Professional Documents
Culture Documents
Instumentation and Controle
Instumentation and Controle
Process variables like temperatures, pressures, flow rates, levels and compositions
must be monitored and controlled in all distillation processes. These process
variables within a distillation system affect one another, whereby a change in one
process variable will result in changes in other process variables. Thus, in column
control one should be looking at the whole column and not focusing on any
particular sections only.
Each column has a control system that consists of several control loops. The loops
adjust process variables as needed to compensate for changes due to disturbances
during plant operation. Each of the process variables has its own control loop,
which typically consists of a sensor and transmitter, controller and control valve.
See the Figure below. Each control loop keeps track of the associated process
variable. An adjustment is made to a process variable by varying the opening of its
control valve. The stream flow rate is therefore adjusted and a desirable variable is
being controlled.
The sensor measures the process variable from the plant (i.e. plant data) and the
transmitter sends the information to the DCS (Distributed Control System)
controller located in the control room. The controller checks if the process variable
agrees with the set point. If not, it will send corrective signal to the control valve
that will make adjustment in the plant so as to match the process variable to the set
point. This goes on continuously, essentially in a loop - hence the term "control
loop".
There are several control loops associated with the distillation
column:
A:-Temperature:
Application Considerations
Selection
In process control a wide selection of temperature sensors are available.
However, the required range, linearity, and accuracy can limit the selection. In the
final selection of a sensor, other factors may have to be taken into consideration,
such as remote indication, error correction, calibration, vibration sensitivity, size,
response time, longevity, maintenance requirements, and cost. The choice of
sensor devices in instrumentation should not be degraded from a cost standpoint.
Process control is only as good as the monitoring elements.
Installation
Care must be taken in locating the sensing portion of the temperature sensor,
it should be fully encompassed by the medium whose temperature is being
measured, and not be in contact with the walls of the container. The sensor should
be screened from reflected heat and radiant heat if necessary. The sensor should
also be placed downstream from the fluids being mixed, to ensure that the
temperature has stabilized, but as close as possible to the point of mixing, to give
as fast as possible temperature measurement for good control. A low thermal time
constant in the sensor is necessary for a quick response. Compensation and
calibration may be necessary when using pressure-spring devices with long tubes
especially when accurate readings are required.
Calibration
Temperature calibration can be performed on most temperature sensing
devices by immersing them in known temperature standards which are the
equilibrium points of solid/liquid or liquid/gas mixtures, which is also known as
the triple point. Most temperature sensing devices are rugged and reliable, but can
go out of calibration due to leakage during use or contamination during
manufacture and should therefore be checked on a regular basis.
Protection
In some applications, temperature sensing devices are placed in wells or
enclosures to prevent mechanical damage or for ease of replacement. This kind of
protection can greatly increase the system response time, which in some
circumstances may be unacceptable. Sensors may need also to be protected from
over temperature, so that a second more rugged device may be needed to protect
the main sensing device. Semiconductor devices may have built in over
temperature protection. A fail-safe mechanism may also be incorporated for system
shutdown, when processing volatile or corrosive materials.
B:-Level:
Selection
The selection of a flow meter for a specific application to a large extent will
depend on the required accuracy and the presence of particulates, although the
required accuracy is sometimes down graded because of cost. One of the most
accurate meters is the magnetic flow meter which can be accurate to 1 percent of
full scale reading or deflection (FSD). The meter is good for low flow rates, with
high viscosities and has low energy loss, but is expensive and requires a
conductive fluid.
The turbine gives high accuracies and can be used when there is vapor
present, but the turbine is better with clean low viscosity fluids. Table 8.3 gives a
comparison of flow meter characteristics.
The general purpose and most commonly used devices are the pressure
differential sensors used with pipe constrictions. These devices will give accuracies
in the 3 percent range when used with solid state pressure sensors which convert
the readings directly into electrical units or the rotameter for direct visual reading.
The Venturi tube has the highest accuracy and least energy loss followed by
the flow nozzle and the orifice plate. For cost effectiveness the devices are in the
reverse order. If large amounts of particulates are present, the Venture tube is
preferred. The differential pressure devices operate best between 30 and 100
percent of the flow range. The elbow should also be considered in these
applications. Gas flow can be best measured with an anemometer. Solid-state
anemometers are now available with good accuracy, are very small in size, and are
cost effective.
For open channel applications the flume is the most accurate and best if
particulates are present, but is the most expensive. Particular attention should also
be given to manufacturer’s specifications and application notes.
Installation
Because of the turbulence generated by any type of obstruction in an
otherwise smooth pipe, attention has to be given to the placement of flow sensors.
The position of the pressure taps can be critical for accurate measurements. The
manufacturer’s recommendations should be followed during installation. In
differential pressure sensing devices the upstream tap should be one to three pipe
diameters from the plate or constriction and the down stream tap up to eight pipe
diameters from the constriction.
Calibration
Flow meters need periodic calibration. This can be done by using another
calibrated meter as a reference or by using a known flow rate. Accuracy can vary
over the range of the instrument and with temperature and specific weight changes
in the fluid, which may all have to be taken into account. Thus, the meter should be
calibrated over temperature as well as range, so that the appropriate corrections can
be made to the readings. A spot check of the readings should be made periodically
to check for instrument drift that may be caused by the instrument going out of
calibration, particulate build up, or erosion.
Summary of Flow Meter Characteristics
Meter Type Range Accuracy Comments
Percent
Orifice plate 3 to 1 ± 3 FSD Low cost and
accuracy
Venturi tube 3 to 1 ± 1 FSD High cost, good
accuracy, low
losses
Flow nozzle 3 to 1 ± 2 FSD Medium cost,
accuracy
Dall tube 3 to 1 ± 2 FSD Medium cost,
accuracy, low
losses
Elbow 3 to 1 ± 6 −10 FSD Low cost, losses,
sensitivity
Pilot static tube 3 to 1 ± 4 FSD Low sensitivity
Control Scheme:
REFERENCE:-
www.separationprocesses.com , chap-2