REPUBLIC OF THE PHILIPPINES

DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS


OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

GENERAL NOTES : FIRE PROTECTION : ABBREVATIONS: SYMBOLS: ASST. BUILDING OFFICIAL : DATE :

ITC - INSPECTOR TEST CONNECTION


1. USE NON-COMBUSTIBLE CEILING MATERIAL. - PENDENT SPRINKLER HEAD APPROVED:
1. ALL FIRE PROTECTION WORKS SHALL CONFORM WITH THE LATES
BUILDING OFFICIAL : DATE :
EDITION OF NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) CODES RN - RISER NIPPLE
2. MAXIMUM RADIUS ALLOWED PER SPRINKLER 1S 2.0 M. - UPRIGHT SPRINKLER HEAD
NO. 13, 14, 20 & 72. FHV - FIRE HOSE VALVE
3. FOR ADDITIONAL HEADS MAX. OF 5 HEADS ARE ALLOWED FOR - SIDEWALL SPRINKLER HEAD (EXTENDED)
2. READ THE DRAWING CONNECTION WITH OTHER RELATED DRAWINGS AFSR - AUTOMATIC FIRE SPRINKLER RISER
EVERY TAPPING TO THE EXISTING LOCATION OF SPRINKLER HEADS.
AND SPECIFICATIONS. THE ARCHITECT AND THE ENGINEER SHALL BE - SIDEWALL SPRINKLER HEAD (ORDINARY)
NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES FOUND THEREIN. 4. PROVIDE SPRINKLER HEAD GUARD AT STORAGE AREAS. DSPR - DRY STAND PIPE RISER FHC
- FIRE HOSE CABINET
3. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF 5. USED 215°F HEAD RATING FOR KITCHEN AREAS AND 165°F PG - PRESSURE GAUGE

SPRINKLER IN COORDINATION WITH THE ARCHITECTURAL CEILING HEAD FOR OTHER AREAS. - HANGER
PRV - PRESSURE RELIEF VALVE
LAYOUT. ANY RELOCATION SHALL BE SUBJECT TO ARCHITECTS AND
6. DO NOT REDUCE EXISTING NUMBER OF HEAD PROVISON AT SITE WFS - WATER FLOW SWITCH - 2-WAY BRACKET
ENGINEER'S APPROVAL.
PROVIDE 9mmØ ROUND BAR HANGER ACHORGE DIRECTLY TO EXISTING SLAB.
FCV - FLOOR CONTROL VALVE - 4-WAY BRACKET
4. ALL DRAIN PIPES FOR INSPECTORS TEST CONNECTION AND DRAIN
7. ALL SPRINKLER PIPES SHALL BE PAINTED WITH INTERNATIONAL RED
VALVES SHALL BE PIPED TO THE NEAREST FLOOR DRAIN / SLOPE SINK CV - CHECK VALVE - GATE VALVE
COORDINATE WITH ADMINISTRATION OFFICE FOR SPRINKLER INSTALLATION.
PROVIDED BY THE PLUMBING CONTRACTOR.
GV - GATE VALVE - GATE HOSE VALVE
5. PIPE SLEEVES SHALL BE PROVIDED FOR ALL PIPES PASSING THRU SLABS. 8. PROVIDE AT LEAST ONE (1) UNIT 5 KGS. ABC PROTABLE DRY

WALLS, GIRDER AND BEAMS. CHEMICAL FIRE EXTINGUISHERS FOR EVERY ROOM. SS - SUPERVISORY SWITCH - CHECK VALVE

6. MINIMUM PIPE SIZES FOR ALL SPRINKLER SHALL BE 25mm 9. UPRIGHT SPRINKLER HEADS TO BE USED AT OPEN CEILING AREAS ONLY. FP - FIRE PUMP
- ALARM CHECK VALVE
OTHERWISE NOTED.
JP - JOCKEY PUMP
- FLOW DETECTOR
7. ALL PIPE SIZES ARE IN MILLIMETER (mm) DIAMETER, UNLESS OTHERWISE
MM - MILLIMETER
NOTED. ALICIA
BANILAD
- FLUSHING CONNECTION
BAN

TOWN
TOWER CENTER
LAM

RESIDENCES

TYP - TYPICAL
TO TA

8. WORKMANSHIP : THE WORK THROUGHOUT SHALL BE EXECUTED IN THE - CONCENTRIC CONNECTION


BEST AND MOST THOROUGH MANNER KNOWN TO TRADE AND TO THE GPM - GALLONS PER MINUTE
.

- ECCENTRIC REDUCER
A V E

CEBU MEMORIAL PARK


SATISFACTION OF THE ARCHITECT AND THE ENGINEER. GAISANO
COUNTRY
PSI
N C O

MALL - POUNDS PER SQUARE INCH.


THIS SITE - 2-WAY FIRE DEPARTMENT CONNECTION
C U E

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING ALL UC BANILAD


CAMPUS
VECO
AD

HZ - HERTZ
M .

RO

GOVERNMENT / LOCAL CONSTRUCTION AND OPERATION PERMIT AND PAY


RA
V .

- 2-WAY ROOF MANIFOLD CONNECTION


CA
G O

ALL REQUIRED FEES. PRIS


SAN
ROA
D
V - VOLT
ROAD

- PORTABLE FIRE EXTINGUISHER


IF I C

LANGUAGE
AD
Y

SCHOOL
AC

10. REFER TO TECHNICAL SPECIFICATIONS FOR PUMP & MATERIAL


C I T

RO

ST. MI

FP 5KG CAP (DRY CHEM)


ST P

CHAE
L ROAD
- FIRE PROTECTION
D
LA

COA

SAPPHIRE
NI
U

BA

SPECIFICATIONS.
C E B

E M
D

E R
OL

A L
D

- FIRE EXTINGUISHER (WHEELED


T O

E T

TYPE )-25KG CAP (DRY CHEM)


R E

11. PIPE HANGERS & SWAY BRACES LOCATION SHALL BE AS PER NFPA MAIN HOTEL
S T

A N
& SUITES N
E X
D
D

N
PARA D I
3 R

O A M
DI SE VI
STANDARD AND LEAST ONE (1) HANGER BETWEEN HEAD.
M O N
LLAG A D
E RO
I

AD D

SCHEDULE OF EQUIPMENTS
VICINITY MAP CAPACITY HEAD POWER
ELECTRICAL
EQUIPTMENT REMARKS
(gpm) (psi) (hp)
VOLTS PHASE HERTZ
VERTICAL TURBINE PUMP WITH RATED
CAPACITY OF 400 GPM @ 100 PSI
FIRE PUMP 400 100 40 400 3 60 THE PUMP CUT - IN POINT SHOULD
BE 105 PSI LESS THAN JOCKEY PUMP
; CUT-OUT 105 PSI
VERTICAL TURBINE PUMP WITH RATED
CAPACITY OF 20 GPM AT 110 PSI
JOCKEY PUMP 20 110 3 400 3 60 THE PUMP CUT-IN 110 PSI AND
PUMP CUT-OFF IS 120 PSI

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 1
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A GENERAL NOTES AND SPECIFICATION NTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .
B LEGEND, ABBREVIATIONS, SYMBOLS NTS.

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C EQUIPMENT SCHEDULES NTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18 D VICINITY MAP NTS.
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 54 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

B
A B B' C C' D B B B' C C' D A B B' A-12 C C' D ASST. BUILDING OFFICIAL : DATE :
17.58 17.58 17.58
5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80
0.80 1.85 4.15 5.00 2.15 4.43 1.80 5.49 1.61 2.10 2.15 4.43 1.80 5.49 1.61 2.10
150Ø AFSS RISER 0.80 150Ø AFSS RISER 0.80 150Ø AFSS RISER APPROVED:
65ØFHV 65ØFHV 65ØFHV
100ØFCV 100ØFCV 100ØFCV
100ØWFS 100ØWFS 100ØWFS
BUILDING OFFICIAL : DATE :
4 4 4
F
50ØDL STACK 50ØDL STACK 50ØDL STACK
I R F I R F I
E W A L L 25ØDV 20 LBS HCFC AUTOMATIC E W A L L 25ØDV 20 LBS HCFC AUTOMATIC R E W A L L 25ØDV
5 5 5

2.00

2.00
SHO. FIRE SUPPRESSORS FIRE SUPPRESSORS

PIPECHASE

PIPECHASE
FIRE EXIT STAIR FIRE EXIT STAIR FIRE EXIT STAIR
CANOPY LINE ABOVE UP EE RM. UP EE RM. UP
2.88

2.88

2.88
T&B A = 11.73 SQM. 0.80 M. CANOPY LINE A = 11.73 SQM.
01 02 03 04 05 06 07 08
0.80 M. CANOPY LINE A
01 02 =0311.73 SQM.
01 02 03 04 05 06 4.09 SQM. 09 4.09 SQM. 04 05 06 07 08 09
07 08 09 10 10
W W

2.00

2.00

2.00
W W
KID'S POOL W D D 9 W W D 9 W W D 0.80 M. CANOPY LINE
2
20 19 18 17 16
15 14 13 12 11 GENSET 8
8 10 D
20 19 18 17 16
15 14 13 12 11 CONCRETE SLAB 8
8 10 D
17 16 15 14 13
12 11 10
5 1 10 DN 10
AREA 1 W 1 DN W
D
LOW WALL PARTITION 3
100Ø 8
W
9
100Ø 8
W
9
100Ø
5 5 5 5 5 5

2.05

2.05
01

DN FHC FHC
T&B T&B
38Ø 4.30 SQM. D 38Ø 4.30 SQM. D 38Ø
300 MM POOL CURB D 2 2
FHC 4 D T&B D T&B

4.82

4.82
2 3.87 SQM. 2 3.87 SQM.
25Ø 38Ø 25Ø 32Ø 25Ø W ACU W ACU
09 10 5 5

0.80 M. CANOPY LINE

0.80 M. CANOPY LINE


ACU W ACU W

0.80 M. CANOPY LINE


2.77

2.77
RN 50Ø BEDROOM 01 5 BEDROOM 01 5
RN 50Ø RN 50Ø

75Ø

75Ø
0.80 M. CANOPY LINE
W W BEDROOM 01
2 16.85 SQM. BEDROOM 02 BEDROOM 02 BEDROOM 01 2 16.85 SQM. BEDROOM 02 BEDROOM 02
11.72 SQM. 11.10 SQM. 12.10 SQM. 11.72 SQM. 11.10 SQM. 12.10 SQM.
W W
2 2
D D D D D D D D
7.90

7.90

7.90

7.90

7.90

7.90
TV TV TV TV
8 25Ø 25Ø
8 38Ø 8 25Ø 8 8 25Ø 25Ø
8 38Ø 8 25Ø 8

75Ø
08 11 TV TV W TV TV W

1.00 1.36

1.00 1.36
Y

Y
2 2
Y
W D D W D D
2
UNIT 03 7 7 PFE
UNIT 04 2
UNIT 03 7 7 PFE
UNIT 04
KITCHEN PFE KITCHEN PFE

A
24.46 SQM. KITCHEN KITCHEN
RN 50Ø 10LBS
22.16 SQM. 24.46 SQM.
10LBS
22.16 SQM.
DRYING
10LBS DRYING DRYING
10LBS DRYING

W
3.95

3.95
75Ø

75Ø
W AREA D D AREA W W AREA D D AREA W
25Ø 25Ø 32Ø 25Ø 5 2.00 SQM. 9 SCREEN
DOOR DINING LIVING LIVING
SCREEN
DOOR
9 2.00 SQM. 5 5 2.00 SQM. 9 SCREEN
DOOR DINING LIVING LIVING
SCREEN
DOOR
9 2.00 SQM.5

L
07 12 RN 50Ø DINING RN 50Ø DINING
D D D D

1.60

1.60
L

L
T&B 2 2 T&B T&B 2 2 T&B
3.36 SQM. 3.36 SQM. 3.36 SQM. 3.36 SQM.

