COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1

1C1 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1666.9 -31.0 35.1 1650.8 64.2 -73.1
2 1697.0 -31.2 36.1 1680.9 65.8 -75.7
3 1666.5 -31.0 35.2 1650.3 64.2 -73.2
4 1112.8 -16.3 23.8 1096.6 32.9 -49.1
5 1270.3 -30.4 18.7 1254.2 63.1 -39.4
6 1668.2 -30.8 35.2 1652.1 64.2 -73.1
7 1268.3 -30.6 21.7 1252.2 63.1 -41.0
8 1111.7 -17.2 23.1 1095.6 33.1 -48.8
9 1668.2 -30.9 31.9 1652.1 64.2 -71.4
10 1696.7 -30.6 36.8 1680.6 65.6 -76.0
11 1666.5 -31.0 35.2 1650.3 64.2 -73.2
12 1361.4 8.4 26.7 1347.6 35.2 -59.4
13 1417.6 -59.8 31.6 1403.8 71.4 -61.9
14 1435.5 -24.9 71.4 1421.7 52.8 -83.6
15 1343.6 -26.5 -13.1 1329.7 53.8 -37.8
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1696.7 - 1696.7
M1 (kN.m) 65.6 33.9 0.0
M2 (kN.m) -76.0 -33.9 -109.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.424 Le1/b1 = 5.3 < 15.0 400
Beta = 0.50 Le2/b2 = 5.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 8.9 / 8.3 kN As (Required): %1.07 1717.50 mm2 8T20
vc'(1/2)= 1.08 / 1.01 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.06 / 0.06 N/mm2
Links = R8-225

2C1 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1347.1 -90.3 102.2 1331.0 86.4 -96.2
2 1369.8 -91.7 105.7 1353.7 86.5 -99.4
3 1346.4 -90.4 102.2 1330.3 86.5 -96.0
4 901.9 -47.1 68.8 885.8 46.3 -64.7
5 1028.1 -88.4 55.2 1012.0 84.0 -52.4
6 1348.3 -89.8 102.6 1332.2 86.2 -96.4
7 1024.8 -88.8 57.3 1008.7 84.2 -54.8
8 900.9 -48.3 67.8 884.8 47.1 -63.9
9 1349.9 -90.2 99.8 1333.7 86.3 -93.5
10 1369.5 -91.0 106.3 1353.4 85.9 -100.0
11 1346.4 -90.4 102.2 1330.3 86.5 -96.0
12 1104.1 -60.3 83.1 1090.3 54.5 -78.0
13 1142.0 -89.6 86.5 1128.2 88.9 -81.5
14 1155.1 -74.7 108.4 1141.3 71.3 -105.5
15 1090.9 -75.3 61.2 1077.1 72.1 -54.0
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1369.5 - 1369.5
M1 (kN.m) -91.0 -27.4 0.0
M2 (kN.m) 106.3 27.4 160.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.342 Le1/b1 = 5.7 < 15.0 400
Beta = 0.60 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 57.7 / 44.5 kN As (Required): %1.38 2210.92 mm2 8T20
vc'(1/2)= 1.51 / 1.40 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.40 / 0.31 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2

3C1 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1021.2 -83.5 91.9 1005.1 86.4 -94.2
2 1037.7 -83.0 95.1 1021.6 85.4 -97.4
3 1020.5 -83.6 91.4 1004.4 86.4 -93.7
4 686.3 -45.3 61.7 670.1 47.4 -63.2
5 781.0 -80.6 50.5 764.8 83.1 -52.0
6 1022.3 -82.8 92.6 1006.1 86.0 -94.8
7 777.3 -81.1 49.7 761.2 83.4 -52.2
8 685.5 -46.6 60.7 669.3 48.4 -62.3
9 1024.5 -83.2 92.5 1008.4 86.2 -93.8
10 1037.5 -82.4 95.3 1021.3 84.8 -97.7
11 1020.5 -83.6 91.4 1004.4 86.4 -93.7
12 840.5 -58.7 75.1 826.7 57.7 -76.7
13 862.6 -79.8 77.3 848.8 85.6 -79.5
14 870.8 -68.9 93.0 857.0 71.3 -99.3
15 832.3 -69.6 59.5 818.5 72.0 -57.0
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1037.7 - 1037.7
M1 (kN.m) 85.4 20.8 0.0
M2 (kN.m) -97.4 -20.8 -157.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.259 Le1/b1 = 5.7 < 15.0 400
Beta = 0.70 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 54.8 / 64.1 kN As (Required): %0.98 1566.26 mm2 8T16
vc'(1/2)= 1.21 / 1.28 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.38 / 0.45 N/mm2
Links = R8-175

4C1 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 693.7 -86.7 94.1 677.6 85.7 -92.4
2 704.3 -85.6 97.4 688.2 84.1 -95.6
3 693.1 -86.8 93.5 677.0 85.8 -91.7
4 469.3 -47.8 63.1 453.1 47.8 -62.0
5 532.5 -83.1 52.2 516.3 81.9 -51.6
6 694.4 -85.9 95.0 678.3 85.0 -93.1
7 529.5 -83.7 50.6 513.3 82.4 -50.3
8 468.6 -49.1 62.1 452.5 48.8 -61.1
9 696.5 -86.4 95.5 680.4 85.5 -93.5
10 704.2 -85.1 97.5 688.1 83.8 -95.7
11 693.1 -86.8 93.5 677.0 85.8 -91.7
12 573.4 -65.6 77.4 559.6 61.0 -75.7
13 584.0 -78.4 78.7 570.1 81.2 -77.6
14 588.2 -71.7 88.8 574.4 70.8 -92.0
15 569.2 -72.2 67.3 555.3 71.4 -61.2
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 704.3 - 704.3
M1 (kN.m) -85.6 -14.1 0.0
M2 (kN.m) 97.4 14.1 165.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.176 Le1/b1 = 5.7 < 15.0 400
Beta = 0.80 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 55.4 / 60.3 kN As (Required): %1.06 1699.75 mm2 8T20
vc'(1/2)= 1.08 / 1.13 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.39 / 0.42 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3

5C1 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 363.5 -93.7 100.6 347.4 103.7 -111.3
2 368.8 -91.8 104.0 352.6 102.3 -115.1
3 363.2 -93.9 99.8 347.1 103.9 -110.6
4 250.2 -52.3 67.4 234.1 56.9 -74.3
5 281.9 -89.5 55.9 265.8 99.0 -61.6
6 363.8 -93.2 101.7 347.6 103.3 -112.8
7 280.1 -90.0 54.3 264.0 99.4 -60.6
8 249.8 -54.1 65.9 233.7 59.3 -72.5
9 365.3 -93.4 102.0 349.1 103.5 -112.1
10 368.9 -90.5 104.3 352.8 100.3 -115.5
11 363.2 -93.9 99.8 347.1 103.9 -110.6
12 302.0 -75.1 83.1 288.2 80.0 -91.8
13 305.4 -80.3 83.6 291.5 92.0 -92.9
14 306.9 -77.5 88.6 293.1 85.7 -102.2
15 300.4 -77.9 78.2 286.6 86.3 -82.5
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 368.8 - 368.8
M1 (kN.m) 102.3 7.4 0.0
M2 (kN.m) -115.1 -7.4 -206.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 5.7 < 15.0 400
Beta = 0.89 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 63.1 / 73.3 kN As (Required): %1.79 2866.75 mm2 12T20
vc'(1/2)= 0.94 / 1.01 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.44 / 0.51 N/mm2
Links = R8-225

6C1 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 37.4 -63.3 68.1 21.2 18.6 -12.7
2 36.7 -61.7 70.5 20.6 16.4 -12.8
3 37.2 -63.3 67.5 21.1 18.6 -12.3
4 34.0 -36.5 46.2 17.9 14.4 -11.0
5 34.5 -60.1 38.9 18.3 17.2 -9.2
6 37.3 -62.3 68.0 21.1 18.2 -12.8
7 34.1 -60.9 36.0 18.0 17.5 -8.1
8 34.0 -35.7 46.3 17.8 14.4 -10.9
9 37.7 -62.9 71.0 21.6 18.4 -13.8
10 36.8 -63.5 70.4 20.7 16.8 -12.9
11 37.2 -63.3 67.5 21.1 18.6 -12.3
12 31.8 -53.1 56.6 18.0 15.2 -10.7
13 32.1 -52.1 56.5 18.2 16.2 -10.8
14 32.2 -52.5 56.1 18.4 15.7 -11.6
15 31.7 -52.7 56.9 17.8 15.8 -9.9
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 36.8 - 36.8
M1 (kN.m) -63.5 -0.7 0.0
M2 (kN.m) 70.4 0.7 133.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 6.6 < 15.0 400
Beta = 0.99 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.3 / 28.3 kN As (Required): %1.24 1989.09 mm2 8T20
vc'(1/2)= 0.64 / 0.64 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.19 / 0.20 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4

1C2 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2214.0 -46.7 -24.2 2197.9 96.9 50.1
2 2254.0 -47.7 -25.5 2237.9 100.3 52.5
3 2121.3 -46.7 -25.4 2105.2 96.9 52.8
4 1455.0 -21.4 -15.1 1438.9 43.4 31.8
5 1804.5 -46.2 -11.6 1788.3 95.8 23.8
6 2215.6 -46.5 -24.1 2199.5 96.9 50.2
7 1807.2 -46.4 -8.5 1791.1 95.8 21.8
8 1452.0 -21.9 -15.9 1435.9 43.6 32.3
9 2210.4 -46.6 -27.5 2194.2 97.0 52.2
10 2255.4 -47.5 -24.7 2239.3 100.1 51.9
11 2121.3 -46.7 -25.4 2105.2 96.9 52.8
12 1808.7 -3.3 -23.0 1794.9 61.1 43.9
13 1867.5 -73.4 -17.1 1853.6 98.2 39.3
14 1891.7 -38.2 30.4 1877.8 79.6 1.5
15 1784.5 -38.5 -70.5 1770.7 79.8 81.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 2254.0 - 2254.0
M1 (kN.m) 100.3 45.1 118.3
M2 (kN.m) 52.5 45.1 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.563 Le1/b1 = 5.3 < 15.0 400
Beta = 0.34 Le2/b2 = 4.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 21.5 / 9.6 kN As (Required): %2.04 3258.50 mm2 12T20
vc'(1/2)= 1.56 / 1.51 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.15 / 0.07 N/mm2
Links = R8-225

2C2 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1778.2 -136.4 -70.3 1762.1 129.5 65.6
2 1808.6 -139.5 -73.8 1792.5 130.8 68.8
3 1704.1 -136.3 -74.2 1688.0 129.3 69.4
4 1171.6 -62.7 -44.4 1155.5 61.3 41.4
5 1449.5 -134.5 -33.3 1433.4 127.1 30.7
6 1779.7 -135.8 -69.9 1763.6 129.3 65.3
7 1460.9 -134.7 -29.3 1444.7 127.2 24.8
8 1169.0 -63.3 -45.8 1152.9 61.6 42.7
9 1766.2 -136.2 -74.7 1750.1 129.4 71.8
10 1809.7 -139.4 -72.8 1793.6 130.6 67.8
11 1704.1 -136.3 -74.2 1688.0 129.3 69.4
12 1456.8 -96.8 -61.6 1442.9 88.5 57.6
13 1496.1 -127.3 -55.2 1482.3 124.3 51.3
14 1511.2 -112.0 -11.2 1497.3 106.3 7.2
15 1441.7 -112.2 -105.6 1427.9 106.5 101.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1808.6 - 1808.6
M1 (kN.m) -139.5 -36.2 -174.4
M2 (kN.m) -73.8 -36.2 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.452 Le1/b1 = 5.7 < 15.0 400
Beta = 0.47 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 87.2 / 69.1 kN As (Required): %2.15 3432.59 mm2 12T20
vc'(1/2)= 1.97 / 1.98 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.61 / 0.48 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5

3C2 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1339.9 -126.2 -62.4 1323.8 131.0 62.8
2 1362.7 -126.2 -65.3 1346.6 130.9 65.7
3 1284.2 -126.0 -66.2 1268.1 130.8 66.6
4 885.5 -61.1 -39.4 869.4 63.7 39.7
5 1092.2 -123.2 -28.9 1076.0 127.7 28.8
6 1341.2 -125.5 -61.4 1325.1 130.6 61.9
7 1104.4 -123.6 -24.5 1088.3 127.9 23.2
8 883.5 -61.5 -40.9 867.4 64.0 41.1
9 1327.2 -126.0 -67.0 1311.1 130.9 68.6
10 1363.5 -126.5 -64.7 1347.3 130.9 65.1
11 1284.2 -126.0 -66.2 1268.1 130.8 66.6
12 1101.5 -92.8 -54.0 1087.7 93.2 54.5
13 1123.9 -114.6 -49.5 1110.1 122.1 49.6
14 1130.0 -103.6 -17.3 1116.1 107.5 15.3
15 1095.5 -103.8 -86.2 1081.7 107.7 88.9
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1362.7 - 1362.7
M1 (kN.m) 130.9 27.3 170.4
M2 (kN.m) 65.7 27.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.341 Le1/b1 = 5.7 < 15.0 400
Beta = 0.60 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 83.6 / 58.4 kN As (Required): %1.51 2415.93 mm2 8T20
vc'(1/2)= 1.57 / 1.57 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.59 / 0.41 N/mm2
Links = R8-225

4C2 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 901.0 -127.2 -62.5 884.8 119.4 61.1
2 916.7 -126.0 -65.2 900.6 116.7 63.8
3 863.5 -127.0 -66.5 847.4 119.1 65.1
4 598.5 -63.0 -39.7 582.4 60.7 38.8
5 734.7 -123.7 -28.6 718.6 115.8 27.8
6 901.8 -126.5 -61.2 885.7 118.9 60.0
7 745.0 -124.0 -24.0 728.9 116.1 22.3
8 597.2 -63.4 -41.2 581.0 60.9 40.3
9 890.3 -127.1 -67.2 874.2 119.3 66.8
10 917.2 -126.4 -65.0 901.0 117.0 63.5
11 863.5 -127.0 -66.5 847.4 119.1 65.1
12 743.4 -97.9 -53.3 729.5 87.5 52.3
13 753.6 -111.2 -50.5 739.8 108.6 49.2
14 754.2 -104.5 -29.4 740.4 98.0 25.6
15 742.7 -104.6 -74.4 728.9 98.2 75.8
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 890.3 - 890.3
M1 (kN.m) -127.1 -17.8 -177.0
M2 (kN.m) -67.2 -17.8 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.223 Le1/b1 = 5.7 < 15.0 400
Beta = 0.74 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 79.8 / 50.1 kN As (Required): %1.18 1888.84 mm2 8T20
vc'(1/2)= 1.26 / 1.27 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.56 / 0.35 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6

5C2 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 459.6 -156.1 -65.4 443.5 203.7 71.1
2 469.4 -154.8 -68.4 453.2 205.9 74.4
3 440.3 -155.8 -69.6 424.2 203.2 75.6
4 309.3 -77.3 -41.2 293.1 96.9 44.7
5 375.0 -151.3 -29.8 358.9 197.5 32.4
6 459.9 -155.4 -63.9 443.7 202.7 69.5
7 380.6 -151.8 -24.5 364.5 198.2 27.0
8 308.8 -77.7 -43.3 292.7 97.6 46.9
9 453.7 -155.8 -70.9 437.6 203.1 76.7
10 469.6 -155.0 -67.9 453.4 206.2 73.8
11 440.3 -155.8 -69.6 424.2 203.2 75.6
12 380.7 -125.8 -54.9 366.9 161.9 59.8
13 383.7 -130.7 -53.7 369.9 172.9 58.3
14 382.4 -128.2 -43.3 368.6 167.3 45.6
15 382.0 -128.4 -65.3 368.2 167.5 72.5
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 453.7 - 453.7
M1 (kN.m) 203.1 9.1 269.5
M2 (kN.m) 76.7 9.1 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.113 Le1/b1 = 5.7 < 15.0 400
Beta = 0.87 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 116.3 / 45.9 kN As (Required): %2.62 4198.38 mm2 16T20
vc'(1/2)= 1.07 / 1.10 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.81 / 0.32 N/mm2
Links = R8-225

6C2 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 27.7 -5.9 -42.3 11.6 0.0 6.8
2 27.7 -6.0 -43.9 11.6 0.0 6.9
3 26.7 -5.9 -45.2 10.5 0.0 7.9
4 28.1 -2.8 -27.8 12.0 0.0 6.3
5 25.4 -5.7 -18.8 9.3 0.0 2.9
6 27.7 -5.8 -42.3 11.6 0.0 6.7
7 29.7 -5.0 -16.2 13.6 0.0 -1.1
8 28.1 -2.7 -27.7 12.0 0.0 6.4
9 23.4 -6.5 -44.8 7.3 0.0 10.8
10 27.7 -6.1 -43.9 11.6 0.0 6.9
11 26.7 -5.9 -45.2 10.5 0.0 7.9
12 23.8 -4.0 -35.1 10.0 0.0 5.9
13 23.8 -5.6 -35.2 10.0 0.0 5.8
14 23.7 -4.8 -34.6 9.9 0.0 4.7
15 23.9 -4.8 -35.7 10.1 0.0 7.0
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 23.4 - 23.4
M1 (kN.m) -6.5 -0.5 0.0
M2 (kN.m) -44.8 -0.5 -51.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 7.2 < 15.0 400
Beta = 0.99 Le2/b2 = 5.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.2 / 18.5 kN As (Required): %0.43 688.35 mm2 8T16
vc'(1/2)= 0.55 / 0.55 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.01 / 0.13 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7

1C3 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2222.3 -46.8 24.3 2206.1 97.2 -50.5
2 2262.8 -47.8 24.9 2246.7 100.6 -52.3
3 2129.5 -46.8 25.5 2113.3 97.1 -53.2
4 1458.8 -21.5 15.8 1442.7 43.4 -32.5
5 1810.9 -46.3 11.2 1794.8 96.2 -23.6
6 2218.3 -46.5 24.3 2202.1 96.9 -50.4
7 2221.1 -47.1 27.1 2205.0 97.2 -52.3
8 1462.4 -21.8 15.0 1446.3 43.9 -32.0
9 1813.1 -46.2 8.0 1796.9 96.1 -21.7
10 2263.2 -47.7 25.7 2247.0 100.4 -52.9
11 2129.5 -46.8 25.5 2113.3 97.1 -53.2
12 1821.9 -2.9 17.1 1808.1 61.1 -39.6
13 1867.9 -74.0 23.1 1854.0 98.6 -44.3
14 1791.2 -38.6 70.6 1777.4 80.0 -82.0
15 1898.5 -38.2 -30.3 1884.7 79.7 -1.9
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 2263.2 - 2263.2
M1 (kN.m) 100.4 45.3 118.5
M2 (kN.m) -52.9 -45.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.566 Le1/b1 = 5.3 < 15.0 400
Beta = 0.34 Le2/b2 = 4.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 21.3 / 9.5 kN As (Required): %2.05 3284.72 mm2 12T20
vc'(1/2)= 1.56 / 1.51 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.15 / 0.07 N/mm2
Links = R8-225

2C3 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1784.8 -136.7 70.1 1768.7 129.5 -65.6
2 1815.4 -139.7 72.5 1799.3 130.8 -67.8
3 1710.6 -136.5 74.0 1694.5 129.3 -69.4
4 1175.0 -62.9 45.3 1158.8 61.3 -42.3
5 1454.7 -134.9 32.2 1438.6 127.3 -29.8
6 1781.7 -136.0 70.4 1765.6 129.4 -65.8
7 1774.9 -137.2 73.8 1758.7 129.9 -71.2
8 1177.3 -63.3 43.9 1161.2 61.5 -41.1
9 1465.5 -134.6 28.1 1449.3 127.1 -23.8
10 1816.1 -139.9 73.6 1800.0 130.8 -68.9
11 1710.6 -136.5 74.0 1694.5 129.3 -69.4
12 1466.3 -96.8 55.0 1452.4 88.3 -51.3
13 1497.4 -127.9 61.4 1483.6 124.6 -57.6
14 1447.0 -112.4 105.4 1433.2 106.5 -101.7
15 1516.6 -112.2 11.0 1502.8 106.3 -7.2
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1816.1 - 1816.1
M1 (kN.m) -139.9 -36.3 -174.6
M2 (kN.m) 73.6 36.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.454 Le1/b1 = 5.7 < 15.0 400
Beta = 0.47 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 87.4 / 69.0 kN As (Required): %2.16 3452.30 mm2 12T20
vc'(1/2)= 1.98 / 1.98 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.61 / 0.48 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8

