Professional Documents
Culture Documents
Realization of A Fault-Tolerant Tunnel Lighting System With S7-400H
Realization of A Fault-Tolerant Tunnel Lighting System With S7-400H
Realization of a Fault-
Tolerant Tunnel Lighting
System With S7-400H
SIMATIC H-System S7-400H
http://support.automation.siemens.com/WW/view/81066268
Warranty and liability
Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These application examples do not
relieve you of the responsibility to use safe practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time without prior notice.
If there are any deviations between the recommendations provided in these
application examples and other Siemens publications – e.g. Catalogs – the
contents of the other documents have priority.
We do not accept any liability for the information contained in this document.
Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
Copyright ã Siemens AG 2013 All rights reserved
not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”). The damages for a breach of a substantial
contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Caution
The functions and solutions described in this article confine themselves to the
realization of the automation task predominantly. Please take into account
furthermore that corresponding protective measures have to be taken up in the
context of Industrial Security when connecting your equipment to other parts of the
plant, the enterprise network or the Internet. Further information can be found
under the Item-ID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404
Table of contents
Warranty and liability ............................................................................................... 2
1 Task................................................................................................................. 4
2 Solution........................................................................................................... 6
2.1 Overview ........................................................................................... 6
2.2 Description of the core functionality.................................................... 8
2.2.1 Function block FB 100 “Tunnel_Lighting_System”.............................. 8
2.2.2 User interface for visualization on the local HMI panel...................... 10
2.3 Hardware and software components ................................................ 13
3 Realization of “Fault Tolerance” .................................................................. 15
3.1 The automation system S7–400H .................................................... 15
3.1.1 Description ...................................................................................... 15
3.1.2 Structure of the H-Systems .............................................................. 15
3.1.3 Function principle ............................................................................ 17
3.2 Distributed I/Os................................................................................ 17
3.2.1 Description ...................................................................................... 17
3.2.2 Redundant I/O structure................................................................... 17
3.3 Redundant connections ................................................................... 18
4 Program Blocks for Tunnel Lighting Control .............................................. 19
Copyright ã Siemens AG 2013 All rights reserved
1 Task
Introduction
The safe operation of a tunnel not only requires security systems (e.g. fire
protection systems), but also systems for ventilation, lighting and traffic sign
control.
For this reason, these systems should also be integrated in the tunnel security
concept and protected against damage.
Today, the use of redundant systems for tunnel operation is a mandatory
requirement, so as to ensure a high level of security and availability. The
complexity of fault-tolerant systems is alleviated through the use of modular
structures.
The individual modules – in this example the systems for safe tunnel operation –
can be easily separated from each other.
The example presented here focuses on the “tunnel lighting system” as a separate
module.
The lighting system is not merely important for traffic safety, it is also closely
connected with the smooth flow of traffic. A high degree of illumination quality
increases the driving safety and driving pleasure and thus conduces to a harmonic
traffic flow.
Copyright ã Siemens AG 2013 All rights reserved
Light sensor
Control room 2
level 1
Control room 1 level 2
level 3
2 Solution
2.1 Overview
Schematic layout
The following figure provides a schematic overview of the solution and its most
important components:
Figure 2-1
Control room 1 Control room 2
FB 100 S7-400H HMI-Panel HMI-Panel S7-400H FB 100
Tunnel_Lighting_ Tunnel_Lighting_
System System
synchronisation
Industrial Ethernet
Copyright ã Siemens AG 2013 All rights reserved
PROFIBUS DP
ET 200M ET 200M
Structure
Each control room is equipped with a fault-tolerant system (CPU 416-5H) including
a distributed I/O system (ET200M) and an HMI panel.
The ET 200M is a redundant system (two head modules) which is additionally
provided with an analog input module and a digital output module.
The HMI panel (MP 370 Touch) is used for visualization and operator control.
Network integration is laid out as follows:
· The S7-400H stations and the HMI panel are connected via Industrial Ethernet
· In control room 1: Connection of the CPU with always the first head module of
the ET 200M stations via PROFIBUS DP.
· In control room 2: Connection of the CPU with always the second head module
of the ET 200M stations via PROFIBUS DP.
Note In our test setup, the use of an analog module for connection with the outside
sensor has been omitted, as the light intensity is entered manually in this
example application.
