GENERAL

NOTES:
1. Work to figured dimensions only.
2. All dimensions are in millimetres unless otherwise stated.
Godown 04

Godown 01 Godown 02 Godown 03 Godown 04 3. All socket outlets shall be mounted at a height of 450mm
a.f.f.l. unless otherwise stated.
3. All access control card and or biometric reader outlets shall
be mounted at a height of 1450mm a.f.f.l. unless otherwise
stated.
4. All distribution boards and or consumer units shall be
GG mounted at a height of 1800mm a.f.f.l. unless otherwise stated.
5. All ring circuits shall have 4x2.5mm2/ pvc sc + 2x2.5mm2/
e.c.c cables unless otherwise specified.
6. All radial circuits shall have 2x2.5mm2/ pvc sc + 2.5mm2/
e.c.c cables unless otherwise specified.
7. All DP switch circuits shall have 2x4.0mm2/ pvc sc +
4.0mm2/ e.c.c cables unless otherwise specified.
4. All power points for Mechanical Engineering Services are

6,000
provisional, and shall be coordinated with respective
contractors for the final location unless otherwise specified.
5. All socket outlet conduits should be 25mm dia. minimum
unless otherwise specified.
6. All signal conduits should be 25mm dia. minimum unless
otherwise specified.
7. Cable trays shall have supporting brackets located at not
more than 3m intervals or and change of direction, transition
FF and junction.
8. Specialized systems shall be by others, however, the
Electrical Sub - Contractor shall provide the necessary
infrastructure in way of raceways i.e Conduits, trunking and
Cable trays.
9. Specialized Sub - Contractors shall provide all cabling,
termination outlets and any other accessories to complete the

6,000
installation as called for.
10. Specialized Sub - Contractors shall mark the location of
power points or any other services required to be provided by
electrical sub- contractor, however, the Engineer shall approve
this provision on site.
11. Security system end equipment i.e. Cameras, Access control
readers and magnetic contacts shall be provided by the Security
systems Sub - Contractor.
EE 12. ICT end equipment i.e. Face plate, Switches, Data Cabinets
and associated Cabling shall be provided by the ICT systems
Sub - Contractor.
13. Nurse call end equipment i.e. call points, dome lights,
master stations and associated Cabling shall be provided by the
Nurse Call systems Sub - Contractor.
14. All Systems shall comply and confirm to the cause and
6,000

effects matrix that will be generated by Engineer in respect to


the installed systems.
void open to void open to void open to void open to 15. All sub-contractors shall provide with working drawings
outlining the entire or and part of the system on site at all time.
Godown Type 1 below Godown Type 1 below Godown Type 1 below Godown Type 1 below

DD
6,000

C
C REV. DESCRIPTION DATE BY

CLIENT:

Java House, nairobi


6,000

CLIENT APPROVAL

SIGNATURE DATE
200

BB ARCHITECTS:
300

ML ML ML
ML
900

LE LE
Academy & Resource LE LE S LE LE S ML

Centre-073 S S lockers S S
1,200

? ? ? Microbiology Lab -106 ?


N
lockers
(Cer. Tiles) (Cer. Tiles)
N
N
ML

urinal
N
6,000

200

Male Changing
N N
Female Changing
S store store S
RoomsS 3 -103
(Cer. Tiles)
store store Rooms 3 -104
(Cer. Tiles)
screed ff screed ff screed ff screed ff ARCHITECTS APPROVAL

lockers
B2 B2 B2 B2
3,300

lockers
? ? S S ? ? S S SIGNATURE DATE
N N N
N N N

ARCHITECTS:
bench

AA
700 1,000

R
6.100 Existing Roof
Gutter above
Existing Roof Existing Roof
Gutter above Gutter above
Luminaire Legend

Symbol Description
01
01-2 02
02 03
03 04
01
01
04 05
05 06
06 07
07 08
08 09
01
01-3
09 10
10 11
11 12
12 ARCHITECTS APPROVAL
Type (J4) 40W, 600x600mm LED Panel Luminaire
SIGNATURE DATE
Type (J4E) as J4 but incorporating Emergency kit

FIRST FLOOR PLAN BLOCKS1-4 Type (CL) 38W, 1200x300mm LED Panel Luminaire
200
29,800

