Professional Documents
Culture Documents
A Review of Commonly Used DC Arc Models PDF
A Review of Commonly Used DC Arc Models PDF
ir
https://www.tarjomano.com/order
Tammy Gammon, P.E. Wei-Jen Lee, P.E. Zhenyuan Zhang Ben Johnson
Senior Member, IEEE Fellow, IEEE Student Member, IEEE Life Fellow, IEEE
John Matthews & Associates University of Texas - Arlington Thermon
P. O. Box 3229 Energy Systems Research Center P. O. Box 609
Cookeville, TN 38502 Arlington, TX 76019 San Marcos, TX 78666
Abtract - The DC arc hazard is a great concern to most popular DC arc model is often believed to be the DC
industry. Quantitative arc-hazard assessments are equivalent of Ralph Lee’s theoretical three-phase AC arc
performed on DC systems to determine a nearby worker’s model; however, this model is not a DC replication of Ralph
potential incident-energy exposure during an arcing Lee’s work. The original Ralph Lee model is more
event. Four viable DC assessment methods are reviewed sophisticated than determining burn hazard directly from the
in this paper. The most widely used model for predicting electrical arc energy, which is the approach taken by the
DC incident energy is based on Lee’s theoretical arc widely used DC model and Ammerman’s DC arc model,
model; the electrical arc power is determined from the addressed in Section III. Ammerman’s method for
maximum power transfer theorem and the arc is depicted determining electrical arc energy is based on an empirically
as a spherical radiant source with uniform heat derived, previously published arc current-power relationship.
transmission in all directions. Like Lee’s model, Ammerman includes two equations for determining incident
Ammerman’s model assumes complete conversion of energy density – one for open air and one for enclosures. In
electrical arc energy into thermal energy, but arc power is Section IV, DC arc testing conducted at the Kinectrics High
determined from an iterative technique constrained by Current Laboratory and a published set of equations for 600-V
arc power and circuit characteristics. Ammerman DC transit systems are discussed. Additional examples,
incorporates multiplying factors which account for the including one on photovoltaic systems, are presented in
higher incident energies associated with arcing in Sections V and VI.
enclosures. Based on DC arc testing, the applicability of
an existing software package has been extended to DC
systems through multiplying factors and equations for II. RALPH LEE’S WORK AND THE SPHERICAL,
DC rail and transit systems and equations have also been RADIANT ARC MODEL
developed. Model derivation is examined in this paper for
suitability to arcing in general and DC specifically. Model One of the most widely used DC models is based on the
performance is assessed using the available, limited data maximum power transfer theorem. Ralph Lee used the
(AC or DC). Example calculations are provided. maximum power transfer theorem in developing a theoretical
arc model to predict the distances for “curable” and “incurable”
burns sustained from three-phase AC arcing faults [1]. The
Index Terms – DC arc model, Ralph Lee model,
“curable” burn distance is analogous to the “arc flash
Ammerman’s model, DC transit systems
boundary” distance used in IEEE 1584 and NFPA 70E. Lee
assumed that the arc behaved as a passive linear resistance
and the system impedance was purely reactive; therefore, by
I. INTRODUCTION the maximum power transfer theorem, the maximum AC arc
power is 50% of the bolted-fault VA. The maximum power
Industry is working at a fast pace to address the DC arc transfer theorem states that the maximum power is
hazard exposure for workers. Unfortunately, the demand to transferred to the load when the load impedance equals the
assess worker risk has outsped the development of accurate source impedance. For a DC circuit, the maximum power
assessment methods for DC power systems. At present the transferred to an arc is 25% of the bolted-fault VA, as
only quantitative methods, which have been verified or are illustrated in Fig. 1. Lee did not use the arc current to
based on representative DC arc testing, have been developed determine the response time of the overcurrent protective
at a well-known high current laboratory. The popular, widely device. His original “curable” and “incurable” burn distances
used theoretical model, based on Ralph Lee’s work is were based on an arc duration of 100 ms.
