Professional Documents
Culture Documents
Qfarm Manual v1.21
Qfarm Manual v1.21
21
Handbook EN 270317 1
2
Index
Introduction......................................................................................................................6
Home.................................................................................................................................10
1 Zoom on farm ambient........................................................................................................11
2 Zoom on ventilation............................................................................................................12
2.C Set diagrams...........................................................................................................14
2.D Ampere.............................................................................................................15
2.E Cooling/Humidification..............................................................................................15
3 Zoom on flap......................................................................................................................16
4 Zoom on ambient heating....................................................................................................17
5 Zoom on radiant heating......................................................................................................18
6 Zoom on animal s accountancy.............................................................................................20
7 Zoom on bird weighing........................................................................................................21
8 Zoom on feeding.................................................................................................................22
9 Zoom on feed distribution....................................................................................................23
0 Zoom on silos.....................................................................................................................23
C. Alarm..........................................................................................................................24
C.D Silence alarm.............................................................................................................25
C.E Reactivate alarm.........................................................................................................25
C.F Restart feed system.....................................................................................................25
C.H Alarm state................................................................................................................26
D. Settings......................................................................................................................28
D.1 Climate...............................................................................................................29
D.2 Animal accounting.......................................................................................................32
D.2.F Eggs accounting..........................................................................................................33
D.3 Feeding...............................................................................................................34
D.3.1 Time clocks.....................................................................................................34
D.3.1.1 Meal times.......................................................................................35
D.3.1.2 Light times.......................................................................................36
D.3.1.3 Water times.....................................................................................36
D.3.1.4 Timer 1 times...................................................................................37
D.3.1.5 Timer 2 times...................................................................................37
D.3.2 Special meal...................................................................................................39
D.3.2.1 First feed upload/Supplementary meal.................................................39
D.3.2.2 % variation of feed in the daily curve.....................................................39
D.3.2.3 Fixed meal from day.. to day................................................................40
D.3.2.4 Manual feed amount..........................................................................40
D.3.2.5 Medicated water...............................................................................41
D.3.2.6 Fast...........................................................................................41
D.3.3 K recording.....................................................................................................42
D.3.4 Silos upload....................................................................................................42
D.4 Bird weighing.............................................................................................................43
D.5 Calendar curves..........................................................................................................44
D.5.1 Calendar curves setting....................................................................................45
D.5.2 Curves activaction...........................................................................................47
D.0 Starting cycle.............................................................................................................49
D.0.F Pre-start up cycle.............................................................................................51
E. Installation.................................................................................................................52
E.1 Climate...............................................................................................................52
E.1.1 Heating....................................................................................................53
E.1.1.1 Ambient.....................................................................................54
E.1.1.2 Radiant heaters................................................................................56
E.1.1.2.1 Modulating heaters...........................................................56
E.1.1.2.2 Sparking heaters..............................................................58
E.1.1.3 Fan-jet............................................................................................59
E.1.1.4 Conditionings..............................................................................60
E.1.1.4.1 Night time heating range.....................................................60
E.1.1.4.2 Increase for humidity........................................................61
E.1.1.4.3 Decrease for humidity / Stop for Ventilation..........................62
E.1.2 Flap.........................................................................................................63
E.1.2.1 Depressiometer...........................................................................64
E.1.2.2 Associative % ...................................................................................65
3
Index
E.1.2.3 Natural.......................................................................................66
E.1.2.3.1 Temperature set..............................................................66
E.1.2.3.2 Floating......................................................................67
E.1.2.3.3 Proportional................................................................69
E.1.2.4 Potentiometer recording....................................................................70
E.1.2.5 Conditionings..............................................................................71
E.1.2.5.1 Increase pressure based upon outdoor temperature...............72
E.1.2.5.2 Anemometer...............................................................73
E.1.2.5.3 External forcing................................................................74
E.1.2.5.4 Draft function..................................................................75
E.1.2.5.5 Delta temperature............................................................76
E.1.2.5.6 Opening reduction for outdoor temperature..........................77
E.1.3 Ventilation................................................................................................78
E.1.3.1 Temperature set...............................................................................79
E.1.3.2 Air-exchange...................................................................................81
E.1.3.3 0-10V Ventilation..............................................................................85
E.1.3.3.1 Proportional................................................................85
E.1.3.3.2 Steps.........................................................................87
E.1.3.4 Conditionings..............................................................................90
E.1.3.4.1 Increase Ventilation based upon indoor humidity...................91
E.1.3.4.2 Increase Ventilation based upon indoor humidity...................92
E.1.3.4.3 Decrease air-exchage set based upon outdoor temp...............93
E.1.3.4.4 Maximum ventilation based upon outdoor temperature..........94
E.1.3.4.5 Night time ventilation settings............................................94
E.1.3.4.6 External forcing................................................................95
E.1.3.4.7 Winter/summer ventilation................................................95
E.1.3.4.8 Ventilation delay..............................................................96
E.1.3.4.9 Increase Ventilation based upon indoor C02/NH3...................97
E.1.3.4.0 Various/Index................................................................100
E.1.4 Humidification.........................................................................................101
E.1.5 Cooling...................................................................................................102
E.1.6 Probe average...............................................................................................105
E.1.7 Special inputs................................................................................................106
E.1.8 Alarm.....................................................................................................107
E.1.8.1 Temperature.............................................................................108
E.1.8.2 Humidity...................................................................................109
E.1.8.3 Pressure...................................................................................110
E.1.8.4 Heating.....................................................................................111
E.1.8.4.1 Ambient....................................................................112
E.1.8.4.1 Radiant.....................................................................112
E.1.8.5 Amper meter..................................................................................113
E.1.8.6 C02/NH3.......................................................................................114
E.1.8.7 Index H..........................................................................................115
E.1.8.8 Flap.........................................................................................116
E.1.8.9 External blocks...............................................................................117
E.1.8.0 Alarm test......................................................................................118
E.2 Feeding............................................................................................................119
E.2.1 Bird weighing................................................................................................120
E.2.1.1 Load cell data .................................................................................120
E.2.1.2 Plate1 calibration ............................................................................122
E.2.1.3 Plate 2 calibration............................................................................122
E.2.2 Feed weighing...............................................................................................123
E.2.2.1 External counters............................................................................123
E.2.2.2 Volumetric................................................................................123
E.2.2.3 Silo weighing..................................................................................124
E.2.2.3.1 Load cell data.................................................................124
E.2.2.3.2 Silo 1 calibration.............................................................125
E.2.2.3.3 Silo 1 calibration.............................................................125
E.2.2.3.4 Silo 3 calibration.............................................................125
E.2.2.3.5 Automatic upload...........................................................126
4
Index
E.2.3Distribution.............................................................................................127
E.2.4Lighting..................................................................................................128
E.2.4.d % Luminosity change.......................................................................130
E.2.5 External counters...........................................................................................130
E.2.6 Alarm settings...............................................................................................131
E.2.7 Alarm activation............................................................................................133
D.3 Clock.................................................................................................................134
D.4 Language...........................................................................................................134
D.5 Manual..............................................................................................................135
D.5.1 Relay outputs................................................................................................135
D.5.2 0-10V outputs...............................................................................................135
D.7 Password...........................................................................................................136
D.8 Display..............................................................................................................137
D.0 Bootstrap...........................................................................................................137
E.H USB management....................................................................................................138
G. Archive......................................................................................................................140
G.1 Alarms/Failures/Events..............................................................................................140
G.2 Climate..............................................................................................................142
G.3 Heating times...........................................................................................................143
G.4 Animals present........................................................................................................144
G.5 Feeding.............................................................................................................145
G.6 Bird weighing...........................................................................................................145
G.7 Silo upload. ..............................................................................................................146
G.8 Daily inspection........................................................................................................147
G.9 Cycle total................................................................................................................148
G.9.1 Feeding..................................................................................................148
G.9.2 Climate...................................................................................................149
H. Check control...................................................................................................................150
H.1 Climate..............................................................................................................150
H.1.1 Climate blocks...............................................................................................151
H.1.2 Probes average..............................................................................................153
H.1.3 Flap potentiometer recording...........................................................................153
H.1.4 Flaps working analysis....................................................................................154
H.1.5 Delta flap analysis..........................................................................................154
H.2 Feeding.............................................................................................................155
H.2.1 Feeding program state....................................................................................155
H.2.2 Lighting program state....................................................................................155
H.6 Inputs...............................................................................................................156
H.7 Relay ouputs.............................................................................................................157
H.8 0-10V outputs...........................................................................................................157
H.9 Load cells.................................................................................................................158
H.9.1 Plate load cells...............................................................................................158
H.9.1 Silo load cells.................................................................................................158
H.H Info...................................................................................................................159
5
Introduction
Introduction
Qfarm
The main feature of the Qfarm range is the color display screen (7”) with WVGA 800x480 dots resolution.
The user interface is easy and friendly. The easy touch screen systems gives both the typical “easy to
use” approach of a touch screen system and the strength and mechanical protection of a polycarbonate
IP55 keyboard.
At every screen the function keys display a different graphic making the program very user friendly.
Each programming step has its own help screen so the program has a “built in” instruction manual.
The Qfarm IP55 protection standards (protection against dust and water jets) make it ideal for damp
and dusty environments.
6
Introduction
Each programming step comes with its help screen so the program has a “built in” instruction manual.
Setting screenshot. When arrived to the last screenshot the display looks like this:
Input the value by using the keys or pressing on the numeric keyboard .. .......
7
Introduction
The main Qfarm feature is that you can fully set and customize the house working configuration.
This is easily done connecting the Qfarm to a PC thru the Qfarm Lab software.
The Qfarm can manage up to 112 inputs, 108 on/off outputs, N. 44 0/10V outputs.
Qfarm Lab programming software has a step-by-step procedure with graphics and notes which enables
you to define and configure the working parameters of the house.
Once the configuration has been completed, Qfarm Lab will print out the list of the components along
with their wiring diagram.
Each complete house configuration is saved to a “program file” which is stored in the PC and transferred
to Qfarm by USB pen drive. Program files can be recalled from Qfarm and edited at any time.
The program settings (temperature, relative humidity, etc.) and all the settings which are related to
the house functionning are directly set by the Qfarm.
The Qfarm programming is assisted by HELP screenshots; while programming only the variables
previously set by PC are shown. (i.e. If Heat 1 is the only option selected, the further heating options
will not be shown. Same rule applies to flaps, cooling, ventilation, etc.).
Summing up:
- The house configuration (number and type of Heaters, flaps, ventilators, etc.) is set by PC and
uploaded to Qfarm via the Qfarm Lab software.
- The program settings related to the functionning of the system (temperature set, Relative
Humidity set, etc.) is done directly on the Qfarm.
Data transfer
Communication with external world is by USB pen drive.
The main programming parameters, the archive downloads and software updates can be made by PC
connection via the USB pen drive (see par. E.H).
USB socket
8
Introduction
Configuration by P.C.
The Settings which characterize the system (number and type of heating, number and type of flaps,
ventilation’s type, etc.) will be set from PC and uploaded on Qfarm module by the Qfarm Lab
software.
9
VIEWING
Home
It’s the main reference screenshot of Qfarm.
It’s the main reference screenshot of Qfarm which display the main system parameters.
It pops up when you switch the unit on or when you press the key
The various screenshots and some settings too are displayed according to the basic setting made by
the Qfarm Lab configuration software.
From the Home page you can go to the Zoom page (keys . ....... ).
10
VIEWING
See paragraph
G.2
> Index T.
Th e p erc eiv ed tem p e ratu re
(Index) is calculated according
to the temperature/ Relative
Hu mid ity co rr ela tio n t ab
uploaded by Qfarm Lab.
To activate Index mode
see par. E.1.3.4.0
11
VIEWING
If Index is active
(see E.1.3.4.0) In Air exchanges On:
remaining time to end
of On.
Ventilation details
Block status Active= one of blocks are activated. Press H to see which block is activated.
Current ventilation Type of ventilation which is currently working (Climate A or B). It’s displayed
only if a double ventilation option is activated and it shows which one.
0-10V Ventilation When using 0-10 V ventilation it shows the output value.
Dehumidification set %RH value over which Dehumidification is activated (see par. E.1.3.4.1).
Air exchange
Air exchange It shows if air-exchange mode is active (ON) or not (Off).
Air exchange time Duration of Air Exchanges. It sums up pause and working time.
12
VIEWING
If Index is active
(see E.1.3.4.0)
Remaining time to
end of On.
Remaining time to
end of Off.
Ventilation details
Dehumidification set %RH value over which Dehumidification is activated (see par. E.1.3.4.1).
Air exchange
13
VIEWING
14
VIEWING
15
VIEWING
3. Zoom on flap
Path: Home>
Name of Flap
(customizable)
See paragraph
D.1 3.F G.2 H.1.1
Go to next page
(if number of Flaps is > than 8)
Pressure drop Outdoor/indoor static pressure difference as felt by the pressure sensor.
Block status Active= one of blocks are activated. Press H to see which block is activated.
16
VIEWING
Name of Heater
(customizable)
Go to next page
(if number of Heaters is > than 8)
Block st at us Active= one of blocks are activated. Press H to see which block is activated.
17
VIEWING
Block status Active= one of blocks are activated. Press H to see which block is activated.
18
VIEWING
Block status Active= one of blocks are activated. Press H to see which block is activated.
19
VIEWING
20
VIEWING
% of weight
measurement in
the +/- 10% from
average weight
21
VIEWING
8. Zoom on feeding
Path: Home>
ON= ON=
hours of current meal hours of current meal
22
VIEWING
Auger off
Auger on
Hopper full
Auger off
Meal either when the
whole Programmed
Hopper empty meal has b ee n
Auger on
distributed or when it’s
not Meal hours.
0. Zoom on silos
Path: Home>
See paragraph
G.7 H.2.1
23
C. Alarm
C. Alarm
The icon displayed on top of key gives the situation of the alarm: that iocn is also displayed on the
Alarm silenced (but ready to start again in case of new alarm conditions).
General alarm is excluded by external selector. The Qfarm alarm functionality is unchanged.
The fact that the external alarm circuit was shut off it’s displayed and recorded in the archives.
The alarm exclusion can be signaled by a buzzer (see par. E.1.8.9.5> Buzzer alarm exclusion).
Active Alarm
Silent Alarm
Alarm is ON:
Max 10 alarms are simultaneously displayed (for the complete list see par. G.1).
Note: when alarm is Active it’s displayed and recorded and the alarm relay is activated.
when alarm is Silent it’s displayed and recorded but the alarm relay is not activated.
24
C. Alarm
Using this procedure you can silence the current alarm: to confirm.
When a new alarm is activated the icon of the alarm key goes back to .
