02877A

723PLUS
Digital
Control

9906-619, 9906-620, 9907-243, 9907-244


Hardware Only
UL Listed E120143
CE Compliant

Hardware Manual

WOODWARD GOVERNOR COMPANY

Manual 02877A
WARNING
Read this entire manual and all other publications pertaining to the
work to be performed before installing, operating, or servicing this
equipment. Practice all plant and safety instructions and
precautions. Failure to follow instructions can cause personal injury
and/or property damage.

The engine, turbine, or other type of prime mover should be


equipped with an overspeed (overtemperature, or overpressure,
where applicable) shutdown device(s), that operates totally
independently of the prime mover control device(s) to protect against
runaway or damage to the engine, turbine, or other type of prime
mover with possible personal injury or loss of life should the
mechanical-hydraulic governor(s) or electric control(s), the
actuator(s), fuel control(s), the driving mechanism(s), the linkage(s),
or the controlled device(s) fail.

CAUTION
To prevent damage to a control system that uses an alternator or
battery-charging device, make sure the charging device is turned off
before disconnecting the battery from the system.

CAUTION
Electronic controls contain static-sensitive parts. Observe the
following precautions to prevent damage to these parts.

• Discharge body static before handling the control (with power to


the control turned off, contact a grounded surface and maintain
contact while handling the control).
• Avoid all plastic, vinyl, and styrofoam (except antistatic versions)
around printed circuit boards.
• Do not touch the components or conductors on a printed circuit
board with your hands or with conductive devices.

The letter designation following the manual number is changed to the next letter in alphabetical order when
an important change is made in the manual.

CHANGED AREAS ARE INDICATED BY A BLACK LINE IN THE MARGIN.

Woodward Governor Company reserves the right to update any portion of this publication at any time.
Information provided by Woodward Governor Company is believed to be correct and reliable. However, no
responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken.
© 1998 by Woodward Governor Company
All Rights Reserved
Manual 02877 723PLUS Hardware Manual

TABLE OF CONTENTS

CHAPTER 1. GENERAL INFORMATION................................................................................................. 1


INTRODUCTION.......................................................................................................................................... 1
DECLARATION OF INCORPORATION ...................................................................................................... 1
APPLICATION ............................................................................................................................................. 1
CONTROL OPTIONS .................................................................................................................................. 1
723PLUS DIGITAL CONTROL ACCESSORIES ......................................................................................... 2

CHAPTER 2. ELECTROSTATIC DISCHARGE AWARENESS............................................................... 5

CHAPTER 3. INSTALLATION ................................................................................................................... 7


SCOPE......................................................................................................................................................... 7
UNPACKING................................................................................................................................................ 7
POWER REQUIREMENTS.......................................................................................................................... 7
LOCATION CONSIDERATIONS ................................................................................................................. 7
CLASS I, DIVISION 2, GROUPS A, B, C, D HAZARDOUS LOCATIONS................................................... 8
INTERNAL JUMPERS ................................................................................................................................. 8
ELECTRICAL CONNECTIONS ................................................................................................................. 10
Shielded Wiring ................................................................................................................................... 10
Power Supply (Terminals 1/2) ............................................................................................................. 11
Analog Outputs (#1 & #2) (Terminals 15/16 & 17/18) ......................................................................... 11
Actuator Outputs (#1 & #2) (Terminals 19/20 & 21/22) ....................................................................... 12
Speed Signal Inputs (Terminals 11/12 & 13/14) .................................................................................. 12
Load Sharing Lines Input (Terminals 9/10) ......................................................................................... 12
Discrete Inputs (Terminals 29–36) ...................................................................................................... 12
Analog Inputs (#1, #2, #3, & #4) (Terminals 42/43, 45/46, 48/49, & 51/52) ........................................ 13
INSTALLATION CHECKOUT PROCEDURE ............................................................................................ 13
SERIAL PORT COMMUNICATIONS......................................................................................................... 16
Termination.......................................................................................................................................... 16
Grounding and Shielding ..................................................................................................................... 18
Special Setup Procedures ................................................................................................................... 19

CHAPTER 4. ENTERING CONTROL SET POINTS ............................................................................. 21


INTRODUCTION........................................................................................................................................ 21
HAND HELD PROGRAMMER AND MENUS ............................................................................................ 21
Configure Menus ................................................................................................................................. 21
Service Menus ..................................................................................................................................... 22
Adjusting Set Points ............................................................................................................................ 22
Hand Held Programmer Keys.............................................................................................................. 23

CHAPTER 5. USING SERVLINK WITH WATCH WINDOW ................................................................ 25


USING WATCH WINDOW......................................................................................................................... 25
DOWNLOADING TO THE 723PLUS ......................................................................................................... 26
TRANSFERRING TUNABLE VALUES BETWEEN 723PLUS CONTROLS .............................................. 27

Woodward Governor Company i


723PLUS Hardware Manual Manual 02877

CHAPTER 6. SERVICE OPTIONS.......................................................................................................... 29


PRODUCT SERVICE OPTIONS ............................................................................................................... 29
Replacement/Exchange ...................................................................................................................... 29
Flat Rate Repair .................................................................................................................................. 30
Flat Rate Remanufacture .................................................................................................................... 30
RETURNING EQUIPMENT FOR REPAIR ................................................................................................ 30
Packing a Control ................................................................................................................................ 30
Additional Instructions ......................................................................................................................... 31
REPLACEMENT PARTS INFORMATION ................................................................................................. 31
HOW TO CONTACT WOODWARD .......................................................................................................... 31
OTHER SERVICE FACILITIES ................................................................................................................. 31
ADDITIONAL AFTERMARKET PRODUCT SUPPORT SERVICES ......................................................... 32
SYSTEM TROUBLE-SHOOTING GUIDE.................................................................................................. 33
Actuators ............................................................................................................................................. 33
Linkage ................................................................................................................................................ 33
Valves.................................................................................................................................................. 33
Oil/Hydraulic System ........................................................................................................................... 34
Fuel Injection Pumps ........................................................................................................................... 34
Fuel/Steam Conditions ........................................................................................................................ 34
Control, Alarm, And Fault Indications .................................................................................................. 34
Input Signals........................................................................................................................................ 34
Output Signals ..................................................................................................................................... 35
Transducers......................................................................................................................................... 35
Magnetic Pickups And Other Speed Sensing Devices ........................................................................ 35
Input Voltage/Power Supplies ................................................................................................... .......... 35
Electrical Connections ......................................................................................................................... 36
Voltage Regulator ................................................................................................................................ 36
External Devices.................................................................................................................................. 36
TECHNICAL ASSISTANCE ....................................................................................................................... 37
General................................................................................................................................................ 37
Prime Mover Information ..................................................................................................................... 37
Governor Information........................................................................................................................... 37

723PLUS CONTROL SPECIFICATIONS................................................................................................ 39

LIST OF FIGURES

1-1. 723 Digital Speed Control ............................................................................................................... 3


1-2. Hand Held Programmer .................................................................................................................. 4
3-1. 723 Control Internal Jumpers.......................................................................................................... 9
3-2. 723 I/O .......................................................................................................................................... 15
3-3. RS-422 Terminator Locations ....................................................................................................... 16
3-4. RS-485 Terminator Locations ....................................................................................................... 16
3-5. 723 RS-232 Connections .............................................................................................................. 17
3-6. 723 RS-422 Connections with Optional Termination at Receiver ................................................. 17
3-7. 723 RS-422 Connections with Optional Termination at Transmitter ............................................. 17
3-8. 723 RS-485 Connections with Optional Termination .................................................................... 17
3-9. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable
with a Separate Signal Ground Wire............................................................................................. 18
3-10. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable
without a Separate Signal Ground Wire........................................................................................ 19
4-1. Hand Held Programmer Functions................................................................................................ 24

ii Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 1
GENERAL INFORMATION

INTRODUCTION This manual describes the Woodward 723PLUS Digital Control hardware,
9906-619 (low voltage) 9906-620 (high voltage), 9907-243 (Wärtsilä, low
voltage), and 9907-244 (Wärtsilä, high voltage). These part numbers are EU
Directive compliant components.