A
WM REF REF WM WM REF REF WM
25Ø 38Ø 25Ø 38Ø
4 4 4 4 4 4

H
A

75Ø

WM REF WM REF

1.60

1.60
T&B T&B
3.36 SQM. D D T&B 3.36 SQM. D D T&B
3.36 SQM. 3.36 SQM.

.
2 2 2 2
06 13

3.95

3.95
75Ø M

75Ø M
DRYING SCREEN DINING LIVING DRYING SCREEN DINING LIVING

1.36 1.00

1.36 1.00
RN 50Ø W AREA D DOOR ACU W
W AREA D DOOR ACU W
5 5
5 2.00 SQM. 9 PFE 5 2.00 SQM. 9 PFE

0.80 M. CANOPY LINE


0.80 M. CANOPY LINE
25Ø 25Ø 32Ø 25Ø BEDROOM 01 BEDROOM 01
W

W W
10LBS
UNIT 02 BEDROOM 02 10LBS
UNIT 02 BEDROOM 02

0
11.69 SQM. 2 11.69 SQM. 2

25Ø

25Ø
KITCHEN 24.12 SQM. 10.46 SQM. KITCHEN 24.12 SQM. 10.46 SQM.
W D W D
RN 50Ø7 RN 50Ø7

0.80 M. CANOPY LINE

0.80 M. CANOPY LINE


2 2

5
D D D D
7.90

7.90

7.90

7.90

7.90

7.90
8 8 TV 8 8
PROPOSED05 UNDERGROUND 14
25Ø 25Ø 25Ø 25Ø

.
D D D D
FIRE RESERVE TANK 8 8 W TV
8 8 W

25Ø

25Ø
1

1
D 2 D 2
12,000 GALS (45 CU.M) 7 PFE 7 PFE
75Ø

UNIT 05 UNIT 05

2.53

2.53
W BEDROOM 02 KITCHEN W BEDROOM 02 KITCHEN
E

2 2
BEDROOM 01
13.97 SQM.
10.99 SQM. 22.16 SQM.
10LBS DRYING
BEDROOM 01
13.97 SQM.
10.99 SQM. 22.16 SQM.
10LBS DRYING

4.15

4.15
W D AREA W W D AREA W

75Ø

75Ø
ACU SCREEN 9 2.00 SQM. 5 ACU SCREEN 9 2.00 SQM.
5
5 DOOR 5 DOOR
LIVING LIVING
04 RN 50Ø 15 DINING DINING

T&B D T&B T&B D T&B


25Ø5.26
D D

1.63

1.63
2 3.36 SQM. 2 3.36 SQM.
3 25Ø 32Ø 25Ø 3
3.56 SQM. 2
3
3.56 SQM. 2
1.50
V
31.59

31.59

31.59

31.59

31.59

31.59
REF REF WM

3 150Ø 36.59
3 3 3 3 3

36.59

36.59
39.09

39.09

39.09
W W
MAIN STAIR 9 RN 50Ø 9 RN 50Ø
UP UP D T&B UP D T&B
RISER = 175 mm. (20 STEPS)
25Ø 25Ø 2 3.36 SQM. 25Ø 25Ø 2 3.36 SQM.

2.80

2.80
75Ø

10 09 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01
11 W AREA W AREA
16 4 4
12
13 14 15 16 17 18 19 20 09 10 11 12 13 14 15 16 17 61.45 SQM. W 09 10 11 12 13 14 15 16 17 61.45 SQM. W
UTILITY / ACU ACU
I

5 5
A

0.80 M. CANOPY LINE


JP

0.80 M. CANOPY LINE


PUMP ROOM DN DN

0.80 M. CANOPY LINE


FP

9.30 SQM. BEDROOM 01 BEDROOM 01


1.20

75Ø

75Ø
BEDROOM 02 11.69 SQM. W A-13 BEDROOM 02 11.69 SQM. W
RN 50Ø D 10.46 SQM. 2 D 10.46 SQM. 2
11 RN 50Ø D D 11 RN 50Ø D D
ELEVATOR
PIPECHASE

PIPECHASE
7.90

7.90

7.90

7.90

7.90

7.90
25Ø 25Ø 25Ø TV TV

PIPECHASE
8 8 8 8
LOBBY

2.25

2.25

2.53 SQM.
17 8 PERSON 8 PERSON
25Ø
ELEVATOR 50Ø 38Ø 25Ø 25Ø
ELEVATOR 50Ø 38Ø 25Ø
R

CAPACITY TV W CAPACITY TV W
D
LOBBY D 2 LOBBY D 2
6
7 PFE
UNIT 06 7 PFE
UNIT 06
22.16 SQM. KITCHEN 22.16 SQM. KITCHEN
W
10LBS W
10LBS

1.05

1.05
3 TV DRYING 3 TV DRYING

Y
100Ø REF REF
75Ø

W D AREA W W D AREAW
ACU ACU

A
5 SCREEN 9 2.00 SQM. 5 5 SCREEN 9 5
STUDIO TYPE PFE DOOR STUDIO TYPE PFE DOOR
2.00 SQM.

75Ø
LIVING

75Ø
NOOK NOOK LIVING
25Ø 18

L W
DINING

L W
DINING
03 15.41 SQM. 15.41 SQM.
10LBS 10LBS
D

1.60 T&B D KITCHEN D T&B T&B D KITCHEN D T&B

1.60
3.36 SQM. 2 2 3.36 SQM. 3.36 SQM. 2 2 3.36 SQM.

L
SOFA BED
RN 50ØD SOFA BED
RN 50ØD
RN 50Ø

A
7 REF WM 7 REF WM
25Ø 38Ø 25Ø 38Ø
2 2 2 2 2 2

H
CANOPY LN.
25Ø 25Ø 25Ø W REF WM
W REF WM

0.80 M.
.

.
9 W 9 W
3.45 T&B T&B
2.35

2.35
2 2

M
D 3.36 SQM. D 3.36 SQM.
25Ø 25Ø 32Ø 38Ø
2.73

KITCHEN KITCHEN
19 2 2

75Ø

75Ø
PFE PFE PFE PFE

5 0

5 0
DRYING LIVING DINING DRYING LIVING DINING
1.40 1.10 1.30 W
5
AREA D
SCREEN
LIVING
PFE
SCREEN
DOOR D DRYING W
W
5
AREA D
SCREEN
LIVING
PFE
SCREEN
DOOR D DRYING W
2.00 SQM. 9 9 AREA 5 2.00 SQM. 9 AREA5
10LBS 10LBS W W DOOR DINING
10LBS DOOR DINING
10LBS 9

.
CONCESSION CONCESSION
5 5 10LBS 2.00 SQM.
10LBS 2.00 SQM.

1
75Ø

D UNIT 01 50Ø UNIT 07 KITCHEN D UNIT 01 50Ø UNIT 07 KITCHEN


RN RN

CANOPY

CANOPY
1.60

1.60
25Ø

25Ø
0.80 M.

0.80 M.
SPACE 01 SPACE 02 T&B T&B

LINE

LINE
2 D D 22.16 SQM. W 2 D D 22.16 SQM. W
22.72 SQM. 22.72 SQM.
1.52

24.85 SQM. 22.14 SQM. SHE HE 3.36 SQM. 7 7 2 3.36 SQM. 7 7 2


W W
7.89

7.89

7.89

REF

7.89

7.89
REF

7.89
TOI. D D TOI. WM
25Ø TV
38Ø 38Ø TV
25Ø 9 WM
25Ø TV
38Ø 38Ø TV
25Ø 9
2 2 ITC ITC ITC
RN 25Ø D D D D D D D D
4.09 4.00 8 8 8 8 8 8 8 8
1.60

1.60
38Ø x 100MMLONG 38Ø x 100MMLONG
1.50

25Ø 25Ø 32Ø 38Ø 25Ø 25Ø 25Ø T&B D T&B T&B D T&B
GD
1
GD
1 3.36 SQM.
D
2
NIPPLE & CAPPED BEDROOM 02 BEDROOM 01 2 3.36 SQM. 3.36 SQM.
D
2
NIPPLEBEDROOM
BEDROOM 01 & CAPPED
02 BEDROOM 02 BEDROOM 01 2 3.36 SQM.
D D BEDROOM 01 BEDROOM 02 11.91 SQM. 11.91 SQM.
12.24 SQM. 16.24 SQM. 13.31 SQM. 12.24 SQM.
5 12 13.31 SQM.
16.24 SQM.
W ACU ACU W W ACU ACU W
5 5 5 5

CANOPY
H A L L W A Y ± .40 M. W

0.80 M.
2.35

2.35

LINE
2.15

6.36 SQM. SD 1 PWD. TV TV


38Ø x 100MM LONG
1 GUARD
4.00 SQM.
NIPPLE & CAPPED HOUSE TV
SD

0.80 M. CANOPY LINE


± .20 M. TV
2 R A I L I N G R A I L I N G

1 1 1 1 1 1
PARKING

M A I N G A T E GD GD
1.20

1.20

1.20
0.50 1.63

0.50 1.63
NO

2 2
ENTRY / EXIT 4-WAY FDC W W
7 7
L 4
I N- 65
E x 100Ø
3.00

3.00

3.00
P Y P L A N T E R S
C A N O
R . C . W W L I NE
3.70

LI N E R . C . C A N O PY
6 R . C. C A NO P Y 6
4.62

4.62

4.62
2.50

PWD
01 PARKING 6 6 6

= SIDE WALL SPRINKLER HEAD = 32 = SIDE WALL SPRINKLER HEAD = 32


1 1 1
2.24 5.00 = PENDENT SPRINKLER HEAD = 11 = PENDENT SPRINKLER HEAD = 11
2 = UPRIGHT SPRINKLER HEAD = 26 2 2
ITC ITC
± 0.00 M. = INSPECTOR TEST CONNECTION =1 = INSPECTOR TEST CONNECTION =1
3.91 4.00 3.80 1.20 1.60 2.20 = PENDENT SPRINKLER HEAD =4
ITC = HCFC AUTOMATIC FIRE SUPPRESSOR =1 = HCFC AUTOMATIC FIRE SUPPRESSOR =1
4.92 6.80 5.00 = INSPECTOR TEST CONNECTION =1 4.92 6.80 5.00 4.92 6.80 5.00
= FIRE HOSE CABINET =1 = FIRE HOSE CABINET =2 = FIRE HOSE CABINET =2
16.72 16.72 16.72
= 10LBS PORTABLE FIRE EXTINGUISHER =2 = 10LBS PORTABLE FIRE EXTINGUISHER =8 = 10LBS PORTABLE FIRE EXTINGUISHER =8

A B C D D A B C D A B C D
R O A
G Y .
6.00

S B R
T E R
M E
6

1 GF FLOOR FIRE PROTECTION PLAN 1 2ND FLOOR FIRE PROTECTION PLAN 1 3RD & 5TH FLOOR FIRE PROTECTION PLAN
M-03 SCALE 1:150 MTS. M-03 SCALE 1:150 MTS. M-03 SCALE 1:150 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 2
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A GROUND FLOOR FIRE PROTECTION PLAN 1:150 MTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .
B 2ND FLOOR FIRE PROTECTION PLAN 1:150 MTS.

