Substation 152: panel: J52-152-AVR-001 PUNCH LIST

NEED CLARIFICATION BELOW PUNCH LIST

1. We need clarify if the selector switch for the LOCAL/REMOTE mode is sufficient. If SCADA mode
required, the selector switch replace to 3 position switch.
2. AVR Relay faulty (watch dag) and emergency stop signals not available in the scheme. Need to be
adding this signal. Modification required
3. Below all signals should be go to PSA, but interfacing not available from AVR Panel to PSA Panel. Need
clarification that who will do this interfacing. SEPCO whether HITHACHI
1. AVR Control supply MCB trip
2. VT MCB Trip
3. Heater and Lighting AC MCB Trip
4. AVR relay Faulty
5. Emergency stop