ELECTRICAL PLAN SYMBOLS ELECTRICAL ONE-LINE SYMBOLS

40 PM IDENTIFICATION SYMBOLS SWITCHES/RECEPTACLES RACEWAY MEDIUM VOLTAGE LOW VOLTAGE MISCELLANEOUS


e LOW VOLTAGE CIRCUIT BREAKER
36:

MOTOR
a HP

a
b
CIRCUIT BREAKER, MEDIUM VOLTAGE b a a = TYPE
3:

HP = HORSEPOWER RATING
SINGLE POLE SWITCH 52 c MCP = MOTOR CIRCUIT PROTECTOR
EXPOSED CONDUIT a = CIRCUIT BREAKER NUMBER FULL LOAD AMPS AS NOTED
b
EQUIP # EQUIPMENT AND INSTRUMENT IDENTIFICATION a = CIRCUIT DESIGNATION d f TM = THERMAL MAGNETIC
2017

b = FRAME SIZE
b = DEVICE SWITCHED DESIGNATION SS = SOLID STATE
BREAK AND CONTINUATION IN CONDUIT RUN
AUG-

b = FRAME SIZE (MANUFACTURER TO DETERMINE PACKAGED EQUIPMENT

a
b
a
c =TYPE FRAME SIZE UNLESS INDICATED) LOAD RATING AS INDICATED
a ANSI RELAY DEVICE
c = NUMBER OF POLES
e: 23-

2 = DOUBLE POLE SWITCH a = ANSI DEVICE FUNCTION a = RATED LOAD

c
EQUIPMENT/INSTRUMENT LOCATOR b
d = TRIP SETTING (AT = AMP TRIP) b b = UNIT(HP, KW, KVA) AS INDICATED
3 = THREE-WAY SWITCH EXPOSED CONDUIT HIDDEN BEHIND WALLS, b = QUANTITY
(AC = MCP CONTINUOUS RATING)
4 = FOUR-WAY SWITCH FLOORS OR OTHER STRUCTURES
otDat

LUMINAIRE IDENTIFICATION e = DESIGNATION TRANSFORMER


b K = KEY OPERATED SWITCH a
a f = INTERRUPTING RATING f a = DEVICE I.D.
X a = CIRCUIT DESIGNATION F = SWITCH AND FUSESTAT HOLDER
c MEDIUM VOLTAGE b
b = KVA RATING
Pl

b = DEVICE SWITCHED FROM P = SWITCH AND PILOT LIGHT UNDERGROUND CONDUIT, DIRECT BURIED
DISCONNECT SWITCH c
c = MOUNTING HEIGHT IN FEET TO BOTTOM OR IN DUCTBANK c = NUMBER OF PHASES
T = THERMOSTAT d
NON-FUSED CUT OUT g d = PRIMARY VOLTAGE
OFFIXTURE D = DIMMER SWITCH * LOW VOLTAGE CIRCUIT BREAKER e
e = SECONDARY VOLTAGE
L = LOW VOLTAGE LIGHT SWITCH AUXILIARY OPERATOR h
f,g = CONNECTION TYPE SYMBOL
M = MANUAL MOTOR STARTER CONDUIT IN SLAB * = S = SHUNT TRIP
MEDIUM VOLTAGE = G = GROUND FAULT INTERRUPTER h = IMPEDANCE
CONDUIT IDENTIFICATION
a DISCONNECTING FUSE = V = SOLENOID KEY RELEASE
XXXX XXXX = CONDUIT NUMBER,
OCCUPANCY SENSOR CONDUIT VERTICAL CHANGE IN DIRECTION GROUNDED WYE CONNECTION
SINGLE FUSE CUT OUT
REFER TO CONDUIT SCHEDULE
a = CIRCUIT DESIGNATION
UNLESS OTHERWISE NOTED, GROUPED CONDUITS b
b = DEVICE SWITCHED DESIGNATION
ARE LABELED LEFT TO RIGHT OR TOP TO BOTTOM. CONDUIT CAP A DELTA CONNECTION

