WB (SC-2) thin fireproof coating for steel structure for outdoor use
(Former name: SC-2 thin fireproof coating for steel structure for outdoor use)
PROFILE
The brand new WB (SC-2) thin fireproof coating for steel structure for outdoor use is applicable to outdoor structures
like petroleum, chemical and oil (gas) tank support. This product plays a role of ornament and protection at ordinary times,
and the coat expands and gets thicker to form fireproof and insulation barrier during fire to prevent the heat from
transmitting to the steel substrate quickly. This product is tested by our test center and national test center for fireproof
building materials according to GB14907-002 Fireproof Coating for Steel Structure, and its physical & chemical properties
and fire resistance meet the prescribed requirements or are even better. It has been widely applied in the key fireproofing
engineering like Wuhan International Exhibition Center, Huai’an Exhibition Center, National Conference Center, Liaoning
Jinxi Oil Refining Works, Sinopec Scientific Research Office Building, Xiamen Exhibition Center.
MAIN PERFORMANCE
This product is tested by our test center and national test center for fireproof building materials according to GB14907-2002
Fireproof Coating for Steel Structure, and its physical & chemical properties and fireproof performance meet the prescribed
requirements or are even better than the indexes below:
TECHNICAL PARAMETERS
Item Technical index
State in the container Even and thick fluid after stirring
Drying time (surface drying) ≤12h
Initial dry crack resistance 1-3 cracks allowable, width≤0.5mm
Appearance and color Grey white
Bonding strength ≥0.15Mpa
Water resistance ≥24h, the coat does not wrinkle, form bubble or shed.
Hot & cold circulation resistance ≥15 times, the coat does not wrinkle, form bubble or shed.
Fire resistance Coat thickness, mm 5.5 Fire resistance rating, h 1.0
China Petroleum Engineering Co. Ltd
WB (SC-2) thin fireproof coating for steel structure for outdoor use
PAINTING
A. Antirust actions shall be taken on the surface of the steel structure, or dirt and dust shall be removed from the surface
coated with antirust paint.
B. The temperature is preferred to fall between 5 and 38℃, the relative humidity shall not be higher than 90% with good
ventilation.
C. It is preferred to use gravity (or jet) spray gun. The thickness of each layer shall not exceed 2.5mm (refer to painting
instructions for detail).
KEY POINTS
Painting is not allowed when the temperature is too low, the humidity is too high, the wind speed is higher than 5m/s
(class 4), or there is dew formed on the surface of the steel structure. This product shall be stored at a cool, dry and
ventilated place at 5-35℃ and the validity period of storage is six months.
RECOMMENDED USE
Fire resistance time (h) Thickness of dry film of coat (mm) Theoretic consumption (kg/m2)
1.5 3.1 3.03
2.0 3.4 3.32
2.5 3.9 3.81
3.0 4.8 4.69
China Petroleum Engineering Co. Ltd
Painting
Instructions
Tel: 0519-88601616
Fax: 0519-88604887
China Petroleum Engineering Co. Ltd
smooth part of the primer shall be roughened to have certain roughness and increase the adhesion between
the fireproof coat and the primer.
Treatments for Different Painting Intervals Between Antirust Primer and Fireproof Coating
Condition Treatment
Painting interval >1 month Roughen the surface gently with abrasive paper,
then paint the fireproof coating
2.2 Painting
2.2.1 Painting of antirust primer
The painting shall comply with the regulations related to the selected antirust primer.
2.2.2 Painting of fireproof coating
2.2.2.1 Preparations: The coating already prepared before delivery, whether topcoat or primer, shall be
stirred to be uniform. Generally, portable electrical stirrer is used on the site. The consistency after
preparation and stirring shall be proper, with the proper consistency, the coating will not flow, bounce or be
absorbed. Dilute with proper amount of tap water if it is too thick.