Using this procedure you can reactivate the current alarm (the alarm would be reactivated should a new
alarm be triggered): to confirm.
Using this procedure you can restart the feeding/water system following the activation of a stop feeding
alarm (see par. E.2.6): to confirm.
25
C. Alarm
* *
*
*
* *
26
C. Alarm
27
D. Settings
D. Settings
Path: Home> Settings
All the end-user parameter settings which are related to the system functionning are in this section
(from Settings you can directly access from any Zoom Screenshot).
You can directly go to setting from every Zoom screenshot by the key .
28
D. Settings
D.1 Climate
Path: Home> Settings> Climate
D.1.H
This screenshot is displayed whenever the Normal Ventilation has been activated.
Once a calendar function is activated the “calendar activated” icon is displayed on the programming page
29
D. Settings
D.1.H
This screenshot is displayed whenever the M3/h/Kg Ventilation has been activated
Once a calendar function is activated the “calendar activated” icon is displayed on the programming page
30
D. Settings
Duration of change Duration of the temporary change. When set to 23:59 the change(s)
(Range: 0h.00m...23h.59m) will remain active until the next starting cycle is carried out (D.0).
‘Ventilation’ set change Variation of the ventilation set. If ‘Ventilation set’ (D.1.2) is set to
(Range: -5.0°...0.0°...5.0°) 25°, entering +1.0° will increase the operating ventilation set to 26°.
‘Heating’ set change Variation of the heating set. If ‘Heating set’ (D.1.1) is 23°, entering
(Range: -5.0°...0.0°...+5.0°) +1.0° will increase the operating heating set to 24°.
‘Air exchange’ set change Variation of the air exchange set (minimum ventilation in M3/hr/kg).
(Range: -50%...0%...+100%) The entered percentage change is a percentage of the current air
exchange setting.
Example, if ‘Air exchange’ (D.1.3) is set to 10%, entering a change
of +20% will increase the operating air exchange to 12%
It is possible to input a temporary change (negative or positive) in these sets for a prefixed timing.
After that the changed set will go back to initial value.
When the temporary change set is activated (by clicking on Active key) the remaining time of duration
of change will be displayed. By pressing the End key the change of set will be stopped.
31
D. Settings
D.2 Animal accounting (only if M3/h/Kg Ventilation or Feeding has been activated).
D.2.F
The setting of the number of animals works in real time with the animals accountancy (the first entry
of the day value is = 0 and afterwards you will find the setting value previously entered, which can be
edited anytime): it’s archived on 24:00.
In case uncorrect numbers were entered during previous days of cycle, the program allows negative
numbers to be introduced as correction.
Once set the total number of animals at cycle start up (this step is made in the Starting cycle see par.
D.0) it’s important to set number the dead or removed animals on a daily basis so that the program can:
- In M3/h/Kg Ventilation, the minimum ventilation is calculated on the present number of animals.
- In Rationed Feeding distribute the exact amount of feed.
A change in the number of animals will automatically recalculate the feed to be distributed, even if
the meal is running.
*
In case extra animals were added, in order to adjourn the conversion you should add the feed which
has been previously consumed by these animals.
To do so see Special meal>Manual feed supply (see par. D.3.2.4).
32
D. Settings
D.2
Eggs collected today type A Eggs collected today type A.
(Range: -999999...0...999999)
The setting of the number of eggs accounting in real time with the animals accountancy (the first
entry of the day value is = 0 and afterwards you will find the setting value previously entered, which
can be edited anytime): it’s archived on 24:00.
In case uncorrect numbers were entered during previous days of cycle, the program allows negative
numbers to be introduced as correction.
33
D. Settings
34
D. Settings
continue untill
meal 15
You can program up to 15 daily meals (digit 'Separator' key to separate hours from minutes).
The first meal can go further 24:00: in this case, when the meal starts ‘day of cycle’ is increased by
one unit and it’s not possible to go back to the previous day.
Note: by setting a 00:00 period the following meal (if any) will not be executed.
If the setting of the period meal are contradictory, feed distribution will not take place and a ‘Wrong
time’ message will be displayed.
By this programming step you can give a different % of feed at each feed meal.
The sum of the active meals (in which a timing has been selected) must be 100% and should not contain
any 0%. On contrary case the program equally divide the % in equal % parts (in Zoom on feeding are
shown the % meal in use).
35
D. Settings
continue untill
period 15
You can program up to 15 daily periods (digit 'Separator' key to separate hours from minutes).
The first period can go further 24:00.
Note: by setting a 00:00 period the following period (if any) will not be executed.
If the setting of the period hours are contradictory, period will not take place and a ‘Wrong time’
message will be displayed.
36
D. Settings
continue untill
period 15
You can program up to 15 daily periods (digit 'Separator' key to separate hours from minutes).
The first period can go further 24:00.
Note: by setting a 00:00 period the following period (if any) will not be executed.
If the setting of the period hours are contradictory, period will not take place and a ‘Wrong time’
message will be displayed.
*1
The distribution of water is never terminated, as the calculation of the water/feed ratio is coherent
only after a meal.
37
D. Settings
continue untill
period 15
You can program up to 15 daily periods (digit 'Separator' key to separate hours from minutes).
The first period can go further 24:00.
Note: by setting a 00:00 period the following period (if any) will not be executed.
If the setting of the period hours are contradictory, period will not take place and a ‘Wrong time’
message will be displayed.
Idem Timer 1
38
D. Settings
Feed to be given You can enter the desired quantity of feed both before the cycle
(Range: 0kg...100000kg) starts and in the early days of the cycle (in the latter case the
running meal must have finished or the feeding curve of the day in
Gr/bird is = 0).
You can use this procedure to add feed to the end of the meal.
This extra feed is both accounted in feed consumptions and recorded
in Archive>Feeding>Supplementary meal.
After setting the Kg of feed to be given, press Enter to start the
procedure.
Press Delete to stop the procedure, press Home to exit without
stop the procedure (it will continue until the distributed of the
programmed feed is over).
39
D. Settings
You can fix the time window of the days in which the Gr/Bird to be distributed are fixed. In this period
the feed distribution is done disregarding the value set by the feeding calendar, so that the feed
quantity given is constant.
Start day of fixed meal This is the day when the program switches from the feed daily
(Range: 0...999) curve to the fixed meal.
End day of fixed meal This is the last day of the fixed meal.
(Range: 0...999) Afterwards the program goes back to the daily feed curve.
As standard setting the meal is 9999g (at will) from day 0 to day 200.
Change this setting to switch to the rationed meal according to growth curves (see par.D.5).
I.e if from day 20 you want to switch to rationed feed you have to set End day of fixed meal=19.
Feed manually distributed but has not been weighed in the silos.
The setting of Manual feed supply works in real time with the birds accountancy (the first entry of the
day value is = 0 and afterwards you will find the setting value previously entered, which can be edited
anytime): it’s archived on 24:00.
In case uncorrect numbers were entered during previous days of cycle, the program allows negative
numbers to be introduced as correction.
Manual feed supply Amount of feed manually distributed that has not been weighed in the silos.
(Range: -32000kg...0kg...32000kg) This amount is added to the total amount of feed distributed during the day.
This setting operates in real time, at the begining of the day will be reset
o 0, during the day the figures entered will be added together and the total
for today will be shown.
If incorrect data of previous day were entered it is possible to enter negative
data to correct the error.
Consumption is recorded and stored in Archive>Feeding>Manual feed supply
(see par. G.5).
40
D. Settings
Medicated water to be given Quantity of water to be dosed into the medicated water tank (this is
(Range: 0Lt...10000Lt) included in the water consumption).
Enter the number of litres to be dosed then press the Enter key.
Press Delete to stop the procedure, press Home to exit without stop
the procedure (it will continue until the water tank is empty).
Medicated working:
when starting the medication mode, the Water line valve will be closed and the Fill Medication tank
valve is kept open until the tank has reached the required level.
The starting of water pump to download the tank (Empty medication tank) will be operated according
to the settings in Medication mode (see par. E.2.3):
0= the download water pump starts as soon as the medicated water level has been reached in the tank.
1= the download water pump starts 1 minute after the upload of water into the tank has been started.
The water pump works until is switched off by the tank level sensor* (Water tank empty sensor
contact) then the pump is switched off and the Water line valve is opened again.
* At pump start up (Empty medication tank) the intervention of the tank level sensor (Water tank
empty sensor contact) is delayed by 2 minutes to avoid system fluctuations.
You program the day of cycle and the time you want to start the fast.
Day of month of start fast Day of the current month you want to start fast.
(Range: 1...31)
Fastworking:
At fast start up, silos spyral and feeding lines are switched off. Lights are switched on (if required).
Water is turned on (during off hours). After some time feeding line can be started on again for some
time to empty the system (see par. E.2.3 Off timer mangers in fast - On timer mangers in fast).
The fast activated mode is given by the ALARM key being on. You go out from fast following the
Restart feed system procedure (see par. C.F). At that moment the daily meal is being distributed
(if in meal hours) otherwise meal will not be distributed anymore (in this case meal can be manually
distributed according to the First feed upload/Supplementary meal, see par. D.3.2.1 procedure).
When Hour of start fast = 00:00 fast is not performed. When fast is over the Hour of start fast is
automatically set to 00:00. A new cycle will reset these values.
41
D. Settings
D.3.3 K recording
Path: Home> Settings> Feeding> K recording
Active only in a volumetric feed distribution system (no Silo’s load cells in the system).
K calculation procedure (start) Press Enter to run the feed auger for 30 seconds, collect the feed
(Range: 30”) in a container and weigh it.
ATTENTION: whilst the auger is running the hopper limit switch is
NOT ACTIVE!
K calculation procedure (end) Enter the weight, in kilos, of feed the auger moved during the 30
(Range: 0.0kg...5.0Kg...300.0kg) second run time. Based upon this setting the feed distribution
system converts the auger running time into kilos of feed distributed
to the birds.
By activating this procedure the feed distribution will be stopped (if it’s on); by pressing Enter it starts
for 30 sec then stops and the next screenshot is displayed (the one where you set the Kg of feed
downloaded in 30 sec) then by pressing Enter the distribution starts again (if it has to).
The input value of KG is archived in par. E.2.2.2 (and can also be directly entered).
During the auger working the hopper limit switch input is NOT ACTIVE !
Always check hopper is not already full.
Active only in a volumetric feed distribution system (no Silo’s load cells in the system): by this procedure
you can manually record the silos uploads, so they can be archived (Archive>Upload>Silos).
When silos have load cells the silos uploaded is automatically handled, recorded and archived.
Silo upload Weight of feed loaded in the silo. Using this procedure you can
(Range: 0kg...32000kg) manually enter the amount of feed loaded into the silo, so they can
be archived (Archive>Upload Silos).
42
D. Settings
In case of Type of weight capture= Automatic (E.2.1.1.H.0) the following settings will be displayed:
In case of Type of weight capture= Target (E.2.1.1.H.0) the following settings will be displayed:
Plate 1 target weight variation In case growth is not according to the target weight as programmed
(Range: -80%...0%...80%) in the calendar (Home>D>5>1>E>2-3), this % discrepancy enables
to correct the capture weight without having to correct the growth
curve.
Plate 2 target weight variation In case growth is not according to the target weight as programmed
(Range: -80%...0%...80%) in the calendar (Home>D>5>1>E>2-3), this % discrepancy enables
to correct the capture weight without having to correct the growth
curve.
In case of cycle with females + males, when all females are taken away the program will automatically
switch to the Male cycle and the Females weighing plate will became the 2nd Male: the bird weighing
unit which was set on Females starts weighing Males from the beginning of the next day (for this step
the actual capture Male weight is automatically copied on the new bird weigh unit).
43
D. Settings
D.5 Calendar
Path: Home> Settings> Calendar curves
The calendar program works in a way that allows to input data on several points (up to 20) which
represent the days of live of animals.
The curve is then automatically calculated by adjacent points by linear interpolation.
To activate the CLIMATE section of calendar (Heating, Ventilation, etc) see par. D.5.2.
The FEEDING section of calendar is always active. Unless the fixed meal is activated, see par. D.3.2.3.
In this case by de-activating the fixed meal, the calendar is automatically activated.
44
D. Settings
Showing
graphic curves By pressing you go to next
step (continue to point 19)
By pressing you go
to Feeding curve
Showing
graphic curves By pressing you go to next
step (continue to point 19)
By pressing you returns
to Climate curve
To activate the CLIMATE section of calendar (Heating, Ventilation, etc) see par. D.5.2.
The FEEDING section of calendar is always active. Unless the fixed meal is activated, see par. D.3.2.3.
In this case by de-activating the fixed meal, the calendar is automatically activated.
45
D. Settings
CLIMATE CALENDAR
Age of birds *1 Day of life of bird at this point of the growth curve.
(Range: 0...999) Cannot be changed (=0) at point zero of curve.
Air exchange Air exchange set at this point of the growth curve.
(Range: 0%...3%...100%)
m3/h/Kg minimum ventilation m3/h/kg set at this point of the growth curve.
(Range: 0.10...0.90°...5.00)
Last point of curve If YES, beyond this day, all the values at this point are
(Range: No...Yes) kept constant for the remaining days.
It's not present at point zero of curve.
FEEDING CALENDAR
Age of birds *1 Day of life of bird at this point of the growth curve.
(Range: 0...999) Cannot be changed (=0) at point zero of curve.
Females target weight Females target weight at this point of the growth curve.
(Range: 0gr...42gr...50000gr)
Males target weight Males target weight at this point of the growth curve..
(Range: 0gr...42gr...50000gr)
Females Gr/bird feed Females feed quantity, in grams/bird, at this point of the growth
(Range: 0gr...9gr...50000gr) curve*3.
Males Gr/bird feed Males feed quantity, in grams/bird, at this point of the growth
(Range: 0gr...9gr...50000gr) curve*3.
Maximum luminosity % (FFU) Maximum luminosity % at this point of the growth curve.
(Range: 0%...100%)
Last point of curve? If YES, beyond this day, all the values at this point are
(Range: No...Yes)
*1 kept constant for the remaining days.
It's not present at point zero of curve.
*1
These settings can be set either on the Climate page or on the Feeding page (their value will be copied
from one setting page to the other).
*2
See par. E.1.3.4.1
*3
By setting 9999 the feed distribution is given at will until the first day when the value is different
from 9999 (rationed feed).
*4
By setting 0.00 the water distribution is given at will (water will be distributed without limitation at
set time).
46
D. Settings
Once a calendar function is activated the “calendar activated” icon is displayed on the programming page
Example of Ventilation Set is input from calendar and
calendar activation it’s not editable in Setting
47
D. Settings
The change of the set of the Heating implies changes in other settings related to this set, according to
the following scheme:
The change of the set of the Ventilation implies changes in other settings related to this set, according
to the following scheme:
01 Flap
Continue relative set
until to 16 Flap
relative set
Flap temperature
of the relative probe
48
D. Settings
ATTENTION
Pressing Enter will start a new cycle and delete all information from the previous cycle!