a DISCONNECT SWITCH
o

SWITCH AND SINGLE RECEPTACLE


t
abi

INDICATES KEYNOTE X b A = TYPE, REFER TO DISCONNECT SCHEDULE


X a = CIRCUIT DESIGNATION J JUNCTION BOX MEDIUM VOLTAGE
: TM or

(PERTAINS ONLY TO SHEET WHERE NOTE IS FOUND) a ENGINE-GENERATOR RATINGS AS INDICATED ON


b = DEVICE TYPE DESIGNATION DISCONNECTING FUSE
DOUBLE FUSE CUT OUT b THE DRAWINGS
G
CONDUIT SEAL c
~ a = KVA/KW
User

A DISCONNECT SWITCH d b = VOLTAGE/CONNECTION


a
a = TYPE, REFER TO DISCONNECT SCHEDULE b DUPLEX RECEPTACLE B e c = PHASE
CONDUIT TEE MEDIUM VOLTAGE SINGLE FUSE
a = CIRCUIT DESIGNATION d = WIRE
b = DEVICE TYPE DESIGNATION FUSED DISCONNECT SWITCH e = PF
B = TYPE, REFER TO DISCONNECT SCHEDULE
a DUCTBANK
GROUNDING b QUADRUPLEX RECEPTACLE
APPROXIMATE DIMENSIONS
b = FUSE RATING
a = CIRCUIT DESIGNATION
SHOWN ON DUCTBANK SECTIONS MEDIUM VOLTAGE DOUBLE FUSE a
b = DEVICE TYPE DESIGNATION

b
CURRENT TRANSFORMER WITH
UNDERGROUND GROUND CABLE
b SHORTING TERMINAL BLOCK
#4/0 SDBC UNLESS OTHERWISE NOTED a
IN FLOOR DUPLEX RECEPTACLE a = QUANTITY
b
a = CIRCUIT DESIGNATION b = RATIO
GROUND ROD
b = DEVICE TYPE DESIGNATION
CONDUIT SIZE AND CONDUCTORS MEDIUM VOLTAGE c a d
GROUND ROD AND GROUND WELL a LIVE FRONT TERMINATOR FUSE
IN FLOOR QUADRUPLEX RECEPTACLE POTENTIAL TRANSFORMER
b
a = CIRCUIT DESIGNATION INDIVIDUAL CONDUCTORS a = QUANTITY
GROUND CONNECTION
b b = RATIO
b = DEVICE TYPE DESIGNATION
MEDIUM VOLTAGE ELBOW
W"C-(3-X (Ø), 1-Y (N) & 1-Z (G)) c,d = CONNECTION TYPE SYMBOL
a DUPLEX RECEPTACLE w/SPLIT WIRE
b W"C (WHERE INDICATED): W = CONDUIT TRADE SIZE COMBINATION STARTER
a = CIRCUIT DESIGNATION SSM SOLID STATE
WITH CONTROL POWER TRANSFORMER
LUMINAIRES b = DEVICE TYPE DESIGNATION
3-X (Ø):
MEDIUM VOLTAGE TEE a
a = CIRCUIT BREAKER DISCONNECT,
MULTIFUNCTION METER

3 = QUANTITY TYPE AS NOTED


a
APPLIANCE RECEPTACLE X = SIZE OF CONDUCTORS b = STARTER TYPE
b b
a = CIRCUIT DESIGNATION (Ø) = DESIGNATES PHASE CONDUCTORS c = NEMA STARTER SIZE ATP
2', 4', OR 8' STRIP
c AMPERE TEST POINT
b = DEVICE TYPE DESIGNATION d = OVERLOAD

MEDIUM VOLTAGE CONTACTOR


B WELDING RECEPTACLE 1-Y (N)(WHERE INDICATED): d
2' X 2' LAY-IN TROFFER
a = CIRCUIT DESIGNATION 1 = QUANTITY
VTP
a b = DISCONNECT TYPE Y = SIZE OF CONDUCTORS VOLTAGE TEST POINT
(N) = DESIGNATES NEUTRAL CONDUCTORS
1

a
e: 2:

SPECIAL PURPOSE RECEPTACLE MEDIUM VOLTAGE STARTER


2' X 4' LAY-IN TROFFER b
a = CIRCUIT DESIGNATION
Scal

b = DEVICE TYPE DESIGNATION 1-Z (G)(WHERE INDICATED):