2.2.2.2 Operation
① It is preferred to use gravity (jet) spray gun (with air compressor of automatic pressure regulation
0.6~0.9m3/min, nozzle diameter 4-6mm, air pressure 0.4~0.6Mpa) to paint this coating. For partial repair or
painting in small area where conditions for spray painting are not satisfied, you can paint manually with
tools like plastering knife. The topcoat can be painted by brush painting, roller painting, spray painting or
combination of above modes. The spray gun used to paint the primer can also be used to paint the topcoat
when the nozzle is adjustable within the range of 1-3mm.
② The thickness of each layer shall not exceed 2.0mm, when it is sunny, paint by spraying every 8-24
hours. You can start to paint next layer only when the previous layer is basically dried.
China Petroleum Engineering Co. Ltd
③Topcoat can be painted upon request of ornament, but it is compulsory for outdoor use. Generally, the
topcoat is painted by spraying once or twice, make sure the color at the split joint is uniform and the primer
is completely covered. The topcoat shall be smooth rather than rough. The theoretic consumption of the
topcoat is 0.3kg/m2.
④ The thicknesses of the coats are identified according to the requirements on fire resistance time of the
coated steel structure.
Fire resistance time VS Theoretic consumption
Theoretic
Item Thickness of dry film Actual consumption
consumption
Time (mm) (㎏/㎡)
(㎏/㎡)
As appropriate, the consumption varies
1.5h 3.1 2.95
with actual thickness of film, painting
2.0h 3.3 3.15 loss, painting mode, shape and size of
component, ambient environment,
2.5h 3.8 3.60 coating distribution and otherwise,
generally, it is 1.2-1.5 times larger than
3.0h 4.9 4.60 the theoretic consumption.
2.2.2.3 Deposit may occur for the specific weights of different ingredients in the coating vary, make sure to
stir all the coating and deposits in the barrel to be uniform before painting.
2.2.2.4 If the steel structure is exposed outdoor, measures shall be adopted to prevent the steel structure from
being exposed in the rain during painting.
~ THE END ~
China Petroleum Engineering Co. Ltd
TEST REPORT
No. Gn201303927
Product name: Thin fireproof coating for steel structure for outdoor use
Test Report
No. Gn201303927
Product name Thin fireproof coating for steel structure for outdoor use
Specification and model WB (SC-2)
Applicant Jiangsu Lanling Polymer Material Co., Ltd.
Producer Jiangsu Lanling Polymer Material Co., Ltd.
Sender Jiangsu Lanling Polymer Material Co., Ltd.
Sample No. 201303927
Sampler Blank
Sampling base Blank
Sampling place Blank
Sampling date Blank
Sample quantity 100kg
Arrival date 2013-05-14
Test type By commission
Test class Blank
Test date 2013-05-14 ~ 2013-09-10
Test place Quality Inspection Center
Test basis Test outline
Test item Fire resistance
The WB (SC-2) thin fireproof coating for steel structure for outdoor use is
Lanling Polymer Material Co., Ltd. and the results are listed in the summary.
Approved by: (Signature) Reviewed by: (Signature) Prepared by: (Signature) 1 of 5 pages
China Petroleum Engineering Co. Ltd
2 of 5 pages
China Petroleum Engineering Co. Ltd
3 of 5 pages
China Petroleum Engineering Co. Ltd
201303927
Fire Resistance Test Outline of WB (SC-2) Thin Fireproof Coating for Steel Structure for Outdoor Use
(According to Hydrocarbon Time vs. Temperature Rise Curve)
Jiangsu Lanling Polymer Material Co., Ltd. entrusts China National Center for Quality Supervision and Test of Fixed
Fire-Fighting Systems and Fire-resisting Building Components to test the fire resistance of WB (SC-2) thin fireproof
coating for steel structure for outdoor use produced by this company.
1. Target: Test the fire resistance of WB (SC-2) thin fireproof coating for steel structure for outdoor use produced by
this company (according to hydrocarbon time vs. temperature rise), and the fire resistance rating shall be equal to
or higher than 2.0h.
2. Test equipment: As specified in Section 6.5.1 of GB14907-2002.
3. Size and production of specimen: Define the size of the specimen for fire resistance test and produce the same,
steel beam 6m×36B I-shaped steel, thickness of fireproof coat: 4mm.