3C3 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1345.0 -126.2 61.1 1328.9 131.0 -61.7
2 1367.7 -126.0 63.4 1351.6 130.7 -64.0
3 1289.2 -126.0 64.9 1273.1 130.7 -65.6
4 888.3 -61.4 39.4 872.2 63.9 -39.8
5 1096.1 -123.4 27.1 1080.0 127.9 -27.3
6 1342.7 -125.7 62.0 1326.5 130.7 -62.5
7 1333.8 -126.8 65.3 1317.7 131.5 -67.2
8 889.8 -61.2 37.9 873.7 63.8 -38.4
9 1107.9 -123.1 22.6 1091.8 127.6 -21.5
10 1368.5 -126.7 63.9 1352.4 131.1 -64.6
11 1289.2 -126.0 64.9 1273.1 130.7 -65.6
12 1107.6 -92.6 48.5 1093.8 92.9 -48.8
13 1126.2 -114.8 53.0 1112.4 122.4 -53.7
14 1099.6 -103.8 85.2 1085.8 107.7 -88.0
15 1134.2 -103.7 16.3 1120.4 107.6 -14.5
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1368.5 - 1368.5
M1 (kN.m) 131.1 27.4 169.8
M2 (kN.m) -64.6 -27.4 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.342 Le1/b1 = 5.7 < 15.0 400
Beta = 0.60 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 83.8 / 57.7 kN As (Required): %1.51 2414.91 mm2 8T20
vc'(1/2)= 1.57 / 1.58 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.59 / 0.40 N/mm2
Links = R8-225

4C3 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 904.3 -127.2 60.5 888.2 119.1 -59.3
2 919.9 -125.6 62.9 903.8 116.2 -61.6
3 866.8 -126.9 64.5 850.7 118.9 -63.3
4 600.4 -63.3 38.9 584.2 60.9 -38.2
5 737.3 -123.8 26.3 721.2 115.8 -25.6
6 902.8 -126.6 61.8 886.7 118.9 -60.5
7 894.6 -127.9 65.0 878.5 119.8 -64.7
8 601.2 -63.0 37.4 585.1 60.3 -36.7
9 747.3 -123.4 21.6 731.2 115.4 -19.9
10 920.5 -126.5 63.2 904.4 116.9 -61.9
11 866.8 -126.9 64.5 850.7 118.9 -63.3
12 746.6 -97.7 48.9 732.8 87.1 -47.7
13 755.8 -111.3 51.6 742.0 108.6 -50.8
14 745.4 -104.5 72.8 731.6 97.9 -74.3
15 757.0 -104.5 27.7 743.2 97.8 -24.2
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 894.6 - 894.6
M1 (kN.m) -127.9 -17.9 -176.1
M2 (kN.m) 65.0 17.9 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.224 Le1/b1 = 5.7 < 15.0 400
Beta = 0.74 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 79.9 / 49.0 kN As (Required): %1.17 1868.49 mm2 8T20
vc'(1/2)= 1.26 / 1.27 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.56 / 0.34 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9

5C3 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 461.2 -156.1 63.1 445.0 204.1 -68.6
2 470.9 -154.3 65.4 454.8 205.8 -71.2
3 441.9 -155.8 67.3 425.8 203.6 -73.1
4 310.1 -77.7 40.7 294.0 97.6 -44.1
5 376.2 -151.6 27.0 360.1 198.1 -29.5
6 460.4 -155.6 64.6 444.3 203.0 -70.3
7 455.7 -156.8 68.3 439.6 204.7 -73.9
8 310.6 -77.2 38.6 294.5 97.4 -41.8
9 381.7 -151.2 21.6 365.6 197.9 -23.9
10 471.2 -155.4 66.0 455.1 207.0 -71.8
11 441.9 -155.8 67.3 425.8 203.6 -73.1
12 381.9 -125.8 51.8 368.1 162.1 -56.2
13 385.1 -130.8 53.0 371.3 173.3 -57.7
14 383.3 -128.3 63.3 369.5 167.7 -70.4
15 383.8 -128.3 41.4 369.9 167.7 -43.5
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 455.7 - 455.7
M1 (kN.m) 204.7 9.1 268.6
M2 (kN.m) -73.9 -9.1 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.114 Le1/b1 = 5.7 < 15.0 400
Beta = 0.86 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 116.6 / 44.6 kN As (Required): %2.61 4177.43 mm2 16T20
vc'(1/2)= 1.07 / 1.10 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.82 / 0.31 N/mm2
Links = R8-225

6C3 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 27.6 -6.0 42.5 11.5 0.0 -6.7
2 27.6 -6.2 44.2 11.5 0.0 -6.8
3 26.6 -6.0 45.5 10.5 0.0 -7.8
4 28.0 -2.7 27.9 11.9 0.0 -6.3
5 25.4 -5.8 18.8 9.3 0.0 -2.7
6 27.6 -6.0 42.5 11.5 0.0 -6.8
7 23.3 -6.7 45.1 7.2 0.0 -10.7
8 28.0 -2.8 27.9 11.9 0.0 -6.1
9 29.7 -5.2 16.3 13.6 0.0 1.2
10 27.6 -6.1 44.2 11.5 0.0 -6.8
11 26.6 -6.0 45.5 10.5 0.0 -7.8
12 23.7 -4.1 35.4 9.9 0.0 -5.7
13 23.7 -5.7 35.3 9.9 0.0 -5.8
14 23.8 -4.9 35.9 10.0 0.0 -6.9
15 23.6 -4.9 34.8 9.8 0.0 -4.6
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 23.3 - 23.3
M1 (kN.m) -6.7 -0.5 0.0
M2 (kN.m) 45.1 0.5 51.7 400
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 7.2 < 15.0 400
Beta = 0.99 Le2/b2 = 5.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.2 / 18.6 kN As (Required): %0.44 696.14 mm2 8T16
vc'(1/2)= 0.55 / 0.55 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.02 / 0.13 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10

1C4 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1675.2 -30.8 -35.4 1659.1 64.1 73.5
2 1704.2 -31.0 -37.0 1688.0 65.8 76.3
3 1674.7 -30.9 -35.4 1658.6 64.2 73.6
4 1118.3 -16.4 -23.4 1102.1 32.7 49.0
5 1277.1 -30.5 -19.3 1261.0 63.2 39.6
6 1672.0 -30.7 -35.2 1655.8 64.1 73.3
7 1679.1 -31.2 -32.6 1663.0 64.2 71.9
8 1119.3 -16.2 -24.1 1103.2 32.9 49.4
9 1274.2 -30.2 -22.3 1258.0 63.1 41.3
10 1706.4 -31.2 -36.4 1690.3 65.7 76.0
11 1674.7 -30.9 -35.4 1658.6 64.2 73.6
12 1372.0 10.9 -31.8 1358.2 34.1 62.2
13 1420.8 -62.1 -26.9 1406.9 72.4 59.7
14 1350.4 -26.5 12.8 1336.5 53.8 38.1
15 1442.4 -24.7 -71.6 1428.6 52.7 83.8
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1704.2 - 1704.2
M1 (kN.m) 65.8 34.1 0.0
M2 (kN.m) 76.3 34.1 109.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.426 Le1/b1 = 5.3 < 15.0 400
Beta = 0.50 Le2/b2 = 5.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.7 / 8.4 kN As (Required): %1.09 1743.15 mm2 8T20
vc'(1/2)= 1.04 / 1.02 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.05 / 0.06 N/mm2
Links = R8-225

2C4 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1354.2 -90.7 -103.3 1338.1 86.3 96.9
2 1375.6 -91.4 -107.4 1359.5 86.1 100.7
3 1353.4 -90.7 -103.3 1337.3 86.3 96.7
4 907.0 -47.8 -68.8 890.8 46.5 64.5
5 1033.9 -88.9 -56.3 1017.8 84.1 53.2
6 1351.6 -90.2 -102.8 1335.5 86.3 96.5
7 1359.1 -91.1 -101.4 1343.0 86.6 94.7
8 907.3 -47.4 -69.9 891.2 46.1 65.4
9 1029.8 -88.6 -58.5 1013.7 83.9 55.6
10 1377.9 -92.3 -106.8 1361.8 86.4 100.1
11 1353.4 -90.7 -103.3 1337.3 86.3 96.7
12 1112.5 -59.1 -87.4 1098.7 52.8 82.1
13 1145.3 -91.4 -84.1 1131.5 90.4 78.6
14 1096.7 -75.5 -62.1 1082.9 72.0 54.6
15 1161.1 -75.0 -109.4 1147.2 71.2 106.1
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1377.9 - 1377.9
M1 (kN.m) -92.3 -27.6 0.0
M2 (kN.m) -106.8 -27.6 -161.9 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.344 Le1/b1 = 5.7 < 15.0 400
Beta = 0.60 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 57.5 / 45.1 kN As (Required): %1.41 2251.30 mm2 8T20
vc'(1/2)= 1.52 / 1.41 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.40 / 0.32 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11

3C4 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1026.9 -84.1 -93.6 1010.8 86.6 95.5
2 1042.2 -82.5 -97.0 1026.0 84.8 99.1
3 1026.2 -84.1 -93.1 1010.0 86.6 95.0
4 690.5 -46.8 -62.3 674.3 48.3 63.5
5 785.6 -81.3 -52.0 769.5 83.5 53.2
6 1025.0 -83.5 -92.7 1008.8 86.3 94.9
7 1031.8 -84.5 -94.4 1015.7 87.0 95.4
8 690.4 -45.7 -63.3 674.3 47.4 64.5
9 781.3 -81.1 -51.3 765.2 83.3 53.5
10 1044.2 -84.1 -96.8 1028.1 85.9 98.7
11 1026.2 -84.1 -93.1 1010.0 86.6 95.0
12 846.7 -58.3 -78.7 832.8 56.6 80.6
13 865.8 -81.2 -76.5 852.0 87.1 77.8
14 837.0 -70.0 -60.9 823.1 72.2 58.1
15 875.5 -69.5 -94.3 861.7 71.5 100.4
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1044.2 - 1044.2
M1 (kN.m) 85.9 20.9 0.0
M2 (kN.m) 98.7 20.9 158.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.261 Le1/b1 = 5.7 < 15.0 400
Beta = 0.70 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 54.8 / 64.9 kN As (Required): %1.02 1635.80 mm2 8T20
vc'(1/2)= 1.30 / 1.37 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.38 / 0.45 N/mm2
Links = R8-225

4C4 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 697.6 -87.4 -96.1 681.5 86.1 94.1
2 707.3 -85.0 -99.5 691.2 83.5 97.5
3 696.9 -87.5 -95.5 680.8 86.1 93.4
4 472.1 -49.3 -64.1 456.0 48.9 62.8
5 535.6 -83.9 -53.9 519.5 82.4 53.0
6 696.4 -86.8 -95.2 680.2 85.7 93.4
7 701.4 -87.8 -97.7 685.3 86.4 95.4
8 471.9 -48.1 -65.1 455.8 47.8 63.6
9 532.2 -83.6 -52.5 516.0 82.2 51.9
10 708.7 -86.8 -99.5 692.6 84.9 97.4
11 696.9 -87.5 -95.5 680.8 86.1 93.4
12 577.3 -65.5 -80.4 563.5 60.4 79.0
13 586.5 -79.5 -79.1 572.7 82.4 77.1
14 572.3 -72.7 -69.0 558.5 71.7 62.6
15 591.5 -72.3 -90.5 577.6 71.1 93.5
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 708.7 - 708.7
M1 (kN.m) -86.8 -14.2 0.0
M2 (kN.m) -99.5 -14.2 -168.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.177 Le1/b1 = 5.7 < 15.0 400
Beta = 0.80 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 55.3 / 61.3 kN As (Required): %1.10 1759.84 mm2 8T20
vc'(1/2)= 1.09 / 1.13 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.39 / 0.43 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12

5C4 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 365.4 -94.5 -102.9 349.3 104.5 114.2
2 370.3 -90.5 -106.7 354.2 100.4 118.4
3 365.0 -94.6 -102.1 348.9 104.6 113.3
4 251.4 -54.6 -68.2 235.3 60.0 75.4
5 283.4 -90.3 -58.0 267.3 99.9 64.2
6 365.0 -93.9 -101.8 348.9 103.5 112.8
7 367.6 -95.0 -104.5 351.5 105.2 115.2
8 251.3 -52.8 -69.7 235.1 57.9 77.1
9 281.3 -90.1 -56.5 265.2 99.6 63.3
10 370.9 -92.9 -106.4 354.7 103.6 118.0
11 365.0 -94.6 -102.1 348.9 104.6 113.3
12 303.7 -75.5 -85.6 289.9 80.1 95.2
13 306.7 -81.2 -85.1 292.9 93.2 94.1
14 301.9 -78.5 -80.1 288.1 86.8 84.8
15 308.4 -78.2 -90.5 294.6 86.4 104.5
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 370.9 - 370.9
M1 (kN.m) 103.6 7.4 0.0
M2 (kN.m) 118.0 7.4 210.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.093 Le1/b1 = 5.7 < 15.0 400
Beta = 0.89 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 63.2 / 75.0 kN As (Required): %1.84 2944.69 mm2 12T20
vc'(1/2)= 0.94 / 1.01 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.44 / 0.53 N/mm2
Links = R8-225

6C4 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 37.4 -63.8 -68.1 21.3 18.7 12.8
2 36.8 -63.4 -70.4 20.7 16.7 13.0
3 37.3 -63.8 -67.6 21.1 18.7 12.4
4 34.0 -35.3 -46.3 17.8 14.2 11.0
5 34.5 -60.7 -38.7 18.4 17.3 9.4
6 37.4 -64.5 -68.3 21.3 18.9 12.8
7 37.8 -63.6 -71.0 21.7 18.7 13.9
8 33.9 -35.5 -46.0 17.8 14.0 11.1
9 34.1 -60.8 -35.8 18.0 17.3 8.3
10 36.8 -62.5 -70.5 20.7 16.7 13.0
11 37.3 -63.8 -67.6 21.1 18.7 12.4
12 31.8 -53.4 -56.5 18.0 15.2 10.9
13 32.1 -52.5 -56.6 18.3 16.4 10.8
14 31.7 -53.1 -57.0 17.9 15.9 10.0
15 32.2 -52.9 -56.2 18.4 15.8 11.7
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 37.8 - 37.8
M1 (kN.m) -63.6 -0.8 0.0
M2 (kN.m) -71.0 -0.8 -134.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 6.6 < 15.0 400
Beta = 0.99 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.8 / 28.3 kN As (Required): %1.25 1999.25 mm2 8T20
vc'(1/2)= 0.64 / 0.64 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.19 / 0.20 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13

3C5 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2019.8 -1.0 220.4 2003.7 1.7 -227.5
2 1649.1 33.8 180.5 1633.0 -34.1 -186.0
3 2019.2 -1.2 220.2 2003.1 1.8 -227.2
4 1631.0 -35.6 176.0 1614.9 37.0 -181.8
5 1494.5 0.6 111.2 1478.3 -0.2 -114.9
6 2021.9 1.0 221.7 2005.8 -0.3 -228.5
7 1487.9 -1.2 108.9 1471.8 1.7 -114.0
8 1630.1 -38.6 175.4 1614.0 40.0 -181.0
9 2025.0 -0.6 221.7 2008.8 1.4 -227.3
10 1647.9 34.9 179.7 1631.8 -35.2 -185.7
11 2019.2 -1.2 220.2 2003.1 1.8 -227.2
12 1676.7 18.7 181.5 1662.9 -20.8 -187.1
13 1675.2 -20.3 182.0 1661.4 23.6 -188.0
14 1687.3 -0.3 189.5 1673.5 0.9 -200.4
15 1664.6 -1.3 174.0 1650.8 1.9 -174.7
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 2021.9 - 2021.9
M1 (kN.m) 1.0 40.4 0.0
M2 (kN.m) -228.5 -40.4 -245.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.505 Le1/b1 = 5.0 < 15.0 400
Beta = 0.41 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 130.0 kN As (Required): %3.48 5563.01 mm2 20T20
vc'(1/2)= 1.68 / 2.30 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.91 N/mm2
Links = R8-225

4C5 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1361.1 -1.8 225.6 1345.0 2.6 -217.9
2 1113.1 33.9 184.7 1097.0 -32.8 -178.3
3 1360.6 -2.0 225.3 1344.5 2.8 -217.4
4 1101.1 -37.0 180.2 1084.9 37.2 -174.1
5 1010.7 0.3 114.3 994.5 0.5 -110.8
6 1362.2 1.0 226.9 1346.1 -0.3 -218.8
7 1005.8 -2.0 111.7 989.7 2.7 -108.3
8 1100.8 -40.8 179.7 1084.7 41.0 -173.6
9 1365.2 -1.3 227.3 1349.1 2.2 -219.4
10 1112.3 35.0 183.9 1096.2 -33.8 -177.9
11 1360.6 -2.0 225.3 1344.5 2.8 -217.4
12 1130.0 11.5 185.9 1116.2 -13.5 -179.3
13 1129.6 -14.4 186.2 1115.8 17.8 -180.0
14 1135.6 -1.0 190.3 1121.8 1.7 -189.5
15 1124.0 -1.8 181.8 1110.2 2.6 -169.8
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 1365.2 - 1365.2
M1 (kN.m) 2.2 27.3 0.0
M2 (kN.m) 227.3 27.3 243.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.341 Le1/b1 = 5.0 < 15.0 400
Beta = 0.60 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 126.6 kN As (Required): %2.61 4175.34 mm2 16T20
vc'(1/2)= 0.99 / 1.79 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.00 / 0.89 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14

5C5 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 703.4 -2.9 241.3 687.3 2.7 -275.0
2 577.9 35.6 197.4 561.7 -38.9 -224.7
3 703.1 -3.1 240.9 686.9 2.9 -274.6
4 571.7 -40.4 192.7 555.6 43.5 -219.4
5 527.8 -0.5 122.2 511.6 0.1 -138.5
6 703.8 0.0 242.8 687.6 -0.1 -277.0
7 524.7 -3.0 120.5 508.6 2.6 -138.9
8 571.8 -45.1 192.2 555.6 48.6 -218.8
9 706.2 -2.4 242.0 690.1 2.3 -273.5
10 577.4 37.4 196.5 561.3 -41.2 -223.3
11 703.1 -3.1 240.9 686.9 2.9 -274.6
12 584.4 4.1 198.9 570.6 -6.8 -226.5
13 584.5 -8.9 199.0 570.7 11.2 -226.9
14 586.7 -2.1 200.1 572.9 1.9 -232.9
15 582.2 -2.6 197.8 568.4 2.5 -220.4
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 703.8 - 703.8
M1 (kN.m) -0.1 -14.1 0.0
M2 (kN.m) -277.0 -14.1 -288.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.176 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 173.3 kN As (Required): %2.83 4535.83 mm2 16T20
vc'(1/2)= 1.01 / 1.36 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.00 / 1.21 N/mm2
Links = R8-225

6C5 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 45.3 -0.1 165.9 29.1 1.7 -18.5
2 42.5 26.6 135.8 26.4 -5.2 -16.5
3 45.0 -0.1 165.5 28.9 1.8 -17.8
4 42.3 -27.2 133.0 26.2 8.1 -16.2
5 43.1 1.7 85.7 27.0 0.9 -13.0
6 44.9 3.0 165.9 28.8 -0.3 -18.5
7 42.4 -0.7 79.5 26.2 2.2 -10.5
8 42.7 -28.2 132.6 26.6 9.3 -16.3
9 46.2 0.5 171.4 30.1 1.4 -21.0
10 42.5 24.5 136.1 26.3 -4.5 -16.3
11 45.0 -0.1 165.5 28.9 1.8 -17.8
12 38.8 0.9 136.8 24.9 0.3 -15.4
13 38.8 -1.0 136.8 25.0 2.5 -15.5
14 39.2 0.0 136.0 25.3 1.4 -16.5
15 38.4 -0.1 137.6 24.6 1.5 -14.4
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 46.2 - 46.2
M1 (kN.m) 1.4 0.9 0.0
M2 (kN.m) 171.4 0.9 172.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 6.2 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 12.5 / 64.1 kN As (Required): %1.68 2682.35 mm2 12T20
vc'(1/2)= 0.74 / 0.74 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.09 / 0.45 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15

3C6 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2604.2 -1.5 -180.1 2588.1 1.8 183.2
2 2105.7 57.6 -145.0 2089.6 -58.9 147.7
3 2520.1 -1.3 -187.1 2503.9 1.6 190.4
4 2087.1 -60.4 -141.6 2070.9 62.3 144.0
5 2072.4 0.2 -81.8 2056.3 0.0 83.0
6 2610.2 0.5 -179.9 2594.1 -0.1 183.2
7 2078.3 -1.5 -76.7 2062.2 1.6 76.3
8 2083.6 -62.1 -140.8 2067.4 64.2 143.3
9 2596.5 -1.2 -184.4 2580.3 1.6 189.1
10 2103.2 57.4 -146.1 2087.1 -58.8 148.5
11 2520.1 -1.3 -187.1 2503.9 1.6 190.4
12 2151.5 19.1 -149.2 2137.7 -21.5 152.0
13 2149.9 -21.4 -147.9 2136.1 24.5 150.3
14 2167.4 -1.1 -127.4 2153.5 1.4 126.3
15 2134.1 -1.3 -169.6 2120.3 1.6 176.0
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 2596.5 - 2596.5
M1 (kN.m) 1.6 51.9 0.0
M2 (kN.m) 189.1 51.9 204.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.649 Le1/b1 = 5.0 < 15.0 400
Beta = 0.30 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 115.2 kN As (Required): %3.73 5967.69 mm2 20T20
vc'(1/2)= 1.89 / 2.70 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.81 N/mm2
Links = R8-225