Advantages
The solution presented here offers the following advantages:
Assumed knowledge
The following knowledge is assumed:
· Basic experience with STEP 7
Copyright ã Siemens AG 2013 All rights reserved
Overview
The core element of the automation task is the function block
“Tunnel_Lighting_System”.
This block is used to control the tunnel lighting for the entrance, interior and exit
zones in automatic or manual mode.
The function principle of the block depends on the selected mode of operation.
The functional interaction of the required light levels between entrance, exit and
interior light are listed in the following table:
Table 2-3
Time of day Expected light intensity Level
00:00 to 06:00 Set_Val_Lev1 - Set_VAL_Lev2 Level 1 or nightlight,
20:00 to 23:59 respectively
6:00 to 8:00 Set_Val_Lev2 - Set_VAL_Lev3 Level 2 or evening and
18:00 to 20:00 morning twilight,
respectively
08:00 to 18:00 Set_Val_Lev3 -Set_Sensor_MAX_VAL Level 3 or daylight,
respectively
Each control room is equipped with a local HMI panel. The user interface for
visualization on the panels is identical.
Visualization on the local HMI panels
Figure 2-2
Copyright ã Siemens AG 2013 All rights reserved
Note You may also use similar products which deviate from the list above. In this
case, please note that changes to the sample code (e.g. different addresses)
may become necessary.
Please also note that a pairwise and redundant installation requires the use of
Note
modules of the same product and firmware versions.
Software components
Table 2-7
Component Qty. Order number Note
SIMATIC STEP7 V5.5 +SP3 1 6ES7810-5CC11- Floating license for 1user
0YC5..
SIMATIC WinCCFlexible+ RUNTIME 1 6AV6612-0AA51-3CA5 Floating license for 1user
2008 SP3
Note Functionality and application of the blocks are described in the associated online
help.
Copyright ã Siemens AG 2013 All rights reserved
Further libraries
In addition, the following libraries from the SIMATIC library are required for this
example:
· “Redundant IO CGP V5.X“: Blocks for channel group granular redundancy
· “Redundant IO CGP V4.X”: Blocks for channel granular redundancy
· “Redundant IO MGP V3.X”: Blocks for module granular redundancy
These libraries can be opened in the SIMATIC Manager by selecting "File > Open
> Libraries"
The requirements on tunnel lighting control are fulfilled with the help of a
fault-tolerant system.
The automation system S7–400H satisfies the high demands on availability,
intelligence and decentralization placed on modern automation systems.
Furthermore, it also provides all functions required for the acquisition and
preparation of process data, including functions for the control, management and
monitoring of plants and aggregates.
Overview
In order to ensure the reliable availability of the S7–400H system even if an error
occurs, it is laid out in a redundant structure (master and standby station). All
essential components, such as the central processing unit (CPU), the power supply
Copyright ã Siemens AG 2013 All rights reserved
module and the hardware for connection between the two CPUs are doubly
present.
Usually, the master and standby stations are arranged in a centralized structure.
Figure 3-1
Power supply
The H-CPUs are supplied by a power supply unit from the standard system range
of the S7-400. To increase the availability of the power supply, you may also use
two redundant power supply units for each subsystem.
Copyright ã Siemens AG 2013 All rights reserved
Synchronization modules
The synchronization modules are the interlink between the two CPUs. They are
installed in the CPUs and interconnected by means of fiber-optic cables.
Figure 3-2
Fiber-optic cables
The fiber-optic cables are used to interconnect the synchronization modules for the
redundant link between the two CPUs, whereby the upper and lower
synchronization modules are connected pairwise.
The add-on modules in the distributed I/O device ET200M, also referred to as
interface modules (IM), are used as a PROFIBUS DP interface. In a redundant I/O
structure, two interface modules (IMs) per ET 200M station are required and both
must be set to the same bus address.
This is to ensure bumpless continuation by the passive module, if the active add-on
module fails during operation. The active interface is indicated by the LED ACT of
the corresponding add-on module.
Connection of the redundant I/Os to the H-system is effected in the connected DP
slave mode. This means that both the master station and the stand-by station are
connected with the two ET200M stations.
