You are here: Home » Features » Supplementary Grounding Electrodes

Supplementary Grounding Electrodes


[ 0 ] By Michael Johnston | September 4, 2002 | IAEI September-October 2002

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 2 of 9

Figure 1. When supplementary electrodes are installed, they also


must be connected to the equipment, which is connected to the
required equipment grounding conductor

Electrical systems and non-current-carrying metal parts of equipment in an electrical installation generally are required to
be grounded; however, alternatives are given within the NEC that relax the grounding rules for equipment. These
alternatives include isolation, insulation, or guarding as methods of providing equal and effective safety measures without
grounding the metal parts or equipment. It is important to meet all of the provisions of the Code when utilizing any of these
alternatives.

Electrical systems and associated metal equipment, such as metallic raceways and cables, are grounded as required;
however, some electrical systems are not required to be grounded but are permitted to be operated grounded or
ungrounded. Whether systems are grounded as a requirement of 250.20 or grounded by choice, all of the rules for
grounded systems must be followed. When a system is grounded, one conductor of the system itself is intentionally
grounded. When equipment is grounded, it is connected to the earth or some conducting body serving in place of the earth
to minimize differences of potential between the metal component and the earth.

Grounded is defined in Article 100 as “Connected to the earth or to some conducting body that serves in place of the earth.”

Grounding electrode is not defined in the Code but can be described as: “”A conducting element used to connect electrical
systems and/or equipment to the earth.”" The grounding electrode establishes a connection to the earth of lowest practical
impedance to put system-grounded conductors and metal equipment of the system at earth potential.

Function

The earth is considered to be at the potential of zero, the potential one tries to achieve when grounding or earthing systems
and metal equipment associated with the system. The primary purpose of the grounding electrode is to establish and
maintain the electrical equipment and any grounded system conductor at the potential of the earth at the grounding
electrode connection to the earth. The grounding electrode has little or no affect in facilitating overcurrent device operation
and should never be relied upon for this purpose. To rely on the grounding electrode and the earth to serve as a low-
impedance return path to the source is a serious misapplication and violates fundamental principles of safety.

Another essential function of the grounding electrode is to dissipate overvoltages into the earth. Overvoltages can be
caused by different events that occur, such as high-voltage conductors being accidentally connected to the lower-voltage
system by a failure in a transformer, by an overhead conductor dropping on the lower-voltage conductor, or from lightning
strikes in the vicinity of the electrical system and equipment.

Section 250.24(C) requires the equipment grounding conductors, the service-equipment enclosures, and, where the system
is grounded, the grounded service conductor to be connected to a grounding electrode. The conductor used to make this
connection is the grounding electrode conductor.

Supplementary Electrode
When something is supplementary to another, it usually indicates that both are used to achieve one goal. For example, if
the amount of vitamins one takes is shown to be inadequate for minimum daily requirements, a vitamin supplement can be
used to provide the amount desired, but vitamins cannot serve in place of normal food consumption.

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 3 of 9

Although the term supplementary electrode is not defined in the NEC, it can be thought of as an electrode that is over and
above the minimum requirements of the NEC, an addition to any safety grounding or bonding circuit of the electrical
installation. Supplementary electrodes serve to make a connection to the earth that is local to the equipment needing the
supplement. It is imperative that the required equipment grounding conductor remains connected to the equipment also.
This is reinforced by the mandatory provision that the earth shall not be used as the sole equipment grounding conductor.
This language is found in 250.4(A)(5), 250.4(B)(4), and 250.54.

Example Installations
An example of supplementary grounding electrode is a grounding electrode installed at a light pole base in a parking lot.
This grounding electrode at the pole base serves to connect the metal pole to the earth and the equipment grounding
conductor at that location. The NEC does not require this electrode, but does provide minimum rules when such electrodes
are installed. The electrode serves to put the metal pole at the earth potential at the pole location and supplements the
required equipment grounding conductor connected to the pole. Another ancillary function of this electrode includes
dissipation of lightning strikes on the lighting pole by providing a direct path for the strike into the earth at the pole location,
thus enhancing system safety and personnel safety.

Another example of a supplementary electrode is an electrode that would be installed in the local vicinity of sensitive
electronic equipment. This electrode installation is generally installed as an option or as a recommendation by a
manufacturer of the equipment and is primarily directed toward performance. When such electrodes are installed, they also
must be connected to the equipment, which is connected to the required equipment grounding conductor (see figure 1).
Electronic data processing equipment is not permitted to be operated ungrounded or by connection to only its own
grounding electrode.

Section 250.52 provides a list of electrodes that are permitted to be used when grounding electrical systems and/or
equipment. A change in the 2002 edition of the Code removed the word made in reference to certain grounding electrodes.
Generally, the electrode is not made by the installer but rather installed. One of the more common supplementary
grounding electrodes is the familiar grounding rod. Where a ground rod is installed, it is required to be in contact with the
earth for a minimum of 8 ft. Alternative provisions are provided to accomplish ground rod installation when rock bottom is
encountered.

