North Wall
Wood Thickness Code R
¼“ RW
1 B7 1.19
2 B10 2.39
RW =0.2 9
Q=
( 2.861 hrBTU
∙ ft ∙ ℉ )
2
2
( 294.681 ft ) (19.8 ℉ )
BTU
Q=2040.099
hr
East Wall
Construction Material Code R
Outside Air A0 0.333
1” Plaster A1 0.208
4” Concrete Block C3 0.71
1” Plaster A1 0.208
Inside Air E0 0.685
Total 2.144
From Table 9-7, MHVAC by Clifford
East side area = 163.674 ft 2
Glass door area = 20.964 ft 2
1 BTU
Q=
( 2.148 hr ∙ ft ∙ ℉
2 )
( 142.71 ft 2 ) (19.8 ℉)
BTU
Q=1317.938
hr
South Wall
Construction Material Code R
Inside Air E0 0.685
¼ “Plywood - 0.29
Air Space B1 0.91
¼ “ Plywood - 0.29
Inside Air E0 0.685
Total 2.86
From Table 9-7, MHVAC by Clifford
South side area = 313.408 ft 2
BTU
(
Q= 2.9 2
hr ∙ ft ∙ ℉ )
( 313.408 ft 2 ) (19.8 ℉)
BTU
Q=2169.748
hr
West Wall
Construction Material Code R
Outside Air A0 0.333
1” Plaster A1 0.208
4” Concrete Block C3 0.71
1” Plaster A1 0.208
Inside Air E0 0.685
Total 2.144
From Table 9-7, MHVAC by Clifford
West side area = 163.674 ft 2
Glass window area = 102.029 ft 2
1 BTU
Q=
( 2.148 hr ∙ ft ∙ ℉
2 )
( 61.645 ft 2 ) (19.8 ℉ )
BTU
Q=569.296
hr
Ceiling
Construction Material Code R
Inside Air E0 0.685
¼ “Plywood - 0.29
Air Space B1 0.91
12” Concrete C11 1.08
1” Plaster A1 0.208
Inside Air E0 0.685
Total 3.858
From Table 9-7, MHVAC by Clifford
Ceiling area = 440.465 ft 2
1 BTU
Q=
( 3.858 hr ∙ ft ∙ ℉ )
2
2
( 440.465 ft ) ( 19.8℉ )
BTU
Q=2260.551
hr
BTU
(
Q= 0.45 2
hr ∙ ft ∙ ℉ )
( 18.727 ft 2 ) (19.8 ℉ )
BTU
Q=166.858
hr
BTU
(
Q= 1.092 2
hr ∙ ft ∙℉ )
( 102.029 ft 2) (19.8℉ )
BTU
Q=2206.03
hr
BTU
(
Q= 0.8505 2
hr ∙ ft ∙ ℉ )
( 20.964 ft 2 ) (19.8 ℉ )
BTU
Q=346.077
hr
BTU
(
Q= 14
hr ∙ ft )
2
( 102.029 ft 2 ) (0.94)
BTU
Q=1342.702
hr
East Glass Door
Description SC
¼” Clear 0.94
From Table 9-10, MHVAC by Clifford
Glass Door Area = 20.964 ft 2
BTU
(
Q= 50
hr ∙ ft )
2
( 20.964 ft 2 ) (0.94)
BTU
Q=985.308
hr
INDOOR LOADS
People
Let:
Number of occupants = 10 people
BTU
Sensible heat of a person = 230
hr
BTU
Sensible heat of a person = 190
hr
BTU
Q sensible =10 ×230
hr
BTU
Q sensible =230 0
hr
BTU
Q latent =10 ×190
hr
BTU
Qlatent =1900
hr
Lightings
Description Wattage Rating Quantity Total Wattage
LED fluorescent tube 15 Watts 5 75 Watts
BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=75 Watts ×3.4
hr ∙ Watts
BTU
Q=255
hr
Appliances
Description Wattage Rating Quantity Total Wattage
Desktop Computer 200 Watts 2 400 Watts
Laptops 65 Watts 6 390 Watts
Water Disperser 80 Watts 2 160 Watts
Electric fans 40 Watts 4 160 Watts
Total 1110 Watts
BTU
Q=Total Wattage× 3.4
hr ∙ Watts
BTU
Q=1110 Watts ×3.4
hr ∙Watts
BTU
Q=3774
hr
CFM
Q sensible =No. of people × 7.5 ×∆ T × 1.08
person
CFM
Q sensible =10 people ×7.5 × 19.8℉ ×1.08
person
BTU
Q sensible =1603.8
hr
CFM
Q latent =No. of people× 7.5 × Specific Humidity Difference ×0.68
person
CFM grain
Q latent =10 ×7.5 ×52.4475 × 0.68
person lb
BTU
Q latent =2674.823
hr