200

200

200 200 200 200 200


200 1,250
1,250

200 600
200

250
2,400

250

200 200 1,650 100 2,025 200


100 900 100 900 100 900

1,275 200 900


550 200 1,550 200
200

200

100
5,800

5,800

5,800

5,800
900

100
3,200

3,200
900

200 5,050 100 1,650 200


100

200 6,800 200 5,050 200 5,050 200 6,800 200 5,050 200 900
900
200

200

200

200

200

200

200
200

Type (CLE) as CL but incorporating Emergency kit

B2
Type (B2) 38W, 1200mm, LED Linear Batten Luminaire
GEOMAX CONSULTING ENGINEERS
B2E
Type (B2E) as B2 but incorporating Emergency kit

FIRST FLOOR - PART A ST. HELLEN LANE OFF LANG'ATA ROAD, P.O. BOX
53748 - 00200 NAIROBI, TEL: +254 20 57 34 30

1
R2
Type (R2) 58W, 1500mm, IP67, LED Linear Luminaire MOB: +254 722 2072 36 EMAIL:
info@geomaxke.com WEBSITE: www.geomaxke.com
R2E
Type (R2E) as R2 but incorporating Emergency kit 1 : 100
DATE: SCALE: DESIGNED: DRAWN: CHECKED:
L
Type (L) 240V Polycarbonate IP54 18W LED Bulkhead
Issue Date 1 : 100, Designer Author Checker
LE
Type (LE) as J4 but incorporating Emergency kit REVIT FILE WARNING
DON'T SCALE FROM DRAWING. USE
D1
Type (D1) 20W LED Recessed Dimmable Downlighter Luminaire GATEWAY THE GIVEN DIMENSIONS ONLY.

D1E
Type (D1E) as D1 but incorporating Emergency kit PROJECT:
Type (N) 12W low profile luminaire fitted with Microwave sensor
Foodscape Central Processing Unit
N

ML Type (ML) 240V IP44 Twin Frosted Window LED Mirror Light
LIGHT SWITCHING ACCESSORIES LEGEND
G Type (G) 30W LED External Wall mounted luminaire
Symbol Description
X Type (X) 18W LED surface mounted bulkhead luminaire fitted with microwive CONSTRUCTION ISSUE
sensor 10A 1 Gang, 1 Way Light Switch @ 1350mm AFFL
DRAWING REFERENCE AND CODING
FIRE DETECTION & ALARM ACCESSORIES LEGEND TITLE
W
Type (W) 15W Fixed Decorative Up/Down wall light complete with LED KEY
Photoelectric type Analogue Addressable smoke detector 10A 1 Gang, 2 Way Light Switch @ 1350mm AFFL L (--) 01 DRAWING
lamp S
mounted on ceiling complete with fire resistance cable
Photoelectric type Analogue Addressable heat detector 10A 2 Gang, 2 Way Light Switch @ 1350mm AFFL
NUMBER
SERVICES FIRST FLOOR - PART A - LIGHTING, FIRE
H CODE
Type 240V AL wall mounted LED Emergency Exit Sign mounted on ceiling complete with fire resistance cable
Type Analogue Addressable Fire Flash Light mounted on wall L (60)
LAYOUT
CODE
-ELECTRICAL SCHEDULES
DETECTION AND ALARM SYSTEM
Type 240V AL ceiling mounted two sided LED Emergency Exit Sign @ 2100mm AFFL complete with fire resistance cable
10A 1 Gang, 2 Way Dimmer Light Switch @ 1350mm AFFL L (61) -ELECTRICAL SUPPLY LAYOUT
DD

Type Analogue Addressable Fire Sounder mounted on wall L (62) -POWER LAYOUT
@ 2100mm AFFL complete with fire resistance cable 10A 2 Gang, 2 Way Dimmer Light Switch @ 1350mm AFFL L (63) -LIGHTING LAYOUT
Light Motion sensor (occupancy and vacancy sensor). L (64) - STRUCTURED CABLING LAYOUT
D

Type Analogue Addressable Fire Break Glass mounted on


L (65) -SECURITY SYSTEMS LAYOUT
wall @ 1450mm AFFL complete with fire resistance cable
L (66) -NURSE CALL SYSTEMS LAYOUT
PROJECT CODE: DRAWING NO: REV
L (67) -LIGHTING PROTECTION LAYOUT
J1910 L (63) - 09
L - Lighting Luminaire - Min F - Fire Detection & Alarm Accessories
S - Switching Accessories
L (68) -FIRE DETECTION & ALARM LAYOUT
L (69) -P.A. AND CLOCK SYSTEM LAYOUT

1 : 100 1 : 100 1 : 100