Cycle must be started up in order to enable the feed distribution and bird weighing functions!
Important: At the beginning of a new cycle, the program automatically performs the following operations:
- resetting of all filings relevant to the previous cycle.
- recording of the weight of the silos (filed as Silos upload see par. G.7).
49
D. Settings
Once the start up of cycle has been confirmed the screen will display this:
Age of birds Age of the birds, in days, introduced at the start of the cycle.
(Range: 0...999)
Weight of females Average weight, of female birds, at the start of the cycle.
(Range: 0gr...42gr...50000gr)
Weight of males Average weight, of male birds, at the start of the cycle.
(Range: 0gr...42gr...50000gr)
*
When cycle is started with "Mixed birds" (males + females are not separated) and 2 weighing plates
are installed, you must input a number of males and a number of female birds, even if the real number
is unknown. Just make sure the total number of birds is correct.
To set scales for "Mix" working as above see E.2.1.1.H.0 (Type of weight capture= Target).
50
D. Settings
Pre-starting cycle.
You can start the cycle before the incoming of animals so you can get implement the following functions:
- Pre-heating of ambient. The Heating is enabled: the working set is the one input in Heating,
(see par. D.1) this is not the one of the calendar, which (if activated) is operational at cycle start up only.
During this phase only the heating is working (Ventilation is off).
- First supply of feed as per procedure described in Settings>Feeding>Special meal>First feed upload
(par. D.3.2.1), the mangers can be filled up.
When Pre-starting cycle is running will be displayed on the right upper corner of
the screen.
Then, when the birds are incoming into the shed you should perform a Starting cycle procedure (see
previous paragraph*) the Kg of feed previously distributed are displayed in the settings First meal
distribution (this amount can also be edited).
The working time of the heating system and the total quantiy of feed which was distributed during the
pre-start of cycle are accounted in the data of the first day of cycle.
*Getting into the pre-start of cycle (see previous paragraph) will activate the display of the following
page, to remind the pre-start is running.
51
E. Installation
E. Installation
Path: Home> Installation
E.1 Climate
Path: Home> Installation> Climate
52
E. Installation - Heating
Foreword
According to what was set by Qfarm Lab, the Qfarm can control:
The Temperature Settings of the Heating (marked with Heating x relative set) refer to the set Heating
programmed in Settings > Climate (par. D.1): when changing the main function set (Heating), the
sub-functions change accordingly. This Set can be set by Calendar (par. D.5.1).
For example with a set Heating= 20.0° and a Heating 1 relative set = 1.0° the set of temperature
working of the Heating 1 will be of 21.0° (20.0° + 1.0°).
*In case of Heat Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
53
E. Installation - Heating
E.1.1.1 Ambient
Path: Home> Installation> Climate> Heating> Ambient
Temperature differential
Heating differential (only for Normal functioning).
(Range: 0.0°...0.2°...30.0°)
Derivative proportional
(Range: 0.0°...0.2°...30.0°) Heating proportional
(only for Derivative functioning).
0-10V proportional
(Range: 0.0°...0.2°...30.0°) 0-10V heating proportional
(only for 0-10 V functioning).
*
The name of the heaters can be customized (using the software Qfarm Lab).
For the minimum temperature alarm setting see Alarm> Heating> Ambient (par. E.1.8.4.1).
54
E. Installation - Heating
Heating
ON differential
HEATING 1
ON-OFF
Example
- Heating = 28.0° (programmed in Settings>Climate par.D.1)
- 01 Heating relative set = 1.0°
- Differential = 0.2°
As per the above settings the heater starts at 29.0° (28.0+1.0) and stops at 29.2° (28.0+1.0+0.2).
Same as 02 Heating ... 16, but referred to the set 02 Heating relative set ... 16 Heating relative set.
FF
0.2° Hysteresis
O
entrance/escape
proportional
Derivative
Derivative
FF
O
O
N
FF
Derivative
O
0.2° Hysteresis
entrance/escape
N
O
In the derivative mode the heating working pattern is according to the indoor temperature trend.
We suggest the following setting:
Derivative proportional = 1.0°
Derivative = 0.2°
Same as 02 Heating ... 16, but referred to the set 02 Heating relative set ... 16 Heating relative set.
10V
0-10V proportional
7,5V
0-10V
HEATING 1
5,0V
2,5V
Same as 02 Heating ... 16, but referred to the set 02 Heating relative set ... 16 Heating relative set.
55
E. Installation - Heating
Radiant relative set Temperature set of Radiant heating referred to the Set Heating
(Range: -30.0°...0.0°...30.0°) programmed in Settings>Climate (par. D.1).
0-10V Delay movement Delay when actioning 0-10V applied to any 1% step
(Range: 0.0”...1.0”...10.0”) (only for 0-10V functioning).
For the minimum temperature alarm setting see Alarm> Heating> Radiant (par. E.1.8.4.2).
56
E. Installation - Heating
FLOATING HEATING
100% 100%
OFF time calculation *
ti.On ti.On
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
*
When the system works in Floating proportional mode, the On working time is fixed, where as the
OFF time starts from a maximum value (Maximum off time) and it is gradually reduced according to
the cold and hot band width (Warm modulation band and Cold modulation band).
Example: in the middle of the Hot band (Warm modulation band), OFF time is 50% of Maximum off time.
The minimum OFF time is never below the ON time.
When in the neutral band (Neutral Band) the system is OFF.
Beyond the Warm modulation band and Cold modulation band the system is always ON.
10V
0-10V Proportional
0-10V
7,5V
HEATING
5,0V Minimum % controlled
by 0-10V Minimum
2,5V
*1
Minimum opening according to 0-10V Minimum.
0-10 increasing and/or decreasing working is delayed by 0-10V Delay movement for any 1% step.
I.e. when setting 0-10V Delay movement = 1.0" 100 secs are necessary to go from 0% to 100% of
heating.
57
E. Installation - Heating
These parameters refer to the working sets of Heating by Radiant spark ignition.
Radiant relative set Temperature set of Radiant heater referred to the set Heating
(Range: -30.0°...0.0°...30.0°) programmed in Settings>Climate (par. D.1).
Type of minimum valve N.O valve (valve opens when the power is off).
(Range: N.O...N.C.) N.C valve (valve closes when power is off).
Minimum flame block No = block is not active: heaters will be shut off as soon as
(Range: No...Yes) required temperature is reached.
Yes = block is active: heaters will be kept to minimum as soon
as required temperature is reached (heaters are always
kept on).
For the minimum temperature alarm setting see Alarm>Radiant (par. E.1.8.4.2).
Maximum delta
ON
MAXIMUM
Minimum delta
MINIMUM
OFF Radiant heater
probe temperature
The heating start up will be at the preset start up temperature (Heating+Radiant relative set): the
MAXIMUM and MINIMUM valves are being opened and the system is kept in stand-by for the
Spark waiting time*, after the ignition starts. Ignition lasts as long as the Spark ignition time.
If temperature increases by the Maximum delta value, the MAXIMUM is switched off while the MINIMUM
value is kept on. MINIMUM will be switched off if the temperature will increase by the Minimum delta
value (unless Minimum flame Block= Yes, in this case MINIMUM flame is always kept on).
* The stand-by time at start-up (MAXIMUM valve is kep on for a while, typically 15 secs) in order to
put gas pipeline in pressure (as long as the spark is not on, the safety device of heaters does not
supply gas) after that the spark time starts (typically it lasts for 45 secs).
58
E. Installation - Heating
E.1.1.3 Fan-jet
Path: Home> Installation> Climate> Heating> Fan-jet
Delta temperature Set of temperature range between high and low Fan-jet temperature
(Range: 0.0°...1.0°...30.0°) sensors.
Switch off during on ventilation Fan-jet is switched off during the ON ventilation period.
(Range: No...Yes)
Temperature band
ON*
* ON FAN-JET
FAN-JET * Controlled by
Working time and waiting time and from
ON-OFF Ventilation On with
Switch off during on ventilation= Yes
* ON FAN-JET
* Controlled by
Ventilation On with
FAN-JET Switch off during on ventilation= Yes
% 0-10V 0-10V
Minimum vent. High probe temperature -
Low probe temperature
Delta
temperature
59
E. Installation - Heating
By this conditioning you can adjust the night time Heating set of temperature. As option you can also
change the nightime Ventilation set of temperature (par. E.1.3.4.5 Conditioning Ventilation).
Night start time Time when the night time period starts.
(Range: 0h.00m...23.h59 m)
Night end time Time when the night time period ends.
(Range: 0h.00m...23.h59 m)
Night time set variation Variation of the Heating setting during the night time period (+ or -).
(Range: -30.0°...0.0°...30.0°)
Note: when setting 00:00 as start and end time, night ventilation range is excluded.
60
E. Installation - Heating
If outdoor and indoor humidity probe is connected, the dehumidification can be influenced by the
Outdoor - Indoor RH difference so when the outdoor climate is dry (compared with indoor conditions)
dehumidification works by increasing the ventilation rate (see par. E.1.3.4.1); when the outdoor climate
is humid (compared with indoor conditions) dehumidification works by operating the on-off heating.
Humidity delta Dry climate = the Ambient %RH is higher than the Maximum indoor
Indoor/Outdoor humidity ( see par. E.1.3.4.1) and the difference between indoor and
(Range: 0%...100%) outdoor %RH is higher than the Humidity delta Ind/Outd value.
In this case dehumidification starts by reducing the Ventilation Set
(ventilation is increased).
Humid climate = the Ambient %RH is higher than the Maximum indoor
humidity ( see par. E.1.3.4.1) and the difference between indoor and
outdoor %RH is lower than the Humidity delta Ind/Outd value.
In this case dehumidification starts by increasing the Heating Set
(ventilation is not increased).
Humidity delta Ind/Outd =0 the de-humidification by heating is disabled.
Heating set increase Increase of the Heating Set temperature (par. D.1) for every 1% increase
(Range: 0.0°...30.0°) of indoor humidity above the Max indoor humidity (par. E.1.3.4.1).
Maximum set increase Maximum increase of the Heating Set (par. D.1) for de-humidification.
(Range: 0.0°...2.0°...30.0°)
In case the system is working in “Ventilation by Index” mode (par. E.1.3.4.0) and with humid outdoor
conditions the ventilation works according to the reading of the ambient indoor temperature (the
“perceived temperature” reading is automatically excluded). Dehumidification is performed by increasing
the Heating Set (if linked to Index according to par. E.1.3.4.0).
Differential
ON fixed=2%
Humidity delta
For every 1% of RH in excess after the Block is activated (Maximum indoor humidity par. E.1.3.4.1),
the temperature Set of the Heating is increased of the value set in Heating set increase until a maximum
value set in Maximum set increase.
2%
ON*
61
E. Installation - Heating
Example with Delta RH = 15% Dehumidification is done by heating up to a difference of 15%, beyond
this value the heating is not working but the Ventilation set is being reduced so air changes are
increased.
Below 70% of indoor humidity (Maximum indoor humidity) the temperature set of ambient Heating
will be 22.0°, at 70% of indoor humidity will be 22.2° (22.0°+0.2°= 22.2°), due to increase of 0.2°
(Heating set increase) for every extra 1% of ambient humidity, up to a maximum increase of 2.0°
(Maximum set increase) which will bring temperature set of ambient Heating= 24.0° at 79% of indoor
humidity.
If the difference in %RH (Indoor/Outdoor) goes back to be more than 15% the increase in the Heating
Set is not used anymore but at its place the Ventilation Set is being reduced (in case the system is
working in INDEX mode, the Index functionning is reactivated).
Off heating By this conditioning the air heating (not the spark heating) is switched
(Range: No ...Yes) off whenever the Ventilation is switched on.
No = not operational.
Yes = when Ventilation is on (both Air changes and Ventilation), Ambient
Heating is switched off.
Attention: do not set this function when ventilation is in M3/h
mode. If so heating will not operate.
62
E. Installation - Flap
Foreword
According to what was set by PC, the Qfarm can control up to 16 Flaps according to following typical
actioning:
Emergency:
- Flap is closed in normal working conditions. It opens up only as emergency unit (par. E.1.8.8).
63
E. Installation - Flap
E.1.2.1 Depressiometer
Path: Home> Installation> Climate> Flap> Depressiometer
When the flap is set to be controlled by pressure sensor, the flap position is set to give the required
negative pressure of the system (measured by the DP59/W unit).
The system can be operated in 2 ways:
a- according to the start/stop cycle of the flap gearmotor
b- by feedback potentiomenter. This is suitable when system has 2 flaps or more to be kept aligned.
In this case the flaps operate according to an advance percentage.
c- as b, but it also gives the control of temperature of the zone so to give max Delta T from different
zones.
Progress % flap movement: when the flap is fitted with a potentiometer the
(Range: 0%...3%...100%) flap will move this % after each Waiting time (only with Flap with
potentiometer).
Minimum opening % Flap minimum opening with (only with Flap with potentiometer).
(Range: 0%...100%)
1 Pascal 1 Pascal
ON * ON *
FLAP FLAP
CLOSED OPEN
OFF OFF
Pressure set
Air depression
(Pascal)
* Depressiometer Flap=
controlled by Waiting Time and Working Time.
Depressiometer Flap with potentiometer=
controlled by Waiting Time - Progress - Minimum opening.
Delta T= depressiometer with potentiometer + temperature probe=
conditioned by: Waiting Time - Progress - Minimum opening - and by the Delta. T conditionings
(see E.1.2.5.5).
When set Flap aligned (with feedback potentiometer) the flap will be aligned to the reference flap
(as per Qfarm Lab settings).
64
E. Installation - Flap
E.1.2.2 Associative %
Path: Home> Installation> Climate> Flap> Associative %
Associative (A)
Path: Home> Installation> Climate> Flap> Associative %> Associative (A)
With set the Associative Flap working the Flap associative A is positioned to the various % of opening
according to the step of ventilation inserted (with feedback potentiometer).
% Flap A Step0 Step1 Step2 Step3 Step4 Step5 Step6 Step7 Step8 Step9 Step16
posit. posit. posit. posit. posit. posit. posit. posit. posit. posit. posit.
Position
Ventilation STEP STEP STEP STEP STEP STEP STEP STEP STEP STEP Continue STEP
Step 0 1 2 3 4 5 6 7 8 9 until to.. 16
65
E. Installation - Flap
When Natural Air Flaps is selected, flaps works according to the signal given by the indoor temperature
probe.