4. Installation and loading of specimen: Subject to Section 6.5.5 of GB14907-2002.
5. Test condition:
The temperature rise curve and requirement for fire resistance test shall be subject to HC temperature rise curve of
tunnel fire resistance test in Section 5.1.2 of GA/T714-2007, the test lasts for 2h;
6. Assessment: The fire resistance of the fireproof coating for steel structure is assessed according to Section 6.5.6 in
GB14907-2002.
4 of 5 pages
China Petroleum Engineering Co. Ltd
Photo of sample:
5 of 5 pages
China Petroleum Engineering Co. Ltd
TEST REPORT
No. 2011-2388
Product name: Thin fireproof coating for steel structure for outdoor use
China National Center for Quality Supervision and Test of Fixed Fire-Fighting Systems and
Fire-resisting Building Components
China Petroleum Engineering Co. Ltd
Test Report
China National Center for Quality Supervision and Test of Fixed Fire-Fighting Systems and
Fire-resisting Building Components
No. 2011-2388
Product name Thin fireproof coating for steel structure for outdoor use
Specification and model WB (SC-2)
Brand Lanling
Applicant Conformity assessment center of fire-fighting products of MPS
Producer Jiangsu Lanling Polymer Material Co., Ltd.
Subject Jiangsu Lanling Polymer Material Co., Ltd.
Sampler Plant condition inspection team
Sampling place Production workshop
Sampling base 400kg
Sampling date 2011-03-12
Sample sent by Liu Yeqing
Sending date 2011-04-11
Sample quantity 200kg
Sample No. 2011-2388
Test type Type test
Test basis GB14907-2002
Test class Blank
Test item All
Test date 2011-04-20 ~ 2011-11-03
Test place In this center
The WB (SC-2) thin fireproof coating for steel structure for outdoor use
(thickness of coat: 4.8mm, fire resistance test duration: 3.0h, fire resistance
acceptable) sent by Jiangsu Lanling Polymer Material Co., Ltd. is tested in
accordance with GB14907-2002 Fireproof Coating for Steel Structure and is
determined as acceptable.
Conclusion (The following is left blank intentionally)
(Seal special for test)
Issued on: November 7, 2011
Seal special for test, China National Center for Quality Supervision and Test
of Fixed Fire-Fighting Systems and Fire-resisting Building Components
(Seal)
Fire resistance test: Put the I36b steel beam protected by 4.8mm thick WB
Remarks (SC-2) coating on the test furnace, distribute the load 128kN uniformly, and
do the test according to GB14907-2002.
Approved by: (Signature) Reviewed by: (Signature) Prepared by: (Signature) 1 of 5 pages
China Petroleum Engineering Co. Ltd
2 of 5 pages
China Petroleum Engineering Co. Ltd
3 of 5 pages
China Petroleum Engineering Co. Ltd
4 of 5 pages
China Petroleum Engineering Co. Ltd
Photo of sample:
5 of 5 pages
China Petroleum Engineering Co. Ltd
WCB (SF) Ultra-thin fireproof coating for steel structure for outdoor use
PAINTING
A. Antirust paint shall be applied on the surface of the steel structure, or dirt and dust shall be removed from the surface
coated with antirust paint.
B. Stir completely to be uniform before painting, add proper amount of diluter (not larger than 5%) to facilitate the
painting if the coating is too thick.
C. The fireproof coating shall be painted by layer. The thickness of the dry film of the first layer shall not exceed 200μm,
and the thickness of the dry film of the subsequent layers shall not exceed 300μm. The interval of each layer shall be 24
hours (23±2℃) (refer to painting instructions for detail).
D. Preferred ambient environment: temperature 0-35℃, relative humidity≤85%.
E. The thickness of the dry film of the topcoat for steel structure is about 40μm, and generally two layers of the topcoat are
required for the steel structure for outdoor use.