DECLARATION In accordance with the EMC Directive 89/336/EEC and its amendments, this
OF controlling device, manufactured by the Woodward Governor Company, is
INCORPORATION applied solely as a component to be incorporated into a prime mover system.
Woodward Governor declares that this controlling device complies with the
requirements of EN50081–2 and EN50082–2 when put into service per the
installation and operating instructions outlined the product manual.

NOTICE: This controlling device is intended to be put into service only upon
incorporation into a prime mover system that itself has met the requirements of
the above Directive and bears the CE mark.

APPLICATION The 723PLUS Digital Control can be programmed to suit applications requiring
two magnetic pickups (MPUs) or proximity switches (e.g. for torsional filtering)
as the hardware includes two speed inputs. It also includes four analog inputs,
three analog outputs, eight discrete inputs and three discrete outputs, all of which
can be programmed to satisfy the application. The control can be used in load
sharing systems as it contains circuitry and connections to support this.

The two LON channels can be used to support Woodward LonTalk® or LinkNet®
input/output nodes control functions.

The 723PLUS control (Figure 1-1) consists of a single printed circuit board in a
sheet-metal chassis. Connections are via three terminal strips and three 9-pin
subminiature D connectors.

CONTROL The 723PLUS control requires the following power supply input voltages, with 40
OPTIONS watts as the nominal power consumption at rated voltage:
• 18–40 Vdc (24 or 32 Vdc nominal)
• 90–150 Vdc (125 Vdc nominal)

Discrete input voltages provide on/off command signals to the electronic control.
Each discrete input requires 10 mA at its 24 Vdc nominal voltage rating (for 24
volt switching logic).

Woodward Governor Company 1


723PLUS Hardware Manual Manual 02877

Other control options are:


• proximity switch input for speed signal frequencies below 100 Hz (see
NOTE)
• 0–1 mA for meter drivers
• tandem actuator outputs
• dual actuator outputs (0–200 mA)

The control may be used with either proximity switches (see NOTE) or magnetic
pickups. The minimum frequency for steady state speed control is 30 Hz. For
more information see Control Specifications (inside back cover).

NOTE
EU Directive compliant applications are not currently able to use
proximity switches due to the sensitivity of the switches.

723PLUS • Hand Held Programmer (Figure 1-2), part number 9907-205, can be used
DIGITAL for adjusting the 723PLUS control. It plugs into serial port J1 of the
CONTROL control. This part is EU Directive compliant.
ACCESSORIES
• SPM-A Synchronizer, for synchronizing the generator phase to that of the
power bus. The synchronizer generates a close generator breaker signal to
parallel the generator with the power bus.
• Power Output Sensor, for load sharing or droop operation in mechanical
load applications.
• Real Power Sensor, for load sharing or droop-parallel generator
applications.
• Digital Synchronizer and Load Control (DSLC) for generator load
management.
• Rack Position Sensor, for mechanical load sharing.
• Load Pulse Unit, for improved system load transient response.

• LinkNet® nodes for additional input/output control functions.

2 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Figure 1-1. 723PLUS Digital Speed Control

Woodward Governor Company 3


723PLUS Hardware Manual Manual 02877

Figure 1-2. Hand Held Programmer

4 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 2
ELECTROSTATIC DISCHARGE AWARENESS

All electronic equipment is static-sensitive, some components more than others.


To protect these components from static damage, you must take special
precautions to minimize or eliminate electrostatic discharges.

Follow these precautions when working with or near the control.


1. Before doing maintenance on the electronic control, discharge the static
electricity on your body to ground by touching and holding a grounded metal
object (pipes, cabinets, equipment, etc.).
2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much as
possible because these do not store static electric charges as much as
synthetics.
3. Keep plastic, vinyl, and styrofoam materials (such as plastic or styrofoam
cups, cup holders, cigarette packages, cellophane wrappers, vinyl books or
folders, plastic bottles, and plastic ash trays) away from the control, the
modules, and the work area as much as possible.
4. Do not remove the printed circuit board (PCB) from the control cabinet unless
absolutely necessary. If you must remove the PCB from the control cabinet,
follow these precautions:
• Do not touch any part of the PCB except the edges.
• Do not touch the electrical conductors, the connectors, or the components
with conductive devices or with your hands.
• When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.

Woodward Governor Company 5


723PLUS Hardware Manual Manual 02877

6 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 3
INSTALLATION

SCOPE This chapter contains general installation instructions for the 723PLUS control.
Power requirements, environmental precautions, and location considerations are
included to help you determine the best location for the control. Additional
information includes unpacking instructions, electrical connections, and
installation checkout procedures.

UNPACKING Before handling the control, read Chapter 2, Electrostatic Discharge Awareness.
Be careful when unpacking the electronic control. Check the control for signs of
damage such as bent panels, scratches, and loose or broken parts. If any damage is
found, immediately notify the shipper.

POWER The high-voltage versions of the 723PLUS Digital Speed Control require a
REQUIREMENTS voltage source of 90 to 150 Vdc. The low-voltage versions require a voltage
source of 18 to 40 Vdc.

CAUTION
To prevent damage to the control, do not exceed the input voltage
range.

NOTE
If a battery is used for operating power, an alternator or other battery-
charging device is necessary to maintain a stable supply voltage.

CAUTION
To prevent damage to the control, make sure that the alternator or
other battery-charging device is turned off or disconnected before
disconnecting the battery from the control.

LOCA TION Consider these requirements when selecting the mounting location:
CONSIDERATIONS
• adequate ventilation for cooling
• space for servicing and repair
• protection from direct exposure to water or to a condensation-prone
environment
• protection from high-voltage or high-current devices, or devices which
produce electromagnetic interference in excess of levels defined in
EN50082–2

Woodward Governor Company 7


723PLUS Hardware Manual Manual 02877

• avoidance of vibration
• selection of a location that will provide an operating temperature range of
–40 to +70 °C (–40 to +158 °F)

The control must NOT be mounted on the prime mover.

CLASS I, DIVISION 2, GROUPS A, B, C, D HAZARDOUS LOCATIONS

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D,


or non-hazardous locations only.

WARNING
Explosion Hazard—Substitution of components may impair
suitability for Class I, Division 2.
Explosion Hazard—Do not disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.