addressed in Section II. The section includes a brief review of Lee conceptualized the arc as a perfect sphere radiating
radiant heat projection and thermal energy absorption by heat, essentially a blackbody radiator. Thermal radiation is
human skin. With the theoretical model, the arc power is the emission of electromagnetic waves in the range of 100 nm
determined by the maximum power transfer theorem. The to 100 um, covering the infrared, visible and part of the
ultraviolet spectrums [2], as shown in Fig. 2. For an ideal
blackbody at rest, the specific distribution of the thermal
wavelengths only depends on its temperature. The rate of
radiant heat, q, is a function of temperature as defined by the
Stefan-Boltzmann law [3] in (1) where A and T are the surface 100 ms, would sustain a “curable” arc burn [1, Table IV].
area and temperature of the transmitting body, respectively. (Please note that the duration of elevated skin temperature
does not necessarily coincide with the duration of heat
∙ ∙ , 5.6697 ∙ 10 (1) exposure. For an illustration, refer to Fig. 7 in companion
paper [6].) Lee produced quite remarkable work.
In contrast, the widely used DC arc model in (2) based on
the maximum power transfer theorem simply assumes that all
electrical arc energy is converted directly to an incident
2
energy density (J/cm ) absorbed by a surface at a distance, d.
, ⋅
(2)
35
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
higher than 50% of the bolted fault current, as specified by the The IEEE 1584, three-phase AC, arc test data has also
maximum power transfer theorem. Furthermore, the been analyzed to determine if the power delivered to the arc
measured DC arc voltages are significantly lower than 50% of approaches the theoretical 50% maximum for AC systems
the supply voltage. It should be noted that the data in the [18], [19]. The average ratios of arc power to available VA
figures represent one limited set of tests conducted using a were 0.332 and 0.214, respectively, for 165 low voltage (“LV,”
325-V DC supply, a 3/8-in (9.5mm) electrode gap width and <1 kV) and 148 medium voltage (“MV,” >1 kV) tests [18]. The
series vertical electrodes in open air. Different DC supply medium voltage ratios were lower because the arc current
voltages, bolted-fault currents, gap widths, electrode approaches the magnitude of the bolted fault current and the
orientations and configurations are expected to result in a arc voltage is a relatively small percentage of the system
wide range of arc currents, arc voltages and incident energy voltage over the gap widths tested.
densities. It is very unwise to use the maximum power Lee’s original equation to determine the curable burn
transfer theorem to predict DC arc current and incident energy distance for three-phase AC arcs was modified to calculate
density. Accurate estimation of the arc current is essential in incident energy density (J/cm2) in the IEEE Standard 1584-
determining the expected response time of the overcurrent 2002 [20]. For the 1584-modified form in (3), the system
protective device. The DC time constant, which may delay voltage, bolted-fault current, time and distance to the arc are
the arcing fault current in reaching its full magnitude, also expressed in kV, kA, seconds and mm, respectively.
needs consideration in the operation of the protective device;
it has been addressed in [8], [17]. 2.142 ∙ 10 ∙ ∙ ∙ (3)
∑
% (4)
36
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
. . .
The DC arc current, voltage and power determined by ∙ 1.757 ∙ ∙ ∙ ,
Ammerman’s model, displayed in Figs. 3 and 4, more closely 0.821 , 1 (9)
match Hall’s data than the “theoretical” values previously
discussed. However, it must be remembered that the Stokes The ac arc current (line) is constrained by the phase-to-
equation was formulated for series (opposing) electrodes in neutral voltage, system impedance and arc resistance.
