24


(odd)

IFM. Fuses (5 x 20 mm) are not included. B24

4. Extra Terminals — Two field-side terminals are 27 A25

internally connected on the IFM for each channel, 28 B25

and are available for power source common


connections. A26

5. Isolation — Each point is individually fused. The B26

fuse clips and blown fuse indicators are isolated 29 A27

into 4 groups. This allows use of 4 separate power 30


(even)
B27

supplies.
A32

6. Dimensions — Refer to page 187. B32


(odd)

35 A33

36 B33

Blown Fuse
Indicator Circuit

+DC

COM
A3 - A33 (ODD)

Publication 1492-TD008D-EN-P - January 2009


106 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-F120-2 Pinout

Fusible Extra Terminals with 120V AC/DC Blown Fuse 1 B1


3 B2
LED Indicators for Outputs 5 B3

(odd)

35 B18
37 B19
39 B20

2 B21
4 B22
6 B23

(even)

36 B38
38 B39
40 B40

A1 A11 A21 A31


A2 A12 A22 A32

Application Notes A9 A19 A29 A39


A10 A20 A30 A40

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage Blown Fuse
and current ratings of the IFM. When this IFM is Indicator Circuit
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., an MOV wired across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The power bus, fuse clips, and blown
fuse indicators are isolated into four groups of
10 terminals (eight fuse clips and blown fuse
indicators). This allows each group of output
devices to reference a different power source.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 107

1492-IFM40F-FS-2 1492-IFM40F-FS24-2
Fusible 16 Individually Isolated with Extra Terminals for Fusible 16 Individually Isolated with Extra Terminals and
120V AC/DC Outputs 24V AC/DC Blown Fuse LED Indicators for Outputs

Application Notes Application Notes


1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
and current ratings of the IFM.
used with a hard contact (relay) output circuit that
2. Wiring — Refer to the Label Section on page 181. switches an inductive load, surge suppression must
For Field-Side Wiring Diagrams, refer to the be used (e.g., a 1N4004 diode reverse-wired across
Wiring System web site information on page 186. a DC load).
3. Fusing — Fuse holders are included with the 2. Wiring — Refer to the Label Section on page 181.
IFM. Fuses (5 x 20 mm) are not included. For Field-Side Wiring Diagrams, refer to the
4. Isolation — The fuse clips are isolated into Wiring System web site information on page 186.
16 groups of terminals. This allows each output 3. Fusing — Fuse holders are included with the
device to reference a different power source. IFM. Fuses (5 x 20 mm) are not included.
5. Dimensions — Refer to page 187. 4. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
Pinout This allows each output device to reference a
6 B3
different power source.
(even)
5. Dimensions — Refer to page 187.
36 B18
Pinout
6 B3

5 A3 (even)

(odd) 36 B18

35 A18
5 A3

(odd)

35 A18

Blown Fuse Indicator Circuit

Publication 1492-TD008D-EN-P - January 2009


108 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-FS24-4 Pinout
5 A18
Fusible Individually Isolated with 24V AC/DC Blown
Fuse Indicators and 4 Terminals/Output 6 B18

A2

B2

7 A19

8 B19

A3

B3

33 A32
Application Notes
34 B32
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage A16
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that B16
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across 35 A33
a DC load or an MOV for AC loads).
36 B33
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
A17
Wiring System web site information on page 186.
3. Fusing — 20 fuse holders are included with the B17
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips and blown fuse Blown Fuse
indicators are isolated into 16 groups of terminals. Indicator Circuit
This allows each output device to reference a
different power source.
6. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 109

1492-IFM40F-FS-4 Pinout
5 A18
Fusible 16 Individually Isolated 240V AC/DC with 4
Terminals/Output 6 B18

A2

B2

7 A19

8 B19

A3

B3

33 A32
:Application Notes
34 B32
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage A16
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that B16
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across 35 A33
a DC load or an MOV for AC loads).
36 B33
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
A17
Wiring System web site information on page 186.
3. Fusing — 20 fuse holders are included with the B17
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips are isolated into
16 groups of terminals. This allows each output
device to reference a different power source.
6. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


110 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-FS120-2 Pinout
1492-RIFM40F-FS120-2 6 B3

Fusible 16 Individually Isolated with Extra Terminals and (even)

120V AC/DC Blown Fuse LED Indicators for Outputs 36 B18

5 A3

(odd)

35 A18

Blown Fuse Indicator Circuit


Application Notes
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across
a DC load or an MOV across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
This allows each output device to reference a
different power source.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 111

1492-IFM40F-FS120-4 Pinout
1492-IFM40F-FS120-4 5
6
A2
B2
A3
Fusible 16 Individually Isolated with 120V AC/DC Blown B3

Fuse LED Indicators & 4 Terminals/Output 7


8
A4
B4

A5
B5 (even)

(odd)
33 A30
34 B30

A31
B31
35 A32
36 B32

A33
B33

Blown Fuse
Indicator Circuit

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that
switches an inductive load, surge suppression must
be used (e.g., a 1N4004 diode reverse-wired across
a DC load or an MOV across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
This allows each output device to reference a
different power source.
6. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


112 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-FS240-4 Pinout
5 A18

6 B18
Fusible 16 Individually Isolated with 240V AC/DC Blown
Fuse LED Indicators & 4 Terminals/Output A2

B2

7 A19

8 B19

A3

B3

33 A32

34 B32

A16

B16

35 A33

36 B33
Application Notes
A17

1. Compatibility — To ensure proper operation B17

with the I/O module, do not exceed the voltage


and current ratings of the IFM. When this IFM is
used with a hard contact (relay) output circuit that
Blown Fuse
switches an inductive load, surge suppression must Indicator Circuit
be used (e.g., a 1N4004 diode reverse-wired across
a DC load or an MOV across an AC load).
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
This allows each output device to reference a
different power source.
6. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 113

1492-IFM40F-FS24A-4 Pinout
Fusible 16 Individually Isolated 24V AC/DC with 4 A2
B2
Terminals/Input 5 A3
6 B3

A4
B4

7 A5
8 B5

(even)

(odd)
A30
B30

33 A31
34 B31

A32
B32

35 A33
36 B33

Blown Fuse
Application Notes Indicator Circuit
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
and current ratings of the IFM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
This allows each input device to reference a
different power source.
6. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


114 Digital/Analog Programmable Controller Wiring Systems

1492-IFM40F-FSA-4 1492-IFM40F-FS120A-4
Fusible 16 Individually Isolated 120V AC/DC 1492-RIFM40F-FS120A-4
4 Terminals/Input Fusible 16 Individually Isolated with 120V AC/DC Blown
Fuse LED Indicators & 4 Terminals/Input

Application Notes Application Notes


1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage and current ratings of the IFM.
and current ratings of the IFM. 2. Wiring — Refer to the Label Section on page 181.
2. Wiring — Refer to the Label Section on page 181. For Field-Side Wiring Diagrams, refer to the
For Field-Side Wiring Diagrams, refer to the Wiring System web site information on page 186.
Wiring System web site information on page 186. 3. Fusing — Fuse holders are included with the
3. Fusing — Fuse holders are included with the IFM. Fuses (5 x 20 mm) are not included.
IFM. Fuses (5 x 20 mm) are not included. 4. Extra Terminals — Two field-side terminals are
4. Extra Terminals — Two field-side terminals are internally connected on the IFM for each channel,
internally connected on the IFM for each channel, and are available for power source common
and are available for power source common connections.
connections. 5. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
5. Isolation — The fuse clips are isolated into
This allows each input device to reference a
16 groups of terminals. This allows each input
different power source.
device to reference a different power source.
6. Dimensions — Refer to page 187.
6. Dimensions — Refer to page 187.
Pinout
Pinout A2
A2 B2
5 A3
B2
6 B3
5 A3
A4
6 B3 B4

A4 7 A5
B4 8 B5

(even)
7 A5
8 B5 (odd)
A30

(even) B30

33 A31
(odd) B31
34
A30
A32
B30
B32

33 A31 35 A33
36 B33
34 B31
A32 Blown Fuse
B32 Indicator Circuit
35 A33
36 B33

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 115

1492-IFM40F-FS240A-4 Pinout
A2
B2

Fusible 16 Individually Isolated with 240V AC/DC Blown 5


6
A3
B3
Fuse LED Indicators and 4 Terminals/Input A4
B4

7 A5
8 B5

(even)

(odd)
A30
B30

33 A31
34 B31

A32
B32

35 A33
36 B33

Blown Fuse
Indicator Circuit

Application Notes
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
and current ratings of the IFM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Fuse holders are included with the
IFM. Fuses (5 x 20 mm) are not included.
4. Extra Terminals — Two field-side terminals are
internally connected on the IFM for each channel,
and are available for power source common
connections.
5. Isolation — The fuse clips and blown fuse
indicators are isolated into 16 groups of terminals.
This allows each input device to reference a
different power source.
Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


116 Digital/Analog Programmable Controller Wiring Systems

1492-XIM2024-8R Pinout

Relay Master (LED Indicating) 20-Pin Master with Eight CN TB


~~
(8) 24V DC Relays A3
3 K0 A4
A5
~~
A6
4 K1 A7
A8
~~
B3
5 K2 B4
B5
~~
B6
6 K3 B7
B8
~~
B9
7 K4 B10
B11
~~
B12
8 K5 B13
B14
~~
A9
Application Notes 9 K6 A10
A11
~~
A12
1. Compatibility — To ensure proper operation 10 K7 A13

with the I/O module, do not exceed the voltage A14

and current ratings of the XIM. 20 B16


7 CJ
2. Wiring — Refer to the Label Section on page 181. 8
OUT

For Field-Side Wiring Diagrams, refer to the


Wiring System web site information on page 186. 19 B15

3. Dimensions — Refer to page 187. 1 B1

4. Maximum Relay Switching — Refer to 2 B2


page 192. 1
CJOUT
2
5. LEDs provide PLC output ON/OFF indication.
CN CJOUT
6. With expansion module and cable (included with 11 20
expansion module) can expand to 16 relays. 12 24

13 28

14 30

15 32

16 31

17 34

18 33

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 117

1492-XIM20120-8R Pinout

CN TB
Relays Masters (LED Indicating) 20-Pin Master with ~~
A3
Eight (8) 120V AC Relays 3 K0 A4
A5
~~
A6
4 K1 A7
A8
~~
B3
5 K2 B4
B5
~~
B6
6 K3 B7
B8
~~
B9
7 K4 B10
B11
~~
B12
8 K5 B13
B14
~~
A9
9 K6 A10
A11
Application Notes ~~
A12
10 K7 A13

1. Compatibility — To ensure proper operation A14

with the I/O module, do not exceed the voltage 20 B16

and current ratings of the XIM. 7 CJ


8
OUT

2. Wiring — Refer to the Label Section on page 181.


For Field-Side Wiring Diagrams, refer to the 19 B15

Wiring System web site information on page 186. 1 B1

3. Dimensions — Refer to page 187.


4. Maximum Relay Switching — Refer to 2 B2
1
page 192. 2
CJOUT

5. LEDs provide PLC output ON/OFF indication. CN CJOUT


11 20
6. With expansion module and cable (included with
12 24
expansion module) can expand to 16 relays.
13 28

14 30

15 32

16 31

17 34

18 33

Publication 1492-TD008D-EN-P - January 2009


118 Digital/Analog Programmable Controller Wiring Systems

1492-XIM2024-16R Pinout
1492-XIM2024-16R

Relays Master (LED Indicating) 20-Pin Master with TB 1


C N
Sixteen (16) 24V DC Relays 3 K 16
3
4
5
~~
6
4 K 17 7
8
~~
9
K 18 10
5
~~ 11
12
6 K 19 13
~~ 14
15
7 K 20 16
~~ 17
18
8 K 21 19
~~ 20
21
9 K 22 22
23
~~
24
10 K 23 25
26
~~ TB 2
1
11 K 24 2
~~ 3

Application Notes 12 K 25
4
5
6
~~
7
1. Compatibility — To ensure proper operation 13
K 26 8
9
~~
with the I/O module, do not exceed the voltage 10
11
and current ratings of the XIM. 14 K 27

~~ 12
13
2. Wiring — Refer to the Label Section on page 181. 15 K 28 14
~~ 15
For Field-Side Wiring Diagrams, refer to the K 29
16
17
Wiring System web site information on page 186.
16
~~ 18
19
3. Dimensions — Refer to page 187. 17 K 30 20
21
~~
4. Maximum Relay Switching — Refer to K 31
22
23
page 192.
18
24
TB 2
5. LEDs provide PLC output ON/OFF indication. 20
26

6. No expansion capability. 19 25

TB 1
1 1
2 2

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 119

1492-XIM2024-16RF Pinout
1492-XIM2024-16RF

Relay Master (LED Indicating) 20-Pin Master with CN


~~ TB1
Sixteen (16) 24V DC Relays with Fusing 3 K0
3
4
~~ 5
6
4 K1 7
8
~~
9
K2 10
5
~~ 11
12
6 K3 13
~~ 14
15
7 K4 16
~~ 17
18
8 K5 19
~~ 20
21
9 K6 22
~~ 23
24
10 K7 25
26
~~ TB2
1
11 K0 2
~~ 3
4
12 K1 5

Application Notes ~~ 6
7
K2 8
13
9
~~
1. Compatibility — To ensure proper operation 14 K3
10
11

with the I/O module, do not exceed the voltage ~~ 12


13

and current ratings of the XIM. 15


~~
K4 14
15
16
2. Wiring — Refer to the Label Section on page 181. 16 K5 17
~~ 18
For Field-Side Wiring Diagrams, refer to the K6
19
20
Wiring System web site information on page 186.
17
21
~~
22
3. Dimensions — Refer to 187. 18 K7 23
24

4. Maximum Relay Switching — Refer to TB2


26
page 192. 20
19 25

5. LEDs provide PLC output ON/OFF indication. 1


TB1
1

6. No expansion capability. 2 2

Publication 1492-TD008D-EN-P - January 2009


120 Digital/Analog Programmable Controller Wiring Systems

1492-XIM20120-16R Pinout
1492-XIM2024-16R

Relay Master (LED Indicating) 20-Pin Master with C N TB 1


3
Sixteen (16) 120V AC Relays 3 K 16 4
5
~~
6
4 K 17 7
8
~~
9
K 18 10
5
~~ 11
12
6 K 19 13
~~ 14
15
7 K 20 16
~~ 17
18
8 K 21 19
~~ 20
21
9 K 22 22
23
~~
24
10 K 23 25
26
~~ TB 2
1
11 K 24 2
~~ 3
4

Application Notes 12
~~
K 25 5
6
7
K 26 8
13
1. Compatibility — To ensure proper operation ~~ 9
10
with the I/O module, do not exceed the voltage 14 K 27 11
12
~~
and current ratings of the XIM. 13
15 K 28 14
2. Wiring — Refer to the Label Section on page 181. ~~ 15
16
For Field-Side Wiring Diagrams, refer to the 16 K 29 17
~~ 18
Wiring System web site information on page 186. K 30
19
20
17
3. Dimensions — Refer to page 187. ~~
21
22
4. Maximum Relay Switching — Refer to 18 K 31 23
24
page 192. TB 2
26
5. LEDs provide PLC output ON/OFF indication. 20
19 25

6. No expansion capability. TB 1
1 1
2 2

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 121

1492-XIM20120-16RF Pinout
1492-XIM20120-16RF

Relay Master (LED Indicating) 20-Pin Master with CN


~~ TB1
3
Sixteen (16) 120V AC Relays with Fusing 3 K0 4
~~ 5
6
4 K1 7
8
~~
9
K2 10
5
~~ 11
12
6 K3 13
~~ 14
15
7 K4 16
~~ 17
18
8 K5 19
~~ 20
21
9 K6 22
~~ 23
24
10 K7 25
26
~~ TB2
1
11 K0 2
~~ 3
4

Application Notes 12
~~
K1 5
6
7
K2 8
13

1. Compatibility — To ensure proper operation ~~ 9


10

with the I/O module, do not exceed the voltage 14


~~
K3 11
12

and current ratings of the XIM. 15 K4


13
14
~~ 15
2. Wiring — Refer to the Label Section on page 181. 16
K5 17
For Field-Side Wiring Diagrams, refer to the 16
~~ 18
19
Wiring System web site information on page 186. 17 K6 20
21
~~
3. Dimensions — Refer to page 187. 22
18 K7 23

4. Maximum Relay Switching — Refer to 24


TB2
page 192. 20
26

5. LEDs provide PLC output ON/OFF indication. 19 25

TB1

6. No expansion capability. 1
2 2
1

Publication 1492-TD008D-EN-P - January 2009


122 Digital/Analog Programmable Controller Wiring Systems

1492-XIM4024-8R Pinout
CN TB
~~
A3
Relay Master (LED Indicating) 40-Pin Master with Eight 3 K0 A4
A5
(8) 24V DC Relays ~~
A6
4 K1 A7
A8
~~
B3
5 K2 B4
B5
~~
B6
6 K3 B7
B8
~~
B9
7 K4 B10
B11
~~
B12
8 K5 B13
B14
~~
A9
9 K6 A10
A11
~~
A12
10 K7 A13
Application Notes A14

20 B16
1. Compatibility — To ensure proper operation 7 CJ
OUT
8
with the I/O module, do not exceed the voltage
and current ratings of the XIM. 19 B15

2. Wiring — Refer to the Label Section on page 181. 1 B1


For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. 2 B2

3. Dimensions — Refer to page 187. 1


2
CJOUT

4. Maximum Relay Switching — Refer to


page 192.
5. LEDs provide PLC output ON/OFF indication.
6. With expansion module(s) and cable (included
with expansion module) can expand to 32 relays.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 123

1492-XIM4024-8R, Continued

Pinout, Continued

CN TB CN CJOUT
~~
A3 21 20
5 K0 A4
23 24
A5
~~ 25 28
A6
7 K1 A7 27 30
A8
~~ 29 32
B3
K2 B4 31 31
9
B5
~~ 33 34
B6
35 33
11 K3 B7
B8
~~ 6 12
B9
13 K4 B10 8 11

B11
~~ 10 14
B12
12 13
15 K5 B13
B14 14 16
~~
A9 16 15
17 K6 A10
A11 18 18
~~
A12 20 17
19 K7 A13
A14 CJOUT 22 22
7
37 B15 24 26
8
39 B16
26 19
5
38 A15 9
28 21
10
40 A16
3 30 23
2 A1 4
6 32 25
4 A2
1
1 34 27
B1
2
3 B2 36 29

Publication 1492-TD008D-EN-P - January 2009


124 Digital/Analog Programmable Controller Wiring Systems

1492-XIM4024-16R
1492-RXIM4024-16R

Relay Master (LED Indicating) 40-Pin Master with


Sixteen (16) 24V DC Relays

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Dimensions — Refer to page 187.
4. Maximum Relay Switching — Refer to
page 192.
5. LEDs provide PLC output ON/OFF indication.
6. With expansion module(s) and cable(s) (included
with expansion module) can expand to 32 relays.

Pinout

Refer to page 125.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 125

1492-XIM4024-16R
1492-RXIM4024-16R, Continued
Pinout, Continued
CN TB1 CN TB2
~~ ~~
A3 A3
5 A4 21 K8 A4
K0
A5 A5
~~ ~~
A6 A6
23 K9 A7
7 K1 A7
A8
~~
A8 ~~
B3
B3
25 K10 B4
9 K2 B4
B5
B5 ~~
~~ B6
B6
27 K11 B7
11 K3 B7
B8
B8 ~~
~~ B9
B9 29 K12 B10
13 K4 B10 B11
B11 ~~
~~ B12
B12 31 K13 B13
15 K5 B13 B14
B14
~~
~~ A9
A9 33 K14 A10
A11
17 K6 A10 ~~
A11 A12
~~
A12 35 K15 A13

K7 A13 A14
19
A14 CJOUT
TB2
7
37 B1
8
39 B2
5
38 A1 9
10
40 A2

TB1
3
2 A1 4
6
4 A2
1
1 B1
2
3 B2

CN CJOUT
6 20

8 24

10 28

12 30

14 32

16 31

18 34

20 33

22 12

24 11

26 14

28 13

30 16

32 15

34 18

36 17

Publication 1492-TD008D-EN-P - January 2009


126 Digital/Analog Programmable Controller Wiring Systems

1492-XIM4024-16RF Pinout
CN
Relay Master (LED Indicating) 40-Pin Master with ~~ TB1
3

Sixteen (16) 24V DC Relays with Fusing 5 K0 4

~~ 5
6

7 K1 7
8
~~
9
K2 10
9
~~ 11
12
K3 13
11
~~ 14
15
13 K4 16

~~ 17
18

15 K5 19

~~ 20
21
K6 22
17
Application Notes ~~ 23

24
K7 25
19
1. Compatibility — To ensure proper operation 26
~~ TB2
with the I/O module, do not exceed the voltage 1

and current ratings of the XIM. 21 K8 2

~~ 3

2. Wiring — Refer to the Label Section on page 181. CN CJOUT 4


6 20 K9 5
For Field-Side Wiring Diagrams, refer to the 8 24
23
~~ 6

Wiring System web site information on page 186. 10 28


7
8
25 K10
3. Dimensions — Refer to page 187. 12 30
~~ 9
14 32 10
4. Maximum Relay Switching — Refer to 16 31
27 K11 11

page 192. 18 34 ~~ 12
13
20 33
5. LEDs provide PLC output ON/OFF indication. 29 K12 14
22 12 ~~ 15
6. With expansion module(s) and cable(s) (included 24 11
16

with expansion module) can expand to 32 relays. 26 14 31 K13 17

28 13
~~ 18
19
30 16 K14 20
33
32 15 ~~ 21

34 18 22
36 17 K15 23
35
24
CJOUT
TB2
7
37 25 8
39
5
38 26 9
10
40
TB1 3
2 2 4
6
4
1
1 1
2
3

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 127

1492-XIM24-8R
1492-RXIM24-8R
Relay Expander (LED Indicating) with Eight (8) 24V DC
Relays

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. This relay expander must be used with a 24V DC
relay master.
4. Dimensions — Refer to page 187.
5. Maximum Relay Switching — Refer to
page 192.
6. LEDs provide PLC output ON/OFF indication.