1 = QUANTITY
ot

d VARIABLE FREQUENCY DRIVE


Pl

Z = SIZE OF CONDUCTORS UTILITY METER


LUMINAIRE POLE MOUNTED TWIST LOCK RECEPTACLE WITH FEATURES AS SHOWN
a (G) = DESIGNATES GROUND CONDUCTORS
a = AMP RATING MOV-ELBOW ARRESTER
a = INPUT CONTACTOR
pen

a
b = OUTPUT CONTACTOR
d_Pen_v0905.

a
TELEPHONE OUTLET c = BYPASS STARTER
STROBE b U{3-X (Ø) & 1-X (G)} LR
A a = CIRCUIT DESIGNATION d = INPUT CIRCUIT BREAKER
a = COLOR b = MOUNTING HEIGHT VFD
U = NUMBER OF PARALLEL RUNS
R = RED LL LINE REACTOR
a
G = GREEN DATA COMMUNICATIONS OUTLET
b
o_St

A = AMBER a = CIRCUIT DESIGNATION b


LOAD REACTOR LIGHTNING ARRESTER
b = MOUNTING HEIGHT
l

MULTI CONDUCTOR CABLES


ol
: Car

LUMINAIRE, EMERGENCY BATTERY-POWERED K/2/C#16S


pt

K (WHERE INDICATED) = NUMBER OF PAIRS


i
gnScr

2/C#16S = TWO CONDUCTOR, 16 GAUGE, TWISTED


LUMINAIRE, EMERGENCY/EXIT BATTERY-POWERED
FIRE ALARM SHIELDED PAIR REDUCED VOLTAGE SOLID STATE STARTER SPD SURGE PROTECTIVE
Desi

WITH FEATURES AS SHOWN DEVICE


K/3/C#16S BS = BYPASS STARTER
d
a

K (WHERE INDICATED) = NUMBER OF TRIPLETS RVSS BS


LUMINAIRE, EMERGENCY BATTERY-POWERED REMOTE
ctb

SMOKE DETECTOR 3/C#16S = THREE CONDUCTOR, 16 GAUGE, TWISTED


e: gshade.

a = TYPE SHIELDED TRIPLETS


DRAWOUT CONNECTION
LUMINAIRE, SURFACE OR PENDANT MOUNTED I = IONIZATION
P = PHOTOELECTRIC N/CX
d = DUCT DETECTOR N = NUMBER OF CONDUCTORS IN THE CABLE
Tabl

LUMINAIRE, WALL MOUNTED X = SIZE OF CONDUCTORS


FACP FIRE ALARM CONTROL PANEL GROUND
or
Col

LUMINAIRE, FLOOD/SPOT
F FIRE ALARM PULL STATION
FIBER OPTIC CABLES
CAPACITOR
1
: Layout

F FIRE ALARM HORN/STROBE COMBINATION FO/N


LUMINAIRE, EXIT ONE OR TWO FACES AS INDICATED.
ARROW POINTS IN DIRECTION OF EGRESS. N = NUMBER OF INDIVIDUAL FIBERS
EQUIPMENT ENCLOSURE BATTERY
M odel

F FIRE ALARM STROBE

LUMINAIRE, WALL WASHER


F FIRE SPRINKLER K KIRK KEY INTERLOCK
F = FLOW SWITCH
PE PHOTOCELL T = TAMPER SWITCH

LOAD BANK
t
abio

DESIGNED JOB NO.


NEER
m or

NEER

CAC SOUTH VALLEY WATER RECLAMATION FACILITY VERIFY SCALES


10548.B10
LAST SAVED BY:t

NE ENGI

PROJECT ENGI

DRAWN BAR IS ONE INCH ON


PARTNER

ORIGINAL DRAWING DRAWING NO.