open air under fairly stable arcing conditions. Arcing at lower Equation (9) was formulated from a multiple regression fit of
voltages, wider gap widths, higher bolted-fault currents or with the available data set. The three-phase AC electrical arc
parallel electrodes may result in a lower Iarc/Ibf ratio and a energy was calculated and the spherical incident energy
different V-I characteristic. The presence of an enclosure may density component, ES, in (7) was defined; then, the maximum
tend to increase the Iarc/Ibf ratio. incident energy density equation in (8) for open air, ES, was
Ammerman used the equations in (7) based on Wilkins’ formulated from a “best-fit” statistical analysis. Finally the
work to determine the DC incident energy density, where d is values for a and k were determined for the enclosure incident
the worker distance, and the factors k and a account for the energy density component, E1, by a “least-squares best fit”
arc energy that is reflected from the enclosure walls and statistical analysis. The statistical analysis is based on an AC
projected to the front of the enclosure. data set which may not uniformly represent a wide cross-
section of electrical parameters or typical configurations
∙ (7) where an AC or DC arcing fault may occur. The determined a
and k values are based on a progressive, three-stage
, statistical analysis and a specific set of three-phase AC arc
4 data.
, The 1584 test database includes 54 LV “panel”
(14inx12inx7.5in) tests, 87 LV “switchgear” (20inx20inx20in)
tests and 78 MV “switchgear” (45inx30inx30in) tests. The
Inspired by Ammerman’s work, Fontaine [25] further calorimeter distance was 600-610 mm for 43 of 54 LV panel
extended Wilkins’ iterative technique and more tests, 78 of 87 LV switchgear tests and 56 of 78 MV
comprehensively presented the application of the Wilkins’ a switchgear tests. The 22 MV switchgear tests conducted at
and k factors in determining the incident energy projected other calorimeter distances involved only one bolted-fault
from enclosures. Wilkins’ constants and the effective current level at 15 kA. Indeed, the low-voltage multipliers at
multipliers used to calculate the DC enclosure incident energy 18 in to 24 in and the medium-voltage multiplier at 24 in may
density, E1, from the DC open air incident energy, Es, are be reasonable for vertical electrodes and for the three-phase
provided in Table II for various worker distances. AC 1584 arc data. However, the increase in the LV and MV
Wilkins used the 1584 data set (310 entries) and 37 switchgear multipliers as the distance from the arc increases
additional tests performed at Ferraz-Shawmut to develop is a concern. Data to validate the use of these multipliers,
37
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
even in three-phase AC systems, is sparse if not inadequate. incident energy density than Ammerman predicts for a panel,
There is no data to validate the use of these multipliers over but less than Ammerman predicts for switchgear. In
the wide range of typical applications in DC systems. This comparison with the incident energy densities predicted by the
paper does not support or endorse the use of these multipliers DC Ammerman model and the three-phase AC 1584 models,
at any arbitrary distance in DC arc modeling. As the Wilkins’ a 3x factor for enclosures, suggested for the DC theoretical
constants suggest, the effect of the arc distance and the model appears high. Since the 1584 equations have been
enclosure size certainly impact the level of incident energy developed to conservatively predict the incident energy
impressed on a surface. A deeper understanding is needed density for a three-phase AC arcing fault, the higher 1584
of the thermodynamic projection of heat and the relationships incident energy predictions are expected. The 1584 incident
between enclosure dimensions, electrode gap widths, energy predictions should be considerably higher than a
electrode-to-back-panel distance and electrode orientation, as single-phase DC arcing fault.
well as bolted-fault current and system voltage. Heat transfer
from the arc is dependent on the system type – DC and AC
single-phase or AC three-phase. The total heat generated IV. WORK IN DC ARC TESTING & MODELING
and the directional projection of the arc’s thermal energy are
impacted by the physical presence and combustive properties Kinectrics has conducted a DC arc testing program in their
of real world electrical equipment. High Current Laboratory. The range of test parameters
Like the widely used “theoretical” DC arc model, covered is listed in Table IV [26]. Based on the DC arc
Ammerman’s DC arc model assumes 100% conversion of testing, multiplying factors for DC systems have been included
TM
electrical arc energy into incident energy absorbed by the in ArcPro and verified for the range of bolted fault currents
receiving surface. In reality, the electrical arc energy is also from 2 to 25 kA covering gaps up to 0.5 in for 130 Vdc and up
converted to additional forms of energy (refer to Section II, to 2 in for 260 Vdc. The technical basis of the arc model used
paragraph 6). Furthermore, not all forms of thermal energy, in the commercial software is described in Appendix A.