Figure 3-3
The use of redundant I/O modules ensures that the connected I/Os remain
available for the process, even if the following situations arise:
· Failure of a signal module
· Failure of an interface module
· Failure of the ET200M station
· Failure of an H-CPU
· Failure of a PROFIBUS-DP segment
SFC 1,
SFC 51
FB 1
„H-SYS_STATUS“
DB 101
„SYS_DATA_HMI“
SFC 2, 3,4
FC 6, 8, 105
OB 1 FB 100
„Tunnel_Lighting_System“
Copyright ã Siemens AG 2013 All rights reserved
DB 102
„HMI_CONTROLLER“
DATE#2089-12-31.
FC 8 The function FC 8 is used to extract the data format FB100
TIME_OF_DAY from the DATE_AND_TIME format. “Tunnel_Lighting_System“
FC 105 The “Scale Values” function is used to convert integral FB100
values into real numeric values. “Tunnel_Lighting_System“
The sub-list identified by the SZL-ID (system status list ID) W#16#0071 provides
information on the current status of the H-system. 16 bytes can be read out in total.
The data record is structured as follows:
Table 4-3
Copyright ã Siemens AG 2013 All rights reserved
W#16#000B: LINK-UP
W#16#000C: UPDATE
W#16#000D: DEFECTIVE
W#16#000E: SELFTEST
W#16#000F: NO POWER
bz_cpu_1 2 bytes Mode of CPU in rack 1
(see values for bz_cpu_0)
bz_cpu_2 2 bytes Reserved
cpu_valid 1 byte Validity of variables bz_cpu_0 and bz_cpu_1
B#16#01: bz_cpu_0 valid
B#16#02: bz_cpu_1 valid
B#16#03: bz_cpu_0 and bz_cpu_1 valid
hsync_f 1 byte Status of connection quality
(valid only, if b bit 0 is set in mwstat2)
Bit 0: Fiber optics connection quality of the synchronization
modules in the upper receptacle is limited
Bit 1: Fiber optics connection quality of the synchronization
modules in the lower receptacle is limited
Bit 2-7: 0
The figure and table below show the call interface of the user function block
“H-SYS_STATUS” (FB 1).
Figure 4-2
Copyright ã Siemens AG 2013 All rights reserved
Input parameters
The input parameters have the following meanings:
Table 4-4
Parameter Data type Note
=1: possible
(Bit 0 from mwstat2 of SZL data record)
bz_cpu_0 WORD Operating status of CPU in rack 0
(bz_cpu_0 of SZL data record)
bz_cpu_1 WORD Operating status of CPU in rack 1
(bz_cpu_1 of SZL data record)
Output parameters
The output parameters have the following meanings:
Table 4-5
Parameter Data type Note
Note The light intensity measured by the outside sensor is defined manually at the
“Tunnel_Lighting_System” block (FB 100).
The selection of the light level for the entrance and exit zones depends on the light
intensity measured outside the tunnel by the light sensor.
Table 4-7
Light intensity measured by the outside sensor Level
in Cd (lm/ser)
Set_Val_Lev1 - Set_Val_Lev2 Level 1
Set_Val_Lev2 - Set_Val_Lev3 Level 2
Set_Val_Lev3 - Set_Sensor_MAX_VAL Level 3
Weather-induced influences or similar reasons may cause variations in the results
of light intensity measurement. If this occurs at the defined transitions to adjacent
light levels, fast changes in the light levels cannot be avoided.
Light intensity
Set_Sensor_Max_
Value
Level 3
Copyright ã Siemens AG 2013 All rights reserved
Set_Value_Lev3
Level 2
Set_Value_Lev2
Level 1
Set_Value_Lev1
00:00 06:00 08:00 18:00 20:00 23:59
In order to avoid light flickering at least for minor variations, a hysteresis is used.
This hysteresis represents sort of an “environment” around the setpoint value
within the range of which the actual value may vary. The control system will react
only, if the actual value exceeds the maximum value or falls below the minimum
value of this range.
In this application, the hysteresis is controlled with the help of a timer. If the value
measured by the sensor exceeds a defined limit to the next light level, a timer will
be started (time value: 1 minute). If the sensor value levels out to the previous
range within this period, the timing element will be reset.
If the sensor value remains within the new range even after the period has
elapsed, the relevant light level will be activated.