MNH MISCELLANEOUS ELECTRICAL UPGRADES
CHECKED ELECTRICAL 0 1" 00GE01
PLI

CLL
SCI

DATE
LEGEND IF NOT ONE INCH ON
THIS SHEET, ADJUST
SHEET NO.
DI

SCALES ACCORDINGLY
REV DATE BY DESCRIPTION OF XXX

PROJECT NO. FILE NAME: 10548B1000GE001.dgn


ABBREVIATIONS POWER DEVICE FUNCTION NUMBERS
A AMP J JUNCTION BOX TACH TACHOMETER 1 MASTER ELEMENT 83 AUTOMATIC SELECTIVE CONTROL OR TRANSFER RELAY
ABS ABSOLUTE TB - X TERMINAL BLOCK - UNIT X 2 TIME-DELAY STARTING OR CLOSING RELAY 84 OPERATING MECHANISM
37 PM AC ALTERNATING CURRENT K KEY INTERLOCK TC THERMOCOUPLE / TIME CLOCK / TRAY CABLE 3 CHECKING OR INTERLOCKING RELAY 85 PILOT COMMUNICATIONS, CARRIER OR PILOT-WIRE RELAY
ACK ACKNOWLEDGE KA KILOAMP TD TEMPERATURE DETECTOR RELAY 4 MASTER CONTACTOR 86 LOCKOUT RELAY
37:

ACTR ACTUATOR KV KILOVOLT TE TOTALLY ENCLOSED 5 STOPPING DEVICE 87 DIFFERENTIAL PROTECTIVE RELAY
AF AMP FRAME KVA KILOVOLT AMPERE TEFC TOTALLY ENCLOSED FAN COOLED 6 STARTING CIRCUIT BREAKER 88 AUXILIARY MOTOR OR MOTOR GENERATOR
3:

AFC AUTOMATIC FREQUENCY CONTROL KVAR KILOVAR (REACTANCE) TENV TOTALLY ENCLOSED NON-VENTILATED 7 ANODE CIRCUIT BREAKER 89 LINE SWITCH
2017

AIC AMP INTERRUPTING CAPACITY KW KILOWATT TERM TERMINAL 8 CONTROL POWER DISCONNECTING DEVICE 90 REGULATING DEVICE
AM AMMETER KWD KILOWATT DEMAND TJB TERMINAL JUNCTION BOX 9 REVERSING DEVICE 91 VOLTAGE DIRECTIONAL RELAY
AUG-

ANN ANNUNCIATOR KWH KILOWATT HOUR TM THERMAL MAGNETIC 10 UNIT SEQUENCE SWITCH 92 VOLTAGE AND POWER DIRECTIONAL RELAY
ANT ANTENNA TP TWISTED PAIR 11 MULTIFUNCTION DEVICE 93 FIELD-CHANGING CONTACTOR
e: 23-

APU AUXILIARY POWER UNIT L LONG-TIME TS TEMPERATURE SWITCH 12 OVER-SPEED DEVICE 94 TRIPPING OR TRIP-FREE RELAY
ARM ARMORED CABLE L-B LINE-BUS TS1W TWO SPEED CONSEQUENT POLE, ONE WINDING 13 SYNCHRONOUS-SPEED DEVICE
AS AMMETER SWITCH L-G LINE-GROUND TS2W TWO SPEED SEPARATE WINDING 14 UNDER-SPEED DEVICE
otDat

ASYM ASYMMETRICAL LA LIGHTNING ARRESTOR TSTAT THERMOSTAT 15 SPEED OR FREQUENCY MATCHING DEVICE COMMONLY USED SUFFIX LETTERS APPLIED TO
AT AMP TRIP LBL LABEL 16 DATA COMMUNICATIONS DEVICE
POWER DEVICE FUNCTION NUMBERS
Pl