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C 3RD & 5TH FLOOR FIRE PROTECTION PLAN 1:150 MTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 55 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

B B B
A B B' A-12 C C' D A B B' A-12 C C' D A B B' A-12 C C' D ASST. BUILDING OFFICIAL : DATE :
17.58 17.58 17.58
5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80 5.78 0.80 6.00 1.20 3.80
2.15 4.43 1.80 5.49 1.61 2.10 2.15 4.43 1.80 5.49 1.61 2.10
0.80 150Ø AFSS RISER 0.80 150Ø AFSS RISER APPROVED:
65ØFHV 65ØFHV
100ØFCV 100ØFCV
100ØWFS 100ØWFS
BUILDING OFFICIAL : DATE :
4 4 4 150Ø AFSS RISER
50ØDL STACK 50ØDL STACK
F I F I
20 LBS HCFC AUTOMATIC R E W A L L 25ØDV 20 LBS HCFC AUTOMATIC R E W A L L 25ØDV
5 5 5
2.00

2.00

2.00
FIRE SUPPRESSORS FIRE SUPPRESSORS

PIPECHASE

PIPECHASE
FIRE EXIT STAIR FIRE EXIT STAIR
EE RM. UP EE RM. UP
2.88

2.88

2.88
0.80 M. CANOPY LINE A 0.80 M. CANOPY LINE A
4.09 SQM. 01 02 =0311.73 SQM.
04 05 06 07 08 09 4.09 SQM. 01 02 =0311.73 SQM.
04 05 06 07 08 09
W W

2.00

2.00
W W

2.00
W W W W D C O N C R E T E S L A B
9 8 D 17 16 15 14 13 0.80 M. CANOPY LINE 9 8 10 D 17 16 15 14 13 12 0.80 M. CANOPY LINE
8 10 D 12 11 10 8 10 11 10
10 1
DN DN

0.87
1 W W
100Ø 8
W
9
100Ø 8
W
9 2 - 65x100
2.05

2.05
5 T&B
FHC 5 5 T&B
FHC 5 5 ROOF MANIFOLD 5
4.30 SQM. D 38Ø 4.30 SQM.
D PC
2
38Ø PC CONCRETE
2 SLAB
T&B D T&B
D CONCRETE
4.82

4.82
3.87 SQM. 2 3.87 SQM.
2 W SLAB
W ACU 5 ACU
5

0.80 M. CANOPY LINE


W
0.80 M. CANOPY LINE

ACU W ACU 5

0.80 M. CANOPY LINE


2.77

2.77
BEDROOM 01 5 W BEDROOM 01

0.80 M. CANOPY LINE


RN 50Ø RN 50Ø

75Ø

75Ø
W BEDROOM 01 BEDROOM 01
2 16.85 SQM. BEDROOM 02 BEDROOM 02 2 16.85 SQM. BEDROOM 02 BEDROOM 02
11.72 SQM. 11.10 SQM. 12.10 SQM. 11.72 SQM. 11.10 SQM. 12.10 SQM. W
W 2
2 D D D D
D D D D 8 8 8 8
7.90

7.90

7.90

7.90
TV TV TV TV

7.90

7.90
8 25Ø 25Ø
8 38Ø8 25Ø8 25Ø 25Ø 38Ø 25Ø
W
TV TV W TV TV 2
1.00 1.36

1.00 1.36
W D D

Y
W D D 2
2 7 7
2
UNIT 03 7 7 PFE
UNIT 04 UNIT 03 PFE
UNIT 04
KITCHEN PFE KITCHEN PFE
A

A
24.46 SQM. KITCHEN KITCHEN
22.16 SQM.
10LBS 24.46 SQM. 22.16 SQM.
10LBS
DRYING
10LBS DRYING W DRYING D 10LBS DRYINGW
W

W
3.95

3.95
D
D
75Ø

D AREA W

75Ø
W AREA 5 AREA 9 9 AREA 5
SCREEN SCREEN SCREEN SCREEN
5 2.00 SQM. 9 9 2.00 SQM.5 2.00 SQM. 2.00 SQM.
DOOR DINING LIVING LIVING DOOR DOOR DINING LIVING LIVING DOOR
L

L
RN 50Ø DINING
D RN 50Ø DINING
D
D D
1.60

1.60
2
L

L
T&B 2 2 T&B T&B 2 T&B
3.36 SQM. 3.36 SQM. 3.36 SQM. 3.36 SQM.
A

A
WM REF REF WM WM REF REF WM
25Ø 38Ø 25Ø 38Ø
4 4 4 4 4 CONCRETE CONCRETE
4

SLOPE
H

SLOPE
SLAB SLAB
WM REF WM PC
REF PC
1.60

1.60
T&B T&B D D
3.36 SQM. D D T&B 3.36 SQM. 2 2
T&B
3.36 SQM. 3.36 SQM.
.

.
2 2
3.95

3.95
75Ø M

75Ø M
SCREEN DINING LIVING SCREEN DINING LIVING W
W DRYING D
1.36 1.00

1.36 1.00
DRYING W
W AREA D DOOR ACU 9 DOOR ACU 5
5 5 AREA
5 2.00 SQM. 9 PFE PFE

0.80 M. CANOPY LINE


2.00 SQM.

0.80 M. CANOPY LINE


BEDROOM 01 BEDROOM 01 W
W
10LBS
UNIT 02 BEDROOM 02 10LBS
UNIT 02 BEDROOM 02 2
0

0
11.69 SQM. 2 11.69 SQM.
25Ø

25Ø
KITCHEN W KITCHEN D
W 24.12 SQM. D 10.46 SQM. 24.12 SQM. 10.46 SQM.
2 7 D D
RN 50Ø7 RN 50Ø

0.80 M. CANOPY LINE


0.80 M. CANOPY LINE

2 D D
5

5
8 8
8 8
7.90

7.90

7.90

7.90
TV TV

7.90

7.90
25Ø 25Ø 25Ø 25Ø
.

.
D D
D D 8 W
TV W TV 8 D
8 8 2
25Ø

25Ø
1

1
D 2 7
7 PFE
UNIT 05
W PFE
UNIT 05
2.53

2.53
W BEDROOM 02 KITCHEN 2 BEDROOM 02 KITCHEN
2 BEDROOM 01
13.97 SQM.
10.99 SQM. 22.16 SQM.
10LBS DRYING
BEDROOM 01
13.97 SQM.
10.99 SQM. 22.16 SQM.
10LBS D DRYINGW
W
4.15

4.15
W D AREA W 9 AREA 5
5
75Ø

75Ø
ACU SCREEN 9 2.00 SQM.5 ACU SCREEN
5 DOOR DOOR 2.00 SQM.
LIVING LIVING
DINING DINING
D D
T&B D D T&B T&B 2 T&B
2
1.63

1.63
3.56 SQM. 2 2 3.36 SQM. 3.56 SQM. 3.36 SQM. CONCRETE
3 1.50
3 1.50 3 SLAB
31.59

31.59

31.59

31.59

31.59

31.59
REF WM REF WM

3 3 3 3 3 PC CONCRETE
3
36.59

36.59

36.59
SLAB
PC PC PC
39.09

39.09
W W

39.09
PC
9 RN 50Ø 9 RN 50Ø D
D
UP D T&B UP T&B 1
25Ø 25Ø 25Ø 25Ø 2
2 3.36 SQM. W 3.36 SQM.
2.80

2.80
W 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01
AREA 4 08 07 06 05 04 03 02 01
4 AREA W
09 10 11 12 13 14 15 16 17 61.45 SQM. W 09 10 11 12 13 14 15 16 17 5
ACU 5 61.45 SQM. ACU 09 10 11 12 13 14 15 16 17

A A

0.80 M. CANOPY LINE


0.80 M. CANOPY LINE

0.80 M. CANOPY LINE

DN DN A

0.80 M. CANOPY LINE


DN
BEDROOM 01 BEDROOM 01
A-13 A-13
75Ø

75Ø
W
BEDROOM 02 11.69 SQM. W BEDROOM 02 2
A-13
2 D 11.69 SQM.
D 10.46 SQM. 11 10.46 SQM. D
11 RN 50Ø D D
RN 50Ø D D 11
8 8
7.90

7.90

7.90

7.90
TV TV

7.90

7.90
PIPECHASE

PIPECHASE
8 8

PIPECHASE
2.25

2.25
2.53 SQM.

2.53 SQM.

SLOPE
2.53 SQM.
8 PERSON 8 PERSON
CAPACITY 25Ø
ELEVATOR 50Ø 38Ø TV 25Ø W CAPACITY 25Ø
ELEVATOR 50Ø 38Ø
D
TV 25Ø W
2
LOBBY D 2 LOBBY 7
7 PFE
UNIT 06 PFE
UNIT 06
22.16 SQM. KITCHEN W 22.16 SQM. KITCHEN
W
10LBS 3 10LBS
1.05

1.05
3 TV TV
Y

Y
REF DRYING W REF D DRYING W
W 1.50 D AREA W 5 9 AREA5
ACU ACU
A

A
5 SCREEN 9 2.00 SQM. 5 SCREEN
STUDIO TYPE PFE LIVING DOOR STUDIO TYPE PFE LIVING DOOR
2.00 SQM.
75Ø

75Ø
NOOK NOOK
L W

DINING

L W
DINING
15.41 SQM. 15.41 SQM. WT WT
D D
T&B D 10LBS
KITCHEN D T&B T&B 10LBS
KITCHEN T&B
1.60

1.60
2 2 CONCRETE
3.36 SQM. 2 2 3.36 SQM. 3.36 SQM. 3.36 SQM.
L

L
SOFA BED
RN 50ØD SOFA BED
RN 50ØD7 SLAB
A

A
7 REF WM REF WM PC PC
25Ø 38Ø 25Ø 38Ø
2 2 2 2 2 CONCRETE
2
H

H
CANOPY LN.

CANOPY LN.
SLAB
REF WM PC PC PC
REF WM
0.80 M.

W W

0.80 M.
W
.

.
9 W T&B 9 2 T&B
D
2.35

2.35
2
M

M
D 3.36 SQM. 2 3.36 SQM.
KITCHEN 2 KITCHEN
75Ø

75Ø
DRYING
PFE W DRYING D
PFE
5 0

5 0
LIVING DINING SCREEN
LIVING DINING SCREEN W
W LIVING LIVING D
5
AREA D
2.00 SQM. 9
SCREEN PFE DOOR D DRYING W
9 AREA 5
5 AREA 9 SCREEN PFE DOOR 9
DRYING
AREA
5
DOOR DINING
10LBS 2.00 SQM. DOOR DINING
10LBS
.

.
10LBS 2.00 SQM.
D 10LBS 2.00 SQM.
1

1
UNIT 01 50Ø UNIT 07 UNIT 07
CANOPY

D KITCHEN UNIT 01 50Ø KITCHEN


RN RN

CANOPY
0.80 M.
1.60

1.60
25Ø

25Ø
2

0.80 M.
LINE

T&B 2 T&B D D W

LINE
22.72 SQM. D D 22.16 SQM. W 22.16 SQM.
22.72 SQM. 7 7 2
3.36 SQM. 7 7 2 3.36 SQM.
W W CONCRETE

SLOPE
SLOPE
7.89

REF
7.89

7.89

REF

7.89
WM
25Ø TV
38Ø TV
25Ø 9 WM
25Ø TV
38Ø TV
25Ø 9

7.89

7.89
38Ø D
38Ø
D
SLAB
D D
ITC D D ITC
D D 8 8 8 8
8 8 8 8
1.60

1.60

38Ø x 100MMLONG D 38Ø x 100MMLONG D


T&B NIPPLEBEDROOM
& CAPPED D T&B T&B T&B
BEDROOM NIPPLE & CAPPED
D BEDROOM 02 BEDROOM 01 2 BEDROOM 02 BEDROOM 01 2 CONCRETE
3.36 SQM. 2 BEDROOM 01 02 11.91 SQM.
2 3.36 SQM. 3.36 SQM. 01 BEDROOM 02 11.91 SQM.
3.36 SQM. SLAB
13.31 SQM. 12.24 SQM. 13.31 SQM. 12.24 SQM.
16.24 SQM. 16.24 SQM.
W W
W ACU ACU W 5 ACU ACU 5
5 5
CANOPY

CANOPY
0.80 M.