AVERTISSEMENT
Risque d’explosion—La substitution de composants peut rendre ce
matériel inacceptable pour les emplacements de Classe 1, Division 2.
Risque d’explosion—Avant de déconnecter l’équipement, coupler le
courant ou s’assurer que l’emplacement est désigné non dangereux.

NOTE
Installation wiring must be in accordance with Class I, Division 2
wiring methods in Article 501–4(b) of the NEC, and in accordance
with the authority having jurisdiction.

INTERNAL The 723PLUS control has ten, two-position internal jumpers (JPR1 through
JUMPERS JPR20) located on the top of the printed circuit board. If it is necessary to change
any jumper to match your control requirements, and this suits the nature of the
software, be sure to read Chapter 2, Electrostatic Discharge Awareness.

Remove power and all inputs. Wait 45 seconds, then remove cover. With your
fingers or a small pair of tweezers, carefully remove the appropriate jumper and
replace it securely over the proper two connectors (see Figure 3-1).

8 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Figure 3-1. 723PLUS Control Internal Jumpers

Woodward Governor Company 9


723PLUS Hardware Manual Manual 02877

The jumper connections are listed:


JPR10 analog output #1 0–1 mA
* JPR9 analog output #1 0–20 mA

JPR12 analog output #2 0–1 mA


* JPR11 analog output #2 0–20 mA

* JPR13 & JPR2 actuator output #1 0–200 mA, single


JPR13 & JPR1 actuator output #1 0–20 mA, single
JPR14 & JPR2 actuator output #1 0–160 mA, tandem

JPR15 & JPR3 actuator output #2 0–200 mA, single


* JPR15 & JPR4 actuator output #2 0–20 mA, single
JPR16 & JPR3 actuator output #2 0–160 mA, tandem

* JPR6 & JPR18 speed sensor #1 magnetic pickup


JPR5 & JPR17 speed sensor #1 proximity switch
(see NOTE on page 2)

* JPR8 & JPR19 speed sensor #2 magnetic pickup


JPR7 & JPR20 speed sensor #2 proximity switch
(see NOTE on page 2)
*—default jumper settings

ELECTRICAL External wiring connections and shielding requirements for each installation are
CONNECTIONS shown in Chapter 5 of the software manual appropriate to the application.

Shielded Wiring All shielded cable must be twisted conductor pairs. Do not attempt to tin the
braided shield. All signal lines should be shielded to prevent picking up stray
signals from adjacent equipment. Connect the shields to the nearest chassis
ground. Wire exposed beyond the shield should be as short as possible, not
exceeding 50 mm (2 inches). The other end of the shields must be left open and
insulated from any other conductor. DO NOT run shielded signal wires along with
other wires carrying large currents. See Woodward application note 50532,
Interference Control in Electronic Governing Systems for more information.

Where shielded cable is required, cut the cable to the desired length and prepare
the cable as instructed below.
1. Strip outer insulation from BOTH ENDS, exposing the braided or spiral
wrapped shield. DO NOT CUT THE SHIELD.
2. Using a sharp, pointed tool, carefully spread the strands of the shield.
3. Pull inner conductor(s) out of the shield. If the shield is the braided type, twist
it to prevent fraying.
4. Remove 6 mm (1/4 inch) of insulation from the inner conductors.

10 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Installations with severe electromagnetic interference (EMI) may require


additional shielding precautions. Contact Woodward Governor Company for
more information.

Power Supply Power supply output must be low impedance (for example, directly from
(Terminals 1/2) batteries). DO NOT power the control from high-voltage sources with resistors
and zener diodes in series with the control power input. The 723PLUS control
contains a switching power supply which requires a current surge to start
properly.

CAUTION
To prevent damage to the control, do not power a low-voltage control
from high-voltage sources, and do not power any control from high-
voltage sources with resistors and zener diodes in series with the
power input.

Run the power leads directly from the power source to the control. DO NOT
POWER OTHER DEVICES WITH LEADS COMMON TO THE CONTROL.
Avoid long wire lengths. Connect the positive (line) to terminal 1 and negative
(common) to terminal 2. If the power source is a battery, be sure the system
includes an alternator or other battery-charging device.

If possible, do NOT turn off control power as part of a normal shutdown


procedure. Leave the control powered except for service of the system and
extended periods of disuse.

CAUTION
Do NOT apply power to the control at this time. Applying power may
damage the control.
To prevent damage to the engine, apply power to the 723PLUS
control at least 60 seconds prior to starting the engine. The control
must have time to do its power up diagnostics and become
operational. Do not start the engine unless the green POWER AND
CPU OK indicator on the 723PLUS control cover comes on, because
test failure turns off the output of the control.

Analog Outputs Use shielded twisted-pair wires to connect to terminals 15(+) & 16(–) and 17(+)
(#1 & #2) & 18(–). For an electrically isolated input device such as a 4 to 20 mA input
(Terminals 15/16 analog meter, the shield should be grounded at the control end of the cable. For
& 17/18) input to other devices, use the recommendation of the device manufacturer.

Woodward Governor Company 11


723PLUS Hardware Manual Manual 02877

CAUTION
To prevent possible damage to the control or poor control
performance resulting from ground loop problems, we recommend
using current-loop isolators if the 723PLUS control's analog inputs
and outputs must both be used with non-isolated devices. A number
of manufacturers offer 20 mA loop isolators. Consult Woodward
Governor Company for further information.

Actuator Outputs The actuator wires connect to terminals 19(+) & 20(–) and 21(+) & 22(–). Use
(#1 & #2) shielded wires with the shield connected to chassis at the control.
(Terminals 19/20
& 21/22)

Speed Signal Connect a magnetic pick-up (MPU) or proximity switch (see NOTE on page 2) to
Inputs (Terminals terminals 11 and 12. You may need to connect a second MPU/proximity switch to
11/12 & 13/14) terminals 13 and 14 (see relevant application manual). Use shielded wire for all
speed sensor connections. Connect the shield to the chassis. Make sure the shield
has continuity the entire distance to the speed sensor, and make sure the shield is
insulated from all other conducting surfaces.

WARNING
The number of gear teeth is used by the control to convert pulses
from the speed sensing device to engine rpm. To prevent possible
serious injury from an overspeeding engine, make sure the control is
properly programmed to convert the gear-tooth count into engine
rpm. Improper conversion could cause engine overspeed.

Load Sharing Connect the output of a Woodward Load Sensor, or another 723PLUS control's
Lines Input load sharing lines, to terminals 9(+) and 10(–). Use a shielded twisted-pair cable.
(Terminals 9/10) Wire the remainder of the load sensor in accordance with the wiring diagram for
the sensor used.

Discrete Inputs For Lloyd’s Register of Shipping applications, use only isolated contacts (dry
(Terminals 29–36) or signal rated) for the discrete inputs. Power these contacts from the
control-supplied Aux Voltage.

Discrete inputs are the switch input commands to the 723PLUS control. In low
voltage systems, or other systems where nominal 24 Vdc is available, the discrete
inputs should be powered by this external voltage.

If you are using the control-supplied aux voltage, jumper terminal 37 to terminal
38. This connects the control's common to the discrete input common. Terminal
39 then supplies power (approximately +24 Vdc) to the discrete inputs. Since the
aux voltage is not isolated from other control circuits, use only isolated contacts
(dry or signal voltage rated) for the discrete circuits. DO NOT POWER ANY
OTHER DEVICES WITH THE AUX VOLTAGE SOURCE.