4C6 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1746.8 -3.3 -182.3 1730.7 5.6 176.8
2 1414.2 56.2 -146.7 1398.0 -51.5 142.4
3 1690.4 -3.1 -189.5 1674.3 5.4 183.9
4 1401.8 -61.9 -143.5 1385.6 60.5 139.2
5 1391.8 -1.3 -82.4 1375.6 3.5 79.6
6 1751.1 -0.4 -181.7 1735.0 2.3 176.2
7 1400.1 -3.3 -75.8 1384.0 5.4 71.4
8 1399.2 -64.4 -142.7 1383.1 63.4 138.4
9 1737.4 -3.0 -188.0 1721.3 5.3 184.2
10 1412.4 55.8 -148.2 1396.3 -51.1 143.7
11 1690.4 -3.1 -189.5 1674.3 5.4 183.9
12 1443.3 10.7 -150.7 1429.5 -11.6 146.4
13 1442.5 -16.1 -150.0 1428.7 20.7 145.3
14 1449.9 -2.6 -136.9 1436.0 4.5 128.4
15 1436.0 -2.8 -163.8 1422.2 4.7 163.2
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 1737.4 - 1737.4
M1 (kN.m) 5.3 34.7 0.0
M2 (kN.m) -188.0 -34.7 -205.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.434 Le1/b1 = 5.0 < 15.0 400
Beta = 0.49 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.6 / 109.0 kN As (Required): %2.50 3995.04 mm2 16T20
vc'(1/2)= 1.63 / 2.06 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.01 / 0.76 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16

5C6 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 896.0 -3.3 -193.2 879.9 -1.3 215.9
2 728.0 68.1 -155.4 711.8 -89.9 173.5
3 867.2 -3.0 -200.9 851.1 -1.7 224.3
4 721.0 -74.0 -152.1 704.9 89.4 169.9
5 716.8 -0.6 -87.3 700.7 -4.6 97.7
6 899.2 -0.2 -192.3 883.0 -3.8 214.8
7 723.0 -3.1 -78.7 706.8 -1.7 89.2
8 718.7 -76.9 -151.3 702.5 91.7 169.0
9 889.3 -2.9 -200.9 873.2 -1.7 223.4
10 727.2 67.8 -157.2 711.0 -89.7 175.5
11 867.2 -3.0 -200.9 851.1 -1.7 224.3
12 740.7 4.0 -159.5 726.9 -10.5 178.3
13 740.3 -9.4 -159.3 726.5 8.4 177.9
14 742.2 -2.6 -153.5 728.3 -1.1 168.6
15 738.9 -2.8 -165.3 725.1 -1.0 187.6
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 727.2 - 727.2
M1 (kN.m) -89.7 -14.5 0.0
M2 (kN.m) 175.5 14.5 246.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.182 Le1/b1 = 5.0 < 15.0 400
Beta = 0.79 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 141.7 kN As (Required): %2.23 3563.17 mm2 12T20
vc'(1/2)= 0.85 / 1.43 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.00 / 0.99 N/mm2
Links = R8-225

6C6 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 26.0 -0.6 -127.8 9.9 0.0 13.8
2 26.4 2.0 -103.4 10.3 0.0 12.2
3 25.1 -0.5 -133.2 9.0 0.0 15.3
4 26.8 -2.9 -100.9 10.7 0.0 11.8
5 24.1 -0.4 -56.6 8.0 0.0 5.3
6 26.4 0.0 -128.1 10.3 0.0 13.3
7 34.7 -0.4 -54.1 18.6 0.0 -4.1
8 26.4 -3.3 -100.6 10.3 0.0 12.1
9 15.5 -0.9 -129.7 -0.6 0.0 23.0
10 26.4 1.9 -103.3 10.3 0.0 12.5
11 25.1 -0.5 -133.2 9.0 0.0 15.3
12 22.4 0.4 -105.4 8.6 0.0 11.6
13 22.4 -1.3 -105.5 8.6 0.0 11.6
14 22.5 -0.5 -105.0 8.7 0.0 9.9
15 22.4 -0.5 -105.9 8.5 0.0 13.2
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 25.1 - 25.1
M1 (kN.m) -0.5 -0.5 0.0
M2 (kN.m) -133.2 -0.5 -133.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 6.7 < 15.0 400
Beta = 0.99 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 50.9 kN As (Required): %1.27 2024.91 mm2 8T20
vc'(1/2)= 0.62 / 0.62 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.00 / 0.36 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17

3C7 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2571.1 1.6 171.9 2554.9 -1.3 -175.5
2 2070.6 60.8 137.6 2054.4 -62.1 -140.3
3 2487.2 1.7 179.0 2471.1 -1.5 -182.7
4 2071.9 -58.9 136.7 2055.7 60.7 -139.6
5 2051.8 3.3 76.3 2035.7 -3.3 -77.8
6 2592.6 2.2 176.4 2576.5 -1.9 -179.8
7 2561.0 0.7 175.8 2544.9 -0.5 -180.8
8 2048.9 -58.7 133.2 2032.8 60.7 -136.0
9 2062.1 3.9 72.3 2046.0 -3.7 -72.3
10 2072.0 59.9 136.6 2055.8 -61.4 -139.6
11 2487.2 1.7 179.0 2471.1 -1.5 -182.7
12 2125.1 22.1 141.1 2111.3 -24.6 -143.9
13 2121.9 -19.4 142.5 2108.1 22.4 -145.6
14 2107.0 1.3 162.9 2093.2 -1.0 -169.6
15 2140.0 1.4 120.7 2126.2 -1.2 -120.0
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 2592.6 - 2592.6
M1 (kN.m) 2.2 51.9 0.0
M2 (kN.m) -179.8 -51.9 -195.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.648 Le1/b1 = 5.0 < 15.0 400
Beta = 0.30 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 39.8 / 110.8 kN As (Required): %3.60 5759.12 mm2 20T20
vc'(1/2)= 2.63 / 2.68 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.28 / 0.78 N/mm2
Links = R8-225

4C7 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1724.8 -0.6 172.9 1708.6 3.2 -167.8
2 1390.8 58.9 138.5 1374.7 -53.4 -134.4
3 1668.6 -0.5 180.1 1652.5 3.1 -175.0
4 1391.5 -60.4 137.4 1375.4 58.9 -133.4
5 1377.9 1.6 76.1 1361.8 0.9 -73.7
6 1739.3 1.4 177.6 1723.1 0.4 -172.3
7 1713.6 -1.7 178.4 1697.5 4.3 -175.0
8 1376.2 -61.4 134.1 1360.1 60.9 -130.1
9 1389.2 2.2 70.4 1373.1 0.3 -66.3
10 1391.7 57.8 137.1 1375.5 -52.6 -133.2
11 1668.6 -0.5 180.1 1652.5 3.1 -175.0
12 1425.5 13.3 142.2 1411.7 -13.9 -137.9
13 1424.2 -14.2 143.0 1410.3 19.2 -139.0
14 1418.0 -0.5 156.0 1404.2 2.7 -155.8
15 1431.6 -0.4 129.2 1417.8 2.6 -121.1
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1739.3 - 1739.3
M1 (kN.m) 1.4 34.8 0.0
M2 (kN.m) 177.6 34.8 194.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.435 Le1/b1 = 5.0 < 15.0 400
Beta = 0.49 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.2 / 104.0 kN As (Required): %2.35 3754.44 mm2 12T20
vc'(1/2)= 0.98 / 1.97 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.00 / 0.73 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18

5C7 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 884.0 0.3 182.4 867.8 -6.7 -203.8
2 715.0 71.7 146.1 698.8 -96.0 -163.2
3 855.3 0.5 190.2 839.2 -6.9 -212.3
4 715.7 -72.1 144.9 699.6 87.1 -161.8
5 708.9 3.1 79.7 692.8 -10.0 -89.2
6 893.2 2.2 187.5 877.0 -6.7 -209.5
7 876.1 -1.0 189.8 860.0 -5.4 -211.0
8 706.0 -72.9 141.4 689.9 85.5 -158.1
9 716.7 3.7 72.2 700.6 -10.6 -81.9
10 715.4 70.5 144.4 699.3 -94.3 -161.2
11 855.3 0.5 190.2 839.2 -6.9 -212.3
12 730.9 7.2 150.3 717.1 -15.2 -167.9
13 730.4 -6.7 150.6 716.6 4.1 -168.4
14 729.1 0.3 156.4 715.3 -5.5 -177.6
15 732.2 0.2 144.6 718.4 -5.5 -158.6
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 715.0 - 715.0
M1 (kN.m) -96.0 -14.3 0.0
M2 (kN.m) -163.2 -14.3 -239.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.179 Le1/b1 = 5.0 < 15.0 400
Beta = 0.79 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 55.9 / 134.1 kN As (Required): %2.13 3408.12 mm2 12T20
vc'(1/2)= 1.26 / 1.42 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.39 / 0.94 N/mm2
Links = R8-225

6C7 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 27.6 1.1 123.9 11.5 0.0 -11.7
2 28.0 3.7 99.5 11.9 0.0 -10.4
3 26.6 1.1 129.4 10.5 0.0 -13.3
4 27.6 -2.0 99.1 11.5 0.0 -10.6
5 25.2 1.2 54.7 9.0 0.0 -3.8
6 27.2 0.6 126.3 11.0 0.0 -12.4
7 16.7 0.9 125.6 0.6 0.0 -21.2
8 28.0 -1.6 96.7 11.9 0.0 -10.1
9 35.9 1.6 53.1 19.8 0.0 5.6
10 28.0 3.7 99.5 11.9 0.0 -10.2
11 26.6 1.1 129.4 10.5 0.0 -13.3
12 23.7 1.8 102.3 9.9 0.0 -9.9
13 23.7 0.0 102.3 9.9 0.0 -9.9
14 23.6 0.9 102.8 9.8 0.0 -11.5
15 23.8 0.9 101.9 10.0 0.0 -8.2
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 26.6 - 26.6
M1 (kN.m) 1.1 0.5 0.0
M2 (kN.m) 129.4 0.5 130.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.007 Le1/b1 = 6.7 < 15.0 400
Beta = 0.99 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 48.9 kN As (Required): %1.23 1968.24 mm2 8T20
vc'(1/2)= 0.63 / 0.62 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.00 / 0.34 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-19

3C8 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1989.1 -0.5 -216.2 1972.9 1.0 222.2
2 1618.1 35.6 -175.2 1601.9 -35.8 180.2
3 1988.5 -0.7 -215.9 1972.4 1.1 221.9
4 1615.2 -36.6 -174.9 1599.1 37.6 179.6
5 1476.2 1.3 -109.7 1460.1 -1.0 112.8
6 2005.0 1.1 -219.7 1988.9 -0.6 226.1
7 1992.1 -1.2 -217.0 1976.0 1.7 221.8
8 1599.2 -36.1 -170.5 1583.0 37.4 175.4
9 1473.2 1.6 -108.9 1457.1 -1.3 113.3
10 1618.2 33.4 -176.0 1602.1 -34.1 180.6
11 1988.5 -0.7 -215.9 1972.4 1.1 221.9
12 1652.0 21.1 -178.5 1638.2 -23.5 183.7
13 1649.3 -21.9 -178.0 1635.5 25.1 182.8
14 1639.3 -0.8 -170.5 1625.5 1.3 170.4
15 1662.0 0.0 -186.0 1648.2 0.3 196.1
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 2005.0 - 2005.0
M1 (kN.m) 1.1 40.1 0.0
M2 (kN.m) 226.1 40.1 242.9 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.501 Le1/b1 = 5.0 < 15.0 400
Beta = 0.42 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 127.4 kN As (Required): %3.42 5473.91 mm2 20T20
vc'(1/2)= 1.59 / 2.28 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.89 N/mm2
Links = R8-225

4C8 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1340.7 -1.9 -221.3 1324.6 2.8 212.9
2 1092.7 35.3 -179.2 1076.5 -33.9 172.6
3 1340.2 -2.1 -220.9 1324.1 3.0 212.4
4 1090.3 -38.5 -179.0 1074.2 38.5 172.2
5 998.6 0.4 -112.8 982.4 0.4 108.6
6 1350.7 0.7 -224.7 1334.6 0.0 216.4
7 1343.4 -2.7 -222.4 1327.2 3.6 214.1
8 1080.4 -38.5 -174.6 1064.2 39.0 168.1
9 995.9 0.7 -111.6 979.7 0.0 107.5
10 1092.6 32.7 -180.1 1076.5 -31.5 173.2
11 1340.2 -2.1 -220.9 1324.1 3.0 212.4
12 1113.5 12.6 -182.5 1099.7 -14.8 175.8
13 1112.4 -15.8 -182.3 1098.6 19.4 175.2
14 1107.2 -1.9 -178.2 1093.4 2.7 165.7
15 1118.8 -1.3 -186.7 1105.0 2.0 185.3
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1350.7 - 1350.7
M1 (kN.m) 0.7 27.0 0.0
M2 (kN.m) -224.7 -27.0 -241.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.338 Le1/b1 = 5.0 < 15.0 400
Beta = 0.60 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 124.0 kN As (Required): %2.56 4090.96 mm2 16T20
vc'(1/2)= 0.79 / 1.77 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.00 / 0.87 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-20

5C8 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 693.0 -3.3 -237.2 676.9 2.6 271.2
2 567.5 37.4 -192.1 551.4 -41.8 219.4
3 692.7 -3.4 -236.7 676.5 2.8 270.8
4 566.2 -42.7 -191.7 550.1 46.1 219.0
5 521.5 -0.6 -121.1 505.4 -0.3 138.2
6 697.9 -0.1 -240.6 681.8 -0.5 274.8
7 695.0 -4.2 -237.3 678.9 3.6 269.0
8 561.4 -42.7 -187.3 545.3 45.5 214.0
9 519.5 -0.2 -121.0 503.3 -0.8 140.4
10 567.4 34.2 -193.0 551.3 -38.0 220.7
11 692.7 -3.4 -236.7 676.5 2.8 270.8
12 576.0 4.4 -195.5 562.2 -7.7 223.7
13 575.8 -9.7 -195.6 562.0 11.9 223.4
14 573.7 -2.8 -194.4 559.9 2.3 217.3
15 578.1 -2.5 -196.7 564.3 1.9 229.8
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 697.9 - 697.9
M1 (kN.m) -0.5 -14.0 0.0
M2 (kN.m) 274.8 14.0 286.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.174 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 171.8 kN As (Required): %2.80 4485.97 mm2 16T20
vc'(1/2)= 0.90 / 1.36 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.00 / 1.20 N/mm2
Links = R8-225

6C8 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 45.7 -0.7 -160.0 29.6 3.6 18.2
2 43.0 24.4 -130.2 26.8 -2.8 16.0
3 45.5 -0.7 -159.6 29.3 3.6 17.5
4 42.5 -25.7 -129.7 26.3 8.4 16.2
5 43.5 1.3 -82.2 27.4 2.5 12.9
6 45.0 0.4 -163.2 28.9 1.6 18.3
7 46.7 -0.7 -165.3 30.5 3.7 20.7
8 43.2 -27.6 -126.9 27.0 10.5 15.9
9 42.6 1.3 -76.9 26.4 2.5 10.3
10 43.0 25.1 -129.8 26.8 -2.9 16.1
11 45.5 -0.7 -159.6 29.3 3.6 17.5
12 39.1 0.5 -131.9 25.3 1.8 15.2
13 39.2 -1.6 -132.0 25.3 4.2 15.2
14 38.8 -0.6 -132.8 25.0 3.0 14.1
15 39.5 -0.5 -131.2 25.7 2.9 16.2
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 46.7 - 46.7
M1 (kN.m) 3.7 0.9 0.0
M2 (kN.m) -165.3 -0.9 -169.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 6.2 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 12.7 / 62.0 kN As (Required): %1.63 2610.91 mm2 12T20
vc'(1/2)= 0.74 / 0.74 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.09 / 0.43 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-21

1C9 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2715.8 13.7 72.6 2699.7 -28.6 -150.8
2 2089.4 2.3 55.2 2073.3 -4.1 -114.6
3 2716.1 13.6 72.7 2699.9 -28.6 -150.9
4 2387.2 18.7 64.7 2371.1 -39.8 -134.3
5 2006.9 12.9 36.5 1990.7 -27.0 -76.3
6 2347.0 18.8 62.5 2330.9 -38.9 -130.0
7 2194.8 12.3 49.3 2178.7 -26.1 -98.4
8 2754.7 12.8 74.9 2738.6 -29.1 -154.8
9 2701.2 14.1 69.4 2685.1 -29.2 -149.1
10 2090.7 3.1 55.0 2074.6 -4.6 -114.9
11 2716.1 13.6 72.7 2699.9 -28.6 -150.9
12 2235.2 50.5 59.9 2221.4 -52.3 -124.4
13 2276.3 -27.8 59.9 2262.5 4.9 -124.5
14 2281.4 12.2 96.5 2267.6 -24.4 -138.0
15 2230.1 10.5 23.4 2216.2 -23.1 -110.9
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 2754.7 - 2754.7
M1 (kN.m) -29.1 -55.1 0.0
M2 (kN.m) -154.8 -55.1 -171.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.689 Le1/b1 = 4.8 < 15.0 400
Beta = 0.30 Le2/b2 = 5.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 10.9 / 44.8 kN As (Required): %3.51 5623.07 mm2 20T20
vc'(1/2)= 2.04 / 2.04 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.08 / 0.31 N/mm2
Links = R8-225

2C9 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2173.5 44.5 206.6 2157.3 -45.4 -190.2
2 1676.3 8.7 157.4 1660.2 -10.6 -144.6
3 2173.4 44.4 206.8 2157.2 -45.4 -190.2
4 1909.0 59.6 183.8 1892.9 -59.2 -169.4
5 1607.9 41.3 104.5 1591.7 -41.7 -96.8
6 1878.9 59.8 178.5 1862.8 -60.2 -164.1
7 1757.8 39.2 135.0 1741.7 -39.4 -125.1
8 2201.7 43.2 212.8 2185.6 -43.7 -195.4
9 2161.8 45.8 204.2 2145.7 -46.9 -187.5
10 1678.2 9.8 156.7 1662.0 -11.4 -144.7
11 2173.4 44.4 206.8 2157.2 -45.4 -190.2
12 1790.7 65.9 170.6 1776.9 -68.0 -157.0
13 1820.3 7.8 170.6 1806.4 -7.3 -157.0
14 1823.3 37.3 182.3 1809.5 -38.2 -171.8
15 1787.7 36.3 158.8 1773.9 -37.1 -142.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 2201.7 - 2201.7
M1 (kN.m) -43.7 -44.0 0.0
M2 (kN.m) 212.8 44.0 228.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.550 Le1/b1 = 4.8 < 15.0 400
Beta = 0.36 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.7 / 100.7 kN As (Required): %3.50 5592.40 mm2 20T20
vc'(1/2)= 2.26 / 2.28 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.19 / 0.71 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-22

3C9 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1635.9 49.9 178.3 1619.8 -51.5 -184.6
2 1264.7 14.1 136.2 1248.6 -14.9 -140.7
3 1635.7 49.7 178.1 1619.6 -51.3 -184.3
4 1436.7 62.5 158.3 1420.6 -64.2 -163.9
5 1212.7 44.8 90.9 1196.6 -46.0 -94.4
6 1415.2 65.1 154.4 1399.1 -66.8 -159.6
7 1324.7 41.6 115.1 1308.6 -42.7 -120.6
8 1655.7 46.8 183.6 1639.6 -48.4 -189.6
9 1627.4 51.9 178.4 1611.2 -53.6 -183.1
10 1266.4 14.6 134.9 1250.3 -15.4 -140.1
11 1635.7 49.7 178.1 1619.6 -51.3 -184.3
12 1350.1 62.8 147.2 1336.2 -66.7 -152.3
13 1368.5 19.7 147.2 1354.7 -18.5 -152.3
14 1370.0 41.6 154.9 1356.2 -43.0 -165.0
15 1348.6 40.9 139.5 1334.7 -42.2 -139.6
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 1655.7 - 1655.7
M1 (kN.m) -48.4 -33.1 0.0
M2 (kN.m) -189.6 -33.1 -214.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.414 Le1/b1 = 4.8 < 15.0 400
Beta = 0.51 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 30.3 / 106.6 kN As (Required): %2.53 4045.26 mm2 16T20
vc'(1/2)= 1.84 / 1.96 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.21 / 0.75 N/mm2
Links = R8-225