0.80 M.
2.35

2.35
LINE

LINE
TV TV

TV TV
0.80 M. CANOPY LINE
0.80 M. CANOPY LINE

PC PC
R A I L I N G R A I L I N G

1 1 1 1 1 1

0.50
GD GD
1.20

1.20
0.50 1.63

0.50 1.63

2 2 W
W 7
7 CONCRETE

2.82
SLAB
3.00

3.00

3.00
W

2.50
W L I N E L I N E
R . C . C A N O P Y 6 R . C . C A N O P Y
6
4.62

4.62

4.62
6 6 6

= SIDE WALL SPRINKLER HEAD = 32 = SIDE WALL SPRINKLER HEAD = 32

1.80
1 1 1
= PENDENT SPRINKLER HEAD = 11 = PENDENT SPRINKLER HEAD = 11
2 ITC 2 ITC 2
= INSPECTOR TEST CONNECTION =1 = INSPECTOR TEST CONNECTION =1

4.92 6.80 5.00


= HCFC AUTOMATIC FIRE SUPPRESSOR =1
4.92 6.80 5.00
= HCFC AUTOMATIC FIRE SUPPRESSOR =1 4.92 6.80 5.00
= FIRE HOSE CABINET =2 = FIRE HOSE CABINET =2 16.72
16.72 16.72
= 10LBS PORTABLE FIRE EXTINGUISHER =8 = 10LBS PORTABLE FIRE EXTINGUISHER =8

A B C D A B C D A B C D

1 4TH FLOOR FIRE PROTECTION PLAN 1 6TH FLOOR FIRE PROTECTION PLAN 1 ROOF DECK FIRE PROTECTION PLAN
M-03 SCALE 1:150 MTS. M-03 SCALE 1:150 MTS. M-03 SCALE 1:150 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 3
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A 4TH FLOOR FIRE PROTECTION PLAN 1:150 MTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .
B 6TH FLOOR FIRE PROTECTION PLAN 1:150 MTS.

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C ROOF DECK FIRE PROTECTION PLAN 1:150 MTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 56 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:
UPPER ROOF

ASST. BUILDING OFFICIAL : DATE :

ROOF MANIFOLD
100mmØx65mmØx65mmØ APPROVED:

BUILDING OFFICIAL : DATE :

ROOF DECK

TO FACP (BY ELECTRICAL CONTRACTOR)

FCV WFS 75mmØ CROSSMAIN


150mmØ COMBINATION WET
STANDPIPE RISER SG GV

ITC 25mmØ
GV
25mmØ DRAIN

FIRE HOSE VALVE FHC


6TH. FLR. LINE 65mmØ

TO FACP (BY ELECTRICAL CONTRACTOR) FP-C JP-C


FCV
WFS 75mmØ CROSSMAIN
150mmØ COMBINATION WET
STANDPIPE RISER SG GV

ITC 25mmØ
GV PRV-25Ø 150Ø
25mmØ DRAIN

GV CV JP
FIRE HOSE VALVE FHC 150Ø
5TH. FLR. LINE 65mmØ

FMD
150Ø FIRE RESERVE TANK

50Ø
TO FACP (BY ELECTRICAL CONTRACTOR)

FCV WFS 75mmØ CROSSMAIN


PRV-100Ø
12,000 GALS.
150mmØ COMBINATION WET
STANDPIPE RISER
GV (45 CU.M.)
SG GV

ITC 25mmØ 150Ø


GV
25mmØ DRAIN GV CV 150Ø
ACV CV FP
FIRE HOSE VALVE FHC 100Ø
4TH. FLR. LINE 65mmØ

TO FACP (BY ELECTRICAL CONTRACTOR)

150mmØ COMBINATION WET


FCV
WFS 75mmØ CROSSMAIN
150Ø 4 WAY-FDC
STANDPIPE RISER SG GV
4X65Ø X 100Ø 2 PUMP DETAIL
GV
ITC 25mmØ
TO SYSTEM FP 1 SCALE N.T.S.

25mmØ DRAIN

FIRE HOSE VALVE FHC


3RD. FLR. LINE 65mmØ

TO FACP (BY ELECTRICAL CONTRACTOR)

FCV WFS 75mmØ CROSSMAIN


150mmØ COMBINATION WET
STANDPIPE RISER SG GV

ITC 25mmØ
GV
25mmØ DRAIN

FIRE HOSE VALVE FHC


2ND. FLR. LINE 65mmØ

100mmØ
TO FACP (BY ELECTRICAL CONTRACTOR)

FCV WFS 75mmØ CROSSMAIN


150mmØ COMBINATION WET
STANDPIPE RISER SG GV FIRE DEPARTMENT
CONNECTION 4-WAY
ITC 25mmØ 4x65mmx100mm
GV
25mmØ DRAIN

50mmØ DRAIN RISER PIPE


FHC
ACV
GND. FLR. LINE
TO NEAREST TO NEAREST
DRAIN STUB OUT TO FIRE PUMP DRAIN STUB OUT

1 SPRINKLER SYSTEM RISER DIAGRAM


FP 7 SCALE N.T.S.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 4
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A SPRINKLER SYSTEM RISER DIAGRAMS NTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .
B PUMP DETAILS NTS.

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 57 64
FLOW METER PRESSURE SWITCH FIRE PUMP EQUIPMENT FIRE DEPARTMENT
SIDEWALL SPRINKLER HEAD DETAIL 2 (ANNUBAR TYPE) DETAIL 3 PIPING CONNECTION 4 ARRANGEMENT DETAIL 5 CONNECTION DETAIL
FP-DT-01-06

SUPERVISORY SWICTH PUMP ROOM DETAIL OF SUPERVISORY FLOOR


DETAIL OF SPRINKLER HEADS 7 CONNECTION DETAIL 8 PIPE SUPPORT 9 ALARM CHECK VALVE DETAIL 10 CONTROL VALVE ASSEMBLY
FP-DT-01-06
NTS FP-DT-01-06 FP-DT-01-06 FP-DT-01-06

SCHEDULE OF PIPE SLEEVES


SIZE OF SIZE OF
BRANCHLINES PIPE SLEEVES
25MMØ 50MMØ
32MMØ 50MMØ
40MMØ 65MMØ
50MMØ 75MMØ
65MMØ 100MMØ
75MMØ 100MMØ
100MMØ 150MMØ
150MMØ 225MMØ
200MMØ 300MMØ

FIRE EXTINGUISHER
11 ACCEPTABLE TYPES OF HANGERS 12 ALARM MOTOR GONG DETAIL 13 MOUNTING DETAIL 14 PIPE SLEEVE DETAIL 15 DETAIL OF INSPECTOR TEST CONNECTION

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 5
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A MISCELLANEOUS DETAILS NTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 58 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

ASST. BUILDING OFFICIAL : DATE :

APPROVED:

BUILDING OFFICIAL : DATE :

SPRINKLER HEAD @ TYPICAL INSTALLATION OF


1 GARBAGE CHUTE DETAIL 2 FLOW SWITCH DETAIL SPOT DETAIL PENDENT SPRINKLER HEAD
NTS

STANDPIPE FIRE HOSE VALVE DETAIL ACCEPTABLE TYPES TYPICAL CUT-OFF


DETAIL OF ROOF MANIFOLD 7
5 NTS
SWAY BRACE DETAIL OF SWAY BRACING 10 SPRINKLER DETAIL
6

ADJUSTABLE CLEVIS
11 FIRE HOSE CABINET WITH FIRE EXTINGUISHER FLUSHING CONNECTION DETAIL PIPE HANGER DETAIL PIPE RISER BRACKET DETAIL

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

FP 6
THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE
ENGR. DIOSDADO N. EJERCITO, JR. CHECKED BY: . A MISCELLANEOUS DETAILS NTS.
PROFFESSIONAL MECHANICAL ENGINEER
PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO DATE: .

W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg


S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 59 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

GENERAL SPECIFICATIONS ALICIA


BANILAD
RECOMMENDING APPROVAL:

BAN
TOWN
TOWER CENTER

LAM
RESIDENCES

TO TA
ASST. BUILDING OFFICIAL : DATE :

.
APPROVED:

A V E
CEBU MEMORIAL PARK
GAISANO BUILDING OFFICIAL : DATE :
COUNTRY

N C O
MALL
THIS SITE

C U E
UC BANILAD
VECO
CAMPUS

AD
M .

RO
RA
V .

CA
G O
PRIS

D
SAN

RO A
ROA
D

I F IC
LANGUAGE

AD
Y
SCHOOL

C
S T PA
C I T

RO
ST. M
ICHA
EL RO
AD

AD

CO A

SAPPHIRE
IL
U

N
BA
C E B
E M

LD
E R
A L

O
D

T O

E T
R E
MAIN HOTEL

S T
A N
& SUITES N
E X
D

D
N
PARA D I

3 R
O A M
DISE M
VILLAG A O N
E RO D

I
AD D

VICINITY MAP

SINGLE-SPLIT TYPE DX SYSTEM AC UNITS


FAN COIL UNIT (FCU) CONDENSING UNIT
REFRIGERANT ELECTRICAL REFRIGERANT
ELECTRICAL CHARACTERISTICS UNIT SELECTED UNIT
SELECTED UNIT PIPE SIZE, FLARE CHARACTERISTICS PIPE SIZE, FLARE UNIT REMARKS
QTY COOLING DIMENSION WEIGHT (MM) COOLING (MM) DIMENSION WEIGHT REF.
DESIGNATION (TOTAL) TYPE HxWxD DESIGNATION QTY LOCATION CAPACITY Wx H x D
CAPACITY INPUT (KG) MOTOR SIZE (KG) USED
(W) V/Ø/HZ (MM) (HP) (KW) V Ø HZ (MM)
(HP) GL LL GL LL

FCU-1 35 1.0HP WALL MOUNTED 28 220 1 35 1.0HP 1. EACH UNIT SHALL BE FACTORY TESTED
60 280x770x223 8 9.5 6.4 ACCU 1 SEE PLANS 0.680 220 1 60 9.5 6.4 550x658x275 23 R-32
ANDASSEMBLED TO MEET THE DESIGN
REQUIREMENTAND SHALL BE COMPLETE W/
FCU-2 2 2.0HP WALL MOUNTED 33 220 1 60 295x990x263 13 12.7 6.4 ACCU 2 2 SEE PLANS 2.0HP 1.365 220 1 60 12.7 6.4 595x845x300 36 R-32 DECORATIVEPANELS, WASHABLE TYPE AIR
FILTERS ANDWIRED REMOTE CONTROLLERS,
FAN SPEED CONTROL AND WIDE RANGE OF
TEMPERATURE SETTINGS
2. USE BRAND: DAIKIN OR APPROVED EQUAL.
3. MECHANICAL CONTRACTOR SHALL
COORDINATE WITH AC SUPPLIER FOR
REFRIGERANT PIPE SIZING BASED ONACTUAL
PIPING LENGTH AT SITE.
4. INSTALLER: SHALL BE A CERTIFIED
INSTALLEROF THE USED BRAND.