12 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

If you are supplying the discrete input voltage (24 Vdc), connect the voltage
source negative (–) to terminal 37 (DO NOT INSTALL THE JUMPER FROM
TERMINAL 37 TO 38). Then run the voltage source positive (+) to the
appropriate switch or relay contact and then to the corresponding discrete input.

Analog Inputs Use shielded twisted-pair cable to connect to terminals 42(+) & 43(–), 45(+) &
(#1, #2, #3, & #4) 46(-), 48(+) & 49(–), and 51(+) & 52(–). Ensure that a jumper is installed between
(Terminals 42/43, relevant terminals (41 & 42–#1, 44 & 45–#2, 47 & 48–#3, 49 & 50–#4) for the
45/46, 48/49, & 51/ mA input. These inputs are not isolated from the other control inputs and outputs
52) (except the power supply input and the discrete inputs). If any other analog input
or output is used in a common ground system, an isolator must be installed. A
number of manufacturers offer 20 mA loop isolators. Consult Woodward
Governor Company for further information.

INSTALLATION With the installation complete, do the following checkout procedure before
CHECKOUT beginning set point entry or initial start-up adjustments.
PROCEDURE
1. Visual inspection
A. Check the linkage between the actuator and fuel metering device for
looseness or binding. Refer to the appropriate actuator manual, and
Manual 25070, Electric Governor Installation Guide for additional
information on linkage.

WARNING
To prevent possible serious injury from an overspeeding engine, the
actuator lever or stroke should be near but not at the minimum
position when the fuel valve or fuel rack is at the minimum fuel
delivery position.

B. Check for correct wiring in accordance with the plant wiring diagram,
(see relevant Application Manual).
C. Check for broken terminals and loose terminal screws.
D. Check the speed sensor(s) for visible damage. If the sensor is a
magnetic pickup, check the clearance between the gear and the sensor,
and adjust if necessary. Clearance should be between 0.25 and 1.25 mm
(0.010 and 0.050 inch) at the closest point. Make sure the gear runout
does not exceed the pickup gap.
2. Check for grounds

Check for grounds by measuring the resistance from all control terminals to
chassis. All terminals except terminals 2 and 24 should measure infinite resistance
(the resistance of terminals 2 and 24 depends on whether a floating or grounded
power source is used). If a resistance less than infinite is obtained, remove the
connections from each terminal one at a time until the resistance is infinite. Check
the line that was removed last to locate the fault.

Woodward Governor Company 13


723PLUS Hardware Manual Manual 02877

723PLUS I/O

14 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Figure 3-2. 723PLUS I/O

Woodward Governor Company 15


723PLUS Hardware Manual Manual 02877

SERIAL PORT The 723PLUS has two serial ports for communications. They may be software
COM MUNICATIONS configured as RS-232, RS-422, or RS-485. These ports may be software
configured to function as MODBUS communications ports at the time the
application software is written. If the J2 and J3 port are configured as a MODBUS
port, they will support either MODBUS ASCII or MODBUS RTU protocols.

Termination For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receivers, termination should be at the receiver farthest
from the transmitter. Figure 3-3 is an example.

Figure 3-3. RS-422 Terminator Locations

Communicating with the OpTrend® operator interface is a special case of Figure


3-3. Because the OpTrend master cannot put its transmitter into a high-impedance
state, and our bit rate is less than 90k bits/sec, termination is not needed at the
slave. Termination is needed at the OpTrend receiver, but because there is no way
to locate it there, it has to be put at the alternate location.

For RS-485, termination should be at each end of the cable. If termination can’t be
located at the end of a cable, put it as close as possible to the ends. Figure 3-4 is an
example.

Figure 3-4. RS-485 Terminator Locations

16 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

If you do not know if a master can put its transmitter into a high-impedance state,
terminate the line as shown in Figure 3-3. It does not hurt to terminate the line
even when it is not needed as in the case of the OpTrend operator interface.

Termination is accomplished using a three-resistor voltage divider between a


positive voltage and ground. The impedance of the resistor network should be
equal to the characteristic impedance of the cable. This is usually about 100 to 120
ohms. The purpose is to maintain a voltage level between the two differential lines
so that the receiver will be in a stable condition. The differential voltage can range
between 0.2 and 6 volts; but the maximum voltage between either receiver input
and circuit ground must be less than 10 volts. There is one termination resistor
network for each port located on the 723PLUS board. Connection to this resistor
network is made through the 9-pin connectors on pins 6 and 9. See Figures 3-5
through 3-8 for termination and cable connection examples.

Figure 3-5. 723PLUS RS-232 Connections Figure 3-6. 723PLUS RS-422 Connections with
Optional Termination at Receiver

Figure 3-7. 723PLUS RS-422 Connections with Figure 3-8. 723PLUS RS-485 Connections
Optional Termination at Transmitter with Optional Termination

Woodward Governor Company 17


723PLUS Hardware Manual Manual 02877

Grounding and The RS-422 and RS-485 specifications state that a ground wire is needed if there
Shielding is no other ground path between units. The preferred method to do this is to
include a separate wire in the cable that connects the circuit grounds together.
Connect the shield to earth ground at one point only. The alternate way is to
connect all circuit grounds to the shield, and then connect the shield to earth
ground at one point only. If the latter method is used, and there are non-isolated
nodes on the party line, connect the shield to ground at a non-isolated node, not at
an isolated node. Figures 3-9 and 3-10 illustrate these cabling approaches.

NOTE
Non-isolated nodes may not have a signal ground available. If signal
ground is not available, use the alternate wiring scheme in Figure
3-10 with the signal ground connection removed on those nodes
only.

Figure 3-9. Preferred Multipoint Wiring Using Shielded Twisted-pair Cable with
a Separate Signal Ground Wire

NOTE
The SG (signal ground) connection is not required if signal ground is
unavailable.

18 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Figure 3-10. Alternate Multipoint Wiring Using Shielded Twisted-pair Cable


without a Separate Signal Ground Wire

Special Setup Node Addresses. The LinkNet modules each have rotary switches that set the
Procedures module address. Before installing or replacing the modules, insure that the
addresses are set to the value listed on the hardware description for that module.

Woodward Governor Company 19


723PLUS Hardware Manual Manual 02877

20 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 4
ENTERING CONTROL SET POINTS

INTRODUCTION Due to the variety of installations, plus system and component tolerances, the
723PLUS control must be tuned to each system for optimum performance.

This chapter contains information on how to enter control set points through the
control's menu system using the Hand Held Programmer. If you have access to the
Watch Window software tool and ServLink software, you can set up and tune the
723PLUS control from a PC (personal computer) using the instructions in Chapter
5 of this manual.

WARNING
An improperly calibrated control could cause an engine overspeed or
other damage to the engine. To prevent possible serious injury from
an overspeeding engine, read this entire procedure before starting
the engine.

HAND HELD The Hand Held Programmer is a hand-held computer terminal that gets its power
PROGRAMMER from the 723PLUS control. The terminal connects to the RS-422 communication
AND MENUS serial port on the control (terminal J1). To connect the terminal, slightly loosen the
right-hand screw in the cover over J1 and rotate the cover clockwise to expose the
9-pin connector. Then firmly seat the connector on the terminal into J1.