such as visible light, are absorbed by the receiving surface The 600-Vdc arc testing was conducted with series
with the same efficiency. Human skin has a greater electrodes in open air and with parallel electrodes directed
coefficient of absorption for infrared wavelengths than visible either downward or outward (i.e., vertical or horizontal) in an
light (refer to Section II, paragraph 6). enclosure. The enclosure tests resulted in higher incident
Table III presents a comparison of results predicted by the energy measurements than the open air testing. The
“theoretical” DC and the Ammerman DC arc models, as well enclosure incident energy measurements were similar for the
as the 1584 three-phase AC arc equations. The Ammerman vertical and horizontal electrode orientations. The equations
DC model more closely matches the measured arc current, in (10) were developed [26] and apply to open air DC arcing
arc voltage and estimated arc power for the 1800-A, bolted- [27]. In (10), the bolted fault and arc currents are expressed
fault DC arc test conducted by Hall [16] than the theoretical in kA; the electrode gap, G, and calorimeter distance, D, are
model. The theoretical DC model predicts an incident energy expressed in inches. The arc duration time, t, is expressed in
density which is 66% higher than the Ammerman DC model seconds.
for open air. The theoretical model predicts a slightly higher
. .
0.9063 ∙ 0.1051 ∙ ∙ 1 (10)
6
TABLE III 0.9694 0.0589 0.4793 ln 1.0027
COMPARISON OF HALL DATA WITH DC & AC MODELS 0.1
a
Iarc Varc Parc IE
The sustainability of the arc at gap widths up to 6 inches
A V kW cal/cm2 depended on the supply voltage, the bolted fault current and
Hall DC Arc Data for Tests, g = 3/8 in, Vs = 325 V the electrode configuration. For all of 600-V tests conducted,
Ibf = 1800A 1500 50 75 the arcing fault current ranged between 64% and 97% of the
DC Arc Models bolted fault current. The 600-V equation could be used to
"Theoretical" 900 162.5 146.3 1.33 conservatively predict incident energy for 125-V and 250-V
DC systems in areas without overcurrent protection or with
"Theoretical" x 3 3.99
overcurrent protective devices not anticipated to respond.
Ammerman open air 1467 60 88.3 0.80 However with responsive circuit protection in place, accurately
Ammerman panel 1467 60 88.3 1.22
Ammerman swgr 1467 60 88.3 1.78
600-V open air 1612 0.89 TABLE IV
DC ARC TEST RANGE AT HIGH CURRENT LAB [26]
Three-Phase AC (for grounded & ungrounded systems)
DC voltage (V) 125, 250, 600
1584 open air grd 1234 2.14
Bolted fault current (kA) 1 - 25
1584 open air ug 1234 2.77
Electrode gap width (in) 0.2 - 6 (6-152 mm)
1584 panel grd 1404 3.82 Arc duration (s) 0.01 - 2
1584 panel ug 1404 4.96 Arc distance (in) 6, 12, 22, 34 (152-864 mm)
1584 switchgear grd 1404 3.64 Electrode/enclosure Vertical series electrodes in
1584 switchgear ug 1404 4.72 configuration open air; vertical & horizontal
a
IE predicted at 18 in (457 mm) from arc, duration = 1s. parallel electrodes in enclosure
38
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
estimating the arc current is a critical step; the incident energy incident energy density predicted for an arc duration ranging
depends on the response time of the protective device, from 0 to 2 s is displayed in Fig. 5 for both the single- and
activated by the magnitude of the fault current. double-string case studies.