Pinout

Refer to page 128.

Publication 1492-TD008D-EN-P - January 2009


128 Digital/Analog Programmable Controller Wiring Systems

1492-XIM24-8R, Continued
1492-RXIM24-8R, Continued
Pinout, Continued
CJIN TB CJIN CJOUT
~~ 1
A1 30
16 2
K0 A2
31 3
A3
~~ 32
4
A4 6
12 K1 A5 5
25
A6 7
~~
B1 26 8
8 K2 B2 9
29
B3 10
~~
B4 24 20
6 K3 B5
23 24
B6
~~
B7 22 28

4 K4 B8
21 30
B9
~~ 20 32
B10
3 K5 B11 19 31
B12
~~ 18 34
A7
2 K6 A8 17 33
A9
~~ 15 14
A10
1 K7 A11 14 12
A12
13 13

27 11 16

28 10 11

9 15

7 18

5 17

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 129

1492-XIM120-8R

Relay Expander (LED Indicating) with Eight (8) 120V AC


Relays

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. This relay expander must be used with a 120V AC
relay master.
4. Dimensions — Refer to page 187.
5. Maximum Relay Switching — Refer to
page 192.
6. LEDs provide PLC output ON/OFF indication.

Pinout

Refer to page 130.

Publication 1492-TD008D-EN-P - January 2009


130 Digital/Analog Programmable Controller Wiring Systems

1492-XIM120-8R, Continued

Pinout, Continued

CJIN TB CJIN CJOUT


~~
A1 1
30
16 K0 A2 2

A3 31 3
~~ 4
A4 32
6
12 K1 A5
5
A6 25
7
~~
B1 26 8
8 K2 B2 9
29
B3 10
~~
B4 24 20
6 K3 B5
B6 23 24
~~
B7 22 28
4 K4 B8
21 30
B9
~~ 20 32
B10
3 K5 B11 19 31
B12
~~ 18 34
A7
2 K6 A8 17 33
A9
~~ 15 14
A10
1 K7 A11 14 12
A12
13 13

27 16
11

28 10 11

9 15

7 18

5 17

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 131

1492-XIM24-16RF Pinout

Expander with Sixteen (16) 24V DC Relays with Fusing 1492-XIM24-16RF


CJIN ~~ TB1
1
16 K16 2
3
~~
4
12 K17 5
6
~~
7
K18 8
8
~~ 9
10
K19 11
6
~~ 12
13
4 K20 14
~~ 15
16
3 K21 17
Application Notes ~~ 18
19
2 K22 20
1. Compatibility — To ensure proper operation ~~ 21
with the I/O module, do not exceed the voltage 22
and current ratings of the XIM. 1
K23 23
24
2. Wiring — Refer to the Label Section on page 181. ~~ TB2
1
For Field-Side Wiring Diagrams, refer to the K24 2
24
Wiring System web site information on page 186. ~~ 3
4
3. This relay expander must be used with a 24 VDC K25 5
23
relay master. ~~ 6
7
4. Dimensions — Refer to page 187. K26 8
22
5. Maximum Relay Switching — Refer to ~~ 9

page 192. 10
11
21 K27
6. LEDs provide PLC output ON/OFF indication. ~~ 12
13
20 K28 14
~~ 15
16
19 K29 17
~~ 18
19
18 K30 20
~~ 21
22
17
K31 23
24
CJIN

27
28

Publication 1492-TD008D-EN-P - January 2009


132 Digital/Analog Programmable Controller Wiring Systems

1492-XIMF-F24-2

Fusible 8-Channel Expander with 24V DC Blown Fuse


Indicators

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Extra Terminals — Eight field-side terminals are
jumpered together on the XIM. For some I/O
modules, the terminals are also internally
connected to module common through the pre-
wired cable. Refer to the XIM and CABLE
pinouts.
4. Dimensions — Refer to page 187.
5. LEDs provide blown fuse indication.

Pinout

Refer to page 133.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 133

1492-XIMF-F24-2, Continued

Pinout, Continued

CJIN TB CJIN CJOUT


1
F8 30
16 2
B1
31 3
4
32
F9 6
12 B2

5
25
7
F10
8 B3 26 8
9
29
10
F11
6 B4
24 20

23 24
F12
4 B5
22 28

21 30
F13
3 B6 20 32

19 31
F14
2 B7 18 34

17 33
F15
1 B8
15 14

14 12
A1
A2 13 13

A3
27 11 16
A4
A5 10 11
28
A6
9 15
A7
A8 7 18

5 17

Publication 1492-TD008D-EN-P - January 2009


134 Digital/Analog Programmable Controller Wiring Systems

1492-XIMF-F120-2

Fusible 8-Channel Expander with 120V AC Blown Fuse


Indicators

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Extra Terminals — Eight field-side terminals are
jumpered together on the XIM. For some I/O
modules, the terminals are also internally
connected to module common through the pre-
wired cable. Refer to the XIM and CABLE
pinouts.
4. Dimensions — Refer to page 187.
5. LEDs provide blown fuse indication.

Pinout

Refer to page 135.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 135

1492-XIMF-F120-2, Continued

Pinout, Continued
CJIN TB CJIN CJOUT
F8 30
1
16 B1 2
31 3
4
32
F9 6
12 B2

5
25
F10 7
8 B3 26 8
9
29
10
F11
6 B4
24 20

23 24
F12
4 B5
22 28

21 30
F13
3 B6
20 32

19 31
F14
2 B7 18 34

17 33
F15
1 B8
15 14

14 12
A1
A2 13 13
A3
27 11 16
A4

28 A5 10 11
A6
A7 9 15

A8 7 18

5 17

Publication 1492-TD008D-EN-P - January 2009


136 Digital/Analog Programmable Controller Wiring Systems

1492-XIMF-2

Expander with Eight (8) Feed-Through Channels

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the XIM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Extra Terminals — Eight field-side terminals are
jumpered together on the XIM. For some I/O
modules, the terminals are also internally
connected to module common through the pre-
wired cable. Refer to the XIM and CABLE
pinouts.
4. Dimensions — Refer to page 187.

Pinout

Refer to page 137.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 137

1492-XIMF-2, Continued

Pinout, Continued

CJIN TB CJIN CJOUT


1
30
16 B1 2
31 3
4
32
6
12 B2

5
25
7
8 B3 26 8
9
29
10

6 B4
24 20

23 24
4 B5
22 28

21 30

3 B6 20 32

19 31

2 B7 18 34

17 33

1 B8
15 14

14 12
A1
A2 13 13
A3
27 11 16
A4

28 A5 10 11
A6
9 15
A7
A8 7 18

5 17

Publication 1492-TD008D-EN-P - January 2009


138 Digital/Analog Programmable Controller Wiring Systems

Digital Cable Bulletin 1492 pre-wired cables are designed to minimize control wiring in a
panel. Digital pre-wired cables, when used with an IFM or XIM, replace the
Specifications point-to-point wiring between Allen-Bradley programmable controller I/O
modules and individual terminal blocks. The digital ready-to-wire cables
provide one end of the cable pre-terminated, for either an IFM (IFM-ready
cable) or a programmable controller I/O module (I/O module-ready cable).

Pre-Wired Cables

Specifications

The pre-wired cables have a Bulletin 1746 Removable Terminal Block,


1756 Removable Terminal Block, 1769 Removable Terminal Block, or 1771
Wiring Arm on one end and a cable connector on the other to connect to the
IFM or XIM. The broad offering of digital pre-wired cables supports over 100
different 16- and 32-point Bulletin 1746, 1756, 1769, 1794, and 1771 digital
I/O modules.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 139

Digital Cable Pre-Wired Cables, Continued


Specifications, Continued
Digital Pre-Wired Cable Specifications
Catalog Standard Cable Insulation No. of Conductor Nominal Outer I/O Module Connector
Number Lengths Rating Conductors Size Diameter
1492-CABLE➊A 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25R Red Removable Terminal Block
1492-CABLE➊B 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25B Blue Removable Terminal Block
1492-CABLE➊C 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25R Red Removable Terminal Block
1492-CABLE➊CR 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25R Red Removable Terminal Block
1492-CABLE➊D 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25C Orange Removable Terminal Block
1492-CABLE➊E 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25B Blue Removable Terminal Block
1492-CABLE➊F 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1771-WH (16-Point/21 Terminal) Wiring Arm
1492-CABLE➊FF 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1771-WHF (16-Point/21 Terminal) Fused Wiring Arm
1492-CABLE➊G 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25R Red Removable Terminal Block
1492-CABLE➊H 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1746-N3 40-Pin Cable Connector
1492-CABLE➊J 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CABLE➊K 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CABLE➊L 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CABLE➊M 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CABLE➊N 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25C Orange Removable Terminal Block
1492-CABLE➊R 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CAB➊R71 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
1492-CABLE➊S 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1746-RT25C Orange Removable Terminal Block
1492-CABLE➊T 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 11.7 mm (0.46 in.) 1771-WA (8-Point/10 Terminal) Wiring Arm
1492-CABLE➊U 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1756-TBNH Removable Terminal Block
1492-CABLE➊V 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1756-TBNH Removable Terminal Block
1492-CABLE➊W 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1756-TBNH Removable Terminal Block
1492-CABLE➊X 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1756-TBNH Removable Terminal Block
1492-CABLE➊Y 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1756-TBCH Removable Terminal Block
1492-CABLE➊Z 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1756-TBCH Removable Terminal Block
1492-CAB➊A62 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1762-L40xxx Input Terminal
1492-CAB➊B62 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1762-L40xxx Output Terminal
1492-CAB➊A64 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-24AWA, -24BWA Input Terminal
1492-CAB➊B64 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-28BXB Input Terminal
1492-CAB➊C64 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-24AWA, -24BWA Output Terminal
1492-CAB➊F64 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-28BXB Output Terminal
1492-CAB➊A69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊B69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊C69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN10 Removable Terminal Block
1492-CAB➊D69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊E69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊F69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊G69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊H69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block

Publication 1492-TD008D-EN-P - January 2009


140 Digital/Analog Programmable Controller Wiring Systems

Digital Pre-Wired Cable Specifications (Continued)


Catalog Standard Cable Insulation No. of Conductor Nominal Outer I/O Module Connector
Number Lengths Rating Conductors Size Diameter
1492-CAB➊J69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.1 mm (0.46 in.) (2) 1769-RTBN18 Removable Terminal Block
1492-CAB➊K69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.1 mm (0.46 in.) (2) 1769-RTBN18 Removable Terminal Block
1492-CAB➊L69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊M69 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1769-RTBN18 Removable Terminal Block
1492-CAB➊A7H 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 20C-DA1-A and 20C-D01 Terminals
1492-CAB➊A7S 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 20C-DB1-A and 20C-D01 Terminals
1492-CAB➊B7H 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) TB2
1492-CAB➊A94 0.5, 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 37-Pin male D-shell ➋
1492-CAB➊B94 0.5, 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 62-Pin male D-shell ➌

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the
desired cable length into the catalog number (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example:
Catalog Number 1492-CABLE005A is for a 0.5 m cable for the 1746-IA16 I/O Module. Also refer to
Build-to-Order Length Cables on page 65.
➋ Mates with 1794 Flex D-shell style base: 1794-TB37DS
➌ Mates with 1794 Flex D-shell style base: 1794-TB62DS

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 141

Digital Cable Pinouts


Digital/Analog Programmable Controller Wiring Systems

Specifications, Continued
Digital Pre-Wired Cables

The following diagrams illustrate how the individual conductors in the digital
pre-wired cables are terminated at both ends. The description listed first is the
wire color of the conductor connected to the PLC or PowerFlex drive
removable terminal block (Bulletin 1746, 1756, 1762, 1764, 1769, 700S and
700H I/O) wiring arm (1771 I/O) or D-shell connector (Cat. No. 1794-
TB37DS or 1794-62DS). The number that follows in parentheses is the
corresponding pin number of the IFM/XIM mating connector.

Shield
Base Color Stripe Color

Blue (24) White/Green (22)

NC
20 or 40 Connector Pin Number

Black (23) White/Red (19)

No Connection Individual Conductor


Twisted Pair Jumper Wire
I/O Pin Connector Definition

1 39
19
1

20
2

40
2

20-Conductor Cable 40-Conductor Cable


IFM Mating Connector Definition

Publication 1492-TD008D-EN-P - January 2009


142 Digital/Analog Programmable Controller Wiring Systems

Digital Cable Pinouts, Continued


Digital/Analog Programmable Controller Wiring Systems

Specifications, Continued
Red RTB Blue RTB
Red (3) 1 Red (3) 1
2 Green (4) 2 Green (4)
Orange (5) 3 Orange (5) 3
4 Blue (6) 4 Blue (6)
White/Black (7) 5 White/Black (7) 5
6 Red/Black (8) 6 Red/Black (8)
Green/Black (9) 7 Green/Black (9) 7
8 Orange/Black (10) 8 Orange/Black (10)
Blue/Black (11) 9 Blue/Black (11) 9
10 Black/White (12) 10 Black/White (12)
Red/White (13) 11 Red/White (13) 11
12 Green/White (14) 12 Green/White (14)
Blue/White (15) 13 Blue/White (15) 13
14 Black/Red (16) 14 Black/Red (16)
White/Red (17) 15 White/Red (17) 15
16 Orange/Red (18) 16 Orange/Red (18)
Blue/Red (19) 17 Blue/Red (19) 17
18 Red/Green (20) 18 Red/Green (20)

1492-CABLE➊A 1492-CABLE➊B

White (2) Red RTB White (2) Orange RTB White (2) Blue RTB
Black (1) 1
Red (3) Black (1) 1 Black (1) 1
2 2 Red (3) 2 Red (3)
Green (4) 3 Green (4) 3 Green (4) 3
4 Orange (5) 4 Orange (5) 4 Orange (5)
Blue (6) 5 Blue (6) 5 Blue (6) 5
6 White/Black (7) 6 White/Black (7) 6 White/Black (7)
Red/Black (8) 7 Red/Black (8) 7 Red/Black (8) 7
8 Green/Black (9) 8 Green/Black (9) 8 Green/Black (9)
Orange/Black (10) 9
10 Blue/Red (19) Orange/Black (10) 9 Blue/Red (19) Orange/Black (10) 9
10 10
Black/White (12) 11 Red/Green (20) Black/White (12) 11 Red/Green (20) Black/White (12) 11
Blue/Black (11)
12 12 12
Green/White (14) Blue/Black (11) Blue/Black (11) Green/White (14) Red/White (13)
13
14 Green/White (14) 13
14
13
14
Black/Red (16) Red/White (13) Red/White (13) Black/Red (16) Blue/White (15)
15
16 Black/Red (16) 15
16
15
16
Orange/Red (18) 17 Blue/White (15) Blue/White (15) Orange/Red (18) White/Red (17)
18 Orange/Red (18) 17
18
17
18 Blue/Red (20)
White/Red (17) White/Red (17) Red/Green (19)
1492-CABLE➊C 1492-CABLE➊D 1492-CABLE➊E

A Black (1) CAUTION


DISCONNECT A Black (1)
B White (2) POWER
BEFORE B White (2)
C Blue/Red (19) SERVICING
FUSES C Blue/Red (19)
D ALL FUSES
30-250V D
00 Red (3) 00 Red (3)
01 Green (4) 01 Green (4)
02 Orange (5) 02 Orange (5)
03 Blue (6) 03 Blue (6)
04 White/Black (7) 04 White/Black (7) Jumper
05 Red/Black (8) 05 Red/Black (8) White (2) Red RTB
06 Green/Black (9) 06 Green/Black (9) Black (1) 1
Orange/Black (10)
2 Red (3)
07
07 Orange/Black (10) Green (4) 3
10 Blue/Black (11)
4 Orange (5)
10 Blue/Black (11) Blue (6) 5
11 Black/White (12)
6 White/Black (7)
11 Black/White (12) Red/Black (8) 7
12 Red/White (13) 8 Green/Black (9)
12 Red/White (13) Orange/Black (10) 9
13 Green/White (14) 13 Green/White (14) Black/White (12)
10 Blue/Red (19)
11
14 Blue/White (15) 14 Blue/White (15) 12 Blue/Black (11)
15 Black/Red (16) Green/White (14) 13
15 Black/Red (16) 14 Red/White (13)
16 White/Red (17) Black/Red (16) 15
16 White/Red (17) 16 Blue/White (15)
17 Orange/Red (18) Orange/Red (18) 17
17 Orange/Red (18) 18 White/Red (17)
E Red/Green (20) E Red/Green (20)

1492-CABLE➊F 1492-CABLE➊FF 1492-CABLE➊G

➊ Refer to footnote on page 149.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 143

Digital Cable Pinouts, Continued


Specifications, Continued
1 Orange (5) 1 Black (1)
White/Black (7) 2 Red (3) 2
3 Green/Black (9) 3 Orange (5)
Blue/Black (11) 4 White/Black (7) 4
5 Red/White (13) 5 Green/Black (9)
Blue/White (15) 6 Blue/Black (11) 6
7 White/Red (17) 7 Red/White (13)
Blue/Red (19) 8 Blue/White (15) 8
9 Black (1) 9 White/Red (17)
Red (3) 10 Blue/Red (19) 10
11 Orange/Green (21) 11 White/Red-Blue (37)
White/Black-Red (23) 12 White/Black-Green (39) 12
13 Green/Black-White (25) 13 Orange/Green (21)
Blue/Black-White (27) 14 White/Black-Red (23) 14
15 White/Red-Green (29) 15 Green/Black-White (25)
Green/Black-Orange (31) 16 Blue/Black-White (27) 16
17 Blue/White-Orange (33) 17 White/Red-Green (29)
White/Red-Orange (35) 18 Green/Black-Orange (31) 18
19 White/Red-Blue (37) 19 Blue/White-Orange (33)
White/Black-Green (39) 20 White/Red-Orange (35) 20
21 Blue (6) 21 White (2)
Red/Black (8) 22 Green (4) 22
23 Orange/Black (10) 23 Blue (6)
Black/White (12) 24 Red/Black (8) 24
25 Green/White (14) 25 Orange/Black (10)
Black/Red (16) 26 Black/White (12) 26
27 Orange/Red (18) 27 Green/White (14)
Red/Green (20) 28 Black/Red (16) 28
29 White (2) 29 Orange/Red (18)
Green (4) 30 Red/Green (20) 30
31 Black/White-Red (22) 31 Black/White-Green (38)
Red/Black-White (24) 32 Red/White-Green (40) 32
33 Orange/Black-White (26) 33 Black/White-Red (22)
Black/Red-Green (28) 34 Red/Black-White (24) 34
35 Red/Black-Green (30) 35 Orange/Black-White (26)
Orange/Black-Green (32) 36 Black/Red-Green (28) 36
37 Black/White-Orange (34) 37 Red/Black-Green (30)
Orange/White-Blue (36) 38 Orange/Black-Green (32) 38
40
39 Black/White-Green (38) 39 Black/White-Orange (34)
Red/White-Green (40) Orange/White-Blue (36) 40

1492-CABLE➊J 1492-CABLE➊K
Orange (5) 2
1 Black (1)
Green/Black (9) 4
3 White/Black (7)
Red/White (13) 6
5 Blue/Black (11)
White/Red (17) 8
7 Blue/White (15)
White/Red-Blue (37) 10
9 Blue/Red (19)
Orange/Green (21) 12
11 Red (3)
Green/Black-White (25) 14
13 White/Black-Red (23)
White/Red-Green (29) 16
15 Blue/Black-White (27)
17 Green/Black-Orange (31)
Black (1)
➋ Blue/White-Orange (33) 18
White (2) White/Black-Green (39) 20
19 White/Red-Orange (35)
Red (3) Blue (6) 22
21 White (2)
Green (4) Orange/Black (10) 24
23 Red/Black (8)
Orange (5) Green/White (14) 26
25 Black/White (12)
Blue (6)
Orange/Red (18) 28
27 Black/Red (16)
1 2 White/Black (7)
Black/White-Green (38) 30
29 Red/Green (20)
Red/Black (8) 31 Green (4)
Green/Black (9) Black/White-Red (22) 32
33 Red/Black-White (24)
Orange/Black (10) Orange/Black-White (26) 34
Red/Black-Green (30) 36
35 Black/Red-Green (28)
Blue/Black (11)
Black/White (12) Black/White-Orange (34) 38
37 Orange/Black-Green (32)
Red/White (13) Red/White-Green (40) 40
39 Orange/White-Blue (36)
Green/White (14)
Blue/White (15)
Black/Red (16) 1 Blue (6)
Orange (5) 2
White/Red (17) 3 Red/Black (8)
1492-CABLE➊L White/Black (7) 4
Orange/Red (18) 5 Orange/Black (10)
Green/Black (9) 6
Blue/Red (19) 7 Black/White (12)
Blue/Black (11) 8
Red/Green (20) 9 NC
Orange/Green (21)
NC 10
11 Green/White (14)
Black/White-Red (22) Red/White (13) 12
13 Black/Red (16)
White/Black-Red (23) Blue/White (15) 14
15 Orange/Red (18)
Red/Black-White (24) White/Red (17) 16
17 Red/Green (20)
Green/Black-White (25) Blue/Red (19) 18
39 40 19 NC
Orange/Black-White (26) NC 20
21 Black/White-Red (22)
Blue/Black-White (27) Orange/Green (21) 22
23 Red/Black-White (24)
Black/Red-Green (28) White/Black-Red (23) 24

White/Red-Green (29)
25 Orange/Black-White (26)
Green/Black-White (25) 26
Red/Black-Green (30)
27 Black/Red-Green (28)
Blue/Black-White (27) 28
Green/Black-Orange (31)
29 NC
NC 30
Orange/Black-Green (32) 31 Red/Black-Green (30)
White/Red-Green (29) 32
1492-CABLE➊H Blue/White-Orange (33) Green/Black-Orange (31) 34
33 Orange/Black-Green (32)
Black/White-Orange (34) 35 Black/White-Orange (34)
Blue/White-Orange (33) 36
White/Red-Orange (35) 37 Orange/White-Blue (36)
White/Red-Orange (35) 38
Orange/White-Blue (36) 39 NC
NC 40
White/Red-Blue (37)
Black/White-Green (38)
White/Black-Green (39)
Red/White-Green (40) 1492-CABLE➊M
➊ Refer to footnote on page 149.
➋ Connector Pin reference. For the IFM end reference, refer to the table on page 151 and match the wire color to
the IFM Pin reference number.