This reduction of light flickering is effective only in automatic mode.
The figure and table below show the call interface of the user function block
“Tunnel_Lighting_System” (FB 100).
Figure4-3
Copyright ã Siemens AG 2013 All rights reserved
Input parameters
The input parameters have the following meanings:
Table 4-8
Parameter Data type Note
LIGHT_SENSOR_OUTSIDE INT Analog value measured in Cd (lm/ser)
AUTO_MODE_ON BOOL Automatic mode
MANUAL_MODE_ON BOOL Manual mode
ACTUAL_SYS_DATE_TIME DATE_ Current system date and time
AND_TIME
Entry_EXIT_LIGHTLEV_1_MAN BOOL Entrance and exit light at level 1 in
manual mode
Entry_EXIT_LIGHTLEV_2_MAN BOOL Entrance and exit light at level 2 in
manual mode
Entry_EXIT_LIGHTLEV_3_MAN BOOL Entrance and exit light at level 3 in
manual mode
SET_ELAPSED_T_COUNTER_PV BOOL Reset of elapsed-time counter to 0
Set_VAL_Level_1 REAL Sensor limit value for level 1 in Cd
(lm/ser)
Set_VAL_Level_2 REAL Sensor limit value for level 2 in Cd
(lm/ser)
Output parameters
The output parameters have the following meanings:
Table 4-9
Name of the variable Data type Note
ENTRY_LIGHT_1 BOOL Entrance light, level 1
ENTRY_LIGHT_2 BOOL Entrance light, level 2
ENTRY_LIGHT_3 BOOL Entrance light, level 3
EXIT_LIGHT_1 BOOL Exit light, level 1
EXIT_LIGHT_2 BOOL Exit light, level 2
EXIT_LIGHT_3 BOOL Exit light, level 3
TUNNEL_INSIDE_DAYLIGHT BOOL Interior light for the period
08:00-18:00
Copyright ã Siemens AG 2013 All rights reserved
Description of variables
The figure and table below show the variables of data block “SYS_DATA_HMI”
(DB 101).
Figure 4-4
Copyright ã Siemens AG 2013 All rights reserved
08:00-18:00
EXIT_ENTRY_DAYLIGHT_ BOOL Daylight for entrance and exit zone
ON
EXIT_ENTRY_NIGHTLIGHT BOOL Nightlight for entrance and exit zone
_ON
PLC_Rack_0_RUN_P BOOL CPU rack 0 in redundant mode
PLC_Rack_1_RUN_P BOOL CPU rack 1 in redundant mode
PLC_Rack_0_RUN_S BOOL CPU rack 0 in solo mode
PLC_Rack_1_RUN_S BOOL CPU rack 1 in solo mode
PLC_Rack_0_Stop BOOL CPU rack 0 in STOP mode
PLC_Rack_1_Stop BOOL CPU rack 1 in STOP mode
SYNC_Link_UP_01 BOOL Status of synchronization link-up 01:
Synchronization between CPU 0 and
CPU 1
=0: not possible
=1: possible
Fiber_Optic_Con_0 BOOL =0: no fault
=1: Fiber optics connection quality of
the synchronization modules in the
upper receptacle is limited
Fiber_Optic_Con_1 BOOL =0: no fault
=1: Fiber optics connection quality of
the synchronization modules in the
lower receptacle is limited
T_Inside_Night_Light BOOL Interior light for the period 20:00-06:00
T_Inside_SunUP_Dw_ON BOOL Interior light for the periods
06:00-08:00 and 18:00-20:00
EXIT_ENTRY_SunUP_Dw_ BOOL Evening and morning twilight for the
ON entrance and exit zone
5 Configuration
5.1 Address overview
The following figure illustrates the structure of the S7 project for the tunnel lighting
control system.