4C9 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1102.3 55.0 182.4 1086.1 -55.8 -175.7
2 854.9 17.0 139.4 838.8 -17.9 -133.8
3 1102.0 54.8 182.1 1085.9 -55.6 -175.3
4 968.7 67.6 161.8 952.6 -68.0 -156.3
5 820.1 48.7 93.3 804.0 -49.2 -90.2
6 954.9 71.1 158.1 938.7 -71.8 -152.3
7 894.5 44.8 117.7 878.4 -45.3 -113.6
8 1114.7 51.2 187.5 1098.5 -51.8 -180.4
9 1096.7 57.5 182.7 1080.6 -58.3 -176.0
10 856.3 17.4 137.9 840.2 -18.0 -133.1
11 1102.0 54.8 182.1 1085.9 -55.6 -175.3
12 911.3 60.2 150.6 897.5 -63.4 -145.0
13 921.1 30.9 150.5 907.3 -29.0 -145.0
14 921.6 45.8 154.7 907.8 -46.5 -154.7
15 910.8 45.2 146.4 897.0 -45.8 -135.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 1114.7 - 1114.7
M1 (kN.m) -51.8 -22.3 0.0
M2 (kN.m) 187.5 22.3 222.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.279 Le1/b1 = 4.8 < 15.0 400
Beta = 0.68 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 32.7 / 103.1 kN As (Required): %2.03 3242.64 mm2 12T20
vc'(1/2)= 1.43 / 1.52 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.23 / 0.72 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-23

5C9 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 570.6 59.9 196.2 554.4 -63.2 -225.9
2 445.6 19.4 150.3 429.5 -19.5 -173.8
3 570.4 59.7 195.8 554.2 -62.9 -225.6
4 503.2 72.7 173.4 487.1 -77.6 -198.5
5 429.1 52.5 100.6 412.9 -55.3 -115.7
6 496.2 76.7 169.8 480.1 -81.0 -194.8
7 465.9 48.1 127.6 449.8 -50.8 -148.9
8 576.5 54.9 201.8 560.3 -58.3 -232.6
9 568.1 62.7 195.4 551.9 -66.1 -222.7
10 446.7 20.4 148.3 430.6 -21.0 -170.9
11 570.4 59.7 195.8 554.2 -62.9 -225.6
12 472.9 57.3 162.0 459.1 -62.5 -186.6
13 476.8 41.7 161.8 462.9 -42.0 -186.3
14 476.8 49.7 163.0 463.0 -52.4 -192.6
15 472.8 49.4 160.8 459.0 -52.0 -180.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 576.5 - 576.5
M1 (kN.m) -58.3 -11.5 0.0
M2 (kN.m) -232.6 -11.5 -281.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.144 Le1/b1 = 4.8 < 15.0 400
Beta = 0.83 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 52.6 / 144.8 kN As (Required): %2.74 4377.99 mm2 16T20
vc'(1/2)= 1.20 / 1.25 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.37 / 1.01 N/mm2
Links = R8-225

6C9 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 39.6 43.8 130.9 23.5 -20.1 -14.7
2 38.0 16.7 98.5 21.9 -11.6 -12.4
3 39.4 43.8 130.5 23.3 -20.1 -14.0
4 37.4 50.8 118.5 21.3 -20.3 -14.5
5 38.0 38.1 67.3 21.9 -17.1 -10.3
6 38.0 56.4 115.0 21.9 -24.2 -14.4
7 37.6 34.1 81.4 21.4 -15.1 -9.1
8 38.8 41.0 133.1 22.7 -17.4 -14.9
9 40.1 46.2 135.1 24.0 -21.3 -16.9
10 38.2 13.9 99.7 22.1 -10.4 -12.3
11 39.4 43.8 130.5 23.3 -20.1 -14.0
12 33.8 38.0 108.0 20.0 -18.3 -12.3
13 34.2 34.6 108.2 20.4 -15.2 -12.3
14 34.4 36.3 107.3 20.5 -16.8 -13.3
15 33.7 36.3 108.9 19.9 -16.7 -11.3
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 40.1 - 40.1
M1 (kN.m) 46.2 0.8 0.0
M2 (kN.m) 135.1 0.8 180.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 6.1 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 26.9 / 50.7 kN As (Required): %1.78 2841.17 mm2 12T20
vc'(1/2)= 0.74 / 0.73 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.19 / 0.35 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-24

3C10 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2150.0 71.8 -138.5 2133.8 -74.2 140.2
2 1645.9 14.0 -100.2 1629.8 -15.0 101.6
3 2070.9 70.3 -145.5 2054.8 -72.7 147.4
4 1868.4 94.4 -124.9 1852.3 -97.3 126.5
5 1719.2 66.6 -60.4 1703.0 -68.6 60.6
6 1837.2 97.1 -119.6 1821.1 -100.0 121.5
7 1843.0 63.6 -79.6 1826.9 -65.4 79.0
8 2177.7 71.1 -140.9 2161.5 -73.6 142.8
9 2129.5 73.7 -141.6 2113.4 -76.3 144.8
10 1649.5 12.0 -103.2 1633.4 -12.9 104.1
11 2070.9 70.3 -145.5 2054.8 -72.7 147.4
12 1769.4 81.4 -114.1 1755.6 -86.0 115.6
13 1785.7 36.6 -114.6 1771.8 -36.0 116.1
14 1791.6 59.7 -93.6 1777.8 -61.8 91.3
15 1763.5 58.3 -135.2 1749.6 -60.2 140.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 2177.7 - 2177.7
M1 (kN.m) -73.6 -43.6 0.0
M2 (kN.m) 142.8 43.6 169.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.544 Le1/b1 = 4.8 < 15.0 400
Beta = 0.37 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 55.8 / 91.8 kN As (Required): %2.62 4198.41 mm2 16T20
vc'(1/2)= 2.31 / 2.32 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.39 / 0.64 N/mm2
Links = R8-225

4C10 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1443.4 77.8 -138.7 1427.3 -78.2 133.6
2 1107.3 18.3 -99.8 1091.2 -20.4 95.9
3 1390.7 76.1 -146.0 1374.5 -76.4 140.8
4 1255.2 99.6 -126.1 1239.1 -98.2 121.6
5 1155.3 71.5 -59.6 1139.2 -71.7 56.9
6 1233.6 103.9 -120.5 1217.5 -103.3 116.4
7 1241.0 67.9 -78.3 1224.8 -68.1 73.6
8 1462.6 76.3 -140.6 1446.5 -75.9 135.5
9 1425.7 80.1 -143.1 1409.6 -80.5 139.6
10 1109.7 15.6 -103.4 1093.6 -17.4 99.2
11 1390.7 76.1 -146.0 1374.5 -76.4 140.8
12 1189.7 79.1 -114.3 1175.9 -82.0 110.1
13 1197.7 48.8 -114.9 1183.9 -46.4 110.6
14 1198.9 64.7 -101.4 1185.1 -65.0 93.2
15 1188.4 63.2 -127.9 1174.6 -63.5 127.5
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 1425.7 - 1425.7
M1 (kN.m) -80.5 -28.5 0.0
M2 (kN.m) -143.1 -28.5 -190.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.356 Le1/b1 = 4.8 < 15.0 400
Beta = 0.58 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 69.1 / 85.1 kN As (Required): %1.90 3040.99 mm2 12T20
vc'(1/2)= 1.80 / 1.76 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.48 / 0.60 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-25

5C10 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 740.6 90.8 -145.7 724.5 -103.9 163.0
2 568.5 20.9 -104.0 552.4 -18.7 116.3
3 713.7 88.6 -153.4 697.6 -101.3 171.5
4 648.4 117.1 -133.0 632.3 -139.6 148.7
5 594.5 82.6 -62.0 578.4 -94.3 69.5
6 634.6 122.2 -127.0 618.5 -142.9 142.0
7 639.2 78.3 -80.6 623.1 -89.1 91.0
8 753.3 89.0 -147.2 737.2 -104.3 164.5
9 729.7 93.6 -151.7 713.6 -107.2 168.7
10 569.6 17.5 -108.5 553.5 -14.9 121.5
11 713.7 88.6 -153.4 697.6 -101.3 171.5
12 611.6 82.8 -120.0 597.8 -96.3 134.2
13 614.2 66.4 -120.7 600.4 -74.6 135.0
14 613.7 75.5 -114.4 599.9 -86.5 125.2
15 612.1 73.8 -126.2 598.3 -84.4 144.1
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 648.4 - 648.4
M1 (kN.m) -139.6 -13.0 0.0
M2 (kN.m) 148.7 13.0 262.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.162 Le1/b1 = 4.8 < 15.0 400
Beta = 0.81 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 88.4 / 108.3 kN As (Required): %2.47 3944.43 mm2 16T20
vc'(1/2)= 1.30 / 1.37 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.62 / 0.76 N/mm2
Links = R8-225

6C10 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 31.7 12.9 -101.4 15.5 0.0 8.0
2 32.8 11.1 -75.6 16.7 0.0 5.6
3 30.6 12.6 -106.8 14.5 0.0 9.6
4 28.8 8.4 -90.3 12.7 0.0 10.0
5 28.4 11.9 -43.7 12.3 0.0 1.5
6 29.0 8.8 -87.7 12.9 0.0 9.4
7 35.6 11.0 -59.3 19.4 0.0 -3.0
8 32.2 13.5 -103.7 16.1 0.0 7.4
9 22.1 13.4 -102.0 6.0 0.0 16.1
10 32.1 10.2 -75.9 16.0 0.0 6.8
11 30.6 12.6 -106.8 14.5 0.0 9.6
12 27.2 11.7 -83.8 13.3 0.0 6.7
13 26.9 9.6 -83.9 13.1 0.0 6.9
14 27.2 10.8 -83.3 13.3 0.0 5.1
15 26.9 10.5 -84.3 13.1 0.0 8.5
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 30.6 - 30.6
M1 (kN.m) 12.6 0.6 0.0
M2 (kN.m) -106.8 -0.6 -119.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 6.6 < 15.0 400
Beta = 0.99 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.5 / 39.4 kN As (Required): %1.11 1776.55 mm2 8T20
vc'(1/2)= 0.63 / 0.63 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.03 / 0.28 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-26

3C11 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2456.1 1.4 162.7 2439.9 -1.4 -167.1
2 1977.8 -56.8 133.3 1961.7 58.2 -136.8
3 2372.1 1.3 169.7 2356.0 -1.2 -174.2
4 1999.7 59.1 128.4 1983.5 -60.4 -131.9
5 1967.7 1.3 74.8 1951.6 -1.2 -77.1
6 1971.4 60.9 125.7 1955.2 -62.1 -128.9
7 2449.7 0.5 165.3 2433.5 -0.5 -170.9
8 2503.8 -0.1 172.3 2487.7 0.1 -176.5
9 1975.2 1.7 71.6 1959.1 -1.7 -72.5
10 1958.4 -57.1 126.5 1942.3 58.4 -130.4
11 2372.1 1.3 169.7 2356.0 -1.2 -174.2
12 2027.8 21.2 134.6 2014.0 -24.0 -138.2
13 2030.2 -18.9 134.1 2016.4 21.7 -137.7
14 2012.5 1.1 155.2 1998.7 -1.1 -162.5
15 2045.5 1.2 113.5 2031.7 -1.2 -113.4
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 2503.8 - 2503.8
M1 (kN.m) 0.1 50.1 0.0
M2 (kN.m) -176.5 -50.1 -191.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.626 Le1/b1 = 5.0 < 15.0 400
Beta = 0.30 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 41.0 / 105.9 kN As (Required): %3.41 5463.78 mm2 20T20
vc'(1/2)= 2.57 / 2.59 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.29 / 0.74 N/mm2
Links = R8-225

4C11 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1643.8 1.6 165.7 1627.7 -1.0 -161.6
2 1324.6 -56.3 136.5 1308.4 53.5 -133.2
3 1587.6 1.4 172.9 1571.5 -0.8 -168.6
4 1341.6 58.8 129.9 1325.4 -55.1 -126.6
5 1317.5 1.4 76.2 1301.4 -0.9 -74.4
6 1322.0 62.0 127.8 1305.9 -59.0 -124.3
7 1637.1 0.5 169.0 1621.0 -0.1 -166.0
8 1676.0 -0.1 175.4 1659.9 0.7 -170.9
9 1325.9 1.9 71.8 1309.8 -1.3 -68.6
10 1311.9 -57.9 129.0 1295.8 55.8 -126.1
11 1587.6 1.4 172.9 1571.5 -0.8 -168.6
12 1357.4 14.5 137.1 1343.6 -17.0 -133.7
13 1359.2 -11.9 136.5 1345.3 15.4 -133.1
14 1351.4 1.3 150.1 1337.6 -0.8 -150.6
15 1365.2 1.3 123.5 1351.4 -0.8 -116.1
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 1676.0 - 1676.0
M1 (kN.m) 0.7 33.5 0.0
M2 (kN.m) 175.4 33.5 192.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.419 Le1/b1 = 5.0 < 15.0 400
Beta = 0.51 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.2 / 100.2 kN As (Required): %2.24 3576.90 mm2 12T20
vc'(1/2)= 1.52 / 1.90 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.00 / 0.70 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-27

5C11 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 832.5 3.8 176.8 816.4 -7.5 -198.2
2 672.9 -64.7 146.2 656.7 80.4 -163.9
3 803.9 3.5 184.4 787.8 -7.1 -206.5
4 683.5 70.6 137.9 667.4 -91.9 -154.5
5 667.7 3.4 81.4 651.5 -6.8 -91.5
6 670.9 74.4 136.0 654.7 -93.8 -152.6
7 828.0 2.3 181.2 811.8 -5.4 -202.5
8 853.1 1.7 187.2 837.0 -5.7 -209.6
9 673.5 4.3 75.6 657.4 -8.1 -86.0
10 664.9 -66.5 137.7 648.7 80.6 -154.3
11 803.9 3.5 184.4 787.8 -7.1 -206.5
12 687.9 9.8 146.3 674.1 -15.6 -164.0
13 688.9 -3.6 145.5 675.0 3.3 -163.1
14 686.8 3.2 151.8 673.0 -6.2 -173.0
15 690.0 3.1 140.0 676.2 -6.1 -154.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 672.9 - 672.9
M1 (kN.m) 80.4 13.5 0.0
M2 (kN.m) -163.9 -13.5 -228.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.168 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 56.1 / 130.3 kN As (Required): %1.98 3175.56 mm2 12T20
vc'(1/2)= 1.24 / 1.38 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.39 / 0.91 N/mm2
Links = R8-225

6C11 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 22.4 -10.3 116.3 6.3 0.0 -15.3
2 22.0 -13.7 94.4 5.9 0.0 -14.9
3 21.5 -10.0 121.6 5.4 0.0 -16.8
4 25.8 -1.9 93.1 9.7 0.0 -11.3
5 21.2 -9.3 52.8 5.1 0.0 -7.0
6 25.7 -2.3 90.7 9.5 0.0 -11.5
7 16.2 -8.9 117.2 0.1 0.0 -20.6
8 21.8 -10.8 121.5 5.6 0.0 -16.4
9 29.7 -10.6 51.3 13.6 0.0 0.6
10 22.8 -12.9 91.7 6.6 0.0 -13.5
11 21.5 -10.0 121.6 5.4 0.0 -16.8
12 19.3 -7.7 96.1 5.5 0.0 -12.9
13 19.5 -9.2 95.9 5.7 0.0 -12.7
14 19.3 -8.5 96.5 5.5 0.0 -14.5
15 19.5 -8.4 95.5 5.7 0.0 -11.1
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 21.8 - 21.8
M1 (kN.m) -10.8 -0.4 0.0
M2 (kN.m) 121.5 0.4 132.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.005 Le1/b1 = 6.7 < 15.0 400
Beta = 0.99 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.6 / 45.9 kN As (Required): %1.25 2007.91 mm2 8T20
vc'(1/2)= 0.63 / 0.62 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.03 / 0.32 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-28

3C12 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1930.1 0.4 -200.0 1914.0 -0.3 205.6
2 1575.4 -32.5 -163.1 1559.3 33.2 168.0
3 1929.5 0.2 -199.7 1913.3 -0.2 205.3
4 1575.8 33.2 -164.0 1559.7 -33.7 168.3
5 1444.3 0.3 -102.7 1428.2 -0.1 105.5
6 1556.7 36.5 -158.8 1540.6 -36.9 163.5
7 1932.0 -0.3 -200.6 1915.9 0.4 205.1
8 1964.7 0.0 -208.4 1948.6 0.2 214.3
9 1442.0 0.6 -102.0 1425.9 -0.5 106.1
10 1559.9 -35.5 -160.0 1543.7 36.0 164.1
11 1929.5 0.2 -199.7 1913.3 -0.2 205.3
12 1602.2 21.0 -165.0 1588.4 -23.9 169.6
13 1602.1 -20.4 -165.0 1588.3 23.4 169.6
14 1591.3 0.0 -157.3 1577.5 0.1 156.9
15 1613.0 0.6 -172.7 1599.2 -0.6 182.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 1964.7 - 1964.7
M1 (kN.m) 0.2 39.3 0.0
M2 (kN.m) 214.3 39.3 231.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.491 Le1/b1 = 5.0 < 15.0 400
Beta = 0.43 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 118.3 kN As (Required): %3.20 5120.98 mm2 20T20
vc'(1/2)= 1.57 / 2.24 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.83 N/mm2
Links = R8-225

4C12 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1304.0 0.5 -205.6 1287.9 -0.5 198.0
2 1066.1 -32.8 -167.6 1050.0 32.3 161.9
3 1303.4 0.4 -205.1 1287.3 -0.4 197.5
4 1066.2 33.7 -168.5 1050.1 -33.1 162.0
5 979.0 0.4 -106.1 962.8 -0.4 102.5
6 1054.1 38.1 -163.2 1038.0 -37.7 157.3
7 1305.7 -0.2 -206.4 1289.5 0.2 198.7
8 1325.7 0.3 -213.8 1309.6 -0.3 206.2
9 976.9 0.8 -105.2 960.8 -0.8 101.6
10 1056.5 -37.1 -164.7 1040.3 36.7 158.5
11 1303.4 0.4 -205.1 1287.3 -0.4 197.5
12 1082.8 14.1 -169.5 1069.0 -17.2 163.4
13 1082.8 -13.3 -169.6 1069.0 16.3 163.3
14 1077.3 0.2 -165.4 1063.5 -0.2 153.7
15 1088.3 0.6 -173.7 1074.5 -0.7 173.0
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 1325.7 - 1325.7
M1 (kN.m) -0.3 -26.5 0.0
M2 (kN.m) -213.8 -26.5 -230.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.331 Le1/b1 = 5.0 < 15.0 400
Beta = 0.61 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 25.3 / 115.6 kN As (Required): %2.37 3794.79 mm2 16T20
vc'(1/2)= 1.72 / 1.75 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.18 / 0.81 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-29

5C12 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 675.6 0.3 -219.8 659.5 -0.4 249.8
2 555.2 -34.0 -178.6 539.1 37.2 202.1
3 675.3 0.1 -219.2 659.1 -0.2 249.3
4 554.8 34.6 -180.4 538.7 -37.9 205.6
5 511.9 0.2 -113.5 495.7 -0.2 128.2
6 549.0 40.5 -174.7 532.8 -44.1 199.0
7 676.9 -0.6 -219.9 660.7 0.6 248.5
8 686.3 -0.3 -228.0 670.1 0.3 258.6
9 510.3 0.6 -113.3 494.2 -0.7 129.8
10 550.4 -39.4 -176.1 534.3 42.8 199.9
11 675.3 0.1 -219.2 659.1 -0.2 249.3
12 561.7 7.1 -181.2 547.8 -10.0 205.8
13 561.6 -6.6 -181.3 547.8 9.4 206.1
14 559.6 0.2 -180.1 545.8 -0.2 199.8
15 563.7 0.3 -182.4 549.9 -0.4 212.1
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 686.3 - 686.3
M1 (kN.m) -0.3 -13.7 0.0
M2 (kN.m) 258.6 13.7 269.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.172 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 28.2 / 162.2 kN As (Required): %2.57 4115.56 mm2 16T20
vc'(1/2)= 1.24 / 1.35 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.20 / 1.14 N/mm2
Links = R8-225

