Professional Documents
Culture Documents
Building Design Reviewer
Building Design Reviewer
CLASSES OF FIRE:
Class A – fires involving ORDINARY COMBUSTIBLE MATERIALS (wood, cloth, rubber,
and plastics)
Class B – fires involving FLAMMABLE LIQUIDS and GASES
Class C – fires involving ENERGIZED ELECTRICAL EQUIPMENT
Class D – fires involving COMBUSTIBLE MATERIALS (METALS) *Sodium, Magnesium,
Potassium
Class K – fires in cooking appliances (Kitchen) involving COMBUSTIBLE COOKING
MEDIA (i.e. vegetable or animal oils and fats)
B. Active Fire Protection Systems – consist of those that take an ADDITIONAL ACTION to
activate in the event of a fire.
o Smoke Detectors – sensing devices which sends signals to alarm panels when
activated.
o Smoke Alarms – sensing devices which alarms when activated.
Sprinker Systems – thermosensitive devices designed to react at predetermined
temperatures by releasing a STREAM OF WATER and distributing it in SPECIFIED
PATTERNS
o Wet Pipe System
o Dry Pipe System
o Preaction System
o Deluge System
FIRE SUPRESSION SYSTEMS
o Extinguishment Mechanisms
o Fire Suppression Agents
Aqueous Agents (i.e. water and fire-fighting foam)
Nonaqueous Agents (for materials which water would react i.e. electrical
systems)
o Cooling: Heat Reduction
o Smothering: Oxygen Deprivation
o Fuel Removal
Fire Alarm Signals
o Manual Fire Alarm
o Automatic Fire Alarm
Automatics Suppression Systems
o Sprinkler System Components
Sprinkler (head)
Pipe and Tube
System valves
FDAS
o Fire Detection and Alarm Systems
Fire Detection
o Types of Initiating Devices
Spot-Type
Line-Type
Video
MIDTERM EXAM
Egress
o Minimum width = 915 mm
FDAS – fire detection and alarm system
FALAR 1 – been designed in accordance with the fire code provisions
FALAR 2 – been constructed in accordance with the fire code provisions
Class K – class of fire (vegetable oil)
FALAR 3 – periodically been maintained
RA 9514 – Presidential decree 1185
SIX STORY FIRE EXITS (72 occupants) – ‘2’
FIRE PROTECTION
o Passive
Compartmentation
Protection of Structural members
o Active
FDAS
Fire Alarms
Sprinkler – thermosensitive devices – designed to react at predetermined temperatures
by automatically releasing a stream of water
FALAR 1:
o Basis of designs for exits and egress
FALAR 2
o Egress Calculation
o Testing and Commissioning, and acceptance data of FDAS
FALAR 3
o Number of Active Exits
o Testing and Maintenance records done in the components of FDAS
BFP = bureau of fire protection
Fire- active principle
‘exits’ sufficient to permit the fast
Fire Safety Checklist
Fire Safety Evaluation Clearance
Flame Spread Rating
o Class A – 0 - 25
o Class B – 26 – 75
o Class C – 76 – 200
o Class D – 201 - 500
o Class E - over 500
ELECTRICAL CIRCUITS
Electric Circuit– the complete path traversed by an electric current
o the entire house wiring installation
Branch Circuit – the circuit conductors between the final over-current protective device
and the outlets.
Pic
pic
o Source of voltage
o Wiring
o Load
Service Entrance– the portion of the supply conductors which EXTENDS from the
street main duct to the SWITCHBOARD of the building supply
o Overhead service
o Underground service
Pic
Pic
Electric Meter – pic
Feeder – pic, pic
Main Feeder
TW – Thermoplastic Waterproof
THWN – Thermoplastic Heat and Water-resistant Nylon-coated
THHN – Thermoplastic High Heat-resistant Nylon-coated
AWG – American wire gauge
o Watts
o Amperes
o Wire
o Pipe
The smallest diameter of a CONDUIT PIPE:
o That could accommodate up to 3 PIECES of #14 TW wire
(2.0mm^2) is 13 mm diameter
o Determine the size or rating of the over-current protective device using TABLE 4-
1
RANGE LOAD
o Determine the load capacity of the range (appliance rating)
By inspection – the range load is at 8.0kW (8000 Watts)
8000 watts/ 230 volts = 34.78 Amperes
o Apply the demand load factor
The ratio of the Max. Load in a given time period to the Max. Possible
Load
The Demand Factor is either EQUAL to or LESS THAN 1
o TABLE 4-6 DEMAND LOAD FOR HOUSELOD APPLIANCES
34.78 amperes x 80% df = 27.82 amperes
for a 27.82 amperes – use 2 pieces 8.0mm^2 TW copper wire having an
ampacity of 40 amperes
The SMALLEST DIAMETER OF A CONDUIT PIPE – that could
accommodate up to 2 pieces of #8 TW Wire (8.0mm^2) is 20 mm
diameter
Since the amperage requires is 27.82 amperes, use 40 AMPERES over-
current protective device
The 8.0mm^2 TW Copper Wire has 40 AMPERES CAPACITY, hence
80% of 40 amps is 32 amperes which doesn’t exceed the required
amperage of 27.82 amperes.