The programmer does a power-up self-test whenever it is plugged into the control.
When the self-test is complete, the screen will display two lines of information.
This is information relating to the application. Pressing the ID key will change the
display to show the part number of the software and version letter.

The programmer screen is a four-line, backlighted LCD display. The display


permits you to look at two separate functions or menu items at the same time. Use
the UP/DOWN ARROW key to toggle between the two displayed items. The
BKSP and SPACE keys will scroll through the display to show the remainder of a
prompt if it is longer than the display screen's 18 characters.

The 723PLUS has two sets of menus—the Service menus and the Configure
menus. The Service menus allow easy access and tuning while the engine is
running. The Configure menus may be entered only if the I/O is shutdown (hence
the engine stopped).

Configure Menus To access the Configure menus, the engine must be shut down. Press the • key.
The display will show, “To select configure, press enter”. Press the ENTER key
and the display will show, “To shutdown I/O, press enter”. Press the ENTER key
and this will allow you into the Configure menus.

Woodward Governor Company 21


723PLUS Hardware Manual Manual 02877

NOTE
If the engine is running during this process, it will be shut down due
to shutting down the I/O of the control.

To move between the menus use the LEFT ARROW and RIGHT ARROW keys.
To move through the set points within a menu, use the UP ARROW and DOWN
ARROW keys. Once within a menu, to return to the menu header, press the ESC
key.

To leave the Configure menus press the ESC key. The set points will be
automatically saved when leaving Configure.

Service Menus To access the Service menus press the DOWN ARROW key. To move between
menus, and to move through set points within menus follow the instructions as for
the Configure menus. Also to return to return to the menu header, or to leave
Service, follow the Configure instructions.

Adjusting Set To adjust a set point, use the TURTLE UP or the RABBIT UP keys to increase the
Points value, and the TURTLE or RABBIT DOWN keys to decrease the value. The
RABBIT UP and RABBIT DOWN keys will make the rate of change faster than
the TURTLE UP and TURTLE DOWN keys. This is useful during initial setup
where a value may need to be changed significantly. Where necessary, to select
TRUE, use either the TURTLE UP or the RABBIT UP keys, and to select FALSE,
use the TURTLE DOWN or RABBIT DOWN keys.

Use the + or – keys to change integer values in the application software.

To obtain an exact value, press the = key. Key in the required figure and press
ENTER.

NOTE
This may be done only if the figure is within 10% of the existing
value.

To save set points at any time, use the SAVE key. This will transfer all new set
point values into the EEPROM memory. The EEPROM retains all set points when
power is removed from the control.

CAUTION
To prevent possible damage to the engine resulting from improper
control settings, make sure you save the set points before removing
power from the control. Failure to save the set points before
removing power from the control causes them to revert to the
previously saved settings.

22 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Hand Held The programmer keys do the following functions (see Figure 4-1):
Programmer (left arrow) Moves backward through Configure or Service, one menu at
Keys a time.
(right arrow) Advances through Configure or Service, one menu at a time.
(up/down arrow) Toggles between the two displayed items.
(up arrow) Moves backward through each menu, one step at a time.
(down arrow) Advances through each menu, one step at a time. Selects
Service from Main Screen.
(turtle up) Increases the displayed set point value slowly.
(turtle down) Decreases the displayed set point value slowly.
(rabbit up) Increases the displayed set point value quickly (about 10
times faster than the turtle keys).
(rabbit down) Decreases the displayed set point value quickly (about 10
times faster than the turtle keys).
– (minus) Increases set point values by one step at a time.
+ (plus) Decreases set point values by one step at a time.
(solid square) Not used.
ID Displays the 723PLUS control part number and software
revision level.
ESC To return to menu header or to main screen.
SAVE Saves entered values (set points).
BKSP Scrolls left through line of display.
SPACE Scrolls right through line of display.
ENTER Used when entering exact values and accessing Configure.
= (equals) For entering exact values (within 10%).
• (decimal) To select Configure.

Woodward Governor Company 23


723PLUS Hardware Manual Manual 02877

Figure 4-1. Hand Held Programmer Functions

24 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 5
USING SERVLINK WITH WATCH WINDOW

USING WATCH Here are brief instructions for using the Watch Window in conjunction with
WINDOW ServLink to view the variables for your 723PLUS control on a PC (personal
computer). These instructions are meant to be introductory only. Full on-line help
is available in each application. It is assumed that you already have Servlink and
Watch Window installed. The default installation location can be found by
clicking the START icon (Microsoft Windows 95 or later) on the main menu bar
and then clicking the PROGRAMS menu item. Look for an icon called
WOODWARD WATCH WINDOW.
1. Make sure that all other programs that may access your computer
communications port are shut down.
2. Get the right cable to talk from your PC to the control (5416-614 will work for
J2 and J3, 5416-870 for J1).
3. Start the Servlink server and open a new file. Select the proper COM port for
your PC, verify that POINT TO POINT communications mode is selected,
and verify that the baud rate matches the baud rate of the 723PLUS. The
default baud rate is 19 200. See the on-line help file if you have been changing
the port settings of your control.
4. Select OK. If everything is working right, you should see an animated picture
of a string of “1”s and “0”s flying from the control to the PC on your screen.
You now have a network definition file whose default name is NET1. You
should save this file as “your filename.NET” (use FILE/SAVE AS). Link this
name to your control part number, as it will work only with that application.
For instance, if the upper level control number is 9907-031, you could save
the file as 9907031.NET. DO NOT DISCONNECT THE SERVER.
5. In the Servlink window you will now have another dialog window titled “your
filename.net”. In this window you will see a ballhead icon and a control
identifier name. Unless you have given the control a serial number (or name)
with the SLSN.EXE program, this name will display as “<unidentified>”.
6. Start the Watch Window application. When Watch executes, you will have a
screen displaying three windows entitled Watch Window, Explorer, and
Inspector.
7. The Explorer window will have two groups displayed, SERVICE and
CONFIGURE. Double clicking on either of these will expand them to show
groups of values. Explorer is used only to locate a tunable or monitor value. In
order to change a value or monitor a value, you must drag and drop a value
from the Explorer window into the Inspector window.

Woodward Governor Company 25


723PLUS Hardware Manual Manual 02877

8. Once a value is displayed in the Inspector, you can see several blocks of
information. The most important blocks for a tunable value are the FIELD and
VALUE blocks. The FIELD block is used to identify a particular value, and
the VALUE block displays the current value of a variable. There are two
types of values available in Watch. One is a monitor value, which is marked
in the INSPECTOR window with a pair of glasses. This means it may only be
looked at. The other value is a read/write value, which is marked with a
pencil. The read/write type may be modified using the up and down arrows in
the value block.