6C12 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 48.4 -0.1 -154.1 32.3 0.0 19.4
2 44.9 -25.3 -127.9 28.8 4.7 17.6
3 48.1 -0.1 -153.6 32.0 0.0 18.8
4 44.6 25.2 -124.4 28.5 -4.7 16.7
5 45.5 0.0 -81.3 29.4 0.0 13.9
6 45.3 26.3 -121.9 29.1 -7.0 16.4
7 48.9 0.0 -157.2 32.8 0.1 20.9
8 46.9 -0.1 -160.8 30.8 0.0 19.8
9 44.8 -0.1 -77.4 28.7 0.0 12.0
10 45.7 -26.4 -123.8 29.6 6.9 17.5
11 48.1 -0.1 -153.6 32.0 0.0 18.8
12 41.4 1.0 -127.3 27.5 -1.3 16.3
13 41.3 -1.2 -127.0 27.5 1.3 16.2
14 41.0 -0.1 -128.0 27.2 0.0 15.2
15 41.7 -0.1 -126.3 27.9 0.0 17.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 46.9 - 46.9
M1 (kN.m) -0.1 -0.9 0.0
M2 (kN.m) -160.8 -0.9 -161.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 6.2 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 11.1 / 60.2 kN As (Required): %1.52 2434.01 mm2 8T20
vc'(1/2)= 0.65 / 0.65 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.08 / 0.42 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-30

1C13 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1377.4 7.5 29.4 1361.2 -15.7 -61.0
2 1370.9 9.0 31.6 1354.7 -17.8 -65.5
3 1377.4 7.4 29.4 1361.2 -15.7 -60.9
4 1020.3 2.5 21.0 1004.2 -6.3 -43.6
5 1039.4 7.4 16.1 1023.3 -15.4 -34.0
6 1071.8 2.9 21.0 1055.6 -5.7 -43.7
7 1296.1 7.8 33.5 1280.0 -16.9 -65.6
8 1303.6 6.8 29.8 1287.5 -16.8 -60.4
9 1242.8 7.3 19.9 1226.7 -15.2 -46.1
10 1393.1 9.3 31.3 1377.0 -17.4 -66.0
11 1377.4 7.4 29.4 1361.2 -15.7 -60.9
12 1106.0 47.9 25.2 1092.1 -47.0 -51.0
13 1200.2 -35.5 23.8 1186.4 21.0 -50.5
14 1179.6 7.1 60.9 1165.7 -13.8 -64.8
15 1126.6 5.3 -11.9 1112.8 -12.2 -36.7
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1393.1 - 1393.1
M1 (kN.m) -17.4 -27.9 0.0
M2 (kN.m) -66.0 -27.9 -82.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.348 Le1/b1 = 4.7 < 15.0 400
Beta = 0.59 Le2/b2 = 5.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.9 / 8.2 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 1.17 / 0.87 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.02 / 0.06 N/mm2
Links = R8-175

2C13 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1138.4 23.0 82.6 1122.3 -21.4 -76.1
2 1126.7 24.9 89.6 1110.6 -22.4 -81.9
3 1138.4 22.8 82.5 1122.2 -21.3 -76.0
4 844.1 10.4 58.4 828.0 -10.6 -54.3
5 862.5 22.3 45.8 846.4 -20.6 -42.6
6 901.7 8.3 59.2 885.6 -6.0 -54.4
7 1060.6 24.4 89.3 1044.4 -23.4 -82.8
8 1075.9 23.9 82.8 1059.7 -23.4 -75.8
9 1035.7 22.2 62.0 1019.6 -20.4 -56.7
10 1131.7 26.1 88.6 1115.5 -25.0 -82.0
11 1138.4 22.8 82.5 1122.2 -21.3 -76.0
12 925.9 55.1 69.1 912.1 -54.0 -63.7
13 979.8 -17.0 68.4 965.9 18.7 -63.0
14 970.9 19.7 81.4 957.1 -18.4 -78.7
15 934.7 18.3 56.1 920.9 -17.0 -48.1
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1131.7 - 1131.7
M1 (kN.m) 26.1 22.6 0.0
M2 (kN.m) 88.6 22.6 106.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.283 Le1/b1 = 4.5 < 15.0 400
Beta = 0.67 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 36.4 / 37.6 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 1.36 / 1.27 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.25 / 0.26 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-31

3C13 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 875.8 21.8 71.2 859.7 -21.7 -75.5
2 863.9 20.6 77.7 847.8 -20.3 -81.5
3 875.8 21.6 71.1 859.6 -21.6 -75.4
4 650.4 13.3 49.9 634.3 -13.6 -53.5
5 665.5 20.6 39.8 649.3 -20.4 -42.5
6 702.0 6.0 51.0 685.9 -5.0 -54.0
7 809.7 23.8 75.7 793.5 -24.2 -81.1
8 826.3 24.5 71.7 810.2 -25.0 -75.6
9 801.9 20.7 55.2 785.8 -20.5 -57.6
10 861.7 25.3 76.1 845.6 -25.5 -80.9
11 875.8 21.6 71.1 859.6 -21.6 -75.4
12 722.5 43.9 59.5 708.6 -45.4 -63.2
13 743.5 -7.8 59.1 729.7 9.5 -62.6
14 743.7 18.5 67.4 729.9 -18.5 -75.8
15 722.3 17.5 51.2 708.5 -17.4 -49.9
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 722.5 - 722.5
M1 (kN.m) -45.4 -14.4 0.0
M2 (kN.m) -63.2 -14.4 -99.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.181 Le1/b1 = 4.5 < 15.0 400
Beta = 0.79 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 29.8 / 47.7 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 1.16 / 1.15 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.21 / 0.33 N/mm2
Links = R8-175

4C13 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 601.7 22.7 70.9 585.6 -22.4 -63.9
2 591.6 19.8 77.4 575.5 -19.1 -69.5
3 601.7 22.5 70.8 585.6 -22.1 -63.7
4 448.6 15.6 49.6 432.5 -15.8 -44.8
5 459.4 21.0 39.7 443.3 -20.6 -35.8
6 487.6 5.4 50.7 471.5 -4.7 -45.5
7 553.3 25.1 75.2 537.1 -25.0 -68.1
8 567.1 26.4 71.5 551.0 -26.5 -64.2
9 554.1 21.4 55.3 538.0 -20.9 -49.4
10 587.2 26.3 75.7 571.1 -26.0 -68.4
11 601.7 22.5 70.8 585.6 -22.1 -63.7
12 502.7 35.2 59.1 488.9 -36.7 -53.4
13 504.7 2.3 58.9 490.9 -0.2 -52.9
14 508.9 19.1 63.5 495.1 -18.9 -63.0
15 498.5 18.4 54.6 484.7 -18.1 -43.3
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 553.3 - 553.3
M1 (kN.m) 25.1 11.1 0.0
M2 (kN.m) 75.2 11.1 96.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.138 Le1/b1 = 4.5 < 15.0 400
Beta = 0.84 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 47.8 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 0.78 / 1.01 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.01 / 0.33 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-32

5C13 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 318.6 23.8 85.6 302.5 -25.3 -117.2
2 312.3 20.5 92.7 296.1 -22.0 -125.8
3 318.5 23.5 85.3 302.4 -25.1 -116.8
4 240.1 16.6 60.1 224.0 -17.5 -82.8
5 245.8 21.8 48.3 229.7 -23.2 -66.7
6 261.6 4.6 61.3 245.5 -5.0 -84.0
7 291.7 26.5 90.9 275.5 -28.3 -124.5
8 299.6 27.6 86.1 283.5 -29.4 -117.5
9 295.6 22.2 66.5 279.5 -23.7 -90.6
10 309.8 28.7 91.0 293.7 -30.5 -124.3
11 318.5 23.5 85.3 302.4 -25.1 -116.8
12 269.3 27.0 71.2 255.4 -29.9 -97.6
13 264.6 12.2 71.2 250.7 -11.9 -97.4
14 268.7 19.8 72.2 254.9 -21.1 -103.1
15 265.1 19.4 70.2 251.3 -20.7 -91.9
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 291.7 - 291.7
M1 (kN.m) -28.3 -5.8 0.0
M2 (kN.m) -124.5 -5.8 -150.4 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.073 Le1/b1 = 4.5 < 15.0 400
Beta = 0.91 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 19.0 / 71.8 kN As (Required): %1.09 1740.18 mm2 8T20
vc'(1/2)= 0.84 / 0.84 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.13 / 0.50 N/mm2
Links = R8-225

6C13 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 39.1 15.5 22.0 22.9 -4.6 0.0
2 35.5 13.9 25.8 19.4 -2.2 0.0
3 39.1 15.5 22.0 22.9 -4.6 0.0
4 33.5 10.4 15.0 17.4 -5.8 0.0
5 36.9 14.0 11.0 20.7 -3.7 0.0
6 41.0 2.8 15.3 24.8 1.4 0.0
7 33.8 17.1 23.5 17.7 -5.8 0.0
8 36.1 19.9 22.9 20.0 -7.4 0.0
9 40.9 14.6 17.5 24.8 -3.9 0.0
10 31.0 17.1 24.6 14.9 -6.6 0.0
11 39.1 15.5 22.0 22.9 -4.6 0.0
12 33.6 13.2 18.4 19.8 -4.7 0.0
13 32.6 12.5 18.3 18.7 -3.2 0.0
14 33.1 12.8 18.2 19.3 -3.9 0.0
15 33.1 12.8 18.5 19.2 -3.9 0.0
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 36.1 - 36.1
M1 (kN.m) 19.9 0.7 0.0
M2 (kN.m) 22.9 0.7 42.6 400
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 5.7 < 15.0 400
Beta = 0.99 Le2/b2 = 7.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 9.1 / 8.6 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 0.56 / 0.55 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.06 / 0.06 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-33

1C14 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1791.2 10.9 -28.3 1775.1 -22.7 59.0
2 1719.1 13.8 -30.8 1703.0 -27.5 64.3
3 1758.2 11.1 -28.3 1742.1 -23.2 59.0
4 1281.6 2.1 -20.1 1265.4 -5.5 41.9
5 1454.0 10.7 -15.8 1437.9 -22.4 32.3
6 1309.9 2.8 -20.4 1293.8 -5.5 42.5
7 1710.0 11.2 -28.0 1693.8 -23.9 62.4
8 1634.8 11.4 -27.6 1618.6 -25.6 58.8
9 1657.0 10.7 -24.3 1640.9 -22.1 45.8
10 1847.1 12.6 -31.2 1831.0 -24.7 63.8
11 1758.2 11.1 -28.3 1742.1 -23.2 59.0
12 1436.8 51.9 -22.9 1423.0 -53.6 48.9
13 1538.9 -34.0 -24.3 1525.1 16.3 49.4
14 1474.3 8.9 12.9 1460.4 -18.5 35.0
15 1501.4 8.9 -60.0 1487.6 -18.8 63.3
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1847.1 - 1847.1
M1 (kN.m) -24.7 -36.9 0.0
M2 (kN.m) 63.8 36.9 80.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.462 Le1/b1 = 4.7 < 15.0 400
Beta = 0.46 Le2/b2 = 5.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 7.4 kN As (Required): %0.93 1494.91 mm2 8T16
vc'(1/2)= 1.32 / 0.95 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.02 / 0.05 N/mm2
Links = R8-175

2C14 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1478.3 31.7 -81.1 1462.2 -28.8 72.6
2 1412.7 37.7 -87.6 1396.6 -33.4 79.1
3 1448.6 32.5 -81.2 1432.5 -29.7 72.7
4 1061.3 8.4 -58.2 1045.2 -8.2 51.8
5 1203.0 31.0 -44.7 1186.9 -27.9 39.7
6 1103.5 6.3 -58.4 1087.4 -2.6 52.4
7 1402.3 33.4 -85.4 1386.2 -31.1 76.0
8 1350.6 36.0 -80.0 1334.5 -34.1 72.2
9 1374.1 30.8 -63.5 1358.0 -27.6 57.3
10 1498.3 35.5 -88.6 1482.2 -33.6 78.9
11 1448.6 32.5 -81.2 1432.5 -29.7 72.7
12 1198.0 63.4 -67.3 1184.2 -61.2 60.2
13 1257.6 -11.4 -67.9 1243.8 14.1 60.9
14 1221.4 25.6 -54.9 1207.6 -23.1 45.1
15 1234.2 26.4 -80.3 1220.4 -24.0 75.9
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1498.3 - 1498.3
M1 (kN.m) 35.5 30.0 0.0
M2 (kN.m) -88.6 -30.0 -108.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.375 Le1/b1 = 4.5 < 15.0 400
Beta = 0.56 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.0 / 36.7 kN As (Required): %0.79 1257.35 mm2 8T16
vc'(1/2)= 1.24 / 1.43 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.02 / 0.26 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-34

3C14 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1127.7 27.0 -70.1 1111.6 -26.6 72.8
2 1076.8 29.5 -75.1 1060.6 -28.8 78.6
3 1103.7 28.2 -70.3 1087.6 -27.9 73.0
4 811.4 9.4 -51.0 795.3 -9.3 52.5
5 918.3 25.9 -38.4 902.1 -25.3 39.6
6 849.6 0.1 -50.5 833.5 1.7 52.5
7 1065.2 29.6 -75.2 1049.1 -29.6 77.1
8 1030.5 33.6 -69.1 1014.4 -33.9 72.3
9 1050.8 25.7 -53.1 1034.7 -25.1 56.2
10 1135.8 32.2 -76.6 1119.6 -32.5 79.2
11 1103.7 28.2 -70.3 1087.6 -27.9 73.0
12 924.2 49.0 -58.3 910.4 -50.3 60.4
13 949.1 -4.8 -58.6 935.2 6.8 61.0
14 935.2 21.6 -50.3 921.3 -21.2 47.7
15 938.1 22.6 -66.5 924.3 -22.3 73.7
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1135.8 - 1135.8
M1 (kN.m) -32.5 -22.7 0.0
M2 (kN.m) 79.2 22.7 101.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.284 Le1/b1 = 4.5 < 15.0 400
Beta = 0.67 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 34.5 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 0.89 / 1.24 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.00 / 0.24 N/mm2
Links = R8-175

4C14 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 758.0 25.6 -68.4 741.8 -24.0 58.7
2 725.1 26.6 -73.1 708.9 -24.2 63.2
3 741.4 27.0 -68.5 725.2 -25.5 58.8
4 546.4 10.1 -49.9 530.3 -10.1 42.6
5 617.3 24.2 -37.3 601.2 -22.5 31.8
6 571.4 -3.2 -49.2 555.3 5.0 42.3
7 714.5 28.7 -73.4 698.4 -27.3 62.7
8 693.4 33.9 -67.5 677.3 -33.0 58.1
9 707.1 24.1 -51.6 690.9 -22.4 44.7
10 764.6 31.6 -74.7 748.5 -30.3 64.1
11 741.4 27.0 -68.5 725.2 -25.5 58.8
12 627.5 38.1 -56.9 613.7 -38.6 48.7
13 631.9 3.8 -57.1 618.0 -0.6 49.1
14 630.7 20.4 -52.5 616.9 -19.0 38.9
15 628.7 21.5 -61.5 614.9 -20.2 58.9
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 764.6 - 764.6
M1 (kN.m) 31.6 15.3 0.0
M2 (kN.m) -74.7 -15.3 -99.4 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.191 Le1/b1 = 4.5 < 15.0 400
Beta = 0.78 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.5 / 30.8 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 0.86 / 0.99 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.01 / 0.21 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-35

5C14 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 366.5 28.1 -86.9 350.4 -34.1 125.9
2 357.3 29.8 -92.9 341.2 -37.4 134.5
3 358.7 29.9 -87.1 342.5 -36.1 126.2
4 263.4 10.2 -63.5 247.3 -11.2 91.9
5 297.2 26.3 -47.4 281.1 -32.1 68.7
6 266.1 -5.9 -62.6 250.0 5.2 90.7
7 346.3 32.0 -93.1 330.2 -38.6 134.7
8 336.1 37.7 -85.9 320.0 -44.5 124.7
9 340.8 26.2 -65.8 324.6 -32.0 95.6
10 385.0 36.4 -94.8 368.9 -43.4 136.9
11 358.7 29.9 -87.1 342.5 -36.1 126.2
12 306.4 30.7 -72.4 292.6 -37.3 104.8
13 303.4 15.2 -72.5 289.6 -18.4 105.0
14 306.0 22.3 -71.6 292.2 -27.1 99.9
15 303.8 23.6 -73.3 290.0 -28.6 109.9
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 385.0 - 385.0
M1 (kN.m) -43.4 -7.7 0.0
M2 (kN.m) 136.9 7.7 175.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.096 Le1/b1 = 4.5 < 15.0 400
Beta = 0.88 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.4 / 75.9 kN As (Required): %1.33 2125.90 mm2 8T20
vc'(1/2)= 0.89 / 0.87 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.19 / 0.53 N/mm2
Links = R8-225

6C14 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 16.1 0.0 0.0 0.0 0.0 0.0
2 16.1 0.0 0.0 0.0 0.0 0.0
3 16.1 0.0 0.0 0.0 0.0 0.0
4 16.1 0.0 0.0 0.0 0.0 0.0
5 16.1 0.0 0.0 0.0 0.0 0.0
6 16.1 0.0 0.0 0.0 0.0 0.0
7 16.1 0.0 0.0 0.0 0.0 0.0
8 16.1 0.0 0.0 0.0 0.0 0.0
9 16.1 0.0 0.0 0.0 0.0 0.0
10 16.1 0.0 0.0 0.0 0.0 0.0
11 16.1 0.0 0.0 0.0 0.0 0.0
12 13.8 0.6 0.0 0.0 0.0 0.0
13 13.8 -0.6 0.0 0.0 0.0 0.0
14 13.8 0.0 0.6 0.0 0.0 0.0
15 13.8 0.0 -0.6 0.0 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 16.1 - 16.1
M1 (kN.m) 0.0 -0.3 0.0
M2 (kN.m) 0.0 0.3 0.6 400
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.004 Le1/b1 = 6.4 < 15.0 400
Beta = 1.00 Le2/b2 = 7.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.2 / 0.2 kN As (Required): %0.40 (min) 640.00 mm2 8T16
vc'(1/2)= 0.54 / 0.54 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-36

1C15 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2613.7 -34.4 -33.6 2597.6 71.4 70.1
2 2516.6 -34.5 -33.8 2500.4 72.7 70.7
3 2497.3 -34.1 -36.2 2481.2 70.6 75.6
4 1797.1 -16.7 -20.9 1781.0 33.6 43.5
5 2201.7 -34.0 -14.5 2185.5 70.5 29.5
6 2540.0 -34.9 -34.0 2523.9 72.9 70.8
7 2242.0 -33.2 -13.2 2225.9 68.5 31.6
8 2267.9 -35.7 -20.7 2251.8 72.3 44.9
9 2595.2 -34.8 -35.0 2579.1 72.5 68.2
10 2119.5 -15.0 -33.6 2103.4 32.6 68.6
11 2497.3 -34.1 -36.2 2481.2 70.6 75.6
12 2231.1 14.1 -26.8 2217.3 24.9 57.6
13 2102.1 -70.6 -29.0 2088.3 92.4 58.6
14 2201.5 -28.4 14.4 2187.7 59.1 31.5
15 2131.7 -28.2 -70.1 2117.9 58.3 84.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 2613.7 - 2613.7
M1 (kN.m) 71.4 52.3 92.4
M2 (kN.m) 70.1 52.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.653 Le1/b1 = 4.7 < 15.0 400
Beta = 0.30 Le2/b2 = 5.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.6 / 5.7 kN As (Required): %2.32 3715.59 mm2 12T20
vc'(1/2)= 1.14 / 1.25 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.03 / 0.04 N/mm2
Links = R8-225

2C15 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2085.9 -103.9 -93.9 2069.8 102.7 81.2
2 2001.8 -105.2 -95.4 1985.7 103.5 85.0
3 1995.3 -102.5 -101.6 1979.1 101.0 88.6
4 1442.4 -49.8 -57.8 1426.3 50.1 47.9
5 1752.1 -102.2 -38.9 1736.0 100.6 31.9
6 2007.0 -107.0 -96.2 1990.9 107.8 85.5
7 1802.4 -99.0 -39.2 1786.3 96.6 28.9
8 1807.4 -105.3 -58.7 1791.3 103.2 50.2
9 2055.3 -105.7 -93.9 2039.1 104.9 84.6
10 1715.7 -46.5 -92.2 1699.6 45.3 78.3
11 1995.3 -102.5 -101.6 1979.1 101.0 88.6
12 1767.7 -49.7 -77.3 1753.9 48.5 67.0
13 1690.7 -121.0 -78.5 1676.9 120.3 67.9
14 1750.3 -86.1 -48.2 1736.5 85.3 36.8
15 1708.2 -84.6 -107.6 1694.3 83.5 98.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 2085.9 - 2085.9
M1 (kN.m) -103.9 -41.7 -140.9
M2 (kN.m) -93.9 -41.7 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.521 Le1/b1 = 4.6 < 15.0 400
Beta = 0.39 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 80.4 / 35.2 kN As (Required): %2.06 3300.82 mm2 12T20
vc'(1/2)= 2.21 / 1.89 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.56 / 0.25 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-37

