Metering Devices IQ DP-4000: Cutler-Hammer

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Technical Data

Cutler-Hammer Effective: May 2000 Page 1

Supercedes TD.17.03.T.E
pages 1-4, dated May 1999
Metering Devices
IQ DP-4000

IQ DP-4000
Applications
■ Monitoring of all common
electrical parameters
■ Optional protective alarm
functions
Metered/Monitored Parameters
■ RMS sensing
■ Phase currents
■ Volts: L-L, L-N
■ Power: real, reactive, apparent
■ Energy: real, reactive, apparent
■ Frequency
■ Power factor
■ % THD: Current and Voltage
■ Min/max values
■ Fixed or sliding demand windows

Communications
■ Optional interface capability to
computer network for data collec-
tion, storage and/or printout via
the Cutler-Hammer PowerNet General Description Protective/Event Alarming
System The IQ DP-4000 is a microprocessor- ■ Undervoltage
Physical Characteristics based monitoring and protective ■ Overvoltage

■ Large visible LED display device that provides complete elec- ■ Current phase loss
trical metering and system voltage ■ Voltage phase loss
■ Height: 10.25 inches
protection. In one compact, standard ■ Phase reversal
■ Width: 6.72 inches
package the IQ DP-4000 will provide
■ Depth:4.42 inches without PONI ■ Phase unbalance
an alternative to individually
5.40 inches with PONI mounted and wired conventional ■ Optional current and power

■ Membrane Faceplate NEMA 3R meters and switches. The new DP- demand threshold
and 12 rated 4000 also monitors Apparent Power Retrofit Opportunities
Listings/Certifications (VA), Reactive Energy (Var-Hours), ■ Retrofit of existing electrical
Apparent Energy (VA-Hours), and distribution systems with the IQ
■ UL/CUL/CSA Listed
percent THD to provide the user DP-4000 for power, quality, load,
■ CE mark EN61010-1 (1993)
with basic power quality information. and energy monitoring.
EN50082-2 (1994) The IQ DP-4000 meets and surpasses
■ Mounting Flange option for
Ratings UL/CSA/CE standards.
application where additional
■ Application to 500 kV, no PTs door mounting space is required.
The IQ DP-4000’s rugged construc-
to 600V tion is designed to withstand harsh (See TD.17.08.T.E page 2).
■ CT ratios selectable from 5:5A conditions such as temperature ■ Separate wall mounted enclosure,
to 12800:5A variations, outdoor applications, Enclosed IQ
■ Standard 120/600 Vac line and industrial environments. The (See TD.17.08.T.E page 1).
3-phase power supply module, membrane faceplate pushbuttons
99-264 Vac or 99-275 Vdc. are easy-to-use and both the parame-
Two separate source power ter LED and window displays are
supply modules available easily visible.

TD.17.03A.T.E
Technical Data Metering Devices Cutler-Hammer
Page 2 Effective: May 2000 IQ DP-4000

Historical Values ■ Optional Current and Power Inputs/Outputs (4100 Model)


■ Present Demand Current (Per Demand Threshold ■ Three form C relay outputs select-
Phase) 5, 10, 15, 20, 25, 30, 45 or Description of Protection Functions able: Trip, Alarm, kWHR pulse
60 minute windows Overvoltage initiator
■ Present Demand Watts, Vars, Range 105% to 140% (5% increments). ■ One synch input for kW utility
and VA 5, 10, 15, 20, 25, 30, 45 or demand sync
60 minute windows Undervoltage
Model Input Output
Sliding or fixed window for power Range 60% to 95% (5% increments).
Sync pulse input (Model 4100) 4000 0 0
Phase Unbalance 4100 1 Digital 3 Relays
Cutler-Hammer PowerNet broad (dry contact)
cast demand sync Deviation between any two phases
percentage of nominal line voltage
■ Minimum and Maximum Values Drilling Pattern
preset by DIP switches. Range 5% to
Current (per phase) 40% (5% increments). 5.38
Voltage (per phase, L-L, L-N) 2.69
Watts, Vars and VA Phase Reversal
Power Factor (displacement Any two phases become reversed for
8.90
and apparent) the selected delay.
Frequency
Voltage Phase Loss
■ Peak Values Less than 50% of the nominal line 6.68 9.38
Percent THD Parameters voltage detected.
Demand Parameters
Current Phase Loss 4.45
Alarm/Protective Functions 4.69
Smallest phase current is less than
■ Alarm/Protective functions
1/16 of the largest phase current.
(all models) include: .06 RAD
2.23 4 Places
Overvoltage Delay
Undervoltage Allows a delay before an alarm
Current phase loss occurs. (Range 1-20 seconds in 2.53
Voltage phase loss 1 second increments). 5.06
Phase unbalance .218 DIA
Note: Unit must be powered for this 10 Places
Phase reversal
to occur.
■ User-programmable alarm and
IQ DP-4000 Side View
reset threshold levels and delay
intervals With Communication Module
5.400
0.50 4.420
Faceplate Without Communication Module
Current Transformer Connections

Power
Module
P3

Setpoint Display
LED Bank
Power Module
Connection Setpoint DIP
GND

Switch Bank 1
Chassis Ground
Pulse
Sync.