The Temperature Settings of the Natural Flap (marked with Flap x relative set) refer to the set Ventilation
programmed in Settings > Climate (par. D.1): when changing the main function set (Ventilation), the
sub-functions change accordingly. This Set can be set by Calendar (par. D.5.1).
For example with a set Ventilation= 25.0° and a Flap.1 relative set = 2.0° the set of temperature working
of the Flap 1 will be of 27.0° (25.0° + 2.0°).
*
The name of the flaps can be customized (using the software Qfarm Lab).
01 Flap
Continue relative set
until to... 16 Flap
relative set
*In case of Heat Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
66
E. Installation - Flap
E.1.2.3.2 Floating
Path: Home> Installation> Climate> Flap> Natural flap> Floating
E.1.2.3.2.1 Flap 1
Path: Home> Installation> Climate> Flap> Natural flap> Floating> Flap 1
These settings establish the working of the Natural Flap with driving Floating or Derivative (the driving
Floating or Derivative allows to obtain a regulation on the Flaps without the help of the feedback
potentiometer) according to the indoor temperature.
Neutral band No Flap 1 action neutral band. Only with Floating flap.
(Range: 0.0°...0.2°...30.0°)
These settings (as the functionning diagrams shown here below) refer to Flap 1; the settings of the
other flaps can be programmed by getting to “settings”.
67
E. Installation - Flap
100% 100%
OFF time calculation *
ti.On ti.On
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
* When the system works in Floating proportional mode, the ON working time is fixed
(On Time), where as the OFF time starts from a maximum (Maximum off time) and it is
gradually reduced according to the cold and hot band width (Closed band and Open band).
Example. in the middle of the Closed band, OFF time is 50% of Maximum off time.
The minimum OFF time is never below the On Time.
When in the neutral band (Neutral band) the system is OFF.
Beyond the Closed band and Open band the system is always ON.
ON OPEN
0.2° Hysteresis
Flap 1 probe temperature
entrance/escape
Max value + 0.2°
A
Proportional
O Derivative
*O
FF
A
*O
FF Derivative
N
N O
O
C
*
ON CLOSED
* ON A and ON C : ON relay is controlled by the cycle given by On time and Maximum off time.
In Derivative mode the flap works according to the “trend” of the indoor temperature.
We suggest the following settings: Proportional = 1.0° Derivative = 0.2°
68
E. Installation - Flap
E.1.2.3.3 Proportional
Path: Home> Installation> Climate> Flap Natural> Proportional
E.1.2.3.3.1 Flap 1
Path: Home> Installation> Climate> Flap Natural> Proportional> Flap 1
When flap working is set on Natural 0-10V or with Feedback Potentiometer, flap works in natural
ventilation mode and is actioned according to the temperature probe in a proportional way according
to the position of the flap (when controlled by potentiometer a feedback potentiometer is required).
These settings (as the functionning diagrams shown here below) refer to Flap 1; the settings of the
other flaps can be programmed by getting to “settings”.
100%
Proportional 100% *3 10V
Proportional 10V *3
75% 7,5V
50% 5,0V
Set referred to the Ventilation set Set referred to the Ventilation set
01 Flap relative set programmed in Settings>Climate 16 Flap relative set programmed in Settings>Climate
*1
In order to minimize the flap adjustments, a “no work” proportional band can be set at proportional
band of not driving (Neutral band).
For example with Neutral band= 0.2° the flap driving will be made every 0.2° of variation of the
temperature probe. When increasing this value the number of on-off cycles is reduced but the
accuracy of the system is reduced too.
*2
Minimum opening according to Minimum opening.
*3
Maximum opening according to Maximum opening.
When flap is controlled by feedback potentiometer (PT option), the accuracy of the system is given by
the accuracy of the flap mechanical system.
The system checks and corrects this deviation to optimize the system.
To obtain the complete closing and opening flaps, when set 0% is required and 100%, closing and
opening relay stays always in "on" condition in order to stop the flap with safety's limit-switch.
69
E. Installation - Flap
ATTENTION: before running this calibration procedure ensure that the flap operates correctly in
manual mode.
>
>
This recording procedure refers to Flap 1 only; the recording of the other flaps settings can be
programmed by getting to “settings”.
The recorded values are also recorded in the “Flap recording” register (par. H.1.3).
70
E. Installation - Flap
71
E. Installation - Flap
By this conditioning the flap working pressure can be conditioned to the outdoor temperature.
This function is very important, as it allows the flap opening to be decreased during winter conditions
so that cold air is pushed upward.
Outdoor temperature set If the outdoor temperature drops below this setting the Pressure set
(Range: -30.0°...10.0°...50.0°) will be increased (as set at E.1.2.1).
Increase set pressure The amount the Pressure set is increased for every 1° the outdoor
(Range: 0P...300P) temperature drops below the Outdoor temperature value.
Differential
ON fixed=0.2°
Pressure
Set
Increase
OFF Temperatura
Esterna
For every 1° decrease of outdoor temperature when the Block is activated (Outdoor temperature set),
the Pressure set of the Flaps is increased until a maximum value set in Max Increase.
This function is very important, as it allows the flap opening to be decreased during winter.
Above 10.0° of outdoor temperature (Outdoor temperature set) the flap working depression will be 20
Pa, at 10.0° of outdoor temperature will be 22P (20P+2P= 22P), due to increase of 2P (Increase set
pressure) for every lower outdoor temperature degree, up to a maximum increase of 10P (Maximum
pressure increase) which will bring set of flap working depression= 30P at 6.0° of outdoor temperature.
72
E. Installation - Flap
E.1.2.5.2 Anemometer
Path: Home> Installation> Climate> Flap> Conditionings> Anemometer
By this conditioning the windmeter located on right or left side can condition the opening/closing of each
flap.
Left anemometer set Threshold intervention speed of the left windmeter (Km/h).
(Range: 0K...30 K...500K)
Right anemometer set Threshold intervention speed of the right windmeter (Km/h).
(Range: 0K...30 K...500K)
Wind gust minimum time Minimum duration of a gust of wind. If the duration of the gust
(Range: 0m.00s...60m.00s) exceeds this time the wind intervention will operate.
Duration of intervention Duration the intervention will operate for this time.
(Range: 0m.00s...60m.00s)
ON Controlled by
Wind gust minimum timing
Left anemometer
ON Controlled by
Wind gust minimum timing
Right anemometer
73
E. Installation - Flap
By the Conditionings the flaps can be conditioned to work according to following parameters:
Outdoor minimum block Outdoor temperature under which activates the ‘Outdoor min block’.
(Range: -30.0°...-10.0°...50.0°)
Outdoor maximum block Outdoor temperature over which activates the ‘Outdoor max block’.
(Range: -30.0°...40.0°...50.0°)
*
This feature allows to force by external selector a max step of closing/opening of flaps.
74
E. Installation - Flap
If system is set on Natural Ventilation mode and has a top-roof flap, this function enables accurate
control of temperature in the upper part of the shed so that the natural “upward” convection air path
is garanteed.
Delta intervention draft Differential of intervention between the probe of the Flap and the
(Range: 0.0°...30.0°) probe of Draft.
When the sensor feels the temperature in the upper part of the shed is lower than the roof-top flap
sensor (located inside the shed at lower level) gives a signal so the roof-vent starts closing and
temperature of upper part of shed goes up proportionally to re-create a proper upwards draft.
The max number of draft probes is 2.
Differential
fixed=0.2° ON *
DRAFT BLOCK
*
The Draft Block is activated if the temperature of the Draft probe is lower than the Delta intervention
draft to the temperature of the probe of the flap controlled by the Draft Block (it is usually the Flap
of the “roof-flap”).
With the intervention of the Draft Block the Flap controlled by this Block draft will work with the
probe of Draft (1 or 2), up to when the temperature of the draught probe won't again overcome the
temperature of the probe Flap.
75
E. Installation - Flap
Max change in opening % of Max change in opening of flap according to Delta T intervention.
(Range: 0%...20%...50%)
Delta T= 0.5°
Sampling time= 5m.00s
Max change in opening= 15%
Progress= 3% (par. E.1.2.1)
Minimum opening= 5% (par. E.1.2.1)
When the zone temperature of a flap differs by 0,5°C (+ or -) by the average temperature of the
activated flaps (for this type of system) the position of the flap is adjusted by 3%
(Progress). Opening or closing will take place according to the value of Delta T (positive or
negative). This check will be performed every 5 min (Sampling time).
Max adjustment of flap position will be + or - 15% Max (Max change in opening).
According to the Delta T adjustment flap which is (for example) 50% opened can be closed down to
min 35% or opened up to 65% max.
Anyway the flap adjustment will not force the window to close below 3% (Minimum opening).
76
E. Installation - Flap
By this conditioning the Flap % of Opening (Associative operation) can be conditioned to the outdoor
temperature.
This function is very important, as it allows the flap opening to be decreased during winter conditions
so that cold air is pushed upward.
Outdoor temperature set Outdoor temperature set below which flap opening reduction.
(Range: -30.0°...10.0°...50.0°)
Opening reduction Flap Opening reduction (calculated on the flap position) for every
(Range: 0%...100%) 1° less than the outdoor temperature set (with Associative
operation).
i.e.: when decreasing by 10% an opening already set as 20% the
total final opening will be 18%.
Differential
ON fixed=0.2°
Opening
reduction
OFF Temperatura
Esterna
For every 1° decrease of outdoor temperature when the Block is activated (Outdoor temperature set),
percentage of Flap opening (with Associative operation) is decrease of the value set in Opening
reduction, until a maximum value set in Maximun opening reduction.
When External Temperature is over 10.0° (Outdoor temperature set) flap opening will be 20% (Step 1
flap position), at 10.0° of external temperature opening will be 18% (20% - 10% of 20%= 18%) due
to 10% reduction (Opening reduction) for every lower outdoor temperature degree, up to a maximum
of 50% reduction (Maximun opening reduction, % calculated on the absolute value of Step 1 flap
position) which will bring flap to 10% opening at 6.0° of outdoor temperature.
Note: The example refers to the % of the window position at Step 1 (Step 1 flap position), but the
reduction applies to all other connected steps.
77
E. Installation - Ventilation
Foreword
According to what was set by PC, the Qfarm can control up to 16 independent and fully configurable
ventilation steps according to following typical actioning:
- On-Off.
- Fan speed control by transformer.
- Proportional by 0 -10 V for triac / inverter speed control.
- Or a combinations of the 3 systems above.
78
E. Installation - Ventilation
The Temperature Settings of the Ventilation steps (marked with Step 1 relative set) refer to the set
Ventilation programmed in Settings>Climate (par. D.1): this Set can be set by Calendar (par. D.5.1).
For example wit h a Ventilation Set = 25.0° and a Step 1 relative set = 1.0° the start up temperature of
Step 1 will be of 26.0° (25.0° + 1.0°).
Apart the Step 1, the sets of start of the whole other Step (from Step 2 to Step 16) they are referred
to the start up temperature of the previous step.
Step 2 Temperature set of this step above the previous step (Step 1).
relative set
(Range: 0.0°...1.0°...30.0°)
Step 3 Temperature set of this step above the previous step (Step 2).
set relativo
(Range: 0.0°...1.0°...30.0°)
Step16 Temperature set of this step above the previous step (Step 15).
relative set
(Range: 0.0°...1.0°...30.0°)
Ventilation differential Differential Ventilation: given a Ventilation step, it’s the difference
(Range: 0.0°...0.2°...30.0°) in temperature required to go back to the previous step.
*The reference’s temperature of the Ventilation can be also the average among the probes of the
Ventilation, the Flaps probe, and the Heating probes (see Probe Average par. E.1.6).
In case of Ventilation Index control is the temperature as felt by the animals (see Index par . E.1.3.4.0).
79
E. Installation - Ventilation
Ventilation Ventilation
differential ON *1 differential ON *1
STEP 1 STEP 2
VENTIL. VENTIL.
The same for all
the other steps
OFF *
OFF * (max 16)
*1
Ventilation steps are programmed “one by one” in sequence according to the temperature pattern
as set by Qfarm Lab.
Ventilation Rotation
When temperature is higher than the Ventilation Set, the last relays can be cyclically rotated as per
“Rotation Tab” (setting by Qfarm Lab) to the Rotation time and the Minimum rotation step and
Maximum rotation step (see par. E.1.3.2).
In this way you can cyclically shift the start up of the last ventilation step (to rotate air changes steps
see next paragraph).
80
E. Installation - Ventilation
E.1.3.2 Air-exchange
Path: Home> Installation> Climate> Ventilation> Air-exchange
Cycle duration Duration of air exchange cycle. This is the total of the on and off
(Range: 0m.00s...10 m.00s...60m.00s) operating times of the air exchange.
Exchange band Proportional Band in which the working time (ON) is calculated as
(Range: 0.0°...1.0°...30.0°) percentage of the duration of the Air Exchanges cycle.
Minimum step exchange Minimum Ventilation step in cyclic rotation during the phase of Air
(Range: 1...16) exchanges (0 = Air exchanges are not activated)*.
The cycle sequence mode is the one set by Qfarm Lab.
Maximum step exchange Maximum Ventilation step in cyclic rotation during the phase of Air
(Range: 1...16) exchanges*.
The cycle sequence mode is the one set by Qfarm Lab.
Position flap in exchange Flap position during Air exchange (ventilation step 0: during on time).
(Range: 0...1...2) 0=during Air exchange flaps are positioned as step 0.
1=during Air exchange flaps are positioned as the current active step.
2=during Air exchange the flaps are closed.
Closing flap in off time m3/h Closing Flap during ventilation Off time in m3/h.
(Range: Yes...No) Yes= during ventilation Off the flaps are closed.
No= during ventilation Off the flaps are positioned as the current
active step.
Minimum rotation step Minimum ventilation step in cyclic rotation during the phase of Cyclic
(Range: 1...16) rotation. The cycle sequence mode is the one set by Qfarm Lab.
Maximum rotation step Maximum ventilation step in cyclic rotation during the phase of Cyclic
(Range: 1...16) rotation. The cycle sequence mode is the one set by Qfarm Lab.
Continue
81
E. Installation - Ventilation
Previous step memory Yes = when 100% of step is reached, the parzialization will only affect
m3/h/kg the next step (the previous step stays at 100%).
(Range: Yes...No) No = when 100% of step is reached, the parzialization will affect
current step and the next step.
% max air changes in M3/h This is the max working percentage of the step (Steps are activated in
(Range: 0 ...100 )
% %
sequence and % of M3/h is re-calculated at each step).
This function works only with Previous step memory m3/h/kg= No.
*
Active only in Normal ventilation mode.
82
E. Installation - Ventilation
Exchange band
*1
*1 Relay output in the time
ON 100%
Maximum % controlled by
Time cycle Exchange maximum %
ON OFF ON 75%
Time cycle
50%
ON OFF ON
STEP 0 STEP 1
Time cycle
VENTIL. VENTIL.