Publication 1492-TD008D-EN-P -January 2009


144 Digital/Analog Programmable Controller Wiring Systems

Digital Cable Pinouts, Continued


Specifications, Continued

Jumper
Orange RTB White (2)
Black (1)
White (2) 1 A Blue/Red (19)
2 Red (3) Black (1) 2 1 White (2)
0 Red (3)
Green (4) 3
4 White/Black (7) 4 3 Red (3)
Orange (5) 1 Green (4)
Blue (6) 5 Red/Black (8) 6 5 Green (4)
6 White/Black (7) 2 Orange (5)
Red/Black (8) 7 3 Blue (6) Green/Black (9) 8 7 Orange (5)
8 Green/Black (9)
Orange/Black (10) 9 4 Blue/White (15) Orange/Black (10) 10 9 Blue (6)
10 Blue/Red (19) 5 Black/Red (16)
Black/White (12) 11 Blue/Black (11) 12 11 Blue/White (15)
12 Blue/Black (11) 6 White/Red (17)
Green/White (14) 13 Black/White (12) 14 13 Black/Red (16)
14 Red/White (13) 7 Orange/Red (18) White/Red (17)
Red/White (13) 16 15
Black/Red (16) 15 B White/Black (7)
16 Blue/White (15) Green/White (14) 18 17 Orange/Red (18)
Orange/Red (18) 17 Blue/Black (11)
18 White/Red (17) Red/Green (20) 20 19 Blue/Red (19)

1492-CABLE➊N 1492-CABLE➊T 1492-CABLE➊U

Orange (5)
1 Blue (6)
1 Black (1) 2
Red (3) 2
White/Black (7)
3 Red/Black (8)
3 Orange (5) 4
White/Black (7) 4
Green/Black (9)
5 Orange/Black (10)
5 Green/Black (9) 6
Blue/Black (11) 6
Blue/Black (11)
7 Black/White (12)
7 Red/White (13) 8
Blue/White (15) 8
Red/White (13)
9 Green/White (14)
9 White/Red (17) 10
Blue/Red (19) 10
Blue/White (15)
11 Black/Red (16)
11 Orange/Green (21) 12
White/Black-Red (23) 12
13 Green/Black-White (25) White/Red (17) 14
13 Orange/Red (18)
Blue/Black-White (27) 14
Blue/Red (19)
15 Red/Green (20)
15 White/Red-Green (29) 16
Green/Black-Orange (31) 16
Black/White-Red (22)
17 NC
17 Blue/White-Orange (33) 18
White/Red-Orange (35) 18 19 Orange/Green (21)
19 White/Red-Blue (37) NC 20
White/Black-Green (39) 20
21 White (2) White/Black-Red (23) 22
21 Red/Black-White (24)
Green (4) 22
Orange/Black-White (26)
23 NC
23 Blue (6) 24
Red/Black (8) 24 25 Green/Black-White (25)
25 Orange/Black (10) NC 26
Black/White (12) 26 27 Black/Red-Green (28)
27 Green/White (14) Blue/Black-White (27) 28
Black/Red (16) 28 29 NC
29 Orange/Red (18) Red/Black-Green (30) 30
Red/Green (20) 30 31 White/Red-Green (29)
31 Black/White-Red (22) NC 32
Red/Black-White (24) 32
Green/Black-Orange (31)
33 Orange/Black-Green (32)
33 Orange/Black-White (26) 34
Black/Red-Green (28) 34 35 NC
35 Red/Black-Green (30) Black/White-Orange (34) 36
Orange/Black-Green (32) 36
NC
37 Blue/White-Orange (33)
37 Black/White-Orange (34) 38
Orange/White-Blue (36) 38
White/Red-Orange (35) 40
39 Orange/White-Blue (36)
Red/White-Green (40) 40
39 Black/White-Green (38)

1492-CAB➊R71
1492-CABLE➊R
NC 2 1 Black (1)
White (2) 4 3 Red (3)
Green (4) 6 5 Orange (5)
Blue (6) 8 7 White/Black (7)
Red/Black (8) 10 9 Green/Black (9)
Black/White (12) 12 11 Blue/Black (11)
Green/White (14) 14 13 Red/White (13)
White (2) 1
Orange RTB Black/Red (16) 16 15 Blue/White (15)
2 Red (3) Orange/Red (18) 18 17 White/Red (17) White (2) 2 1 Red (3)
Green (4) 3
4 Orange (5) NC 20 19 Blue/Red (19) Green (4) 4 3 Orange (5)
Blue (6) 5 Blue (6) 6 5 White/Black (7)
6 White/Black (7)
Red/Black (8) 7 1492-CABLE➊V Red/Black (8) 8 7 Green/Black (9)
8 Green/Black (9)
NC 9 Orange/Black (10) 10 9 Black (1)
10 NC
Black/White (12) 11 Black/White (12) 12 11 Blue/Black (11)
12 Blue/Black (11) Red/White (13)
Green/White (14) 13 Green/White (14) 14 13
14 Red/White (13) Blue/White (15)
Black/Red (16) 15 Black/Red (16) 16 15
16 Blue/White (15) Orange/Red (18) 18 17 White/Red (17)
Orange/Red (18) 17
18 White/Red (17) Red/Green (20) 20 19 Blue/Red (19)

1492-CABLE➊S 1492-CABLE➊W
➊ Refer to footnote on page 149.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 145

Digital Cable Pinouts, Continued


Specifications, Continued

Orange (5) 2 1 Blue (6)


White/Black (7) 4 3 Red/Black (8)
Green/Black (9) 6 5 Orange/Black (10)
Blue/Black (11) 8 7 Black/White (12)
Red/White (13) 10 9 Green/White (14)
Green (4) 2 1 Red (3) Blue/White (15) 12 11 Black/Red (16)
Blue (6) 4 3 Orange (5) White/Red (17) 14 13 Orange/Red (18)
Blue/Red (19) 16 15 Red/Green (20)
Red/Black (8) 6 5 White/Black (7) Orange/Green (21) 18 17 Black/White-Red (22)
Orange/Black (10) 8 7 Green/Black (9) White/Black-Red (23) 20 19 Red/Black-White (24)
Green/Black-White (25) 22 21 Orange/Black-White (26)
Black (1) 10 9 White (2)
Blue/Black-White (27) 24 23 Black/Red-Green (28)
Black/White (12) 12 11 Blue/Black (11) White/Red-Green (29) 26 25 Red/Black-Green (30)
Green/White (14) Green/Black-Orange (31) 28 27 Orange/Black-Green (32)
14 13 Red/White (13) Blue/White-Orange (33) 30 29 Black/White-Orange (34)
Black/Red (16) 16 15 Blue/White (15) White/Red-Orange (35) 32 31 Orange/White-Blue (36)
18 17 White/Red (17) NC 34 33 NC
Orange/Red (18) NC 36 35 NC
Blue/Red (19) 20 19 Red/Green (20)

1492-CABLE➊X 1492-CABLE➊Y

White/Black (7) 2 1 Orange (5)


Blue/Black (11) 4 3 Green/Black (9)
Blue/White (15) 6 5 Red/White (13)
Blue/Red (19) 8 7 White/Red (17) Black (1)
White/Black-Red (23) 10 9 Orange/Green (21) White (2) 1
2 Red (3)
Blue/Black-White (27) 12 11 Green/Black-White (25) Green (4) 3
4 Orange (5)
Green/Black-Orange (31) 14 13 White/Red-Green (29) Blue (6) 5
6 White/Black (7)
Black (1) White/Red-Orange(35) 16 15 Blue/White-Orange (33) White/Black-Green (39) Red/Black (8) 7
8 Green/Black (9)
18 17 Orange/Black (10) 9
Red(3) Red/Black (8) 20 19 Blue (6) White/Red-Blue (37) 10 Blue/Red (19)
Black/White (12) 11
Black/White (12) 22 21 Orange/Black (10) 12 Blue/Black (11)
Green/White (14) 13
Black/Red (16) 24 23 Green/White (14) 14 Red/White (13)
Red/Green (20) Black/Red (16) 15
26 25 Orange/Red (18) 16 Blue/White (15)
Red/Black-White (24) 28 27 Black/White-Red (22) Orange/Red (18) 17
18 White/Red (17)
Black/Red-Green (28) 30 29 Orange/Black-White (26)
Orange/Black-Green (32) 32 31 Red/Black-Green (30) 1492-CABLE➊CR
Orange/White-Blue (36) 34 33 Black/White-Orange (34)
White (2) 36 35
Red/White-Green (40) (Red RTB)
Green (4) Black/White/Green (38)

1492-CABLE➊Z
Orange/Black/White (26)
Green/Black/Orange (31)

Orange/White/Blue (36)
White/Black/Green (39)
Black/White/Green (38)
White/Red/Orange (35)

Red/White/Green (40)
Red/Black/Green (30)
Black/White/Red (22)
Blue/Black/White (27)

White/Red/Blue (37)
White/Black/Red (23)
White/Red/Blue (37)

Orange/Black (10)

Green/White (14)

Orange/Red (18)
Black/White (12)

White/Red (17)
Red/Green (20)

White/Black (7)
Red/White (13)
Blue/Black (11)
Black/Red (16)

Red/Black (8)
Red/Black (8)

White (2)
Black (1)

Blue (6)

Row B
Row B (High Row)
(High Row) 1 2 3 4 5 6 7 8 9 10 11 12 13
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Row A 1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Row A (Low Row)
(Low Row)
Black/White (12)

Black/Red/Green (28)

Black/White/Green (38)
White (2)

Black (1)
Red (3)

Black/Red (16)
Red/Green (20)
Red/Black/White (24)

Orange/Black/Green (32)
Green (4)

Black/White/Orange (34)
Blue/White (15)
Green/White (14)

Orange/Green (21)
Orange/Black (10)

White/Red/Green (29)
Blue (6)

Blue/Red (19)
Blue/White/Orange (33)
Orange/Red (18)

Green/Black/White (25)

Green/Black (9)
Red (3)
Green (4)

Orange (5)

1492-CAB➊A62 1492-CAB➊B62
➊ Refer to footnote on page 149.

Publication 1492-TD008D-EN-P -January 2009


146 Digital/Analog Programmable Controller Wiring Systems

Digital Cable Pinouts, Continued


Specifications, Continued Orange/Black (10)

Orange/Black (10)
Blue/White (15)
Blue/Black (11)

Blue/Black (11)
Red/White (13)

Red/White (13)
White/Red (17)
Red/Black (8)

Red/Black (8)
Orange (5)

Orange (5)
White (2)
White (2)

Red (3)

Red (3)
Row B Row B
(High Row) (High Row)
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10

Row A 1 2 3 4 5 6 7 8 9 Row A 1 2 3 4 5 6 7 8 9 10 11
(Low Row) (Low Row)

Orange/Red (18)
Black/Red (16)
Green/White (14)
Black/White (12)
Blue/Red (19)
Red/Green (20)
Green/Black (9)
White/Black (7)

Black (1)
Green (4)
Blue (6)
Orange/Black (10)
Green/White (14)
Black/White (12)
Blue/Red (19)
Red/Green (20)
Green/Black (9)
White/Black (7)
Blue (6)
Green (4)
Black (1)

Orange/Red (18)
Blue/White (15)

Blue/Black (11)
White/Red (17)

Red/White (13)

Orange/Black (10)
Black/Red (16)

Red/Black (8)

Black/White (12)
Blue/White (15)

Red/White (13)
Black/Red (16)

Blue/Red (19)
Red/Black (8)
White (2)
Black (1)

White (2)
Black (1)

Blue (6)
1492-CAB➊A64 Row B 1492-CAB➊B64
(High Row) Row B
1 2 3 4 5 6 7 8 9 10 (High Row)
1 2 3 4 5 6 7 8 9 10
Row A 1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
(Low Row) Row A
(Low Row)
Red (3)
Green (4)
Orange (5)
Blue (6)
White/Black (7)
Green/Black (9)
Blue/Red (19)
Red/Green (20)
Black/White (12)
Green/White (14)

Red (3)
Green (4)
Orange (5)
White/Black (7)
Green/Black (9)
White/Red (17)
Orange/Red (18)

Red/Green (20)
Green/White (14)
Blue/Black (11)
1492-CAB➊C64 1492-CAB➊F64

1 Red (3) 1 Red (3)


Green (4) 2
Green (4) 2
3 Orange (5) 3 Orange (5)
Blue (6) 4 Blue (6) 4 Orange/Black (10)
5 White/Black (7) 5 White/Black (7) Red (3) 5
Black (1)
Red/Black (8) 6 Red/Black (8) 6 6
7 Green/Black (9) 7 Green/Black (9) White/Black (7) 7
Orange (5)
Orange/Black (10) 8 Orange/Black (10) 8
Black (1)
8
9 Blue/Black (11) 9
White (2)
Blue/Red (19) 10
9
Green/Black (9)
Black/White (12) 10 Black/White (12) 10
Red/Green (20) 11
11 Red/White (13) 11
Blue/Black (11) 12 Red/White (13)
Green/White (14) 12 Green/White (14) 12
13
13 Blue/White (15) 13 Red/White (13) Blue/Black (11) 14 White/Red (17)
Black/Red (16) 14 Black/Red (16) 14
15 White/Red (17) 15 Blue/White (15) Blue/White (15)
Orange/Red (18) 16
Black (1) Orange/Red (18) 16
17 17 White/Red (17)
Blue/Red (19) 18
White (2)
Blue/Red (19) 18

Red/Green (20) Red/Green (20)


1492-CAB➊B69 1492-CAB➊C69
1492-CAB➊A69
Black (1)
Red (3)
1 White (2) 1 White (2)
2 Red (3) 2
Orange (5)
3 Green (4) 3 Green (4)
4 Orange (5) 4
White/Black (7)
5 Blue (6) 5 Blue (6)
6 White/Black (7) 6
Green/Black (9)
7 Red/Black (8) 7 Red/Black (8)
8 Green/Black (9) 8
Blue/Black (11)
9 Black/White (12) 9 Orange/Black (10)
10 Blue/Black (11) 10
Red/White (13)
11 Green/White (14) 11 Black/White (12)
12 Red/White (13) 12
Blue/White (15)
13 Black/Red (16) 13 Green/White (14)
14 Blue/White (15) 14
White/Red (17)
15 Orange/Red (18) 15 Black/Red (16)
16 White/Red (17) 16
17 NC 17 Orange/Red (18)
NC 18 Blue/Red (19) 18

Red/Green (20)
1492-CAB➊D69 1492-CAB➊E69

White (1)
Green (4) 2
1 Red (3) Green (4) 2
1 Red (3) 1 Black (2)
3 Orange (5) 3 Orange (5) Red (3) 2
Blue (6) 4 Blue (6) 4 Orange (5) 4
3 Green (4)
Red/Black (8)
5 White/Black (7) 5 White/Black (7) 5 Blue (6)
6 Red/Black (8) 6
White/Black (7) 6
Orange/Black (10)
7 Green/Black (9) 7 Green/Black (9) 7 Red/Black (8)
8 Orange/Black (10) 8
Green/Black (9) 8
Black/White (12)
9 Blue/Black (11) 9 Blue/Black (11) 9 Orange/Black (10)
10 Black/White (12) 10
Blue/Red(19) 10
Green/White (14)
11 Red/White (13) 11 Red/White (13) 11 Black/White (12)
12 Green/White (14) 12
Blue/Black (11) 12
Black/Red (16)
13 Blue/White (15) 13 NC 13 Green/White (14)
14 NC 14
Red/White(13) 14
Orange/Red (18)
15 White/Red (17) 15 NC 15 Black/Red (16)
16 NC 16
Blue/White(15) 16
NC
17 NC 17 Blue/Red (19) 17 Orange/Red (18)
18 Red/Green (20) 18
White/Red (17) 18

1492-CAB➊F69 1492-CAB➊G69 1492-CAB➊H69

➊ Refer to footnote on page 149.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 147

Digital Cable Pinouts, Continued


Specifications, Continued
L R
1 Orange (5)
White/Black (7) 1 Blue (6)
2
3 Green/Black (9) Red/Black (8) 2
Blue/Black (11) 4 3 Orange/Black (10)
5 Red/White (13) Black/White (12) 4
Blue/White (15) 6 5 Green/White (14)
7 White/Red (17) Black/Red (16) 6 7 Orange/Red (18)
Blue/Red (19) 8
9 White/Black/Green (39) Red/Green (20) 8 9 Black/White/Green (38)
White/Black/Red (23) 10 White/Red/Blue (37)
11 Orange/Green (21) Red/Black/White (24) 10 Red/White/Green (40)
Blue/Black/White (27) 12 11 Black/White/Red (22)
13 Green/Black/White (25) Black/Red/Green (28) 12
Green/Black/Orange (31) 14 13 Orange/Black/White (26)
15 White/Red/Green (29) Orange/Black/Green (32) 14
White/Red/Orange (35) 16 15 Red/Black/Green (30)
17 Blue/White/Orange (33) Orange/White/Blue (36) 16
Black (1) 17 Black/White/Orange (34)
18 White (2)
Red (3) 18
1492-CAB➊J69 ➋
Green (4)

L R
Red (3)
1 Black (1) 1 White (2)
Orange (5) 2 Blue (6) 2 Green (4)
3 White/Black (7)
Green/Black (9) 4 3 Red/Black (8)
5 Blue/Black (11) Orange/Black (10) 4
Red/White (13) 6 5 Black/White (12)
7 Blue/White (15) Green/White (14) 6
White/Red (17) 8 7 Black/Red (16)
9 Blue/Red (19) Orange/Red (18) 8 9
Orange/Green (21) 10 Red/Green (20)
11 White/Black/Red (23) Black/White/Red (22) 10
Green/Black/White (25) 12 11 Red/Black/White (24)
13 Blue/Black/White (27) Orange/Black/White (26) 12
White/Red/Green (29) 14 13 Black/Red/Green (28)
15 Green/Black/Orange (31) Red/Black/Green (30) 14
Blue/White/Orange (33) 16 15 Orange/Black/Green (32)
17 White/Red/Orange (35) Black/White/Orange (34) 16
White/Black/Green (39) 17 Orange/White/Blue (36)
18 Black/White/Green (38)
White/Red/Blue (37) 18
Red/White/Green (40)

1492-CAB➊K69 ➋
1 Black (1) Black (1)
White (2) 1
Blue/Black (11) 2 Red (3) 2
White (2)
3 Black/White (12) 3
Red/White (13) 4 Green (4)
5
Orange (5) 4
Green (4) Green/White (14) 5 Blue (6)
6 White/Black (7) 6
Orange (5) 7 NC 7 Red/Black (8)
NC 8 Green/Black (9) 8
9 NC 9 Orange/Black (10)
NC 10 Blue/Red (19)
11 10
NC Red/Green (20) 11 Black/White (12)
NC 12 Blue/Black (11) 12
13 Red/Black (8) 13
Green/Black (9) Green/White (14)
Blue/White (15) 14 Red/White (13) 14
15 15
Black/Red (16) Black/Red (16)
White/Red (17) 16 Blue/White (15) 16
17 Orange/Red (18) 17 Orange/Red (18)
Blue/Red (19) White/Red (17)
18 18
Red/Green (20)
Red (3) 19
1492-CAB➊L69 Orange (5) 18
37 Green (4) 1492-CAB➊M69
NA 17
36 Blue (6)
White/Black (7) 16
35 NA
Green/Black (9) 15
34 Red/Black (8)
NA 14
33 Orange/Black (10)
Blue/Black (11) 13
32 NA
Red/White (13) 12
31 Black/White (12)
NA 11
30 Green/White (14)
Blue/White (15) 10
29 NA
28 Black/Red (16)
White/Red (17) 9
27 Orange/Red (18)
NA 8
26 NA
NA 7
25 NA
NA 6
24 NA
NA 5
23 NA
NA 4 22
NA
Red/Green (20) 3 21
Blue/Red (19)
NA 2 20
White (2)
Black (1) 1

Flex D-shell End


1492-CAB➊A94
➊ Refer to footnote on page 149.
➋ 1492-CAB➊K69 and 1492-CAB➊J69 are made up of two (2) individual 18-pin terminal blocks connected to a single cable assembly.

