TRANSMISSION LOSS (conductance, ¿ U × A × ∆ ℉ )

North Wall
Wood Thickness Code R
¼“ RW
1 B7 1.19
2 B10 2.39
RW =0.2 9

Construction Material Code R


Inside Air E0 0.685
¼ “Plywood - 0.29
Air Space B1 0.91
¼ “ Plywood - 0.29
Inside Air E0 0.685
Total 2.86
From Table 9-7, MHVAC by Clifford
North side area = 313.408 ft 2

Wooden door area = 18.727 ft 2

Total north wall area = 313.408 - 18.727 = 294.681 ft 2

Q=
( 2.861 hrBTU
∙ ft ∙ ℉ )
2
2
( 294.681 ft ) (19.8 ℉ )

BTU
Q=2040.099
hr

East Wall
Construction Material Code R
Outside Air A0 0.333
1” Plaster A1 0.208
4” Concrete Block C3 0.71
1” Plaster A1 0.208
Inside Air E0 0.685
Total 2.144
From Table 9-7, MHVAC by Clifford
East side area = 163.674 ft 2
Glass door area = 20.964 ft 2

Total east wall area = 163.674 - 20.964 = 142.71 ft 2

1 BTU
Q=
( 2.148 hr ∙ ft ∙ ℉
2 )
( 142.71 ft 2 ) (19.8 ℉)

BTU
Q=1317.938
hr

South Wall
Construction Material Code R
Inside Air E0 0.685
¼ “Plywood - 0.29
Air Space B1 0.91
¼ “ Plywood - 0.29
Inside Air E0 0.685
Total 2.86
From Table 9-7, MHVAC by Clifford
South side area = 313.408 ft 2

BTU
(
Q= 2.9 2
hr ∙ ft ∙ ℉ )
( 313.408 ft 2 ) (19.8 ℉)

BTU
Q=2169.748
hr

West Wall
Construction Material Code R
Outside Air A0 0.333
1” Plaster A1 0.208
4” Concrete Block C3 0.71
1” Plaster A1 0.208
Inside Air E0 0.685
Total 2.144
From Table 9-7, MHVAC by Clifford
West side area = 163.674 ft 2
Glass window area = 102.029 ft 2

Total west wall area = 163.674 - 102.029= 61.645 ft 2

1 BTU
Q=
( 2.148 hr ∙ ft ∙ ℉
2 )
( 61.645 ft 2 ) (19.8 ℉ )

BTU
Q=569.296
hr

Ceiling
Construction Material Code R
Inside Air E0 0.685
¼ “Plywood - 0.29
Air Space B1 0.91
12” Concrete C11 1.08
1” Plaster A1 0.208
Inside Air E0 0.685
Total 3.858
From Table 9-7, MHVAC by Clifford
Ceiling area = 440.465 ft 2

1 BTU
Q=
( 3.858 hr ∙ ft ∙ ℉ )
2
2
( 440.465 ft ) ( 19.8℉ )

BTU
Q=2260.551
hr

North Wooden Door


Description U
1 3/8” Hollow core Flush Door 0.45
From Table 7-6a, MHVAC by Clifford
A = 18.727 ft 2

BTU
(
Q= 0.45 2
hr ∙ ft ∙ ℉ )
( 18.727 ft 2 ) (19.8 ℉ )
BTU
Q=166.858
hr

West Glass Window


Description U Multiplier
¼” Flat Glass, Single Glass; No Shade, Summer 1.04
Metal Frame, Single Glass 1.1-1.0 (1.05 ave.)
From Table 7-5, MHVAC by Clifford
BTU
U = 1.04 x 1.05 = 1.092
hr ∙ ft 2 ∙ ℉
A = 102.029 ft 2

BTU
(
Q= 1.092 2
hr ∙ ft ∙℉ )
( 102.029 ft 2) (19.8℉ )

BTU
Q=2206.03
hr

East Glass Door


Description U Multiplier
¼” Flat Glass, Single Glass; Indoor Shade, Summer 0.81
Metal Frame, Single Glass 1.1-1.0 (1.05 ave.)
From Table 7-5, MHVAC by Clifford
BTU
U = 0.81 x 1.05 = 0.8505
hr ∙ ft 2 ∙ ℉
A = 20.964 ft 2

BTU
(
Q= 0.8505 2
hr ∙ ft ∙ ℉ )
( 20.964 ft 2 ) (19.8 ℉ )

BTU
Q=346.077
hr

TRANSMISSION LOSS (Fenestration,


Q= Area× Shading Coefficient × Solar Heat Gain Factor)
Solving for SHGF
Time of year: August 24 & April 20
Time of day: 11 am
10 ° North Latitude 18 ° North Latitude 20 ° North Latitude
East West East West East West
46 14 SHGFE SHGFW 51 14
Table 15, MHVAC
BTU
SHGFE =50
hr ∙ ft 2
BTU
SHGFW = 14
hr ∙ ft 2

West Glass Window


Description SC
¼” Clear 0.94
From Table 9-10, MHVAC by Clifford
Glass window area = 102.029 ft 2

BTU
(
Q= 14
hr ∙ ft )
2
( 102.029 ft 2 ) (0.94)

BTU
Q=1342.702
hr
East Glass Door
Description SC
¼” Clear 0.94
From Table 9-10, MHVAC by Clifford
Glass Door Area = 20.964 ft 2

BTU
(
Q= 50
hr ∙ ft )
2
( 20.964 ft 2 ) (0.94)

BTU
Q=985.308
hr
INDOOR LOADS

People
Let:
Number of occupants = 10 people
BTU
Sensible heat of a person = 230
hr
BTU
Sensible heat of a person = 190
hr

Qsensible =No. of people× Sensible Heat Factor

BTU
Q sensible =10 ×230
hr
BTU
Q sensible =230 0
hr

Qlatent =No. of people× Latent Heat Factor

BTU
Q latent =10 ×190
hr
BTU
Qlatent =1900
hr

Lightings
Description Wattage Rating Quantity Total Wattage
LED fluorescent tube 15 Watts 5 75 Watts

BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=75 Watts ×3.4
hr ∙ Watts
BTU
Q=255
hr

Appliances
Description Wattage Rating Quantity Total Wattage
Desktop Computer 200 Watts 2 400 Watts
Laptops 65 Watts 6 390 Watts
Water Disperser 80 Watts 2 160 Watts
Electric fans 40 Watts 4 160 Watts
Total 1110 Watts

BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=1110 Watts ×3.4
hr ∙Watts
BTU
Q=3774
hr

VENTILATION/ FILTRATION/ AIR CHANGE

CFM
Q sensible =No. of people × 7.5 ×∆ T × 1.08
person
CFM
Q sensible =10 people ×7.5 × 19.8℉ ×1.08
person
BTU
Q sensible =1603.8
hr

CFM
Q latent =No. of people× 7.5 × Specific Humidity Difference ×0.68
person
CFM grain
Q latent =10 ×7.5 ×52.4475 × 0.68
person lb
BTU
Q latent =2674.823
hr