EXHAUST AIR BLOWERS


LEGEND & SYMBOLS UNIT
DESIGNATION
QTY. AREA SERVED
CAPACITY
(CFM)
TYPE
EXTERNAL
S.P.
(in.)
MOTOR SIZE
(W)
V
ELECTRICAL
CHARACTERISTICS

PH HZ
MOTOR
CONTROLLER
REMARKS

TEF-1 78 SEE PLANS 50 CEILING CASSETTE FAN 0.125 11 220 1 60 INTERLOCK TO SWITCH SIMILAR TO KRUGER, NIAGARA

TEF-2 2 SEE PLANS 150 CEILING CASSETTE FAN 0.125 19 220 1 60 INTERLOCK TO SWITCH SIMILAR TO KRUGER, NIAGARA

RH-1 35 SEE PLANS 250 CEILING CASSETTE W/ RANGE HOOD 0.125 28 220 1 60 WYE DELTA SIMILAR TO KRUGER, NIAGARA

PRESSURIZATION AIR BLOWER


ELECTRICAL
EXTERNAL CHARACTERISTICS
UNIT CAPACITY MOTOR SIZE MOTOR
QTY. AREA SERVED TYPE S.P. REMARKS
DESIGNATION (CFM) (KW) CONTROLLER
(Pa) V PH HZ

PB-1 1 ROOF DECK SLAB 6,000 SISW CENTRIFUGAL FAN 300 10.2 220 3 60 VSD SIMILAR TO KRUGER, NIAGARA

WINDOW TYPE AIR CONDITIONING UNITS EQUIPMENT SCHEDULE


CAPACITY
ITEM NO. QTY HP VOLTAGE WATTS REMARKS
BTU/HR
WAC-1 40 1.0 16,000 230/1/60 945 HITACHI OR APPROVED EQUAL

D.L

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A

B
GENERAL NOTES AND SPECIFICATION

LEGEND
NTS.

NTS.
M 1
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 48 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

B
A B B' C C' D B B B' C C' D A B B' A-12 C C' D ASST. BUILDING OFFICIAL : DATE :
17.58 17.58 17.58
5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80
0.80 1.85 4.15 5.00 2.15 4.43 1.80 5.49 1.61 2.10 2.15 4.43 1.80 5.49 1.61 2.10
0.80 0.80 APPROVED:

150Ø SMOKE STACK WITH FIBER 150Ø SMOKE STACK WITH FIBER
TEF-2 BUILDING OFFICIAL : DATE :
4 GLASS INSULATION & G.A 24 ALUMINUM 4 GLASS INSULATION & G.A 24 ALUMINUM 4
50 CFM
F I R E W A L L CLADDING (UP TO 3RD FLOOR SLAB) F I R E W A L L
CLADDING (UP TO 3RD FLOOR SLAB) F I R E W A L L
5 5 5

2.00

2.00
SHO. ACCU-1 ACCU-1

PIPECHASE

PIPECHASE
FIRE EXIT STAIR FIRE EXIT STAIR FIRE EXIT STAIR

100Ø
CANOPY LINE ABOVE UP EE RM. UP ACCU-1 EE RM. UP ACCU-1
2.88

2.88

2.88
T&B A = 11.73 SQM. 0.80 M. CANOPY LINE A = 11.73 SQM. 0.80 M. CANOPY LINE A
01 02 =0311.73
01 02 03 04 05 06
07 08 09 1.0HP 4.09 SQM. 01 02 03 04 05 06 07 08 09 10 1.0HP 4.09 SQM.
SQM.
04 05 06 07 08 09
10 W 1.0HP W 1.0HP

2.00

2.00

2.00
W W
KID'S POOL W D D 9 W W D 9 W W D 0.80 M. CANOPY LINE
2
20 19 18 17 16
15 14 13 12 11 GENSET 8
8 10 D
20 19 18 17 16
15 14 13 12 11 CONCRETE SLAB 8
8 10 D
17 16 15 14 13
12 11 10
5 1 10 DN 10
AREA 1 W 1 DN W
D W W
LOW WALL PARTITION 3 TEF-2 8 9 TEF-2 8 9

5 5 5 5 5 5

2.05

2.05
01

DN 150 CFM 150 CFM


T&B TEF-2 T&B TEF-2
GENSET
300 MM EXHAUST
POOL CURB DUCT D
4.30 SQM. D
2 150 CFM
4.30 SQM. D
2 150 CFM
4 T&B T&B
WITH VERTICAL EXHAUST LOUVER D D

4.82

4.82
2 3.87 SQM. 2 3.87 SQM.
W ACU WAC-1 W ACU WAC-1
09 (BELOW STAIR LANDING) 10 5
WAC-1 5
WAC-1

0.80 M. CANOPY LINE

0.80 M. CANOPY LINE


1.0HP FCU-1 FCU-1 ACU W 1.0HP FCU-1 FCU-1 ACU W

0.80 M. CANOPY LINE


2.77

2.77
BEDROOM 01 1.0HP 5 BEDROOM 01
BEDROOM 02
1.0HP 5

0.80 M. CANOPY LINE


W BEDROOM 02 W
1.0HP BEDROOM 01
2 16.85 SQM. 1.0HP
11.72 SQM.
1.0HP 02
BEDROOM BEDROOM 01 2 16.85 SQM.
11.72 SQM. 1.0HP02
BEDROOM
12.10 SQM.
11.10 SQM. 12.10 SQM. 11.10 SQM.
W W
2 2
D D D D D D D D
7.90

7.90

7.90

7.90

7.90

7.90
TV TV TV TV
8 8 8 8 8 8 8 8
08 11 TV TV W TV TV W

1.00 1.36

1.00 1.36
Y

Y
2 2
Y
W D D W D D
2 7 7 2 7 7
KITCHEN UNIT 03 UNIT 04 KITCHEN UNIT 03 UNIT 04

A
24.46 SQM. 22.16 SQM. KITCHEN 24.46 SQM. 22.16 SQM. KITCHEN

DRYING RH-1 RH-1 DRYING DRYING RH-1 RH-1 DRYING

W
3.95

3.95
W AREA D D AREA W W AREA D D AREA W
5 2.00 SQM. 9 SCREEN
380 CFM 380 CFM SCREEN
9 2.00 SQM. 5 5 2.00 SQM. 9 SCREEN
380 CFM 380 CFM SCREEN
9 2.00 SQM.5

100Ø

100Ø

100Ø

100Ø
DOOR DINING LIVING LIVING DOOR DOOR DINING LIVING LIVING DOOR

L
DINING DINING
07 12
D D D D

1.60

1.60
L

L
T&B 2 2 T&B T&B 2 2 T&B
3.36 SQM. TEF-1 TEF-2 3.36 SQM. 3.36 SQM. TEF-1 TEF-2 3.36 SQM.

A
WM REF
50 CFM REF
150 CFM WM WM REF
50 CFM REF
150 CFM WM

4 4 4 4 4 4

H
A

WM REFTEF-1 TEF-2 WM TEF-1


REF TEF-2

1.60

1.60
T&B 50 CFM 150 DCFM T&B 50 CFM 150 DCFM
T&B T&B

100Ø

100Ø
3.36 SQM. D 3.36 SQM. D
3.36 SQM. 3.36 SQM.

.
2 2 2 2

100Ø

100Ø
06 13

3.95

3.95
M

M
DRYING SCREEN DINING LIVING DRYING SCREEN DINING LIVING

1.36 1.00

1.36 1.00
W AREA D DOOR WAC-1 ACU W
W AREA D DOOR WAC-1 ACU W
5 2.00 SQM. 9 RH-1 5
5 2.00 SQM. 9 RH-1 FCU-1 5

0.80 M. CANOPY LINE


FCU-1 1.0HP 1.0HP
1.0HP

0.80 M. CANOPY LINE


380 CFM BEDROOM 01 380 CFM BEDROOM 01
W

W W
UNIT 02 1.0HP02
BEDROOM UNIT 02 BEDROOM 02

0
11.69 SQM. 2 11.69 SQM. 2
KITCHEN 24.12 SQM. 10.46 SQM. KITCHEN 24.12 SQM. 10.46 SQM.
W D W D

0.80 M. CANOPY LINE

0.80 M. CANOPY LINE


2 7 2 7

5
D D D D
7.90

7.90

7.90

7.90

7.90

7.90
8 8 TV 8 8
ACCU-1 ACCU-1
05 14 ACCU-1 ACCU-1

.
1.0HP D
8
D
8 W 1.0HP 1.0HP TV D
8
D
8 W 1.0HP

1
D 2 D 2
7 7
UNIT 05 UNIT 05

2.53

2.53
W BEDROOM 02 KITCHEN W KITCHEN
BEDROOM 02
E

2 22.16 SQM. 2 22.16 SQM.


BEDROOM 01 FCU-1
10.99 SQM. BEDROOM 01 10.99 SQM.
FCU-1
13.97 SQM. RH-1 DRYING 13.97 SQM. RH-1 DRYING
1.0HP

4.15

4.15
W
ACU 380 CFM SCREEN
D AREA W
9 2.00 SQM. 5
W
ACU
1.0HP 380 CFM SCREEN
D AREA W
9 2.00 SQM.
5

100Ø

100Ø
5 DOOR 5 DOOR
LIVING LIVING
04 15 TEF-2 WAC-1 DINING TEF-2 WAC-1 DINING

T&B
150 CFM D T&B T&B
150 CFM D T&B
5.26 D
1.0HP D
1.0HP

1.63

1.63
3.56 SQM. 2 3.36 SQM. 3.56 SQM. 2 3.36 SQM.
3 3
2 TEF-2 3
2 TEF-2
1.50
V
31.59

31.59

31.59

31.59

31.59

31.59
150 CFM
REF 150 CFM
REF WM

3 3 3 3 3 3
36.59

36.59

36.59
TEF-2 TEF-2
39.09

39.09

39.09
W W
MAIN STAIR 9 150DCFM T&B
9 150DCFM T&B

100Ø

100Ø
RISER = 175 mm. (20 STEPS) UP UP UP
2 3.36 SQM. 2 3.36 SQM.

2.80

2.80
10 09 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01
11 W AREA W AREA
16 4 4
12
13 14 15 16 17 18 19 20 09 10 11 12 13 14 15 16 17 61.45 SQM. WAC-1 W 09 10 11 12 13 14 15 16 17 61.45 SQM. WAC-1 W
UTILITY / ACU ACU
I

5 5
FCU-1 1.0HP A FCU-1 1.0HP

0.80 M. CANOPY LINE

0.80 M. CANOPY LINE


PUMP ROOM DN DN

0.80 M. CANOPY LINE


1.0HP BEDROOM 01 BEDROOM 01
9.30 SQM.
1.20 BEDROOM 02 11.69 SQM. W A-13 1.0HP02
BEDROOM 11.69 SQM. W
D 10.46 SQM. 2 D 10.46 SQM. 2
11 D D 11 D D
ELEVATOR
PIPECHASE

PIPECHASE
7.90

7.90

7.90

7.90

7.90

7.90
TV TV

PIPECHASE
8 8 8 8
LOBBY

2.25

2.25

2.53 SQM.
17 8 PERSON ACCU-1 8 PERSON ACCU-1
ELEVATOR RANGE HOOD WITH AIR RECYCLING ELEVATOR RANGE HOOD WITH TV AIR RECYCLING
R

CAPACITY TV W 1.0HP CAPACITY W 1.0HP


D
LOBBY ACTIVATEDD CARBON FILTER 2 LOBBY ACTIVATEDD CARBON FILTER 2
(TYPICAL TO ALL)UNIT 06 (TYPICAL TO ALL)UNIT 06
7 7
6
22.16 SQM. KITCHEN 22.16 SQM. KITCHEN
100Ø WALL CAP W 100Ø WALL CAP W

1.05

1.05
3 TV DRYING 3 TV DRYING

Y
REF REF
ACCU-2 ACCU-2 (TYPICAL TO ALL) W
RH-1 D AREA W (TYPICAL TO ALL) W
RH-1 D AREAW
ACU ACU

A
5 SCREEN 9 2.00 SQM. 5 5 SCREEN 9 5
2.00 SQM.