Publication 1492-TD008D-EN-P -January 2009


148 Digital/Analog Programmable Controller Wiring Systems

Digital Cable Pinouts, Continued


Specifications, Continued
21
42 Cable Wiring Table Conductor for 1492-CAB➊B94

62 1 2 Connector 62 Conductor Color Code Connectors 40- Connector 62 Conductor Color Code Connectors
Pin D–Shell Pin Reference, Pin D–Shell 40-Pin
Reference, End 2 Reference, Reference,
End 1 End 1 End 2
15 Black 1 39 Orange/Green 21
23 White 2 28 Black/White/Red 22
16 Red 3 40 White/Black/Red 23
24 Green 4 29 Red/Black/White 24
17 Orange 5 41 Green/Black/White 25
4 Blue 6 45 Orange/Black/White 26
18 White/Black 7 42 Blue/Black/White 27
5 Red/Black 8 46 Black/Red/Green 28
19 Green/Black 9 59 White/Red/Green 29
39 40 6 Orange/Black 10 47 Red/Black/Green 30
43
1 20 Blue/Black 11 60 Green/Black/Orange 31
22
End 1 End 2 7 Black/White 12 48 Orange/Black/Green 32
1492-CAB➊B94 21 Red/White 13 61 Blue/White/Orange 33
8 Green/White 14 49 Black/White/Orange 34
36 Blue/White 15 62 White/Red/Orange 35
25 Black/Red 16 50 Orange/White/Blue 36
37 White/Red 17 57 White/Red/Blue 37
26 Orange/Red 18 1 Black/White/Green 38
38 Blue/Red 19 58 White/Black/Green 39
27 Red/Green 20 11 12 13 14 15 16 17 18 19 20 2 Red/White/Green 40

21 22 23
White (2) Green/White (14)
Red (3) Black/White (12)
Red/White (13)
Green (4) Blue/White (15)
Orange (5)
Blue (6)

24 25 26
White/Red (17)
White/Black (7)
Blue/Red (19)
Red/Black (8) Red/Green (20)
Green/Black (9) Orange/Red (18)

Black (1)
21 22 23

Green/White (14)
11 12 13 14

White (2)
Black/White (12) Orange/Black (10)
Red (3) Red/White (13)
Blue/White (15)
Green (4) 1492-CABA7H
Orange (5)
Orange/Black (10) 1 Red/Black (8) 9
24 25 26

White/Red (17)
Black (1) 2 White (2) 10
Blue/Red (19)
Red/Green (20) Green/White (14) 3 Red (3) 11
15 16 17 18

Blue (6) Black/White (12)


Orange/Red (18) Red/White (13) 4 Green (4) 12
White/Black (7) Blue/White (15) 5 Green/Black (9) 13
Red/Black (8) White/Red (17) 6 Orange (5) 14
Blue/Red (19)
Red/Green (20) 7 Blue (6) 15
Green/Black (9) Orange/Red (18) 8 16
White/Black (7)

1492-CABB7H 1492-CABA7S
➊ Refer to footnote on page 149.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 149

Digital Cable I/O Module-Ready Cables


WD3 Writer Designed tag 3Digital/Analog Programmable Controller Wiring Systems

Specifications, Continued

The I/O module-ready cables have a pre-wired wiring arm or removable


terminal block on one end to connect the programmable controller I/O
module and 12…40 individually colored #18 or #22 AWG conductors on the
other. These cables provide the convenience of a pre-wired I/O module
connector, while still allowing the flexibility to wire to standard terminal
blocks.
Pre-wired I/O module connectors include:
• Catalog Number 1746-N3 40-point plug-in connector (Catalog
Number CABLE➊N3)
• Bulletin 1746 16-point removable terminal blocks in Red, Blue, and
Orange (Catalog Number CABLE➊RTBR, ➊RTBB, ➊RTBO)
• Catalog Number 1756-TBCH 36-point removable terminal block
(Catalog Number CABLE➊TBCH)
• Catalog Number 1756-TBNH 20-point removable terminal block
(Catalog Number CABLE➊TBNH)
• Catalog Number 1769-RTBN10 8-point removable terminal block
(Catalog Number CABLE➊RTN10)
• Catalog Number 1769-RTBN18 20-point removable terminal block
(Catalog Number CABLE➊RTN18)
• Catalog Number 1769-RTBN32I and 1769-RTBN320 for 32-point 1769
I/O modules
• Catalog Number 1771-WH 16-point wiring arm (Catalog
Number CABLE➊WH)
• Catalog Number 1771-WN 32-point wiring arm (Catalog
Number CABLE➊WN)
• Catalog Number 1771-WHF 16-point fused wiring arm (with fuses)
(Catalog Number CABLE➊WHF)
• Catalog Number 1771-WD 6-point wiring arm (Catalog
Number CABLE➊WD)
• Catalog Number 1771-WA 8-point wiring arm (Catalog
Number CABLE➊WA)
➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length
into the catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog
Number 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also
refer to Build-to-Order Length Cables on page 65.

Publication 1492-TD008D-EN-P -January 2009


150 Digital/Analog Programmable Controller Wiring Systems

Digital Cable I/O Module-Ready Cables, Continued


Specifications, Continued
I/O Module-Ready Cable Specifications
Catalog Number Cable Insulation Number of Conductor Nominal Outer I/O Module
Lengths Rating Conductors Size Diameter Connector
1492-CABLE➊N3 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.2 mm (0.44 in.) 1746-N3 (40-Point) Plug-in Connector
1492-CABLE➊RTBB 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1746-RT25B Blue Removable Terminal Block
1492-CABLE➊RTBO 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1746-RT25C Orange Removable Terminal
Block
1492-CABLE➊RTBR 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1746-RT25R Red Removable Terminal Block
1492-CABLE➊TBCH 1.0, 2.5, 5.0 m 300V 80°C 40 #18 AWG 14.1 mm (0.55 in.) 1756-TBCH (36-Point) Removable Terminal
Block
1492-CABLE➊TBNH 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1756-TBNH (20-Point) Removable Terminal
Block
1492-CAB➊T62 1.0, 2.5, 5.0 m 300V 80°C 25 #18 AWG 13.2 mm (0.52 in.) 1762-L40xxx Output Connector
1492-CAB➊X62 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 1762-L40xxx Input Connector
1492-CAB➊T64 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1764-24AWA, -24BWA Output Terminal
1492-CAB➊U64 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1764-28BXB Output Terminal
1492-CAB➊W64 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-24AWA, -BWA Input Terminal
1492-CAB➊X64 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 1764-28BXBH Input Terminal
1492-CAB➊RTN10 1.0, 2.5, 5.0 m 300V 80°C 12 #18 AWG 9.0 mm (0.36 in.) 1769-RTBN10 Removable Terminal Block
1492-CAB➊RTN18 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1769-RTBN18 (20-Point) Removable Terminal
Block
1492-CAB➊RTN32I 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) (2) 1769-RTBN18 (20-Point) Removable
Terminal Block
1492-CAB➊RTN32O 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) (2) 1769-RTBN18 (20-Point) Removable
Terminal Block
1492-CAB➊G94 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 37-pin male D-shell➋
1492-CAB➊H94 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 62-pin male D-shell➌
1492-CABLE➊WA 1.0, 2.5, 5.0 m 300V 80°C 12 #18 AWG 9.0 mm (0.36 in.) 1771-WA (8-Point/10 Terminal) Wiring Arm
1492-CABLE➊WD 1.0, 2.5, 5.0 m 300V 80°C 12 #18 AWG 9.0 mm (0.36 in.) 1771-WD (6-Point/12 Terminal) Wiring Arm
1492-CABLE➊WH 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1771-WH (16-Point/21 Terminal) Wiring Arm
1492-CABLE➊WHF 1.0, 2.5, 5.0 m 300V 80°C 20 #18 AWG 11.4 mm (0.45 in.) 1771-WHF (16-Point/21 Terminal) Fused
Wiring Arm
1492-CABLE➊WN 1.0, 2.5, 5.0 m 300V 80°C 40 #18 AWG 14.1 mm (0.55 in.) 1771-WN (32-Point/40 Terminal) Wiring Arm
➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length
into the catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog
Number 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also
refer to Build-to-Order Length Cables on page 65.
➋ Mates with Bul. 1794 Flex D-shell style base: Cat. No. 1794-TB37DS.
➌ Mates with Bul. 1794 Flex D-shell style base: Cat. No. 1794-TB62DS.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 151

Digital Cable I/O Module-Ready Cables, Continued


Specifications, Continued
Wire Colors for I/O Module-Ready Cables and IFM Pint Reference Number for I/O
Ready Pre-Wired Cables

IFM Pin Wire Color IFM Pin Wire Color


Reference Base/Stripe/Stripe Reference Base/Stripe/Stripe
Number Number
1 Black 21 Orange/Green
2 White 22 Black/White/Red
3 Red 23 White/Black/Red
4 Green 24 Red/Black/White
5 Orange 25 Green/Black/White
6 Blue 26 Orange/Black/White
7 White/Black 27 Blue/Black/White
8 Red/Black 28 Black/Red/Green
9 Green/Black 29 White/Red/Green
10 Orange/Black 30 Red/Black/Green
11 Blue/Black 31 Green/Black/Orange
12 Black/White 32 Orange/Black/Green
13 Red/White 33 Blue/White/Orange
14 Green/White 34 Black/White/Orange
15 Blue/White 35 White/Red/Orange
16 Black/Red 36 Orange/White/Blue
17 White/Red 37 White/Red/Blue
18 Orange/Red 38 Black/White/Green
19 Blue/Red 39 White/Black/Green
20 Red/Green 40 Red/White/Green

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length
into the catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog
Number 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also
refer to Build-to-Order Length Cables on page 65.

Publication 1492-TD008D-EN-P -January 2009


152 Digital/Analog Programmable Controller Wiring Systems

Digital Cable I/O Module-Ready Cables, Continued


Specifications, Continued
Below is the wire color table for I/O module-ready cables. Each conductor is
given a reference number in the table on page 151. The reference number is
used in the illustrations that follow to indicate the corresponding screw
terminal.
1492-CABLE➊N3 1492-CABLE➊TBCH 1492-CABLE➊TBNH 1492-CABLE➊WN 1492-CABLE➊WH 1492-CABLE➊WF
1 2
2 1 2 1
4 3 1 1
2 2
6 5 4 3 3 3 CAUTION A
4 4 1 A DISCONNECT 1
8 7 6 5 5 5 POWER
B
6 6 2 B BEFORE
SERVICING 2
10 9 7 7 FUSES C
3
8 7 8 8
9 3 C ALL FUSES
D
12 11 10
9
D
30-250V

10 9 10 11
14 13 11 00
00
4
12 11 12 12 4 01
16 15 14
13 13
5 01
5
18 17 14 15 02
14 13 16
15
6 02
6
20 19 16 17 17 03
03
16 15 18 18 7 04
7
22 21 19 19 8
04
8
24 23 18 17 20 20
21 21 05
05
9
22 9
26 25 20 19 22 23 23 10 06
06
10
24 07
28 27 24 25 25 11
07
11
10
30 29 26 26
27 27 12
10
12
11
32 31 28 28
29 29 13
11
13
12 12
34 33 30 30
31 31 14 13
14
13
36 35 32 32
33 33 15 14
15
14
34 34 16 16
35 35 15 15
36 36 17 17
38
37 37 18
16 16
18
39 40 38 39 39 17 17
40 19 19
40 E E
20
20

1492-CABLE➊RTBR
1492-CABLE➊RTBB
1492-CABLE➊WD 1492-CABLE➊WA 1492-CABLE➊RTBO 1492-CAB➊T62 1492-CAB➊X62
Green/Black/White

Orange/Black/White
Green/Black/While
White/Black/Red
Black/White/Red

Red/Black/White

1
White/Red/Green

White/Black/Red
Black/White/Red
Blue/Black/White
Black/Red/Green
1

Red/Black/White
1
Orange/Green

Orange/Green
Orange/Red

Ornage/Red
2
Red/Green
Blue/White

Red/Green
White/Red

2
Black/Red

White/Red
2

Black/Red
Blue/Red

Blue/Red
3
White

4
Black

Black
3 3 5
4 4 6
7 Row B
5 5 8 (High Row) Row B
9 (High Row)
1 2 3 4 5 6 7 8 9 1011 1213
6 6 10 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 41 5
11 Row A 1 2 3 4 5 6 7 8 9 10 11 12
7 7 12 (Low Row) Row A 1 2 3 4 5 6 7 8 9 10 11 1213 14
13 (Low Row)
8 14
8
9 15

Red
White
Blue
Green/Black
Blue/White
Green/White
Red/White

Orange/Black

Green
Blue/Black

White/Black
Orange
Black/White

Red/Black
Orange

White/Black
Red/Black
Blue

Orange/Black

Red/White
Green//White
Green
Red

Black/White
Blue/Black
Green/Black

9 16
10 17
10 18
11
12
1492-CAB➊T64 1492-CAB➊U64
Orange/Green
Orange/Green

Green/White
Green/White

Orange/Red
Orange/Red

Blue/White

Red/Green
Red/Green

White/Red
Blue/White

White/Red

Red/White

Black/Red
Red/White

Black/Red

Blue/Red
Blue/Red
Black

Black

Row B Row B
(High Row) (High Row)
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10 11 Row A 1 2 3 4 5 6 7 8 9 10 11
Row A
(Low Row) (Low Row)
Green
Red
Orange

White/Black

Green/Black

Orange

Orange/Black

Black/White
Blue

Blue/Black
Red/Black
Red/Black

White/Black
Blue/Black
Black/White

White
Green

Red
White

Green/Black
Orange/Black
Blue

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m, and
050 = 5.0 m). Example: Catalog Number 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also refer to Build-to-Order Length
Cables on page 65.
➋ The 1492-CABRTN32F and -RTN320 are made up of two (2) individual 18-pin terminal blocks (L = Left, R=Right) connected to a single cable assembly.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 153

Digital Cable
Specifications, Continued
1492-CAB➊W64 1492-CAB➊X64 1492-CAB➊RTN10

White/Orange
White/Orange

White/Brown
White/Yellow
White/Green
White/Brown
White/Yellow
White/Green

White/Black
White/Black

White/Blue
White/Blue

White/Red
White/Red
1

Black
Black
3
4 6
5 2
Row B Row B 7 5
(High Row) (High Row) 6 8
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 8 10
9 7
10 12
11 9
Row A 1 2 3 4 5 6 7 8 9 Row A 1 2 3 4 5 6 7 8 9
(Low Row) 12 14
13 11
(Low Row)
White

Brown
Blue

Orange
Red

White

Brown
Violet

Blue

Orange
Gray

Red
Yellow

Violet
Gray
Green

Yellow

Green
1492-CAB➊RTN18 1492-CAB➊RTN32I 1492-CAB➊RTN320➋

3 1 L R
L R

4 2
1 2 2
1 1 22 1 1,2
1
2
21,22 21
2 2 21 3 23 22
6 4
3 5 4 4
3 3 24 3
4 23 5
3
5
4 4
25
23
25
24 24

8 6
5 7 6 6
5 5 26 5
6 25 7 7
6 6
27 27
26 26
7 28 8 28
10 8
7 9 8 8
7
9 9 30
7
9
8 27 9 9
8
10 10
29 29
28
30 30

12 10
9 11 10 10
11 11 32 11
10 29 11 11
12 12
31
33
31
32 32
12 12 12 31 13 13 33

14 12
11 13 14 14
13 13 34 13
14 33 15 15
14 14
35 35
34 34
16 36
16 14
13 15 16 16
15 15 36 15
16 35 17 17
16
37 37
36

17 17 38 17 18 18 38 38
18 16
15 17 18 18 18 37 19
20 19,20
39
40 39,40
17 19
20 18
Cable Wiring Table Conductor for 1492-CAB➊H94

62-Pin D-shell End Conductor Color Code 62-Pin D-Shell End Conductor Color Code
42 15 Black 39 Orange/Green
21
23 White 28 Black/White/Red
Red 19
62 16 Red 40 White/Black/Red
Orange 18
37 Green
NA 17
36 Blue 24 Green 29 Red/Black/White
White/Black 16
35 NA 17 Orange 41 Green/Black/White
Green/Black 15
34 Red/Black
33 Orange/Black 4 Blue 45 Orange/Black/White
NA 14
Blue/Black 13
32 NA 18 White/Black 42 Blue/Black/White
Red/White
31 Black/White
12 5 Red/Black 46 Black/Red/Green
NA 11
30 Green/White
29 NA 19 Green/Black 59 White/Red/Green
Blue/White 10
28 Black/Red 6 Orange/Black 47 Red/Black/Green
White/Red 9
27 Orange/Red
NA 8 20 Blue/Black 60 Green/Black/Orange
26 NA
NA 7
25 NA 7 Black/White 48 Orange/Black/Green
NA 6
24 NA 21 Red/White 61 Blue/White/Orange
NA 5
23 NA
NA 4 22
NA 8 Green/White 49 Black/White/Orange
Red/Green 3 21
Blue/Red 36 Blue/White 62 White/Red/Orange
NA 2 20
White
Black 1 25 Black/Red 50 Orange/White/Blue
43 37 White/Red 57 White/Red/Blue
1492-CAB➊G94 ➌ 1
22 26 Orange/Red 1 Black/White/Green
End 38 Blue/Red 58 White/Black/Green
1492-CAB➊H94 ➌ 27 Red/Green 2 Red/White/Green

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number (010 = 1.0 m, 025 = 2.5 m, and
050 = 5.0 m). Example: Catalog Number 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also refer to Build-to-Order Length
Cables on page 65.
➋ The 1492-CAB➊RTN32I and -RTN320 are made up of two (2) individual 18-pin terminal blocks (L = Left, R=Right) connected to a single cable assembly.
➌ Cable 1492-CAB➊G94 and -CAB➊H94 do not follow the cable wire color code chart on page151.

Publication 1492-TD008D-EN-P -January 2009


154 Digital/Analog Programmable Controller Wiring Systems

Digital Cable IFM-Ready Cable Specifications


Specifications, Continued

IFM-ready cables have a cable connector on one end to attach to the IFM and
either 20 or 40 individually colored conductors on the other end (Catalog
Numbers CABLE➊P and CABLE➊Q, respectively). These cables allow the
IFM to be used in specialty applications that require a custom connection.

IFM-Ready Cable Specifications


Catalog Cable Lengths Insulation Number of Conductor Nominal Outer Current/ Compatible
Number Rating Conductors Size Diameter Conductor IFM Catalog
Numbers
1492-CABLE➊P 1.0, 2.5, 5.0 m 300V 80°C 20 #22 AWG 9.0 mm (0.36 in.) 2A 1492-IFM20_ _ _
1492-XIM20_ _ _
1492-CABLE➊Q 1.0, 2.5, 5.0 m 300V 80°C 40 #22 AWG 11.7 mm (0.46 in.) 2A 1492-IFM40_ _ _
1492-XIM40_ _ _

Each colored conductor is connected to one pin of the molded cable


connector as listed in the tables below.

1492-CABLE➊P
Connector Pin Wire Color Connector Pin Wire Color
Number Base/Stripe/Stripe Number Base/Stripe/Stripe
1 Black 11 Blue/Black
2 White 12 Black/White
3 Red 13 Red/White
4 Green 14 Green/White
5 Orange 15 Blue/White
6 Blue 16 Black/Red
7 White/Black 17 White/Red
8 Red/Black 18 Orange/Red
9 Green/Black 19 Blue/Red
10 Orange/Black 20 Red/Green

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the desired cable length into the
catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CABLE025P is
for a 2.5 m, 20 conductor IFM-ready cable. Also refer to Build-to-Order Length Cables on page 65.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 155

Digital Cable IFM-Ready Cable Specifications, Continued


Specifications, Continued
1492-CABLE➊Q
Connector Pin Wire Color Connector Pin Wire Color
Number Base/Stripe/Stripe Number Base/Stripe/Stripe
1 Black 21 Orange/Green
2 White 22 Black/White/Red
3 Red 23 White/Black/Red
4 Green 24 Red/Black/White
5 Orange 25 Green/Black/White
6 Blue 26 Orange/Black/White
7 White/Black 27 Blue/Black/White
8 Red/Black 28 Black/Red/Green
9 Green/Black 29 White/Red/Green
10 Orange/Black 30 Red/Black/Green
11 Blue/Black 31 Green/Black/Orange
12 Black/White 32 Orange/Black/Green
13 Red/White 33 Blue/White/Orange
14 Green/White 34 Black/White/Orange
15 Blue/White 35 White/Red/Orange
16 Black/Red 36 Orange/White/Blue
17 White/Red 37 White/Red/Blue
18 Orange/Red 38 Black/White/Green
19 Blue/Red 39 White/Black/Green
20 Red/Green 40 Red/White/Green

➊ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the desired cable length into the
catalog number (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Catalog Number 1492-CABLE025P is
for a 2.5 m, 20 conductor IFM-ready cable. Also refer to Build-to-Order Length Cables on page 65.

