Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

RCA for the Month of August 1-8-2019 to 31-8-2019

DATE FLOW CODE FROM TO BREAKDOWN TIME TONNAGE LOSS


1/8/2019 Z2S06M1 6:00
R1M23 23:00 12:20 1:33 233T
11/8/2019
Z1p37 14:15 14:45 0:50 132T
18/8/2019 Z3M03 10:20 14:40 4:33 217T
19/8/2019 Z1M10 10:20 12:45 2:41 301T
22/8/2019 W2A17 17:30 19:45 2:25 384 T
24/8/2019 R1S01 23:45 0:10 0:41 72T
J2J02 12:45 13:00 0:25 43T
28/8/2019
Raw Mill-2 22:50 23:40 1:23 100T
19 to 31-8-2019

FAULT
Motor Ground.
Main motor starter fault.
Unit Fault
Star Contactor Heat up.
Tripped (unit fault)
Feed divertor Motor problem.
Separator motor tripped with unit fault alarm.
ID fan tripped with not ready alarm.
Bridge reclaimer power cable damaged.
REASON
Motor undercapacity in design.
MV trolley spring charging motors' cable was broken.
PS-431 Mal-functioning
Frequent start stops, rotor starter under capacity
Bearings issue
Brake of motor was operated and not releasing the motor.
Separator fan bearing issue lead to overcurrent.
Relay base for cooling fan was loose and led to tripping.
Cable damaged when it touched track due to cable drum issue.
ACTION
250kw, 1500 rpm installed. Motor to be re-winded.
attached the cable.
By-passed.(caused many trips)
Carbonised contacts cleaned, Jumps replaced.
Motor replaced.
Removed brake and released the mechanism.
Reset the fault and continued operation.( caused multiple trippings until fan bearing seezed.
Relay base changed.
Repaired the cable.

You might also like