ATO AUTOMATIC THROW OVER LC LIGHTING CONTACT OR UHF ULTRA HIGH FREQUENCY 17 SHUNTING OR DISCHARGE SWITCH
ATP AMMETER TEST POINT LCP- X LOCAL CONTROL PANEL NO. X UNG UNGROUNDED 18 ACCELERATING OR DECELERATING DEVICE
A ALARM ONLY
ATS AUTOMATIC TRANSFER SWITCH LL LEAD-LAG LOAD REACTOR UPS UNINTERRUPTABLE POWER SUPPLY 19 STARTING-TO-RUNNING TRANSITION CONTACTOR
B BUS PROTECTION
AUTO XFMR AUTOMATIC TRANSFORMER LP LIGHT POLE UVR UNDER VOLTAGE RELAY 20 ELECTRICALLY OPERATED VALVE
G GROUND FAULT PROTECTION
AUX AUXILIARY LP - X LIGHTING PANEL NO. X 21 DISTANCE RELAY
(RELAY CT IN A SYSTEM NEUTRAL CIRCUIT OR GENERATOR PROTECTION)
AWG AMERICAN WIRE GAGE LTG LIGHTING V VOLT 22 EQUALIZER CIRCUIT BREAKER
GS GROUND FAULT PROTECTION
LV LOW VOLTAGE VA VOLT AMPERE 23 TEMPERATURE CONTROL DEVICE
(RELAY CT IN TOROIDAL OR GROUND SENSOR TYPE)
B BELL LVL LEVEL VAR VARMETER 24 VOLTS PER HERTZ RELAY
BAT BATTERY L LINE PROTECTION
VCP VENDOR CONTROL PANEL 25 SYNCHRONIZING OR SYNCHRONISM-CHECK DEVICE
BFG BELOW FINISHED GRADE M MOTOR PROTECTION
M-X MOTOR CONTROLLER NO. X VFD VARIABLE FREQUENCY DRIVE 26 APPARATUS THERMAL DEVICE
BHP BRAKE HORSEPOWER N GROUND FAULT PROTECTION
MA MILLIAMPERE VHF VERY HIGH FREQUENCY 27 UNDERVOLTAGE RELAY
(RELAY COIL CONNECTED IN RESIDUAL CT CIRCUIT)
o

BKR BREAKER MCA MOTOR CIRCUIT AMPS VM VOLTMETER 27N GROUND FAULT UNDERVOLTAGE RELAY
t
abi

BRF BELOW RAISED FLOOR T TRANSFORMER PROTECTION


MCC - X MOTOR CONTROL CENTER NO. X VP VAPORPROOF 28 FLAME DETECTOR
: TM or

V VOLTAGE
MCP MOTOR CIRCUIT PROTECTOR VR VOLTAGE REGULATOR 29 ISOLATING CONTACTOR
C CONDUIT / CONTINUOUS LOAD P PHASE PROTECTION
MH MANHOLE / MOUNTING HEIGHT VS VOLTAGE SWITCH 30 ANNUNCIATOR RELAY
CB CIRCUIT BREAKER MLO MAIN LUGS ONLY VT VOLTAGE TRANSFORMER 31 SEPARATE EXCITATION DEVICE
User