Publication 1492-TD008D-EN-P -January 2009


156 Digital/Analog Programmable Controller Wiring Systems

Analog IFM Specifications (1492-AIFM-xx and 1492-RAIFM-xx))

AIFM Page No. for Page No. for AIFM Page No. for Page No. for AIFM Page No. for Page No. for
Catalog Number Application Notes, Specifications Catalog Number Application Specifications Catalog Number Application Specifications
and Pinout Notes, and Pinout Notes, and Pinout
1492-AIFM8-3, -RAIFM8-3 158 188 1492-AIFM4C-F-5 160 188 1492-AIFM16-F-5 164 188
1492-AIFM4-3, -RAIFM4-3 157 188 1492-AIFM4I-F-5 161 188 1492-AIFMPI 166 188
1492-AIFM6S-3, -RAIFM6S-3 158 188 1492-AIFM8-F-5 162 188 1492-AIFMQS 165 188
1492-AIFM6TC-3 159 188 1492-AIFM16-F-3 163 188 — — —

For all AIFM dimensions, refer to page 187.


For general Adhesive Label Card information, refer to page 181.
For Field-Side Wiring Diagrams, refer to the Wiring System web page at
http://www.ab.com/raise. Refer to page 186 for specific platform web site
information. Refer to the online documentation for new product information.

Symbols and Terminal Identification Conventions Used


Throughout the Pinout Section

1492-AIFM Field-Side Terminal ➊


1492 Pre-Wired Cable

I/O Module Connection

Fuse and Blown Fuse Indicator


One-Pole DIP Switch

Two-Pole DIP Switch


1492-AIFM and Cable Connection (D-Shell Pin)

Test Point

➊ Field-Side Terminal Identification Convention:

C1 C2 C3 C4 C5 . . .

B1 B2 B3 B4 B5 . . . B1 B2 B3 B4 B5 . . .

A1 A2 A3 A4 A5 . . .
A1 A2 A3 A4 A5 . . .

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 157

1492-AIFM4-3 Pinout
1492-RAIFM4-3
2 A3
Feed-Through 4-channel Input, Output or 2-in/2-out B3
Combination with 3 Terminals/Channel 1 A7
B7
TP1 TP2
8 A1

15 A2

TP3 TP4
14 A5

13 A6

Application Notes TP5 TP6


12 B1

1. Compatibility — To ensure proper operation


11 B2
with the I/O module, do not exceed the voltage
TP7 TP8
and current ratings of the AIFM. 10 B5
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the 9 B6

Wiring System web site information on page 186. D-Shell Housing


A4
3. DIP Switches — Selectable resistors are available A8
to current limit the Catalog Numbers 1771-OFE2 B4
and -OFE3 output circuits. By opening the switch B8

(off or down position), 250 Ω series impedance is


inserted into the output circuit. Default switch
position is on/closed/no series impedance. Do
not exceed maximum loop impedance of output
module (1200 Ω for -OFE2; 450 Ω for -OFE3).
4. Test Points — With optional 250 Ω series
impedance in output circuit (refer to DIP
Switches), test points can be used to measure loop
voltage/current. Refer to the Pinout for test point
circuit location.
5. Shield Terminals — Four field-side terminals are
jumpered together on the AIFM and internally
connected to the D-shell housing.
6. Dimensions — Refer to page 188.

Publication 1492-TD008D-EN-P - January 2009


158 Digital/Analog Programmable Controller Wiring Systems

1492-AIFM6S-3 1492-AIFM8-3
1492-RAIFM6S-3 1492-RAIFM8-3
Feed-Through 6-Channel Isolated with 3...4 Feed-Through 8-Channel Differential 16-Channel Single-
Terminals/Channel Ended with 3 Terminals/Channel

Application Notes Application Notes


1. Compatibility — To ensure proper operation
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage
with the I/O module, do not exceed the voltage
and current ratings of the AIFM.
and current ratings of the AIFM.
2. Wiring — Refer to the Label Section on page 181.
2. Wiring — Refer to the Label Section on page 181. For Field-Side Wiring Diagrams, refer to the
For Field-Side Wiring Diagrams, refer to the Wiring System web site information on page 186.
Wiring System web site information on page 186. 3. Extra Terminals — Eight field-side terminals are
3. Shield Terminals — Six field-side terminals are jumpered together on the AIFM. For some I/O
jumpered together on the AIFM and internally modules, the terminals are also internally
connected to the D-shell housing. connected to module common through the pre-
4. Dimensions — Refer to page 187. wired cable. Refer to the AIFM and ACABLE
pinouts.
Pinout
13
4. Shield Terminals — Eight field-side terminals
B1
12
are jumpered together on the AIFM and internally
A1
25
connected to the D-shell housing.
B2
24
5. Dimensions — Refer to page 187.
B3
11 A3
Pinout
3 B1
23 B4 2 B2
22 B5 1 B3
14 B4
9 A5 15 B5
21 B6 16 B6
17 B7
19 B7
18 B8
6 A7 12 B9
13 B10
18 B8
25 B11
17 B9 24 B12
23 B13
4 A9
22 B14
16 B10 20 B15
21
15 B11 B16

2 A11 4 A9
6 A10
14 B12 8 A11
10 A12
19 A13
D-Shell Housing A14
A2 A15
A4 A16

A6 D-Shell Housing
A1
A8 A2
A10 A3
A4
A12 A5
A6
A7
A8

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 159

1492-AIFM6TC-3 Pinout
13 B1
25 B2
Thermocouple 6-Channel with 3 Terminals/Channel 24 B3
23 B4
22 B5
21 B6
19 B7
18 B8
17 B9
16 B10
15 B11
14 B12
6 A7

T
Application Notes 20
12 A1
1. Compatibility — To ensure proper operation 11 A3

with the I/O module, do not exceed the voltage 9 A5

and current ratings of the AIFM. 4 A9


2 A11
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
D-Shell Housing
Wiring System web site information on page 186. A2
A4
3. Shield Terminals — Six field-side terminals are A6

jumpered together on the AIFM and internally A8


A10
connected to the D-shell housing. A12

4. Cold Junction Compensation — This AIFM


contains on-board cold junction compensation
(CTC) through a thermistor (T) and isothermal bar
mounted to the field-side terminals. Do not install
the cold junction sensor (provided with the
Catalog Number 1756-IT6I or 1756-IT6I2
thermocouple input module) on the removable
terminal block of the pre-wired cable. This module
is NOT compatible with other PLC systems (e.g.
bulletin numbers 1746, 1771, etc.) that do not have
external CJC capability.
5. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


160 Digital/Analog Programmable Controller Wiring Systems

1492-AIFM4C-F-5 Pinout
8 B1

Fusible 2-channel Input, 2-Channel Output with 24V DC 15 B2

Blown Fuse Indicators, Test Points, 5 Terminals/Input,


14 B3
3 Terminals/Output
13 B4

12 B5

11 B6

2 B7

10 B8

9 B9

Application Notes 1 B10

1. Compatibility — To ensure proper operation TP1 TP2


B11

with the I/O module, do not exceed the voltage A1

and current ratings of the AIFM. TP3 TP4

2. Wiring — Refer to the Label Section on page 181. A2

For Field-Side Wiring Diagrams, refer to the B12


A5
Wiring System web site information on page 186. .
.
.
.
3. Fusing — Fuse holders are included with the A8
D-Shell Housing
AIFM. Fuses (5 x 20 mm) are not included. Do A9
.
.
not exceed 2 A per input, 12 A per AIFM. .
.
A12
4. Isolation — The fuse clips and blown fuse
indicators are internally connected to one power
source field-side terminal. All inputs must
reference the same power source.
5. DIP Switches — For ease of wiring, unused
inputs can be jumpered to module common by
closing the DIP switches (ON position) for analog
modules that have this capability. Default switch
position is OPEN/OFF/NOT jumpered together.
6. Test Points — When using a two-wire
transmitter, test points (TP1-TP2) can be used to
measure input loop current. Refer to the Pinout
for test point circuit location.
7. Extra Terminals — Four field-side terminals are
internally jumpered on the AIFM. They can be
used for power source common connections.
8. Shield Terminals — Four field-side terminals are
jumpered together on AIFM and internally
connected to the D-shell housing.
9. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 161

1492-AIFM4I-F-5 Pinout
8 B1

Fusible 4-Channel Input with 24V DC Blown Fuse 15 B2

Indicators, Test Points, 5 Terminals/Input


14 B3

13 B4

12 B5

11 B6
2
B7
10 B8

Application Notes 9 B9

1 B10
1. Compatibility — To ensure proper operation
with the I/O module, do not exceed the voltage TP1 TP2
B11

and current ratings of the AIFM. A1


.
.
.
TP7 TP8 .
2. Wiring — Refer to the Label Section on page 181. .
A4
For Field-Side Wiring Diagrams, refer to the
B12
Wiring System web site information on page 186. A5
.
.
.
3. Fusing — Fuse holders are included with the .
.
A8
AIFM. Fuses (5 x 20 mm) are not included. Do D-Shell Housing
A9
not exceed 2 A per input, 12 A per AIFM. .
.
.
.
.
4. Isolation — The fuse clips and blown fuse A12

indicators are internally connected to one power


source field-side terminal. All inputs must
reference the same power source.
5. DIP Switches — For ease of wiring, unused
inputs can be jumpered to module common by
closing the DIP switches (ON position) for analog
modules that have this capability. Default switch
position is OPEN/OFF/NOT jumpered together.
6. Test Points — When using a two-wire
transmitter, test points (TP1-TP2) can be used to
measure input loop current. Refer to the Pinout
for test point circuit location.
7. Extra Terminals — Four field-side terminals are
internally jumpered on the AIFM. They can be
used for power source common connections.
8. Shield Terminals — Four field-side terminals are
jumpered together on the AIFM and internally
connected to the D-shell housing.
9. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


162 Digital/Analog Programmable Controller Wiring Systems

1492-AIFM8-F-5 Pinout
3 C1

Fusible 8-Channel Input with 24V DC Blown Fuse 2 C2

Indicators, 5 Terminals/Channel 1 C3

14 C4
15 C5

16 C6
17 C7

18 C8
12 C9

13 C10
25 C11

24 C12
23 C13

22 C14
Application Notes 20 C15

21 C16
1. Compatibility — To ensure proper operation 6
with the I/O module, do not exceed the voltage 19 B1
and current ratings of the AIFM. B2
.
.
2. Wiring — Refer to the Label Section on page 181. .
.
.
For Field-Side Wiring Diagrams, refer to the B9

Wiring System web site information on page 186. B10


.
.
.
3. Fusing — Fuse holders are included with the .
.
B18
AIFM. Fuses (5 x 20 mm) are not included. Do D-Shell Housing
A1
.
not exceed 2 A per input, 12 A per AIFM. .
.
.
.
4. Isolation — The fuse clips and blown fuse A18

indicators are internally connected to one power


source field-side terminal. All inputs must
reference the same power source.
5. DIP Switches — For ease of wiring, unused
inputs can be jumpered to module common by
closing the DIP switches (ON position) for analog
modules that have this capability. Default switch
position is OPEN/OFF/NOT jumpered together.
6. Extra Terminals — Nine field-side terminals are
internally jumpered on the AIFM. They can be
used for power source common connections.
7. Shield Terminals — Eighteen field-side terminals
are jumpered together on the AIFM and internally
connected to the D-shell housing.
8. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 163

1492-AIFM16-F-3 Pinout

Fusible 16-Channel Inputs with 24V DC Blown Fuse 3 B2

Indicators, 3 Terminals/Channel 2 B3

1 B4

14 B5

15 B6

16 B7

17 B8

18 B9

12 B10

Application Notes 13 B11

25
1. Compatibility — To ensure proper operation B12

with the I/O module, do not exceed the voltage 24 B13

and current ratings of the AIFM. 23 B14


2. Wiring — Refer to the Label Section on page 181.
22 B15
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186. 20 B16

3. Fusing — Fuse holders are included with the 21 B17


AIFM. Fuses (5 x 20 mm) are not included. Do 4 B18
not exceed 2 A per input, 12 A per AIFM. 6
8 B1
4. Isolation — The fuse clips and blown fuse 10
indicators are internally connected to one power 19
C1
.
.
.
source field-side terminal. All inputs must .
.
C16
reference the same power source. D-Shell Housing
A1
5. DIP Switches — For ease of wiring, unused .
.
.
.
inputs can be jumpered to module common by .
A18
closing the DIP switches (ON position) for analog
modules that have this capability. Default switch
position is OPEN/OFF/NOT jumpered together.
6. Shield Terminals — Eighteen field-side terminals
are jumpered together on the AIFM and internally
connected to the D-shell housing.
7. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


164 Digital/Analog Programmable Controller Wiring Systems

1492-AIFM16-F-5 6. Extra Terminals — Sixteen field-side terminals


(C9…C16 on TB1 and TB2) are internally
Fusible 16-Channel Input with 24V DC Blown Fuse jumpered on the AIFM and connected to module
Indicators, 5 Terminals/Channel common. Eighteen field-side terminals (B10…B18
on TB1 and TB2) are internally jumpered on the
AIFM and can be used for power source common
connections. There are two field-side terminals
(A17 and A18 on TB1) that can be externally
jumpered to connect the two groups of field-side
TB2 terminals.
7. Shield Terminals — Sixteen field-side terminals
TB1 are jumpered together on the AIFM and internally
connected to the D-shell housing.
8. Dimensions — Refer to page 187.

Pinout
Application Notes TB1 TB2
3 C1 12 C1

1. Compatibility — To ensure proper operation 2 C2 13 C2

with the I/O module, do not exceed the voltage 1 C3 25 C3


and current ratings of the AIFM. 14 C4 24 C4

2. Wiring — Refer to the Label Section on page 181. 15 C5 23 C5

For Field-Side Wiring Diagrams, refer to the 16 C6 22 C6

Wiring System web site information on page 186. 17 C7 20 C7

3. Fusing — Fuse holders are included with the 18 C8 21 C8

AIFM. Fuses (5 x 20 mm) are not included. Do C9


.
.
C9
.
.
not exceed 2 A per input, 12 A per AIFM.
. .
. .
C16 C16
A17
4. Isolation — The fuse clips and blown fuse 4
6
indicators are internally connected to two separate 8
10
B1 B1

power source field-side terminals. All inputs within 19


B2
.
.
.
.
B2
.
.
.
.
a group(TB1 or TB2) must reference the same
. .
B9 B9

power source. B10


.
.
.
B10
.
.
.
B18 B18
5. DIP Switches — For ease of wiring, unused A18

inputs can be jumpered to module common by


closing the DIP switches (ON position) for analog SH
D-Shell Housing
A1
.
.
.
A1
.
.
.
modules that have this capability. Default switch A8 A8

position is OPEN/OFF/NOT jumpered together.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 165

1492-AIFMQS Pinout
12 White/Blue 1
+INT 1 + Interrogate 1
Fusible 4-Input/4 Output Channel with 8 Fuses & 24V DC -INT 1
24

13 White/Orange
Blue/White 11

2
- Interrogate 1
+RET 1 + Return 1
Blown Fuse Indicators -RET 1
25 Orange/White 3
- Return 1
11 White/Green 17
+OUT 1 Drive Output 1
23 Green/White 26
OUT COM Drive Common
9 White/Brown 10
+INT 2 + Interrogate 2
21 Brown/White 19
-INT 2 - Interrogate 2
10 White/Gray 20
+RET 2 + Return 2
22 Gray/White 12
-RET 2 - Return 2
8 Red/Blue 25
+OUT 2 ➌ Drive Output 2
OUT COM
6 Red/Orange 4
+INT 3 + Interrogate 3
18 Orange/Red 5
-INT 3 - Interrogate 3
20 Red/Green 15
+RET 3 + Return 3
19 Green/Red 6
-RET 3 - Return 3
5 Red/Brown 9
+OUT 3 Drive Output 3
17 Brown/Red 8
OUT COM Drive Common
3 Red/Gray 22
+INT 4 + Interrogate 4
15 Gray/Red 14
Application Notes -INT 4
+RET 4
4 Black/Blue 23
- Interrogate 4
+ Return 4
16 Blue/Black 24
-RET 4 - Return 4
1. Compatibility — To ensure proper operation +OUT 4
2 Black/Orange 18
Drive Output 4

with the I/O module, do not exceed the voltage OUT COM

and current ratings of the AIFM. COM


LDT COM Blue/Red
7 21
LDT Common
2. Wiring — Refer to the Label Section on page 181. LDT COM
1
Orange/Black
13
LDT Common

For Field-Side Wiring Diagrams, refer to the GND DRAIN


Wiring System web site information on page 186. SH

3. Fusing — Fuse holders are included with the SH

AIFM. Fuses (5 x 20 mm) are not included. Do -V

not exceed 3 A per input, 12 A per AIFM. -V1F

-V4F
4. Isolation — The fuse clips and blown fuse
indicators are internally connected to two separate +V
+V1F
power source field-side terminals. All inputs within +V4F
a group must reference the same power source.
5. Extra Terminals — Four field-side terminals (on
TB1) are internally jumpered on the AIFM and
connected to module common. Four field-side
terminals (on TB1) are internally jumpered on the
AIFM and can be used for power source common
connections.
6. Shield Terminals — Eight field-side terminals
are jumpered together on the AIFM and internally
connected to the D-shell housing.
7. Dimensions — Refer to page 187.

Publication 1492-TD008D-EN-P - January 2009


166 Digital/Analog Programmable Controller Wiring Systems

1492-AIFMPI

Fusible 8-Input/2 Output Channels

Application Notes

1. Compatibility — To ensure proper operation


with the I/O module, do not exceed the voltage
and current ratings of the AIFM.
2. Wiring — Refer to the Label Section on page 181.
For Field-Side Wiring Diagrams, refer to the
Wiring System web site information on page 186.
3. Fusing — Two fuse holders for the outputs are
included with the AIFM. Eight fuses (0.25 A, 5 x
20 mm) are included with the fused supply inputs.
Do not exceed 2 A per output.
4. Isolation — The fuse clips and blown fuse
indicators are internally connected to one power
source field-side terminal. All inputs must
reference the same power source.
5. Jumpers — J0…J7 provide the option of
connecting the negative inputs to the return. J8
commons the shield to the return. Default switch
position is OPEN/OFF/NOT jumpered together.
6. Shield Terminals — Eight field-side terminals
are jumpered together on the AIFM and internally
connected to the D-shell housing.
7. The 1492-AIFMPI is designed exclusively for the
1757-PIM module.
8. Dimensions — Refer to page 187.

Pinout

Refer to page 167.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 167

1492-AIFMPI, Continued

Pinout, Continued

CN TB TB
+ V0
B9
1 +24
2 CHANNEL 0
J0 F0
3

B2

+ F1
1 B4
2 CHANNEL 7
J7
3
– F2
B6
1
9 B1
22 2
J8 F3
3
SHELL B3 B8
+V
B5 FUSED 0-7
F4
B7 B11
SHIELD
IN 0...7
B10 F5
B13
B12

B14 F6
B15
B16
V0 F7
A9 RTN B17
CHANNEL
12
4 A1 +0
0 IN 24 V1
14 A2 –0 B18
+DC
1 3 A3 +1 F8
IN
15 A4 –1 25 B19 OUT 0
2 A5 +2
2 IN F9
16 A6 –2
1 13 B20 OUT 1
3 A7 +3 IN
17 A8 –3
8 A10 +4
4 IN V1
18 A11 –4 A18 RTN
7 A12 +5 IN
5
19 A13 –5 A19 RTN
OUT 0
6 A14 +6 IN
6 20
A20 RTN
A15 –6 OUT 1
5 A16 +7
7 21 IN
A17 –7

Publication 1492-TD008D-EN-P - January 2009


168 Digital/Analog Programmable Controller Wiring Systems

Analog Cable Bulletin 1492 pre-wired cables are designed to minimize control wiring in a
Digital/Analog Programmable Controller Wiring Systems

panel. Analog pre-wired cables, when used with an AIFM, replace the point-
Specifications to-point wiring between Allen-Bradley programmable controller I/O modules
and individual terminal blocks. The analog ready-to-wire cables provide one
end of the cable pre-terminated for an AIFM (AIFM-ready cable).