DOWNLOADING NOTE that this is the only way to download to a 723PLUS, and it will not work
TO THE 723PLUS on a regular 723.
1. Make sure that all other programs that may access your computer’s
communication port are shut down.
2. Get the right cable to talk from your PC to the control J1 port (5416-870).
3. Start the Servlink server and open a new file. From the dialog window, select
the proper COM port for your PC, select POINT TO POINT communications
mode, and set the baud rate to 19200.
4. Select OK. If everything is working right, you should see an animated picture
of a string of “1”s and “0”s flying from the control to the PC on your screen.
You now have a network definition file whose default name is NET1. You
should save this file. Link this name to your control part number as it will only
work with that application. For instance if the upper level control number is
9907-031, you could save the file as 9907031.NET. DO NOT DISCONNECT
THE SERVER.
5. In the Servlink window you will now have another dialog window titled “your
filename.net”. In this window you will see a ballhead icon and a control
identifier name. Unless you have given the control a serial number (or name)
with the SLSN.EXE program, this name will display as “<unidentified>”.
6. Start the Watch Window program. Under the title bar in the Explorer window
you will find a tab with your network file and the control ID displayed. Right
click this tab to display the pop-up menu, and select LOAD APPLICATION.
This will close the Inspector window and open a new window where you will
enter the name of the file you want to download. Once the filename is correct,
click on the OPEN button. A Warning screen will ask you to make sure the
engine is shut down before downloading. Downloading will proceed
automatically once your accept the message to shut down the engine.

WARNING
Be sure the engine is shut down before downloading. An engine
overspeed is possible if the engine is running during the download
process.

26 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

TRANSFERRING Note that this will not work with regular 723 controls.
TUNABLE
1. Make sure that all other programs that may access your computer’s
VALUES
communication port are shut down.
BETWEEN
723PLUS 2. Get the right cable to talk from your PC to the control (5416-870 for J1, 5415-
CONTROLS 614 for J2 or J3).
3. Start the Servlink server and open a new file. From the dialog window, select
the proper COM port for your PC, select POINT TO POINT communications
mode, and set the baud rate to 19200.
4. Select OK. If everything is working right, you should see an animated picture
of a string of “1”s and “0”s flying from the control to the PC on your screen.
You now have a network definition file whose default name is NET1. You
should save this file. Link this name to your control part number as it will only
work with that application. For instance if the upper level control number is
9907-031, you could save the file as 9907031.NET. DO NOT DISCONNECT
THE SERVER.
5. In the Servlink window you will now have another dialog window titled “your
filename.net”. In this window you will see a ballhead icon and a control
identifier name. Unless you have given the control a serial number (or name)
with the SLSN.EXE program, this name will display as “<unidentified>”.
6. Start the Watch Window program. Under the title bar in the Explorer window
you will find a tab with your network file and the control id displayed. Right
click this tab to display the pop-up menu, and select CONFIGURATION. If
you want to take the configuration from a control, select SAVE TO FILE. If
you want to download a new configuration to a control with an existing
application, then select LOAD FROM FILE.
7. If you select SAVE TO FILE, you will have to provide the name of a file
where you want to save the configuration. If your control has a part number of
9907-031 then you might want to call this file 9907031.cfg. Make the name
meaningful so you can find it easily the next time you need it.
8. If you select LOAD FROM FILE you will get a confirmation warning telling
you that the unit will be shut down. If you answer yes then you will be asked
for the name of the configuration file that you want to download.

Woodward Governor Company 27


723PLUS Hardware Manual Manual 02877

28 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

CHAPTER 6
SERVICE OPTIONS

PRODUCT The following are the factory options available for the service of Woodward
SERVICE equipment:
OPTIONS
• Replacement/Exchange (3-year warranty) (24-hour service)
• Flat Rate Repair (6-month warranty)
• Flat Rate Remanufacture (3-year warranty)

If you are experiencing problems with installation or unsatisfactory performance


of an installed system, the following options are available:
• Consult the system troubleshooting guide in this section.
• Contact Woodward technical assistance (see HOW TO CONTACT
WOODWARD later in this chapter) and discuss your problem. In most
cases, your problem can be resolved over the phone. If not, you can select
which course of action you wish to pursue based on the available services
listed in this section.

Replacement/ Replacement/Exchange is a premium program designed for the user who is in


Exchange need of immediate service. It allows the user to request and receive a like-new
replacement unit in minimum time (usually within 24 hours of the request),
providing a suitable unit is available at the time of the request, thereby minimizing
costly downtime. This is also a Flat Rate structured program and includes the full
3-year warranty.

This option allows customers to call in advance of a scheduled outage or an


unexpected outage and request a replacement control unit. If the unit is available
at the time of the call, it can usually be shipped out within 24 hours. The customer
replaces his field control unit with the like-new replacement and returns the field
unit to the Woodward facility as explained later in this chapter.

Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. The customer is invoiced the flat rate charge at the time the
replacement unit is shipped and must return the field unit to Woodward within 30
days. If the unit is not received within that time frame, the customer is invoiced
the difference between the flat rate replacement/exchange charge and the current
list price of a new unit.

Return Shipment Authorization Label. To ensure prompt receipt of the core,


and avoid additional charges, the package must be properly marked. A return
authorization label is included with every Replacement/Exchange unit that leaves
Woodward. The core should be repackaged and the return authorization label
affixed to the outside of the package. Without the authorization label, receipt of
the returned core could be delayed and cause additional charges to be applied.

Woodward Governor Company 29


723PLUS Hardware Manual Manual 02877

Flat Rate Repair Flat Rate Repair is available for the majority of standard products in the field.
This program offers the user repair service for their products with the advantage
of knowing in advance what the cost will be. All repair work carries a 180-day
warranty on replaced parts and labor.

Flat Rate Flat Rate Remanufacture is very similar to the Flat Rate Repair option with the
Remanufacture exception that the unit will be returned to the user in “like new” condition and
carry with it a full 3-year warranty. This option is applicable to mechanical
products only.

RETURNING If any part of the electronic control is to be returned to Woodward Governor


EQUIPMENT FOR Company for repair, attach a tag to the part with the following information:
REPAIR
• name and location where the control is installed;
• name and phone number of contact person;
• complete Woodward Governor Company part number(s) and serial
number(s);
• description of the problem;
• instructions describing the desired type of repair.

WARNING
Explosion Hazard—Do not connect or disconnect while circuit is live,
unless area is known to be non-hazardous.
Explosion Hazard—Substitution of components may impair
suitability for Class I, Division 2.

CAUTION
To prevent damage to electronic components caused by improper
handling, read and observe the precautions in Woodward Governor
Company Manual 82715, Guide for Handling and Protection of
Electronic Controls, Printed Circuit Boards, and Modules.

Packing a Control Use the following materials when returning a complete control:
• protective caps on all connectors;
• antistatic protective bags on all electronic modules;
• packing materials that will not damage the surface of the unit;
• at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
• a packing carton with double walls;
• a strong tape around the outside of the carton for increased strength.

30 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Additional When returning equipment to Woodward, please telephone and ask for the
Instructions Customer Service Department [(800) 835–5182 or (970) 663–3900]. They will
help expedite the processing of your order through our distributors or local service
facility. Factory repairs will be greatly expedited if a purchase order has been
issued for the item(s) to be repaired. Make arrangements in advance if possible.

REPLACEMENT When ordering replacement parts for electronic controls, include the following
PARTS information:
INFORMATION
• the part number(s) (XXXX-XXX) that is on the enclosure nameplate;
• the unit serial number, which is also on the nameplate.