Figure 5-1
S7-400H S7-400H
„T_Control_Room1_PLC1“ „T_Control_Room2_PLC2“
ET 200M ET 200M
IP addresses
The modules are addressed as follows:
Table 5-1
Hardware Address Subnet mask
H-CPU_1 192.168.0.130 255.255.255.0
“T_Control_Room_1_PLC1”
H-CPU_2 192.168.0.131 255.255.255.0
“T_Control_Room_1_PLC2”
HMI Multipanel 192.168.0.3 255.255.255.0
“Control_Room_HMI_1”
HMI Multipanel 192.168.0.4 255.255.255.0
“Control_Room_HMI_2”
Connection ID
Communication between the modules is realized by means of S7 connections. The
following table provides an overview:
Table 5-2
H-CPU_1 Control Center/T_Control_Room_1_PLC1
Local ID Partner ID Partner Type Active connection buildup
1 S7-connection_1 Control_Room_1_HMI S7 connection no
2 S7-connection_3 Control_Room_2_HMI S7 connection no
H-CPU_2 Control Center/T_Control_Room_2_PLC2
Local ID Partner ID Partner Type Active connection buildup
3 S7-connection_2 Control_Room_1_HMI S7 connection no
4 S7-connection_4 Control_Room_2_HMI S7 connection no
Table5-3
Control_Room_1_HMI
Local ID Partner ID Partner Type Active connection buildup
Copyright ã Siemens AG 2013 All rights reserved
Table 5-4
No. Action Notes
1. Open a STEP 7 project in the SIMATIC
Manager. Select the H-system Tunnel and
open the hardware configuration dialog.
2. In the Properties dialog for the H-CPU you
can define the following properties:
· Definition of monitoring times:
– Max. scan cycle time extension
Copyright ã Siemens AG 2013 All rights reserved
CPU1: IP address:192.168.0.130,
subnet mask:225.225.225.0.
CPU2: IP address:192.168.0.131,
subnet mask:225.225.225.0.
Note The data block number for the redundant I/Os should not be used somewhere
else in the user program. Previous data blocks will be deleted and generated
anew.
Note For further information on H-system configuration, please refer to the following
manual: “SIMATIC Fault-tolerant systems S7-400H”, see \3\.
Table 5-5
No. Action Notes
1. Select the HMI station
“Control_Room_1_HMI” and
open the hardware configuration
dialog.
Select “Properties HMI IE>
General> Interface
Properties>Parameters” to open
a dialog where you can define
the IP address and the network:
Copyright ã Siemens AG 2013 All rights reserved
Control_Room_1_HMI:
IP address:192.168.0.3
Subnet mask:225.225.225.0
Control_Room_2_HMI:
IP address:192.168.0.4
Subnet mask:225.225.225.0
The term ‘redundant I/Os” refers to input/output modules which are available in
twofold and redundantly configured and operated in pairs. The redundancy mode is
defined in the Properties dialog of the signal modules.
Table 5-6
No. Action Notes
1. Open the Properties dialog for
the signal module “SM322 DO16
24 V / 0.5 A” and select the
“Redundancy tab” where you
can define the redundant mode
settings.
Note A current list of modules suitable for redundant operation can be found in the
following system manual:
“Fault-tolerant system S7-400H“, chapter “Signal modules for redundancy”,
see \3\.
To enable communication between the HMI panel and the H-CPUs, the relevant
S7 connections are to be created in NetPro.
Table 5-7
No. Action Notes
2. To add a new connection, first
select CPU 1. Use your right
mouse button or the shortcut
Ctrl+N to add a new connection.
Now select the connection type
"S7 connection” and confirm
your selection with OK.
Configuration of connections
The HMI panels are connected with the two H-CPUs via Industrial Ethernet. To
enable the exchange of variables between these components, the relevant
connections must be specified in WinCC flexible.
· S7-connection_1 or S7-connection_3 is connected to the first H-CPU
(T_Control_Room_1_PLC1) via Industrial Ethernet.
· S7-connection_2 or S7-connection_4 is connected to the second H-CPU
(T_Control_Room_2_PLC2) via Industrial Ethernet.
· Control_Raum_1_PLC_Changer_12 and/or
Control_Raum_2_PLC_Changer_12 has been connected “manually” to an
S7-300/400 unit via Industrial Ethernet and provides an auxiliary connection
for the “WechseleVerbindung” function.
Figure 5-2
Copyright ã Siemens AG 2013 All rights reserved
Note Please make sure to enter the receptacle and slot numbers correctly.
With the help of the internal system function “WechseleVerbindung” and the status
analysis of the H-CPUs, a connection to the active H-CPU will be established,
depending on the operating mode of the CPU.