Table III includes the arc current and incident energy Tables VI and VII show that the incident energy (0.5-s arc
predicted by (10), the 600-Vdc open air model. It is not duration) predicted by the Ammerman, 600-V open air and
surprising that the model predicts an arc current that is slightly theoretical DC arc models lie in fairly close proximity for the
higher (7.5%) than the arc current initiated by a 325-Vdc system parameters given. For 260-Vdc arcing across a 1-in
supply. It also predicts an incident energy density slightly gap, the 2007 report [28, Fig. 7] suggests an available bolted
higher (11%) than the value predicted by Ammerman for open fault current of 18.7 kA would result in a 9.2-kA arc current, a
air. Equation (10) was derived from testing bolted fault magnitude significantly lower than Ammerman’s model
currents between 2 and 25 kA, a range higher than the bolted predicts but probably more representative of actual arcing in
fault current for the example data in Table III; gap widths for DC power systems. Arc duration and therefore incident
the 600-V testing were also probably wider than 3/8-in arc gap energy are governed by the arc current when responsive
used. Although not published in [26], enclosure multiplying protective devices are present. The arc current and incident
factors (based on 20inx20inx20in test enclosures) were energy density predicted by the 1584 three-phase AC
formulated for (10) [27]. equations do not and are not expected to match the values
A summary of the 130-V and 260-V DC arc testing program predicted by the DC arc models. A 250-V, three-phase Vac
was published in [28]. Although detailed test data and system would be associated with low magnitude, possibly
formulations were not included, [28] contains some valuable non-sustaining, arc currents.
observations about the testing. A 130-Vdc supply was
capable of sustaining arcs across 0.25-in and 0.5-in gap TABLE VI
widths; however, 0.25-in gap arcing could not be sustained SINGLE-STRING BATTERY SYSTEM
using a single-phase, 125-Vac supply and similar bolted fault System Ibf, Vdc, gap 18.7 kA 258 V 20 mm
current levels. Arcing was sustained across 1-in and 2-in Iarc Iarc/Ibf IE (cal/cm2)
gaps using a 260-Vdc supply. To achieve sustainable AC Arc models (kA) (%) 18”, t=0.5 s
arcs across 1-in and 2-in gaps, the single-phase AC supply
Ammerman open air 11.8 63 5.1
voltage had to be increased to 480 or 600 Vac [28]. Unlike
AC arcs, DC arcs do not pass through current zero and do not Theoretical 9.4 50 5.5
require re-ignition each half cycle. A single-phase, AC arc 600-V open air 12.6 67 6.0
current oscillates at the same fundamental time-varying 1584 open air, gnda 6.8 36 6.9
frequency as the AC supply voltage; the arc plasma column 1584 open air, ugb 6.8 36 9.0
(and radiated heat) will also expand and contract. Under a
“gnd” - grounded system; b “ug” - ungrounded system
stable arcing conditions, the magnitudes of DC arc current are
much more constant over time. The DC arc plasma column TABLE VII
also exhibits much less variation [26]. DOUBLE-STRING BATTERY SYSTEM
For average DC and AC rms arc currents over a range of 2 System Ibf, Vdc, gap 39.0 kA 258 V 20 mm
to 10 kA, the heat flux (the rate of incident energy) is Iarc Iarc/Ibf
2
IE (cal/cm )
approximately 1.25 times higher for DC arcing [28]. Rough arc Arc models (kA) (%) d=18 in, t=0.5 s
current and heat flux interpretations of figures presented in
[28] are provided in Table V. Ammerman open air 23.5 60 11.0
Theoretical 19.5 50 11.4
TABLE V 600-V open air 25.4 65 12.1
260-V DC ARC TEST RESULTS IN [28, FIGS. 7 AND 8] a 1584 open air, gnda 11.7 30 12.5
Gap width (in) 1 2 1584 open air, ugb 11.7 30 16.2
a
Bolted fault current (kA) 2 – 25 2 – 31 “gnd” - grounded system; b “ug” - ungrounded system
2
Arc current (kA) 1¼ – 11½ /3 – 9½
2
Heat flux (cal/cm -s) at 12 in ⅟3 – 12½ ⅟3 – 18
a
Ranges estimated by rough visual interpretation of graphs.
