Professional Documents
Culture Documents
M-4272 Presentation 20120119
M-4272 Presentation 20120119
Introduction
To maintain plant operation and process continuity, motor
buses may require transfer from a present (old) source to a new
source:
- Power plants
- Industrial facilities
Introduction
The coast down period and resultant voltage and frequency decay
may take seconds, and unsupervised source transfer may cause
damage.
Maintenance
Motor Bus Transfer
GSU
Transformer
Unit Aux Startup
Transformer Transformer
MAIN VT STARTUP VT
NC NO
G Motor Bus
M M M Other
MOTOR BUS VT Load
Motor Bus Transfer
Two-Breaker Configuration
MAIN SOURCE STARTUP SOURCE
CT-M CT-SU
52 N.C. N.O. 52
M VT-B SU
M M
Motor Bus Transfer
M M M M M M
Motor Bus Transfer
Three-Breaker Configuration
(Main-Tie-Main)
NORMAL SOURCE (Main 1 ) ALTERNATE SOURCE (Main 2)
CT-M1 CT-M2
M-4272 M-4272
VT-M1 VT-M2
52 N.C. N.C. 52
M1 M2
VT-B1 VT-B2
BUS-TIE
STATION BUS SYSTEM BUS 1 BUS 2
52T
CT-B1 CT-B2
N.O.
M M M M
Motor Bus Transfer
Motor Size: The larger the motor, the longer the time the voltage
will take to decay on an induction motor.
Loading: The higher the load on the motors, the faster the motor
bus frequency will decay.
Inertia: The higher the inertia of the aggregate motor loads on the
motor bus, the more slowly the motor bus frequency will decay
during the disconnected coast down period. That has a direct
impact on how fast the phase angle changes.
- Low inertia loads will cause the phase angle to change quickly,
as the frequency of motor bus decays quickly, and the slip
frequency between the motor bus and the new source
quickly increases.
Motor Bus Transfer
- Voltage will tend to decay much more rapidly on a motor bus with all
induction motors
Resultant V/Hz
E
R =
1.3
3p
u
@ -95 degree
θ
s
ES = 1 pu @ 0 degrees
Motor Bus Transfer
▪ Voltages and phase angle between the motor bus and the new
source must be evaluated prior to the transfer to assure that the
motor bus and the new source are in synchronism and that the
new source voltage is within acceptable limits.
Source 1 Source 2
(Old Source) (New Source)
Motor Bus
M M M
Motor Bus Transfer
Source 1 Source 2
(Old Source) (New Source)
Motor Bus
M M M
Motor Bus Transfer
Source 1 Source 2
(New Source) (Old Source)
Motor Bus
M M M
Motor Bus Transfer
Open Transition
▪ Open Transition - Methods
- Fast Transfer
- In-Phase Transfer
- Residual Voltage Transfer
- Fixed Time Transfer
▪ Open Transition - Modes
- Sequential Mode
- Simultaneous Mode
Motor Bus Transfer
Open Transition
Source 1 Source 2
(Old Source) (New Source)
Motor Bus
M M M
Motor Bus Transfer
Open Transition
Source 1 Source 2
(Old Source) (New Source)
Motor Bus
M M M
Motor Bus Transfer
Open Transition
Source 1 Source 2
(New Source) (Old Source)
Motor Bus
M M M
Motor Bus Transfer
-π
-2π
Motor Bus Transfer
Fast Transfer Method
The new source breaker will
be closed by the Fast
Transfer Method if the
phase angle between the
motor bus and the new
source is within or moves
into the phase angle limit
during the Fast Transfer
Enable (Time) Window.
One-cycle phase angle
response is required.
Closing is also supervised
by an Upper and Lower
Voltage Limit check on the
new source.
Motor Bus Transfer
In-Phase Transfer Method
The new source breaker will be closed using the In-Phase
Transfer Method by predicting movement through zero phase
coincidence between the motor bus and the new source during
the In-Phase Transfer Enable Window.
Closing is also supervised by an Upper and Lower Voltage Limit
check on the new source and a Slip (∆
∆F) Frequency Limit between
the motor bus and the new source.
The calculation of the predicted phase coincidence shall be
compared with the breaker closing time setting for the new
source breaker for the In-Phase Transfer method.
In order to accurately predict phase coincidence, considering the
decaying motor bus frequency, the phase angle, slip frequency
and rate-of-change of frequency between the motor bus and the
new source must be calculated and inserted in the following
second order partial differential equation to solve for the precise
breaker closing advance angle (Φ) to compensate for the breaker
closing time (TB). One-cycle response is required.
Motor Bus Transfer
In-Phase Transfer Method
Motor Bus Transfer
Open Transition – Sequential Mode
Transfer Timing Sequence
Delays Eliminated
Fast Transfer
Sequential Trip and Close of Old
and New Source Breakers (“early b” breaker status contact)
Advantages
- Fast (5 to 7 cycles)
- Transient torques are reduced due to speed of transfer
- Transfer of complete bus with reduced interrupting of process
- Rapid supervision of the phase angle just prior and just after old
source interruption is mandatory and possible with high-speed
sync-check relays
- Avoids parallel transfer operation
- Avoids exposure to breaker failure effects
Fast Transfer
Simultaneous Trip and Close of Old
and New Source Breakers
Advantages
- REALLY Fast - minimum dead time for bus (2 to 3 cycles)
- Least exposure to transient torque in motors if system operates
as expected
- Transfer of complete bus with minimum interrupting of process
- Rapid supervision of the phase angle just prior and just after
old source interruption is mandatory and possible with high-
speed sync-check relays
- Avoids “intentional” parallel transfer operation
Considerations – Breaker Failure Scheme is a MUST !
- Failure of old source breaker to trip back feeds generator from
new source
- AND exposes equipment to double-fed faults for which it was
not designed
- Presently, the majority of fast transfer systems are NOT
supervised by high-speed sync-check relays
Motor Bus Transfer
Conclusions
The fast transfer requires a ringdown or simulation analysis to
determine the phase angle limit at the instant of connection to
the new source.
Conclusions
The in-phase transfer offers an opportunity to synchronize a
motor bus on the first available slip cycle
- This type of transfer will enable process continuity as the
motors are still spinning and the resultant V/Hz for an in-
phase close is well below the 1.33 pu maximum
M-0272
M-0236B
Motor Bus Transfer
M-4272
Digital Motor Bus Transfer System
Uses M-3425A
Expanded I/O Platform
Motor Bus Transfer
M-4272
Digital Motor Bus Transfer System
Motor Bus Transfer
Load shedding
– Programmable Load shedding with no time delay
Motor Bus Transfer