Professional Documents
Culture Documents
J250 Electronic General Information
J250 Electronic General Information
J250 Electronic General Information
Product Focus
Features J250 Electronic Trip
and Ground Fault / Earth
Leakage Protector
KEMA
Digitrip 310+
Features Ir
Field installable
LS or LSI tLD
Long Time Pick-up – No Rating Plug – customer convenience
250A Settings 250, 225, 200, 175, 160, 150, 125, 100
160A Settings 160, 150, 125, 110, 100, 90, 80, 63
100A Settings 100, 90, 80, 70, 63, 50, 45, 40 ISD
50A Settings 50, 45, 40, 32, 30, 25, 20
Adjustable Long Time Delay – better coordination tSD
2-24 seconds @ 6 x Ir Ii
Adjustable Short Time Pick-up – limits nuisance trips at 14X
2-14 x Ir
Adjustable Short Time Delay
50, 120 milliseconds
Adjustment Seal
New Cutler-Hammer Chip – room to grow
Status Indicator & No Trip Test Indicator – LEDs
Push-to-Trip
Plug-in Test Kit – external power not required
Catalog Numbers
Trip Unit LS LSI LS LSI LS LSI LS LSI
Type