3C15 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1573.0 -103.5 -71.9 1556.9 107.1 71.2
2 1505.3 -104.2 -76.6 1489.1 107.6 77.1
3 1506.0 -101.4 -79.1 1489.9 104.7 78.5
4 1093.1 -51.1 -41.5 1077.0 53.3 39.9
5 1320.6 -100.9 -26.6 1304.5 104.2 25.4
6 1505.3 -110.3 -77.9 1489.2 115.0 78.1
7 1366.1 -96.2 -23.2 1350.0 98.8 20.5
8 1362.2 -103.0 -43.4 1346.1 106.0 42.9
9 1543.3 -106.2 -75.6 1527.1 110.0 76.4
10 1303.9 -45.5 -68.7 1287.8 47.0 67.1
11 1506.0 -101.4 -79.1 1489.9 104.7 78.5
12 1321.0 -59.9 -59.7 1307.1 61.0 59.0
13 1287.4 -110.3 -59.8 1273.6 115.0 59.3
14 1313.6 -86.2 -39.2 1299.8 89.2 34.9
15 1294.7 -84.0 -80.4 1280.9 86.8 83.4
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1505.3 - 1505.3
M1 (kN.m) 115.0 30.1 158.7
M2 (kN.m) 78.1 30.1 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.376 Le1/b1 = 4.6 < 15.0 400
Beta = 0.56 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 75.1 / 54.6 kN As (Required): %1.51 2419.12 mm2 8T20
vc'(1/2)= 1.74 / 1.75 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.53 / 0.38 N/mm2
Links = R8-225

4C15 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1065.8 -108.0 -68.4 1049.6 106.5 63.9
2 1016.5 -108.7 -74.7 1000.4 107.2 71.2
3 1021.1 -105.4 -75.9 1005.0 103.8 71.2
4 745.7 -53.9 -38.1 729.5 53.3 34.4
5 895.3 -104.8 -23.5 879.2 103.2 20.9
6 1018.0 -116.9 -76.2 1001.9 116.1 72.5
7 930.0 -99.0 -18.7 913.9 97.1 14.6
8 922.4 -106.5 -40.7 906.3 104.8 37.7
9 1041.6 -111.2 -73.5 1025.5 109.8 70.6
10 887.5 -47.2 -64.3 871.4 46.1 59.3
11 1021.1 -105.4 -75.9 1005.0 103.8 71.2
12 887.4 -72.9 -57.2 873.6 69.7 53.3
13 880.1 -104.7 -56.6 866.3 105.4 53.0
14 886.2 -90.0 -43.8 872.4 88.8 36.1
15 881.4 -87.6 -70.1 867.6 86.3 70.2
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1018.0 - 1018.0
M1 (kN.m) -116.9 -20.4 -170.6
M2 (kN.m) -76.2 -20.4 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.254 Le1/b1 = 4.6 < 15.0 400
Beta = 0.70 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 70.0 / 46.8 kN As (Required): %1.16 1860.60 mm2 8T20
vc'(1/2)= 1.39 / 1.40 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.49 / 0.33 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-38

5C15 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 570.0 -125.8 -68.2 553.9 148.1 76.1
2 539.3 -124.3 -76.0 523.2 145.1 84.5
3 546.7 -122.6 -76.1 530.5 144.5 84.8
4 404.7 -65.3 -36.4 388.6 78.2 40.7
5 482.5 -121.7 -21.8 466.3 143.4 24.2
6 550.6 -137.9 -78.1 534.4 162.3 87.2
7 500.3 -114.7 -14.9 484.2 135.6 17.2
8 493.4 -122.6 -39.6 477.3 142.6 44.2
9 556.6 -129.6 -75.2 540.4 152.4 82.9
10 470.1 -55.0 -62.9 454.0 66.6 69.9
11 546.7 -122.6 -76.1 530.5 144.5 84.8
12 471.4 -96.6 -57.3 457.5 113.2 63.9
13 474.5 -110.2 -56.1 460.7 130.4 62.8
14 472.6 -104.8 -50.8 458.8 123.3 53.9
15 473.2 -102.0 -62.6 459.4 120.3 72.7
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 550.6 - 550.6
M1 (kN.m) 162.3 11.0 235.4
M2 (kN.m) 87.2 11.0 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.138 Le1/b1 = 4.6 < 15.0 400
Beta = 0.84 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 100.0 / 45.1 kN As (Required): %2.10 3355.63 mm2 12T20
vc'(1/2)= 1.15 / 1.09 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.70 / 0.32 N/mm2
Links = R8-225

6C15 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 43.1 -18.0 -57.3 27.0 0.0 -4.2
2 36.2 -27.8 -61.3 20.1 0.0 2.2
3 41.9 -17.4 -62.9 25.8 0.0 -2.6
4 43.3 0.8 -34.2 27.1 0.0 -5.5
5 35.6 -17.5 -21.8 19.5 0.0 -5.5
6 36.2 -10.5 -59.8 20.0 0.0 1.6
7 45.4 -16.1 -22.4 29.2 0.0 -13.1
8 39.2 -26.7 -37.5 23.0 0.0 -2.6
9 32.9 -18.4 -58.0 16.8 0.0 4.3
10 47.2 -7.7 -55.6 31.1 0.0 -6.5
11 41.9 -17.4 -62.9 25.8 0.0 -2.6
12 36.1 -14.1 -48.0 22.3 0.0 -2.9
13 36.7 -15.5 -47.5 22.9 0.0 -3.4
14 36.6 -15.0 -47.1 22.8 0.0 -4.9
15 36.2 -14.5 -48.3 22.4 0.0 -1.4
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 36.2 - 36.2
M1 (kN.m) -27.8 -0.7 0.0
M2 (kN.m) -61.3 -0.7 -88.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 6.4 < 15.0 400
Beta = 0.99 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 9.2 / 21.2 kN As (Required): %0.78 1252.50 mm2 8T16
vc'(1/2)= 0.55 / 0.55 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.06 / 0.15 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-39

3C16 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2496.0 0.0 185.3 2479.9 0.2 -191.0
2 2031.1 59.6 145.4 2015.0 -60.8 -149.1
3 2414.3 -0.3 192.1 2398.2 0.6 -197.9
4 1996.6 -58.9 149.5 1980.5 60.4 -154.8
5 1983.0 -2.0 87.7 1966.9 2.5 -90.8
6 2031.2 -57.2 144.7 2015.1 59.1 -148.7
7 2496.3 -0.9 186.8 2480.2 1.0 -193.4
8 2008.5 57.3 142.6 1992.4 -58.5 -146.7
9 1984.7 -1.6 86.0 1968.5 2.1 -88.2
10 2484.0 0.7 193.0 2467.9 -0.7 -199.6
11 2414.3 -0.3 192.1 2398.2 0.6 -197.9
12 2063.6 20.8 152.9 2049.8 -23.3 -157.7
13 2060.2 -20.7 152.8 2046.4 23.7 -157.4
14 2044.9 0.0 173.5 2031.1 0.2 -181.8
15 2078.9 0.0 132.2 2065.1 0.2 -133.2
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 2484.0 - 2484.0
M1 (kN.m) -0.7 -49.7 0.0
M2 (kN.m) -199.6 -49.7 -214.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.621 Le1/b1 = 5.0 < 15.0 400
Beta = 0.30 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 118.5 kN As (Required): %3.70 5916.10 mm2 20T20
vc'(1/2)= 1.61 / 2.62 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.83 N/mm2
Links = R8-225

4C16 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1666.4 3.3 191.1 1650.3 -6.6 -187.8
2 1360.0 62.2 149.2 1343.9 -61.8 -146.0
3 1611.8 2.9 198.0 1595.6 -6.1 -194.6
4 1333.1 -56.3 154.7 1316.9 51.0 -152.6
5 1326.0 0.8 90.9 1309.9 -3.9 -89.7
6 1359.7 -54.3 148.3 1343.5 48.9 -145.3
7 1664.9 2.3 192.8 1648.8 -5.6 -190.4
8 1343.6 61.2 147.0 1327.5 -62.2 -144.3
9 1329.0 1.3 89.0 1312.8 -4.4 -86.7
10 1656.2 2.2 199.7 1640.1 -4.0 -196.9
11 1611.8 2.9 198.0 1595.6 -6.1 -194.6
12 1378.5 16.4 157.3 1364.7 -21.9 -154.7
13 1375.3 -11.0 157.9 1361.5 11.1 -155.0
14 1369.6 2.7 170.8 1355.8 -5.4 -172.0
15 1384.3 2.7 144.3 1370.4 -5.4 -137.8
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1656.2 - 1656.2
M1 (kN.m) -4.0 -33.1 0.0
M2 (kN.m) 199.7 33.1 216.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.414 Le1/b1 = 5.0 < 15.0 400
Beta = 0.51 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.6 / 114.3 kN As (Required): %2.56 4099.07 mm2 16T20
vc'(1/2)= 1.49 / 1.99 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.01 / 0.80 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-40

5C16 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 849.7 -0.6 206.0 833.6 11.6 -230.2
2 698.3 69.0 160.5 682.1 -76.3 -179.6
3 822.0 -1.1 213.4 805.8 12.0 -238.2
4 680.2 -68.8 167.2 664.1 92.4 -186.5
5 678.8 -3.7 98.5 662.7 15.0 -110.5
6 696.7 -67.9 159.0 680.6 93.9 -177.6
7 848.3 -1.5 208.4 832.1 12.2 -232.4
8 687.0 66.5 158.5 670.9 -71.0 -177.1
9 681.3 -3.3 96.1 665.2 14.8 -108.6
10 844.4 1.0 216.2 828.3 4.8 -241.7
11 822.0 -1.1 213.4 805.8 12.0 -238.2
12 703.6 6.3 169.3 689.7 0.0 -189.3
13 701.6 -7.3 170.5 687.7 19.1 -190.4
14 700.7 -0.5 175.9 686.8 9.6 -199.3
15 704.5 -0.5 163.9 690.6 9.5 -180.4
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 680.2 - 680.2
M1 (kN.m) 92.4 13.6 0.0
M2 (kN.m) -186.5 -13.6 -260.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.170 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 5.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 53.7 / 150.5 kN As (Required): %2.45 3915.08 mm2 16T20
vc'(1/2)= 1.30 / 1.47 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.38 / 1.05 N/mm2
Links = R8-225

6C16 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 11.3 14.3 127.6 -4.9 0.0 -24.9
2 18.6 26.9 98.9 2.5 0.0 -17.2
3 10.5 13.8 132.7 -5.6 0.0 -26.3
4 11.9 -5.1 104.1 -4.3 0.0 -23.7
5 14.3 13.3 59.1 -1.8 0.0 -13.0
6 18.6 3.7 100.6 2.4 0.0 -17.7
7 6.7 12.8 127.8 -9.4 0.0 -28.8
8 15.7 25.7 97.2 -0.4 0.0 -19.8
9 19.2 14.3 57.5 3.1 0.0 -8.3
10 7.4 6.6 132.8 -8.7 0.0 -28.3
11 10.5 13.8 132.7 -5.6 0.0 -26.3
12 10.6 12.8 105.0 -3.2 0.0 -20.5
13 10.0 10.7 105.5 -3.8 0.0 -20.9
14 10.1 11.9 105.9 -3.7 0.0 -22.5
15 10.5 11.6 104.6 -3.3 0.0 -18.9
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 10.5 - 10.5
M1 (kN.m) 13.8 0.2 0.0
M2 (kN.m) 132.7 0.2 146.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.003 Le1/b1 = 6.7 < 15.0 400
Beta = 1.00 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.3 / 53.7 kN As (Required): %1.42 2269.90 mm2 8T20
vc'(1/2)= 0.59 / 0.60 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.03 / 0.38 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-41

1C17 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1864.1 -22.6 45.7 1848.0 46.9 -94.9
2 1844.3 -22.2 45.6 1828.1 47.0 -94.5
3 1864.0 -22.7 45.9 1847.8 46.9 -95.1
4 1278.2 -12.3 30.9 1262.0 24.4 -64.1
5 1452.3 -22.1 23.7 1436.1 45.9 -49.9
6 1829.6 -23.0 45.5 1813.5 48.0 -94.7
7 1508.0 -21.5 26.5 1491.9 44.0 -50.9
8 1607.9 -23.8 31.7 1591.7 47.0 -64.2
9 1833.2 -23.1 42.9 1817.1 47.9 -93.8
10 1549.1 -10.3 44.9 1533.0 23.3 -94.6
11 1864.0 -22.7 45.9 1847.8 46.9 -95.1
12 1622.0 22.4 39.0 1608.2 6.0 -79.0
13 1489.7 -59.9 36.8 1475.9 71.7 -78.3
14 1583.2 -17.8 73.6 1569.4 38.1 -91.7
15 1528.5 -19.7 2.1 1514.7 39.6 -65.5
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 1864.0 - 1864.0
M1 (kN.m) 46.9 37.3 0.0
M2 (kN.m) -95.1 -37.3 -116.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.466 Le1/b1 = 4.7 < 15.0 400
Beta = 0.46 Le2/b2 = 5.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.5 / 22.6 kN As (Required): %1.42 2270.51 mm2 8T20
vc'(1/2)= 1.15 / 1.32 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.04 / 0.16 N/mm2
Links = R8-225

2C17 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1477.3 -67.5 129.4 1461.2 66.7 -119.4
2 1464.1 -67.6 129.8 1447.9 66.5 -119.3
3 1476.9 -67.6 129.6 1460.8 66.8 -119.5
4 1015.6 -35.1 86.6 999.4 34.9 -80.4
5 1150.9 -65.8 67.8 1134.8 64.6 -63.1
6 1442.0 -69.5 129.6 1425.9 70.0 -119.4
7 1200.3 -62.9 69.3 1184.2 60.9 -64.9
8 1277.1 -68.4 88.5 1261.0 66.7 -81.5
9 1450.5 -69.2 127.8 1434.4 68.8 -117.5
10 1237.8 -32.3 127.8 1221.7 31.4 -118.2
11 1476.9 -67.6 129.6 1460.8 66.8 -119.5
12 1273.9 -21.5 107.7 1260.1 20.6 -99.5
13 1192.8 -90.3 106.7 1178.9 89.9 -98.4
14 1252.3 -55.3 118.8 1238.5 54.6 -113.4
15 1214.3 -56.5 95.7 1200.5 55.8 -84.5
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 1476.9 - 1476.9
M1 (kN.m) -67.6 -29.5 0.0
M2 (kN.m) 129.6 29.5 168.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.369 Le1/b1 = 4.6 < 15.0 400
Beta = 0.57 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 60.0 / 55.7 kN As (Required): %1.64 2625.31 mm2 12T20
vc'(1/2)= 1.77 / 1.59 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.42 / 0.39 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-42

3C17 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1107.4 -65.8 111.2 1091.2 67.8 -115.7
2 1098.5 -66.3 112.3 1082.4 68.2 -116.1
3 1106.9 -66.0 111.1 1090.8 68.0 -115.6
4 763.8 -33.6 73.7 747.7 34.8 -77.3
5 864.3 -63.4 58.8 848.1 65.2 -61.4
6 1076.9 -70.1 111.9 1060.8 72.9 -116.0
7 903.9 -59.0 58.1 887.8 60.1 -62.1
8 960.4 -65.3 76.4 944.2 66.8 -79.4
9 1086.2 -68.3 111.9 1070.0 70.6 -115.1
10 932.4 -30.3 109.0 916.3 31.1 -113.9
11 1106.9 -66.0 111.1 1090.8 68.0 -115.6
12 943.7 -30.2 92.4 929.8 30.1 -96.3
13 905.8 -78.7 91.8 892.0 82.2 -95.4
14 936.2 -54.0 99.6 922.4 55.7 -108.3
15 913.3 -54.9 84.6 899.4 56.6 -83.4
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1076.9 - 1076.9
M1 (kN.m) 72.9 21.5 0.0
M2 (kN.m) -116.0 -21.5 -166.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.269 Le1/b1 = 4.6 < 15.0 400
Beta = 0.69 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 53.6 / 74.3 kN As (Required): %1.15 1845.31 mm2 8T20
vc'(1/2)= 1.40 / 1.42 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.38 / 0.52 N/mm2
Links = R8-225

4C17 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 744.7 -68.5 113.4 728.6 68.8 -108.8
2 739.6 -69.5 114.8 723.5 69.6 -110.0
3 744.4 -68.8 113.2 728.2 69.0 -108.5
4 516.4 -34.6 75.0 500.3 34.9 -72.1
5 583.3 -65.7 60.2 567.2 65.9 -57.9
6 722.3 -74.1 114.4 706.2 74.9 -110.0
7 611.1 -60.2 59.1 595.0 60.0 -56.7
8 648.4 -67.3 78.1 632.3 67.1 -74.7
9 730.1 -71.6 114.6 714.0 72.1 -109.9
10 630.1 -31.2 110.8 613.9 31.3 -106.2
11 744.4 -68.8 113.2 728.2 69.0 -108.5
12 627.6 -41.5 94.1 613.8 39.8 -90.5
13 616.9 -72.1 93.8 603.1 74.2 -89.7
14 628.0 -56.5 98.0 614.2 56.7 -99.6
15 616.4 -57.0 89.9 602.6 57.3 -80.7
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 722.3 - 722.3
M1 (kN.m) 74.9 14.4 0.0
M2 (kN.m) 114.4 14.4 173.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.181 Le1/b1 = 4.6 < 15.0 400
Beta = 0.79 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 48.7 / 72.3 kN As (Required): %1.17 1864.01 mm2 8T20
vc'(1/2)= 1.15 / 1.17 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.34 / 0.51 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-43

5C17 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 388.1 -72.8 124.0 372.0 77.3 -146.2
2 386.0 -73.5 124.8 369.9 78.2 -145.8
3 387.9 -73.1 123.7 371.8 77.6 -146.0
4 272.9 -37.0 82.3 256.7 39.0 -97.8
5 307.6 -69.7 66.1 291.5 74.0 -78.3
6 376.3 -79.8 124.0 360.2 84.6 -144.1
7 322.0 -63.3 66.4 305.9 67.1 -81.4
8 341.3 -71.7 85.7 325.1 76.0 -101.3
9 380.8 -76.5 124.0 364.7 81.2 -143.8
10 329.4 -31.9 121.5 313.3 33.9 -144.5
11 387.9 -73.1 123.7 371.8 77.6 -146.0
12 324.1 -53.7 102.7 310.2 55.6 -121.1
13 325.4 -66.9 102.7 311.5 72.4 -121.0
14 326.9 -60.2 103.7 313.0 63.9 -127.0
15 322.6 -60.4 101.6 308.8 64.1 -115.1
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 376.3 - 376.3
M1 (kN.m) 84.6 7.5 0.0
M2 (kN.m) -144.1 -7.5 -219.2 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.094 Le1/b1 = 4.6 < 15.0 400
Beta = 0.89 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 47.9 / 88.7 kN As (Required): %1.95 3123.51 mm2 12T20
vc'(1/2)= 0.97 / 0.97 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.34 / 0.62 N/mm2
Links = R8-225

6C17 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 29.0 -53.5 72.7 12.9 22.0 -8.6
2 29.4 -52.6 76.3 13.3 21.5 -10.3
3 28.8 -53.5 72.6 12.7 22.0 -8.1
4 29.3 -29.6 46.5 13.2 13.7 -6.8
5 28.3 -50.9 37.9 12.2 20.5 -6.5
6 26.0 -57.9 78.2 9.8 25.8 -10.8
7 30.0 -46.6 31.5 13.8 17.6 -3.8
8 30.5 -51.2 49.2 14.4 20.5 -8.8
9 28.5 -56.0 78.2 12.4 23.6 -11.2
10 31.3 -26.6 68.1 15.1 10.9 -6.2
11 28.8 -53.5 72.6 12.7 22.0 -8.1
12 24.9 -44.5 60.6 11.1 18.0 -7.5
13 25.4 -44.4 60.0 11.6 19.0 -7.2
14 25.5 -44.5 59.5 11.7 18.5 -8.3
15 24.8 -44.3 61.1 11.0 18.5 -6.4
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 26.0 - 26.0
M1 (kN.m) -57.9 -0.5 0.0
M2 (kN.m) 78.2 0.5 135.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 5.8 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.9 / 29.7 kN As (Required): %1.29 2056.15 mm2 8T20
vc'(1/2)= 0.64 / 0.64 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.20 / 0.21 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-44