Down to Earth
The NEC provides minimum provisions in this case and many supplementary ground rods used for sensitive electronic
equipment far exceed these rules. The important item to remember is safety first, then enhancements directed toward
electronic equipment performance. Generally speaking, a premises wiring system that meets the requirements of the NEC
relative to grounding and bonding will be a stable platform in which to provide grounding enhancements. It is common in the
IT industry to be concerned with power quality issues. Many power quality organizations insist on a thorough grounding and
bonding system analysis prior to application of filtering equipment.

It is common during the grounding and bonding system analysis to discover grounding and bonding connections in
locations other than those permitted by the Code that require correction prior to any effective application of noise filters to
the system. During these surveys, supplemental grounding electrodes are often discovered and improper connections to
these electrodes are revealed. It is important to get back to basics at this point and the basics in this sense has to include
verification that equipment grounding conductors (safety grounds) are always connected. Safety first, then work on
enhancing equipment performance. This does not discount the importance of reducing data errors due to RF interferences
and EMI in the grounding circuit(s), because these are critical issues also. It is always better to approach this situation with
the best of both worlds in mind. One should not be installed without the other.

Isolated Grounding Circuits

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 4 of 9

Figure 2. A closer inspection reveals that the isolated equipment


grounding conductor was installed and connected to the receptacle,
but was routed directly to a ground rod

The NEC includes provisions for installation of isolated equipment grounding conductors for the reduction of
electromagnetic interferences in electronic equipment. In these provisions, it is clear that the earth shall not be used as the
sole equipment grounding conductor. A situation once came up where I was checking the polarity of an isolated grounding
type (IG) receptacle installed for a cash register and found it to read “no ground.” A closer inspection revealed that the
isolated equipment grounding conductor was installed and connected to the receptacle, but was routed directly to a ground
rod. This is not considered an isolated grounding conductor for the purposes of 250.146(D) or 250.96 (see figure 2). In this
case, the earth was relied upon for the equipment grounding conductor (safety ground). A ground fault would attempt to
flow through the earth to the source, but would be limited by this high impedance path. This is a common and serious
violation that can be attributed to lack of knowledge of the purpose of grounding and bonding.

Rod Pipe or Plate Electrodes

Figure 3. Electrodes consisting of a rode, pipe, or plate that do not


have a resistance to ground of 25 ohms or less must not be
installed less than 1.8 m (6 ft) apart or less than indicated in the
manufacturer's installation instructions, if applicable

Where a rod, pipe or plate electrode is installed for a system or service due to the lack of any electrodes required by 250.52
(A)(1) through (A)(4), it is required to have a resistance of not more than 25 ohms-to-ground. Where the resistance is in
question, an additional electrode can be installed and at that point no maximum resistance would be required.

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 5 of 9

Resistance of installed rod, pipe, or plate electrodes is important and applicable to these types of electrodes when installed
as a requirement of the Code. “A single electrode consisting of a rod, pipe, or plate that does not have a resistance to
ground of 25 ohms or less shall be augmented by one additional electrode of any of the types specified by 250.52(A)(2)
through (A)(7).”1 These electrodes must not be installed less than 1.8 m (6 ft) apart or less than indicated in the
manufacturer’s installation instructions, if applicable. “The paralleling efficiency of rods longer than 2.5 m (8 ft) is improved
by spacing greater than 1.8 m (6 ft)”2 as the possibilities of their effective resistance areas overlapping are reduced (see
figure 3).

Figure 4. Generally, an additional supplementary electrode is


connected to the equipment at the same location where the
equipment grounding conductor is connected to the apparatus

Electrodes installed as supplementary do not have to meet the maximum resistance to ground requirements of 250.56 or
the requirements for bonding all electrodes together as indicated in 250.50 and 53(C). Typically, when an additional
supplementary electrode is installed, it provides ground reference local to the equipment to which it is connected.
Generally, it is connected to the equipment at the same location where the equipment grounding conductor is connected to
the apparatus (see figure 4).

Supplementary Electrodes Compared to Supplemental Electrodes


Unlike supplementary electrodes covered by 250.54, the supplemental electrodes referred to in 250.53(D)(2) are required
where an underground metal water pipe is used as the electrode required by 250.50

Figure 5. Where the supplemental electrode is a rod, pipe, or plate


type, it should comply with 250.56 for maximum resistance or an
additional electrode can be installed

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 6 of 9

“A metal underground water pipe” electrode for a system or service “shall be supplemented by an additional electrode of a
type specified in 250.52(A)(2) through (A)(7). Where the supplemental electrode is a rod, pipe, or plate type, it shall comply
with 250.56 for maximum resistance or an additional electrode can be installed. The supplemental electrode shall be
permitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the nonflexible
grounded service raceway, or any grounded service enclosure”3 (see figure 5).