100Ø

100Ø
STUDIO TYPE DOOR STUDIO TYPE DOOR
2.0HP 2.0HP 18
NOOK380 CFM LIVING NOOK380 CFM LIVING

W
DINING

W
DINING
03 15.41 SQM. 15.41 SQM.
D

T&B D WAC-1 KITCHEN D T&B D WAC-1 KITCHEN D

L
T&B T&B

1.60

1.60
3.36 SQM. 2 2 3.36 SQM. 3.36 SQM. 2 2 3.36 SQM.

L
1.0HPSOFA BED D TEF-2 1.0HPSOFA BED D TEF-2

A
7 REF 7 REF
150 CFM WM
150 CFM WM

2 2 2 2 2 2

H
TEF-2 TEF-2

CANOPY LN.
WM WM
W TEF-2
REF W TEF-2
REF

0.80 M.
150 CFM 150 CFM

.
9 W 9 W
3.45 100Ø WALL CAP
150 CFM
T&B
150 CFM
T&B
2.35

2.35
2 2

100Ø

100Ø
M

M
(TYPICAL TO ALL) D 3.36 SQM. D 3.36 SQM.
2.73

KITCHEN KITCHEN
FCU-2 FCU-2 19 2 2

RH-1 RH-1

0
DRYING LIVING DINING DRYING LIVING DINING
2.0HP 2.0HP 1.40 1.10 1.30 W AREA D LIVING SCREEN
DOOR D DRYING W
W AREA D LIVING SCREEN
DOOR D DRYING W

5
5 SCREEN 5 SCREEN
2.00 SQM. 9 380 CFMDINING 9 AREA 5 2.00 SQM. 9 380 CFMDINING AREA5

100Ø

100Ø
W W DOOR DOOR 9

.
2.00 SQM. 2.00 SQM.
5 5
CONCESSION CONCESSION

1
D UNIT 01 UNIT 07 KITCHEN D UNIT 01 UNIT 07 KITCHEN

CANOPY

CANOPY
1.60

1.60
0.80 M.

0.80 M.
SPACE 01 SPACE 02 T&B T&B

LINE

LINE
2 D D 22.16 SQM. W 2 D D 22.16 SQM. W
TEF-2 22.72 SQM. RH-1 TEF-2 22.72 SQM. RH-1
1.52

24.85 SQM. 22.14 SQM. SHE HE 3.36 SQM. 7 7 2 3.36 SQM. 7 7 2


W W
150 CFM 380 CFM 150 CFM 380 CFM
7.89

7.89

7.89

REF

7.89

7.89
REF

7.89
TOI. D D TOI. WM TV TV 9 WM TV TV 9
TEF-1 2 2 TEF-1
D D D D D D D D
4.09 4.00 50 CFM
TEF-2 8 8 TEF-2 TEF-2 8 8 TEF-2
50 CFM 8 8 8 8
1.60

1.60
T & B 150 DCFM T & B 150 DCFM
1.50

T & B150 CFM T & B150 CFM


100Ø

100Ø
GD GD D D
BEDROOM 02 BEDROOM 01 2 3.36 SQM. BEDROOM 01 BEDROOM 02 BEDROOM 01 2 3.36 SQM.
1 1 D D
3.36 SQM. 2
BEDROOM 01 FCU-1 02
BEDROOM 11.91 SQM.
3.36 SQM. 2 FCU-1 FCU-1
5 12 FCU-1 12.24 SQM. 16.24 SQM. BEDROOM 02 11.91 SQM. 12.24 SQM.

W
16.24 SQM. 1.0HP
13.31 SQM.
1.0HP W W 1.0HP
13.31 SQM.
1.0HP W
ACU ACU ACU ACU
5 5 5 5
TEF-1

CANOPY
H A L L W A Y ± .40 M. W

0.80 M.
2.35

2.35

LINE
2.15

SD 1 TV TV
6.36 SQM. GUARD50 CFM PWD.
1
HOUSE 4.00 SQM. WAC-1 WAC-1
WAC-1 TVWAC-1
SD
1.0HP 1.0HP

0.80 M. CANOPY LINE


± .20 M. TV
2
1.0HP R A I L I N G 1.0HP R A I L I N G

1 1 1 ACCU-1 ACCU-1 1 1 ACCU-1 ACCU-1 1


PARKING

M A I N G A T E GD GD
1.20

1.20

1.20
1.0HP 1.0HP 1.0HP 1.0HP
0.50 1.63

0.50 1.63
NO

2 2
ENTRY / EXIT W W
7 7
L I N E
3.00

3.00

3.00
P Y P L A N T E R S
C A N O
R . C . W W L IN E
3.70

LI N E R . C . C A N OP Y
6 R .C . C AN O P Y 6
4.62

4.62

4.62
2.50

PWD
01 PARKING 6 6 6

1 1 1
2.24 5.00 NOTE: NOTE: NOTE:
2 2 2
± 0.00 M. LOCATE CONDENSATE DRAIN LINE TO ITS LOCATE CONDENSATE DRAIN LINE TO ITS LOCATE CONDENSATE DRAIN LINE TO ITS
3.91 4.00 3.80 1.20 1.60
NEAREST PLUMBING 2.20
DRAIN COLLECTOR NEAREST PLUMBING DRAIN COLLECTOR NEAREST PLUMBING DRAIN COLLECTOR
4.92 6.80 5.00 4.92 6.80 5.00 4.92 6.80 5.00
16.72 16.72 16.72

A B C DA D A B C D A B C D
R O
G Y .
6.00

S B R
T E R
M E
6

A GF FLOOR AIR CONDITIONING & VENTILATION PLAN B 2ND FLOOR AIR CONDITIONING & VENTILATION PLAN C 3RD & 5TH FLOOR AIR CONDITIONING & VENTILATION PLAN
SCALE 1:150 MTS. SCALE 1:150 MTS. SCALE 1:150 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A

B
GROUND FLOOR AIR CONDITONING & VENTILATION PLAN

2ND FLOOR AIR CONDITONING & VENTILATION PLAN


1:150 MTS.

1:150 MTS.
M 2
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C 3RD & 5TH FLOOR AIR CONDITONING & VENTILATION PLAN 1:150 MTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 49 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
OFFICE OF THE BUILDING OFFICIAL
CEBU CITY

RECOMMENDING APPROVAL:

B B B
A B B' A-12 C C' D A B B' A-12 C C' D A B B' A-12 C C' D ASST. BUILDING OFFICIAL : DATE :
17.58 17.58 17.58
5.78 6.00 1.20 3.80 5.78 6.00 1.20 3.80 5.78 0.80 6.00 1.20 3.80
2.15 4.43 1.80 5.49 1.61 2.10 2.15 4.43 1.80 5.49 1.61 2.10
0.80 0.80 APPROVED:

BUILDING OFFICIAL : DATE :


4 4 750 x 400 SAR 4
F I R E W F I R E W
A L L A L L
5 5 5
2.00

2.00

2.00
ACCU-1 ACCU-1

PIPECHASE

PIPECHASE
FIRE EXIT STAIR FIRE EXIT STAIR
EE RM. UP ACCU-1 EE RM. UP ACCU-1
2.88

2.88

2.88
0.80 M. CANOPY LINE A 0.80 M. CANOPY LINE A
1.0HP 4.09 SQM. 01 02 =0311.73 SQM.
04 05 06 07 1.0HP 4.09 SQM. 01 02 =0311.73 SQM.
04 05 06 07 08 09
W
08 09
1.0HP W 1.0HP PB

2.00

2.00
W W
1,200 x 200

2.00
W W W W D C O N C R E T E S L A B
9 8 D 17 16 15 14 13 0.80 M. CANOPY LINE 9 8 10 D 17 16 15 14 13 12 0.80 M. CANOPY LINE
8 10 10 D
DN
12 11 10 8 10 1 DN
11 10
1

0.87
1 W W W W
8 8
TEF-2 9 TEF-2 9
2.05

2.05
5 T&B
150 CFM
TEF-2
5 5 T&B
150 CFM
DPC TEF-2
5 5 5
D PC CONCRETE
4.30 SQM. 4.30 SQM. 2
150 CFM 150 DCFM SLAB
2
D T&B T&B SEE SCHEMATIC DIAGRAM CONCRETE
4.82

4.82
3.87 SQM. 2 3.87 SQM.
2 W SLAB
W
5
ACU WAC-1 5 ACU WAC-1
WAC-1 WAC-1

0.80 M. CANOPY LINE


W
0.80 M. CANOPY LINE

1.0HP FCU-1 FCU-1 ACU W 1.0HP FCU-1 FCU-1 ACU 5

0.80 M. CANOPY LINE


2.77

2.77
BEDROOM 01 1.0HP 5 W BEDROOM 01 1.0HP

0.80 M. CANOPY LINE


BEDROOM 02 1.0HP 02
W
2 16.85 SQM. 1.0HP
11.72 SQM. BEDROOM BEDROOM 01 2 16.85 SQM. 1.0HP02
BEDROOM 1.0HP 02
BEDROOM BEDROOM 01
11.10 SQM. 12.10 SQM. 11.72 SQM. 11.10 SQM. 12.10 SQM. W
W 2
2 D D D D
D D D D 8 8 8 8
7.90

7.90

7.90

7.90
TV TV TV TV

7.90

7.90
8 8 8 8
W
TV TV W TV TV 2
1.00 1.36

1.00 1.36
W D D
Y

Y
W D D 2
2 7 7
2 7 7
KITCHEN UNIT 03 UNIT 04 KITCHEN UNIT 03 UNIT 04
A

A
24.46 SQM. 22.16 SQM. KITCHEN 24.46 SQM. 22.16 SQM. KITCHEN

DRYING RH-1 RH-1 DRYING W DRYING D RH-1 RH-1 DRYING W


W

W
3.95

3.95
D
W AREA D D AREA W
SCREEN 380 CFM SCREEN 5 AREA 9 SCREEN 380 CFM SCREEN 9 AREA 5
5 2.00 SQM. 9 380 CFM 9 2.00 SQM. 5 2.00 SQM. 380 CFM 2.00 SQM.

100Ø

100Ø
100Ø

100Ø
DOOR DINING LIVING LIVING DOOR DOOR DINING LIVING LIVING DOOR
L

L
DINING DINING
D D
D D
1.60

1.60
2
L

L
T&B 2 2 T&B T&B 2 T&B
3.36 SQM. TEF-1 TEF-2 3.36 SQM. 3.36 SQM. TEF-1 TEF-2 3.36 SQM.
A

A
WM REF 50 CFM 150 CFM
REF WM WM 50 CFM
REF
150 CFM
REF WM

4 4 4 4 4 CONCRETE CONCRETE
4

SLOPE
H

SLOPE
SLAB SLAB
WM REF TEF-1 TEF-2 WM TEF-1
PC
REF TEF-2
PC
1.60

1.60
T&B 50 CFM 150 DCFM T&B
T&B D50 CFM 150 DCFM T&B

100Ø

100Ø
3.36 SQM. D 3.36 SQM. 2 2
3.36 SQM. 3.36 SQM.
.

