Professional Documents
Culture Documents
04 Shankar Rajasekaran - Design and Testing of Unidirectional Air Flow Systems
04 Shankar Rajasekaran - Design and Testing of Unidirectional Air Flow Systems
Source : www.cdc.gov/ophss/csels/dsepd/ss1978/lesson1/section10.html
Contamination
Can be controlled by
- Stringent procedural protocols
Surface
- Regular & proper cleaning
CONTAMINANTS
Airborne Difficult to detect and remove
Note : Liquid phase contaminants suspended in air behave as Solid phase contaminants
Sources of Contaminant ingress in an OR
• Door, wall and ceiling gaps.
• HVAC system
• Personnel traffic
• Material traffic
• Internal generation from procedures
Basic concepts in Contamination Control
• Source limitation
• Personnel protocols
• Procedural protocols
• Primary (physical) barriers
• Layouts
• Anterooms
• Graded isolation
• Secondary (indirect) barriers
• Pressure differentials
• Air flow patterns
• Purging
• Removing internally generated contaminants
• Dilution
• Supplying clean air
Active part of the system
• Once the boundary structures are thoroughly cleaned, they are less
likely to generate contaminants immediately.
• Moreover, they cannot help in removing the internally generated
contaminants.
• It is the HVAC system that is capable of removing the internally
generated contaminants on a real time basis.
• Also the HVAC system is be capable of limiting the ingress of
contaminants into the OR.
Requirements of a HVAC system for OR
• Should maintain temperature and relative humidity requirements.
• Should add adequate amount of out side air to ensure gaseous
contaminants are kept under control.
• Should ensure that only negligible or insignificant levels of contaminants
are introduced –
• Adequate air filtration in the supply air circuit.
• Should be capable of removing the internally generated contaminants. –
• Providing streamlined air flow over critical area without eddies or swirls.
• Suitable positioning of supply and return air points
• Providing adequate air changes
• Should be capable of limiting the ingress of contaminants through door,
wall and ceiling gaps –
• Building adequate positive pressure
• By building adequate levels of primary barriers
Eddies / Swirls as a reservoir of contaminants
• Eddies in air flow have a negative pressure core.
• This negative pressure holds up contaminants and obstructs their
removal.
• Eddies do not have a precise and constant structure / size and hence
their capability to hold on to the contaminants is also not constant.
Negative
pressure
core
Streamlined air flow Turbulent air flow
Source: http://www.arch.ttu.edu/courses/2013/fall.htm
Laminar Air Flow
• Streamlined unidirectional flow
• Absence of eddies or swirls in the flow
• Represented by Reynolds number,
• Re < 2000 is laminar
• Re 2000 to 4000 is transitional
• Re > 4000 is turbulent
Reynolds number, Re
• Ratio of inertial forces to viscous forces.
• It is a dimension less number.
• If viscous forces are dominant, flow will be laminar and if inertial forces are
dominant, flow will be turbulent.
• Re = pVD / u, where,
p = Density of air V = velocity of air
D = Diameter of flow u = viscosity of air
• Lower velocity gives lower Re and hence laminar flow
• But Re is also proportional to D, which is the diameter of the duct or the pipe in
which the fluid flows
Unidirectional Air Flow (UDAF)
• IEST RP CC 002.3 – Unidirectional Flow Clean Air Devices
• Air flow in a single direction through a clean air device or a clean zone with
essentially parallel stream lines.
• Air flow characterised by deviation of not more than 14 degrees from the
straight line flow through the work zone
• Measured using Relative Standard deviation of air velocity normal to the
plane of air flow.
• RSD = (std dev / av ) x 100
• RSD less than 15% can be classified as unidirectional flow.
Unidirectional Air Flow
• ISO 14644 – 3 : 2003 - Cleanrooms & Associated controlled
environments
• Controlled air flow through the entire cross section of a critical zone with a
steady velocity and approximately parallel streamlines.
• This type of air flow results in a directed transport of particles away from the
clean zone.
• Air flow pattern in which the point to point readings of velocities are within a
defined percentage of the average air flow velocity (typically with +/- 10 %).
UDAF system Vs Turbulent flow system.
UDAF System Turbulent flow system
Low face velocity High face velocity
High level of velocity uniformity Low level of velocity uniformity
Non aspirating flow Aspirating flow
Low occurrence of flow vortices High occurrences of flow vortices
Smooth parallel flow lines Irregular and chaotic flow lines
Near constant velocity Fluctuating velocity
Non mixing flow Mixing flow
Benefits of using a UDAF Ultra Clean system
• Effective in removing away the contaminants generated from within
the critical work zone quickly.
• Protects the critical work zone against contaminant ingress from less
critical surrounding areas due to non aspirating character.
• Supplies clean air over the critical zone.
Turbulent Vs Unidirectional Air flow OR
Actual Site Values
Particle Average Particle Average Particle Maximum allowable
sizes in concentration concentration measured particle
micro measured on the on the Operating table concentration for
metres Operating table in a in a Unidirectional Air achieving ISO Class 5 ,
Turbulent Air flow OR flow OR in particles per ISO 14644-1 : 2015 in
In particles per cubic cubic foot particles per cubic
foot foot
0.3 60625 85 290
0.5 13111 45 100
1 3400 21 24
3 671 4 -
5 109 1 8
10 9 0 -
Components of a UDAF system
• Duct connecting collars
• Air flow controllers
• Air flow stabilisers
• Up stream plenum
• Air Filters
• Down stream plenum
• Diffusers
• Exit air pick up
Volume control Upstream plenum
damper
Ideally,
V1 << V2,
P1 >> P2
Consider
this as the V2 is a function of P1
discharge
plenum V2 not a function of V1.
side
This will provide laminar flow
Assume this constriction Consider this as
as the perforation in the the OR side
diffuser
Diffusers to achieve UDAF
• 2012 - ASHRAE Handbook – HVAC Systems & Equipment describes
• Defines Laminar Flow diffusers as those having a free area (open area of
perforation for air flow) of less than 35%.
• ASHRAE standard 170 : 2013 - Ventilation of Healthcare Facilities
• Advises use of Group “E” Non aspirating Diffusers for operating Rooms.
• HTM – 03 – 01 : 2007 – Specialised ventilation for Healthcare
premises
• Advises use of Plenum type laminar flow style diffusers. (Note : These are not
true laminar flow systems in the strict sense of the word, but produce
downward displacement parallel flow air distribution)
Considerations for Laminar Air Flow Diffusers
Discharge plenum side Perforation Supply Air
X Diffuser
D
OR Side
5D
Source :
ASHRAE Journal
article Feb 2014 –
Improving
operating room
contamination
control
MULTIPLE ARRAY DIFFUSER
SINGLE LARGE DIFFUSER
40
SINGLE LARGE DIFFUSER
41
RESULT FROM ASHRAE STUDY
Source :
ASHRAE Journal article
Feb 2014 – Improving
operating room
contamination control
Problems at site
• Damaged filters
• Improper filter installation
• Improper fitment of laminar diffusers
• Static charge build up on synthetic diffuser screens leading to
contamination build up.
• Air leakage through the Surgical pendent chute
• Improper insulation of the Surgical pendent chute
• Duct leakage
• Improper positioning and sizing of return air suction points
• Improper air balancing
• Improper testing methods
Thank you for your attention