ON OFF ON 25%
Minimum % controlled by
Air exchange % *3
OFF 0%
*1
Minimum time on the relay=
Set referred to the
Minimum on. The relationship time On Step 1 relative set
/ time Off is calculated every 0.1° of Ventilation set
the Exchange band. Ventilation temperature probe
- Below 27.0° (28.0° Ventilation Set - 1.0° Exchange band) the ventilation step will work 1 minute
every 10 minutes of the cyle (10% of Time of exchange cycle). This for any temperature below 27.0°.
- When T = 27.1 ° Step one will work 2 minutes and will pause for 8 minutes (Time of exchange cycle=
10m); for every 0.1° increase in temperature the “On working time” will increase by 1 minute and
the “Off working time” will decrease by 1 minute accordingly (being the cycle duration still 10m) to
reach 10m (100%) of “On working time” at 28.0° (Ventilation Set).
The max percentage can be limited (Exchange maximum %).
When setting Exchange maximum % = 0 the “On working time” is kept fixed as per value
Air exchange programmed in Settings>Climate (par. D.1).
*2
For example with set: Minimum step exchange = 1 and Maximum step exchange = 4 during the On
time Steps from 1 to 4 will be rotated.
If the setting was Minimum step exchange = 1 and Maximum step exchange = 1 the working step
would have been only the step 1.
*3
This value (as set in Settings>Climate, see par.C.1) can be influenced by the outdoor temperature,
see par. E.1.3.4.3.
83
E. Installation - Ventilation
OFF 0%
*1
Minimum time on the relay=
Minimum on. The relationship time On Set referred to the
Ventilation
/ time Off is calculated every 0.1° of Ventilation set
the Exchange band. Ventilation temperature probe
Air-exchange (active when ambient temperature is lower than Ventilation set): inside the Exchange
band, starting from a minimum % percentage automatically calculated (number of animals, their weight
and t he required M3 of ventilation per Kg live weight), the program will switch Step of Ventilation to
garantee the minimum calculated air flow by increasing the “ON” value proportionally to the increase
in ambient temperature, up to 100% of the step*2.
When the indoor temperature is higher than required the M 3/h/kg calculation rate is left and the
system goes into the “normal” mode (the ventilation steps are activated according to the room
temperature).
i.e. when considering the following sets:
- Ventilation = 28.0° (see par. D.1)
- Minimum variation = 100% *3 (see par. D.1)
- Time of exchange cycle = 10m.00s
- Exchange band = 1.0°
With ventilation steps of 30.000 M3/h capacity and with a minimum air flow of 3.000 M3/h the
functionning will be:
- Below 27.0° (28.0° Set Ventilation - 1.0° Exchange band), the minimum air flow is given by the first
step running in a “1 minute on” and “9 minutes off” mode (in order to get 10% of fan air flow), this
referred to any temperature below 27.0°C in order to garantee the minimum calculated air flow
(3.000 M3/h)*2.
- When T = 27.1 ° Step will work 2 minutes and will pause for 8 minutes (Time of cycle = 10m);
for every 0.1° increase in temperature the On working time will increase by 1 minute and the “Off
working time” will decrease by 1 minutes accordingly (being the cycle duration still 10m) to reach 10m
(100%) of “On working time” at 28.0° (Ventilation Set).
- Beyond 28°C (which is the Ventilation set value) the M3/h/kg is left and the “normal” functionning
mode starts as the ventilation steps are activated according to room temperature.
*2
In example when the calculated minimum air changes are more than 30.000 M3/h (i.e 36.000 M3/h)
The program can work in the two different ways:
1> Partializing step data storage m3/h/Kg= No : the 1nd and 2nd step will then run in a partial mode
and it will run at 60% capacity as it has a 60.000 M3/h overall capacity.
2> Partializing step data storage m3/h/Kg= Yes : the first fan will be kept at 100% capacity and only
the second fan will be parzialized (working at 20% partial capacity).
*3
This value (as set in Settings>Climate, see par.C.1) can be influenced by the outdoor temperature,
see par. E.1.3.4.3.
84
E. Installation - Ventilation
E.1.3.3.1 Proportional
Path: Home> Install> Climate> Ventilation> 0-10V Ventilation> Proportional
The 0-10V continuous (stepless) ventilation controls an inverter system in a stepless way.
Air-exchanges ventilation % of fan speed referred to the Step 0 working period: during the Off
(Range: 0%...10 %...100%) time, ventilation is switched off.
Operative only with Normal Ventilation.
100%
75%
50%
STEP X
VENTIL.
25%
X is the first step selected by Qfarm Lab tab with 0-10V proportional functionning,
Y is the last step selected by Qfarm Lab tab with 0-10V proportional functionning.
Proportional functionning can be either associated to one step or to more consecutive steps
(from X to Y).
*1
At the Step 0 you can activate a cycle of Air Exchanges working this way:
The % of Air Exchanges (see Settings>Climate par. D.1) settings gives the minimum percentage of
fan working time in Air Exchanges (% referred to the Cycle duration see par. E.1.3.2).
Fans will be switched on during the On working time up to % of Ventilation set in Air exchange
ventilation.
During the Off time fans are switched off.
85
E. Installation - Ventilation
Application example:
In the example described in the tab the system works by 0-10V regulation on Step 1 and by On-Off
ventilation on next 6 Steps.
The 0-10V ventilation is switched on at the start temperature as programmed on Step 1 in the 0-10V
tab (in this example step 0 is active only as Air Exchanges mode) and will be increased proportionally
to 100% during the whole Step 1. Afterwards the output will be kept at 10V.
Note: at Step 0 the 0-10V ventilation activates the air changes mode according to the percentage as
programmed in Air exchange ventilation (only with “Normal ventilation”).
100%
75%
50%
STEP X
VENTIL.
25%
0%
Ventilation
temperature probe
X is the first step selected by Qfarm Lab tab with 0-10V proportional functionning,
Y is the last step selected by Qfarm Lab tab with 0-10V proportional functionning.
Proportional functionning can be either associated to one step or to more consecutive steps
(from X to Y).
86
E. Installation - Ventilation
E.1.3.3.2 Steps
Path: Home> Installation> Climate> Ventilation> 0-10V Ventilation>> Steps
Type 2 (0-10V output = RAMP on Qfarm Lab, does not apply to m3/h/Kg ventilation).
With one or more controllers, you can get more ventilation steps in 0-100% ventilation mode by
increasing the number of fans of each single step.
For each step, the minimum start up % can be selected.
I.e. 3 steps with 6 fans:
on first step, 2 fans are controlled from minimum % to 100%. When step 2 is activated, the 4 fans
are activated at 50% minimum rate and gradually increased to 100%. When step 3 is activated, all
the 6 fans are activated at 66% minimum rate and gradually increased to 100%.
Type 3 (0-10V output = ASSOC on Qfarm Lab, does not apply to m3/h/Kg ventilation).
Allow to obtain more ventilation step (inverter or triac) at fixed %.
Step 0 exchanges % of fan speed referred to the Step 0 (in On working period): during
(Range: 0%...100%) the Off time, ventilation is switched off.
Operat ive only wit h Normal Ventilation.
Maximum forcing Time of ventilation forcing (100%) when moving to the next step
(Range: 0m.00s...60m.00s) (works both in decreasing and increasing ventilation patterns): by
this step you can clean the fan mesh of the exhaust chimney fans.
87
E. Installation - Ventilation
80%
70%
50%
40%
STEP 1 STEP 2 STEP 3
30%
VENTIL. VENTIL. VENTIL.
20%
10%
0%
80%
70%
50%
40%
STEP 1 STEP 2 STEP 3
30%
VENTIL. VENTIL. VENTIL.
20%
10%
0%
With Normal Ventilation, at the Step 0, it is possible insert a cycle of Air exchanges and work in this way:
the setting % of the Air Exchanges (see Settings>Climate par. D.1) establishes the minimum percentage
of time of ignition of the fans in Air Exchanges (% referred to the Time of exchange cycle see par.
E.1.3.2), that they will be inserted during the On time to % of Ventilation set in Step 0 exchange:
during the Off time ventilation is switched off.
With m3/h/Kg Ventilation ‘Air Exchanges’ are not actived (like upon explained) because minimum
ventilation is variable and determined from m3/h/Kg calculation.
The 0-10V steps have the following peculiarity; when activated (regardless if value is increasing or
decreasing), 100% ventilation rate can be forced for the duration given in Maximum forcing.
This is useful when trying to clean the mesh of chimney exhaust fans.
88
E. Installation - Ventilation
Rotating Ventilation
When the temperature is higher than the Ventilation set, the last active relays can be cyclically rotated
according to the “Rotating actioning table” (set by Qfarm Lab), to the Rotation time and to the Minimum
rotation step and Maximum rotation step (see par. E.1.3.2).
90%
80%
70%
66%
60%
50%
50%
40%
STEP 1 STEP 2 STEP 3
30%
VENTIL. VENTIL. VENTIL.
20%
10%
0%
Step 0 Step1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step16
Exchange Ventil. Ventil. Ventil. Ventil. Ventil. Ventil. Ventil. Ventil. Ventil.
STEP STEP STEP STEP STEP STEP STEP STEP STEP Continue STEP
0 1 2 3 4 5 6 7 8 till to.. 16
89
E. Installation - Ventilation
90
E. Installation - Ventilation
This function allows increase of ventilation rate (by reducing the Ventilation temperature Set) whenever
%RH goes beyond desired value: so the ambient is de-humidified.
Maximum indoor humidity %RH value over which Dehumidification is activated, so indoor
Calendar humidity is decresed by increasing the ventilation rate.
(Range: 0%...80 %...100%) When activating the calendar setting the message of activation is
displayed. In this case the set cannot be modified on this setting
(see par D.5.2).
Ventilation set decrease Decrease of the temperature Ventilation set (see par. D.1) for every 1%
(Range: 0.0°...30.0°) of % RH exceeding the Maximum indoor humidity value*2.
Make sure the Ventilation Differential (par. E.1.3.1.F.7) is higher or
equal to this setting.
Max ventilation set decrease Maximum decrease of the Ventilation set in Dehumidification*2.
(Range: 0.0°...2.0°...30.0°)
Differential
fixed=2% ON*
* Decrease of Ventilation set controlled
by Max ventil. set decrease
VENTILAT.
SET
DECREASE
OFF Ambient
humidity
For every 1% in excess of ambient humidity when the Block is activated (Maximum indoor humidity),
the temperature Set of the Ventilation is decrease of value as set in Ventilation set decrease, until a maximum
value set in Max ventilation set decrease. This reduction also applies to the Heating set (see “Heating
decrease according to indoor % Rh”, par. E.1.1.4.3).
If the outdoor RH probe is installed, the Decrease Ventilation Set is influenced by the outdoor RH
(see par E.1.1.4.2).
Below 65% of indoor humidity (Maximum indoor humidity) the Ventilation temperature set will be
25.0°, at 65% of indoor humidity will be 24.8° (25.0°-0.2°= 24.8°), due to decrease of 0.2° (Ventilation
set decrease) for every extra 1% of ambient humidity, up to a maximum decrease of 2.0° (Max ventilation
set decrease). This will bring temperature set of Ventilation= 23.0° at 74% of indoor humidity.
*1
When the Index working mode has been selected (set by Qfarm Lab and activated according to
par. E.1.3.4.0) this set determines the maximum ambient %RH (in case of humid cimate) on beyond
of which the Index working is de-activated and the system starts de-humidifying by increasing the
Heating set.
*2
If the system works by Index (activated as per par. E.1.3.4.0) this function is not activated as the
Temperature/RH correlation is already done thru the Index.
91
E. Installation - Ventilation
This function allows decrease of ventilation rate (by increasing the Ventilation temperature Set)
whenever %RH goes above desired value: it permits a saving on heating*1.
Minimum indoor humidity %RH value under which works on the increase of the Ventilation
(Range: 0%...40 %...100%) set, reducing the ventilation rate *1.
Ventilation set increase Increase of the Ventilation temperature set (see par. D.1) for every
(Range: 0.0°...30.0°) 1% of % RH decreasing the Minimum indoor humidity value *1.
Make sure the Ventilation differential (par. E.1.3.1.F.7) is higher or
equal to this setting.
Differential
ON* fixed=2%
*Increase of Ventilation Set
controlled by Max ventil. set increase
VENTILAT.
SET
INCREASE
OFF Ambient
humidity
For every 1% decrease of ambient humidity when the Block is activated (Minimum indoor humidity), the
temperature Set of the Ventilation is increase of value as set in Ventilation set increase, until a maximum
value set in Max ventilation set increase.
Above 50% of indoor humidity (Minimum indoor humidity) the Ventilation temperature set will be
25.0°, at 50% of indoor humidity will be 25.2° (25.0°+0.2°= 25.2°), due to increase of 0.2° (Ventilation
set increase) for every 1% decrease of ambient humidity, up to a maximum increase of 2.0° (Max
ventilation set increase). This will bring temperature set of Ventilation= 27.0° at 41% of indoor humidity.
*1
If the system works by Index (activated as per par. E.1.3.4.0) this function is not activated as the
Temperature/RH correlation is already done thru the Index.
92
E. Installation - Ventilation
This function allows decrease the % of air changes when outdoor temperature is very cold.
Outdoor temperature set Outdoor temperature under which the decrease of Air exchange*1
(Range: -30.0°...10.0°...50.0°) set is activated (see par. D.1).
Air exchange decrease Decrease of the % Air exchange*1 set for every 1° decreasing of
(Range: 0%...100%) Outdoor temperature set.
i.e.: when decreasing by 10% an air exchange already set as 20%
the total final air exchange will be 18%.
Differential
ON* fixed=1.0°°
*Decrease of Air-Exchange Set
controlled by Maximum decrease AIR
EXCHANGE
SET
DECREASE
OFF Outdoor
temperature
For every 1% decrease of outdoor temperature when the Block is activated (Outdoor temperature
set ), the % Air exchange*1 is decrease of the value set in Air exchange decrease, until a maximum
value set in Maximum set decrease.
When outdoor temperature is higher that 10.0° (Outdoor temperature set) the Air exchange*1 set will
be 20%, at 10.0° of outdoor temperature will be 18% (20% - 10% of 20%= 18%), due to decrease of
10% (Air exchange decrease) for every lower outdoor temperature degree, up to a maximum decrease
of 50% (Maximum pressure decrease, as % calculated value).
This will bring set of Air exchange= 10% at 6.0°C of outdoor temperature.
*1
m3/h minimum calculation in M3/h Ventilation mode.