39
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
In [8] Doan presented an example for a 135-V battery with results in Fig. 5 illustrate the potential to severely burn or kill
a short-circuit current of 1338 A. A 2-s arc duration was set, when high fault currents are available and sensitive
the maximum value used in arc-flash studies. The incident responsive devices are not protecting the system.
energy predicted by the Ammerman and the theoretical DC
arc models is listed in Table VIII. Fig. 6 displays the predicted
incident energy as a function of time. For 135-V arcing across VI. PHOTOVOLTAIC INSTALLATIONS
an assumed 0.5-in gap width, the Ammerman and the
theoretical DC models predict arc currents in closer proximity The maximum power transfer theorem states that maximum
than the previous example. The incident energy predictions power is transferred to a linear load when the load impedance
for the open air Ammerman and theoretical DC models are matches the source impedance. As shown in Fig. 1, 25% of
almost identical. The proximity in the results lends confidence the DC short-circuit power is the maximum power transferred
in the performance of each model for 130-Vdc systems and to the DC arc; the DC arc current and arc voltage are equal to
open air arcing. However, the incident energy values 50% of the short circuit current and open circuit voltage. The
predicted by the Ammerman panel and switchgear models are arc is assumed to be a passive linear resistance and any non-
considerably higher than the theoretical DC model, but linearity of the DC power source is not addressed.
considerably lower than three times the DC theoretical model, Photovoltaic cells are highly nonlinear elements. The voltage
which is sometimes applied to enclosure arcing. These two and current at maximum load power may even be estimated
battery examples suggest that the Ammerman and theoretical as 80% of the open circuit voltage and 94% of the short circuit
DC arc models may be adequate for predicting open air current for utility-grade photovoltaic cells [29, Table II].
incident energy on 125 to 250 Vdc bus when protective Therefore, the maximum load power might be estimated as
devices are not expected to interrupt the arcing fault. 75% of the short circuit power – three times higher than the
However, no arc testing has been done in the public domain maximum power transfer theorem for linear DC loads.
to verify either model’s performance for these conditions. However, usage of either the maximum power transfer
Furthermore, arcing occurs in a wide range of DC systems theorem or of the photovoltaic maximum power point to
(and system voltages) and often occurs in some type of predict maximum arc power fails to address the potential
electrical enclosure. current limiting effect of the arc resistance.
The open air incident energy values predicted by the DC Large photovoltaic arrays are becoming increasingly
arc models shown in Figs. 5 and 6 do provide an excellent common on commercial and industrial sites to reduce the
perspective of the wide range of potential incident energy consumption of utility power. The number of solar farms
exposures in the 125-V to 250-V DC range. Low short-circuit connected to the utility grid increases annually to decrease
capacity certainly limits the potential heat exposure, even for a the dependence on fossil fuel in electric power generation.
325-Vdc supply as shown in Table III. But fairly low voltage The differences between photovoltaic cells and batteries may
DC supplies do not necessary limit the risk of injury. The need to be addressed in arc hazard assessment. Two recent
papers provide additional information about photo voltaic
TABLE VIII systems [29], [30] and are excellent references on the subject.
MODEL RESULTS WITH 135-V BATTERY, ISC = 1338A Reference [30] discusses an arc-flash hazard study
Arc Models Iarc Varc IE (cal/cm2), t = 2 s, conducted for a 1.3-MW photovoltaic system.
A V d = 18 in (457 mm) An example solar farm study presented in depth in [29] will
Ammerman open air 751 59 0.81 be briefly covered in this work; the arc hazard is being
Ammerman panel 751 59 1.23 analyzed for a recombiner panel. The photovoltaic system
Ammerman switchgear 751 59 1.80 parameters are summarized in Table IX. The arc currents
Theoretical 669 67.5 0.82 and incident energies predicted by the various DC arc models,
Theoretical (3 x IE) 2.5 as well as the Standard 1584 three-phase AC arc models, are
600-V open air model “blows up” (invalid for Ibf < 2000 A) provided in Table X for comparison. Without conducting arc
tests supplied by photovoltaic cells, it is difficult to even guess
which DC model is the best predictor of arc current. The DC
2
incident energy predictions range from 1.61 to 38.1 cal/cm .