3C18 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1995.6 1.3 -217.2 1979.5 -1.6 222.6
2 1617.7 37.3 -174.6 1601.5 -38.2 179.4
3 1995.0 1.2 -216.9 1978.8 -1.5 222.3
4 1625.8 -34.9 -177.0 1609.7 35.3 180.9
5 1481.1 -0.7 -110.5 1465.0 0.6 113.2
6 1621.0 -32.4 -176.0 1604.9 33.0 180.6
7 1996.9 0.6 -217.6 1980.8 -1.0 222.0
8 1602.3 36.1 -170.4 1586.2 -37.2 175.0
9 1479.9 -0.3 -110.0 1463.7 0.2 113.7
10 2015.8 0.0 -222.3 1999.7 -0.4 227.4
11 1995.0 1.2 -216.9 1978.8 -1.5 222.3
12 1654.5 22.5 -178.8 1640.6 -25.7 183.1
13 1657.6 -20.4 -179.4 1643.8 23.0 184.0
14 1645.0 0.8 -171.5 1631.2 -1.1 171.0
15 1667.1 1.3 -186.7 1653.2 -1.6 196.1
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 2015.8 - 2015.8
M1 (kN.m) -0.4 -40.3 0.0
M2 (kN.m) 227.4 40.3 244.1 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.504 Le1/b1 = 5.0 < 15.0 400
Beta = 0.42 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 127.6 kN As (Required): %3.45 5523.85 mm2 20T20
vc'(1/2)= 1.70 / 2.29 N/mm2 As (Provided): %3.93 6283.19 mm2
v (1/2)= 0.00 / 0.89 N/mm2
Links = R8-225

4C18 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1346.2 3.1 -222.9 1330.1 -4.0 215.5
2 1092.7 39.6 -179.1 1076.6 -39.5 173.4
3 1345.7 3.0 -222.5 1329.5 -3.8 215.0
4 1099.0 -34.4 -181.8 1082.9 33.0 175.6
5 1002.7 0.6 -114.0 986.5 -1.3 110.5
6 1095.2 -31.5 -180.5 1079.0 30.4 174.4
7 1347.4 2.3 -223.5 1331.3 -3.2 215.9
8 1083.4 39.2 -175.1 1067.2 -39.7 169.5
9 1001.5 1.0 -113.4 985.4 -1.7 110.2
10 1359.4 0.5 -228.2 1343.3 -1.1 220.6
11 1345.7 3.0 -222.5 1329.5 -3.8 215.0
12 1116.9 16.7 -183.6 1103.0 -20.4 177.3
13 1118.3 -11.7 -184.0 1104.5 13.9 178.1
14 1111.9 2.4 -179.7 1098.1 -3.1 168.1
15 1123.2 2.6 -187.9 1109.4 -3.4 187.2
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 1359.4 - 1359.4
M1 (kN.m) -1.1 -27.2 0.0
M2 (kN.m) -228.2 -27.2 -244.6 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.340 Le1/b1 = 5.0 < 15.0 400
Beta = 0.60 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 125.1 kN As (Required): %2.62 4186.83 mm2 16T20
vc'(1/2)= 1.41 / 1.78 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.00 / 0.88 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-45

5C18 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 697.6 4.0 -236.1 681.4 -3.5 264.6
2 568.7 43.5 -189.6 552.5 -47.0 212.6
3 697.2 3.9 -235.6 681.1 -3.3 264.1
4 572.3 -36.8 -192.3 556.2 41.0 214.9
5 524.8 1.0 -120.5 508.7 -0.3 133.8
6 569.8 -32.9 -191.6 553.7 36.5 215.5
7 698.4 3.1 -236.2 682.3 -2.5 263.7
8 564.3 42.2 -185.3 548.2 -45.1 207.3
9 524.1 1.5 -120.1 507.9 -0.8 134.0
10 704.4 1.3 -241.2 688.3 -0.9 269.3
11 697.2 3.9 -235.6 681.1 -3.3 264.1
12 579.5 10.4 -194.7 565.6 -12.7 218.0
13 579.9 -3.8 -194.7 566.1 6.9 218.1
14 577.5 3.4 -193.5 563.7 -2.9 212.0
15 581.8 3.2 -195.8 568.0 -2.8 224.2
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 704.4 - 704.4
M1 (kN.m) 1.3 14.1 0.0
M2 (kN.m) 269.3 14.1 280.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.176 Le1/b1 = 5.0 < 15.0 400
Beta = 0.80 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 30.2 / 170.2 kN As (Required): %2.73 4362.32 mm2 16T20
vc'(1/2)= 1.26 / 1.37 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.21 / 1.19 N/mm2
Links = R8-225

6C18 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 47.6 0.7 -173.8 31.5 -3.7 23.5
2 43.6 25.7 -139.4 27.5 -8.5 19.5
3 47.3 0.7 -173.3 31.2 -3.7 22.8
4 44.8 -24.4 -142.6 28.7 2.8 21.1
5 44.8 -1.4 -91.8 28.7 -2.5 16.5
6 44.1 -25.1 -138.4 27.9 2.7 19.2
7 48.0 0.7 -176.0 31.9 -3.6 24.5
8 44.6 27.5 -137.7 28.4 -10.4 19.8
9 44.4 -1.3 -90.4 28.3 -2.6 15.6
10 47.4 -0.4 -179.7 31.3 -1.7 25.1
11 47.3 0.7 -173.3 31.2 -3.7 22.8
12 40.7 1.6 -143.1 26.9 -4.2 19.4
13 40.7 -0.5 -143.6 26.9 -1.8 19.7
14 40.4 0.6 -144.1 26.5 -3.1 18.5
15 41.1 0.4 -142.6 27.3 -3.0 20.6
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 47.4 - 47.4
M1 (kN.m) -1.7 -0.9 0.0
M2 (kN.m) -179.7 -0.9 -181.4 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.012 Le1/b1 = 6.2 < 15.0 400
Beta = 0.99 Le2/b2 = 6.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 12.6 / 68.3 kN As (Required): %1.77 2839.65 mm2 12T20
vc'(1/2)= 0.74 / 0.74 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.09 / 0.48 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-46

1C19 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1776.1 31.5 40.8 1760.0 -65.7 -84.4
2 1787.3 32.2 40.8 1771.2 -66.1 -84.1
3 1775.4 31.5 40.8 1759.3 -65.7 -84.5
4 1182.4 16.2 27.5 1166.2 -34.8 -57.3
5 1331.4 31.5 21.3 1315.3 -65.6 -44.8
6 1781.1 31.7 40.5 1765.0 -65.7 -84.3
7 1327.0 31.2 24.3 1310.9 -65.5 -46.4
8 1521.0 30.1 29.2 1504.9 -65.2 -58.2
9 1779.2 31.6 37.7 1763.1 -65.8 -82.8
10 1443.6 18.1 39.3 1427.5 -35.7 -83.5
11 1775.4 31.5 40.8 1759.3 -65.7 -84.5
12 1507.2 60.0 36.2 1493.4 -72.1 -71.2
13 1451.6 -7.7 31.4 1437.8 -37.0 -68.8
14 1523.8 26.9 72.7 1510.0 -55.0 -90.8
15 1435.1 25.4 -5.1 1421.2 -54.2 -49.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1787.3 - 1787.3
M1 (kN.m) -66.1 -35.7 0.0
M2 (kN.m) -84.1 -35.7 -115.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.447 Le1/b1 = 5.3 < 15.0 400
Beta = 0.48 Le2/b2 = 5.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 9.8 / 14.7 kN As (Required): %1.29 2070.21 mm2 8T20
vc'(1/2)= 1.13 / 1.19 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.07 / 0.10 N/mm2
Links = R8-225

2C19 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1431.7 92.3 116.9 1415.6 -85.6 -110.5
2 1442.3 92.6 118.0 1426.2 -86.0 -111.1
3 1430.8 92.2 116.9 1414.7 -85.6 -110.3
4 953.1 49.1 78.0 937.0 -45.4 -74.1
5 1075.1 92.1 61.7 1058.9 -85.4 -59.0
6 1436.5 92.9 117.0 1420.4 -86.0 -110.3
7 1069.7 91.5 64.1 1053.6 -85.0 -61.5
8 1228.0 90.3 82.1 1211.8 -83.9 -77.6
9 1436.0 92.6 114.5 1419.9 -85.8 -107.9
10 1162.6 50.8 113.7 1146.5 -47.0 -107.7
11 1430.8 92.2 116.9 1414.7 -85.6 -110.3
12 1212.0 90.7 98.5 1198.2 -87.9 -93.3
13 1173.4 62.6 95.1 1159.6 -54.2 -89.8
14 1223.8 76.8 119.4 1210.0 -71.3 -115.9
15 1161.6 76.5 74.2 1147.8 -70.9 -67.2
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1442.3 - 1442.3
M1 (kN.m) 92.6 28.8 0.0
M2 (kN.m) 118.0 28.8 171.5 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.361 Le1/b1 = 5.7 < 15.0 400
Beta = 0.58 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 58.8 / 50.7 kN As (Required): %1.65 2642.09 mm2 12T20
vc'(1/2)= 1.63 / 1.54 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.41 / 0.35 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-47

3C19 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1083.1 82.5 103.6 1066.9 -83.7 -106.7
2 1092.1 82.1 106.3 1075.9 -83.6 -108.8
3 1082.2 82.4 103.2 1066.1 -83.7 -106.3
4 722.1 44.5 67.5 706.0 -44.9 -70.2
5 815.3 82.2 55.3 799.1 -83.5 -57.4
6 1087.2 83.6 104.3 1071.0 -84.6 -107.1
7 809.9 81.4 55.1 793.8 -82.8 -58.0
8 930.8 80.4 73.8 914.7 -81.7 -75.9
9 1087.6 82.9 104.0 1071.4 -84.0 -106.2
10 879.3 45.2 99.3 863.2 -46.0 -102.7
11 1082.2 82.4 103.2 1066.1 -83.7 -106.3
12 914.2 79.0 87.0 900.4 -83.5 -89.9
13 890.8 58.0 84.7 876.9 -55.5 -87.0
14 921.2 68.6 101.7 907.3 -69.7 -108.5
15 883.8 68.4 69.9 870.0 -69.4 -68.4
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 1092.1 - 1092.1
M1 (kN.m) -83.6 -21.8 0.0
M2 (kN.m) -108.8 -21.8 -165.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.273 Le1/b1 = 5.7 < 15.0 400
Beta = 0.68 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 54.7 / 67.4 kN As (Required): %1.16 1863.25 mm2 8T20
vc'(1/2)= 1.33 / 1.38 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.38 / 0.47 N/mm2
Links = R8-225

4C19 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 734.2 84.2 105.6 718.0 -82.1 -104.2
2 740.9 83.7 109.0 724.8 -81.6 -107.2
3 733.5 84.1 105.1 717.3 -82.0 -103.6
4 491.6 45.7 68.3 475.5 -44.5 -67.6
5 554.9 83.9 56.8 538.8 -81.8 -56.5
6 737.1 85.5 106.5 721.0 -83.4 -104.8
7 550.7 83.0 55.9 534.5 -81.0 -55.7
8 632.9 81.9 75.8 616.8 -80.1 -74.8
9 737.8 84.6 106.8 721.7 -82.4 -105.1
10 596.6 46.1 100.6 580.5 -44.7 -99.4
11 733.5 84.1 105.1 717.3 -82.0 -103.6
12 618.0 76.5 88.2 604.1 -78.5 -87.4
13 606.1 63.4 86.8 592.2 -57.8 -85.3
14 621.3 70.0 97.7 607.5 -68.2 -100.9
15 602.7 69.9 77.3 588.9 -68.1 -71.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 740.9 - 740.9
M1 (kN.m) 83.7 14.8 0.0
M2 (kN.m) 109.0 14.8 174.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.185 Le1/b1 = 5.7 < 15.0 400
Beta = 0.79 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 54.7 / 66.7 kN As (Required): %1.17 1879.20 mm2 8T20
vc'(1/2)= 1.11 / 1.14 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.38 / 0.47 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-48

5C19 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 383.7 89.5 112.0 367.6 -99.2 -123.5
2 387.7 89.0 115.6 371.6 -98.4 -126.5
3 383.3 89.3 111.4 367.2 -99.1 -122.8
4 260.6 48.2 72.6 244.4 -53.7 -80.7
5 293.3 89.1 60.1 277.1 -98.8 -65.8
6 385.2 90.5 113.3 369.0 -100.1 -125.1
7 290.6 88.2 59.4 274.5 -98.1 -65.9
8 333.6 86.4 80.4 317.4 -95.9 -87.8
9 385.9 89.8 113.0 369.8 -99.6 -123.8
10 313.2 49.8 106.5 297.0 -55.3 -117.8
11 383.3 89.3 111.4 367.2 -99.1 -122.8
12 322.4 77.3 93.2 308.6 -89.0 -103.0
13 318.1 71.2 92.5 304.3 -75.7 -101.6
14 323.4 74.2 97.9 309.6 -82.4 -111.7
15 317.1 74.3 87.8 303.3 -82.3 -92.9
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 385.2 - 385.2
M1 (kN.m) -100.1 -7.7 0.0
M2 (kN.m) -125.1 -7.7 -213.7 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.096 Le1/b1 = 5.7 < 15.0 400
Beta = 0.88 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 62.6 / 74.7 kN As (Required): %1.88 3000.02 mm2 12T20
vc'(1/2)= 0.95 / 0.97 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.44 / 0.52 N/mm2
Links = R8-225

6C19 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 36.5 60.7 78.7 20.4 -15.0 -13.3
2 37.1 61.3 83.6 21.0 -15.1 -15.1
3 36.3 60.7 78.1 20.2 -15.0 -12.9
4 32.3 32.3 48.6 16.1 -10.1 -9.7
5 33.9 60.6 44.4 17.8 -15.0 -9.5
6 36.6 62.6 78.2 20.5 -15.5 -13.3
7 33.4 59.3 41.3 17.3 -14.7 -8.5
8 36.6 59.4 58.9 20.4 -14.4 -13.4
9 36.9 61.2 81.8 20.8 -15.1 -14.4
10 32.7 32.3 73.8 16.5 -10.2 -11.4
11 36.3 60.7 78.1 20.2 -15.0 -12.9
12 31.4 50.5 65.2 17.6 -13.4 -11.3
13 31.0 50.5 65.3 17.2 -12.1 -11.2
14 31.5 50.4 64.9 17.7 -12.7 -12.1
15 31.0 50.6 65.6 17.1 -12.8 -10.4
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 37.1 - 37.1
M1 (kN.m) 61.3 0.7 0.0
M2 (kN.m) 83.6 0.7 144.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 6.6 < 15.0 400
Beta = 0.99 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 26.1 / 32.9 kN As (Required): %1.36 2170.84 mm2 8T20
vc'(1/2)= 0.64 / 0.64 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.18 / 0.23 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-49

1C20 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2341.4 48.5 -27.7 2325.3 -100.9 57.9
2 2278.6 49.2 -28.6 2262.5 -101.3 60.0
3 2247.8 48.4 -29.0 2231.7 -100.7 60.6
4 1617.5 22.6 -17.1 1601.4 -48.1 35.6
5 1878.6 48.4 -13.6 1862.5 -100.8 27.6
6 2348.1 48.6 -28.0 2332.0 -100.8 58.2
7 1879.7 48.1 -10.4 1863.6 -100.6 25.7
8 1998.3 47.4 -17.4 1982.2 -100.5 38.9
9 2339.3 48.6 -31.0 2323.2 -101.0 59.9
10 1891.1 24.3 -28.0 1875.0 -49.0 56.4
11 2247.8 48.4 -29.0 2231.7 -100.7 60.6
12 1971.8 74.6 -20.1 1958.0 -100.9 45.7
13 1913.9 5.1 -25.9 1900.1 -65.0 50.3
14 1994.0 40.0 23.6 1980.1 -83.0 11.1
15 1891.8 39.7 -69.6 1877.9 -82.8 84.9
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 2348.1 - 2348.1
M1 (kN.m) -100.8 -47.0 -119.2
M2 (kN.m) 58.2 47.0 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.587 Le1/b1 = 5.3 < 15.0 400
Beta = 0.32 Le2/b2 = 4.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 23.3 / 4.2 kN As (Required): %2.20 3512.57 mm2 12T20
vc'(1/2)= 1.63 / 1.18 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.16 / 0.03 N/mm2
Links = R8-225

2C20 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1873.9 141.1 -83.1 1857.8 -131.2 77.8
2 1809.9 141.8 -86.6 1793.8 -131.8 83.8
3 1799.0 140.8 -86.9 1782.9 -130.8 81.5
4 1310.8 67.2 -50.3 1294.7 -62.6 44.2
5 1505.1 140.9 -40.2 1488.9 -131.0 37.2
6 1881.2 141.6 -82.9 1865.0 -131.5 77.6
7 1515.1 140.2 -35.8 1498.9 -130.5 31.0
8 1592.8 139.7 -55.3 1576.7 -130.0 53.1
9 1863.1 141.4 -87.6 1846.9 -131.5 84.1
10 1520.6 68.8 -81.8 1504.4 -64.0 75.2
11 1799.0 140.8 -86.9 1782.9 -130.8 81.5
12 1575.0 130.6 -65.7 1561.2 -125.3 61.3
13 1535.2 101.3 -72.1 1521.4 -90.4 67.6
14 1588.5 116.0 -24.2 1574.7 -107.9 19.9
15 1521.7 115.9 -113.5 1507.9 -107.7 109.1
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 1863.1 - 1863.1
M1 (kN.m) 141.4 37.3 181.5
M2 (kN.m) -87.6 -37.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.466 Le1/b1 = 5.7 < 15.0 400
Beta = 0.46 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 90.6 / 74.2 kN As (Required): %2.32 3712.41 mm2 12T20
vc'(1/2)= 2.01 / 2.04 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.63 / 0.52 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-50

3C20 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1409.2 126.8 -77.0 1393.1 -130.4 77.3
2 1354.1 126.9 -83.7 1338.0 -130.5 85.6
3 1352.9 126.3 -80.7 1336.7 -130.0 81.1
4 995.7 61.2 -42.6 979.6 -62.9 41.2
5 1132.5 126.5 -37.3 1116.4 -130.2 37.1
6 1415.7 127.8 -75.6 1399.6 -131.3 75.9
7 1143.8 125.7 -32.0 1127.6 -129.5 30.7
8 1194.2 125.2 -53.5 1178.1 -128.7 54.5
9 1397.4 127.2 -82.1 1381.2 -130.8 83.6
10 1149.2 61.7 -74.3 1133.1 -63.9 73.6
11 1352.9 126.3 -80.7 1336.7 -130.0 81.1
12 1181.5 115.0 -61.5 1167.7 -121.7 61.5
13 1157.9 93.4 -66.2 1144.1 -92.8 66.6
14 1186.5 104.3 -31.2 1172.6 -107.3 29.2
15 1153.0 104.1 -96.5 1139.1 -107.1 98.9
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 1397.4 - 1397.4
M1 (kN.m) -130.8 -27.9 -180.2
M2 (kN.m) 83.6 27.9 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.349 Le1/b1 = 5.7 < 15.0 400
Beta = 0.59 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 85.6 / 65.1 kN As (Required): %1.73 2764.40 mm2 12T20
vc'(1/2)= 1.70 / 1.72 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.60 / 0.46 N/mm2
Links = R8-225

4C20 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 946.8 125.9 -78.8 930.7 -116.4 77.1
2 906.3 126.3 -87.4 890.2 -117.5 86.9
3 908.9 125.4 -82.6 892.8 -115.9 81.0
4 676.2 60.5 -41.6 660.1 -55.2 39.4
5 761.8 125.7 -38.1 745.7 -116.3 37.1
6 951.6 127.1 -76.6 935.5 -117.3 75.1
7 771.4 124.8 -32.4 755.3 -115.5 30.5
8 801.1 124.8 -56.0 785.0 -116.3 55.5
9 936.8 126.4 -84.1 920.7 -116.8 83.4
10 776.6 60.9 -75.1 760.4 -55.5 72.9
11 908.9 125.4 -82.6 892.8 -115.9 81.0
12 791.9 110.3 -63.7 778.1 -106.4 62.2
13 780.5 96.7 -66.8 766.6 -84.9 65.6
14 792.0 103.6 -43.9 778.1 -95.7 40.1
15 780.4 103.5 -86.6 766.6 -95.6 87.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 906.3 - 906.3
M1 (kN.m) 126.3 18.1 190.8
M2 (kN.m) -87.4 -18.1 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.227 Le1/b1 = 5.7 < 15.0 400
Beta = 0.74 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 80.7 / 58.1 kN As (Required): %1.37 2185.15 mm2 8T20
vc'(1/2)= 1.28 / 1.30 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.56 / 0.41 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-51