Pre-Wired Cables

Specifications

The pre-wired cables have a Bulletin 1746 Removable Terminal Block,


Bulletin 1756 Removable Terminal Block, Bulletin 1769 Removable Terminal
Block, Bulletin 1771 Wiring Arm, or Bul. 1794 (Flex) 37-pin D-Shell (mates
with Cat. No. 1794-TB37DS) on one end and a D-shell on the other to
connect to the AIFM. All analog cables have an overall shield and most have
#22 AWG twisted pairs for additional noise immunity. In addition, most
analog cables have prepared ring lugs on the drain wire for convenient
grounding of the cable shield to the programmable controller chassis. The
broad offering of analog pre-wired cables supports over 40 different
Bulletin 1746, 1756, 1769, 1771, 700S, 700H, and 1794 analog, RTD, and
thermocouple (1756 only) I/O modules.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 169

Analog Cable Pre-Wired Cables, Continued


Specifications, Continued
Analog Pre-Wired Cable Specifications
Catalog Number Standard Cable I/O Module AIFM No. of Insulation Conductor Nominal Outer
and Length ➊ Lengths Connector Connector Conductors ➋➌ Rating Size Diameter
1492-ACABLE➊A 0.5, 1.0, 2.5, 5.0 m 1746-RT28 12-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACABLE➊B 0.5, 1.0, 2.5, 5.0 m 1746-RT26 2-Position and 1746-RT27 8-Position 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
Removable Terminal Block
1492-ACABLE➊C 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊D 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊E 0.5, 1.0, 2.5, 5.0 m 1771-WG (21 terminal) 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊F 0.5, 1.0, 2.5, 5.0 m 1771-WG (21 terminal) Wiring Arm 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊G 0.5, 1.0, 2.5, 5.0 m 1771-WC (10 terminal) Wiring Arm 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACABLE➊H 0.5, 1.0, 2.5, 5.0 m 1771-WF (18 terminal) Wiring Arm 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊J 0.5, 1.0, 2.5, 5.0 m 1771-WF (18 terminal) Wiring Arm 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊K 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")
1492-ACABLE➊L 0.5, 1.0, 2.5, 5.0 m 1746-RT28 12-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACABLE➊M 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")
1492-ACABLE➊P 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")
1492-ACABLE➊Q 0.5, 1.0, 2.5, 5.0 m 1746-QS (26 terminal D-shell) 25-pin D-shell 12 Twisted Pairs 300V 80°C 22 AWG 10.2 mm (0.40")
1492-ACABLE➊R 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊X 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊Y 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊YT 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊Z 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊A46 0.5, 1.0, 2.5, 5.0 m 1746-RT25G Green Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 10.2 mm (0.40")
1492-ACABLE➊TA 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊TB 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊TC 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊TD 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊UA 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊UB 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊UC 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊UD 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊VA 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 15-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊VB 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 15-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊WA 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊WB 0.5, 1.0, 2.5, 5.0 m 1756-TBNH 20-Position Removable Terminal Block 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACABLE➊XA 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")
1492-ACABLE➊XB 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")
1492-ACABLE➊ZA 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊ZB 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACABLE➊ZC 0.5, 1.0, 2.5, 5.0 m 1756-TBCH 36-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊AA69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN10 12-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊AB69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN10 12-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊BA69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊BB69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊BC69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊BD69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 15-pin D-shell 5 Twisted Pairs 300V 80°C 22 AWG 7.44 mm (0.293")
1492-ACAB➊C69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊CA69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊CB69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊CC69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊D69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊EA69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊EB69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊ED69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1492-ACAB➊HA69 0.5, 1.0, 2.5, 5.0 m 1769-RTBN18 20-Position Removable Terminal Block 25-pin D-shell 11 Twisted Pairs 300V 80°C 22 AWG 11.5 mm (0.45")

Publication 1492-TD008D-EN-P -January 2009


170 Digital/Analog Programmable Controller Wiring Systems

Analog Pre-Wired Cable Specifications


Catalog Number Standard Cable I/O Module AIFM No. of Insulation Conductor Nominal Outer
and Length ➊ Lengths Connector Connector Conductors ➋➌ Rating Size Diameter
1492-ACAB➊Z7H 0.5, 1.0, 2.5, 5.0 m 20C-DA1-A or 20C-DA1-B I/O Board 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACAB➊Z7S 0.5, 1.0, 2.5, 5.0 m Terminal TB1 (Pins 1…12) 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACAB➊X7S 0.5, 1.0, 2.5, 5.0 m Terminal TB1 (Pins 13…25) 25-pin D-shell 9 Twisted Pairs 300V 80°C 22 AWG 6.78 mm (0.267")
1492-ACAB➊Z94 0.5, 1.0, 2.5, 5.0 m 37-Pin D-Shell Connector to Mate with Cat. No. 25-pin D-shell 20 Conductors 300V 80°C 22 AWG 8.43 mm (0.332")
1794-TB37DS Base

➊ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m and 5.0 m. To order, insert the desired cable
length code into the catalog number (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example:
Catalog Number 1492-ACABLE005A is for a 0.5 m cable for the 1746-NI4 I/O Module. Also refer to
Build-to-Order Length Cables on page 65.
➋ All pre-wired analog cables have an overall shield. On 1492-ACABLE➊C and 1492-ACABLE➊D, the drain wire
is connected to the shield terminal on the I/O module connector. All other 1492-ACABLEs have a ring lug on the
7.87" (200 mm) exposed drain wire at the I/O module end of the cable.
➌ Not every connection is always used.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 171

Analog Cable Pinouts


Specifications, Continued
Analog Pre-Wired Cables

The following diagrams indicate how the analog pre-wired cables are
connected on both ends. The description listed first is the wire color of the
conductor connected to the screw terminal on the respective Wiring Arm or
Removable Terminal Block. The number that follows in parentheses is the
corresponding pin number in the D-shell connector on the other end.

Shield
Base Color Stripe Color

Blue (24) White/Green (22)

NC
20 or 40 Connector Pin Number

Black (23) White/Red (19)

No Connection Individual Conductor


Twisted Pair Jumper Wire

Output Pin Connector Definition

11
1
15 1 25

9 8 14
13

15-Pin D-Shell Connector 25-Pin D-Shell Connector

AIFM Mating Connector Definition

Publication 1492-TD008D-EN-P -January 2009


172 Digital/Analog Programmable Controller Wiring Systems

Analog Cable Pinouts, Continued


Specifications, Continued

NC

Red (3)
Black (2)
White (1)
Black (14)
Green (15)
0 Red (8) 0 Yellow (2) Black (16)
1 Black (15) 1 Black (1) Blue (17)
2 NC Black (18)

3 White (14) 0 Red (8) Yellow (12)


4 Black (13) 1 Black (15) Black (13)
5 Yellow (2) Brown (25)
2 White (14)
Black (24)
6 Green (12) 3 Black (13)
7 Orange (23)
Black (11)
4 Green (12) Black (22)
8 NC
5 Black (11) Red (20)
9 Blue (10) White (21)
10 Black (9) 6 Blue (10)
11 7 Drain
Black (1) Black (9)

1492-ACABLE___A 1492-ACABLE___B 1492-ACABLE___C

1 Red (3) 1 Red (3)


2 Black (2) Brown (2)
2
3 White (1) 3 Black (1)
4 Black (14) 4 White (14)
5 NC Orange (4)
5
NC
6 Green (15) 6 White/Black (15)
NC 7 Black (16) 7 White/Brown (16)
Blue (13) 8 Blue (17) 8 White/Red (17)
White/Blue (24) 9 Black (18) 9 White/Orange (18)
White/Violet (25) 10 NC Blue (10)
10
White/Green (23) 11 Yellow (12) 11 Violet (12)
Green (12) 12 Black (13) 12 Gray (13)

Yellow (11) 13 Brown (25) 13 White/Black/Brown (25)


NC 14 Black (24) 14 White/Gray (24)
15 NC 15 Green (8)
NC
16 Orange (23) 16 White/Violet (23)
White/Yellow (22)
17 Black (22) 17 White/Blue (22)
White/Red (19)
18 Red (20) 18 White/Yellow (20)
White/Orange (21)
19 White (21) 19 White/Green (21)
White/Brown (18)
20 Red (6) 20 Yellow (6)
Orange (9)
21 Green (19) 21 NC
Red (6)
NC

Drain

1492-ACABLE___D 1492-ACABLE___E 1492-ACABLE___F

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 173

Analog Cable Pinouts, Continued


Specifications, Continued

18 Red (3) 18 White/Violet (25)


Black (2) Green (12)
16 White (1) 16 Blue (13)
Black (14) White/Green (23)
14 Green (15) 14 Yellow (11)
Red (25)
Black (16) White/Blue (24)
Red (8) A 12 Blue (17) 12 Red (13)
White/Orange (21) White (15)
Black (15) 0 Black (18) Orange (9) Green (3)
10 NC 10 White/Yellow (22)
1 Blue (4)
White (14) NC White/Brown (18) Yellow (5)
8 Yellow (12) 8 Red (6) Brown (1)
Black (13) 2
Black (13) Black (14)
White/Red (19) Red (9)
Green (12) 3 6 Brown (25) 6 White (16) White (11)
Black (24) Brown (4)
Black (11) 4 Black (10)
4 Orange (23) 4 White/Black (17) Black (24)
Blue (10) 5 Black (22) Violet (14) NC
2 Red (20)
Black (9) 6 2 Black (2) NC
White (21) Gray (15) Green (23)
NC 7 Blue (21)
Black (22)
NC B
Black (18)* Yellow (19)
Black (20)
Orange (17)

1492-ACABLE___K*
1492-ACABLE___G 1492-ACABLE___H
1492-ACABLE___J
Red (9)
(3) White 2 1
Red (4) Black (10)
0 Red (8) (15) Black Black (14) White (11)
1 Black (15) NC NC Black (24)
NC NC Green (23)
2 NC (1) Blue Green (2)
Black (22)
3
(17) Black Black (16) Blue (21)
White (14) NC NC
4 Black (13) NC NC Black (20)
5 NC (7) Brown Yellow (8) Yellow (19)
(19) Black Black (18) Black (18)
6 NC NC NC Orange (17)
7 Green (11) NC NC Black (16)
(5) Red Orange (6) Brown (1)
8 Black (2) Black (14)
(21) White Black (20)
White (15)
NC NC
9 NC Green (3)
NC NC
10 Blue (9) (24) Red Red (12) Blue (4)
Yellow (5)
11 Black (1) (13) Blue Green (25)
Red (13)
36 35
Red (25)

1492-ACABLE___L 1492-ACABLE___P*
1492-ACABLE___M

White/Black (15)
NC
Black/Orange (2) White/Brown (16)
9 Orange/Black (1) NC
18
Red/Brown (5) 26 White/Red (17)
Green/White (23)
Brown/Red (17)
White/Green (11) NC
Red/Green (20) Blue/Black (16) White/Orange (18)
Green/Red (19) Red/Blue (8) NC
Black/Blue (4)
Orange/Red (18) Violet (12)
Gray/Red (15) Blue/Red (7)
Red/Orange (6)
Red/Gray (15) NC
Orange/White (25) Gray (13)
Gray/White (22)
White/Orange (13)
White/Gray (22)
Green (8)
Blue/White (24) Brown/White (22) White-Black/Brown (25)
White/Blue (12) 10 19
1 Orange (4)
White/Brown (9)
White/Gray (24)

Red (3) NC
Brown (2) White/Yellow (20)
1492-ACABLE___Q White/Green (21)

* Cable uses twisted pair conductors. 1492-ACABLE___R

Publication 1492-TD008D-EN-P -January 2009


174 Digital/Analog Programmable Controller Wiring Systems

Analog Cable Pinouts, Continued


Specifications, Continued
Red (3) 2 1 Red (3) 2 1 Brown (2)
Black (1) 4 3 Black (1) 4 3 White (14)
White/Black (15) 6 5 White/Black (15) 6 5 White/Brown (16)
White/Red (17) 8 7 White/Red (17) 8 7 White/Orange (18)
Orange (4) Brown (2) Orange (4)
White/Blue (22) 10 9 White/Brown (16) Yellow (6)
10 9
Yellow (6) Gray (13) Violet (12) 12 11 Gray (13)
Violet (12) 12 11
White/Black/Brown (25) 14 13 White/Black/Brown (25) 14 13 White/Gray (24)
White/Violet (23) 16 15 White/Violet (23) 16 15 White/Blue (22)
White/Yellow (20) 18 17 White/Yellow (20) 18 17 White/Green (21)
20 19 20 19

22 21 22 21

24 23 24 23

26 25 26 25

28 27 28 27

20 29 30 29

32 31 32 31

34 33 34 33

36 35 36 35

1492-ACABLE___TA 1492-ACABLE___TB

Red (3) 2 1
Black (2) 4 3
Red (3) 2 1
Red (3) 2 1
White (1) Black (2) 4 3
6 5 Brown (2) 4 3
White (1) 6 5
Black(14) 8 7 Black (1) 6 5
Yellow (6) Black(14) 8 7
10 9 Yellow (6) White (14) 8 7
Black (21) Black (21)
10 9
Green (15) 12 11 Orange (4) 10 9 Yellow (6)
Green (15) 12 11
Black (16) 14 13 White/Black (15) 12 11
Black (16) 14 13
Blue (17) 16 15 White/Brown (16) 14 13
Blue (17) 16 15
Black (18) 18 17 White/Red (17) 16 15
Black (18) 18 17
20 19 20 19
White/Orange (18) 18 17

22 21 22 21
Violet (12) 20 19

24 23 24 23
Gray (13) 22 21

26 25 26 25
White/Black/Brown (25) 24 23

28 27
White/Gray (24) 26 25
28 27
30 29
Blue (10) 28 27 Green (8)
30 29
32 31
White/Violet (23) 30 29
32 31
34 33
White/Blue (22) 32 31
34 33
36 35
White/Yellow (20) 34 33
36 35 White/Green (21) 36 35

1492-ACABLE___TC 1492-ACABLE___TD 1492-ACABLE___UA

Red (3) 2 1
Red (3) 2 1 Red (3) 2 1
Brown (2) 4 3 J1
Black (2) 4 3 Black (2) 4 3
Black (1) 6 5
White (1) 6 5 White (1) 6 5
White(14) 8 7 Black(14) 8 7
J2
Orange (4) Black(14) 8 7
Red (6)
10 9 Red (6) 10 9
Yellow (6) Green (19)
10 9
Green (19)
White/Black (15) 12 11
Green (15) 12 11 Green (15) 12 11
White/Brown (16) 14 13 J3
Black (16) 14 13 Black (16) 14 13
White/Red (17) 16 15
Blue (17) 16 15 Blue (17) 16 15
White/Orange (18) 18 17
J4
Black (18) 18 17 Black (18) 18 17
Violet (12) 20 19
Yellow (12) 20 19 Yellow (12) 20 19
Gray (13) J5
22 21
Black (13) 22 21 Black (13) 22 21
White/Black/Brown (25) 24 23
Brown(25) 24 23 Brown(25) 24 23
White/Gray (24) J6
26 25
Black (24) 26 25 Black (24) 26 25
Green (8) 28 27 28 27
28 27
Blue (10)
White/Violet (23) 30 29
Orange (23) 30 29 Orange (23) 30 29
J7
White/Blue (22) 32 31
Black (22) 32 31 Black (22) 32 31
White/Yellow (20) 34 33
Red (20) 34 33 Red (20) 34 33
J8
White/Green (21) 36 35
White (21) 36 35 White (21) 36 35

1492-ACABLE___UB 1492-ACABLE___UC 1492-ACABLE___UD

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 175

Analog Cable Pinouts, Continued


Specifications, Continued

2 1 2 1
Red (8) 4 3
4 3 Red (8)
Black (15)
6 5 6 5 Black (15)
Black (13)
Black (13)
8 7 White (14) 8 7
White (14)
10 9 10 9

12 11 12 11
Green (12)
14 13 14 13 Green (12)
Black (11)
16 15 Black (11)
16 15 Black (9) Black (9)
18 17 Blue (10) 18 17
Blue (10)
20 19 20 19

1492-ACABLE___VA 1492-ACABLE___VB

2 1 2 1 NC
Yellow (12) Red (3)
4 3 Yellow (12) 4 3 Red (3)
Black (13) Black (2)
Black (24) 6 5 Black (14) Black (13) 6 5 Black (2)
White (1) Black (24) Black (14)
Brown (25) 8 7 NC 8 7
Brown (25) White (1)
10 9 10 9
12 11 Black (22) 12 11
Orange (23) Green (15)
14 13 Black (16) Orange (23) 14 13 Green (15)
Black (22)
White (21) 16 15 Black (18) 16 15 Black (16)
Red (20) 18 17 Blue (17) White (21) Black (18)
NC 18 17
Red (20) Blue (17)
20 19 20 19
Red (6)
Green (19)

1492-ACABLE___WA 1492-ACABLE___WB

Blue (24) 2 1 Blue (24) 2 1 Red (13)


Red (13)
4 3 NC 4 3 NC

6 5 Black (23) 6 5 Black (25)


Black (23) Black (25)
Yellow (19) 8 7 White (22) Yellow (19) 8 7 White (22)
10 9 10 9 NC

Black (18) 12 11 Black (21) Black (18) 12 11 Black (21)


Brown (6)
NC 14 13 NC Black (20) 14 13 NC

16 15 Orange (15) 16 15 Green (17)


Orange (15) Green (17)
18 17 NC 18 17 NC
20 19 Black (14) 20 19 Black (16)
Black (14) Black (16)

1492-ACABLE___X 1492-ACABLE___Y

Publication 1492-TD008D-EN-P -January 2009


176 Digital/Analog Programmable Controller Wiring Systems

Analog Cable Pinouts, Continued


Specifications, Continued

Green (23) 2 1 Orange (17) NC 2 1 NC


NC 4 3 NC Green (23) 4 3 Orange (17) White/Blue (24) 2 1 Blue (13)
Black (22) 6 5 Black (16) Black (22) 6 5 Black (16)
White (11) 8 7 Yellow (19) NC 8 7 NC Yellow (11) 4 3 Green (12)
NC 10 9 NC White (11) 10 9 Yellow (19) White/Green (23) 6 5 White/Violet (25)
Black (24) 12 11 Black (18) Black (24) 12 11 Black (18)
Red (9) 14 13 Blue (21) NC 14 13 NC White/Red (19) 8 7 White/Yellow (22)
NC 16 15 NC Red (9) 16 15 Blue (21)
Black (10) Black (20) Red (6) 10 9 Orange (9)
18 17 Black (10) 18 17 Black (20)
NC 20 19 NC NC 20 19 NC White/Brown (18) 12 11 White/Orange (21)
NC 22 21 NC NC 22 21 NC
NC 24 23 NC NC 24 23 NC NC 14 13 NC
White (15) 26 25 Blue (4) White (15) 26 25 Blue (4)
Gray (15) 16 15 White/Black (17)
Green (3) 28 27 Yellow (5) Green (3) 28 27 Yellow (5)
Brown (1) 30 29 Black (14) Brown (1) 30 29 Black (14) Black (2) 18 17 Brown (4)
Red (12) 32 31 Red (2) Red (12) 32 31 Red (2)
NC 34 33 NC NC 34 33 NC Violet (14) 20 19 White (16)
Red (13) 36 35 Red (25) Red (13) 36 35 Red (25)

1492-ACABLE___XB* 1492-ACABLE___Z
1492-ACABLE___XA*

2 1 White/Green (23) 2 1 White/Violet (25)


White/Green (23) White/Violet (25)
4 3 NC 4 3 NC
White/Yellow (22) 6 5 White/Blue (24) White/Yellow (22) 6 5 White/Blue (24)
8 7
White/Brown (18) White (16) 8 7 White/Brown (18)
White (16) 10 9 NC 10 9 NC
Gray (15) 12 11 White/Black (17) Gray (15) 12 11 White/Black (17)
NC 14 13 NC NC 14 13 NC Black (23) Blue (24)
NC 16 15 NC NC 16 15 NC
NC 18 17 NC Violet (14) 18 17 Blue (13)
Violet (14) 20 19 Blue (13) NC 20 19 NC
Black (2) 22 21 White/Orange (21) Black (2) 22 21 White/Orange (21) Black (25) Red (13)
NC 24 23 NC NC 24 23 NC
NC 26 25 NC NC 26 25 NC Black (20) Brown (6)
NC 28 27 NC NC 28 27 NC
NC 30 29 NC NC 30 29 NC
NC 32 31 NC NC 32 31 NC
NC 34 33 NC NC 34 33 NC 2 1
NC 36 35 NC NC 36 35 NC
4 3
6 5
8 7
10 9
1492-ACABLE___ZA 1492-ACABLE___ZB 12 11

14 13
16 15

2 1
18 17
White/Green (23) White/Violet (25)
4 3 20 19
White/Yellow (22) 6 5 White/Blue (24)
8 7
White (16) 10 9
White/Brown (18)
Gray (15) 12 11 White/Black (17)
NC
Red(3) 1
14 13 NC 2 Brown (2)
NC 16 15 NC Black (1) 3
Violet (14) 18 17 Blue (13) 4 Blue (14) Black (14) Orange (15)
NC 20 19 NC Violet (15) 5
6 Gray (16)
Black (2) 22 21 White/Orange (21) White (17) 7
NC 24 23 NC 8 White/Black (18) Black (16) Green (17)
NC 26 25 NC Orange (6) 9
NC 28 27 NC
10 White/Brown (19)
Yellow (12) 11
NC 30 29 NC 12 Green (13)
NC 32 31 NC White/Violet (25) 13
14 White/Blue (24) Black (18) Yellow (19)
NC 34 33 NC
NC 36 35 NC
White/Green (23) 15
16 White/Yellow (22)
White/Red (20) 17
18 White/Orange (21)
Black (21) White (22)

1492-ACAB___A46 1492-ACABLE___YT
1492-ACABLE___ZC (Green RTB)

* Cable uses twisted pair conductors.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 177

Analog Cable Pinouts, Continued


Specifications, Continued

1 Red (8)
2
3
1 Red (8) 4
NC 2 1 NC 5 White (14)
6
3 Black (15) 2 Red (8) 7
NC 4 3 8
5 White (14) NC 4 Black (15) Green (12)
NC 6 9
5 NC 10
7 Black (13) 6 11
NC 8 7 Black (13) 12
9 NC NC 8 White (14) 13 Blue (10)
NC 10 9 NC 14
NC 10 15
16 Black (9)
17
18