CCTV CLOSED CIRCUIT TELEVISION MOD MOTOR OPERATED DAMPER VTP VOLTAGE TEST POINT 32 DIRECTIONAL POWER RELAY
CCW COUNTER CLOCKWISE MOV METAL OXIDE VARISTOR 33 POSITION SWITCH
ABBREVIATIONS
CKT CIRCUIT MRP MOTOR PROTECTION RELAY W WATT / WEST 34 MASTER SEQUENCE DEVICE
COAX COAXIAL CABLE MS-X MOTOR STARTER NO. X WT WATER TIGHT 35 BRUSH-OPERATING OR SLIP-RING SHORT-CIRCUITING DEVICE AFD - ARC FLASH DETECTOR
COM COMMON MSP MOTOR STARTING PANEL WP WEATHER PROOF 36 POLARITY DEVICE CLK - CLOCK OR TIMING SOURCE
COMM COMMUNICATION MTO MANUAL THROW OVER 37 UNDERCURRENT OR UNDERPOWER RELAY DDR - DYNAMIC DISTURBANCE RECORDER
CPT CONTROL POWER TRANSFORMER MTR-X MOTOR NO. X XFMR TRANSFORMER 38 BEARING PROTECTIVE DEVICE DFR - DIGITAL FAULT RECORDER
CS CONTROL SWITCH MTS MANUAL TRANSFER SWITCH 39 MECHANICAL CONDITION MONITOR ENV - ENVIRONMENTAL DATA
CT CURRENT TRANSFORMER MV MEGAVOLT 40 FIELD RELAY HIZ - HIGH IMPEDANCE FAULT DETECTOR
CV CONTROL VALVE MVA MEGAVOLT-AMPERES 41 FIELD CIRCUIT BREAKER HMI - HUMAN MACHINE INTERFACE
CW CLOCKWISE / COOL WHITE MVS MEDIUM VOLTAGE SWITCH 42 RUNNING CIRCUIT BREAKER HST - HISTORIAN
MW MEGAWATT 43 MANUAL TRANSFER OR SELECTOR DEVICE LGC - SCHEME LOGIC
DC DIRECT CURRENT 44 UNIT SEQUENCE STARTING RELAY MET - SUBSTATION METERING
DCS DISTRIBUTED CONTROL SYSTEM N NEUTRAL 45 ABNORMAL ATMOSPHERIC CONDITION MONITOR PDC - PHASOR DATA CONCENTRATOR
DCU - X DISTRIBUTED CONTROL UNIT NO. X NC NORMALLY CLOSED 46 REVERSE-PHASE OR BALANCE CURRENT RELAY PMU - PHASOR MEASUREMENT UNIT
DEMO DEMOLITION NEC NATIONAL ELECTRICAL CODE 47 PHASE-BALANCE OR PHASE-SEQUENCE VOLTAGE RELAY PQM - POWER QUALITY MONITOR
DISC DISCONNECT SWITCH NFC NONMETALLIC FLEXIBLE CONDUIT 48 INCOMPLETE SEQUENCE RELAY RIO - REMOTE I/O DEVICE
DM DEMAND METER NL NIGHT LIGHT 49 MACHINE OR TRANSFORMER THERMAL RELAY RTU - REMOTE TELEMETRY UNIT/REMOTE TERMINAL UNIT
DPDT DOUBLE POLE DOUBLE THROW NO NORMALLY OPEN 50 INSTANTANEOUS OVERCURRENT RELAY SER - SEQUENCE OF EVENTS RECORDER
DPST DOUBLE POLE SINGLE THROW NP NAMEPLATE 51 AC TIME OVERCURRENT RELAY TCM - TRIP CIRCUIT MONITOR
DS DOOR SWITCH 52 AC CIRCUIT BREAKER
O OPEN OR OPENED 53 FIELD EXCITATION RELAY
E/G EMERGENCY GENERATOR OH OVERHEAD 54 TURNING GEAR ENGAGING DEVICE
EM EMERGENCY OL OVERLOAD RELAY 55 POWER FACTOR RELAY
EMT ELECTRICAL METALLIC TUBING 56 FIELD APPLICATION RELAY
ENCL ENCLOSURE P POLE 57 SHORT-CIRCUITING OR GROUNDING DEVICE
ENG ENGINE PA PUBLIC ADDRESS 58 RECTIFICATION FAILURE RELAY
ENT ELECTRICAL NON-METALLIC TUBING PB PUSHBUTTON / PULL BOX 59 OVERVOLTAGE RELAY
EP EXPLOSION PROOF PCS PVC COATED GALVANIZED STEEL CONDUIT 60 VOLTAGE OR CURRENT BALANCE RELAY
ETM ELAPSED TIME METER PCM PROCESS CONTROL MODULE 61 DENSITY SWITCH OR SENSOR
1

PE PHOTOCELL 62 TIME-DELAY STOPPING OR OPENING RELAY


e: 2:

FA FIRE ALARM PF POWER FACTOR 63 PRESSURE SWITCH


FACP FIRE ALARM CONTROL PANEL PFCC POWER FACTOR CORRECTION CAPACITOR
Scal

64 GROUND DETECTOR RELAY


FDR FEEDER PFR PHASE FAILURE RELAY 65 GOVERNOR
ot

FLA FULL LOAD AMPS PH PHASE 66 NOTCHING OR JOGGING DEVICE


Pl

FLX FLEXIBLE CONDUIT PNL PANEL 67 AC DIRECTIONAL OVERCURRENT RELAY


FO FIBER OPTIC PPX POWER PANEL NO. X 68 BLOCKING OR OUT OF STEP RELAY
pen

FRC FIBERGLASS RIGID CONDUIT PRI PRIMARY 69 PERMISSIVE CONTROL DEVICE


d_Pen_v0905.

