Professional Documents
Culture Documents
Ring Main Unit Type SF6, Gas-Insulated, 8DJH: Siemens
Ring Main Unit Type SF6, Gas-Insulated, 8DJH: Siemens
Contents
1. What is meant of RMU
2. Where used
3. Types of RMU
4. Advanteges of 8DJH
5. Technical
6. Pricing
2. Where used
Used for power distribution in secondary distribution
systems, such as:
· Substations, customer transfer substations, distribution
substations and public utilities.
· Industrial plants
3. Types of RMU
Gas\Air
GIS
Insulated Air Insulated
(8DJH)
(Simosec)
SF6 gas
Busbars Air insulated Air insulated
Insulated
Switching
SF6 SF6 Air
devices
Rated
current of 630A Up to 1250A 630A
busbar
Rated
current of Up to 630A Up to 1250A Up to 630A
feeder
Cost High Very high Low
4. Advantages of 8DJH
1.Service life: Under normal operating conditions,
the expected service life is at least 35 years,
probably 40 to 50 years
2.Personal safety
· Safe-to-touch.
· HV HRC fuses and cable sealing ends are only
accessible when outgoing feeders are earthed
· Operation only possible when enclosure is closed
· Logical mechanical interlocking
· Capacitive voltage detecting system
· Feeder earthing via make-proof earthing switches.
3.Maintenance-free design
4.Maximum supply reliability
5.Installation, operation, extension and replacement
without SF6 gas work
6.Reduced operating costs
7.Cost-efficient investment.
8.Type and routine-tested
9.Small dimensions
10. Standardized
5. Technical
5.3. Typicals
Typical Description
K Cable feeder
K(E) Cable feeder with make-proof earthing switch
R Ring main feeder
T Transformer feeder
L Circuit breaker feeder
M Metering panel
S Bus sectionalizer panel with switch disconnector
H Bus sectionalizer panel with switch disconnector / fuse
combination
V Bus sectionalizer panel with circuit breaker
B.Vacuum circuit-breaker
Ø Types of Vacuum circuit beaker
I. Type 1.1 with three-position disconnector
5.8. Operation