1492-ACAB___AA69
1492-ACAB___BA69
1492-ACAB___AB69

1 1 Red (8) 1
2 2 2 Black (15)
3 NC Black (15) 3
3 Red (8) NC 4 4 Red (8)
4 NC
5 5 White (14) 5
6 6 6 Black (13)
7 NC Black (13) 7
7 White (14) NC 8 8 White (14)
8 NC
9 9 Green (12) 9
10 10 10 Black (11)
11 Black (11) 11
11 Green (12) 12 NC Green (12)
12 NC NC 12
13 13 Blue (10) 13
14 14 14 Black (9)
Blue (10) 15 NC Black (9) 15
16
15
NC 16 NC 16 Blue (10)
Black (9) 17 NC 17
17 18
18 NC NC 18

1492-ACAB___BB69 1492-ACAB___BC69 1492-ACAB___BD69

1 1 White/Violet (25) 1
2 White/Green (23) 2 2
3 White/Blue (24) 3 White/Blue (24) 3 White/Blue (24)
White/Yellow (22) 4 White/Yellow (22) 4 White/Yellow (22) 4
5 White/Violet (25) 5 5 White/Violet (25)
White/Green (23) 6 6 6
7
White/Green (23)
8
7 White/Brown (18) 7
White (16) 8 8
9 White/Black (17) 9 White/Black (17) 9 White/Black (17)
Gray (15) 10 Gray (15) 10 Gray (15) 10
11 White/Brown (18) 11 11 White/Brown (18)
White (16) 12 12 12
13 White/Orange (21) White (16)
14
13 White/Orange (21) 13 White/Orange (21)
Black (2) Black (2) 14 Black (2) 14
15 15 Blue (13) 15 Blue (13)
16 Violet (14) 16 16
17 Blue (13) Violet (14)
17 17
Violet (14) 18 18 18

1492-ACAB___CA69 1492-ACAB___CB69 1492-ACAB___CC69

L L R
R

1
1 1 1
Red (3) Violet (12) 2
2 2 2
3 3 3 Red (3) 3 Violet (12)
4 4 4 4
5 Black (1) 5 White/Black/Brown (25) 5 5
6 6 6 6
7 7 7 Black (1) 7 White/Black/Brown (25)
8 8 8 8
9 White/Black (15) 9 White/Violet (23) 9 9
10 10 10 10
11 11 11 White/Black (15) 11 White/Violet (23)
12 12 12 12
13 White/Red (17) 13 White/Yellow (20) 13 13
14 14 14 14
15 15 White/Red (17) 15 White/Yellow (20)
White/Green (21) 15
Yellow (6) 16 White/Green (21)
Yellow (6) 16 16 16
17 Orange (4) 17 17 Orange (4) 17

18 18 18 18

1492-ACAB___EA69 ➊ 1492-ACAB___EB69 ➊

Publication 1492-TD008D-EN-P -January 2009


178 Digital/Analog Programmable Controller Wiring Systems

Analog Cable Pinouts, Continued


Specifications, Continued

1 Blue (13)
1 Yellow (6)
White/Red (19) 2 White/Black (15) 2
3
Red (6) 4
3 Green (12) White/Brown (16) 4
5
5 White/Violet (25) White/Red (17) 6
White/Brown (18) 6 7
7 White/Blue (24) White/Orange (18) 8
White/Black (17) 8 9
9 Yellow (11) Violet (12) 10
Brown (4) 10 11
11 White/Green (23) Gray (13) 12
White (16) 12 13
13 White/Yellow (22) White/Blue/Brown (25) 14
Gray (15) 14
15 Orange (9) 15 Orange (4)
Black (2) 16 White/Grey (24) 16
17 White/Yellow (20)
17 White/Orange (21) Red (3) 18
Violet (14) 18
White/Green (21)
Brown (2)
1492-ACAB___D69
1492-ACAB___C69

L R

1 Red (3) 1 Violet (12)


Brown (2) 2 Gray (13) 2
3 3
4 4
5 Black (1) 5 White/Black/Brown (25)
White (14) 6 White/Gray (24) 6
7 7
8 8
9 White/Black (15) 9 White/Violet (23)
White/Brown (16) 10 White/Blue (22) 10
11 11
12 12
13 White/Red (17) 13 White/Yellow (20)
White/Orange (18) 14 White/Green (21) 14
15 15
Yellow (6) 16 Orange (4) 16
17 17

18 18
L
R
1492-ACAB___EC69 ➊ 1
1
Brown (2) 2 Gray (13) 2
3 Red (3) 3 Violet (12)
4 4
5 5
White (14) 6 White/Gray (24) 6
7 Black (1) 7 White/Black/Brown (25)
8 8
9 9
White/Brown (16) 10 White/Blue (22) 10
White/Black (15)
12
11
13
1492-ACAB___ED69 ➊ 12
11 White/Violet (23)
White/Orange (18) 14 13
White/Green (21) 14
15 White/Red (17) 15 White/Yellow (20)
Yellow (6) 16 Orange (4) 16
17 17
18 18

1492-ACAB___ED69 ➊
19
37
18
36
17
35
16
34
15
33
14
32
13
31
Cable Wiring Table Conductor for 1492-ACAB__Z94
12
30
11 Connector 37- Conductor Color Code Connectors Connector 37- Conductor Color Code Connectors
29
25
24
23
22
21
20
19
18
17
4 16
3 15
2 14

10 Pin D-Shell, 25-Pin D-Shell, Pin D-Shell, 25-Pin D-Shell,


13

12
11
10
9

7
6

1
8

28 End 1 End 2 End 1 End 2


9
27
8
26
1 Black — 31 White/Brown 13
7
6
25 End 2 2 Brown — 12 White/Red 25
24
5
23
(AIFM) 19 Red 3 30 White/Orange 24
4 22 37 Orange 2 10 White/Yellow 23
3 21 18 Yellow 1 28 White/Green 22
2 20
1 36 Green 14 9 White/Blue 20
16 Blue 15 27 White/Violet 21
End 1 34 Violet 16 3 White/Grey 6
15 Grey 17 21 White/Black/Brown 19
(Flex Base) 33 White 18 5 Shield Case
1492-ACAB___Z94 13 White/Black 12 — — —

➊ Cable is made up of two (Left & Right pair) individual terminal blocks.

Publication 1492-TD008D-EN-P -January 2009


Digital/Analog Programmable Controller Wiring Systems 179

Analog Cable Pinouts, Continued


Specifications, Continued
1
Red (13)
White (15) 2 Red (25)
3 Green (3)
Brown (1) Blue (4) 4
5 Yellow (5)
6
Black (14) 7 Red (9)
Black (10) 8
9 White (11)
Black (24) 10
11 Green (23)
Black (22) 12
13 Blue (21)
Black (20) 14
15 Yellow (19)
Black (18) 16
17 Orange (17)
Black (16) 18

1492-ACAB___HA69*

Yellow (19)
Black (18) 13
Black (25) 1 Black (16) 14 Black (25) 1
Red (13) 2 Orange (17) 15 Red (13) 2
Black (23) 3 Red (9) 16 3
Black (23) 4
Blue (24) 4 Black (10) 17
Blue (24) 5
Black (14) 5 White (11) 18
Black (21) 6
Orange (15) 6 Black (24) 19 White (22) 7
Black (2) 7 Green (23) 20 Bare Wire (MTG) 8
Yellow (19) 8 Black (22) 21 Black (18) 9
Black (18) 9 Yellow (19) 10
Blue (21) 22
Green (17) 10 Black (16) 11
Black (20) 23
Black (16) Green (17) 12
Bare Wire (MTG) 24
1492-ACABZ7H 1492-ACABZ7S
1492-ACABX7S

➊ Cable is made up of two (Left & Right pair) individual terminal blocks. * Cable uses twisted pair conductors.

Publication 1492-TD008D-EN-P -January 2009


180 Digital/Analog Programmable Controller Wiring Systems

Dimensions Approximate dimensions are shown in millimeters unless otherwise indicated (to convert to inches,
multiply by 0.0394). Dimensions are not to be used for manufacturing purposes.

Digital IFM Mating Connector

39 mm
29 mm 38 mm 54.4 mm
(1.54 in.)
(1.15 in.) (1.50 in.) (2.15 in.)

34.3 mm 35.9 mm
(1.35 in.) (1.42 in.)
9.0 mm
11.7 mm
(0.36 in.)
(0.46 in.)
10 mm
(1.40 in.) 10 mm
(1.40 in.)
20-Point Cable Dimensions 40-Point Cable Dimensions

Analog D-Shell Connector

2.4 in. 2.9 in. 0.7 in.


0.7 in.
60 mm 73 mm 17 mm
17 mm

1.6 in. 1.6 in.


39 mm 39 mm

1.8 in. 2.3 in.


44 mm 58 mm

15-Pin D-Shell Dimensions 25-Pin D-Shell Dimensions

Wiring System Module The following is an example to show the length (L) and width (W) and Height
(H) dimension layout for a Wiring System Module. Refer to the Quick
Dimensions Reference table on Page 187 for a complete list of module dimensions.

2.78 in.
(70.5 mm) Height
1.67 in.
(42.5 mm)

4.33 in. 3.27 in.


(110 mm) (83 mm)
Length Width

Publication 1492-TD008D-EN-P -January 2009


181

Marking Systems Pre-Printed and Blank Adhesive Label Cards


All Bulletin 1492 IFMs, XIFMs, and AIFMs come with an adhesive label card.
To see an example, refer to pages 182 and 183. The label card provides the
field-side connection descriptions for the programmable controller I/O
module. The label strips basically copy the wiring descriptions from the I/O
module in the chassis down to the Interface Module terminals on the DIN
Rail.
The label cards list all of the compatible I/O modules and their respective
wiring descriptions. Depending on the I/O module that is used, the label
strip(s) are simply peeled from the label card and applied to the field-side
terminals on the Interface Module.
Labels are provided in the octal and decimal numbering systems for
Bulletin 1746 I/O modules. Labels for Bulletin 1771 I/O modules are
supplied in the octal numbering system, like the I/O modules themselves.
Labels for Bulletin 1756 and 1769 I/O modules are supplied in the decimal
numbering system, like the I/O modules. Interface Modules with LEDs or
fuse clips come with the LEDs or fuse clips/blown fuse indicators numbered
in decimal. LED and fuse labels are also provided in octal for use with
Bulletin 1771 I/O modules. The LED or fuse conversion label(s) are placed
directly on the circuit board of the Interface Module. For extra terminal
modules, pre-printed labels are provided to identify the power bus(ses) or
commoned terminals (middle and/or lower rows of terminals) on the
Interface Module. For each I/O module, corresponding labels with L1, L2,
COM, or +V are provided. The labels indicate isolated power busses or
grouped commons with a different letter or number. For example, L1-A, L1-B,
L1-C or COM1, COM2, COM3, etc.
In addition, if generic numbering of the field-side terminals is desired, numeric
labels are provided. Examples: 1…20, 1…40, and evens and odds. For write-
on identification, the label cards contain blank label strips (for field-side
terminals) and rectangular boxes (for the large group marking area on each
IFM, XIFM, or AIFM).
Examples of available label cards are on page 182. This information is helpful
for determining field-side wiring layouts prior to installation. Label cards can
be ordered as spare parts should a replacement be required. Refer to page 187
for a listing of label cards that apply to your IFM.
An example of how the labels are applied is shown below:

Publication 1492-TD008D-EN-P - January 2009


182

Marking Systems, Part 1 of Adhesive Label Card for Catalog Numbers 1492-IFM20F,
Continued (Example Label -IFM20D24, and -IFM20D120
Cards)

I/O CAT. NO. MODULE LABEL

IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN L2 L2
1746-IA16, IM16, 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
IN16 (AC) IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 L2 L2

IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM COM
1746-IB16, IC16, 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
IH16, IN16 (DC),
ITB16 IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM COM
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

+V +V IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM COM
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1746-IG16
IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM COM
+V +V 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN +V +V
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1746-IV16, ITV16
IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN +V +V
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1746-OA16, L1 L1 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT L1 L1
OW16 (AC) 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 2
1769-OA16, L1 L1 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT L1 L1
OW16 (AC) 1 1 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 2 2

1746-OB16, OB16E, +V +V OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT COM COM
OBP16, OG16, 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
OV16, OVP16 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT COM COM
1769-OB16, 0V16 +V +V 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1746-OW16 (DC) +V1 +V1 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT +V2 +V2
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1769-OW16 (DC)
+V1 +V1 OUT
00
OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT +V2 +V2
01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1746-OX8 (AC) L1 OUT L1 OUT L1 OUT L1 OUT OUT L1 OUT L1 OUT L1 OUT L1
1769-OW8I (AC) 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7

1746-OX8 (DC) +V0 OUT OUT OUT OUT OUT +V4 OUT +V5 OUT +V6 OUT +V7
1769-OW8I (DC) 0 +V1 1 +V2 2 +V3 3 4 5 6 7

1756-IA8D, L1 IN IN IN IN L2 L2 L2 L2 L2 L2 L2 L2 IN IN IN IN L1 L2
TC-IDX081 0 0 1 2 3 0 0 0 0 1 1 1 1 4 5 6 7 1 1

1756-IA16, IN16, L2 L2 IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN L2 L2
TC-IDA161 0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 1

1756-IB16, IC16, GND GND IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN GND GND


TC-IDD161, IDE161 0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 1

1756-OA8, ON8, L1 OUT OUT OUT OUT L1 L1 L1 L1 L1 L1 L1 L1 OUT OUT OUT OUT L1
TC-ODC081 0 0 1 2 3 0 0 0 0 1 1 1 1 4 5 6 7 1

Publication 1492-TD008D-EN-P - January 2009


183

Marking Systems, Part 2 of Adhesive Label Card for Catalog Numbers 1492-IFM20F,
Continued (Example Label -IFM20D24, and -IFM20D120
Cards)

1756-OA8D, OA8E, L2 OUT OUT OUT OUT L1 L1 L1 L1 L1 L1 L1 L1 OUT OUT OUT OUT L2 L1
TC-ODX081 0 0 1 2 3 0 0 0 0 1 1 1 1 4 5 6 7 1 1

1756-OA16, L1 L2 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT L1 L2
TC-ODA161 0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 1

1756-OB8, OC8, +DC OUT OUT OUT OUT RTN +DC +DC +DC RTN +DC +DC +DC +DC OUT OUT OUT OUT RTN RTN
TC-ODD081, 0 0 1 2 3 0 0 0 0 0 1 1 1 1 4 5 6 7 1 1
TC-ODE081

1756-OB16E, +DC RTN OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT +DC RTN
TC-ODD161 0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 1
1769-IA8I IN L2 IN L2 IN L2 IN L2 IN L2 IN L2 IN L2 IN L2
0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7
1769-IA16 IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
L2 L2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 L2 L2
1769-IM12 IN IN IN IN IN IN IN IN IN IN IN IN L2 L2
0 1 2 3 4 5 6 7 8 9 10 11
1769-IQ16 SINK COM COM IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM COM
1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 2
1769-IQ16 SOURCE +VDC +VDC IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN +VDC +VDC
1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 2

1769-OA8 (AC), L1 OUT OUT OUT OUT L1 OUT OUT OUT OUT L1 L1
OW8 1 0 1 2 3 1 4 5 6 7 2 2
1769-OW8 (DC) +VDC OUT OUT OUT OUT +VDC OUT OUT OUT OUT +VDC +VDC
1 0 1 2 3 1 4 5 6 7 2 2

1771-IAD (AC), IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
IND (AC) L1 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 L2
1771-IMD (AC) IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 L2
1771-IAD (DC), IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM
IND (DC) +V 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
1771-IMD (DC) IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN COM
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
1771-IBD, ICD IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 COM

IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN IN
1771-IGD +V +V 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 +V COM

1771-OAD, OND, OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
L1 L1 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 L1 L2
OMD

1771-OBD, OGD +V +V OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT +V COM
00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

NUMERIC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
LED LABEL 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Publication 1492-TD008D-EN-P - January 2009


184 Digital/Analog Programmable Controller Wiring Systems

Accessories
Digital/Analog Programmable Controller Wiring Systems

Catalog Number 1492-IFMFH1 Catalog Number 1492-ISOSW-1 Catalog Number 1492-SJM5-10


Fuse Holder Isolation Switch Fuse Plug Insulated Side Jumper

Replacement Fuse Holders

IFM

The 1492-IFMFH1 fuse holders accommodate either a 5 x 20 mm fuse or the


Catalog Number 1492-ISOSW-1 isolation switch plug and reside in the IFM
or AIFM under normal operation. All of the fusible Bulletin 1492 IFMs and
AIFMs come standard with fuse holders (for the number of fuse holders
included, refer to the specifications for each IFM or AIFM).
Replacement fuse holders (Catalog Number 1492-IFMFHI) are available in
packages of 20. Catalog Number 1492-IFMFHI fuse holders are not
compatible with fusible expandable XIMs.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 185

Accessories, Continued Replacement Fuse Holders, Continued

AIFM

The Catalog Number 1492-IFMFH1 fuse holders accommodate a 5 x 20 mm


fuse or the Catalog Number 1492-ISOSW-1 isolation switch fuse plug and
reside in the AIFM under normal operation. All of the fusible Catalog
Number 1492 AIFMs come standard with the fuse holders — 10 fuse holders
with the Catalog Number 1492-AIFM4C-F-5, -AIFM4I-F-5, and -AIFM8-F-5
modules; 20 fuse holders with the Catalog Number 1492-AIFM16-F-3, and
-AIFM16-F-5 modules. Replacement fuse holders are available in packages of
20.

Replacement Relays

The relays in the Relay Master and Relay Expander modules are replaceable.
The following replacement relays must be used:

Replacement Relays

XIM Catalog Number Replacement Part Catalog Number


1492-XIM4024-16R, -16RF 700-HK36Z24
1492-XIM4024-8R 700-HK36Z24
1492-XIM2024-8R, -16R 700-HK36Z24
1492-XIM20120-8R, -16R, -16RF 700-HK36A1
1492-XIM24-8R, -16RF 700-HK36Z24
1492-XIM120-8R 700-HK36A1
Flexible Relay Module Expansion Cable W22101-061-01

Isolation Switch Plugs

The Catalog Number 1492-ISOSW-1 is an isolation switch or “dummy fuse”


in a 5 x 20 mm fuse form factor. The isolation switch plugs will fit into the
Catalog Number 1492-IFMFH1 fuse holders. If fusing is not desired on a
fusible IFM or AIFM, the Catalog Number 1492-ISOSW-1 isolating switch
can be used to provide feed-through functionality under normal operation and
isolation switch functionality once power has been removed from the circuit.
The isolation switch can then be opened for maintenance and troubleshooting.
Metering equipment can also be inserted into a two-wire transmitter circuit to
measure input loop current. The Catalog Number 1492-ISOSW-1 isolation
switch plugs are available in packages of four.

Publication 1492-TD008D-EN-P - January 2009


186 Digital/Analog Programmable Controller Wiring Systems

Accessories, Continued Insulated Side Jumpers

The Catalog Number 1492-SJM5-10 is a 10-pole “comb-style” insulated side


jumper. A side cutter can be used to cut the 10-pole jumper into smaller pole
assemblies. The jumper fits the field-side terminal spacings on all of the
Bulletin 1492 IFMs and AIFMs. Use of this jumper is a convenient means of
connecting unused inputs together on the feed-through. The Catalog
Number 1492-SJM5-10 insulated side jumpers are available in packages of 10.

Web Site Information Wiring diagrams are provided on-line if you require additional information to
wire your field device to the terminals of the IFM, XIM or AIFM wiring
system modules.
Visit the following web site for I/O wiring diagrams of the Interface Modules
and cables:
1. http://www.ab.com/raise
2. Type in the catalog number of the IFM/XIM or AIFM you are
interested in. Click on “Submit.”
3. Click on the Modify key (lower left).
4. Click on the areas that indicate NO SELECTION and enter your
information (e.g, I/O Platform, I/O Module, etc.).
5. To obtain the wiring diagram, be sure to select the Pre-Wired Cable
Connector selection.
6. Configure the 1492 cable for your application by filling in the NO
SELECTION areas.
7. Click on the Accept key for the 1492 cable.
8. Click on the Accept key for the 1492 wiring system module (E.g., 1492-
IFM20F).
9. The configuration results page is displayed. In the selected components
table column “Supplementary Documents,” click on the “Wiring
Diagram for the I/O Module to IFM.”