93
E. Installation - Ventilation
Outdoor temperature set Sets the outdoor temperature which activates the ‘Outdoor
(Range: -30.0°...10.0°...50.0°) temperature block’.
Maximum step ventilation Maximum ventilation allowed when ‘Outdoor temperature block’ is
(Range: 0...16) activated (when ventilation is made in steps).
Differential
ON* fixed=1.0°
MAXIMUM
VENTIL.
BLOCK
OFF Outdoor
temperature
*
OUTDOOR TEMPERATURE BLOCK can influence the maximum ventilation step (in case of step
ventilation) or % maximum ventilation speed insert (when ventilation is proportional).
Below a certain external temperature (Outdoor temperature set) the maximum ventilation can be
limited (Maximum step ventilation or Maximum % ventilation).
By this conditioning you can adjust the night time Ventilation set of temperature. As option you can
also change the nightime Heating set of temperature (par. E.1.1.4.1 Heating conditioning).
Night start time Time (hours:mins) when the night time period starts.
(Range: 0h.00m...23.h59 m)
Night end time Time (hours:mins) when the night time period ends.
(Range: 0h.00m...23.h59 m)
Night time set variation Variation of the Ventilation setting during the night time period
(Range: -30.0°...0.0°...30.0°) (+ or -).
Note: when setting 00:00 as start and end time, night ventilation range is excluded.
94
E. Installation - Ventilation
The ventilation increase and decrease steps can be blocked by an external contact.
Decrease ventilation block Limit Ventilation step allowed (decreasing steps) when
(Range: 0...16) “Ventilation decreasing contact” is closed *.
Increase ventilation block Limit Ventilation step allowed (increasing steps) when
(Range: 0...16) “Ventilation increasing contact“ is closed *.
*
In case Increase/Decrease Flaps blocks were set by Qfarm Lab (see par. E.1.2.5.3), these blocks
influence the Ventilation only.
In case of winter/summer Ventilation, by this setting you can differentiate some parameters in the 2
ventilation systems.
Summer pressure set Summer ventilation air pressure set. In case of winter/summer
(Range: 0P...20 P...300P) ventilation this is the summer ventilation Pressure set and the
winter ventilation Pressure Set is the one set par. E.1.2.1.
Working time summer flap Flap working time works by summer pressure sensor (different from
(Range: 0.0”...2.0”...900.0”) the winter Ventilation one set in par. E.1.2.1).
Waiting time summer flap Flap waiting time works by summer pressure sensor (different from
(Range: 0.0”...5.0”...900.0”) the winter Ventilation one set in par. E.1.2.1).
Progress tunnel flap % summer Flap advance (only with Flap with potentiometer): the
(Range: 0%...3%...100%) feedback Flap with potentiometer will move of this percentage after
every Waiting Time (different from the winter Ventilation one set in
par. E.1.2.1).
Summer step increase delay Ventilation step time delay in Summer ventilation (different from
(Range: 0m.00s...10m.00s) the Winter ventilation one set in par. E.1.3.4.8).
Summer step decrease delay Flap closing time delay in switching a step when Summer ventilation
(Range: 0m.00s...10m.00s) is decreasing (different from the Winter ventilation one set in par.
E.1.3.4.8).
95
E. Installation - Ventilation
Fan shutters start Start up step, when coming from a stop, to make fan shutters
(Range: 0...1...3) opening easier (when fans are in speed voltage regulation by
transformer); this condition remains during the Shutter start time.
Shutter start time Time duration of the fan shutters start section.
(Range: 0m.00s...10m.00s)
Ventilation increase delay This is the delay in response when the ambient temperature
(Range: 0m.00s...10m.00s) requires to switch to a higher step.
On the contary flaps are operated immediately in order to make
easier flaps opening before the increase in ventilation.
In pressure operation during this delay the flaps will be forced open.
Ventilation decrease delay This is the delay in closing flaps when ventilation is decreasing,
(Range: 0m.00s...10m.00s) when ambient temperature requires a passage to a lower ventilation
step. The flap actionning is performed after this delay.
Forced block time When a further ventilation step is activated during the forced block
(Range: 0m.00s...2 m.00s) time, the forced opening of flap (controlled by depressiometer, see
Ventilation increase delay) will be activated only once.
When the forced block time = 0m.00s this function is not active.
96
E. Installation - Ventilation
This function can increase ventilation rate (by reducing the Ventilation temperature set or by increasing
the % of Air changes*1) whenever CO2 or NH3 will be increasing some preset values.
Maximun indoor CO2 ppm CO2 set (over this value, ventilation rate is increased).
(Range: 0pm...2800 pm...10000pm)
Ventilation temperature set Decrease of the temperature Ventilation set (see par. D.1) for each
decrease CO2 intervention step higher than the Maximun indoor CO2.
(Range: 0.0°...30.0°) Make sure the Ventilation Differential (par. E.1.3.1.F.7) is higher or
equal to this setting.
Max ventilation temperature Maximum decrease of the Ventilation set for C02 intervention.
set decrease
(Range: 0.0°...2.0°...30.0°)
% of Air exchange increase Increase % of Air exchange*1 for each CO2 intervention step higher
(Range: 0%...100%)
than the Maximun indoor CO2 (calculated on the Air exchange*1).
i.e.: when increasing by 20% an air exchange already set as 10%
the total final air exchange will be 12%.
Max % of Air exchange increase Maximum Increase % of Air exchange*1 for CO2 intervention.
(Range: 0 ...50 ...100 )
% % %
Maximun indoor NH3 ppm NH3 set (over this value, ventilation rate is increased).
(Range: 0.0pm...16.0 pm...100.0pm)
Ventilation temperature set Decrease of the temperature Ventilation set (see par. D.1) for each
decrease NH3 intervention step higher than the Maximun indoor NH3.
(Range: 0.0°...30.0°) Make sure the Ventilation Differential (par. E.1.3.1.F.7) is higher or
equal to this setting.
Max ventilation temperature Maximum decrease of the Ventilation set for NH3 intervention.
set decrease
(Range: 0.0°...2.0°...30.0°)
% of Air exchange increase Increase % of Air exchange*1 for each NH3 intervention step higher
(Range: 0%...100%) than the Maximun indoor NH3 (calculated on the Air exchange*1).
i.e.: when increasing by 20% an air exchange already set as 10%
the total final air exchange will be 12%.
Max % of Air exchange increase Maximum Increase % of Air exchange*1 for NH3 intervention.
(Range: 0 ...50 ...100 )
i.e.: max additional air exchange is 50% so if air exchange is already
% % %
*1
Minimum calculation in m3/h Ventilation mode.
CO2 and NH3 concentration in the air can act on ventilation in two ways:
1> Reduction of temperature Ventilation set by CO2 or NH3 intervention
2>Increase of Air exchanges setting by CO2 or NH3 intervention.
See diagrams on next page.
97
E. Installation - Ventilation
OFF C0 2 indoor C0 2
ppm
Below 2800 ppm of ambient C02 (Maximun indoor CO2) the Ventilation temperature set will be 25.0°,
at 2800 ppm of ambient C02 will be 24.8° (25.0°-0.2°= 24.8°), due to decrease of 0.2° (Ventilation
set decrease) for every extra 50 ppm (CO2 intervention step) of ambient C02, up to a maximum
decrease of 1.0° (Max ventilation temperature set decrease).
This will bring temperature set of Ventilation= 24.0° at 3000 ppm of CO2.
Below 2800 ppm of ambient C02 (Maximun indoor CO2) the Air-exchange*1 set will be 20%, at 2800 ppm
of ambient C02 will be 22% (20% + 10% of 20%= 22%), due to increase of 10% (% of Air exchange
increase) for every extra 50 ppm (CO2 intervention step) of ambient C02, up to a maximum increase of
50% (Max % of Air exchange increase). This will bring set of Air-exchange*1= 30% a 3000 ppm of CO2.
*1
Minimum calculation in m3/h Ventilation mode.
98
E. Installation - Ventilation
Below 18 ppm of ambient NH3 (Maximun indoor NH3) the Ventilation temperature set will be 25.0°,
at 18 ppm of ambient NH3 will be 24.8° (25.0°-0.2°= 24.8°), due to decrease of 0.2° (Ventilation set
decrease) for every extra 0,5 ppm (NH3 intervention step) of ambient NH3, up to a maximum decrease
of 1.0° (Max ventilation temperature set decrease).
This will bring temperature set of Ventilation= 24.0° at 20 ppm of NH3.
Below 18 ppm of ambient NH3 (Maximun indoor NH3) the Air-exchange*1 set will be 20%, at 18 ppm of
ambient NH3 will be 22% (20% + 10% of 20%= 22%), due to increase of 10% (% of Air exchange
increase) for every extra 0.5 ppm (NH3 intervention step) of ambient NH3, up to a maximum increase of
50% (Max % of Air exchange increase). This will bring set of Air-exchange*1= 30% a 20 ppm of NH3.
*1
Minimum calculation in m3/h Ventilation mode.
99
E. Installation - Ventilation
E.1.3.4.0 Various-Index
Path: Home> Installation> Climate> Ventilation> Conditionings> Various/Index
Index ambient heating Index ambient Heating function activation (perceived temperature)
(Range: No...Yes) No = Ambient sensing probe reading
Yes = Temperature as perceived by animals*.
Index radiant heating Index radiant Heating function activation (perceived temperature)
(Range: No...Yes) No = Ambient sensing probe reading
Yes = Temperature as perceived by animals*.
*
Active only the Index tab has been previously loaded by Qfarm Lab.
When index is act ivat ed ( YES) the working temperature is no longer the one read by the temperature
probe, but it becomes the temperature as “perceived” by the animals. In the screenshots of the
various functions it will be displayed that the woking temperature is the Index temperature.
If any outdoor %RH has been installed in case of humid outdoor conditions the ventilation working
temperature goes back to the temperature read by the temperature probe (the perceived temperature
is excluded) and the Heating set can be increased to dehumidify the ambient (see par. E.1.1.4.2
Heating increase according to indoor % Rh).
100
E. Installation - Humidification
E.1.4 Humidification
Path: Home> Installation> Climate> Humidification
The %Rh control activates the Humidification in case of low indoor %Rh, the temperature control
switches the humidification off in case it goes below the minimum indoor temperature.
Humidity start set Set of the humidity control (absolute setting). If the RH reading is
(Range: 0%...60 %...100%) below this setting the humidification control will be on.
Humidity
* ON HUMIDIFICATION ON* ON* ON* ON* differential
Controlled by
ON HUMIDIF. BLOCK
for low indoor temperature
HUMIDIF
With set On time= different from 0m.00s and On time= different from 0m.00s Humidification is operated by
timer mode with respective On and Off time (set like On time and Off time).
HUMIDIF
BLOCK
OFF Ventilation
With negative setting the value is deducted temperature probe*
Temp.stop
from referring Set (Ventilation).
relative set
Set referred to the Ventilation set as programmed in Settings>Climate
This Set can be set by Calendar (par. D.5.1) Ventilation
* In case of Ventilation Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
101
E. Installation - Cooling
E.1.5 Cooling
Path: Home> Installation> Climate> Cooling
The temperature control activates the Cooling system in case of high indoor temperature.
The %Rh control switches the cooling off in case of high indoor %Rh.
Cooling 1 temperature set Temperature set Cooling 1: when the temperature is above this
relative/absolute set setting the cooling control will be on. This setting is either an
(Range: -30.0°...30.0°...50.0°) absolute or a relative setting depending upon previous option Cooling
setting mode.
Cooling 1 humidity set Humidity set Cooling 1: above this set the Cooling 1 is off.
absolute set Absolute value setting.
(Range: 0%...75 %...100%)
Cooling 2 temperature set Temperature set Cooling 2: when the temperature is above this
relative/absolute set setting the cooling control will be on. This setting is either an
(Range: -30.0°...32.0°...50.0°) absolute or a relative setting depending upon previous option Cooling
setting mode.
Cooling 2 humidity set Humidity set Cooling 1: above this set the Cooling 1 is off.
absolute set Absolute value setting.
(Range: 0%...75 %...100%)
Off minimum time Off minimum time calculation with Off calculated = Yes
(Range: 0m.00s...0m.10s...60m.00s)
102
E. Installation - Cooling
Temperat.
differential ON*
* Controlled by
ON MAX HUMIDITY
COOL 1 BLOCK
COOL if Humidity control is
This set can be either an absolute or a
present.
1 relative setting according to what has
been selected in the previous option
Cooling setting mode.
OFF Ventilation
temperature probe*
If Relative= value setting related to
Ventilation set
Cooling 1 temperature set (Settings > Climate see par. D.1).
When set a On time = 0m.00s the Cooling works as a normal On-Off system.
Humidif.
differential ON*
Temperat.
differential ON* ON* ON* ON*
* Controlled by
ON MAX HUMIDITY COOL 1 BLOCK
if Humidity control is present.
COOL
1
OFF OFF OFF OFF Ventilation
temperature probe*
Timer band
This set can be either an absolute or a relative setting
Cooling 1 temperature set
according to what has been selected in the previous option
Cooling setting mode. If Relative= value setting related to
Ventilation set (Settings > Climate see par. D.1).
*In case of Ventilation Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
If On time is different from 0m.00s and Off calculated= No the Timer band Cooling is working by timer
(On and Off times are as set in On time and Off time).
In the case the indoor % humidity goes above the maximum allowed value, Timer band cooling will
work continously (without temporization), in case %RH Indoor Humidity goes above the max
allowed value.
Same for Cooling 2 (if any).
103
E. Installation - Cooling
Diff.temp
ON* ON* ON* ON* ON*
* Controlled by
ON MAX HUMIDITY COOL 1
BLOCK
if Humidity control is present.
COOL 1
With set On time= different from 0m.00s and Off Calculated= Yes inside of Timer band Cooling is
actioned in temporized mode with On time fixed (set like On time) and Off time calculated in
proportional mode (starting from maximum value set in Off time and reducing it proportionally step
by step that the inside temperature increase until the value of Off minimum time): exceed Timer
band Cooling’s working is continuous (without temporization), in case %RH Indoor Humidy goes
above the max allowed value.
The above working configuration allows the cooling to operate in a proportional way with increasing
cooling capacity.
The humidity control (if any) switches the cooling off when the limit value is reached.
104
E. Installation - Probes average
When the “Average probes” is activated, this average value of temperature is the working temperature
referred to Ventilation, Humifìdification, Cooling and temperature alarms.
Ventilation 1 probe Is the Ventilation 1 probe considered when calculating the average
(Range: No...Yes) temperature value? Yes-No.
Ventilation 4 probe Is the Ventilation 4 probe considered when calculating the average
(Range: No...Yes) temperature value? Yes-No.
Heating 1 probe Is the Heating 1 probe considered when calculating the average
(Range: No...Yes) temperature value? Yes-No.