.
2 2
100Ø

100Ø
3.95

3.95
M

M
SCREEN DINING LIVING SCREEN DINING LIVING W
W DRYING D
1.36 1.00

1.36 1.00
DRYING
W AREA D DOOR WAC-1 ACU W
9 DOOR WAC-1 ACU 5
5 2.00 SQM. 9 RH-1 FCU-1 5 5 AREA RH-1 FCU-1

0.80 M. CANOPY LINE


1.0HP 2.00 SQM.
1.0HP

0.80 M. CANOPY LINE


380 CFM 1.0HP BEDROOM 01 W 380 CFM 1.0HP BEDROOM 01 W
2
UNIT 02 BEDROOM 02 UNIT 02 BEDROOM 02
0

0
11.69 SQM. 2 11.69 SQM.
KITCHEN W KITCHEN D
W 24.12 SQM. D 10.46 SQM. 24.12 SQM. 10.46 SQM.
2 7 D D

0.80 M. CANOPY LINE


0.80 M. CANOPY LINE

2 7 D D
5

5
8 8
8 8
7.90

7.90

7.90

7.90
TV TV

7.90

7.90
ACCU-1 ACCU-1
ACCU-1 ACCU-1
.

.
D D
1.0HP TV D
8
D
8 W 1.0HP 1.0HP TV 8 8 D
W
2 1.0HP
1

1
D 2 7
7 W
UNIT 05 UNIT 05
2.53

2.53
W BEDROOM 02 KITCHEN 2 BEDROOM 02 KITCHEN
2 BEDROOM 01 22.16 SQM. BEDROOM 01 22.16 SQM.
FCU-1
10.99 SQM. 10.99 SQM.
13.97 SQM. RH-1 DRYING 13.97 SQM. RH-1 D DRYINGW
1.0HP W FCU-1
4.15

4.15
W D AREA W 9 AREA 5
ACU 380 CFM SCREEN 9 2.00 SQM.5 5 ACU 380 CFM SCREEN
100Ø

100Ø
5 2.00 SQM.
TEF-2
LIVING
DINING
DOOR
TEF-2
1.0HP LIVING
DINING
DOOR

WAC-1 WAC-1 D
T&B D T&B T&B D T&B
150 CFM D
1.0HP 150 CFM 2 1.0HP 2
1.63

1.63
3.56 SQM. 2 3.36 SQM. 3.56 SQM. 3.36 SQM. CONCRETE
3
2 TEF-2 3 TEF-2 3 SLAB
1.50 1.50
31.59

31.59

31.59

31.59

31.59

31.59
150 CFM
REF WM 150 CFM
REF WM

3 3 3 3 3 PC CONCRETE
3
36.59

36.59

36.59
SLAB
TEF-2 PC PC TEF-2
PC
39.09

39.09
W W

39.09
D PC
9 150DCFM T&B
9 150DCFM T&B 1
100Ø

100Ø
UP UP 2
2 3.36 SQM. W 3.36 SQM.
2.80

2.80
W 08 07 06 05 04 03 02 01 08 07 06 05 04 03 02 01
AREA 4 08 07 06 05 04 03 02 01
4 AREA W
09 10 11 12 13 14 15 16 17 61.45 SQM. WAC-1 W 09 10 11 12 13 14 15 16 17 WAC-1
FCU-1 ACU 5 61.45 SQM. FCU-1 ACU 5 09 10 11 12 13 14 15 16 17

A 1.0HP A 1.0HP

0.80 M. CANOPY LINE


0.80 M. CANOPY LINE

0.80 M. CANOPY LINE

DN
1.0HP DN A

0.80 M. CANOPY LINE


DN
A-13
BEDROOM 01
A-13
1.0HP BEDROOM 01 W
BEDROOM 02 11.69 SQM. W BEDROOM 02 2
A-13
2 D 11.69 SQM.
D 10.46 SQM. 11 10.46 SQM. D
11 D D 11
D D 8 8
7.90

7.90

7.90

7.90
TV TV

7.90

7.90
PIPECHASE

PIPECHASE
8 8

PIPECHASE
2.25

2.25
2.53 SQM.

2.53 SQM.

SLOPE
ACCU-1 ACCU-1

2.53 SQM.
8 PERSON 8 PERSON
ELEVATOR RANGE HOOD WITH TV AIR RECYCLING ELEVATOR RANGE HOOD WITH AIR RECYCLING W
CAPACITY
LOBBY D CARBON FILTER
W
2
1.0HP CAPACITY
LOBBY D
TV
2 1.0HP
ACTIVATED ACTIVATED7 CARBON FILTER
(TYPICAL TO ALL)UNIT 06 UNIT 06
7
22.16 SQM.
(TYPICAL TO ALL) 22.16 SQM.
KITCHEN W KITCHEN
100Ø WALL CAP W 100Ø WALL CAP 3
1.05

1.05
3 TV TV
Y

Y
REF DRYING W REF D DRYING W
(TYPICAL TO ALL) W
RH-1 1.50 D AREA W (TYPICAL TO ALL) 5 RH-1 9 AREA5
ACU ACU
A

A
5 SCREEN 9 2.00 SQM. 5 SCREEN
STUDIO TYPE 2.00 SQM.
100Ø

100Ø
NOOK LIVING DOOR STUDIO TYPE NOOK LIVING DOOR
380 CFM 380 CFM
W

DINING

W
DINING
15.41 SQM. 15.41 SQM. WT WT
D D
D WAC-1 KITCHEN D WAC-1 KITCHEN
L

L
T&B T&B T&B T&B
1.60

1.60
2 2 CONCRETE
3.36 SQM. 2 2 3.36 SQM. 3.36 SQM. 3.36 SQM.
1.0HPSOFA BED 1.0HPSOFA BED
L

L
TEF-2 D TEF-2 SLAB
D 7
A

A
7 REF REF PC PC
150 CFM WM
150 CFM WM

2 2 2 2 2 CONCRETE
2
H

H
CANOPY LN.

TEF-2 TEF-2

CANOPY LN.
SLAB
WM PC PC PC WM
TEF-2
REF
TEF-2
REF
0.80 M.

W W

0.80 M.
W
150 CFM 150 CFM
.

.
9 W T&B 9 2 T&B
150 CFM 150 CFMD
2.35

2.35

2
100Ø

100Ø
M

M
D 3.36 SQM. 2 3.36 SQM.
KITCHEN 2 KITCHEN

DRYING RH-1 W DRYING D RH-1


0

0
LIVING DINING SCREEN
LIVING DINING SCREEN W
W LIVING LIVING D
AREA D DOOR D DRYING W 5 AREA 9 DOOR DRYING 5
5

5
5 SCREEN SCREEN 9
2.00 SQM. 9 380 CFMDINING 9 AREA 5 380 CFMDINING AREA
100Ø

100Ø
DOOR 2.00 SQM. DOOR
.

.
2.00 SQM. 2.00 SQM.
D
1

1
UNIT 01 UNIT 07 UNIT 07
CANOPY

D KITCHEN UNIT 01 KITCHEN

CANOPY
0.80 M.
1.60

1.60

0.80 M.
LINE

T&B 2 T&B D D W

LINE
22.72 SQM. D D 22.16 SQM. W 22.16 SQM.
3.36 SQM. TEF-2 7 7
RH-1 2 3.36 SQM. TEF-2 22.72 SQM. 7 7 RH-1 2
W W CONCRETE

SLOPE
150 CFM 380 CFM 150 CFM 380 CFM

SLOPE
7.89

REF
7.89

7.89

REF

7.89
WM TV TV 9 WM TV TV 9

7.89

7.89
SLAB
D D D D
D D D D
TEF-2 8 8 8 8 TEF-2 TEF-2 8 8 8 8
TEF-2
1.60

1.60

T & B 150 DCFM T & B 150 D


CFM D
T & B150 CFM T & B150 CFM
100Ø

100Ø
D
BEDROOM 01 BEDROOM 01 2 3.36 SQM. 2 BEDROOM 01 BEDROOM 02 BEDROOM 01 2 CONCRETE
3.36 SQM. 2 BEDROOM 02 12.24 SQM.
3.36 SQM.
11.91 SQM. 12.24 SQM.
3.36 SQM. SLAB
16.24 SQM. BEDROOM 02 11.91 SQM. 16.24 SQM. FCU-1 02
BEDROOM
13.31 SQM. W 13.31 SQM. FCU-1 W
W ACU ACU W ACU 1.0HP ACU
5 5
5
1.0HP 5
CANOPY

CANOPY
0.80 M.

0.80 M.
2.35

2.35
LINE

LINE
TV TV
FCU-1 FCU-1 WAC-1 WAC-1
TV WAC-1 WAC-1
TV
1.0HP 1.0HP 1.0HP 1.0HP
0.80 M. CANOPY LINE
0.80 M. CANOPY LINE

PC PC
1.0HP R A I L I N G 1.0HP R A I L I N G

1 ACCU-1 1 1 ACCU-1 1 1 1

0.50
ACCU-1 GD
ACCU-1 GD
1.20

1.20
1.0HP 1.0HP 1.0HP 1.0HP
0.50 1.63

0.50 1.63

2 2 W
W 7
7 CONCRETE

2.82
SLAB
3.00

3.00

3.00
W

2.50
W L I N E L I N E
R . C . C A N O P Y 6 R . C . C A N O P Y
6
4.62

4.62

4.62
6 6 6

1.80
1 1 1
NOTE: NOTE:
2 2 2
LOCATE CONDENSATE DRAIN LINE TO ITS LOCATE CONDENSATE DRAIN LINE TO ITS
NEAREST PLUMBING DRAIN COLLECTOR NEAREST PLUMBING DRAIN COLLECTOR
4.92 6.80 5.00 4.92 6.80 5.00 4.92 6.80 5.00

16.72 16.72 16.72

A B C D A B C D A B C D

A 4TH FLOOR AIR CONDITIONING & VENTILATION PLAN B 6TH FLOOR AIR CONDITIONING & VENTILATION PLAN C ROOF DECK AIR CONDITIONING & VENTILATION PLAN
SCALE 1:150 MTS. SCALE 1:150 MTS. SCALE 1:150 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A

B
4TH FLOOR AIR CONDITONING & VENTILATION PLAN

6TH FLOOR AIR CONDITONING & VENTILATION PLAN


1:150 MTS.

1:150 MTS.
M 3
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C ROOF DECK AIR CONDITONING & VENTILATION PLAN 1:150 MTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 50 64
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS

1 ½" STANDING SEAM


OFFICE OF THE BUILDING OFFICIAL
FLASHING W/ WELDED RIVETED OR BOLTED
ON 12" ON CENTERS
CEBU CITY
CORNER SEAMS
CURB
DETAIL-A

FLASHING W/ WELDED RECOMMENDING APPROVAL:


CORNER SEAMS
SECTION DETAIL-A

FLASHING DETAIL

ASST. BUILDING OFFICIAL : DATE :

APPROVED:

BUILDING OFFICIAL : DATE :


NOTE:
PROVIDE GRAVITY TYPE
PRESSURE RELIEF DAMPER

TOILET CEILING CASSETTE


1 PRESSURIZATION FAN INSTALLATION DETAIL 2 TYPE EXHAUST FAN DETAIL

AIR COOLED
CONDENSING UNIT

CONTROL WIRES/
CONDUIT TO FCU

REFRIGERANT
PIPES

IN.
mM
150m

FLOOR MOUNTED ACCU'S


CONCRETE PAD
WITH FRAME SUPPORT DETAIL
FRAME SUPPORT
(REFER TO STRUCTURAL ELEVATION SIDE ELEVATION
PLAN FOR DETAIL)
VIBRATION ISOLATOR

3 ACCU MOUNTING DETAIL 4 PIPE HANGER DETAIL 5 REFRIGERANT PIPE RISER

SLAB LEVEL

NOTES:
1. ALL PIPING MUST FOLLOW STANDARD REFRIGERANT PIPING TECHNIQUES,

A STAIR PRESSURIZATION SCHEMATIC RISER DIAGRAM 2.