HOW TO In North America use the following address when shipping or corresponding:
CONTACT Woodward Governor Company
WOODWARD Industrial Controls Group
PO Box 3800
3800 North Wilson Ave
Loveland CO 80539-3800, USA

TELEPHONE: (970) 663-3900 (24 hours a day)


TOLL-FREE PHONE (in North America): (800) 835-5182
FAX: (970) 962-7050

For assistance outside North America, call one of the following international
Woodward Governor Company facilities to obtain the address and phone number
of the facility nearest your location where you will be able to receive information
and service.
FACILITY PHONE NUMBER
Australia 61 2 9758 2322
Brazil 55 19 242 4788
England 44 118 9752727
India 0091 129 232840/41
Japan 81 476 93 4661
The Netherlands 31 2356 61111
Singapore 65 270 0081

There is also information and e-mail addresses on Woodward’s Internet (World


Wide Web) home page:
http://www.woodward.com

OTHER SERVICE Contact Woodward Governor Company, Customer Service Department, for the
FACILITIES name of your nearest Woodward distributor or service facility.

Woodward Governor Company 31


723PLUS Hardware Manual Manual 02877

ADDITIONAL Woodward Aftermarket Services offers the following after-sale support for all
AFTERMARKET Woodward products:
PRODUCT
• Customer Training
SUPPORT
SERVICES • Technical Assistance
• Field Service
• Specialized Services

Customer Training is offered either at our facilities in Loveland and Fort


Collins, Colorado, or at the customer’s site. This training, conducted by
experienced trainers, will assure that customer personnel will be able to maintain
system reliability and availability. For information concerning training available,
call the number above and ask for customer training.

Technical Assistance is available using the Woodward toll-free number. The


Aftermarket application engineering group is available to assist customers with
technical questions or problem solving during normal business hours or as
emergency support 24 hours a day. This group can also provide engineering
support for changes or enhancements after the commissioning of your system. For
technical engineering assistance, call the number above and ask for technical
assistance.

Field Service engineers are dispatched from the Woodward facility in Colorado,
or from one of many regional or worldwide offices located near the customer to
provide prompt response. Woodward field engineers are experienced and are
continually updated on all Woodward products as well as much of the non-
Woodward equipment they interface with. The field engineers ensure that all
documentation is updated, and all field engineers are well informed as to new
problems which might arise. Woodward field service engineers are on-call 24
hours a day. Call the number above and ask for field service.

Specialized Services can be tailored to the specific needs of the customer. These
services can be based on a particular aspect of a single service or a combination of
services and are covered under one low-cost service contract. A contract may be
for regularly scheduled training courses or possibly to have a field engineer visit
the customer site at pre-determined intervals to provide a system analysis, verify
proper operation, and make recommendations for maintenance improvements,
enhancements, or other needs. These contracts are usually custom-designed and
structured to allow ultimate flexibility, thereby allowing the customer to plan and
budget more accurately. For more details, contact the Woodward sales
representative, or call the number above and ask for sales support to discuss
specific needs.

For more information on Woodward aftermarket services, access


http://www.woodward.com on the Internet.

32 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

SYSTEM The following is a general troubleshooting guide for areas to check which may
TROUBLE- present potential difficulties. By making these checks appropriate to your engine/
SHOOTING turbine before contacting Woodward for technical assistance, your system
GUIDE problems can be more quickly and accurately assessed.

Actuators • Is the oil clean?


• Is the oil level normal?
• Does the actuator have the correct hydraulic pressure (if required)?
• Does the actuator have the correct pneumatic pressure (if required)?
• Does the driveshaft rotate (if required), and in the correct direction?
• Is the actuator wiring correct?
• Is the direction of the stroke correct?
• Has the compensation (if so equipped) been adjusted correctly?
• If there is a mechanical governor, are the speed, droop, and load limit
adjusted correctly?
• Is the hydraulic return line free and not clogged?
• Is there back pressure on the hydraulic return line?
• Is the feedback (if any) adjusted correctly and sending the correct signal?

Linkage • Is there slop or lost motion?


• Is there misalignment, binding, or side loading?
• Is there visible wear or scarring?
• Does the linkage move smoothly?

Valves • Does the valve move through it’s proper stroke smoothly?
• Does the valve travel it’s full stroke?
• Can mid-stroke be obtained and held?
• Does the valve fully seat (close) before the governor reaches full
minimum stroke?
• Does the valve fully open before the governor reaches maximum stroke?
• Is the bypass valve(s) (if any) in the proper position?
• If a steam turbine, are there nicks or contamination which allow steam to
pass when the valve is closed?

Woodward Governor Company 33


723PLUS Hardware Manual Manual 02877

Oil/Hydraulic • Is the oil at the proper operating pressure?


System
• Is the oil temperature too high for the type of oil being used?
• Is the oil contaminated?
• Does the actuator have sufficient flow of oil?
• Are the accumulators (if any) charged to the correct pressure?
• Are the filters plugged?
• Is the oil pump operating properly?

Fuel Injection • Are any rack shafts stuck?


Pumps
• Do all rack shafts move through their full stroke smoothly?
• Are all rack shaft settings equal, cylinder to cylinder, as the governor
output shaft is rotated from min to max fuel?
• Are any drain lines clogged?
• Are all injection lines in good condition and free of leaks?

Fuel/Steam • Is the engine/turbine inlet pressure at design specification?


Conditions
• Is the fuel/steam pressure in the proper operating range?
• Are pressure transducers (if any) located close to the engine/turbine?
• Are there any pressure regulating devices or valves which may interfere
with governor operation or proper fuel/steam flow?

Control, Alarm, • Does the governor indicate it is in the correct control mode?
And Fault
• Is the governor issuing any alarms?
Indications
• Are any of the components of the governor indicating hardware faults?
• Does the actuator demand agree with the actual valve position?
• Are any shutdown conditions present?
• Have the control dynamics been tuned to match the system response?

Input Signals • Are all input signals properly scaled?


• Are the inputs free of electrical noise and properly shielded?
• Is the wiring correct?
• Have all field input signals to the control been verified?
• Is the polarity of the signals correct?

34 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

Output Signals • Are the outputs calibrated?


• Have the actuator drivers been calibrated to the stroke of the fuel injection
pump, fuel valves, or turbine valves?
• Are the output signals free of noise and properly shielded?
• Is the wiring correct?

Transducers • Is the transducer calibrated for the proper range?


• Has it been tested by simulating it’s input and measuring it’s output
signal?
• Does the transducer have power?
• Are the sensing lines feeding the transducer clear of obstructions?
• Are all block, bleed, and bypass valves positioned properly?

Magnetic Pickups • Is the wiring between the speed sensing pickup and the control correct?
And Other Speed
• Are there any grounding problems or worn shields?
Sensing Devices
• Is the signal sufficient (at least 1.5 Vrms)?
• Is the signal a clean sine wave or square wave with no spikes or
distortions?
• Is the MPU head clean and free of oil or metallic particles?
• Is the MPU head free of any nicks or chips?
• Is the MPU or proximity probe correctly aligned with the gear?
• Is the speed sensing probe adjusted to the correct gap?
• Is the speed sensing probe head the correct size for the toothed wheel it is
being used with?