Creation of variables
For the status analysis of the H-CPUs, one variable for each H-CPU must be
created in WinCC flexible (“Rack_x_PLC_x_Master”) and referenced to the
corresponding status variable in the data block "SYS_DATA_HMI". In concrete
terms, this means:
· “Rack_0_PLC_1_Master” è Tag “RACK_0_MSTR” in DB 101 (DB101.DBB11)
· “Rack_1_PLC_2_Master” è Tag “RACK_1_MSTR” in DB 101 (DB101.DBB12)
These data block variables may show the following values:
· =0: CPU presently used as standby station
· =1: CPU defined as master.
In WinCC flexible, the acquisition type “cyclic continuous” is selected.
Figure 5-3
Configuration of variables
In the Properties dialog for the WinCC tag “Rack_x_PLC_x_Master”, an upper limit
value of “0” is defined in combination with the event parameter “High limit
exceeded” and the function “ChangeConnection”. As “Connection” partner, the
auxiliary connection “Control_Room_x_PLC_Changer_12” is selected.
The addresses, slots and racks correspond to the connection parameters.
Figure 5-4
Function principle
Initial situation: The first CPU (T_Control_Room_1_PLC_1) is the master CPU; the
Copyright ã Siemens AG 2013 All rights reserved
6 Installation
The following chapter describes all steps required to put the sample project into
service on the basis of this application example and the hardware list.
S7-400H S7-400H
SCALANCE SCALANCE
X208 X208
Copyright ã Siemens AG 2013 All rights reserved
ET 200M ET 200M
Proceed as follows for hardware installation and connection in the control rooms:
Table6-1
No. Action Notes
1. Mount the individual modules to a suitable See HW configuration
module rack.
2. Connect the PS307 for ET 200M and the PS 407 Take note of correct polarity.
for the H-CPUs to power (230 V AC).
3. Use the power supply modules to supply the
other modules with 24V DC.
4. Connect the following devices with the The Engineering-PG is used to load the
SCALANCE X208: controller and the HMI panel in the control
· PROFINET interface of the CPU room.
Depending on the controller or HMI panel to
· PROFINET interface of the HMI panels be loaded, the PC will be connected with the
· PROFINET interface of the Engineering PG relevant X208 of the control room.
Note The guidelines for the installation and setup of components are to be observed.
Please refer to the corresponding device manuals.
NOTICE Connect the system to power only after having completed and checked all
installation and setup work!
Software installation
The Engineering station is used as a configuration calculator for the S7 station. The
following software components must be installed.
Table 6-3
No. Action Notes
1.. Install STEP 7 Follow the instructions of the installation
program.
2. Install WinCC Flexible Follow the instructions of the installation
program.
or
Copyright ã Siemens AG 2013 All rights reserved
Note The light intensity value is entered via the variables table VAT_1:
0 – 27648 corresponds to a light intensity of 0 – 100.000 Cd (lm/ser).
Note If the elapsed-time counter exceeds 32767 hours, it will stop and the SFC 4
“READ_RTM” will show the error message “Overflow”.
8 Related literature
Table 8-1
Topic Title / Link
\1\ Siemens Industry http://support.automation.siemens.com
Online Support
\2\ Download page of http://support.automation.siemens.com/WW/view/81066268
this entry
\3\ Fault-tolerant http://support.automation.siemens.com/WW/view/en/60458386
systems
S7-400H
\4\ WinCC flexible WinCC flexible 2008 Communication Part 1
2008 http://support.automation.siemens.com/WW/view/en/18797552
\5\ System and http://support.automation.siemens.com/WW/view/en/44240604
Standard
Functions for S7-
300/400 Volume
1/2.
\6\ How do you http://support.automation.siemens.com/WW/view/en/23842653
connect a panel
to a SIMATIC H
Copyright ã Siemens AG 2013 All rights reserved
station?
/7/ Step 7 Automating with STEP7 in STL and SCL
Author: Hans Berger
Publicis Publishing
ISBN 3895783242
/8/ SPC automation Automatisieren mit SPS – Theorie und Praxis
[Automating with PLC – Theory and Practice]
Authors: Günter Wellenreuther \ Dieter Zastrow
Publicis Publishing
ISBN 9783834802316
9 History
Table 9-1
Version Date Modifications
V1.0 10/2013 First version