Heating 16 probe Is the Heating 16 probe considered when calculating the average
(Range: No...Yes) temperature value? Yes-No.
Flap 1 probe Is the Flap 1 probe considered when calculating the average
(Range: No...Yes) temperature temperature value? Yes-No.
Flap16 probe Is the Flap16 probe considered when calculating the average
(Range: No...Yes) temperature value? Yes-No.
The temperature values contributing to create the average temperature are shown in Check> Climate>
Probes average (see H.1.2).
105
E. Installa tion- Special inputs
*1
The name of counters 1 and 2 can be customized by Qfarm Lab (i.e. in a QFarm only Climate you
can also input the water and feeding counter).
106
E. Installation - Climate alarm
E.1.8 Alarm
Path: Home> Installation> Climate> Alarm
Foreword
According to what was set by Qfarm Lab can control these types of Alarms:
The intervention of one the above alarms will affect Flaps system (see par. E.1.8.8).
107
E. Installation - Climate alarm
This alarm can keep under control the minimum and maximum ambient temperature level.
Set can be either absolute or relative ones (following the Ventilation set as programmed
SETTING>Climate, see par. D.1) so that ambient temperature will not go beyond preset minumum
and maximum values.
*In case of Ventilation Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
108
E. Installation - Climate alarm
This alarm can keep under control the min and max ambient humidity level.
0.2% 0.2%
ON fixed fixed ON
MINIMUM MAXIMUM
HUMIDITY HUMIDITY
ALARM OFF OFF ALARM OFF Ambient
humidity
Typically the max absolute set is = 97% so it can gives the signal the wet bulb probe has become
dry(with psycrometric kit).
109
E. Installation - Climate alarm
This alarm can keep under control the min and max air-pressure level.
Minimum
absolute set Pressure set (Pascal) of the minimum alarm (absolute setting).
(Range: 0P...300P) Below this setting the alarm is on (0P= alarm excluded).
Maximum
absolute set Pressure set (Pascal) of the maximum alarm (absolute setting).
(Range: 0P...100P...300P) Above this setting the alarm is on.
2P 2P
ON * fixed fixed ON
MINIMUM MAXIMUM
PRESSION PRESSION
ALARM OFF OFF ALARM Air depression
(Pascal)
*
This alarm is not activated during the off ventilation period or when ventilation is operated by timer
in Air exchange or in M3/h/Kg.
110
E. Installation - Climate alarm
This alarm can keep under control the minimum ambient heating temperature level.
0.2°
ON * fixed
MINIMUM
TEMPERAT.
AMBIENT 1
ALARM OFF Ambient 1 Heating
temperature probe*
Minimum
relative set
01 (Heating)
relative set
Heating
01 (Heating) relative set programmed in
Heating> Ambient (par. E.1.1.1)
*In case of Ventilation Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
*1
The alarm of minimum temperature for ambient does not work if it has been excluded (see par. 4.C).
111
E. Installation - Climate alarm
This alarm can keep under control the minimum ambient heating temperature level.
Minimum Temperature set of Minimum alarm referred to the Radiant relative set,
relative set as programmed in Heating> Radiant (see E.1.1.2.1 - E.1.1.2.2).
(Range: -30.0°...-0.5°...30.0°)
0.2°
ON * fixed
MINIMUM
TEMPERAT.
RADIANT
ALARM OFF Radiant Heating
temperature probe*
Minimum
relative set
Radiant
relative set
Heating
01 (Heating) relative set programmed in
Heating> Ambient (par. E.1.1.2.1 - E.1.1.2.2)
*In case of Ventilation Index control is the temperature as felt by the animals (see Index par. E.1.3.4.0).
*1
The alarm of minimum temperature for ambient does not work if it has been excluded (see par. 5.C).
112
E. Installation - Climate alarm
It controls the Amperage take up of the ventilation section and take steps when it goes below a
minimum preset value (it also works when phases are out of balance).
0.2A 0.2A
ON * fixed fixed ON
MINIMUM MAXIMUM
ABSORP. IMBALANCE
ALARM ALARM
OFF OFF
*
This alarm is not activated during the off ventilation period when ventilation is operated by timer
in Air exchange or in M3/h/Kg.
113
E. Installation - Climate alarm
This alarm can keep under control the maximum ambient CO2 and NH3 level.
C0 2 NH3
ppm ppm
MAXIMUM MAXIMUM
C02 NH3
ALARM ALARM
OFF C02 ambient C0 2 OFF NH3 ambient NH3
ppm ppm
114
E. Installation - Climate alarm
This alarm can keep under control the maximum ambient Heat index level.
2
fixed ON
MAXIMUM
INDEX H.
ALARM
OFF Ambient temperature (°F) + + = Index H.
Ambient humidity (%Rh)
Maximum Index H.
absolute set
115
E. Installation - Climate alarm
(Range: No-Op...Open...Closed)
*1
If alarm is in Display mode the intervention is excluded.
*2
When flaps are set to Open, in case of minimum pressure alarm intervention, they are opened and
kept opened all the time (to go back to normal working conditions you should manually close them
until they go back to the normal working pressure). Either you can switch Qfarm off and then on again.
116
E. Installation - Climate alarm
Buzzer alarm exclusion Alarm exclusion (minutes) signaled by acoustic signal (buzzer) from
(Range: 0m.00s...60m.00s) external contact (0m.00s= excluded). See par. C.
117
E. Installation - Climate alarm
The general alarm output (built in on Qfarm) can be tested both manually and automatically.
*1
The manual alarm activation is done by getting in Daily inspections procedure (see par. G.8.E).
Once this time is elapsed it goes back to normal conditions.
*2
The automatic alarm activation is done at Automatic test start time in the selected days of week,
for as log as the Duration of automatic test in seconds.
Once this time is elapsed it goes back to normal conditions.
In the Daily inspection register log (see par. G>8>E), the activation of Alarm test is recorded (when
multiple daily tests are done, the last only will be recorded).
118
E. Installation - Feeding
E.2 Feeding
Path: Home> Installation> Feeding
119
E. Installation - Feeding
Qfarm can control 1 or 2 bird-weighing units according to the setting previously done by Qfarm Lab.
Plate 1 cell sensitivity Balance loading cell data (see technical features of the load cell).
(Range: 0.8...2.000...3.300) Perform a ‘Calibration’ to automatically record this value.
Plate 2 cell sensitivity Balance loading cell data (see technical features of the load cell).
(Range: 0.8...2.000...3.300) Perform a ‘Calibration’ to automatically record this value.
120
E. Installation - Feeding
Point 1>2 uniformity % uniformity below this level the Maximum 2 final % applies*.
(Range: 0%...60%...100)
Type of weight capture Automatic: the capture weight is calculated according to the daily
(Range: Automatic...Target) average reading and automatically updated at each capture.
*1
The percentage of min and max capture weight is calculated according to these settings.
At the beginning of cycle you start with Minimum initial % and Maximum initial % to get by linear
interpolation, at the end of the cycle, a Maximum 1 final % (or Maximum 2 final % if the uniformity is
lower than Point 1>2 uniformity).
121
E. Installation - Feeding
Plate calibration Make sure the weigher is clear and the readout = 0 (if not then perform
the 'Tare' procedure). Place a known weight on the plate.
If the displayed weight, above, does not match the weight expected,
adjust the displayed weight, using the Decr or Incr keys, to the known
weight value. Press Enter to confirm or Exit to quit without saving.
122
E. Installation - Feeding
Foreword
According to what was set by Qfarm Lab, the Qfarm can control the feed weight in the following ways:
Kg per pulse Kg of feed supplied for each pulse of the feed counter.
(Range: 0.00k...1.000k...100.00k)
E.2.2.2 Volumetric
Path: Home> Installation> Feeding> Feed weighing> Volumetric
123
E. Installation - Feeding
Silo 1 cells full-scale Kg full scale of the loading cell (see technical features of the load cell).
(Range: 0k...5000k...100000k)
Silo 1 cells sensitivity Balance loading cell data (see technical features of the load cell).
(Range: 0.8...2.000...3.300) Perform a ‘Calibration’ to automatically record this value.
Silo 2 cells full-scale Kg full scale of the loading cell (see technical features of the load cell).
(Range: 0k...5000k...100000k)
Silo 2 cells sensitivity Balance loading cell data (see technical features of the load cell).
(Range: 0.8...2.000...3.300) Perform a ‘Calibration’ to automatically record this value.
124
E. Installation - Feeding
Silo calibration Make sure the weigher is empty and the readout= 0 (if not then perform
the 'Tare' procedure). Place a known weight on the silo.
If the displayed weight, above, does not match the weight expected,
adjust the displayed weight, using the Decr or Incr keys, to the known
weight value. Press Enter to confirm or Exit to quit without saving.
125
E. Installation - Feeding
Automatic upload weight Kg of feed to be loaded in the silos beyond which the Automatic silo
(Range: 0k...90k...100k) uploading procedure is activated*.
Time check upload Duration time allowed for the weight in the silos to increase.
Beyond which the Automatic silo uploading procedure is
(Range: 0m.00s...0m.20s...2 m.00s) activated.
Time re-start Waiting time after a loading of the silo, after which the Automatic
(Range: 0m.00s...1m.00s...10m.00s) silo uploading procedure finishes.
Weight drift Daily minimum weight (Kg), under which the weight downloaded
(Range: 0k...20k...100k) from the silos is not recorded (inactive setting).
*
Typically, when setting Automatic upload weight= 90K and Time check unload=20s the program can
detect the feed truck is uploading the silos: at this point the program stops the silos auger (if working)
and activate the Automatic silos uploading procedure.
Once the upload has been completed, the feed distributions starts again automatically and the feed
uploaded in the silos is recorded in Archive>Silos upload (par. G.7).
If you were to register "silo loading false signals" due to wind action on the silo (and recorded in
Archive>Silos upload, par. G.7) we suggest to set Automatic upload weight= 90K and Time check
unload=10s.
When the silos feed uploading is done on a “slow” way (say when the download silos auger is working
during the silos upload so that the net uploading difference is less than 90 kg every 20") we suggest
to set Automatic upload weight= 90K and Time check unload=40s.
Obviously the higher the above Automatic upload weight value the higher is the risk that Automatic
silos uploading procedure (mostly due to wind gusts acting on the silos) is unintentionally activated.
To be 100% this will not happen, we recommend to stop the feed distribution before loading the silos.
As option, “Silos uploading” sensors can be installed so they immediately recognize the silos is being
uploaded (in this case the system goes into Silos uploading mode).
In E.2.6. you can set the alarm with maximum allowed time to close the signal of the load sensor silo.
Note: Use this silo upload system where silo is NOT directly uploaded from the feed truck.
The typical use of this system is for small silos which are loaded from a big silo by an auger system.
126
D. Installation - Feeding
E.2.3 Distribution
Path: Home> Installation> Feeding> Distribution
Hopper sensor delay Defines the delay in activating the hopper auger after the feed
(Range: 0m.00s...0m.05s...10m.00s) sensor start signal.
To avoid frequent on-off working of the silo auger due to the action
of the max level hopper sensor, this value has to be set according
to the time required by the feed hopper to become empty when
feeding lines are working.
In this way the hopper is being loading only when it’s really empty.
Delay end distribution Hoppers delay at end of every time cycle for each meal (with
(Range: 0m.00s...60m.00s) rationed meal only). The feeding lines start at the beginning of the
meal and stop after this delay when the rationed meal is completed
or when the time cycle of the meal is over*1.
Delay start feeders Feeder start delay. This helps prevent the feeders running without
(Range: 0m.00s...60m.00s) feed at the start of the cycle.
Feeders on time Feeders run time for when ration feeding with time delayed function.
(Range: 0m.00s...60m.00s) If this is set to 0m.00s then the timing is not used.
Feeders off time Feeders stop time for when ration feeding with time delayed
(Range: 0m.00s...60m.00s) function. If this is set to 0m.00s then the timing is not used.
Medication mode 0= the download water pump starts as soon as the medicated
(Range: 0...1) water level has been reached in the tank*2.
1= the download water pump starts 1 minute after the upload of
water into the tank has been started*2.
Feeders lowering time When the feeding time arrives the feeders are lowered down during
(Range: 0m.00s...2 m.00s) this time settings and then the feeder starts working.
Feeders raising time When the feeding time is over, and after the Delay end distribution
(Range: 0m.00s...2 m.00s) time the feeders are raised up during this time.
Feeders stop during silos loading Feeders stop during silos loading? Yes-No.
(Range: Yes...Si)
Off timer feeders in fast When in ‘Fast procedure’ this is the waiting time of feeders from the
(Range: 0h.00m...6h.00m...12h.00m) fast start up*3.
On timer feeders in fast When in ‘Fast procedure’: feeders working after waiting time
(Range: 0h.00m...0h.05m...12h.00m) Off timer mangers in fast*3.
Light turn-off Number of minutes the lights are turned off for during meal
(Range: 0m.00s...99m.00s) distribution start.
Warning Water/Feed Water/Feed ratio above that level, the value as displayed in the
(Range: 0.00...5.00) feeding screenshot (Home>8) is highlighted in red color.
Water diagram coefficient Display coefficient referred to the Gr/bird of water as per Water/
(Range: 1...4)
Feed diagram (Home>8>F).
I.E. when setting = 2 the value of the Gr/bird of water is halved.
*1
Not active in case of Fast.
*2
For Medicated working see par. D.3.2.5.
*3
For Fast working see par. D.3.2.6.
127
E. Installation - Feeding
E.2.4 Lighting
Path: Home> Installation> Feeding> Lighting
Introduction
According to the setting done Qfarm Lab, Qfarm can control light with control up to 8 lights
(by On / off output and with dawn / sunset 0-10V output), can also control the opening and closing of
hens nests.
The light timing setting is one, both for all the Lights and the Nest opening so that the farmer only
need to set the Start timing and the End timing (all settings referred to these 2 timings) and can be
programmed in Settings>Feeding>Time clocks>Light times (see par. D.3.1.2).
01 (Light 01)*
01 Off light advance Advance time lighting down, referred to Stop hour light.
(Range: 0m.00s...99m.00s)
Opening nests delay Delay time Nests opening, referred to Start hour light.
(Range: 0m.00s...99m.00s)
Closing nests advance Advance time Lests closing, referred to Stop hour light.
(Range: 0m.00s...99m.00s)
* Note. The name of the lights can be customized (using the software Qfarm Lab).
128
E. Installation - Feeding
Operation lights
ON
100% 01 Maximum %*
50% 01 Light 0-10V
10% 01 Minimum %
0%
Stop hour x The Start timing and the End timing can be programmed in Stop hour x
Light times Settings> Feeding> Time clocks> Lighting cycle times (par. C.3.1.2.) Light times
TIME
The characteristics of the 8 0-10V outputs are completely independent: each output 0 -10V may also
be associated with an ON-OFF.