Input Voltage/ • Is the input power within the range of the control’s power supply input?
Power Supplies
• Is the input power free of switching noise or transient spikes?
• Is the power circuit dedicated to the governor only?
• Are the control’s supplies indicating that they are OK?
• Are the control’s supplies outputting the correct voltage?

Woodward Governor Company 35


723PLUS Hardware Manual Manual 02877

Electrical • Are all electrical connections tight and clean?


Connections
• Are all signal wires shielded?
• Are shields continuous from the device to the control?
• Are the shields terminated according to Woodward specifications?
• Are there low voltage signal wires running in the same wiring trays as
high voltage wiring?
• Are the governor’s signal common or grounds not tied to any other
devices?
• Have the signals been checked for electrical noise?

Voltage • Is the voltage regulator working properly?


Regulator

External Devices • Are there external devices the control is dependent on for input signals?
• Are these devices providing the correct signal to the control?
• Is the external device configured or programmed to be compatible with
the control?

36 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

TECHNICAL If you need to telephone for technical assistance, you will need to provide the
ASSISTANCE following information. Please write it down here before phoning:

General Your Name __________________________________________________


Site Location _________________________________________________
Phone Number _______________________________________________
Fax Number _________________________________________________

Prime Mover Engine/Turbine Model Number __________________________________


Information Manufacturer_________________________________________________
Number of Cylinders (if applicable) _______________________________
Type of Fuel (gas, gaseous, steam, etc) ____________________________
Rating ______________________________________________________
Application __________________________________________________

Governor Please list all Woodward governors, actuators, and electronic controls in your
Information system:

Woodward Governor Part Number and Revision Letter


_____________________________________________________
Control Description or Governor Type
_____________________________________________________
Serial Number ________________________________________________

Woodward Governor Part Number and Revision Letter


_____________________________________________________
Control Description or Governor Type
_____________________________________________________
Serial Number ________________________________________________

Woodward Governor Part Number and Revision Letter


_____________________________________________________
Control Description or Governor Type
_____________________________________________________
Serial Number ________________________________________________

If you have an electronic or programmable control, please have the adjustment


setting positions or the menu settings written down and with you when you phone.

Woodward Governor Company 37


723PLUS Hardware Manual Manual 02877

38 Woodward Governor Company


Manual 02877 723PLUS Hardware Manual

723PLUS CONTROL SPECIFICATIONS

Input Power
Low Voltage Model 18–40 Vdc (24 or 32 Vdc nominal)
High Voltage Model 90–150 Vdc (125 Vdc nominal)
Power Consumption 40 W nominal
Inrush Current (Low Voltage Model) 7 A for 0.1 ms
Inrush Current (High Voltage Model) 22 A for 15 ms

Inputs
Speed Signal Inputs (2)
Speed Input Voltage 1.0–50.0 Vrms
Speed Input Frequency Magnetic Pickup: 400 Hz to 15 kHz; Proximity Switch: 30Hz to 15 kHz
Speed Input Impedance 10 kΩ ± 15%
Note: EU Directive compliant applications are not currently able to use proximity switches due to the sensitivity of the
switches.
Discrete Inputs (8)
Discrete Input 24 Vdc, 10 mA nominal,18–40 Vdc range
Response Time 10 ms ±15%
Impedance 2.3 kΩ
Note: For Lloyd’s Register applications, use only control-supplied power.
Analog Inputs (4)
Analog Input ±5 Vdc or 0–20 mA, transducers externally powered
Common Mode Voltage ±40 Vdc
Common Mode Rejection 0.5% of full scale
Accuracy 0.5% of full scale
Load Sharing Input
Analog Input 0–4.5 Vdc
Common Mode Voltage ±40 Vdc
Common Mode Rejection 1.0% of full scale
Accuracy 1.0% of full scale

Outputs
Analog Outputs 0–1 or 4–20 mA (2)
Analog Output 0–1 mA or 4–20 mA (max. 600 Ω load)
Accuracy 0.5% of full scale
Analog Outputs 0–20 or 0–200 mA (2)
Analog Output 0–20 mA (max. 600 Ω load) or 0–200 mA (max. 70 Ω load)
Accuracy 0.5% of full scale
Relay Contact Outputs (3)
Contact Ratings 2.0 A resistive @ 28 Vdc; 0.5 A resistive @ 125 Vdc

Environment
Operating Temperature –40 to +70 °C (–40 to +158 °F)
Storage Temperature –55 to +105 °C (–67 to +221 °F)
Humidity 95% at +20 to +55 °C (+68 to +131 °F)
Lloyd’s Register of Shipping Specification Humidity Test 1
Mechanical Vibration Lloyd’s Register of Shipping Specification Vibration Test 2
Mechanical Shock US MIL-STD 801C Method 516.2, Proc. I, II, V
EMI/RFI Specification Lloyd’s Register of Shipping Specification
EN 50081–2 and EN 50082–2

Compliance
UL/cUL Listing Class 1, Division 2, Groups A, B, C, D
Lloyd’s Register of Shipping Certification Pending
American Bureau of Shipping (ABS) Certification Pending
European Union (EU) Compliant with EMC Directive 89/336/EEC (Low Voltage Model Only)

Woodward Governor Company 39


We appreciate your comments about the content of our publications.
Please send comments to:
Woodward Governor Company/Industrial Controls Group
Attention: Marketing Communications
PO Box 3800
Loveland CO 80539-3800 USA

WOODWARD GOVERNOR COMPANY / INDUSTRIAL CONTROLS GROUP


Engine, Turbomachinery, and Hydraulic Turbine Controls
PO Box 3800 (3800 North Wilson Ave), Loveland CO 80539-3800, USA • Phone (970) 663-3900 • Fax (970) 962-7050
E-mail and World Wide Web Home Page—http://www.woodward.com

Registered Firm
ISO 9001:1994/Q9001-1994
Certificate QSR-36

23 PLANTS 15 REGIONAL SALES OFFICES 18 DISTRIBUTORS/REPS.


IN 10 COUNTRIES— IN 10 COUNTRIES— IN 7 COUNTRIES—

Australia (New South Wales) Canada (Québec) Canada (Alberta & Ontario)
Brazil (Campinas) China (Beijing) Mexico (Mexico City)
China (Tianjin) Czech Republic (Plzen) Netherlands Antilles (Curaçao)
Germany (Aken/Elbe & Kelbra) Germany (Tettnang) Spain (Cadiz)
India (Haryana) Korea (Pusan) United Kingdom (Dyce, Scotland)
Japan (Tomisato & Kobe) Mexico (Mexico City) Unted States (California[2], Delaware,
Netherlands (Hoofddorp & Rotterdam) New Zealand (Christchurch) Indiana, Louisiana, Minnesota, North
Singapore Poland (Warsaw) Carolina, Puerto Rico, Texas[2],
United Kingdom (Reading, England, & United Arab Emirates (Abu Dhabi) Washington)
Prestwick, Scotland) United States (Alabama, California, Venezuela (Caracas)
United States (Colorado[2], Illinois[3], Illinois, Pennsylvania, Texas,
Michigan[2], New York, South Washington)
Carolina, Tennessee)
plus Authorized Independent Service Facilities in 35 countries throughout the world