The 600-V open air equation is the only DC model based on
DC arc testing, but it was formulated from open air arc tests
which were supplied by a lower voltage, controlled DC power
source, not eleven photovoltaic cells connected in series [29].
It seems plausible that the potential DC incident energy
exposure should not exceed the potential exposure from a
three-phase, AC arcing fault. Therefore, the conservative
maximum incident energy exposure is assumed to be less
than or equal to 9.28 cal/cm2, the value predicted for the
three-phase AC low voltage, ungrounded panel enclosure
(highest value predicted by any form of the 1584 equation). It
should also be kept in mind that the available, short circuit
current is very low and the 2-s arc duration used in this
example is long. Heat loss occurs as heat is radiated,
Fig. 6. IE comparison of DC arc models for system in [8]. convected and possibly conducted (molten material) to a
40
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
distance 18 inches (for this example) away from the arc. Also, extended to DC arcing, and 600-V open air equations
as previously addressed in Section II (paragraph 6), not all of developed for rail and transit systems. Only the commercial
the energy generated by the arc is converted to incident software package and 600-Vdc open air equations have been
energy, although the DC theoretical, Ammerman and PV verified by or are based upon representative DC arc testing.
maximum power point models are based on this assumption. While it is agreed that industry needs to address the arc
Long duration, low current arcing may not pose a potential hazards posed by DC systems, accurate methods of
2
incident energy risk even close to 10 cal/cm at an 18-in quantifying the arc hazard are critical. Without accurate
distance from the arc. assessment, any arc flash hazard study performed on a DC
Reference [29] predicts a maximum incident energy of 52 power system has limited value. Inaccurate assessment is
2
cal/cm from a source with an available short circuit of less counterproductive to the effective protection of workers.
than 1000 A. The incident energy prediction in [29] is based Furthermore, inflating potential risks not only adds to the cost
on the maximum power point of a photovoltaic cell, a safety of protection, but also taxes workers with additional personal
multiplier of 3, and a temperature compensation factor for the protective equipment (PPE), which may be more cumbersome
solar cells (not addressed here). Certainly, implementing or hot than necessary. PPE is a necessary means of
such PPE requirements would be counterproductive to protecting workers from arc hazards in energized systems, but
industry, counterproductive to worker safety, and wearing it in some circumstances may also increase the risk
counterproductive to the acceptance and adoption of safe of heat stroke or some form of occupational injury. Industry
work practices. The publication of the results in [29] may needs an acceptable method of DC arc hazard assessment
have been partially motivated to raise awareness in the solar developed in a nationally recognized standard. Support is
photovoltaic industry on the urgent need for arc testing so that needed for research and testing of the DC arc hazard.
the potential arc hazard risk to workers can be assessed
accurately.
VIII. AUTHORS’ INFORMATION
TABLE IX
ELECTRICAL PARAMETERS FOR EXAMPLE SYSTEM [29] Tammy Gammon earned a bachelor, a master of science
Circuit Current Voltage and a Ph.D. in electrical engineering from the Georgia
A V Institute of Technology in the 1990s. She is licensed as a
Open circuit -- 981.2 Professional Engineer in North Carolina. Since 2003, Tammy
Short circuit 940.2 -- has worked as senior electrical engineer for John Matthews
PV maximum power point 879.8 794.2 and Associates. She performs research and analysis in
power and power quality issues, in fires of electrical origin, in
electrical arc and shock injuries, and in product design and
TABLE X manufacturing. Since 2006, Tammy Gammon has also
ARC MODEL RESULTS - EXAMPLE SYSTEM IN TABLE IX served as the research manager for the IEEE/NFPA Arc Flash
DC & 1584 Arc Models Iarc Varc IE cal/cm
2 Research Project. Email: tgammon@tds.net.
(assumed a gap of 4 in) A V d=18in,
t=2s Wei-Jen Lee (S’85-M’85-SM’97-F’07) received the B.S. and
Ammerman open air 782 165 2.35 M.S. degrees from National Taiwan University, Taipei,
Taiwan, R.O.C., and the Ph.D. degree from the University of
Ammerman LV panel 782 165 3.58
Texas, Arlington, in 1978, 1980, and 1985, respectively, all in
Ammerman LV swgr 782 165 5.22
Electrical Engineering. He is currently a professor of the
Ammerman MV swgr 782 165 2.31
Electrical Engineering Department and the director of the
Theoretical 470 491 4.20 Energy Systems Research Center.