5C20 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 484.5 154.4 -83.6 468.4 -204.9 90.7
2 462.9 152.7 -93.8 446.8 -198.7 101.5
3 465.0 153.7 -87.7 448.8 -203.9 94.9
4 352.4 76.6 -42.7 336.3 -105.6 46.4
5 390.3 153.9 -40.7 374.2 -204.0 44.2
6 487.0 156.0 -80.9 470.8 -207.5 87.8
7 395.5 152.9 -33.9 379.4 -202.8 37.1
8 410.2 149.9 -60.1 394.1 -195.4 65.2
9 479.0 154.9 -89.9 462.9 -205.4 97.1
10 402.6 77.8 -79.2 386.5 -106.4 85.7
11 465.0 153.7 -87.7 448.8 -203.9 94.9
12 404.6 129.9 -68.5 390.8 -174.8 74.2
13 400.8 124.0 -70.0 387.0 -162.2 76.0
14 403.1 127.0 -58.7 389.2 -168.6 62.2
15 402.4 126.9 -79.8 388.5 -168.3 87.9
Critical Combination:9 - ((G+Q)P42 *F)
Min Design
N (kN) 479.0 - 479.0
M1 (kN.m) -205.4 -9.6 -288.7
M2 (kN.m) 97.1 9.6 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.120 Le1/b1 = 5.7 < 15.0 400
Beta = 0.86 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 119.3 / 65.1 kN As (Required): %2.87 4591.68 mm2 16T20
vc'(1/2)= 1.08 / 1.17 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.84 / 0.46 N/mm2
Links = R8-225

6C20 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 26.1 6.1 -50.2 10.0 0.0 9.1
2 20.4 17.2 -55.8 4.2 0.0 14.4
3 25.1 6.0 -53.2 9.0 0.0 10.2
4 33.1 -8.3 -27.5 17.0 0.0 2.1
5 24.5 6.6 -22.6 8.4 0.0 4.2
6 26.6 5.9 -49.9 10.4 0.0 8.5
7 28.9 5.8 -19.9 12.8 0.0 0.0
8 23.8 16.9 -36.1 7.6 0.0 9.7
9 21.8 6.8 -52.8 5.7 0.0 13.1
10 29.3 -7.8 -47.6 13.2 0.0 7.3
11 25.1 6.0 -53.2 9.0 0.0 10.2
12 22.5 5.9 -41.7 8.7 0.0 7.6
13 22.5 4.1 -41.7 8.7 0.0 7.7
14 22.4 5.0 -41.1 8.6 0.0 6.6
15 22.6 5.0 -42.2 8.8 0.0 8.8
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 20.4 - 20.4
M1 (kN.m) 17.2 0.4 0.0
M2 (kN.m) -55.8 -0.4 -72.9 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.005 Le1/b1 = 7.2 < 15.0 400
Beta = 0.99 Le2/b2 = 5.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.7 / 23.4 kN As (Required): %0.65 1039.10 mm2 8T16
vc'(1/2)= 0.54 / 0.54 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.04 / 0.16 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-52

1C21 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 2227.7 46.5 24.8 2211.6 -96.8 -51.3
2 1528.7 21.3 15.2 1512.5 -43.1 -30.9
3 2134.3 46.4 26.1 2118.2 -96.7 -54.0
4 2201.3 47.7 26.5 2185.1 -100.3 -55.2
5 1818.3 45.9 11.2 1802.2 -95.7 -23.8
6 2268.4 48.4 25.5 2252.3 -100.4 -53.1
7 2225.0 46.2 27.2 2208.9 -96.7 -52.4
8 1530.5 19.9 16.3 1514.3 -42.9 -31.2
9 1820.0 46.1 8.7 1803.9 -95.7 -22.5
10 2158.7 47.2 24.7 2142.6 -96.9 -53.1
11 2134.3 46.4 26.1 2118.2 -96.7 -54.0
12 1872.3 73.8 23.5 1858.5 -98.3 -44.8
13 1826.4 2.7 17.7 1812.6 -60.8 -40.3
14 1798.7 38.0 67.2 1784.9 -79.4 -79.4
15 1900.1 38.4 -26.0 1886.2 -79.6 -5.7
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 2268.4 - 2268.4
M1 (kN.m) -100.4 -45.4 -118.4
M2 (kN.m) -53.1 -45.4 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.567 Le1/b1 = 5.3 < 15.0 400
Beta = 0.34 Le2/b2 = 4.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 21.2 / 6.8 kN As (Required): %2.06 3297.16 mm2 12T20
vc'(1/2)= 1.56 / 1.38 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.15 / 0.05 N/mm2
Links = R8-225

2C21 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1793.7 136.8 69.4 1777.5 -129.0 -64.7
2 1248.8 62.8 40.4 1232.7 -60.7 -34.8
3 1718.9 136.5 73.3 1702.8 -128.8 -68.5
4 1754.9 140.0 76.4 1738.8 -130.7 -74.1
5 1463.4 134.8 30.9 1447.3 -126.7 -28.6
6 1823.5 141.1 72.5 1807.3 -131.3 -67.7
7 1780.4 136.3 73.0 1764.2 -128.8 -70.3
8 1242.4 61.5 42.2 1226.3 -59.3 -37.8
9 1475.8 135.0 27.3 1459.6 -126.8 -22.9
10 1731.5 137.0 71.3 1715.3 -129.8 -68.2
11 1718.9 136.5 73.3 1702.8 -128.8 -68.5
12 1504.7 128.0 60.8 1490.8 -124.2 -56.8
13 1473.6 96.8 54.4 1459.8 -87.8 -50.5
14 1456.1 112.4 102.2 1442.3 -106.0 -98.3
15 1522.2 112.4 12.9 1508.3 -106.1 -9.1
Critical Combination:6 - ((G+Q)P31 *F)
Min Design
N (kN) 1823.5 - 1823.5
M1 (kN.m) 141.1 36.5 175.1
M2 (kN.m) 72.5 36.5 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.456 Le1/b1 = 5.7 < 15.0 400
Beta = 0.47 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 87.2 / 66.8 kN As (Required): %2.17 3479.45 mm2 12T20
vc'(1/2)= 1.98 / 1.99 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.61 / 0.47 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-53

3C21 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1354.0 126.8 57.1 1337.9 -131.1 -57.9
2 953.0 61.7 28.0 936.8 -63.9 -27.0
3 1297.8 126.5 61.1 1281.7 -130.7 -61.9
4 1316.6 126.7 68.8 1300.4 -130.8 -71.1
5 1104.2 123.9 23.6 1088.1 -127.8 -24.0
6 1375.6 128.1 61.2 1359.4 -132.1 -61.9
7 1339.3 126.4 62.8 1323.1 -130.7 -64.8
8 944.9 60.2 31.7 928.8 -62.4 -31.2
9 1118.1 124.1 18.2 1102.0 -128.0 -17.3
10 1303.0 126.8 61.1 1286.9 -131.3 -62.9
11 1297.8 126.5 61.1 1281.7 -130.7 -61.9
12 1133.6 115.4 49.8 1119.8 -122.5 -50.6
13 1115.0 93.1 45.1 1101.2 -92.9 -45.6
14 1107.9 104.2 80.1 1094.0 -107.7 -83.0
15 1140.8 104.2 14.8 1126.9 -107.7 -13.3
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 1316.6 - 1316.6
M1 (kN.m) -130.8 -26.3 -174.6
M2 (kN.m) -71.1 -26.3 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.329 Le1/b1 = 5.7 < 15.0 400
Beta = 0.62 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 83.9 / 54.4 kN As (Required): %1.52 2426.63 mm2 8T20
vc'(1/2)= 1.58 / 1.58 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.59 / 0.38 N/mm2
Links = R8-225

4C21 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 911.4 127.7 54.9 895.3 -119.1 -53.8
2 648.4 63.0 24.0 632.2 -59.1 -22.2
3 873.6 127.3 59.0 857.5 -118.7 -57.9
4 882.5 126.9 69.4 866.4 -118.0 -69.3
5 743.4 124.2 21.7 727.3 -115.6 -21.1
6 925.9 128.0 59.6 909.8 -117.9 -58.3
7 899.0 127.3 61.6 882.8 -118.7 -61.4
8 641.3 61.5 28.6 625.1 -57.6 -27.3
9 755.2 124.4 15.3 739.1 -115.7 -13.8
10 875.1 128.2 60.2 858.9 -120.7 -59.7
11 873.6 127.3 59.0 857.5 -118.7 -57.9
12 761.7 111.8 47.1 747.8 -108.7 -46.4
13 752.4 98.1 44.1 738.6 -87.1 -43.0
14 751.5 105.0 67.0 737.7 -97.9 -68.5
15 762.6 105.0 24.3 748.8 -97.9 -20.9
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 882.5 - 882.5
M1 (kN.m) 126.9 17.7 178.7
M2 (kN.m) 69.4 17.7 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.221 Le1/b1 = 5.7 < 15.0 400
Beta = 0.75 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 79.9 / 45.2 kN As (Required): %1.20 1924.97 mm2 8T20
vc'(1/2)= 1.26 / 1.27 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.56 / 0.32 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-54

5C21 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 465.0 156.6 56.0 448.9 -205.9 -61.1
2 335.9 80.0 22.5 319.7 -105.6 -24.7
3 445.6 156.1 60.5 429.5 -205.1 -65.9
4 451.0 153.0 73.1 434.8 -200.6 -79.4
5 379.5 151.9 21.2 363.4 -199.9 -23.3
6 474.0 157.2 61.4 457.8 -209.7 -66.9
7 458.3 156.0 64.0 442.2 -205.0 -69.4
8 332.4 77.3 27.9 316.3 -103.1 -30.3
9 386.0 152.2 13.8 369.8 -200.3 -15.7
10 445.4 155.2 62.3 429.3 -199.3 -68.1
11 445.6 156.1 60.5 429.5 -205.1 -65.9
12 388.3 131.4 47.3 374.5 -175.0 -51.7
13 385.1 126.1 45.8 371.3 -163.4 -49.9
14 386.5 128.8 57.1 372.7 -169.3 -63.7
15 386.9 128.7 36.1 373.1 -169.2 -38.0
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 451.0 - 451.0
M1 (kN.m) -200.6 -9.0 -269.3
M2 (kN.m) -79.4 -9.0 0.0 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.113 Le1/b1 = 5.7 < 15.0 400
Beta = 0.87 Le2/b2 = 4.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 117.3 / 50.8 kN As (Required): %2.62 4197.39 mm2 16T20
vc'(1/2)= 1.07 / 1.16 N/mm2 As (Provided): %3.14 5026.55 mm2
v (1/2)= 0.82 / 0.36 N/mm2
Links = R8-225

6C21 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 29.1 5.8 41.5 13.0 0.0 -5.0
2 35.3 -8.5 21.3 19.2 0.0 0.8
3 28.1 5.9 44.5 11.9 0.0 -6.1
4 22.5 17.2 49.3 6.4 0.0 -11.4
5 26.2 5.1 18.2 10.1 0.0 -1.6
6 28.7 6.3 43.5 12.6 0.0 -5.6
7 24.1 6.0 44.5 8.0 0.0 -9.7
8 32.0 -8.3 23.0 15.9 0.0 -2.3
9 31.2 5.0 15.2 15.1 0.0 3.0
10 26.3 16.5 45.6 10.2 0.0 -7.6
11 28.1 5.9 44.5 11.9 0.0 -6.1
12 25.0 5.5 34.5 11.1 0.0 -4.4
13 24.9 4.1 34.6 11.1 0.0 -4.3
14 25.0 4.8 35.1 11.2 0.0 -5.4
15 24.9 4.8 34.0 11.1 0.0 -3.2
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 22.5 - 22.5
M1 (kN.m) 17.2 0.5 0.0
M2 (kN.m) 49.3 0.5 66.4 400
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.006 Le1/b1 = 7.2 < 15.0 400
Beta = 0.99 Le2/b2 = 5.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.7 / 20.2 kN As (Required): %0.58 930.89 mm2 8T16
vc'(1/2)= 0.55 / 0.55 N/mm2 As (Provided): %1.01 1608.50 mm2
v (1/2)= 0.04 / 0.14 N/mm2
Links = R8-175

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-55

1C22 Storey: 1 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1679.2 30.8 -35.0 1663.1 -64.1 73.1
2 1112.0 16.4 -23.3 1095.8 -32.7 49.0
3 1678.3 30.8 -35.0 1662.2 -64.1 73.2
4 1716.7 31.0 -36.5 1700.6 -65.7 75.7
5 1281.0 30.2 -19.2 1264.8 -63.0 39.4
6 1710.0 31.8 -36.6 1693.9 -65.8 76.0
7 1680.0 30.5 -32.6 1663.9 -64.0 71.8
8 1109.7 15.2 -22.1 1093.5 -32.4 48.5
9 1279.4 30.5 -21.8 1263.3 -63.1 40.8
10 1688.2 31.3 -36.1 1672.1 -64.3 73.3
11 1678.3 30.8 -35.0 1662.2 -64.1 73.2
12 1424.0 62.1 -26.7 1410.1 -72.4 59.5
13 1375.4 -10.9 -31.5 1361.6 -34.0 61.9
14 1355.4 24.8 9.8 1341.6 -52.7 39.8
15 1444.0 26.4 -68.0 1430.2 -53.6 81.5
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 1716.7 - 1716.7
M1 (kN.m) -65.7 -34.3 0.0
M2 (kN.m) 75.7 34.3 108.4 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.429 Le1/b1 = 5.3 < 15.0 400
Beta = 0.50 Le2/b2 = 5.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.7 / 10.0 kN As (Required): %1.10 1753.43 mm2 8T20
vc'(1/2)= 1.04 / 1.07 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.05 / 0.07 N/mm2
Links = R8-225

2C22 Storey: 2 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1358.1 90.9 -103.9 1342.0 -86.3 96.7
2 900.8 48.1 -68.6 884.7 -46.6 64.0
3 1356.9 90.9 -103.8 1340.8 -86.3 96.5
4 1387.8 91.6 -108.4 1371.7 -86.1 100.9
5 1037.6 88.9 -57.1 1021.5 -83.9 53.3
6 1381.1 93.0 -107.5 1365.0 -87.0 100.4
7 1360.2 90.5 -101.9 1344.0 -86.0 94.7
8 899.1 46.8 -67.6 883.0 -45.3 63.2
9 1034.8 89.2 -59.1 1018.7 -84.2 55.4
10 1366.5 90.9 -105.8 1350.4 -86.8 98.0
11 1356.9 90.9 -103.8 1340.8 -86.3 96.5
12 1148.4 91.6 -84.5 1134.5 -90.4 78.5
13 1115.8 59.3 -87.9 1102.0 -52.8 82.0
14 1101.1 75.3 -63.6 1087.3 -71.4 55.9
15 1163.1 75.6 -108.8 1149.3 -71.9 104.6
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 1387.8 - 1387.8
M1 (kN.m) 91.6 27.8 0.0
M2 (kN.m) -108.4 -27.8 -162.8 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.347 Le1/b1 = 5.7 < 15.0 400
Beta = 0.59 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 57.8 / 44.2 kN As (Required): %1.43 2289.67 mm2 8T20
vc'(1/2)= 1.52 / 1.40 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.40 / 0.31 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-56

3C22 Storey: 3 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 1030.2 84.6 -95.2 1014.1 -86.9 96.5
2 685.1 47.3 -61.7 669.0 -48.6 62.9
3 1029.1 84.6 -94.7 1013.0 -86.9 96.0
4 1052.7 82.9 -100.2 1036.6 -85.1 101.2
5 788.7 81.7 -53.6 772.6 -83.7 54.3
6 1046.7 84.7 -97.9 1030.6 -86.5 99.5
7 1032.8 84.2 -95.4 1016.7 -86.5 96.0
8 684.1 45.9 -61.6 668.0 -47.2 62.6
9 785.5 81.9 -53.3 769.4 -83.9 54.7
10 1037.2 84.2 -97.6 1021.1 -86.9 98.5
11 1029.1 84.6 -94.7 1013.0 -86.9 96.0
12 868.4 81.7 -77.8 854.6 -87.4 78.6
13 849.5 58.7 -80.1 835.7 -56.9 81.5
14 840.4 70.2 -63.1 826.6 -72.0 60.0
15 877.5 70.3 -94.9 863.7 -72.2 100.1
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 1052.7 - 1052.7
M1 (kN.m) -85.1 -21.1 0.0
M2 (kN.m) 101.2 21.1 160.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.263 Le1/b1 = 5.7 < 15.0 400
Beta = 0.69 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 55.3 / 65.0 kN As (Required): %1.05 1685.05 mm2 8T20
vc'(1/2)= 1.30 / 1.37 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.39 / 0.46 N/mm2
Links = R8-225

4C22 Storey: 4 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 699.7 88.2 -98.1 683.6 -86.8 95.5
2 467.8 50.1 -63.1 451.7 -49.6 61.5
3 698.9 88.1 -97.4 682.8 -86.8 94.7
4 715.0 85.6 -103.5 698.9 -84.1 100.9
5 537.7 84.5 -55.7 521.6 -83.1 54.3
6 710.4 87.6 -100.6 694.2 -85.6 98.2
7 702.1 87.7 -98.9 685.9 -86.4 96.2
8 467.3 48.7 -63.2 451.2 -48.5 61.7
9 534.9 84.8 -54.7 518.8 -83.3 53.5
10 704.9 87.5 -100.8 688.8 -86.4 97.9
11 698.9 88.1 -97.4 682.8 -86.8 94.7
12 588.2 80.1 -80.6 574.4 -83.0 78.1
13 579.2 66.2 -82.0 565.3 -61.0 80.2
14 574.5 73.2 -71.1 560.6 -72.0 64.6
15 592.9 73.1 -91.5 579.1 -72.1 93.8
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 715.0 - 715.0
M1 (kN.m) 85.6 14.3 0.0
M2 (kN.m) -103.5 -14.3 -171.4 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.179 Le1/b1 = 5.7 < 15.0 400
Beta = 0.79 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 56.0 / 61.8 kN As (Required): %1.14 1819.87 mm2 8T20
vc'(1/2)= 1.09 / 1.13 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.39 / 0.43 N/mm2
Links = R8-225

Project: Malaci
OkeBen Services (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-57

5C22 Storey: 5 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 366.1 94.9 -105.8 349.9 -105.2 117.9
2 248.3 55.1 -68.2 232.2 -60.7 76.9
3 365.6 94.8 -104.9 349.5 -105.1 117.0
4 374.5 90.9 -111.0 358.4 -101.0 122.5
5 284.1 90.5 -60.7 268.0 -100.4 67.6
6 371.4 93.8 -108.2 355.3 -104.7 120.4
7 367.7 94.3 -106.2 351.6 -104.5 117.5
8 248.4 52.4 -68.1 232.3 -57.7 76.1
9 282.3 90.8 -59.9 266.1 -100.8 67.6
10 369.1 94.7 -108.8 353.0 -104.6 120.9
11 365.6 94.8 -104.9 349.5 -105.1 117.0
12 307.2 81.5 -87.3 293.4 -93.8 97.0
13 304.3 75.9 -88.0 290.5 -80.7 98.4
14 302.6 78.8 -82.7 288.8 -87.3 88.3
15 308.9 78.6 -92.7 295.1 -87.2 107.1
Critical Combination:10 - ((G+Q)P51 *F)
Min Design
N (kN) 369.1 - 369.1
M1 (kN.m) -104.6 -7.4 0.0
M2 (kN.m) 120.9 7.4 213.9 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 5.7 < 15.0 400
Beta = 0.89 Le2/b2 = 5.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 63.9 / 77.8 kN As (Required): %1.89 3024.98 mm2 12T20
vc'(1/2)= 0.94 / 1.02 N/mm2 As (Provided): %2.36 3769.91 mm2
v (1/2)= 0.45 / 0.55 N/mm2
Links = R8-225

6C22 Storey: 6 (Con.:C20/25 / Steel:Grade 460 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 37.4 63.7 -66.6 21.2 -18.7 12.7
2 33.3 35.3 -39.7 17.2 -14.3 9.2
3 37.2 63.7 -66.0 21.1 -18.7 12.3
4 37.4 63.3 -74.6 21.3 -16.7 14.6
5 34.5 60.7 -37.6 18.4 -17.4 9.3
6 36.8 62.4 -69.4 20.7 -16.8 12.9
7 37.8 63.8 -70.1 21.7 -18.7 13.9
8 33.5 35.6 -41.9 17.4 -14.1 9.9
9 34.1 60.6 -34.2 18.0 -17.4 8.2
10 37.8 64.4 -69.6 21.7 -18.9 13.8
11 37.2 63.7 -66.0 21.1 -18.7 12.3
12 32.1 52.5 -55.4 18.3 -16.4 10.7
13 31.8 53.4 -55.2 18.0 -15.3 10.8
14 31.7 53.0 -55.7 17.9 -15.9 9.9
15 32.2 52.8 -54.9 18.4 -15.8 11.5
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 37.4 - 37.4
M1 (kN.m) 63.3 0.7 0.0
M2 (kN.m) -74.6 -0.7 -137.3 400
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 6.6 < 15.0 400
Beta = 0.99 Le2/b2 = 6.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 27.8 / 29.8 kN As (Required): %1.28 2054.44 mm2 8T20
vc'(1/2)= 0.64 / 0.64 N/mm2 As (Provided): %1.57 2513.27 mm2
v (1/2)= 0.19 / 0.21 N/mm2
Links = R8-225