Operation nests
ON
NEST NEST
OFF OPENING CLOSING
Opening Closing
nests delay nests advance
Start hour x The Start timing and the End timing can be programmed in Stop hour x
Light times Settings> Feeding> Time clocks> Lighting cycle times (par. D.3.1.2.) Light times
TIME
129
E. Installation - Feeding
Variation start time Time (hours:mins) when the variation period starts.
(Range: 0h.00m...23.h59 m)
Variation end time Time (hours:mins) when the variation period endss.
(Range: 0h.00m...23.h59 m)
Note: when setting 00:00 as start and end time, luminosity change is excluded.
Lt per pulse Liters of water supplied for each pulse of the Water meter.
(Range: 0.00Lt...1.00Lt...100.00Lt)
Gas per pulse Gas of unit supplied for each pulse of the Gas meter.
(Range: 0.00u...1.00u...100.00u)
130
E. Installation - Feeding
Low stock alarm Set the number of meals remaining in the silos. If the number of
(0...50) meals available falls below this setting the Low stock alarm is
activated.
The Low stock alarm is calculated based upon the quantity of feed
distributed during the last meal time (0 = not active).
Minimum feed flow Kg of feed which must be downloaded in the time set at Minimum
(0k...100k) feed flow time. If the entered amount of feed falls below this setting
the Minimum feed flow alarm is activated (0=excluded)*1.
Minimum feed flow time In this time the weight decrease in the silos must not be less than the
(Range: 0m.00s...1m.00s...60m.00s) value set in Minimum feed flow otherwise the Minimum feed flow
alarm is activated. This alarm works only if silos have load cells and
it’s not operational with the volumetric system (0=excluded)*1.
Silo auger delay time This is the delay time of the silo’s auger after a Minimum feed flow
(Range: 0m.00s...1m.00s...60m.00s) alarm. After this delay the system tries to download the silos again:
after 3 unsuccessful attempts the Minimum feed flow alarm is
activated and the system needs to be reset to start again *1.
Maximum feed flow Maximum Kg of feed unloaded from the silo between two hoppers limit
(Range: 0kg...32000kg) switch activations. In this way the hopper limit signal checks the
loaded feed does not exceed the required quantity (0= excluded)*1 *2.
Minimum water flow Minimum water consumption alarm below which the Minimum
(Range: 0Lt...10000Lt) water flow alarm starts, calculated in time Water check time (0=
excluded)*3. This alarm is not operation during the water OFF
periods and during the Medicated water procedure.
Maximum water flow Maximum water consumption alarm above which the Maximum water
(Range: 0Lt...10000Lt) flow alarm starts, calculated in time Water check time (0= excl.)*1 * 3.
This alarm is not operation during the Medicated water procedure.
Water flow check time Duration of Water minimum/maximum alarm check (0=
(Range: 0h.00m...12h.00m) excluded)*3.
Maximum delay water supply This is the max allowed delay in minutes to supply water from the
(Range: 0m.00s...60m.00s) start time. At the start time of water supply the supplied water
value could be already more than the value allowed by the Maximum
water flow so the alarm is delayed by this time.
Hens feed alarm Minimum amount of feed to be distributed within a meal period
(Range: 0kg...32000kg) (start time-end time). Setting 0 the alarm is excluded*5.
Continue
131
E. Installation - Feeding
Silo upload signal This is the time duration to check the silo loading signal.
(Range: 0 .00 ...20 .00 ...60 .00 )
m s m s m s When this time is over the Silo upload signal alarm will be
displayed (active only if silo upload signal is present).
Max time opening/closing nests If the ‘Opening/closing nests’ done sensors are installed,
(Range: 0 .00 ...60 .00 )
m s m s after this time closing or opening of nests must be confirmed
by the dedicated sensor (contact is closed).
On contary case the Failed nests opening/closing alarm
is activated. (0=excluded).
*1
When any of these alarms is activated, feed and water distribution automatically stop. To re-start
the system see Restart feed system par. C.F. These alarms are automatically reset on next day.
*2
This alarm is operation only when the feed hopper sensor is connected (see Installation Manual
par. A.19). If the sensor is not connected, set this value = 0.
*3
During Minimum water flow check time the value of distributed water should not be lower than Minimum
water flow alarm and during Maximum water flow check time the value of distributed water should not
be exceed than Maximum water flow alarm otherwise the Water Alarm will be activated (0= alarm
disabled).
*4
Minimum water/feed.
The alarm Minimum water/feed is activated only when the water distribution is over (at the end of
the last period of water distribution).
The alarm, in addition to being reported, is filed in the day’s events.
If activated it can be silenced, see par. C.D.
Maximum water/feed.
The alarm Maximum water/feed is activated only when water distribution is over (at the end of the
last period of water distribution).
The alarm, in addition to being reported, is filed in the day’s events.
If activated it can be silenced, see par. C.D.
*5
In case feed is distributed at will this alarm enables to check that a minimum feed quantity is
distributed for every programmed meal.
If this does not happen the Hens feed alarm will be triggered.
The alarm can be triggered at the end of each meal (if activated can be silenced, see par. C.D) and
it’s automatically reset at the next meal start up.
132
E. Installation - Feeding
Fast Idem
(Range: Enabled...Display)
133
E. Installation
E.3 Clock
Path: Home> Installation> Clock
E.4 Language
Path: Home> Installation> Language
134
E. Installation
E.5 Manual
Path: Home> Installation> Manual
Testing procedure is not recommended for the manual functionning of the system but only
for testing purposes.
The program automatically escapes from manual procedure after 5 min from last action.
The configuration of the inputs and outputs is made by P.C: with the aid of our Qfarm Lab
software.
Qfarm Lab software also provide, for each chosen configuration, the required extension list,
the system layout alongwith the complete wiring diagram.
Complete list of the Outputs and the Inputs available at par. H6-H7-H8-H9.
Qf alarm Alarm relays on board of Qfarm are set into hand mode
When quitting the procedure, the relay automatically goes back to OFF.
135
E. Installation
E.7 Password
Path: Home> Installation> Password
NOTE:
Trying to access a password-protected area displays the following message:
(example of Settings password) enter the password required and press to confirm.
The password is no longer required as long as you are inside the programming section.
Passwords at start-up is set by default as 0000 (password not used).
136
E. Installation
E.8 Display
Path: Home> Installation> Display
Minimum brightness after waiting Display brightness after Waiting time for minimum brightness
(Range: 0%...20 %...50%) (time is calculated from the last time one key was hit).
Waiting time for min. brightness After this time (from the last time one key was hit) the display
(Range: 0m.00s...1m.00s) fades brightness down to the % preset value in Minimum
brightness after waiting.
D.0 Bootstrap
Path: Home> Installation> Bootstrap
Procedure of Bootstrap.
The 'bootstrap' procedure resets all the setting in the Qfarm back to those as originally set at the
factory. The operation table loaded into the Qfarm using the Qfarm Lab software will always remain
in the memory!
ATTENTION: the 'bootstrap' procedure will delete all the settings, made by the user,
since the Qfarm was installed.
137
E. Installation
Write archives on USB pen Archives can be read on PC by using the Qfarm arch-view support
software.
Write SETS on USB pen All Qfarm SETS (settings) are recorded (don’t forget to do it
after the system testing at start up so you have a complete
configuration back-up).
You can then transfer all setting to another Qfarm unit (or in case
of unit replacement the original settings can be reloaded).
Upload SETS from USB pen If SETS were previously recorded (see previous point) the back
SETS can be selectively uploaded as following:
The SETTING SET
The INSTALLATION SET (except the ones at point ).
The RECORDINGS of the flaps potentiometers (if any) and the
RECORDINGS of the load cells calibrations (if any).
Write TAB on USB pen The working TAB (created by Qfarm Lab software) can be
downloaded.
continue
138
E. Installation
Upload TAB from USB pen The working TAB (created by Qfarm Lab software) can be uploaded.
Identify the tab to be uploaded (press to display if there are
others tabs beyond the tab n. 5. Once that's done, press to go
back to first line of the list).
Selected by .. keys the new tab has to be uploaded.
WARNING: when uploading a different TAB from the one currently loaded a
different project could be uploaded, with a completely different assignement of
inputs and outputs and functionning!
139
G. Archive
G. Archive
Path: Home> Archive
In the archives are recorded all the parameters related to the running cycle.
ATTENTION: the start of a new cycle resets all the files of the previous cycle.
Alarms: here are displayed the last 64 alarm interventions of the running cycle: each alarm shows
recording time and date.
Failures: here are displayed the last 64 failures interventions of the running cycle: each failure shows
recording time and date.
Events: here are displayed the last 64 event interventions of the running cycle: each event shows
recording time and date.
140
G. Archive
141
G. Archive
G.3 Climate
Path: Home> Archive> Climate
In this archive are recorded the daily values of indoor and outdoor climate conditions.
Previous Next
day day
Previous Next
registration registration
> Graphics
142
G. Archive
Previous Next
day day
143
G. Archive
Previous Next
day day
Previous Next
day day
144
G. Archive
G.5 Feeding
Path: Home> Archive> Feeding
Previous Next
day day
Previous Next
day day
145
G. Archive
146
G. Archive
This archive recording the performed daily inspection: first ispection is recorded from 00:00 to 11:59,
second ispection is recorded from 12:00 to 23:59. The alarm check test is also recorded (when multiple
daily tests are done, the last only will be recorded).
Previous Next
To perform the “daily day
day
ispection recording
press the key .
147
G. Archive
G.9.1 Feeding
Path: Home> Archive> Cycle total> Feeding
148
G. Archive
G.9.2 Climate
Path: Home> Archive> Cycle total> Climate
Note: These times are referred to Working time periods for running cycle.
the system and are not reset at any They are erased by starting a new cycle.
new cycle but they must be erased
by their own erasing procedure.
149
H. Check control
H. Check Control
Path: Home> Check Control
Through CHECK CONTROL you can display all the working states of Qfarm.
H.1 Climate
Path: Home> Check Control> Climate
150
H. Check control
This screen gives the situation of the Climate blocks state and also shows the current conditionings (if any).
Max number of blocks displayed is 10.
Each block intervention is displayed in the Zoom 1...5 pages (Block state).
Ventilation blocks
Minimum ventilation See par. D.1
Maximum ventilation See par. D.1
Temporary change of ‘Ventilation’ set See par. D.1.H
Ventilation rotation See par. E.1.3.2
Change of ‘Ventilation’ set by indoor humidity See par. E.1.3.4.1 - E.1.3.4.2
Maximum Step by outdoor temperature See par. E.1.3.4.4
Maximum Ventilation % by outdoor temperature See par. E.1.3.4.4
Change of ‘Ventilation’ set by night condition See par. E.1.3.4.5
Ventilation increase See par. E.1.3.4.6
Ventilation decrease See par. E.1.3.4.6
Summer ventilation See par. E.1.3.4.7
Reduction of ‘Ventilation’ set by CO2 See par. E.1.3.4.9
Reduction of ‘Ventilation’ set by NH3 See par. E.1.3.4.9
151
H. Check control
Heating blocks
Temporary change of ‘Heating’ set See par. D.1.H
Minimum spark block See par. E.1.1.2.2
Change of ‘Heating’ set by night condition See par. E.1.1.4.1
Change of ‘Heating’ set by indoor humidity See par. E.1.1.4.2
Heating is stopped because Ventilation is On See par. E.1.1.4.3
Fan-jet is stopped because Ventilation is On See par. E.1.1.3
Flap blocks
Minimum flap opening (flaps by pressure sensor) See par. E.1.2.1 - E.1.2.5.5
Increase of ‘Pressure set’ by outdoor temperature See par. E.1.2.5.1
Left side anemometer See par. E.1.2.5.2
Right side anemometer See par. E.1.2.5.2
Flap increase See par. E.1.2.5.3
Flap decrease See par. E.1.2.5.3
Flap winter See par. E.1.2.5.3
Flap summer See par. E.1.2.5.3
Flap External 1 See par. E.1.2.5.3
Flap External 2 See par. E.1.2.5.3
Open for Cooling See par. E.1.2.5.3
Closed for Cooling See par. E.1.2.5.3
Draft 1 Flap See par. E.1.2.5.4
Draft 2 Flap See par. E.1.2.5.4
Reduction of % flap opening by outdoor temperature See par. E.1.2.5.6
Various blocks
Pre-start up cycle See par. D.0.F
Outdoor climate too humid See par. E.1.1.4.2
Humidification minimum temperature See par. E.1.4
Cool 1 maximum humidity See par. E.1.5
Cool 2 maximum humidity See par. E.1.5
152
H. Check control
This screen display the values in Ohm of storage of the potentiometer of the relative Flap.
The procedure of Potentiometer Recording is explained to par. E.1.2.4
Go to next page
(if number of Flaps is > than 8)
153
H. Check control
This screen gives the situation of the operating status of the flaps with potentiometer.
The procedure of Potentiometer Recording is explained to par. E.1.2.4
Go to next page
(if number of Flaps is > than 8)
This screen gives the situation of the operating status of the flaps with Delta working.
Go to next page
(if number of Flaps is > than 8)
154
H. Check control
H.2 Feeding
Path: Home> Check Control> Feeding
*1
*3
*4
*2
*1
No if Feed time is ON but the meal is over (with rationed feed).
*2
Yes if timing is temporized (see par. E.2.3).
*3
ON during the 3 attempts of re-start the auger (see par.E.2.6 Silo auger delay time)
*4
(not enabled) - Prog (programmed but not currently running) - Yes (running).
*1
Programmed in Light times (see par. D.3.1.2).
155
H. Check control
H.6 Inputs
Path: Home> Check control> Inputs
156
H. Check control
This screen sums up the configuration of the Outputs relays state of the HDY6 extensions.
This is very useful at system start-up to check if extensions (HXNE-HDY6) were properly connected.
The configuration of the inputs and the outputs of the extension modules is made by Qfarm Lab
software. The software also provide, for each chosen configuration, the required extension list, the
system layout alongwith the complete wiring diagram.
This screen sums up the configuration of the 0-10V outputs of the HXDA extensions.
This is very useful at system start-up to check if extensions (HXDA) were properly connected.
The configuration of the inputs and the outputs of the extension modules is made by Qfarm Lab
software. The software also provide, for each chosen configuration, the required extension list, the
system layout alongwith the complete wiring diagram.
157
H. Check control
Dip-switch position
on amplifier TLC2 n.3
158
H. Check control
H.H Info
Path: Home> Check Control> Info
This screens identifyes the plant’s characteristics to control, according to the settings made Qfarm Lab.
159
160
Handbook EN 270317