KEY POINTS
This product belongs to solvent-type coating and ordinary dangerous product, it shall be transported according to
regulations related to ordinary dangerous products. This product shall be stored in the room at 5-35℃, the validity period
for storage is six months, but the product can also be used beyond the period where the test reveals that it meets related
requirements.
RECOMMENDED USE
Fire resistance time (h) Thickness of dry film (mm) Theoretic consumption (kg/m2)
1.0 0.99 1.66
1.5 1.64 2.75
2.0 2.11 3.6
1.5 (Aromatic
2.33 3.97
hydrocarbon)
China Petroleum Engineering Co. Ltd
Painting
Instructions
Tel: 0519-88601616
Fax: 0519-88604887
E-mail: Lanlingpai@163.com
China Petroleum Engineering Co. Ltd
2.2.2.3 If viscosity is too high and painting is affected, diluter less than 5% of the total amount can be added;
for high-pressure airless spray painting, the diluter shall be lower than 15% of the total amount.
2.2.2.4 If the steel structure is exposed outdoor, measures shall be adopted to prevent the steel structure from
being exposed in the rain during painting.
2.2.3 Painting of topcoat
After main fireproof material reaches the required thickness, polish the rough position on the coat to ensure
its ornament, and then start painting the topcoat. The painting interval between the protective topcoat and the
fireproof coating layer is 24 hours (23±2℃) and can be adjusted in accordance with ambient environment
(temperature and humidity) and drying status of main material. The painting parameters of the topcoat are as
follows:
Ambient Thickness of dry
Painting mode Painting layer(s)
environment film (μm)
Brush painting, roller
Outdoor 2 80~100
painting, spray painting
China Petroleum Engineering Co. Ltd
TEST REPORT
No. 2011-2389
Product name: Ultra-thin fireproof coating for steel structure for outdoor use
China National Center for Quality Supervision and Test of Fixed Fire-Fighting Systems and
Fire-resisting Building Components
China Petroleum Engineering Co. Ltd
Test Report
China National Center for Quality Supervision and Test of Fixed Fire-Fighting Systems and
Fire-resisting Building Components
No. 2011-2389
Product name Ultra-thin fireproof coating for steel structure for outdoor use
Specification and model WCB (SF)
Brand Lanling
Applicant Conformity assessment center of firefighting products of MPS
Producer Jiangsu Lanling Polymer Material Co., Ltd.
Subject Jiangsu Lanling Polymer Material Co., Ltd.
Sampler Plant condition inspection team
Sampling place Production workshop
Sampling base 400kg
Sampling date 2011-03-12
Sample sent by Liu Yeqing
Sending date 2011-04-11
Sample quantity 100kg
Type No. 2011-2389
Test type Type test
Test basis GB14907-2002
Test class Blank
Test item All
Test date 2011-04-20 ~ 2011-11-03
Test place In this center
The WCB (SF) ultra-thin fireproof coating for steel structure for outdoor use
(thickness of coat: 2.11mm, fire resistance test duration: 2.0h, fire resistance
acceptable) sent by Jiangsu Lanling Polymer Material Co., Ltd. is tested in
accordance with GB14907-2002 Fireproof Coating for Steel Structure and is
determined as acceptable.
Conclusion (The following is left blank intentionally)
(Seal special for test)
Issued on: November 7, 2011
Seal special for test, China National Center for Quality Supervision and Test
of Fixed Fire-Fighting Systems and Fire-resisting Building Components
(Seal)
Fire resistance test: Put the I36b steel beam protected by 2.11mm thick WCB
Remarks (SF) coating on the test furnace, distribute the load 128kN uniformly, and do
the test according to GB14907-2002.
Approved by: (Signature) Reviewed by: (Signature) Prepared by: (Signature) 1 of 5 pages
China Petroleum Engineering Co. Ltd
2 of 5 pages
China Petroleum Engineering Co. Ltd
3 of 5 pages
China Petroleum Engineering Co. Ltd
4 of 5 pages
China Petroleum Engineering Co. Ltd
Photo of sample:
5 of 5 pages