“Where the supplemental electrode” for the water pipe “is a rod, pipe, or plate electrode, that portion of the bonding jumper
that is the sole connection to the supplemental grounding electrode shall not be required to be any larger than 6 AWG
copper wire or 4 AWG aluminum.…”4

Part III of Article 250 covers the requirements for grounding electrodes and the grounding electrode system. The electrode
system for a service or system is specified in 250.50. The electrodes permitted to be used for grounding services or
systems are included in 250.52(A). Electrodes covered by 250.54 overlay the required grounding electrodes for a service or
separately derived system. Grounding electrodes should never be used as the only safety grounding circuit for equipment.
The earth is a high impedance path and shall not be used as the sole equipment grounding conductor as indicated in
250.54. Supplemental electrodes are permitted by the Code, but their installation must be in addition to the required safety
grounding circuit (the equipment grounding conductor) and should not affect the safety of the circuit or system. It serves to
enhance the required grounding and bonding circuits.

Always refer to the local authority having jurisdiction for any local requirements or when in doubt as to the minimum
requirements for supplementary grounding electrodes or what to look for when installing or inspecting these types of
grounding connections. It never hurts to ask when in doubt.

1 NFPA 70, National Electrical Code, 250.56 Resistance of Rod, Pipe, and Plate Electrodes, (National Fire Protection
Association, 2002). 70-106.

2 NFPA 70, 250.56 FPN, 70-106.

3 NFPA 70, 250.53(D)(2), 70-105.

4 NFPA 70, 250.53(E), 70-105.

Tags: grounding, grounding-electrode

Category: Features, September/October 2002

(No Ratings Yet)

About Michael Johnston: Michael Johnston is NECA’s executive director of standards and safety. Prior to working with
NECA, Mike worked for the International Association of Electrical Inspectors as the director of education, codes and
standards. Mike is a member of the IBEW and has experience as an electrical journeyman wireman, foreman and project
superintendant. Mike achieved all electrical inspector certifications through IAEI and ICC and has worked as an electrical
inspector and electrical inspection field supervisor for the city of Phoenix, AZ. Mike achieved a B.S. in business
management from the University of Phoenix. Mike is the chairman of the NEC Correlating Committee and served on NEC
CMP-5 in the 2002, 2005, 2008, and chair of CMP-5 representing NECA for the 2011 NEC cycle. Johnston is an active
member of ANSI, IAEI, NFPA, ASSE, the NFPA Electrical Section, Education Section, the UL Electrical Council, and
National Safety Council. .

Comments are closed.

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 7 of 9


• Archives

>> Home

>> Archives

>> Articles by Keywords

>> Articles by Author

>> Get newsletter

>> Sitemap

• Sections

◦ Digital Editions
◦ Features
■ Perspectives on PV
◦ Departments
■ Australian Perspective
■ Canadian Code
■ Canadian Perspective
■ Editorial
■ Focus on the Code
■ Safety in Our States
■ The Other Code
■ UL Question Corner
◦ Industry News
◦ Blogs
■ Greg Smith
■ Tim McClintock

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 8 of 9

• Categories

Select Category

• Recent Comments

◦ John Shannon on Transitioning Between Raceways


◦ Ronald L. Sprague, P.E. on Energy Alternatives and NEC Implications
◦ Adam Krause on Transitioning Between Raceways
◦ Thomas Ferguson on Standard Motor Control Circuits
◦ IAEI on GFCI and AFCI Basics

• Pages

◦ About
■ Editorial Team
■ Privacy Statement
■ Terms and Conditions
◦ Advertise
◦ Articles by Topic
◦ Contact Us
■ Subscribe
◦ Contribute
◦ IAEI Magazine Sitemap
◦ IAEI Magazine — Index of Authors
◦ Magazine Archive
◦ Permissions

IAEI, as the keystone of the electrical industry, is a membership driven, non-profit


association promoting electrical safety throughout the industry by providing premier
education, certification of inspectors, advocacy, partnerships and expert leadership in
Electrical Codes and Standards development.

• Permission

The material on this site may not be reproduced, distributed, transmitted, cached or
otherwise used, except with the prior written permission of International Association of
Electrical Inspectors (IAEI).

View permission policy

• IAEI Blog

◦ About
◦ Advertise
◦ Permissions
◦ Contribute
◦ Subscribe
◦ Terms and Conditions

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012
Supplementary Grounding Electrodes - IAEI Magazine : IAEI Blog Page 9 of 9

◦ Contact Us

• Search

• enter search terms

Copyright © IAEI Magazine 2012. All rights reserved. | Privacy | Legal Notice | Site
Map

Bad Behavior has blocked 2666 access attempts in the last 7 days.

http://www.iaei.org/magazine/2002/09/supplementary-grounding-electrodes/ 10/7/2012

You might also like