Theoretical (3 x IE) 12.6 Prof. Lee has been involved in research on arc flash and
PV max power point 880 794 12.7 electrical safety, utility deregulation, renewable energy, smart
PV max power (3 x IE) 38.1 grid, microgrid, load forecasting, power quality, distribution
600-V open air 508 1.61 automation and demand side management, power systems
1584 LV open, uga 936 5.19 analysis, online real time equipment diagnostic and prognostic
1584 LV panel, uga 1,064 9.28 system, and microcomputer based instrument for power
1584 LV swgr, uga 1,064 8.84 systems monitoring, measurement, control, and protection.
1584 MV open, uga 950 3.52 Since 2008, he has also served as the project manager for the
1584 MV swgr, uga 950 4.51 IEEE/NFPA Arc Flash Research Project.
a
1584 - Higher IE are predicted for ungrounded systems. LV IE Prof. Lee is a Fellow of IEEE and registered Professional
are higher due to the 1.5 crest factor for LV systems. Engineer in the State of Texas. Email: wlee@uta.edu.
41
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
REFERENCES
[8] D. Doan, “Arc flash calculations for exposures to dc
[1] R. Lee, “The other electrical hazard: electrical arc blast systems,” IEEE Trans. Ind. Appl., vol. 46, no. 6, pp. 2299-
burns,” IEEE Trans. Ind. Appl., vol. IA-18, no. 3, pp. 246- 2302, Nov./Dec. 2010.
251, May/June 1982. [9] R. L. Doughty, T. E. Neal, T. A. Dear and A. H. Bingham,
[2] D. Pitts and L. Sissom, Schaum’s Outline of Heat Transfer, “Testing update on protective clothing & equipment for
2nd ed. New York: McGraw-Hill Companies, Inc., 1998. electric arc exposure,” IEEE Ind. Appl. Mag., vol. 5, no. 1,
[3] Y. A. Çengel and M. A. Boles, Thermodynamics: An pp. 37-49, Jan./Feb. 1999.
Engineering Approach, 3rd ed. New York: McGraw-Hill [10] H. Wu, email communication, Feb. 18, 2008.
Companies, Inc., 1998. [11] H. Schau and D. Stade, “Impacts of internal arcing faults in
[4] Engineering Guide for Predicting 1st and 2nd Degree Skin low-voltage switchgear assemblies and power systems,” in
Burns from Thermal Radiation, Society of Fire Protection Proc. 28th Universities Power Engineering Conf., Stafford,
Engineers, 2000. United Kingdom, 1995.
[5] C. P. Artz, J. A. Moncrief and B. A. Pruitt, Burns. [12] A. Dasbach, “Untersuchungen zur leistungsbilanz von
Philadelphia, PA: W. B. Saunders Company, 1979. storlichtbogen im hinblick auf die druckbeanspruchung von
[6] T. Gammon, W.-J. Lee, Z. Zhang and B. Johnson, “‘Arc schaltagen,” Ph.D. dissertation, RWTH Aachen Univ.,
flash’ hazards, incident energy, ppe ratings and thermal Aachen, Germany, 1987.
burn injury – a deeper look,” unpublished work. [13] H. Wu, unpublished discussion of Dasbach’s work, Feb.
[7] Standard for Electrical Safety in the Workplace, 2012 ed., 28, 2008.
NFPA Standard 70E, 2011. [14] H. Wu, unpublished key points of Dasbach’s work (in
English), Nov. 18, 2007.
42
Downloaded from https://iranpaper.ir
https://www.tarjomano.com/order
43