The over-current protective device to be used has 40 amperes capacity,
hence 80% of 40 amps = 32 amps, which doesn’t exceed the required
amperage of 27.82 amperes
The wire and the OVER-CURRENT PROTECTIVE DEVICE used is
sufficient enough to carry the load requirement.
o CIRCUIT 6
Has 1 water heater at 2.5 kW
Total load is 2500 watts
Total amperes is 10.86 amperes
AIR CONDITIONER LOAD
o Determine the LOAD CAPACITY of the air conditioner unit (appliance rating)
By inspection the air conditioner is at 1.5 hp
1.5 hp x 746 watts/hp = 1119 watts
1119 watts / 230 volts = 4.86 amperes
Branch circuit conductor supplying a motor shall have an ampacity not
less than 125% of the full load current.
4.86 amperes x 125% = 6.07 amperes
For a 6.07 amperes – use 2 pieces 3.5mm^2 TWCopper Wire having an
ampacity of 20 amperes
The Smallest diameter of a conduit pipe that could accommodate up to 2
pieces of #12 TW wire (3.5 mm^2) is 13 mm diameter.
“Ampacity for the branch circuit protection for a single motor shall be
increased to 250% of the full load current
4.86 amperes x 250% = 12.15 amperes
Since the amperage required is increased to 12.15 amperes, use 30
amperes over-current protective device.
o CIRCUIT 8 has 1 aircon unit at 1.5hp
o Total load is 1119 watts
o Total amperes is 4.86 amperes
o Increasing the load by 125%, 6.07 amperes, the size of wire is 3.5mm^2TW.
o Size of Conduit is 13mm diameter
o Increasing the load by 250%, 12.15 amps, the size for the over-current
protection is 20 amperes.
SERVICE ENTRANCE
Determine the total current load of ALL CIRCUITS IN THE BLDG. (EXCLUDE Air-con
loads)
o Lighting Loads
Circuit 1 – 1000 watts
Circuit 2 – 900 watts
o Small Appliance Loads
Circuit 3 – 2160 watts
Circuit 4 – 2160 watts
o Range Load
Circuit 5 – 8000 watts
o Water Heater Load
Circuit 6 – 2500 watts
Apply demand factor for a dwelling unit
o TOTAL CURRENT LOAD – 16720 watts
o Apply 100% DF for the first 10 kW Load
o Apply 40% for the remaining load in excess of 10000 watts
o 16720 – 10000 watts = 6720 watts
o 6720 watts x 40% = 2688 watts
2 units at 1119 watts each = 2238 watts
2238 watts x 100% = 2238 watts
o TOTAL REQUIRED CURRENT LOAD
Initial 10kW Load – 10000
Excess of 10kW Load – 2688
Air conditioner Load – 2238
TOTAL = 14926 watts
CALCULATE THE TOTAL CONNECTED LOAD PLUS 25% OF THE LARGEST
MOTOR LOAD
o 14926 watts + (25% of 1119 watts) = 15205x75 watts
o 15205.75 watts / 230 volts = 66.11 amperes
Determine the size of main feeder and the neutral line
o For a 63.37 amperes – use 2 pieces 38mm^2 TW copper wire having an
ampacity of 100 amperes.
o “If the computed load exceeds 10000 watts, the conductor and the overcurrent
protection shall be rated not less than 100 amperes.
o “Neutral conductors shall have an ampacity of not less than 70% of the
ungrounded (live wire) conductor or 2 trade size smaller than the ungrounded
conductor/
o Less than 70% of the ampacity of the conductor ware
At 70% of the 100 amperes minimum ampacity for main feeders – 70
amperes
Use 2 pieces 22mm^2 TW COPPER WIRE.
DETERMINE THE SIZE OF THE CONDuit PIPE using TABLE 2-9
o The smalles diameter of a conduit pipe – could accommodate up to 2 pcs of #3
TW wire (38 mm^2) and 1 pc #5 TW wire (22mm^2)is 32 mm diameter.
Determine the size or rating of the over-current protective device (main breaker) using
Table 4-1
o “If the computed load exceeds 10000 watts, the conductor and the overcurrent
protection shall be rated not less than 100 amperes