3.
REFER TO MANUFACTURER DESIGN MANUAL.
ALL WIRING MUST COMPLY WITH THE APPLICABLE LOCAL & NATIONAL ELECT'L CODES.
LIQUID LINE NEED NOT BE INSULATED.
CEILING LINE
CONTROL CONNECTION
2 WIRES
THERMISTOR CABLE
3 WIRES
4. WIRING & PIPING SHOWN ARE GENERAL POINTS-OF-CONNECTION GUIDES ACCESSORY
ONLY AND ARE NOT INTENDED FOR A SPECIFIC INSTALLATION. LIQUID LINE COOLING ACCURATER
METERING DEVICE
5. INSULATE CONDENSATE DRAIN IF INSTALLED IN A CONDITIONED SPACE. INSULATED ( INSTALLED @ UNIT )
SUCTION LINE
AIR FLOW
FCU 24 V CONTROL POWER
PROVIDED INSIDE UNIT

TO ELECTRICAL CONDENSATE
DRAIN LINE

PANEL BOARD
WEATHERPROOF
FUSED DISCONNECT
SWITCH TO OPEN SIGHT
ACCU OW
DRAIN ( DO NOT TRAP )

AIR FL
2 WIRES
( + ) GROUND

HEATING
OW
AIR FL ACCURATER DEVICE
FILTER DRIER ( BIFLOW )
COIL MOISTURE INDICATOR
SIGHT GLASS
OUTDOOR
UNIT ROOF SLAB LEVEL

THERMISTOR CABLE
3 WIRES

CEILING SPACE

CEILING LINE

6 WALL MOUNTED TYPE FAN COIL UNIT DETAIL 7 WINDOW TYPE AIR CONDITIONING UNIT DETAIL

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A

B
STAIR PRESSURIZATION SCHEMATIC DIAGRAM

MISCELLANEOUS DETAILS
NTS.

NTS.
M 4
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 51 64
REPUBLIC OF THE PHILIPPINES
C C' D DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS
3.20 1.20 3.80 OFFICE OF THE BUILDING OFFICIAL
5.00 CEBU CITY

3.20 0.41
150 Ø SMOKE STACK WITH FIBER RECOMMENDING APPROVAL:
GLASS INSULATION & G.A 24 ALUMINUM
F CLADDING (UP TO 3RD FLOOR SLAB)
I R E W A L L
5
ASST. BUILDING OFFICIAL : DATE :
FIRE EXIT STAIR
A = 11.73 SQM.

LINE OF SYMMETRY 03 04 05 06 07 08

1.90
09 10
APPROVED:

2.00
17 16 15 14 13

1.90
12 11
BUILDING OFFICIAL : DATE :
D
3

0.34
GENSET EXHAUST DUCT
WITH VERTICAL EXHAUST LOUVER
12 mm Ø REINFORCEMENT BARS (BELOW STAIR LANDING)
@ EVERY 200mm SPACING C.C. BOTHWAYS
D
4

FOUNDATION BASE 150mm 10


ELEVATED FROM FINISHED FLOOR LINE

EXHAUST PIPE
C CONCRETE PAD LAYOUT PLAN W/ BIRD SCREEN
SCALE 1:50 MTS.
EXHAUST PIPE
W/ BIRD SCREEN

12mm Ø REINFORCEMENT 100mm THK. ISOLATION


BARS@ EVERY 200mm MATERIAL OF WET GRAVEL OR SAND
SPACING C.C. BOTHWAYS THOROUGHLY TAMPED THROUGHOUT

GENSET SPECIFICATION:
A CONCRETE PAD DESIGN PLAN POWER CAPACITY 300 KVA
SCALE 1:30 MTS.
VOLTAGE 240 V
HERTZ 60 Hz
PHASE 3 PHASE
BRAND CATERPILLAR

C C' D
1.20 3.80
5.00
0.19 3.20 0.41 D
3.63
0.16

F I R E W A L L
5

FIRE EXIT STAIR


A = 11.73 SQM.

03 04 05 06 07 08
09 10
2.00

CONCRETE PAD
17 16 15 14 13
1.90

12 11 240 KW / 300KVA
150mm THK.
D
3 EXHAUST PIPE
HIGH HEAT PAINTED

5
0.34

EXHAUST PIPE
HIGH HEAT PAINTED
AIR EXHAUST
LOUVER BELOW
STAIR LANDING
240 KW / 300KVA
GENERATOR SET
D
4
1.00

10
1.83

240 KW / 300KVA
GENERATOR SET
0.82

VIBRATION RUBBER
VIBRATION RUBBER PAD ISOLATOR
PAD ISOLATOR 0.36 1.90

B CONCRETE PAD LAYOUT PLAN 3.20


SCALE 1:50 MTS.

D ELEVATION LAYOUT SECTION @ A E ELEVATION LAYOUT SECTION @ B


SCALE 1:50 MTS. SCALE 1:50 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A

B
CONCRETE PAD DESIGN AND CALCULATION

CONCRETE PAD LAYOUT


1:50 MTS.

1:50 MTS.
M 5
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER C CONCRETE PAD LAYOUT 1:50 MTS.
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18 D ELEVATION LAYOUT SECTION @ A 1:50 MTS.
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY E ELEVATION LAYOUT SECTION @ B 1:50 MTS. 52 64
Hoitway Width : 2.00 2.00 hoistway Width : 2.00

0.37 Car Outside Width : 1.45 0.18 Min. 0.28 0.25 1.12 0.34 0.16 0.94 0.90
1 0.16 0.94 0.05 0.32 0.55
0.94 0.16

OVERHEAD : 4270
No.4 (1 Ton)

0.24
0.32
RW3

0.35

Min. .55
Bare Ceiling Height : 2470

0.57
Ceiling Height : 2300

Entrance Height : 2100

0.33
No.3 (2 Tons) No.2 (1 Ton)

RW1
Car Inside Width : 1.40

0.66
2

Car Inside Depth : 1.10

0.33
Car outside Depth : 1350
No.5 (1 Ton) No.1 (2 Tons)
0.35

0.54
0.43
1.70

1.70
1.70
ELEVATOR 8 PAX.

0.66
RW2 RW1 RW3
0.20

RW2

0.20
TOP FFL.

0.25
0.13
0.50

0.59
0.03
4 3 2 1

0.11

0.09
0.08
0.40
1.09 1.11
0.57 1.05 0.38
5TH FFL. 1.10 0.90
CL of CAR CL of Counterweight CL of CAR
CL of Car

B PLAN OF HOISTWAY C PLAN OF PIT D LOCATION PLAN OF HOISTING HOOK


SCALE 1:20 MTS. SCALE 1:20 MTS. SCALE 1:20 MTS.
TOTAL HEIGHT

4TH FFL.
CL
0.81 B

0.21 Constrcution Width : 1.01 0.15 Wall Thickness


LEGENDS:
TOTAL TRAVEL

Wall Thickness
1 : Hoisting Hook ( Supply & Install By Others)
CL Wall Finish
0.80 ( By Others ) 2 : Power Outlet : ( Supply & Install By Others)
A · Power Supply: 3 Phase, 200~480V,
50/60Hz x 1 Circuit/Lift.
Jamb 11 · Power Supply for Lighting : 200~480V,

0.01
Width : 50 50/60Hz x 1 Circuit/Lift.
· Duct Length from Hoistway Wall : 50mm
0.23 0.20 · Wiring Length from Hoistway : 7500mm
3RD FFL. 0.10 · Add Maintenance Outlet.
2 : Power Outlet : ( Supply & Install By Others)
· Power Supply: 3 Phase, 200~480V,

Panel Block Out


0.90
50/60Hz x 1 Circuit/Lift.

0.58 Inspection

Hall Button
Block Out
Construction Height : 2.22
· Power Supply for Lighting : 200~480V,

Construction Height : 2.20


0.45

0.49

0.49
0.59
0.59

50/60Hz x 1 Circuit/Lift.

Entrance Height : 2100


Opening Height : 2.10

· Duct Length from Hoistway Wall : 50mm


· Wiring Length from Hoistway : 7500mm
· Add Maintenance Outlet.
3 : M.S. Cat Ladder/Pit Ladder (Supply & Install By Others)

0.30

0.30
10 4 : Pit Lighting Switch (Supply & Install By Others)
9
1.10 from FFL

1.08 From FFL

1.08 From FFL


5 : 13A Switch Socket Outlet (Supply & Install By Others)

1.02 From FFL

1.02 From FFL


1.00 From FFL

0.90
2ND FFL. 6 : Pit Lighting (Supply & Install By Others)

7 : Buffer Plinth/Conc. Buffer (Supply & Install By Others)

8 : To Be Waterproof (Supply & Install By Others)

9 : Inspection Panel (Top Floor Only) ( By Hitachi )


FFL FFL FFL

10 : Hall Button / Indicator ( By Hitachi )

A B 11 : Provide Dowels for Elevator Entrance Parts Installation


0.05 (Supply & Install By Others)

Door Opening : 0.80

LOWEST FFL.
SECTION " A " SECTION " B "
PIT DEPTH : 1350

4 5 6
3
8
7
E ENTRANCE & SECTION "A" F CONSTRUCTION ENTRANCE
A SECTION OF HOISTWAY SCALE 1:20 MTS. SCALE 1:20 MTS.
SCALE 1:50 MTS.

SHEET
FROM THE OFFICE OF: REPUBLIC ACT 545 SEALED: APPROVED BY: PROJECT TITLE: CONFORM AND APPROVED: PREPARED BY: DPB GENERAL SITE SHEET NO:
TITLE:
DATE: .
DRWG.# SHEET CONTENTS: SCALE:

THIS DRAWING AS AN INSTRUMENT OF SERVICE IS THE


PROPERTY OF HAMM-ASIA GLOBAL
CORPORATION AND SUCH DRAWING MUST NOT BE
BUILDERS
ENGR. DIOSDADO N. EJERCITO, JR.
PROFFESSIONAL MECHANICAL ENGINEER
A PROPOSED 6-STOREY COMMERCIAL - MR. ANDREW L. BENEDICTO
CHECKED BY:
DATE:
.
.
A ELEVATOR DETAILS AS SHOWN

M 6
W:\HAGBC\LETTERHEADER HAMMASIA HAMMASIA.jpg
S:\Engineering Dept\Fritz\LETTERHEADER NEW12 copy.jpg REPRODUCED OR COPIED IN PART OR WHOLE WITHOUT PRC NO: 0002844 DATE: 12-18-89 RESIDENTIAL ( SERVICE APARTELLE ) BLDG. OWNER
THE CONSENT OF THE COMPANY. ANY VIOLATIONS IS A
CRIMINAL ACT @ IS PUNISHABLE BY LAW.ALL DRAWINGS REVISED BY: .
6
ARE TO BE RETURNED WHEN NO LONGER IN USE.
PTR NO: 2983912 DATE: 01-03-18
DATE: .
ADDRESS: 99 - 101 Plaridel Street, Barangay Ermita, Cebu City
TIN: 130-133-366 PTO-CEBU TALISAY CITY LOCATION: SANGLEY CREEK, NEAR ST. MICHAEL, KASAMBAGAN, CEBU CITY 53 64