Power Module

2
Rotary Select Switch
1/2 Hp @ 240 Vac 1/3 Hp @ 120 Vac

Sync Pulse 3
Alarm 1

4
(dry contact input) Setpoint Save Button
5
Alarm 1 Field Replaceable 6
PONI

Relay
Alarm 2

Fuse 7
8
Alarm 2 Communication 9
MWH Pulse

Relay Connection 10
11
Pulse Initiator/
Load Shed
Relay

System Voltage Input Connections

TD.17.03A.T.E
Cutler-Hammer Metering Devices Technical Data
IQ DP-4000 Effective: May 2000 Page 3

Field Wiring Connections


3-Phase 3-Wire (Up to 600 Volts) 3-Phase 4-Wire (Up to 600 Volts)
Direct Voltage Connection and External Current Transformers Direct Voltage Connection and External Current Transformers
N
C 3CT C 3CT
L3 L3
B 2CT Load B 2CT
Line L2 Line L2 Load
A 1CT A 1CT
L1 L1

(99-275 Vdc) (99-275 Vdc)


(99-264 Vac) (99-264 Vac)
(24-48 Vdc) (24-48 Vdc)
Control Power Control Power
IQ DP-4000 IQ DP-4000
Fuse Fuse
HIC HIB HIA HIC HIB HIA
1 2 3 4 A B C H2C H2B H2A
1 2 3 4 A B C H2C H2B H2A
Neutral Neutral
Term. Term.

Separate Source Power Supply Module Separate Source Power Supply Module

3-Phase 3-Wire (Above 600 Volts) 3-Phase 4-Wire (Above 600 Volts)
External Voltage Transformers and Current Transformers External Voltage Transformers and Current Transformers
N
C 3CT C 3CT
L3 L3
B 2CT Line B 2CT Load
Line L2 Load L2
A 1CT A 1CT
L1 L1

Fuse Fuse

Open Delta WYE


VT Connection Connection

IQ DP-4000 IQ DP-4000
Fuse Fuse
HIC HIB HIA HIC HIB HIA
A B C H2C H2B H2A A B C H2C H2B H2A
Neutral Neutral
Term. Term.

Self-Powered Power Supply Module Self-Powered Power Supply Module

TD.17.03A.T.E
Technical Data Metering Devices
Page 4 Effective: May 2000 IQ DP-4000
Cutler-Hammer

Specifications
Power Requirements Current Input (Each Channel) Voltage Input (Each Channel)
10 VA Nominal Full Voltage Range
Frequency Scale Current: 5 amperes ac (Nominal): 90-600 Vac
50/60 Hz Current Range for Nominal Full
Rated Accuracy: 0-15 amperes ac Scale Voltage: 120-600 Vac
Operating Temperature
-25° to 70°C Overload
Overload
Withstand: 15 amperes ac
Operating Humidity Withstand: 660 Vac
continuous
0.0% to 95% noncondensing continuous
300 amperes ac
4 kV 1.2/50µs
1 second

TD1703ATE
Dry Contact Input
24 Vdc differential across input pair Burden: 0.003 VA Burden: 3-phase power
of terminals; minimum pulse width, module 10 VA
50 msec Control Power Input
Fuses Separate Source Self Powered Dc Source
(Supplied with three-phase power
Input Range, ac 110-240 Vac ±10% 110-600 Vac ±10% N/A
module only.) 3/4 ampere, 600-volt
Frequency Range 45-66 Hz 45-66 Hz N/A
bus type KTK-R-3/4 (3 required)
Input Range, dc 110-250 Vdc ±10% N/A 24-48 Vdc ±20%
Contact Rating (Model 4100) Burden 10 VA 10 VA 10 VA
10 amperes at 120/240 Vac (resistive)
10 amperes at 30 Vdc (resistive) Displayed Values
Compatible with the following Displayed Through Cutler-Hammer Local Display
PowerNet System
systems:
3-phase 3-wire, 3-phase 4-wire Ac Amperes Phases A, B, C ± 0.3% ± 0.3% ± 1 digit
Ac Voltage, Phase A-B, B-C, C-A ± 0.3% ± 0.3% ± 1 digit
Weight Phase A-N, B-N, C-N ± 0.3% ± 0.3% ± 1 digit
6.5 lbs (shipping weight) Watts ± 0.6% ± 0.6% ± 1 digit
Vars ± 0.6% ± 0.6% ± 1 digit
Accuracy VA ± 0.6% ± 0.6% ± 1 digit
Maintained from 3% to 250% of CT Watt-hours ± 0.6% ± 0.6% ± 1 digit
primary rating Var-hours ± 0.6% ± 0.6% ± 1 digit
VA-hours ± 0.6% ± 0.6% ± 1 digit
UL/CUL/CSA Listed Power Factor ± 1% ± 1%
Frequency ± 0.1 Hz ± 0.1 Hz
CE mark % THD Through 31st Harmonic Through 31st Harmonic
EN61010-1 (1993), EN50082-2 (1994)
Note: All accuracy is measured as a percentage of full scale.

Ordering Information
IQ DP-4000
Description Catalog
Number

Separate source control power without I/O IQDP4010


Separate source control power without I/O, dc supply IQDP4020
Three-phase power supply without I/O IQDP4030
Separate source control power with three Form C relay output contacts and one sync pulse input IQDP4110
Separate source control power with three Form C relay output contacts and one sync pulse input, dc supply IQDP4120
Three-phase power supply with three Form C relay output contacts and one sync pulse input IQDP4130
4 indicates a DP-4000 model IQDP4xy0
x=0 indicates no I/O; x=1 indicates I/O
y=1 indicates separate source supply,
y=2 indicates 24-48 Vdc power supply,
y=3 indicates three-phase power supply
Copyright Cutler-Hammer Inc., 2000.
IQ Analyzer/IQ DP-4000 auxiliary power supply IQDPAUXPS
All Rights Reserved.

Cutler-Hammer
TD.17.03A.T.E
Printed in U.S.A. / Z00128