FREQ FREQUENCY PT POTENTIAL TRANSFORMER 70 RHEOSTAT


FU FUSE PVC POLYVINYL CHLORIDE RIGID PLASTIC CONDUIT 71 LIQUID LEVEL SWITCH
FU SW FUSED SWITCH PWR POWER 72 DC CIRCUIT BREAKER
FVNR FULL VOLTAGE NON-REVERSING 73 LOAD-RESISTOR CONTACTOR
FVR FULL VOLTAGE REVERSING RAC RIGID ALUMINUM CONDUIT 74 ALARM RELAY
o_St

FWD FORWARD RECPT RECEPTACLE 75 POSITION CHANGING MECHANISM


REV REVERSE 76 DC OVERCURRENT RELAY
oll

G GROUND / EQUIPMENT GROUND / GROUND FAULT RF RADIO FREQUENCY 77 TELEMETERING DEVICE


: Car

GEN GENERATOR RMS ROOT MEAN SQUARED 78 PHASE-ANGLE MEASURING RELAY


GRC GALVANIZED STEEL RIGID CONDUIT RVAT REDUCED VOLTAGE AUTO TRANSFORMER 79 AC RECLOSING RELAY
pt

GFCI GROUND FAULT CIRCUIT INTERRUPTER (RECEPTACLE) RVNR REDUCED VOLTAGE NON-REVERSING
i

80 FLOW SWITCH
gnScr

GFI GROUND FAULT INTERRUPTER (BREAKER) RVSS REDUCED VOLTAGE SOLID STATE 81 FREQUENCY RELAY
GFR GROUND FAULT RELAY 82 DC LOAD MEASURING RECLOSING RELAY
Desi

S SHIELD / SHORT-TIME
H HOT-LEG SA SURGE ARRESTER
HF HIGH FREQUENCY SC SHORT CIRCUIT
ctb

HP HORSEPOWER SDBC SOFT DRAWN BARE COPPER


e: gshade.

HPS HIGH PRESSURE SODIUM SFL SUB FEED LUGS


HR HOUR SLT SEALTIGHT LIQUIDTIGHT FLEXIBLE CONDUIT
HSTAT HUMIDISTAT SM SURFACE MOUNTED
HV HIGH VOLTAGE SP SINGLE POLE
Tabl

HVAC HEATING/VENTILATION/AIR CONDITIONING SPD SURGE PROTECTIVE DEVICE


or

HZ HERTZ SPDT SINGLE POLE DOUBLE THROW


Col

SPST SINGLE POLE SINGLE THROW


I INSTANTANEOUS LOAD SPKR SPEAKER
IC INTERRUPTING CAPACITY
1

SS SOLID STATE
: Layout

IJB INSTRUMENT JUNCTION BOX STB SHORTING TERMINAL BLOCK


IMC INTERMEDIATE METAL CONDUIT SW SWITCH
INST INSTANTANEOUS SWBD SWITCHBOARD
M odel

INT INTERLOCK SWGR SWITCHGEAR


INTERCOM INTERCOMMUNICATION SYM SYMMETRICAL

NOTES:

1. REFER TO SPECIFICATIONS AND OTHER DRAWINGS FOR ADDITIONAL ABBREVIATIONS.


t
abio

DESIGNED JOB NO.


NEER
m or

NEER

CAC SOUTH VALLEY WATER RECLAMATION FACILITY VERIFY SCALES


10548.B10
LAST SAVED BY:t

NE ENGI

PROJECT ENGI

DRAWN BAR IS ONE INCH ON


PARTNER

ORIGINAL DRAWING DRAWING NO.


MNH MISCELLANEOUS ELECTRICAL UPGRADES
CHECKED ELECTRICAL 0 1" 00GE02
PLI

CLL
SCI

DATE
ABBREVIATIONS IF NOT ONE INCH ON
THIS SHEET, ADJUST
SHEET NO.
DI

SCALES ACCORDINGLY
REV DATE BY DESCRIPTION OF XXX

PROJECT NO. FILE NAME: 10548B1000GE002.dgn

You might also like