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 187

Quick Reference
Digital IFM Specifications

Digital IFM Voltage Max. Max. Current Dimensions Indicator Label Card Replacement
Catalog Number Range Current (Per (Per Module) (W x H x D) (in.)➊ Circuit Current Part
Circuit) (Nominal) Catalog Number ➋
1492-IFM20F, -RIFM20F 0…264V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ — 46006-190-01, 46006-233-01
1492-IFM20FN, -RIFM20FN 0…132V AC/DC 2A 12 A 2.36 x 3.27 x 2.78➌ — 46006-197-01, -237-01, -220-
01
1492-IFM20F-2, -RIFM20F-2 0…264V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ — 46006-192-01, -235-01, -221-
01
1492-IFM20F-3 0…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 — 46006-210-01
1492-IFM20D24 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 2 mA 46006-190-01, 46006-233-01
1492-IFM20D24N 10…30V AC/DC 2A 12 A 2.36 x 3.27 x 2.78 2 mA 46006-197-01, -237-01, -220-
01
1492-IFM20D24-2 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 2 mA 46006-192-01, -235-01, -221-
01
1492-IFM20D24A-2 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 2 mA 46006-211-01
1492-IFM20DS24-4 10…60V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 1.6 mA 46006-209-01
1492-IFM20D24-3 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 2 mA 46006-193-01, 46006-236-01
1492-IFM20D120 85…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 2.5 mA 46006-190-01, 46006-233-01
1492-IFM20D120N 85…132V AC 2A 12 A 2.36 x 3.27 x 2.78 2.5 mA 46006-197-01, -237-01, -220-
01
1492-IFM20D120-2 85…132V AC 2A 12 A 4.33 x 3.27 x 2.78 2.5 mA 46006-192-01, -235-01
1492-IFM20D120A-2 85…132V AC 2A 12 A 4.33 x 3.27 x 2.78 2.5 mA 46006-211-01
1492-IFM20DS120-4 85…132V AC 2A 12 A 4.33 x 3.27 x 2.78 2.6 mA 46006-209-01
1492-IFM20D240-2 204…264V AC 2A 12 A 4.33 x 3.27 x 2.78 2.5 mA 46006-192-01, -235-01
1492-IFM20D240A-2 204…264V AC 2A 12 A 4.33 x 3.27 x 2.78 2.5 mA 46006-211-01
1492-IFM20F-F-2, -RIFM20F-F-2 0…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ — 46006-192-01, -235-01, -221-
01
1492-IFM20F-F24-2, -RIFM20F-F24-2 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ 2 mA 46006-192-01, -235-01, -221-
01
1492-IFM20F-F24A-2, -RIFM20F-F24A-2 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ 2.4 mA 46006-212-01, -189-01
1492-IFM20F-F120-2, -RIFM20F-F120-2 85…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ 2.5 mA 46006-192-01, -235-01, -221-
01
1492-IFM20F-F120A-2, -RIFM20F-F120A-2 85…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ 1.2 mA 46006-212-01, -189-01
1492-IFM20F-F240-2 204…264V AC/DC 2A 12 A 4.72 x 3.27 x 2.78 1.2 mA 46006-192-01, -235-01
1492-IFM20F-FS-2 0…132V AC/DC 2A 12 A 2.36 x 3.27 x 2.78 — 46006-204-01
1492-IFM20F-FS24-2 10…30V AC/DC 2A 12 A 2.36 x 3.27 x 2.78 2 mA 46006-204-01
1492-IFM20F-FS24A-4 10…30V AC/DC 2A 12 A 3.15 x 3.27 x 2.78 2.4 mA 46006-215-01
1492-IFM20F-FS120-2 85…132V AC/DC 2A 12 A 2.36 x 3.27 x 2.78 2.5 mA 46006-204-01
1492-IFM20F-FS120-4 85…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 1.2 mA 46006-214-01
1492-IFM20F-FS120A-4 85…132V AC/DC 2A 12 A 3.15 x 3.27 x 2.78 2.2 mA 46006-215-01
1492-IFM20F-FS240-4 204…264V AC/DC 2A 12 A 4.33 x 3.27 x 2.78 1.2 mA 46006-214-01
1492-IFM40F, -RIFM40F 0…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ — 46006-191-01, -234-01, 252-01
1492-IFM40F-2 0…132V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 — 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01,
-253-01
1492-RIFM40F-2 0…132V AC/DC 2A 12A 8.27 x 3.27 x 2.78 — 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01,
-253-01
1492-IFM40F-3 0…60V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 — 46006-193-01, 46006-236-01
1492-IFM40D24, -RIFM40D24 10…30V AC/DC 2A 12 A 4.33 x 3.27 x 2.78➌ 2 mA 46006-191-01, -234-01, -252-
01
1492-IFM40D24-2 10…30V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 2 mA 46006-194-01, -195-01, -253-
01
1492-IFM40D24A-2 10…30V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 2 mA 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01,
-253-01
1492-RIFM40D24A-2 10…30V AC/DC 2A 12A 8.27 x 3.27 x 2.78 2 mA 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01,
-253-01
1492-IFM40DS24-4 10…60V AC/DC 2A 12 A 6.69 x 3.27 x 2.78 4.1 mA 46006-208-01
1492-IFM40DS24A-4 10…30V AC/DC 2A 12 A 6.69 x 3.27 x 2.78 4.1 mA 46006-208-01
1492-IFM40D24-3 10…30V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 2 mA 46006-193-01, 46006-236-01

Publication 1492-TD008D-EN-P - January 2009


188 Digital/Analog Programmable Controller Wiring Systems

Digital IFM Specifications (Continued)

Digital IFM Voltage Max. Max. Current Dimensions Indicator Label Card Replacement
Catalog Number Range Current (Per (Per Module) (W x H x D) (in.)➊ Circuit Current Part
Circuit) (Nominal) Catalog Number ➋
1492-IFM40D120-2 85…132V AC 2A 12 A 8.27 x 3.27 x 2.78 2.5 mA 46006-194-01, -195-01, -253-
01
1492-IFM40D120A-2 85…132V AC 2A 12 A 8.27 x 3.27 x 2.78 2.5 mA 46006-194-01, -195-01, -253-
01
1492-IFM40DS120-4 85…132V AC 2A 12 A 6.69 x 3.27 x 2.78 2.6 mA 46006-208-01
1492-IFM40DS120A-4 85…132V AC 2A 12 A 6.69 x 3.27 x 2.78 2.6 mA 46006-208-01
1492-IFM40DS240A-4 204…264V AC 2A 12 A 6.69 x 3.27 x 2.78 2.6 mA 46006-208-01
1492-IFM40F-F-2 0…132V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 — 46006-194-01, -195-01, -253-
01
1492-IFM40F-F24-2 10…30V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 2 mA 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01
1492-RIFM40F-F24-2 10…30V AC/DC 2A 12A 8.27 x 3.27 x 2.78 2 mA 46006-224-01, -225-01, -239-
01, -240-01, -194-01, -195-01
1492-IFM40F-F24D-2 10…30V DC 2A 8A 4.72 x 3.27 x 2.78 <0.05 mA 46006-201-01
1492-IFM40F-F24AD-4 10…30V DC 2A 8A 7.09 x 3.27 x 2.78 <0.05 mA 46006-206-01
1492-IFM40F-F120-2 85…132V AC/DC 2A 12 A 8.27 x 3.27 x 2.78 2.5 mA 46006-194-01, -195-01, -253-
01
1492-IFM40F-FS-2 0…132V AC/DC 2A 12 A 4.72 x 3.27 x 2.78 — 46006-201-01
1492-IFM40F-FS24-2 10…30V AC/DC 2A 12 A 4.72 x 3.27 x 2.78 2 mA 46006-201-01
1492-IFM40F-FS24-4 10…30V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 2.4 mA 46006-207-01
1492-IFM40F-FS120-2, -RIFM40F-FS120-2 85…132V AC/DC 2A 12 A 4.72 x 3.27 x 2.78 2.5 mA➌ 46006-201-01
1492-IFM40F-FS120-4 85…132V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 1.4 mA 46006-206-01
1492-RIFM40F-FS120-4 85…30V AC/DC 2A 12A 7.09 x 3.27 x 2.78 1.4 mA 46006-226-01
1492-IFM40F-FS240-4 204…264V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 2.4 mA 46006-207-01
1492-IFM40F-FS24A-4 10…30V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 3.1 mA 46006-226-01
1492-IFM40F-FS120A-4 85…132V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 1.4 mA 46006-226-01
1492-RIFM40F-FS120A-4 85…30V AC/DC 2A 12A 7.09 x 3.27 x 2.78 1.4 mA 46006-226-01
1492-IFM40F-FS-4 0...264V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 — 46006-207-01
1492-IFM40F-FSA-4 0…132V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 — 46006-226-01
1492-IFM40F-FS240A-4 159...265V AC/DC 2A 12 A 7.09 x 3.27 x 2.78 1.4 mA 46006-226-01
➊ Dimensions are in inches. To convert to millimeters, multiply inches by 25.4.
➋ Ships with each module. For spare part, precede part number with the letter “W.”
➌ Add 0.39 in. to the width dimension for Bul. 1492Rxxx module.

Analog IFM Specifications


Analog IFM Voltage Max. Current Max. Current Dimensions Indicator Circuit Label Card
Catalog Number Range (Per Circuit) (Per Module) (W x H x D) (in.) Current (Nominal) Replacement Part
➊ Catalog Number ➋
1492-AIFM4-3, -RAIFM4-3 0…10V DC 2A 12 A 2.36 x 3.27 x 2.74 — 46006-205-01
1492-AIFM4C-F-5 10…30V DC 2A 12 A 3.15 x 3.27 x 2.74 2 mA 46006-203-01
1492-AIFM4I-F-5 10…30V DC 2A 12 A 3.15 x 3.27 x 2.74 2 mA 46006-203-01
1492-AIFM6S-3, -RAIFM6S-3 0…132V AC/DC 2A 12 A 3.15 x 3.27 x 2.74 — 46006-202-01
1492-AIFM6TC-3 0…132V AC/DC 2A 12 A 3.15 x 3.27 x 2.74 — 46006-202-01
1492-AIFMCE4 5…30V DC 2A 8A 5.12 x 3.27 x 2.74 — 46006-232-01
1492-AIFMCE4-F 5…30V DC 2A 8A 5.12 x 3.27 x 2.74 1 mA @ 5V DC 46006-232-01
6 mA @ 24V DC
1492-AIFM8-3, -RAIFM8-3 0…132V AC/DC 2A 12 A 4.33 x 3.27 x 2.74 — 46006-200-01, 46006-
238-01
1492-AIFM8-F-5 10…30V DC 2A 12 A 4.72 x 3.27 x 2.74 2 mA 46006-196-01, -254-
01
1492-AIFM16-F-3 10…30V DC 2A 12 A 4.72 x 3.27 x 2.74 2 mA 46006-213-01
1492-AIFM16-F-5 10…30V DC 2A 12 A 8.27 x 3.27 x 2.74 2 mA 46006-198-01
1492-AIFMQS 10…30V DC 3A 12 A 4.72 x 3.27 x 2.74 — 46006-199-01
1492-AIFMPI 0…30V DC 2A 12 A 4.72 x 3.27 x 2.74 2 mA 46006-243-01

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 189

➊ Dimensions are in inches. To convert to millimeters, multiply inches by 25.4.


➋ Ships with each module. For spare part, precede part number with the letter “W.”

Quick Reference,
Continued

Relay Master/Expandable Interface Module Specifications ➊


Relay Master/Expandable XIM Relay Coil Max. Current Max. Current Dimensions Indicator Circuit Label Card
Catalog Number Voltage (Per Circuit/ (Per Module) (W x H x D) (in.) Current Replacement Part
Range Per Relay ➊ (Nominal) Catalog Number ➋
Pair)
1492-XIM4024-16R, -RXIM4024- 20…26V DC 10/12 A 96 A 9.06 x 3.27 x 2.78 2 mA 46006-222-01
16R
1492-XIM4024-8R 20…26V DC 10/12 A 48 A 6.30 x 3.27 x 2.78 2 mA 46006-216-01
1492-XIM2024-8R 20…26V DC 10/12 A 48 A 6.30 x 3.27 x 2.78 2 mA 46006-216-01
1492-XIM20120-8R 96…132V AC 10/12 A 48 A 6.30 x 3.27 x 2.78 2 mA 46006-216-01
1492-XIM24-8R, -RXIM24-8R 20…26V DC 10/12 A 48 A 6.30 x 3.27 x 2.78 2 mA 46006-217-01
1492-XIM120-8R 96…132V AC 10/12 A 48 A 6.30 x 3.27 x 2.78 2 mA 46006-217-01
1492-XIM2024-16R 20...26V DC 10/12 A 96 A 10.65 x 3.27 x 2 mA 46006-223-01
2.78
1492-XIM2024-16RF 20...26V DC 10/12 A 96 A 10.65 x 3.27 x 2 mA 46006-223-01
2.78
1492-XIM20120-16R 96...132V AC 10/12 A 96 A 10.65 x 3.27 x 2 mA 46006-223-01
2.78
1492-XIM20120-16RF 96...132V AC 10/12 A 96 A 10.65 x 3.27 x 2 mA 46006-223-01
2.78
1492-XIM4024-16RF 20...26V DC 10/12 A 96 A 11.05 x 3.27 x 2 mA 46006-223-01
2.78
1492-XIMF-2 0…132V 2/NA A 4A 3.15 x 3.27 x 2.19 — 46006-218-01
AC/DC
1492-XIMF-F24-2 10…30V DC 2/NA A 4A 3.15 x 3.27 x 2.28 2 mA 46006-218-01
1492-XIMF-F120-2 85…132V AC 2/NA A 4A 3.15 x 3.27 x 2.28 2 mA 46006-218-01
1492-XIM24-16RF 20...26V DC 10/12 A 96 A 11.05 x 3.27 x 2 mA 46006-219-01
2.78
➊Dimensions are in inches. To convert to millimeters, multiply inches by 25.4.
➋Ships with each module. For spare part, precede part number with the letter “W.”

1764-24AWA and -24BWA Base Unit Output Current Ratings when using 1492-IFM20x Modules

IFM Cat. Number Voltage Range 1764-24AWA & 24BWA Max. Current per IFM Module Operating
Max. Current/Output IFM Module Indicator Circuit Ambient
using IFM Current Temperature
0…264V AC (Out 0-Out 3) 2 Amps
1492-IFM20F 12 Amps NA 0°C to 60°C
10…125V DC (Out 4-Out 11) 1 Amps
0…132V AC (Out 0-Out 3) 2 Amps
1492-IFM20FN 12 Amps NA 0°C to 60°C
10…125V DC (Out 4-Out 11) 1 Amps
0…264V AC (Out 0-Out 3) 2 Amps
1492-IFM20F-2 12 Amps NA 0°C to 60°C
10…125V DC (Out 4-Out 11) 1 Amps

Publication 1492-TD008D-EN-P - January 2009


190 Digital/Analog Programmable Controller Wiring Systems

Note: For inputs use standard 2 A/circuit ratings

1764-28BXB Base Unit Output Current Ratings when using 1492-IFM20x Modules

IFM Cat. Number Voltage Range 1764-2BXB Max. Max. Current per IFM Module Operating
Current/Output using IFM IFM Module Indicator Circuit Ambient
Current Temperature
0…264V AC (Out 0-Out 1) 2 AMP
1492-IFM20F 10…125V DC (Out 8-Out 11) 1 AMP 12 Amps NA 0°C to 60°C
24V DC (Out 2-Out 7) 0.5 AMP
0…132V AC (Out 0-Out 1) 2 AMP
1492-IFM20FN 10…125V DC (Out 8-Out 11) 1 AMP 12 Amps NA 0°C to 60°C
24V DC (Out 2-Out 7) 0.5 AMP
0…264V AC (Out 0-Out 1) 2 AMP
1492-IFM20F-2 10…125V DC (Out 8-Out 11) 1 AMP 12 Amps NA 0°C to 60°C
24V DC (Out 2-Out 7) 0.5 AMP
Note: For inputs use standard 2 A/circuit ratings

1762-L40AWA and -L40BWA Base Unit Output Current Ratings when using 1492-IFM40x Module

IFM Cat. Number Voltage Range 1762-L40AWA & Max. Current per IFM Module Operating
-L40BWA max. IFM Module Indicator Circuit Ambient
Current/Output using IFM Current Temperature
0…132V AC (Out 0-Out 3) 2 Amps
1492-IFM40F 12 Amps NA 0°C to 60°C
10…125V DC (Out 4-Out 15) 1 Amps
0…264V AC (Out 0-Out 3) 2 Amps
1492-IFM40F-2 12 Amps NA 0°C to 60°C
10…125V DC (Out 4-Out 15) 1 Amps
Note: For inputs use standard 2 A/circuit ratings.

1762-L40BXB Output Current Ratings when using 1492-IFM40x Modules

IFM Cat. Number Voltage Range 1762-L40BXB Max. Max. Current IFM Module Operating
Current/Output using IFM per IFM Indicator Ambient
Module Circuit Temperature
Current
0…132V AC (Out 0,1,10,11) 2 AMP
1492-IFM40F 10…125VD C (Out 12-Out 15) 1 AMP 12 Amps NA 0°C to 60°C
24V DC (Out 2-Out 9) 0.5 AMP
0…264V AC (Out 0,1,10,11) 2 AMP
1492-IFM40F-2 10…125V DC (Out 12-Out 15) 1 AMP 12 Amps NA 0°C to 60°C
24V DC (Out 2-Out 9) 0.5 AMP
Note: For inputs use standard 2 A/circuit ratings.

Publication 1492-TD008D-EN-P - January 2009


Digital/Analog Programmable Controller Wiring Systems 191

General Wiring System Specifications


Parameter Specifications
Agency Certifications: cULus: Hazardous Locations; Class I Div 2 (all modules, except those with relays);
Modules and Cables Groups A, B, C, and D. Temperature Code T3C @ 60°C.
UL File E10314, Guide No. NRAG
cULus: Ordinary Locations; Module with relays, UL File E113724, Guide No. NRAQ
Agency Certification Modules Factory Mutual (FM): Hazardous Locations; Class I Di v 2 (all except modules with relays); Groups
A, B, C, and D. Temperature Rating: T3C @ 60°C. FM file J.I.3000590
CE Certifications Compliant for all applicable directives
Maximum Peak Transient Voltage 600V ➊
Terminal Block Wire Range (Rated Cross Section) Fixed Screw Style: #12…#22 AWG (4.0...0.2 mm2)
Removable Screw Style: #12 to #22 AWG 2.5...0.5 mm2)
Removable Push-in Style: #12 to #26 AWG (2.5...0.2mm2)
Wire Strip Length Fixed Screw Style:.32 in. (8.0 mm)
Removable Screw Style:.28 in. (7.0 mm)
Removable Push-in Style:.39 in. (10.0 mm)
Recommended Terminal Block Screw Torque Fixed Screw Style: 3.5…4.5 lb-in. (0.38…0.50 Nm)
Removable Screw Style: 3.5…4.5 lb-in. (0.38…0.50 Nm)
Removable Push-in Style: NA (See Figure 1)
Operating Temperature Range 0…+60°C
Operating Humidity 5% to 95% non-condensing
Storage Temperature Cables -20…+80°C
Storage Temperature Modules -40…+85°C
Pollution Degree 2➋
➊ For transients > 600V use a UL Recognized suppression device rated at 2.5 kV withstand.
➋ Pollution Degree 2 is an environment where normally only non-conduction pollution occurs, except for
occasional temporary conductivity caused by condensation shall be expected.

Fixed Screw Style Terminal Block

Max. AWG #22 #20 #18 #16 #14 #12


Max. No. of Wires per Terminal ➊ 3 3 3 2 1 1
➊ Maximum number of the same gauge of wire stranded copper conductors allowed per wire funnel

Figure 1 — Push-in RTB Plug Specifications

Single wire per pole (except by using a ferrule)

For Insertion
- Solid wire: actuator not required
- Stranded wire: actuator required

For Removal

- Solid or stranded wire: actuator required

Clamp Range:
AWG conductor: 26...12 AWG
2
Solid Wire 0.2 ... 2.5 mm
2
Stranded Wire 0.2 ... 2.5 mm
2
Ferrule 0.2 ... 2.5 mm
2
Ferrule w/ plastic collar 0.2 ... 1.5 mm

Publication 1492-TD008D-EN-P - January 2009


192

Maximum Switching Capacity


Relay Contact Rating
Electrical Ratings: Cat. No. 700-HK36___ ➋
Rated Thermal Current (Ith) 1-pole, 1 CO, SPDT - 16 A ➊
Rated Thermal Current (UI) 250V IEC, 300V UL/CSA ➊

Electrical Inductive VAC 120VAC AC-15, 6.2 A


Ratings of B300 Pilot duty, 3 A
Contacts 1/3 Hp (0.24 kW) 1-phase
240VAC AC-15, 3.1 A
B300 Pilot duty, 1.5A
3/4 Hp (0.55 kW) 1-phase
230VAC 0.55 kW 1-phase
Inductive VDC 24VDC DC-13, 5.0 A
125VDC DC-13, 0.2 A
R300 Pilot Duty, 0.22 A
250VDC DC-13, 0.1 A
R300 Pilot duty, 0.11 A
Resistive 23VAC AC-1, 16 A ➊
277VAC 16A General use ➊
Make, Break, 30VDC DC-1, 12 A
and Continuous 10 A, Resistive
Minimum Permissible Contact 300 mW (5V/60 mA or 60V/5 mA) for silver contacts
Rating
➊ Maximum module current:
-10 Amp per relay output
-12 Amps per 2 adjacent relay outputs
➋ Replacement relays:
-24V DC control (coil) voltage (Cat. No. 700-HK36Z24)
-120V AC control (coil) voltage (Cat. No. 700-HK36A1)

Bul. 700-HK36 SPDT


Electrical Life (AC Loads) vs. Contact Life

Resistive load - cos = 1


Inductive load - cos = 0.4
Cycles

Publication 1492-TD008D-EN-P - January 2009


193

Bul. 700-HK36 Maximum DC1 Breaking Capacity


Electrical Life (DC Loads) vs. Contact Life
20.0

DC Breaking Current [A]


10.0
6.0
4.0
2.0 Resistive Load
1.0

0.2

20 60 100 140 180 220


DC Voltage [V]

• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 x 103 can be expected.

• In case of inductive loads (DC13), the connection of a diode in parallel


with the load will permit a similar electrical life as for a DC1 load.
Note: The release time for the load will be increased.

Publication 1492-TD008D-EN-P - January 2009


194

Publication 1492-TD008D-EN-P - January 2009


Publication 1492-TD008D-EN-P — January 2009
Supercedes Publication 1492-TD008C-EN-P — September 2005 Copyright ©2009 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.